This document outlines a federal contract opportunity for renovating a pharmacy at a Veteran Affairs Healthcare System facility in Oklahoma City, Oklahoma. The project involves renovating approximately 12,155 square feet of existing inpatient pharmacy and primary care office space to bring the inpatient pharmacy into compliance with Pharmacy Chapters 797 and 800 standards and to improve efficiency for the growing veteran population. This is a 100% set-aside contract for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification System code is 236220. The estimated value is between $2,000,000 and $4,000,000. Offerors must register in the System for Award Management and complete online representations and certifications. All questions must be submitted in writing to the specified email address. The full solicitation is estimated to be posted on or shortly after March 8, 2021. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PHARMACY RENOVATION
PROJECT LOCATION
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH STREET, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
AMI ENVIRONMENTAL
8802 SOUTH 135TH STREET, SUITE 100
OMAHA, NEBRASKA 68138
PH: (402) 397-5001
/1
/2
:1
:3
P
M
CONSTRUCTION DOCUMENTS
07/10/2020
COVER SHEET
G0.00
RENOVATE PHARMACY FOR
CHAPTER 797-800
KZJS
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
15-2226.013
FDA.01 FIRE ALARM DEMOLITION PLAN - GROUND LEVEL
FA.00 FIRE ALARM RISER DIAGRAM AND DETAILS
FA.01 FIRE ALARM PLAN - GROUND LEVEL
FDX.01 FIRE SUPPRESSION DEMOLITION PLAN - GROUND
LEVEL
FX.00 FIRE SUPPRESSION GENERAL NOTES AND DETAILS
FX.01 FIRE SUPPRESSION PLAN - GROUND LEVEL
E 00 ELECTRICAL INFO SHEET
E001 FLOOR PLAN - DEMOLITION
E101 FLOOR PLAN - LIGHTING
E201 FLOOR PLAN - POWER AND AUXILIARY SYSTEMS
E501 ELECTRICAL DETAILS
P 00 PLUMBING INFO SHEET
P001 GROUND FLOOR DEMOLITION PLAN - PLUMBING
P101 GROUND FLOOR PLAN - PLUMBING
P201 SANITARY RISER DIAGRAM - PLUMBING
P301 DETAILS AND SCHEDULES - PLUMBING
M 00 MECHANICAL INFO SHEET
M 01 GROUND FLOOR PHASING PLAN - MECHANICAL
M001 GROUND FLOOR DEMOLITION PLAN - MECHANICAL
M101 GROUND FLOOR PLAN - MECHANICAL
M201 GROUND FLOOR PIPING PLAN - MECHANICAL PIPING
M401 DETAILS - MECHANICAL
N402 DETAILS - MECHANICAL
M501 SCHEDULE - MECHANICAL
M600 GROUND FLOOR ZONING PLAN - MECHANICAL
AD1.00 DEMO FLOOR AND REFLECTED CEILING PLANS -
GROUND LEVEL
A1.00 NEW FLOOR AND REFLECTED CEILING PLANS -
GROUND LEVEL
A1.01 REFLECTED CEILING PLAN AND DETAILS
A1.10 EQUIPMENT PLAN AND SCHEDULE
A1.20 ROOF PLAN
A5.00 ROOM FINISH SCHEDULE
A5.01 ENLARGED PLANS, INTERIOR ELEVATIONS AND PLAN
DETAILS
A5.02 ENLARGED PLANS AND INTERIOR ELEVATIONS
A6.00 DOOR SCHEDULE AND WINDOW ELEVATIONS
S-001 STRUCTURAL GENERAL NOTES
S-101 FLOOR FRAMING PLAN - GROUND LEVEL AND
SUPPORTING DETAILS
HA100 GENERAL NOTES
HA-101 HAZARDOUS MATERIALS ASSESSMENT
HA-102 HAZARDOUS MATERIALS ASSESSMENT
G0.00 COVER SHEET
G0.01 ABBREVIATION, SYMBOLS, LEGENDS AND GENERAL
NOTES
G0.02 CONTRACTOR STAGING PLAN
G1.01 LIFE SAFETY PLAN - GROUND LEVEL
G1.02 PHASING/ INFECTION CONTROL PLAN
ARCHITECT
STRUCTURAL ENGINEER
FOURFRONT DESIGN INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
SHEET INDEX
GENERAL PLUMBING
MECHANICAL
ELECTRICAL
STRUCTURAL
ALBERTSON ENGINEERING INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
MECHANICAL ENGINEER,
ELECTRICAL ENGINEER
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
FIRE PROTECTION ENGINEER
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
OKLAHOMA CITY
VA MEDICAL CENTER
RENOVATE PHARMACY
FOR CHAPTER 797-800
921 NORTHEAST 13TH STREET
OKLAHOMA CITY, OKLAHOMA 73104
PROJECT #: 635-18-102
FIRE PROTECTION
LOCATION MAP
N
HAZARDOUS MATERIALS SURVEYOR
AMI ENVIRONMENTAL
8802 SOUTH 135TH STREET, SUITE 100
OMAHA, NEBRASKA 68138
PH: (402) 397-5001
HAZARDOUS MATERIALS SURVEY
ARCHITECTURAL
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY
THE OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS
AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES
OR VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT
NO ADDITIONAL EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE
SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF
WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS
DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND
BE RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR
ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO
OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH
ALL OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION
TO REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED
CONSTRUCTION.
E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL
DUCTWORK WITH STRUCTURE, CEILING, LIGHTING, AND PIPING.
F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL
EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.
G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL
PANELS. MAINTAIN ALL CODE REQUIRED CLEARANCES.
H. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT
BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT
THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE
WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND
CONTRACTOR.
I. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING
CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND
GENERAL CONTRACTOR.
J. ALL HYDRONIC PIPING RUNOUTS SHALL BE A MINIMUM OF 3/4" PIPE
SIZE. IF SIZE IS NOT LABELED, THEN ASSUME MINIMUM PIPE SIZE.
K. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INTLET SIZE
UNLESS OTHERWISE NOTED.
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL
DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.
DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED
TO BE REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-
TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND
ARE SHOWN AS HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED
BELOW OR HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL
REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING
BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION REQUIRED
AND AS LISTED BELOW.
C. THE REMOVAL OF HVAC AND PLUMBING EQUIPMENT FROM FINISHED AREAS
AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH
ARCHITECTURAL PLANS AND DETAILS AS WELL AS NOTES ON THE
MECHANICAL DRAWING TO ENSURE PROPER PATCHING AND REPAIR IS
MADE TO THE BUILDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND
REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND
APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR
ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST
RIGHT OF REFUSAL ON ALL ITEMS.
E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE
CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND
STORED OR REINSTALLED ON THE SITE AS DIRECTED. REMOVED OR
SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE OWNER.
F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND
CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL
REMOVALS.
G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL
REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY
OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED
HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE
AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND
ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT
THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE
OWNER AND ARCHITECT.
H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION
SHALL BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:2
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
MECHANICAL INFO SHEET
M 00
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442015-2226.013
07607001- 5- M 00
M 00 MECHANICAL INFO SHEET
M 01 GROUND FLOOR PHASING PLAN - MECHANICAL
M001 GROUND FLOOR DEMOLITION PLAN - MECHANICAL
M101 GROUND FLOOR PLAN - MECHANICAL
M201 GROUND FLOOR PIPING PLAN - MECHANICAL PIPING
M401 DETAILS - MECHANICAL
M402 DETAILS - MECHANICAL
M501 SCHEDULE - MECHANICAL
M600 GROUND FLOOR ZONING PLAN - MECHANICAL
TRUE
NORTH
PLAN
NORTH
NORTH
NORTH
ARROW
SYMBOL LEGEND
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM / SPACE
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION
OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
RECIRCULATING DOMESTIC
HOT WATER (RDHW)
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
PIPE GUIDE
HOSE BIBB
THERMOMETER
PIPE ANCHOR
HB
STEAM TRAP
PH
WH
YH
SIGHT GLASS-REFRIGERANT
POST HYDRANT
YARD HYDRANT
WALL HYDRANT
PRESSURE GAUGE
CA
PN
CONTROL AIR SUPPLY
NEW TO EXISTING CONNECTION
PNEUMATIC TUBE
FIRE WATER (BURIED)
SPRINKLER DRAIN
FIRE SPRINKLER MAIN
TAMPER SWITCH
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
MISCELLANEOUS SYMBOLS
FLOOR SINK
AREA DRAIN
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
RUNNING TRAP
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
RUNNING TRAP WITH CLEANOUTS
ROOF DRAIN
UNION
TEE DOWN
STRAINER
DIELECTRIC UNION
THERMOMETER WELL
CONCENTRIC REDUCER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
ECCENTRIC REDUCER
AIR VENT (MANUAL UNLESS
NOTED)
PITCH PIPE DOWN IN DIR OF
ARROW
TEE UP
SM
FW
D
TS
FS
LPC
HPS
MPC
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPC
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE CONDENSATE
HIGH PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
MEDIUM PRESSURE STEAM
LOW PRESSURE CONDENSATE
LOW PRESSURE STEAM
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
_"FS-_
_"AD-_
_"FD-_
CO
VTR
GCO
_"OD-_
MH
X
A
V
_"RD-_
RD
SAN
SAN
PLUMBING PIPING
ACID VENT
TW
AV
AW
W
DS
LS
SCW
RTW
SHW
V SANITARY VENT
BURIED EXTERIOR WATER
RECIRCULATING TEMPERED
WATER
TEMPERED WATER
DISTILLED WATER
LAWN SPRINKLER
SOFTENED HOT WATER
SOFTENED COLD WATER
ACID WASTE
SUBSOIL OR FOUNDATION DRAIN
STORM DRAIN (BELOW FLOOR)
STORM DRAIN (ABOVE FLOOR)
SANITARY DRAIN (BELOW FLOOR)
SANITARY DRAIN (ABOVE FLOOR)
OXYGEN
GASOLINE
VACUUM
OX
GS
G
VAC
RO
A
FOF
FOG
LPG
FOV
FOR
FOS
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAGE
FUEL OIL FILL
FUEL OIL VENT
REVERSE OSMOSIS PROCESSED
WATER
COMPRESSED AIR
NATURAL GAS
LIQUEFIED PETROLEUM GAS
DEIONIZED WATERDI
PIPING SPECIALTIES AND FITTINGS
WCO
FIRE PROTECTION
XXX
PLUMBING
FIXTURES PLUMBING FIXTURE
DESIGNATION
X"PIPE
SIZE
PIPE SIZE (DIAMETER)
X"/X"
DUCT
SIZE
WIDTH / HEIGHT
REF. DEMO NOTES ( ) XX
CWS
GCWS
CWR
GCS
CR
CS
RL
RD
RS
GCWR
GLYCOL CONDENSER WATER
SUPPLY
GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION LINE
GHCS
GHCR
CD
HCS
HCR
GCR
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
GLYCOL CONDENSER WATER
RETURN
GLYCOL HOT/CHILLED WATER
RETURN
GLYCOL HOT/CHILLED WATER
SUPPLY
CONDENSATE DRAIN
REF. NOTES ( )ABBREVIATIONS
ROOM NAME
150 SF
ROOM NAME
DESIGNATION
ROOM NUMBER
DESIGNATION
ROOM AREA
DESIGNATION
TSTAT THERMOSTAT
TWU TROUGH WALL AIR CONDITIONER
UH UNIT HEATER
UR URINAL
US UTILITY SINK
V VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSETS
WCO WALL CLEANOUT
WF WASH FOUNTAINS
WFU WATER FIXTURE UNITS
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WS WATER SOFTENER
WSHP WATER SOURCE HEAT PUMP
WWHP WATER TO WATER HEAT PUMP
YH YARD HYDRANT
GPH GALLONS PER HOUR
GRV GRAVITY RELIEF VENTILATOR
GPM GALLONS PER MINUTE
GV GAS VENT
GWH GAS WATER HEATER
H HYDRANTS
HB HOSE BIBB
HC HEATING COIL
HCR HOT/COLD WATER RETURN
HCS HOT/COLD WATER SUPPLY
HG GAS: HIGH-PRESSURE
HP HEAT PUMP (AIR SOURCE)
HP HORSEPOWER
HPC HIGH PRESSURE CONDENSTATE
HPS HIGH PRESURE STEAM
HRC HEAT RECOVERY COIL
HU HUMIDIFIER
HWR HOT WATER RETURN (HEATING)
HWS HOT WATER SUPPLY (HEATING)
HX HEAT EXCHANGER
IH INTAKE HOOD
IRH INFRARED RADIANT HEATER
KDH KITCHEN DISHWASHING HOOD
KH KITCHEN HOOD
KW KILOWATT
KWH KILOWATT HOURS
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LH LAB HOOD
LPC LOW PRESSURE CONDENSATE
LPG LIQUIFIED PETROLEUM GAS
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LS LAUNDRY SINK
LSS LAWN SPRINKLER DESIGN
LV LOUVER
LWT LEAVING WATER TEMPERATURE
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MB MACHINE BOLT
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MG GAS: MEDIUM-PRESSURE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPC MEDIUM PRESSURE
CONDENSATE
MPS MEDIUM PRESSURE STEAM
MS MOP SINK
N NITROGEN
NC NORMALLY CLOSED
NG NATURAL GAS
NO NORMALLY OPEN
NPCW NONPOTABLE COLD WATER
NPHW NONPOTABLE HOT WATER
NPHWR NONPOTABLE HOT WATER
RETURN
OA OUTSIDE AIR
OD OVERFLOW ROOF DRAIN
OX OXYGEN
P PUMP
PC POINT OF CURVATURE
PHC PREHEAT COIL
PIV POST INDICATING VALVE
PRV PRESSURE REGULATING VALVE
PS PLASTER SINKS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH,
ABSOLUTE
PSIG POUNDS PER SQUARE INCH,
GAUGE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RA RETURN AIR
RCP RADIANT CEILING PANELS
RD ROOF AREA DRAINS
RDL REFRIGERANT DISCHARGE LINE
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RELIEF AIR
RLF RELIEF FAN
RO REVERSE OSMOSIS WATER
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION LINE
RTU ROOF TOP UNIT
RV RELIEF VALVE
S SINKS
SA SUPPLY AIR
SAN SANITARY SEWER
SB SITZ BATH
SD SMOKE DAMPER
SF SUPPLY FAN
SFU SANITARY FIXTURE UNITS
SH SHOWERS
SHB SHAMPOO BOWLS
SP STATIC PRESSURE
SS SERVICE SINK
SSCU DUSTLESS SPLIT SYSTEM
CONDENSING UNIT
SSFC DUCTLESS SPLIT SYSTEM
SSS SURGEON SCRUB SINKS
ST STORAGE TANK
SUP SUMP PUMP
SW STORM WATER
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVES
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
APD AIR PRESSURE DROP
A COMPRESSED AIR
AFCV AUTO FLOW CONTROL VALVE
AC AIR COMPRESSOR
AD AIR DOOR
AW ACID WASTE
AV ACID VENT
AS AIR SEPARATOR
AW AREA DRAIN
ARD AIR PRESSURE DROP
AMP AMPERE
AHU AIR HANDLING UNIT
BW BEDPAN WASHERS
BV BALL VALVE
BT BATHTUBS
BLV BALANCING VALVE
BLKG BLOCKING
BHP BREAK HORSEPOWER
BFV BUTTERFLY VALVE
BF BACKFLOW PREVENTER
BD BIDET
BC BLOWER COIL
B BOILER
CWS CHILLED WATER SUPPLY
CWR CHILLED WATER RETURN
CU AIR COOLED CONDENSING UNIT
CT COOLING TOWER
CSS CLINICAL SERVICE SINKS
CS CONDENSER WATER SUPPLY
CRAC COMPUTER ROOM AIR
CONDITIONER
CR CONDENSER WATER RETURN
CMU COMBINATION UNITS
CI CAST IRON
CHV CHECK VALVE
CHIU CABINET HEATER
CFM CUBIC FEET PER MINUTE
CF CEILING FANS
CD CONDENSATE DRAIN
CC COOLING COIL
C CHILLER
D DIFFUSER
DB DRY-BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DEG DEGREE
DF DRINKING FOUNTAIN
DGCO DOUBLE GRADE CLEANOUT
DH EMERGENCY DRENCH HOSES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RECIRC
DI DEIONIZED WATER
DOA DEDICATED OUTDOOR AIR UNIT
DP DOMESTIC PUMP
DS DISTILLED WATER
DSA DUCT SOUND ATTENUATORS
DSCW DOMESTIC SOF COLD WATER
DSHW DOMESTIC SOFT HOT WATER
DSHWR DOMESTIC SOFT HOT WATER
RETURN
DST DOMESTIC STORAGE TANK
DTW DOMESTIC TEMPERED WATER
DTWR DOMESTIC TEMPERED WATER
RETURN
DXT DOMESTIC EXPANSION TANK
EA EACH
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE
WASH/SHOWERS
EF EXHAUST FAN
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EH EXHAUST HOOD
ERV ENERGY RECOVERY
VENTILATOR
ES EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER
TEMPERATURE
EX EXPANSION TANK
F FIRE PROTECTION WATER
SUPPLY
F FURNACE
FCO FOOT CANDLE
FCT FLUID COOLER TOWERS
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FLOOR SINKS
FSD FIRE/SMOKE DAMPER
FTR FINNED TUBE RADIATION
G GAS: LOW-PRESSURE
GCR GLYCOL CONDENSER WATER
RETURN
GCS GLYCOL CONDENSER WATER
SUPPLY
GCWR GLYCOL CHILLED WATER
RETURN
GCWS GLYCOL CHILLED WATER
SUPPLY
GD GARBAGE DISPOSAL
GD GRAVITY DAMPER
GDH GAS DUCT HEATER
GHCR GLYCOL HOT/COLD WATER
RETURN
GHCS GLYCOL HOT/COLD WATER
SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GI GREASE INTERCEPTOR
GIV GRAVITY INTAKE VENTILATOR
GPD GALLONS PER DAY
18 Ø
18x10
18/10
ROUND DUCT
VD
FLAT OVAL DUCT-1ST FIG IS
SIDE SHOWN
FLEXIBLE DUCTWORK CONNECTION
RECT DUCT-1ST FIG IS SIDE SHOWN
ACOUSTICAL DUCT LINER
VOLUME DAMPER
MANUAL BALANCING VALVE
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES
EXTRACTOR
SIZE/TYPE
RETURN OR EXHAUST DUCT DOWN
RETURN OR EXHAUST REGISTER
OR GRILLE (VERTICAL MOUNTING)
SUPPLY REGISTER OR GRILLE
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE
LINE PIPE
RETURN OR EXHAUST DUCT UP
(R OR G) (VERTICAL MOUNTING)
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
FLOW
SMOKE DAMPER - FIRE SEPARATION
FIRE DAMPER - FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND CEILING SUPPLY DIFFUSER
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
THERMOSTATIC MIXING VALVE
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
S
H
T
TEMPERATURE SENSOR
FIRE/SMOKE DAMPER - FIRE
SEPARATION
RECTANGULAR RETURN REG OR
GRILLE (HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY DIFF, REG
OR GRILLE (HORIZONTAL
MOUNTING)
VALVES
M
M SIZE/TYPE
FLOW
RECTANGULAR EXHAUST REG OR
GRILLE (HORIZONTAL MOUNTING)
M
VOLUME DAMPER
M
F
S
FS
DEMOLITION GENERAL NOTES GENERAL NOTES
MECHANICAL SHEET LIST
SEE INDIVIDUAL SHEET FOR REFERENCE DEMO NOTES SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES
9/16/20
14 Ø OA
20x10 RA x O
A
1 HP-1
HP-21
14x12 SA
12x10 SA
SF-1
14x14 EGGCRATE
RETURN GRILLE
12x10 SA
14x12 RA
PHASE 1
PHASE 2
PHASING LEGEND
NOTE:
CONTRATOR SHALL PROVIDE ALL NECESARY FIRE DAMPERS AT LIMITS
OF CONSTRUCTION AS NEEDED TO MAINTAIN FIRE SEPARATION.
CERTIFICATION OF USP SPACES WILL HAPPEN AS FOLLOWS AT
CONTRACTORS EXPENSE:
1. AFTER TEMPORARY HEAT PUMPS ARE INSTALLED.
2. AT END OF PHASE I FOR NEW SPACES.
3. AT ENDO OF PHASE II SPACES IN PHASE I WILL BE RECERTIFIED.
MARK CFM ESP HP MANUFACTURER
HP-1 800 0.7 - TRANE GEHV 2.0T
HP-1 1050 0.7 - TRANE GEHV 2.5T
SF-1 800 1.25 .75 HP -
COORDINATE WITH ELECTRICAL CONTRACTOR FOR TEMPORARY
POWER SOURCE FOR HEAT PUMPS AND SUPPLY FAN.
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:2
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
GROUND FLOOR PHASING PLAN -
MECHANICAL
M 01
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442115-2226.013
07607001- 5- M 01
SCALE: 1/8" = 1'-0"
GROUND FLOOR PLAN - MECHANICAL
REF. NOTES ( ):X
1 INSTALL HEAT PUMP IN EXISTING CLEANROOM SPACE THAT WILL NOT BE
USED DURING PHASE I OF CONSTRUCTION. CONTRACTOR SHALL INSTALL
HEATPUMP OVER A SINGLE WEEKEND COORDINATED WITH THE OWNER
FOR DOWNTIME OF SUITE. ONCE HEATPUMP IS INSTALLED AND
OPERATING WHILE CONNECTED TO THE CHILLED WATER THE
CONTRACTOR SHALL HAVE THE IV CLEANROOM SUITE NEXT DOOR
RECERTIFIED FOR OPERATION. SEE PHASING NOTES FOR DETAILS OF
HEAT PUMP SIZE AND CONNECTION.
2 CONNECT NEW DUCT TO EXISTING JUST DOWNSTREAM OF VAV BOX. CAP
DUCT BEHIND VAV BOX AIR TIGHT AND INSULATE.
3 EXTEND RETURN DUCT TO CORRIDOR AND INSTALL TEMPORARY RETURN
AIR GRILLE AS SHOWN.
4 CONNECT HEAT PUMP RETURN TO RETURN DUCT LOCATED IN CEILING AT
THIS LOCATION. CAP RETURN GRILLE ON SOUTH SIDE OF IV SUITE AND IN
REFRIGERATOR ROOM TO HAVE HEAT PUMP ONLY RETURN AIR FROM THE
IV SUITE.
PHASE I
1. INSTALL TEMPORARY WATER SOURCE HEAT PUMP IN CLEANROOM SPACE.
HEAT PUMP SHALL BE TRANE GEHV 2 T UNIT OR SIMILAR. CONNECT HEAT
PUMP TO CHILLED WATER PIPING WITH TEMPORARY HOSES. PIPING SHALL
BE A MINIMUM OF 1" FOR A FLOW OF 6.5 GPM. PROVIDE CIRCUIT SETTER AND
CONTROL VALVE FOR HEAT PUMP TO BE CONTROLLED BY A REMOTE
TEMPERATURE SENSOR IN THE ADJACENT CLEAN ROOM. CONDENSATE
SHALL BE PUMPED TO A SINK IN THE ADJACENT ANTE ROOM. CONNECT
DUCTWORK TO EXISTING DUCT FOR AS SHOWN. INSULATE TEMPORARY
DUCTWORK AS REQUIRED. CONNECT RETURN DUCT AS SHOWN.
2. SPACES ON THE WEST SIDE WILL NEED TO BE CERTIFIED PRIOR TO THE
START OF PHASE II. ALL TESTING AND BALANCING WORK TO PROVIDE
CERTIFICATION MUST BE DONE IN A TIMELY MANNER AT THE END OF PHASE I.
3. INSTALL TEMPORARY WATER SOURCE HEAT PUMP IN CLEANROOM SPACE.
HEAT PUMP SHALL BE TRANE GEHV 2.5 T UNIT OR SIMILAR. PIPING SHALL BE A
MINIMUM1" FOR A FLOW OF 7.5 GPM. PROVIDE CIRCUIT SETTER AND
CONTROL VALVE FOR HEAT PUMP TO BE CONTROLLED BY A REMOTE
TEMPERATURE SENSOR LOCATED OUTSIDE THE REFRIGERATOR ROOM.
CONDENSATE SHALL BE PUMPED TO A SINK IN ANTE ROOM. CONNECT
SUPPLY AND RETURN DUCT AS SHOWN.
PHASE II
1. NEW SYSTEM SHALL SERVE ALL OF PHASE I WHILE PHASE II WORK IS
COMPLETED. TAPS TO DUCT OR PIPING SYSTEM SHALL BE DONE WITH A
MINIMUM OF 7 DAYS ADVANCE NOTICE AND MAY BE PERFORMED ON NIGHTS
OR WEEKENDS.
2. ONCE ALL WORK IS COMPLETE FINAL BALANCING AND CERTIFICATION MUST
BE COMPLETED FOR ALL AFFECTED AND NEW SYSTEMS.
FAN COIL TO REMAIN
UNTIL START OF PHASE II.
T
T
T
TT
TH
H
H
H
T T T
T
T
T
C O
N C
R
A M
P C
O N
C R
A M
P
5 (TYP.)
6 6
5 (TYP.)
CHWS
CHWR
LPS
CPD
3/4" HWS
3/4" HWR
3/4" CWS
3/4" CWR
3/4" CD
3/4" CWS
3/4" CWR
3/4" CD
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
/4
H
W S
/4
H
W R
/4
C
D
/4
C
W R
/4
C
W S
3/4" CWR
3/4" CD
3/4" CWS
1" HWS
1 1/4" HWR
H W
S
/4
H W
R
3/4" CWS
3/4" CWR
1 1/4" HWR
1 1/4" HWS
8 (TYP.)
L P
R
L P
S
L P
S
M
P S
/2
C D
/2
L P
R
/2
L P
S
L P
S
M
P S 1
/4
C D
C W
R C
W S
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:0
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
GROUND FLOOR DEMOLITION PLAN -
MECHANICAL
M001
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442215-2226.013
07607001- 5- M001
REF. DEMO NOTES ( ):X
1 REMOVE EXISTING PIPING, INCLUDING INSULATION, ACCESSORIES AND
ALL ASSOCIATES SUPPORTS.
2 REMOVE THE EXISTING AIR HANDLER. REMOVE DUCTWORK, PIPING AND
CONTROLS FROM UNIT AND COORDINATE REPAIR OF THE ROOF WITH THE
GENERAL CONTRACTOR.
3 REMOVE EXISTING DUCTWORK AS SHOWN, INCLUDING ALL
ACCESSORIES, INSULATION AND HANGERS.
4 REMOVE EXISTING FAN COIL UNIT, INCLUDING SUPPORTS AND
CONTROLS.
5 REMOVE EXISTING AIR TERMINAL AS SHOWN.
6 REMOVE EXISTING VAV BOX INCLUDING ASSOCIATED CONTROLS AND
SUPPORTS.
7 COORDINATE DEMOLITION OF PIPING MAINS WITH OWNER FOR REQUIRED
SHUTDOWN. INSTALL ISOLATION VALVES IN REMAINING PIPE FOR
ISOLATION AND RECONNECTION AS REQUIRED. CAP PIPING AND REPAIR
INSULATION.
8 REMOVE EXISTING PIPING AS SHOWN, CAP PIPING AND REPAIR
INSULATION.
9 CONTRACTOR SHALL REMOVE PIPING AND DUCTWORK IN THIS AREA TO
MAKE WAY FOR INSTALLATION OF STRUCTURAL STEEL. REINSTALL
DUCTWORK AND PIPING AFTER WORK IS COMPLETE.
10 SUPPLY AND RETURN DUCTWORK DOWNSTREAM FROM THIS POINT
SHOULD REMAIN FOR EXTENT OF PHASE ONE. SEE PHASING PLAN M01
FOR DETAILS OF TIE IN LOCATIONS OF DUCTWORK REQUIRED FOR PHASE
I TO KEEP THE IV SUITE ACTIVE. DUCTWORK REMAINING IN PHASE I WILL
BE REMOVED AT THE START OF PHASE II INCLUDING TEMPORARY
EQUIPMENT AND PIPING.
11 CHILLED WATER PIPING TO REMAIN AND STAY ACTIVE FOR EXTENT OF
PHASE I TO CONNECT TO TEMPORARY HEAT PUMPS. SEE PHASING PLAN
ON M01 FOR EXTENT OF WORK REQUIRED. ALL PIPING INCLUDING
TEMPORARY WORK WILL BE REMOVED AT THE START OF PHASE II.
SCALE: 1/8" = 1'-0"
GROUND FLOOR DEMOLITION PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
GROUND FLOOR DEMOLITION PLAN - MECHANICAL PIPING
SCALE: 1/8" = 1'-0"
BASEMENT FLOOR DEMOLITION PLAN - MECHANICAL
N
N
N
S
SS
S S
S S
S S
S
S
S
S
S
S
S S
S
SS
S
SS
S
S S
S
S
S S
S
S
SS
S
S
S S
S S
S
S
SS
S
S
SSS
S S
S S
S
S S
S
S
S
S
S
SS
T
T TT
T
T
T
T
T
T
T
T
T
T
T
T
PS PS PSPSPS
F F
(ON ROOF)
STERILE
STORAGE
GA153
ANTE
GA154a
HAC
GA151b
S T
E R
IL
E
N O
N -H
A Z
A R
D O
U S
G A
WORK AREA
G154c
EXIST. STAIR
E S1
PROCUREMENT/STORAGE
GA151
HAC
GA149c
ANTE ALCOVE
GA149b
ANTE
GA149a
STERILE -
HAZARDOUS
GA149
WORK AREA
G149d
HAZARDOUS
STORAGE
GA148
IV STORAGE
GA143a
LOCKER /
BREAK ROOM
GA142
OFFICE
GA143e
CORRIDOR
CGA8
CONF /
TRAINING
GA143b
14 Ø OA
20x10 RA x O
A
OPEN OFFICE 2
GA143d
OPEN OFFICE 3
GA143
OPEN OFFICE 1
GA150
CHECKING
STATION
GA154d
OFFICE
GA143f
VAV-GA154
VAV-GA149 24x48 S-1
24x48 S-1
(TYP.4)
(TYP.6)
16x16 EA
22x20 SA
22x12 SA x S
A
24x48 S-1
(TYP.2)
14 Ø S-3
(TYP.2)
6 Ø S-3
(TYP.2)
6 Ø S-3
12x12 E-2
6 Ø S-3 x S
A x S
A
V A
V -G
A
12x8 SA
8x8 SA
(TYP.3)
8 Ø S-3
(TYP.2)
x S
A
VAV-GA142
EXV-GA142
6 Ø S-3
6 Ø S-3
10x10 E-1
EXV-GA143B
8 Ø S-3
230 (TYP.2)
V A
V -G
A A
8 Ø S-3
6 Ø S-3
V A
V -G
A B
6 Ø S-3
(TYP.2)
6 Ø S-3
VAV-GA148
14x12 SA
(TYP.2)
16x16 E-1 x E
A
16x20 EA
12x8 E-1
235 16x16 E-1
12 Ø EA12 Ø EA
24x14 SA
12x8 E-1
10x12 SA
VAV-GA153
VAV-GA151
6x8 SA
VAV-GA150
EXV-GA149A
EXV-GA149.1
EXV-GA149.2
EXV-GA149.3
EXV-GA149.4
24x48 S-1
(TYP.2)
VAV-GA154A
10x10 EA
12x10 EA
10x10 SA VAV-GA143F VAV-GA143E
20x16 EA
6x6 E-1
6x6 E-1
E X
V -G
A E
E X
V -G
A
FEXV-GA143A
14x14 E-2
EXV-GA148.1
16x16 E-1
16x16 E-1
8x14 SA x E
-1
18x10 E-1
EXV-GA154A
EXV-GA154
14x14 E-2
E X
V -G
A x E
A
EXV-GA153
14x14 E-2
26 DIA. EA UP TO
EF-1 (ON ROOF)
P R
O C
U R
E M
E N
T /S
T O
R A
G E
G A
FUME HOOD @
765 CFM (TYP.3)
VAV-GA143D3
x S
A x S
A x E
A
24x48 S-1
VAV-GA149A
VAV-GA154C
x S
A
9 (TYP. OF 3)
10 (TYP.)
11(TYP.)
6x6 E-1
6x6 E-1
M101
8x16 SA
8x20 SA
(TYP.)
(TYP.)
12 (TYP.)
(TYP.)
(TYP.)
12 Ø EA
EXV-GA148.2
16x10 EA DN
8x12 SA
14x8 EA
AHU-1
16 Ø EA
14 Ø EA
8 Ø EA
12 Ø EA
8 Ø EA
8 Ø EA
x E
A
16x16 EA
16x16 EA
9 Ø EA
16x10 EA
12x10 SA
6 Ø EA
6 Ø EA
10 Ø EA
9 Ø SA
6 Ø SA 12x12 SA
20x16 EA x E
A
16x16 EA 20x16 EA
10x10 EA
6 Ø S-3
(TYP.2)
EF-1
26 Ø EA
M101
20x30 SA AHU-1
2 1/2" CWS
2 1/2" CWR
3" CWR
3" CWS
2" LPS
1" LPR
1" FROM H-1
ROOF PLAN
115' - 1 1/2"
EF-1
26 Ø EA
EXHAUST FAN
BYPASS PLENUM
CURB
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:1
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
GROUND FLOOR PLAN - MECHANICAL
M101
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442315-2226.013
07607001- 5- M101
REF. NOTES ( ):X
1 THIS SPACE IS RESERVED FOR ELECTRICAL EQUIPMENT. NO PIPING OR
DUCTWORK SHALL PASS BELOW, ABOVE, OR AROUND ELECTRICAL
EQUIPMENT. PROVIDE CODE REQUIRED MINIMUM CLEARANCE ABOVE
ELECTRICAL EQUIPMENT ACCESS SPACE.
2 INSTALL ENVIRONMENTAL MONITOR AT THIS LOCATION. ENVIRONMENTAL
MONITORS SHALL MEASURE PRESSURE, TEMPERATURE, HUMIDITY AND
AIR CHANGES AT CRITICAL SPACES AS DETAILED ON AIRFLOW AND
PRESSURIZATION DIAGRAM. ENVIRONMENTAL MONITORS SHALL BE
SETRA FLEX OR EQUAL AND SHALL BE CLEARLY LABELED FOR THE SPACE
THEY SERVE.
3 INSTALL NEW OUTDOOR AIR HANDLER AS SHOWN IN PLACE OF EXISTING
AIR HANDLER. UNIT TO BE INSTALLED ON EXISTING STRUCTURE,
PROVIDE ADDITIONAL STEEL AS NEEDED FOR SUPPORT OF UNIT. UNIT
INSTALLATION MUST BE COORDINATED WITH TEMPORARY WORKSPACE
AND MUST BE DONE TO MEET THE SCHEDULE REQUIREMENTS FOR THE
PROJECT.
4 COORDINATE NEW DUCTWORK PENETRATIONS OF EXISTING WALL WITH
THE GENERAL CONTRACTOR. SEE STRUCTURAL PLANS FOR REQUIRED
LINTELS TO BE INSTALLED. SEAL PENETRATION AROUND DUCT PER
ARCHITECTURAL PLANS AND SPECIFICATIONS.
5 ROUTE DUCT THROUGH EXISTING PENETRATION OF EXTERIOR WALL.
COORDINATE WORK WITH THE GENERAL CONTRACTOR.
6 INSTALL EXHAUST FANS ON TOP FLOOR ROOF AS SHOWN ON
MANUFACTURER SUPPLIED ROOF CURB. COORDINATE WORK WITH THE
GENERAL CONTRACTOR. MAINTAIN FANS A MINIMUM OF 10' FROM EDGE
OF PARAPET.
7 ROUTE DUCT ACROSS ROOF AS SHOWN, PROVIDE SUPPORTS FROM
ROOF DECK. COORDINATE WORK WITH GENERAL CONTRACTOR AND
OWNER TO MAINTAIN ROOF WARRANTIES.
8 ROUTE DUCT DOWN SIDE OF BUILDING IN CORNER. INSTALL SUPPORTS
AS REQUIRED.
9 CONNECT DUCT TO BIOSAFETY CABINET EXHAUST THIMBLE. COORDINATE
WITH MANUFACTURERS REQUIREMENTS.
10 MAINTAIN ACCESS TO CONTROLS SIDE OF TERMINAL UNITS DURING
CONSTRUCTION. INSTALL CARDBOARD BOX TEMPORARILY THAT
EXTENDS FROM CONTROL BOX DOWN TO CEILING LEVEL .
11 FAN FILTER UNITS WILL BE BALANCED VIA THE FAN AIRFLOW AND WILL
NOT REQUIRE A DAMPER AT THE TAKEOFF FROM THE MAIN.
12 INSTALL CHALLENGE PORTS IN DUCTWORK TO TEST HEPA FILTER.
PORTS SHALL BE INSTALLED IN LOCATION AS SHOWN AND LABELED BY
DIFFUSER.
13 CONTROLS CONTRACTOR SHALL CONNECT ENVIRONMENTAL MONITORS
INTO CAMPUS BMS. ADDITIONALLY, A CONNECTION SHALL BE SETUP FOR
THE PHARMACY TO ACCESS AND DOWNLOAD TRENDS ON THE
ENVIRONMENTAL MONITORS VIA THE BMS WITH A UNIQUE LOG IN THAT
ONLY ACCESS THE TRENDS. THE CONTROLS CONTRACTOR SHALL PLAN
FOR A MINIMUM OF 8 HOURS OF TRAINING WITH PHARMACY STAFF FOR
CONTROLS OUTSIDE THE NORMAL TRAINING REGIMEN.
14 DUCT INSTALLED FOR FUTURE CONNECTION TO BIOSAFETY CABINET AT
THIS LOCATION.
15 ROOM TEMPERATURE SENSOR SHALL BE LOCATED IN ROOM, BUT
TEMPERATURE ADJUSTMENT THERMOSTAT SHALL BE LOCATED OUTSIDE
THE SPACE AND CLEARLY LABELED FOR THE ROOM IT SERVES.
16 DUCT MAIN WILL BE INSTALLED DURING PHASE I. WORK WILL TAKE PLACE
DURING NIGHTS AND WEEKENDS. ALL CONSTRUCTION WORK MUST BE
CLEANED UP PRIOR TO START OF DAY HOURS IN THE PHARMACY DURING
THE WEEK. CAP DUCTWORK AS NEEDED FOR PHASE II.
SCALE: 1/8" = 1'-0"
GROUND FLOOR PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
ROOF PLAN - HVAC
SCALE: 1/4" = 1'-0"
SECTION @ AHU-1 - MECHANICAL
SCALE: 1/4" = 1'-0"
SECTION @ EF-1 - MECHANICAL
NOTE: ALL LOW EXHAUST GRILLES ARE TO
BE 12" A.F.F. UNLESS OTHERWISE NOTED.
N
N
NOTE: LIFE SAFETY HATCHING SHOWN FOR REFERENCE ONLY.
REFER TO SHEET G1.01 FOR FURTHER INFORMATION.
▲ REVISION 1 09/16/2020
C O
N C
R
A M
P C
O N
C R
A M
P
AREAWAY AREAWAY
S
S
SSS
S S
S S
S S
S
S
S
S
S
S
S S
S
SS
S
SS
S
S S
S
S
S S
S
S
SS
S
S
S S
S S
S
S
SS
S
S
SSSS
S
S
S S
S
S S
S
S
S
S
S
S
SS
(ON ROOF)
LPS
CWS
CWR
4"
2" 1"
H-1
(BELOW ROOF)
3CWP-1
LPR
AHU-1
4"
2 1/2"2 1/2"
3"3"
1"
/4
C D
M P
S
L P
S
/4
L P
S
/2
L P
R
2" LPS UP
1" LPR UP
4" CWS UP
4" CWR UP
C W
R C
W S
L P
S 2
M P
S
/4
C
D
2 1/2" LPS
2 1/2" LPR
STERILE
NON-HAZARDOUS
GA154
ANTE
GA154a
HAC
GA151b
STERILE
STORAGE
GA153
PROCUREMENT/STORAGE
GA151
HAC
GA149c
ANTE ALCOVE
GA149b
ANTE
GA149a
WORK AREA
G154c
EXIST. STAIR
E S1
IV STORAGE
GA143a
HAZARDOUS
STORAGE
GA148
STERILE -
HAZARDOUS
GA149
CORRIDOR
CGA8
LOCKER /
BREAK ROOM
GA142
OFFICE
GA143e
CONF /
TRAINING
GA143b
OFFICE
GA143f
OPEN OFFICE 2
GA143d
OPEN OFFICE 3
GA143
CHECKING
STATION
GA149e
CHECKING
STATION
GA154d
OPEN OFFICE 1
GA150
WORK AREA
G149d
VAV-GA151
VAV-GA153
V A
V -G
A
V A
V -G
A
V A
V -G
A E
VAV-GA143F
V A
V -G
A
V A
V -G
A B
V A
V -G
A A
VAV-GA148
VAV-GA154A
VAV-GA149A
3/4" CWS
3/4" CWR
1 1/4" HWS
1 1/4" HWR
3/4" CWS
3/4" HPWS
3/4" CD
3/4" HPWR
3/4" CD 3/4" HPWR
3/4" HPWS
VAV-GA143D
V A
V -G
A
VAV-GA154C
1 1/4" HWS
1 1/4" HWR
1 1/4" HWS
1 1/4" HWR
1" HWS
1" HWR 1" HWR
1" HWS 3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS3/4" HWS
3/4" HWR
3/4" HWR
3/4" HWS
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:1
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
GROUND FLOOR PIPING PLAN -
MECHANICAL PIPING
M201
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442415-2226.013
07607001- 5- M201
REF. NOTES ( ):X
1 INSTALL HUMIDIFIER ON UNDERSIDE OF DOCK ROOF DECK. UNIT TO BE
MOUNTED UP HIGH IN ACCESSIBLE LOCATION FOR MAINTENANCE.
INSTALL PER MANUFACTURER'S REQUIREMENTS FOR PIPING. EXTEND
HUMIDIFIER PIPE UP THROUGH ROOF AND CONNECT TO AIR HANDLER
HUMIDIFIER CONNECTION.
2 CHILLED WATER PIPING SHALL EXTEND BACK TO FLOOR BELOW DOCK
AND CONNECT AT EXISTING MAIN WITH NEW FULL SIZE TAPS.
COORDINATE WORK WITH THE OWNER FOR ANY REQUIRED SHUT DOWNS
TO INSTALL NEW TAPS.
3 INSTALL IN-LINE CIRCULATING PUMP FOR AIR HANDLER IN ACCESSIBLE
LOCATION IN DOCK AS SHOWN.
4 CONNECT NEW LPS AND LPR TO EXISTING SYSTEM AS SHOWN.
COORDINATE WORK WITH VA, WORK WILL BE DONE LIVE AND REQUIRE A
HOT TAP.
5 THIS SPACE IS RESERVED FOR ELECTRICAL EQUIPMENT. NO PIPING OR
DUCTWORK SHALL PASS BELOW, ABOVE, OR AROUND ELECTRICAL
EQUIPMENT. PROVIDE CODE REQUIRED MINIMUM CLEARANCE ABOVE
ELECTRICAL EQUIPMENT ACCESS SPACE.
6 CONNECT NEW HOT WATER PIPING INTO EXISTING AS SHOWN.
7 EXTEND COOLING COIL CONDENSATE PIPING FROM UNIT DRAIN PAN AND
PROVIDE TRAP AS REQUIRED BY MANUFACTURER. CONDENSATE TO
DRAIN ONTO THE ROOF.
8 ALL PIPING TO BE ROUTED BELOW DOCK ROOF DECK TO EXTENT
POSSIBLE.
SCALE: 1/8" = 1'-0"
GROUND FLOOR PLAN - MECHANICAL PIPING
SCALE: 1/8" = 1'-0"
BASEMENT FLOOR PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
GROUND FLOOR PLAN - MECHANICAL PIPING
NOTE:
ALL PIPING SHALL BE 3/4"Ø OR GREATER.
N
N
N
NOTE: LIFE SAFETY HATCHING SHOWN FOR REFERENCE ONLY.
REFER TO SHEET G1.01 FOR FURTHER INFORMATION.
CONCRETE OR
MASONRY PARTITION.
GROUT, SEE
SPECIFICATIONS.
1/4" CLEAR AROUND
PIPE OR INSULATION.
CAULKING, SEE
SPECIFICATIONS.
SLEEVE, SEE
SPECIFICATIONS.
NOTE:
1. CAULK FULL PERIMETER OF PIPE AT BOTH INSIDE & OUTSIDE OF WALL.
1/4" CLEAR AROUND
PIPE OR INSULATION
RISER CLAMP
CONCRETE
FLOOR
CAULKING, SEE
SPECIFICATIONS.
NOTE:
1. CAULK FULL PERIMETER OF PIPE AT BOTH TOP AND BOTTOM OF
FLOOR.
DETAIL OF SLEEVE FOR PIPING
PENETRATION OF FLOOR
DETAIL OF SLEEVE FOR PIPING
PENETRATION OF VERTICAL PARTITIONS
SLEEVE, SEE
SPECIFICATIONS.
SLEEVE HEIGHT
SHALL BE 2" HIGH IN
WET LOCATIONS, AT
FLOOR LEVEL IN ALL
OTHER LOCATIONS
RISER
CLAMP LEG
INSULATION
THREADED ROD
INSULATION
THREADED ROD
HANGER, INSULATION ON
PIPE CONTINUOUS THROUGH
HANGER WITHOUT
SWALLOWING
PIPE, 1"Ø MAX
BAND
THREADED
ROD
HANGER
INSULATION
PIPE
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
SEE CHART
SHEILD LENGTH
SEE CHART
SHEILD LENGTH,
SWIVEL
SHIELD LENGTH FOR PIPE - NOT LESS THAN THE
FOLLOWING:
a. NPS 1/4" TO 3-1/2" 12" LONG AND .048" THICK
b. NPS 4" 12" LONG AND .06" THICK
c. NPS 5" TO 6" 18" LONG AND .06" THICK
d. NPS 8" TO 14" 24" LONG AND .075" THICK
e. NPS 16" TO 24" 24" LONG AND .105" THICK
NOTE:
1. PIPES NPS 8" AND LARGER: INCLUDE WOOD OR REINFORCED CALCIUM-SILICATE-INSULATION INSERTS OF
LENGTH AT LEAST AS LONG AS PROTECTIVE SHIELD.
2. THERMAL-HANGER SHIELDS: INSTALL WITH INSULATION SAME THICKNESS AS PIPING INSULATION.
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
SHIELD TO COVER
180° OF PIPE, SEE
CHART FOR LENGTH
THREADED ROD
U-BOLT (TYP.) UNISTRUT OR STEEL
ANGLE WITH LONG LEG
DOWN
SHIELD TO COVER
360° OF PIPE, SEE
CHART FOR LENGTH
HANGER, INSULATION ON
PIPE CONTINUOUS THROUGH
HANGER WITHOUT
SWALLOWING
PIPE (TYP.)
LONG FLAT SPANS ON OVAL DUCT HAVE A TENDENCY TO SAG. OVAL
DUCT
WITH A MAJOR AXIS OF 42 INCHES OR MORE SHALL BE REINFORCED PER
SMACNA HVAC DUCT CONSTRUCTION STANDARDS TYPE 2.
CHANNEL OR ANGLE
HANGER CLAMP
OR BAND
BOLT
STRAP
OR
ANGLE
ROD (TYP)
DUCT (TYP)
ANGLE (TYP)
NUT (TYP)
NOTES:
1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.
2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO DUCTWORK.
3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCT AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE HANGERS.
4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINTAIN THE INTEGRITY OF THE VAPOR BARRIER.
5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALLY WRAPPED.
ECCENTRIC TRANSITION
B (MAX.)=30°
(EXCEPT 45° IS PERMITTED
AT ROUND TO FLAT OVAL)
(ANGLED)
Offset Type 1
C (MAX.)=45° DIVERGING, 60° CONVERGING
CONCENTRIC TRANSITION
W
W
L
A (MAX.)=15°
A
W
L
W
W
B
W
W
L
C
X + Y = Z
FULL
RADIUS
ELBOW
X
Y Y
X
FULL
RADIUS
ELBOW
X + Y = Z
A B
C D
PLAN
SECTION
TURNING
VANES
PLAN
SECTION
TURNING VANES
W W W W
H H HH
ZZ
Z Z
X
Y
Y
X
PLAN
SECTION
PLAN
SECTION
SHEET METAL 90° ELBOW
DIFFUSER NECK
TRANSITION
(AS REQUIRED)
CEILING
SUPPLY DUCT-
SEE PLANS FOR
SIZES
SUPPLY DIFFUSER
DUCT INSULATION
FLEX DUCT
INSULATE BACKPAN
DAMPER
STANDOFF
DAMPER
QUADRANT LOCK
NOTE:
ALL TAPS TO AIR TERMINALS REQUIRING BALANCING AT DUCT SHALL
BE MADE USING A HIGH EFFICIENCY TAKEOFF.
TYPE RE 1
RADIUS ELBOW
CENTERLINE R = (3W)/2 UNLESS OTHERWISE
SPECIFIED Θ IS NOT RESTRICTED TO 90°.
SQUARE THROAT, R/W=0.5, MAY BE USED,
UP TO 1000 FPM (5 MPS).
W
H
R
Θ
TYPE RE 2
SQUARE THROAT ELBOW
WITH VANES
TYPE RE 3
RADIUS ELBOW WITH VANES
12 11 10 9 8 7 6 5 4 3 1
MODULE LAYOUT:
1. INTAKE
2. PRE-FILTER
3. REDUNDANT PRE-FILTER
4. ACCESS SECTION
5. STEAM HEATING COIL
6. ACCESS SECTION
7. HUMIDIFIER MODULE
8. ACCESS SECTION
9. COOLING COIL
10. ACCESS SECTION
11. COOLING COIL
12. ACCESS SECTION
13. SUPPLY FAN ARRAY
14. FINAL-FILTER
15. DISCHARGE PLENUM
NOTE:
1. ACCESS DOORS TO BE A MINIMUM OF 24" WIDE UNLESS OTHERWISE SHOWN.
1'-6 11/16"
. 8
335"
RETURN AIR
SUPPLY AIR
ACCESS
DOOR (TYP.)
2131415
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:1
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
DETAILS - MECHANICAL
M401
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442515-2226.013
07607001- 5- M401
SCALE: NOT TO SCALE
INTERIOR PIPE SLEEVE DETAILS
SCALE: NOT TO SCALE
PIPE HANGER DETAIL
SCALE: NOT TO SCALE
DUCT HANGER DETAIL
SCALE: NOT TO SCALE
OFFSETS AND TRANSITIONS DETAIL
SCALE: NOT TO SCALE
PARALLEL FLOW BRANCH DETAIL
SCALE: NOT TO SCALE
SUPPLY DIFFUSER/ DUCT CONNECTION DETAIL
SCALE: NOT TO SCALE
HIGH EFFICIENCY TAKEOFF DETAIL
SCALE: NOT TO SCALE
DUCT ELBOW DETAIL
SCALE: NOT TO SCALE
AHU SECTION DESIGNATION DETAIL
[2 m m
[1 m m
[3 m m
8"x8"x3/8" [203x203x8.0mm]
STEEL PLATE
WELD PLATE
TO PIPE
SECURE TO ROOF SLAB
WITH (4) 3/8"
[8.0mm]Ø EXPANSION
BOLTS OR WELD TO
STEEL DECK
CONCRETE ROOF SLAB
OR STEEL ROOF DECK
ROOF SYSTEM
INSULATION AND
MEMBRANE
PRE-MOULDED
FLEXIBLE PIPE
COUNTER FLASHING
CLAMPING RING
ROOF SURFACE
WELD PIPE SADDLE
SUPPORT TO PIPE.
PROVIDE WATER
TIGHT CONNECTION
HIGH COMPRESSIVE
STRENGTH
INSULATION INSERT
UNDER SHIELD
PIPE AND
INSULATION
INSULATION
PROTECTION
SHIELD
SEALANT
2" [50mm]
STEEL PIPE
2-1/2" [65mm]
STEEL PIPE
PROVIDE ALUMINUM
JACKET
NOTES:
PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.
M
IN
2'-3 24 1/256"
1'-3 16 5/256"
3'-7 75/12
8"
STEAM TRAP ASSEMBLY
STEAM LINE DRIP POCKET
[1 m m
M
IN
[3 m m
M
IN
[1 m m
M
IN
[3 m m
M
IN
DRIP LEG (TYP.)
3/4" [20mm] DRAIN
(ALTERNATE LOCATIONS)
(TYPICAL)
STEAM LINE
(TYPICAL)
CAP (TYPICAL)
PIPE T0
STEAM TRAP
(TYPICAL)
NOTE:
DRIP POCKET PIPE SIZE
SAME AS STEAM MAIN
UNLESS OTHERWISE NOTED.
3/4" [20mm] MIN.FROM DRIP
CONNECTION
DRIP
RETURN
3/8" [10mm] TEST
CONNECTION
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION
THREADED
PIPING
ELEVATION
WELDED
PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" [15mm]
BALL VALVE
1/4" [8mm]
COPPER TUBING
1/2" [15mm] x 4" [100mm]
NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE DRAIN
PAN PIPING SHALL BE RIGID COPPER TYPE L
OR TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
DRAIN
PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY
LOCAL VA AND IS INDOORS AND DOES NOT PASS THROUGH
RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR
METALS ARE TO BE CONNECTED.
[2 m m
DIELECTRIC
FITTING
A B
DRAIN TO ROOF
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION
CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
THERMOMETER (TYP.)
P R
E
F
IL
T E
R
OUTSIDE
AIR
D-1
C O
IL
P
R E
H E
A T
C O
IL
C
O O
L
IN
G
LOCATE
SENSOR
OUTSIDE
UNDER
SHIELD
MPS
V-2
V-1
CHR
CHS
SUPPLY FAN
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
TT
TT
TT TT
FTA
F T
E R
F
IL
T
E R
HS
IT
VSMC
T-2
3 6
SD
ONLY WHERE REQUIRED
PSH
SMOKE
DETECTOR
VARIABLE SPEED
MOTOR
CONTROLLER, TYP.
ZC
PDS PDS
TT
SST
SD
SPSTSL
TSL-1
NO
V-4
STEAM HUMIDIFIER
2C
ECC
MT
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN
HIGH PRESSURE LIMIT
SETPOINT IS REACHED
F
IN
A L
F
IL
T E
R
PDS
C O
IL
C
O O
L
IN
G
V-1
CHR
CHS
SUPPLY FAN
TT
NO
DRAIN VALVE
(TYP.)
MANUAL AIR VENT
(TYP.)
THERMOMETER (TYP.)
STRAINER
CONTROL
VALVE
ISOLATION VALVE
(TYP.)
UNION
(TYP.)
AUTOFLOW/ ISOLATION
VALVE
PRESSURE
GAUGE
SUPPLY
RETURN
COIL
CAP WITH HOSE
CONNECTION
(TYP.)
PT PORT
(TYP.)
(HANGER)
ANCHOR
SEE KNEE BRACKET TABLES IN
THE ROUND INDUSTRIAL STD.
FIG. B
FIG. B SUGGESTED SIZING
DUCT SIZE
30" X 12" 36" X 18" 42" X 24" 48" X 30"
ANGLE
1" X 1" X 1/8" 1" X 1" X 1/8"
1-1/4" X 1-1/4" X 1/8" 1-1/4" X 1-1/4" X 1/8"
FIG. A
ANCHORFASTENER
SHOWS SUPPLEMENTAL
FASTENER LOCATIONS
ANCHOR
CL
Y
X
Y
Y
Y
X
FIG. A SUGGESTED SIZING
DUCT SIZE
18" X 12" 24" X 20"
BAND
1-1/2" X 16 GA.
1" X 1/8"
TABLE 4-4
DUCT GAGE
28, 26 24, 22, 20 18, 16
ALLOWABLE
LOAD PER
FASTENER
25 LB
35 LB
50 LB
*WELD, BOLT OR NO. 8 SCREW (MIN.).
DEVIATION PERMITTED BY OTHER
ANALYSIS. X = 1", Y = 2"; ADD OTHERS TO
ACCOMMODATE LOAD. MINIMUM OF 3 ON
24" WIDTH AND UP. ADD ALONG SIDES
NEAREST ANCHORS.
NOTE: 1. BRACKETS ARE SIZED FOR 12 FEET OF DUCT, MAXIMUM.
2. LOCATED DUCTS AGAINST WALL OR MAXIMUM OF 2" AWAY FROM WALL.
3. EACH WALL ANCHOR SHALL SATISFY THE FOLLOWING CRITERIA UNLESS
OTHER ANALYSIS IS MADE:
A. TENSILE LOAD = 3/8" X DUCT WEIGHT; SAFETY FACTOR OF 4.
B. SHEAR LOAD X 1/2 X DUCT WEIGHT; SAFETY FACTOR OF 4.
N
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
635-18-102
ALBERTSON ENGINEERING, INC.
3202 WEST MAIN STREET, SUITE C
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 343-9606
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
SCHEMMER
1044 NORTH 115TH ST, SUITE 3300
OMAHA, NEBRASKA 68154
PH: (402) 493-4800
PROJECT AREA
KEY PLAN
NOT TO SCALE
/1
/2
:0
:2
P
M
CONSTRUCTION DOCUMENTS
7/10/2020
DETAILS - MECHANICAL
M402
RENOVATE PHARMACY FOR
CHAPTER 797_800
MLBARP
OKLAHOMA CITY, OKLAHOMA
OKLAHOMA CITY VAMC
442615-2226.013
07607001- 5- M402
SCALE: NTS
DETAIL FOR SUPPORTING PIPE ON ROOF
SCALE: NTS
STEAM LINE DRIP POCKET STEAM TRAP ASSEMBLY
SCALE: NTS
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)
SCALE: NTS
AIR HANDLING UNIT DRAIN TRAP DETAIL
SCALE: NTS
TERMINAL UNIT WATER COILS - PIPING CONNECTIONS
SCALE: NTS
100% OUTSIDE AIR VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL DIAGRAM
SCALE: NOT TO SCALE
SINGLE COIL PIPING DETAIL (AUTOFLOW VALVE)
SCALE: NOT TO SCALE
DUCT RISER SUPPORTS FROM WALL DETAIL
AIR HANDLING UNIT SCHEDULE
MARK: AHU-1
LOCATION: ROOF
UNIT TYPE:
DRAW THRU / BLOW THRU DRAW THRU
COOL / HEAT / COOL & HEAT COOL & HEAT
VAV / DUAL DUCT/ MULTI ZONE VAV
UNIT ARRANGEMENT:
HORIZONTAL / VERTICAL HORIZONTAL
FLOOR MTD / SUSPENDED ROOF MOUTNED
DISCHARGE ARRANGEMENT FRONT
BASIS OF DESIGN:
BASIS OF DESIGN: TRANE
SERIES / MODEL NUMBER CSAA021
DIMENSIONS (IN) H X W X L 56 X 80 X 335
OPERATING WEIGHT (LBS) 6,539
MINIMUM OUTSIDE AIR CFM 9,500
COMPONENTS (IN DIRECTION OF AIRFLOW):
INLET SECTION BACK INLET
PRE FILTER/ INLET PF-1
REDUNDANT PRE FILTER PF-2
ACCESS SECTION 20"
STEAM HEATING COIL SC-1
ACCESS SECTION 19"
HUMIDIFIER H-1
ACCESS SECTION 24.5"
COOLING COIL CC-1
ACCESS SECTION 19"
COOLING COIL CC-2
ACCESS SECTION 24.5"
SUPPLY AIR FAN SAF-1
FINAL FILTER FF-1
DISCHARGE PLENUM 20"
SUPPLY AIR FAN: SAF-1
NUMBER / SIZE / TYPE 4 / 13.5 / PF
DRIVE TYPE: DIRECT
FAN STATIC PRESSURE - IN W.C. 7.89
EXTERNAL STATIC PRESSURE - IN W.C. 3.00
FAN BHP / RPM 4.37 / 3874
MOTOR HP / RPM 7.5 / 3600
TOTAL BHP 17.484
ELECTRICAL CHARACTERISTICS 460 / 3 / 60
UNIT VIBRATION ISOLATORS 2" SPRING
STEAM COIL: SC-1
COIL CAPACITY - MBH 542.4
AIRFLOW - CFM 9,500
AIR TEMPERATURE EAT/LAT - DEG F 14.5 / 66.6
AIR PRESSURE DROP - IN W.C. 0.34
FLUID TYPE STEAM
CONDENSATE LOAD (LB/HR) 573
STEAM PRESSURE (PSI) 15.0
COILS / ROWS / FINS PER INCH 1 / 2 / 8
FACE AREA - SQFT 13.87
FACE VELOCITY - FPM 685
CHILLED WATER COIL: CC-1
COIL CAPACITY - MBH 650.7
AIRFLOW - CFM 9,500
ENTERING AIR EDB/EWB - DEG F 83.9 / 76.8
LEAVING AIR LDB/LWB - DEG F 58.0 / 57.9
AIR PRESSURE DROP - IN W.C. 0.527
CHILLED WATER FLOW - GPM 81.0
FLUID TYPE WATER
WATER TEMPERATURE EWT/LWT - DEG F 42 / 58
WATER PRESSURE DROP - FT W.C. 18.0
COILS / ROWS / FINS PER INCH 1 / 4 / 12
FACE AREA - SQFT 20.8
FACE VELOCITY - FPM 456
CHILLED WATER COIL: CC-2
COIL CAPACITY - MBH 314.8
AIRFLOW - CFM 9,500
ENTERING AIR EDB/EWB - DEG F 58.0 / 57.0
LEAVING AIR LDB/LWB - DEG F 44.0 / 43.9
AIR PRESSURE DROP - IN W.C. 1.1
CHILLED WATER FLOW - GPM 125.4
FLUID TYPE WATER
WATER TEMPERATURE EWT/LWT - DEG F 42 / 47
WATER PRESSURE DROP - FT W.C. 13.7
COILS / ROWS / FINS PER INCH 1 / 8 / 13
FACE AREA - SQFT 20.8
FACE VELOCITY - FPM 456
PANEL FILTER ASSEMBLY: PF-1
FILTER TYPE 2" PLEATED
MERV 8
AIRFLOW - CFM 9,500
FACE VELOCITY - FPM 285
MEAN AIR PRESSURE DROP - IN W.C. 0.57
PANEL FILTER ASSEMBLY: PF-2
FILTER TYPE 2" PLEATED
MERV 8
AIRFLOW - CFM 9,500
FACE VELOCITY - FPM 285
MEAN AIR PRESSURE DROP - IN W.C. 0.57
FINAL FILTER ASSEMBLY: FF-1
FILTER TYPE 18" BAG MERV 15
PREFILTER TYPE 2" PLEATED MERV 8
MEAN AIR PRESSURE DROP - IN W.C. 0.82
QUANTITY 3
AIRFLOW - CFM 9,500
FACE VELOCITY - FPM 432
HUMIDIFIER:
ENTERING DRY BULB 55.00
ENTERING RELATIVE HUMIDITY 10%
LEAVING RELATIVE HUMIDIITY 40%
AIR TEMPERATURE GAIN 1.23
STEAM FLOW - LBS/HR 126.50
NOTES: 1. UNIT SHALL BE PROVIDED WITH VFD FOR EACH FAN.
2. FAN MOTORS SHALL BE PROVIDED WITH INTEGRAL SHAFT…