2026-06-05 NVARNG ACC Gate Replacement Bid Set.pdf
PDF 12 MB Posted
- Attached to
- ACC Gate Replacement
- Solicitation number
- 43ADG-S4000
- Issued by
- Clark County, Fish Springs CDP, Nevada
About this file
2026-06-05 NVARNG ACC Gate Replacement Bid Set
This is a bid set document for the Nevada Army National Guard (NVARNG) for an ACC Gate Replacement project. The project involves modifying and retrofitting an existing manual sliding entry gate to an automated, access-controlled system. The scope of work includes structural modifications, electrical installation, and trenching work necessary to support the automated gate system. The bid set provides technical specifications, project drawings, and requirements for qualified contractors to submit competitive bids for the gate replacement and installation. Specific details regarding bid submission deadlines, site visit requirements, pre-bid meetings, and award timelines are contained within the bid documents.
The bid set establishes the technical and contractual framework for the automated gate system installation, including equipment specifications, installation standards, and quality requirements that bidders must meet. Pricing proposals and cost structures for the work are to be submitted by interested contractors in accordance with the bid instructions and evaluation criteria outlined in the documentation. Additional details regarding funding sources, budget allocation, any small business or veteran-owned business set-asides, contract term length, and payment terms are specified within the full bid set materials.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SIMPSON COULTER | STUDIO
151 E WARM SPRINGS RD
LAS VEGAS, NV 89119
P: (702) 435-1150
OWNER ARCHITECT
SCS-2024015
BID SET
GATE REPLACEMENT
NEVADA ARMY NATIONAL GUARD
2460 FAIRVIEW DRIVE
CARSON CITY, NV 89701
P: (775) 884-8459
TJK CONSULTING ENGINEERS
8728 SPANISH RIDGE AVENUE,
LAS VEGAS, NV 89148
P: (702) 871-3621
ELECTRICAL ENGINEER
CONSULTANTS
NVARNG ANTHONY COMETA COMPLEX
JUNE 05, 2026
KLEINFELDER
6960 SMOKE RANCH ROAD,
SUITE 110
LAS VEGAS, NV 89128
P: (702) 255-8100
CIVIL ENGINEER
WRIGHT ENGINEERS
1645 VILLAGE CENTER CIRCLE,
SUITE 10
LAS VEGAS, NV 89134
P: (702) 933-7000
STRUCTURAL ENGINEER
VICINITY MAP
NOT TO SCALE
N O
R T
H
PROJECT
SITE
ABBREVIATIONS
AB
ACI
AD
ADJ
AFF
AL
ANSI
ARCH
ASS'Y
ASTM
A/V
BOT
BD
BLDG
BRG
C.F.C.I.
C.F.O.I.
CL OR CLR
CLG
COL
CONC
CONT
CPT
CT
CSK
D
DBL
DEG
DEPT
DTL
DF
DIA
DIM
DWG
EA
EL, ELEV
ELEC
EWC
EXH
EXIST
EXT
FD
FDN
FEC
FLR
FT
FTG
GA
GALV
GB
GFI
GR
GYP. BD.
HB
HDWD
HDWR
HORIZ
HVAC
ID
IN
INCL
INFO
INT
JT
LAM
LAV
LB, LBS
MATL
MAX
MECH
MED
MTL
MEZZ
MIN
MFR
MISC.
MO
MTD
N/A
NIC
NO.
NOM
NVE.
NTS
OC
OD
O.F.C.I.
O.F.O.I.
OPNG
OPP
PLAM
PL
PL
PLYWD
PTD
PVC
QTY
RA
RD
REF.
REQ'D
REV
RM
RO
ROW
SA
SC
SD
SECT
SHT
SIM
SPEC
SQ
SST
STA
STD
STL
STOR
STRUCT
SUSP
SYM
T & G
THK
T.O.
T.O.P.
T.O.S.
T.O.W.
TPTB
TYP
UL
U.N.O.
UR
VERT
V.I.F.
VCT
W/
W.C.
WD
W/O
W.P.
W.I.
YD
AND
AT
EQUAL
FOOT, FEET
INCH, INCHES
POUND, NUMBER
ANCHOR BOLT
AMERICAN CONCRETE INSTITUTE
AREA DRAIN
ADJUSTABLE
ABOVE FINISHED FLOOR
ALUMINUM
AMERICAN NATIONAL
STANDARDS INSTITUTE
ARCHITECT, ARCHITECTURAL
ASSEMBLY
AMERICAN SOCIETY OF TESTING AND
MATERIALS
AUDIO/VISUAL
BOTTOM
BOARD
BUILDING
BEARING
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED,
OWNER INSTALLED
CLEAR
CEILING
COLUMN
CONCRETE
CONTINUOUS
CARPET
CERAMIC TILE
COUNTER SINK
PENNY (NAILS, ETC.)
DOUBLE
DEGREE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIMENSION
DRAWING
EACH
ELEVATION
ELECTRICAL
ELECTRIC WATER COOLER
EXHAUST
EXISTING
EXTERIOR
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER CABINET
FINISH
FLOOR
FOOT OR FEET
FOOTING
GAUGE
GALVANIZED
GRAB BAR, GYPSUM BOARD
GROUND FAULT INTERRUPTER
GRADE
GYPSUM BOARD
HOSE BIBB
HARDWOOD
HARDWARE
HORIZONTAL
HEATING, VENTILATING,
AIR CONDITIONING
INSIDE DIAMETER
INCH OR INCHES
INCLUDE OR INCLUDED
INFORMATION
INTERIOR
JOINT
LAMINATE
LAVATORY
POUND, POUNDS
MATERIALS
MAXIMUM
MECHANICAL
MEDIUM
METAL
MEZZANINE
MANUFACTURER
MINIMUM, MINUTE
MISCELLANEOUS
MASONRY OPENING
MOUNTED
NOT APPLICABLE
NOT IN CONTRACT
NUMBER
NOMINAL
NEVADA ENERGY
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OWNER FURNISHED,
CONTRACTOR INSTALLED
OWNER FURNISHED,
OWNER INSTALLED
OPENING
OPPOSITE
PLASTIC LAMINATE
PROPERTY LINE
PLATE
PLYWOOD
PAPER TOWEL DISPENSER
POLY VINYL CHLORIDE
QUARRY TILE
QUANTITY
RADIUS
RETURN AIR
ROOF DRAIN
REFRIGERATOR
REQUIRED
REVISION, REVERSE
ROOM
ROUGH OPENING
RIGHT OF WAY
SUPPLY AIR
SOLID CORE, SEALED CONCRETE
SOAP DISPENSER, SMOKE DAMPER
SECTION
SHEET
SIMILAR
SPECIFICATION
SQUARE
STAINLESS STEEL
STATION
STANDARD
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SYMMETRICAL
TOP OF CURB
TONGUE AND GROOVE
THICK
TOP OF
TOP OF PARAPET
TOP OF STEEL
TOP OF WALL
TREATED PLYWOOD TERMINAL BOARD
TYPICAL
UNDERWRITER'S LABORATORY
UNLESS NOTED OTHERWISE
URINAL
VERTICAL
VERIFY IN FIELD
VINYL COMPOSITION TILE
WITH
WATER CLOSET
WOOD
WITHOUT
WORK POINT, WALL PADDING
WROUGHT IRON
YARD
FIN
CMU
CNTR
CONCRETE MASONRY UNITS
COUNTER R
T.O.C.
DIAMETER, ROUND, PHASE
CENTERLINECL
ANGLE
QT
AP ACOUSTICAL PANEL
AT
ACOUSTICAL CEILING TILE
BFC BROOM FINISHED CONCRETE
CG CORNER GUARD
COND CONDITION
CP CEMENT PLASTER
DW DISHWASHER
E.I.F.S. EXTERIOR INSULATION AND
FINISH SYSTEM
FS FLOOR SAFE, FLOOR SINK
MB MARKER BOARD
MCJ MASONRY CONTROL JOINT
MS MOP STRIP
RH ROBE HOOK
RB RESILIENT BASE, RUBBER BASE
SCR SHOWER CURTAIN AND ROD
SL LOCKERS
TB TACKBOARD
WF WOOD FLOORING
IBC INTERNATIONAL BUILDING CODE
CO CLEAR OPENING
FOF FACE OF FINISH
GENERAL NOTES
1. ALL CONSTRUCTION SHALL CONFORM TO THE AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG), ANSI A117.1, AND ALL LOCAL GOVERNING FIRE, LIFE SAFETY, AND BUILDING CODES, REQUIREMENTS AND
REGULATIONS, LATEST ADOPTED EDITIONS.
2. ALL DIMENSIONS ARE TO THE FACE OF CONCRETE OR MASONRY FACE OR STUD WALLS, OR CENTERLINE OF
COLUMNS UNLESS NOTED OTHERWISE.
3. CONTRACTOR SHALL COORDINATE ALL DISCIPLINES AND ALL ASPECTS OF WORK. CONFLICTS AND
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.
4. ALL FINISH ELEVATIONS ARE TO TOP OF WALKS, GRADE, PAVING, WALLS, ROOFS, ETC. UNLESS OTHERWISE
NOTED.
5. ALL SOIL BERMS SHALL BE CONSTRUCTED TO DRAIN AWAY FROM VERTICAL SURFACES.
6. ALL GROUND PREPARATION SHALL BE IN CONFORMANCE WITH THE RECOMMENDATIONS OF THE PROJECT GEOTECHNICAL REPORT. THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A COPY OF THIS REPORT.
7. ALL SURFACES WHICH RECEIVE A SPECIAL FINISH, FLOOR COVERING, COATINGS, HARDENERS, WATERPROOFING, ETC. SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE SPECIFIC FINISH MANUFACTURERS SPECIFICATIONS, RECOMMENDATIONS AND INSTRUCTIONS. PRIOR TO APPLICATION OF A SPECIAL FINISH, A WRITTEN ACCEPTANCE
OF THE SURFACE SHALL BE SUBMITTED TO THE ARCHITECT BY THE GENERAL CONTRACTOR.
8. ALL CONCRETE WALKS, RAMPS, STEPS, CURBS AND EQUIPMENT PADS SHALL HAVE A MEDIUM BROOM FINISH, PERPENDICULAR TO THE PATH OF TRAVEL, UNLESS NOTED OTHERWISE.
9. CONTRACTOR SHALL PROVIDE A MINIMUM 4" RAISED CONCRETE HOUSEKEEPING PAD, UNLESS NOTED OTHERWISE AT ALL LOCKERS, MECHANICAL, ELECTRICAL EQUIPMENT (BOILERS, CHILLERS, PUMPS, PANELS, SWITCHBOARDS, ETC.). COORDINATE EXACT SIZE REQUIREMENTS WITH EQUIPMENT TO BE INSTALLED. PROVIDE
ASPHALTIC BITUMINOUS SEPARATIONS BETWEEN ALL ADJACENT SURFACES.
10. SAW CUTS IN LIEU OF CONSTRUCTION JOINTS ARE NOT ALLOWED IN CONCRETE SLABS AND SIDEWALKS. ANY
DEVIATION IS TO BE REQUESTED AND APPROVED BY ARCHITECT.
11. ALL SURFACES UPON WHICH PEDESTRIANS AND OCCUPANTS CAN WALK SHALL BE FINISHED SUCH THAT THE MINIMUM STATIC COEFFICIENT OF SLIDING FRICTION BETWEEN THE SURFACE AND NORMAL HARD-SOLED SHOES =
0.60 AND 0.80 FOR RAMPS.
12. ALL CONCRETE AND MASONRY CONNECTIONS AND JOINTS SHALL BE COMPLETELY SEALED AND WATERPROOFED WITH BACKER ROD AND SEALANT REFER TO EACH APPLICABLE SPECIFICATION SECTION AND/OR DRAWING
DETAILS.
13. CONTRACTOR SHALL COORDINATE ALL CONCRETE SLABS TO SLOPE AWAY FROM BUILDING, TO SLOPE TOWARD
DRAINS AT LESS THAN 2% SLOPE EACH WAY, TO RECESS FOR TILE APPLICATIONS, ETC.
14. ALL CONCRETE, MASONRY, STEEL SURFACES ADJACENT TO SOIL, PLANTERS, GRADED AREAS SHALL BE PROVIDED WITH A MONOLITHIC WATERPROOF SYSTEM EXTENDING FROM BOTTOM OF FOOTING TO 4" ABOVE SOIL.
15. ALL EXPOSED WELDS SHALL BE GROUND SMOOTH AND FINISHED WITH NO PITS FOR ARCHITECTURAL
APPEARANCE TO A LEVEL ACCEPTABLE TO THE ARCHITECT.
16. ALL EXPOSED METAL SURFACES ARE TO BE PAINTED TO MATCH ADJACENT SURFACES.
17. PROVIDE SEALANT, CAULK AND SEPARATION AND/OR APPROPRIATE COATING BETWEEN ALL SIMILAR AND
DISSIMILAR METALS AND MATERIALS.
18. COATINGS MUST COMPLY WITH ALL LOCAL AND FEDERAL LAWS GOVERNING VOLATILE ORGANIC COMPOUNDS, AND ALL EPA RECOMMENDATIONS.
19. CONTRACTOR SHALL NOT SCALE ANY DRAWING IN THIS PROJECT SET. IF A DISCREPANCY IS FOUND, THE ARCHITECT IS TO BE NOTIFIED IMMEDIATELY. GRAPHIC SCALES (IF SHOWN) ARE PROVIDED FOR REFERENCE
ONLY.
20. ALL TRANSITIONS BETWEEN SIMILAR OR DISSIMILAR MATERIALS, EQUIPMENT, ACCESSORIES, ETC. SHALL BE
CAULKED AND/OR SEALED.
21. CONTRACTOR IS RESPONSIBLE TO COORDINATE LOCATION OF ALL ACCESS DOORS FOR PLUMBING, MECHANICAL & ASSOCIATED TRADES TO INSURE SERVICEABILITY OF EQUIPMENT. ALL ACCESS DOORS EXPOSED TO GENERAL
PUBLIC ARE REQUIRED TO BE LOCKABLE.
22. CONTRACTORS LICENSED BY THE OFFICE OF THE STATE FIRE MARSHALL ARE REQUIRED TO SUBMIT PLANS TO THE STATE FIRE MARSHAL FOR REVIEW ON THE AUTOMATIC FIRE SPRINKLER AND ASSOCIATED BOOSTER PUMPS, FIRE ALARM, AND UNDERGROUND FIRE WATER PIPING.
23. CONTRACTOR IS RESPONSIBLE TO SUBMIT DEFERRED SUBMITTALS IN ACCORDANCE WITH IBC 106.3.4.2 AND IBC 106.1.1.
24. CONTRACTOR IS RESPONSIBLE FOR COORDINATING, VERIFYING, AND CONSTRUCTING GRADE VARIATIONS BETWEEN FENCING PILASTERS TO ENSURE A MAXIMUM ALLOWABLE GAP BETWEEN EXISTING OR NEW GRADES
AND BOTTOM OF FENCE PICKETS IS NO MORE THAN 4" UNLESS NOTED OTHERWISE.
25. ALL EXTERIOR CONCRETE PAVING IS TO BE PROVIDED WITH A MINIMUM 8" X 8" X CONTINUOUS THICKENED EDGE WITH CONTINUOUS NO. 4 BAR AT MID-POINT OF SLAB EDGE, UNLESS NOTED OTHERWISE. ALL EXTERIOR CONCRETE PAVING IS TO BE PROVIDED WITH A 6" X 6" X1.6 WELDED WIRE FABRIC AT MID-HEIGHT TO 3" FROM
EACH SLAB EDGE WIDTH.
NORTH
C.2
A1.01
TYP.
A1.01
TYP.
WINDOW / OPENING
IDENTIFICATION TAG
PARTITION
IDENTIFICATION TAG
MATERIAL
IDENTIFICATION TAG
KEYNOTE
REFERENCE
GRID BUBBLE
DOOR
IDENTIFICATION TAG
ROOM NAME /
ROOM NUMBER TAG
NORTH ARROW
ELEVATION DATUM AND
ELEVATION, A.F.F., UNLESS
NOTED OTHERWISE
CENTERLINE
REFERENCE
BUILDING / WALL SECTION
DIRECTION & CALL-OUT
DETAIL /
SECTION CALL-OUT
SYMBOL LEGEND
Name Elevation
Room name
CODE ANALYSIS
PROJECT DESCRIPTION
This project involves the modification & retrofiting of the existing Anthony Cometa Campus' manual sliding entry gate. The site is located along the intersection of Arville Street & West Serene Avenue and the entry gate is located on the north side of the property.
The modifications & retrofiting summary of this entry gate include the following (refer to civil, structural, and electrical drawings for additional information on scope of work).
• Installation of a automated gate operator with access control
• Retrofit the existing metal gate and supports to accomodate gate motor
• Contruction of concrete pad and bollard protection
• Connection of electrical and low voltage back to the existing Feild Maintenance Shop Building
• Installation of automatic vehicle detection loops
This project is exclusively exterior in scope and involves no modifications to the existing building structure, occupancy, or systems.
As such, it does not affect the compliance of the existing building with applicable codes. The proposed work will adhere to all relevant exterior safety, electrical, and zoning standards to ensure compliance without impacting the existing building or existing code requirements.
CODE ANALYSIS
NEVADA STATE PUBLIC WORKS ADOPTED CODES (AND APPLICABLE STANDARDS)
• 2018 International Building Code
• 2018 International Energy Conservation Code
• 2018 Uniform Mechanical Code
• 2018 Uniform Plumbing Code
• 2017 National Electrical Code
• 2018 International Fire Code
• 2018 International Energy Conservation Code
• 2018 International Existing Building Code
• 2009 ICC/ANSI A11.7.1 Accessible & Usable Building & Facilities
• 2018 International Fire Code NFPA Standards
• 2018 International Building Code NFPA Standards
• 2023 Nevada Revised Statutes Chapter 477
SITE AREA:
Parcel Acreage: 54.14 Acres Approximate Work Area: 3,500 SF
P R
O J E
C T
N A
M E
O W
N E
R
S H
E E
T T
IT
L
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
06/05/26
SCS-2024015
G0.01
G E
N E
R A
L N
O T
E S
A N
T H
O N
Y C
O M
E T
A C
O M
P L
E X
G A
T E
R E
P L
A C
E M
E N
T
BID SET
N E
V A
D A
A R
M Y
N A
T
IO
N A
L G
U A
R D
SHEET INDEX
SHEET NO. SHEET NAME
GENERAL
G0.00 COVER SHEET
G0.01 GENERAL NOTES
CIVIL
C0.00 COVER SHEET
C0.01 GENERAL NOTES
C0.02 NOTES, LEGEND & ABBREVIATIONS
C1.00 DEMOLITION PLAN
C3.00 GRADING PLAN
ARCHITECTURAL SITE
AS1.01 ARCHITECTURAL SITE PLAN
AS1.02 ARCHITECTURAL SITE DETAILS
STRUCTURAL
S0.01 GENERAL STRUCTURAL NOTES, ABBREVIATIONS, PLAN AND DETAILS
ELECTRICAL
E0.01 GENERAL INFORMATION
E0.10 IECC
E0.30 SITE PLAN
E1.01 ELECTRICAL PLANS
E5.01 ONE-LINE DIAGRAM AND SCHEDULES
E7.01 DIAGRAMS
NO. DATE DESCRIPTION
06/01/2026
PR
O
JE
CT
N
AM
E
O W
NE
R
SH
EE
T
TI
TL
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
6/5/2026
SCS-2024015
A N
TH
O
N Y
C O
M
ET
A C
O M
PL
EX
G A
TE
R
EP
LA
C
EM
EN
T
BID SET
N
EV
AD
A
AR
M
Y N
AT
IO
N
AL
G U
AR
D
NO. DATE DESCRIPTION
6-5-2026
STATE OF NEVADA
CIVIL ENGINEEROWNER/DEVELOPER
KLEINFELDER
6280E S. VALLEY VIEW BLVD, SUITE 500
LAS VEGAS, NV 89118
NICHOLAS S. APPUGLISE, PE
PHONE - (725) 222-5568
4500 W SILVERADO RANCH BLVD
LAS VEGAS, NEVADA 89139
APN: 177-19-302-011
ACREAGE = 54.14 AC
NEVADA DIVISION OF STATE LANDS
901 S STEWART STREET #5003
CARSON CITY, NV 89701
775-684-2720
NEVADA ARMY NATIONAL
GUARD GATE REPLACEMENT
BID SET
6/5/2026
N
C O
VE
R
S H
EE
T
C0.00
EXCEPTION:
PR
O
JE
CT
N
AM
E
O W
NE
R
SH
EE
T
TI
TL
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
6/5/2026
SCS-2024015
A N
TH
O
N Y
C O
M
ET
A C
O M
PL
EX
G A
TE
R
EP
LA
C
EM
EN
T
BID SET
N
EV
AD
A
AR
M
Y N
AT
IO
N
AL
G U
AR
D
NO. DATE DESCRIPTION
6-5-2026
G
EN
ER
A
L N
O
TE
S
C0.01 s
GB GB GB GBGB GB GB GB
stlt stlt tsi tsi
STLT STLT
ITS ITS
PR
O
JE
CT
N
AM
E
O W
NE
R
SH
EE
T
TI
TL
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
6/5/2026
SCS-2024015
A N
TH
O
N Y
C O
M
ET
A C
O M
PL
EX
G A
TE
R
EP
LA
C
EM
EN
T
BID SET
N
EV
AD
A
AR
M
Y N
AT
IO
N
AL
G U
AR
D
NO. DATE DESCRIPTION
6-5-2026
N O
TE
S, L
EG
EN
D
A
B B
R
EV
IA
TI
O N
S
C0.02
APN #177-19-204-003
COUNTY OF CLARK(AVIATION)
SERENE AVENUE
(PUBLIC
APN #177-19-302-011
STATE OF NEVADA
DIV OF LANDS
3 5
PR
O
JE
CT
N
AM
E
O W
NE
R
SH
EE
T
TI
TL
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
6/5/2026
SCS-2024015
A N
TH
O
N Y
C O
M
ET
A C
O M
PL
EX
G A
TE
R
EP
LA
C
EM
EN
T
BID SET
N
EV
AD
A
AR
M
Y N
AT
IO
N
AL
G U
AR
D
NO. DATE DESCRIPTION
6-5-2026
N
DISCLAIMER NOTE
D
EM
O
LI
TI
O
N P
LA
N
C1.00
APN #177-19-204-003
COUNTY OF CLARK(AVIATION)
SERENE AVENUE
(PUBLIC
APN #177-19-302-011
STATE OF NEVADA
DIV OF LANDS
20165 2347.67
SSMH
2 2
PR
O
JE
CT
N
AM
E
O W
NE
R
SH
EE
T
TI
TL
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
6/5/2026
SCS-2024015
A N
TH
O
N Y
C O
M
ET
A C
O M
PL
EX
G A
TE
R
EP
LA
C
EM
EN
T
BID SET
N
EV
AD
A
AR
M
Y N
AT
IO
N
AL
G U
AR
D
NO. DATE DESCRIPTION
6-5-2026
N
DISCLAIMER NOTE
G R
A D
IN
G
P
LA
N
C3.00
WEST SERENE AVENUE
PROPERTY LINE
A R
V
IL
LE
S
T
02.50 02.50
02.57
02.52 TYP.AS1.02
SHEET NOTES
1. REFER TO CIVIL DRAWINGS FOR GRADING, EXISTING AND
NEW UTILITY LINES, EXISTING SITE AND EROSION CONTROL
PLAN, SURVEY CONTROL POINTS AND ALL CIVIL ASSOCIATED
SITE WORK.
2. THE CONTRACTOR SHALL FIELD SURVEY AND VERIFY EXACT
LOCATIONS OF ALL PROPERTY LINES WITH RESPECT TO THE
NEW PROPOSED WORK, TO CONFORM WITH ALL REQUIRED
SETBACKS. THE CONTRACTOR SHALL ALSO SURVEY THE
EXISTING GRADES AND TOPOGRAPHY WITH RESPECT TO ALL
THE NEW PROPOSED WORK TO CONFIRM COMPLIANCE WITH
ALL REQUIRED HEIGHT LIMITS. SURVEY SHALL BE
PERFORMED PRIOR TO ANY WORK. IF ANY DISCREPANCIES
WITH THE APPROVED PLANS ARE DISCOVERED, NOTIFY THE
ARCHITECT IMMEDIATELY.
3. THE CONTRACTOR SHALL VERIFY THE EXISTENCE AND
LOCATION OF ALL UTILITIES ON THE PROJECT SITE BEFORE
COMMENCING WORK OR ANY TRENCHING. NOTICE OF THE
PROPOSED WORK SHALL BE GIVEN TO THE APPLICABLE GAS,
ELECTRIC, TELEPHONE, SEWER AND WATER AGENCIES
HAVING JURISDICTION.
4. COORDINATE ALL SITE WORK WITH CIVIL, PLUMBING,
ELECTRICAL AND LANDSCAPE DRAWINGS. CONTRACTOR
SHALL NOTIFY ARCHITECT IN WRITING OF ANY
DISCREPANCIES PRIOR TO ANY WORK.
P R
O J E
C T
N A
M E
O W
N E
R
S H
E E
T T
IT
L
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
06/05/2026
SCS-2024015
AS1.01
A R
C H
IT
E
C T
U R
A L
S
IT
E P
L A
N
A N
T H
O N
Y C
O M
E T
A C
O M
P L
E X
G A
T E
R E
P L
A C
E M
E N
T
BID SET
N E
V A
D A
A R
M Y
N A
T
IO
N A
L G
U A
R D
SCALE: 1/64" = 1'-0"1
SITE PLAN
10' - 0" 40' - 0"
20' - 0"
80' - 0"
KEYNOTE LEGEND
NO. KEYNOTE
02.50 EXISTING DRAINAGE CHANNEL TO REMAIN PROTECTED IN
PLACE.
02.52 EXISTING PERIMETER SITE FENCING TO REMAIN PROTECTED
IN PLACE.
02.57 EXISTING HIGH REINFORCED CONCRETE SURFACE.
N
W. SERENE AVE.
02.53 02.53
02.56 02.56
26.0126.01
02.55
02.59 02.59
02.60 02.60
02.61 02.6202.62
W. SERENE AVE.
AS1.02
AS1.02
26.01
02.57
02.5002.50
02.52
02.52
26.01
03.09 03.09
02.54
26.06
05.0905.09
11.2211.22
26.05
03.10
03.13 03.13
26.07
26.07
26.08
11.23
03.09
03.09
02.63
SHEET NOTES
1. REFER TO CIVIL DRAWINGS FOR GRADING, EXISTING AND
NEW UTILITY LINES, EXISTING SITE AND EROSION CONTROL
PLAN, SURVEY CONTROL POINTS AND ALL CIVIL ASSOCIATED
SITE WORK.
2. THE CONTRACTOR SHALL FIELD SURVEY AND VERIFY EXACT
LOCATIONS OF ALL PROPERTY LINES WITH RESPECT TO THE
NEW PROPOSED WORK, TO CONFORM WITH ALL REQUIRED
SETBACKS. THE CONTRACTOR SHALL ALSO SURVEY THE
EXISTING GRADES AND TOPOGRAPHY WITH RESPECT TO ALL
THE NEW PROPOSED WORK TO CONFIRM COMPLIANCE WITH
ALL REQUIRED HEIGHT LIMITS. SURVEY SHALL BE
PERFORMED PRIOR TO ANY WORK. IF ANY DISCREPANCIES
WITH THE APPROVED PLANS ARE DISCOVERED, NOTIFY THE
ARCHITECT IMMEDIATELY.
3. THE CONTRACTOR SHALL VERIFY THE EXISTENCE AND
LOCATION OF ALL UTILITIES ON THE PROJECT SITE BEFORE
COMMENCING WORK OR ANY TRENCHING. NOTICE OF THE
PROPOSED WORK SHALL BE GIVEN TO THE APPLICABLE GAS,
ELECTRIC, TELEPHONE, SEWER AND WATER AGENCIES
HAVING JURISDICTION.
4. COORDINATE ALL SITE WORK WITH CIVIL, PLUMBING,
ELECTRICAL AND LANDSCAPE DRAWINGS. CONTRACTOR
SHALL NOTIFY ARCHITECT IN WRITING OF ANY
DISCREPANCIES PRIOR TO ANY WORK.
PLACEHOLDER 1
0' - 0"
PLACEHOLDER 1
0' - 0"
AS1.02
02.54
02.56
26.06
03.12 03.12
11.22
03.09
10.34
02.54
PLACEHOLDER 1
0' - 0"
PLACEHOLDER 1
0' - 0"
PLACEHOLDER 1
0' - 0"
10.34
11.22
03.12 26.0103.09
D E
P T
H
1/4" WIDE SAWCUT
3/4" SEALANT ROAD SURFACE
1" LONG BACKER ROD
SPACED AT 12" O.C.
18AWG XLPE VEHICLE
LOOP DETECTION
WIRE (4 TURNS)
1/4" WIDE X 2" DEEP
PAVEMENT SAWCUT
4 TURNS OF 18 AWG
XLPE VEHICLE LOOP
DETECTION WIRE
TWISTED PAIR LEAD-IN
WIRE TO ELECTRONIC
VEHICLE LOOP DETECTOR
(MIN 6 TWISTS/FOOT)
8' - 0"
6'
0"
P R
O J E
C T
N A
M E
O W
N E
R
S H
E E
T T
IT
L
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
06/05/2026
SCS-2024015
AS1.02
A R
C H
IT
E
C T
U R
A L
S
IT
E D
E T
A
IL
S
A N
T H
O N
Y C
O M
E T
A C
O M
P L
E X
G A
T E
R E
P L
A C
E M
E N
T
BID SET
N E
V A
D A
A R
M Y
N A
T
IO
N A
L G
U A
R D
SCALE: 1/8" = 1'-0"1
DEMOLITION SITE PLAN
SCALE: 1/8" = 1'-0"2
ENLARGED SITE PLAN
SCALE: 1/8" = 1'-0"3
NORTH ELEVATION
SCALE: 1/8" = 1'-0"4
SOUTH ELEVATION
KEYNOTE LEGEND
NO. KEYNOTE
02.50 EXISTING DRAINAGE CHANNEL TO REMAIN PROTECTED IN
PLACE.
02.52 EXISTING PERIMETER SITE FENCING TO REMAIN PROTECTED
IN PLACE.
02.53 EXISTING CONCRETE CURB TO BE DEMOLISHED TO
ACCOMMODATE SLIDEDRIVER CONCRETE PAD.
02.54 EXISTING MASONRY FENCE PILASTER TO REMAIN
PROTECTED IN PLACE.
02.55 EXISTING ELECTRICAL BOX, CONDUITS, AND CONCRETE
SLAB BELOW TO BE DEMOLISHED AND RELOCATED.
02.56 EXISTING METAL GATE TO BE REMOVED, MODIFIED, AND
THEN REINSTALLED TO FACILITATE MANUFACTURER
REQUIREMENTS FOR MOTORIZED GATE OPERATOR.
02.57 EXISTING HIGH REINFORCED CONCRETE SURFACE.
02.59 EXISTING 4"X4" HSS COLUMN TO BE REPOSITIONED PER
GATE MANUFACTURER'S RECOMMENDATIONS.
02.60 EXISTING EXPOSED CONDUITS TO BE RELOCATED TO
ACCOMMODATE NEW MOTORIZED OPERATOR - REFER TO
MANUFACTURER'S SPECIFICATIONS.
02.61 EXISTING SPEED BUMP TO BE DEMOLISHED.
02.62 EXISTING CONCRETE SLAB & CURB TO BE DEMOLISHED TO
ACCOMMODATE NEW POST LOCATION & UNDERGROUND
CONDUIT.
02.63 EXISTING ELECTRICAL VAULT TO REMAIN PROTECTED IN
PLACE.
03.09 NEW CONCRETE BOLLARD - REFER TO CIVIL DRAWINGS
03.10 NEW CONCRETE 6" PAD TO ACCOMMODATE MOUNTED GATE
ACCESS CONTROL DEVICE - REFER TO CIVIL DRAWINGS
03.12 NEW 20" WIDE BY 30" LENGTH BY 16" DEEP BY CONCRETE
PAD FOR NEW GATE MOTORIZED OPERATOR - REFER TO
MANUFACTURER SPECIFICATIONS
03.13 NEW CONCRETE SLAB & CURB TO MATCH EXISTING
CONDITION.
05.09 NEW LOCATION OF 4"X4" HSS SUPPORT COLUMN PER GATE
MANUFACTURER RECOMMENDATIONS. REFER TO
STRUCTURAL.
10.34 NEW GATE OPENER RAIL TO BE INSTALLED ON EXISTING
METAL GATE - REFER TO MANUFACTURERS SPECIFICATIONS
11.22 NEW SLIDEDRIVER 30F MOTORIZED GATE OPERATOR -
REFER TO MANUFACTURERS SPECIFICATIONS.
11.23 NEW IN-GROUND VEHICLE DETECTION LOOP. REFER TO
MANUFACTURER SPECIFICATIONS.
26.01 EXTERIOR UNDERGROUND CABLE BOX REFER TO
ELECTRICAL DRAWINGS.
26.05 NEW MOUNTED GATE ACCESS CONTROL BOX & CARD KEY
ENTRY DEVICE
26.06 NEW ELECTRICAL PANEL AND CONDUIT LOCATION
26.07 UNDERGROUND CONDUIT TO NEW ACCESS CONTROL BOX.
SEE ELECTRICAL DRAWINGS.
26.08 NEW CONDUITS FOR FUTURE ACCESS CONTROL BOX. SEE
ELECTRICAL DRAWINGS.
SCALE: 3/8" = 1'-0"5
GATE PROFILE
N
4' - 0" 16' - 0"
8' - 0"
32' - 0"
N
4' - 0" 16' - 0"
8' - 0"
32' - 0"
SCALE: 3" = 1'-0"7
VEHICLE DETECTION LOOPS
SCALE: 1/2" = 1'-0"6
VEHICLE DETECTION LOOPS
CONTINUOUS
CENTER LINE
ARCHITECTURAL
DIAMETER
DIAGONAL
CONTROL JOINT
ANCHOR BOLT
INTERNATIONAL BUILDING CODE
HOLLOW STRUCTURAL SECTION
EACH FACE
EACH WAY
ELEVATION
ELECTRICAL
FINISH FLOOR
INFORMATION
AND MATERIALS
CONSTRUCTION
COMPLETE JOINT PENETRATION
GENERAL STRUCTURAL NOTES
AMERICAN IRON AND STEEL
ALL COMMON SURFACES
AMERICAN CONCRETE INSTITUTE
FTG.
FT.
FLR.
HORIZ.
IBC
GA.
G.S.N.
HSS
INFO.
GAUGE
FLOOR
FOOT
HORIZONTAL
FOOTING
ELECT.
AISI
ARCH'L.
ACI
LC
DIA.
C.J.
BOT.
A.C.S.
C.J.P.
CLR.
COL.
DWG.
CONT.
DIAG.
BRG.
A.B.
E.W.
E.F.
EQ.
ELEV.
F.F.
CLEAR DIMENSION TO FACE OF
BOTTOM
DRAWING
COLUMN
BEARING
EQUAL
B.F.F. BELOW FINISH FLOOR
GIRDER TRUSSG.T.
AMERICAN INSTITUTE OF STEELAISC
AMERICAN SOCIETY FOR TESTINGASTM
REBAR
INSTITUTE
PLYWD.
LLH
MAX.
OPP.
N.T.S.
MISC.
PLF
PL.
O.D.
o.c.
MIN.
SPEC.
STD.
SIM.
PSI
PSF
REQ'D.
MECH.
MFR.
LLV
K.O.
KSI
JT.
K
LONG LEG HORIZONTAL
POUNDS PER SQUARE FOOT
OUTSIDE DIAMETER
POUNDS PER SQUARE INCH
POUNDS PER LINEAR FOOT
SPECIFICATION
MISCELLANEOUS
NOT TO SCALE
MANUFACTURER
LONG LEG VERTICAL
MAXIMUM
STANDARD
PLYWOOD
ON CENTER
OPPOSITE
REQUIRED
MINIMUM
PLATE
SIMILAR
MECHANICAL
KIPS PER SQUARE INCH
KIP (1,000 LBS)
KNOCKOUT
JOINT
GLB GLULAM BEAM
LAMINATED VENEER LUMBERLVL
PSL PARALLEL STRAND LUMBER
I.D. INSIDE DIAMETER
LSL LAMINATED STRAND LUMBER
ICC INTERNATIONAL CODE COUNCIL
B.F. BOUNDARY FASTENERS
ENGINEER OF RECORDE.O.R.
AMERICAN WELDING SOCIETYAWS
CONCRETE REINFORCING STEELCRSI
INSTITUTE RCSC RESEARCH COUNCIL ON
STRUCTURAL CONNECTIONS
SLRS SEISMIC LOAD RESISTING SYSTEM
ANCHOR RODA.R.
INSTITUTE
AMERICAN NATIONAL STANDARDS
ALTERNATEALT.
ANSI
CANTILEVEREDCANT.
ANCHOR TIE-DOWN SYSTEMATS
THRU
T.O.L.
T & B
T.O.D.
T.O.F.
T.O.S.
T.O.W.
U.N.O.
VERT.
T & G w/o
TYP.
T.O.
WT.
w/
TONGUE AND GROOVE
UNLESS NOTED OTHERWISE
TOP AND BOTTOM
TOP OF LEDGER
TOP OF WALL
TOP OF STEEL
TOP OF FOOTING
TOP OF DECK
THROUGH
VERTICAL
TYPICAL
TOP OF
WITHOUT
WEIGHT
WITH
SW SHEAR WALL
STK STACKED
EVALUATION SERVICE REPORTESR
IAPMO INTERNATIONAL ASSOCIATION OF
PLUMBING AND MECHANICAL
OFFICIALS
END POSTEP
END STUD(S)ES
KP KING POST
KS KING STUD(S)
TP TRIMMER POST
TS TRIMMER STUD(S)
P POST
STANDARD ABBREVIATIONS
A. GENERAL
THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND
COMPLETENESS NORMALLY EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE
STRUCTURAL ENGINEERS IN THIS OR SIMILAR LOCALITIES. THEY ASSUME THAT THE WORK
DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKMEN WHO
HAVE A WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND
OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT
IS (OR CAN BE) EXPLICITLY SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL USE
INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR MISCELLANEOUS WORK NOT EXPLICITLY
SHOWN.
1.
THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD
OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, TECHNIQUES, SEQUENCES, PROCEDURES, LAGGING, SHORING, BRACING,
FORM-WORK, ETC. AS REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY DURING
CONSTRUCTION. CONSTRUCTION MATERIALS SHALL BE UNIFORMLY SPREAD OUT SUCH THAT
DESIGN LIVE LOAD PER SQUARE FOOT AS NOTED HEREIN IS NOT EXCEEDED.
2.
DESIGN OF ITEMS NOT PART OF THE PRIMARY STRUCTURAL SYSTEM (SUCH AS STAIRS, RAILINGS, NON-STRUCTURAL WALLS) AND PREFABRICATED STRUCTURAL ITEMS (SUCH AS FLOOR, ROOF
TRUSSES) SHALL BE PROVIDED BY OTHERS UNLESS SPECIFICALLY NOTED ON THESE DRAWINGS.
REFER TO SUBMITTALS SECTION FOR ITEMS THAT MUST BE SUBMITTED FOR REVIEW AND FOR
SUBMITTAL REQUIREMENTS.
3.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS AND ELEVATIONS WITH ARCH'L.
DRAWINGS AND RESOLVE ANY DISCREPANCIES WITH THE ARCHITECT PRIOR TO START OF
CONSTRUCTION. CONTRACTOR SHALL ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR
ARCH'L., MECH., PLUMBING AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS AND
SUBCONTRACTORS PRIOR TO CONSTRUCTION.
4.
TYPICAL DETAILS AND NOTES SHALL APPLY, THOUGH NOT NECESSARILY INDICATED AT A
SPECIFIC LOCATION ON PLANS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL
CONFORM TO SIMILAR WORK ON THE PROJECT. DETAILS MAY SHOW ONLY ONE SIDE OF
CONNECTION OR MAY OMIT INFORMATION FOR CLARITY.
5.
NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL
NOTES AND TYPICAL DETAILS.
6.
STANDARDS AND CODE REFERENCES NOTED IN THESE CONSTRUCTION DOCUMENTS REFER TO
THE EDITIONS ADOPTED BY THE BUILDING CODE SPECIFIED IN THE BASIS FOR DESIGN.
REFERENCES NOT SPECIFICALLY ADOPTED BY SAID BUILDING CODE REFER TO THE LATEST
EDITION.
7.
ALL INSPECTIONS REQUIRED BY THE BUILDING CODES, JURISDICTION, OR THESE PLANS SHALL BE PROVIDED BY AN INDEPENDENT INSPECTION COMPANY OR THE BUILDING DEPARTMENT. SITE
VISITS BY THE ENGINEER DO NOT CONSTITUTE AN INSPECTION.
8.
B. BASIS FOR DESIGN
BUILDING CODE: INTERNATIONAL BUILDING CODE 2018 w/ LOCAL AMENDMENTS1.
99 MPH BASIC WIND SPEED (Vasd = 77 MPH)
EXPOSURE C
INTERNAL PRESSURE COEFFICIENT (GCpi) = 0.18
COMPONENT AND CLADDING WIND PRESSURE PER ASCE 7-16
WIND LOADS:2.
SITE CLASS D
SEISMIC DESIGN CATEGORY D
SS = 0.421
S1 = 0.154
SDS = 0.410
SD1 = 0.236
SEISMIC LOADS:3.
NONESNOW LOADS:4.
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR = 1.0
RISK
CATEGORY:
5.
1 1/2"/HR (BASED ON 100-YR RAIN CYCLE)RAIN INTENSITY:6.
C. FOUNDATION
FOUNDATIONS DESIGNED PER LOCAL CODES AND AMENDMENTS1.
ALLOWABLE DEAD PLUS LIVE LOAD SOIL PRESSURE = 1000 PSF.2.
FOOTING EXCAVATIONS SHALL BE CLEAN AND FREE FROM LOOSE DEBRIS, STANDING WATER, OR
UNCOMPACTED MATERIAL AT TIME OF CONCRETE PLACEMENT.
3.
TRENCHES AND EXCAVATIONS UNDER OR ADJACENT TO FOUNDATIONS SHALL BE PROPERLY
BACKFILLED AND COMPACTED.
4.
WATER PROOFING AS MAY BE REQUIRED AT SOIL FACE OF WALLS BELOW GRADE SHALL BE BY
OTHERS.
5.
D. CONCRETE
ALL CONCRETE CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH ACI 318 AND ACI
301, EXCEPT AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
1.
MIN. 28 DAY COMPRESSIVE STRENGTH, f'c, SHALL BE 4500 PSI FOR ALL CONCRETE IN CONTACT
WITH SOIL. (FOUNDATION DESIGN BASED ON 2500 PSI.)
2.
CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY, STAMPED BY AN
APPROPRIATELY LICENSED SPECIALTY ENGINEER, AND APPROVED BY THE ENGINEER OF
RECORD. MIX DESIGNS SHALL INCLUDE THE PROJECT NAME AND INDICATE THEIR USE WITHIN
THE STRUCTURE. MIX DESIGNS SHALL BE PROPORTIONED TO MINIMIZE SHRINKAGE AND HAVE
PROVEN SHRINKAGE CHARACTERISTICS OF 0. 05% OR LESS BASED ON TESTING PER ASTM C157.
3.
IF USED, EARLY STRENGTH CONCRETE SHALL BE PROPORTIONED TO DEVELOP THE 28 DAY
COMPRESSIVE STRENGTH AT THE AGE REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL
SUBMIT TEST DATA FOR REVIEW BY THE STRUCTURAL ENGINEER TO SUBSTANTIATE THE
CONCRETE STRENGTH AT THE REQUIRED AGE.
4.
ALL CONCRETE SHALL BE NORMAL WEIGHT OF 145 POUNDS PER CUBIC FOOT USING HARD ROCK
AGGREGATES CONFORMING TO ASTM C33 U.N.O. THE AGGREGATE IN THE CONCRETE SHALL BE
WELL GRADED. THE NOMINAL MAXIMUM SIZE OF THE COARSE AGGREGATE SHALL BE 1 1/2" FOR
SLABS ON GRADE (1 1/2" MIX) AND 3/4" OR LESS FOR ALL OTHER CONCRETE, U.N.O.
5.
MAX. SLUMP SHALL BE 5 INCHES (EXCEPTION: WHERE ADMIXTURES/PLASTICIZERS HAVE BEEN
INCLUDED IN MIX DESIGN TO IMPROVE WORKABILITY, SLUMP LIMIT SHALL BE BASED ON
ADMIXTURE MFR.'S RECOMMENDATIONS). MIX WATER SHALL BE CLEAN AND POTABLE.
6.
PORTLAND CEMENT SHALL CONFORM TO ASTM C150. TYPE V CEMENT SHALL BE USED FOR
CONCRETE IN CONTACT WITH EARTH. TYPE II CEMENT MAY BE USED ELSEWHERE. CEMENT
SHALL BE TYPE V WITH POZZOLAN WHERE CONCRETE IS IN CONTACT WITH SOIL CONTAINING
VERY SEVERE SULFATE EXPOSURE.
7.
FLY ASH MAY BE USED IN CONCRETE, SUBJECT TO APPROVAL BY THE ARCHITECT, PROVIDED THE
FOLLOWING CONDITIONS ARE MET:
8.
FLY ASH SHALL COMPLY WITH ASTM C618.8.1.
CEMENT CONTENT SHALL BE REDUCED A MINIMUM OF 15 PERCENT UP TO A MAXIMUM OF 25
PERCENT WHEN COMPARED TO AN EQUIVALENT CONCRETE MIX DESIGN WITHOUT FLY ASH. FLY
ASH CONTENT SHALL NOT COMPRISE MORE THAN 35 PERCENT OF THE TOTAL CEMENTITIOUS
CONTENT. THE WATER-CEMENT RATIO SHALL BE CALCULATED BASED ON THE TOTAL
CEMENTITIOUS MATERIAL IN THE MIX.
8.2.
CLASS F FLY ASH SHALL BE USED IN SULFATE RESISTANT CONCRETE WITH f'c EQUAL TO OR
GREATER THAN 4000 PSI. CLASS C FLY ASH MAY BE USED ELSEWHERE.
8.3.
WATER SOLUBLE CHLORIDE ION CONCENTRATIONS IN CONCRETE SHALL BE LIMITED PER ACI 318, SECTION 19.3.2.1, EXPOSURE CLASS "C1".
9.
CALCIUM CHLORIDE SHALL NOT BE ADDED TO THE CONCRETE MIX.10.
TIME BETWEEN CONCRETE BATCHING AND PLACEMENT SHALL BE IN ACCORDANCE WITH ASTM
C94.
11.
CONCRETE MIXING, PLACEMENT AND QUALITY SHALL BE PER ACI 318. SYSTEMATICALLY
MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED. SLABS ON GRADE NEED BE VIBRATED
ONLY AROUND AND UNDER FLOOR DUCTS OR SIMILAR ELEMENTS. REMOVE ALL DEBRIS FROM
FORMS BEFORE PLACING CONCRETE. CONCRETE SHALL NOT BE DROPPED THROUGH
REINFORCING STEEL SO AS TO CAUSE SEGREGATION OF AGGREGATES. UNCONFINED FALL OF
CONCRETE SHALL NOT EXCEED 5 FEET.
12.
PROTECT CONCRETE FROM DAMAGE OR REDUCED STRENGTH DUE TO COLD OR HOT WEATHER
IN ACCORDANCE WITH ACI 305 AND 306. CONTRACTOR SHALL TAKE SPECIAL CURING
PRECAUTIONS TO MINIMIZE SHRINKAGE CRACKING OF CONCRETE SLABS.
13.
ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCEMENT, DOWELS, BOLTS, ANCHORS,
SLEEVES, ETC., SHALL BE SECURELY POSITIONED IN THE FORMS.
14.
CONSTRUCTION JOINT SURFACES SHALL BE CLEANED AND LAITANCE REMOVED. HORIZONTAL
JOINT SURFACES SHALL BE ROUGHENED TO 1/4" AMPLITUDE. THOROUGHLY WET ALL JOINT
SURFACES AND REMOVE STANDING WATER IMMEDIATELY PRIOR TO NEW CONCRETE
PLACEMENT.
15.
CONCRETE SHALL BE CURED IN ACCORDANCE WITH ACI 318, SECTION 26.5.3.2, UNLESS
ALTERNATE METHODS HAVE BEEN APPROVED BY THE ARCHITECT AND ENGINEER. WHERE
CURING COMPOUNDS HAVE BEEN APPROVED FOR SLAB CURING, CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING COMPATIBILITY OF COMPOUNDS WITH ANTICIPATED FLOOR FINISH (e.g., RESILIENT TILE) PRIOR TO CURING COMPOUND APPLICATION.
16.
E. REINFORCING STEEL
REINFORCING STEEL SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH CURRENTLY
ADOPTED ACI 318 AND CRSI'S MANUAL OF STANDARD PRACTICE.
1.
REINFORCING STEEL SHALL CONFORM TO ASTM A615 OR ASTM A706 (A706 REQUIRED FOR ALL
REINFORCING TO BE WELDED) AND SHALL BE GRADE 60 (fy = 60 KSI) DEFORMED BARS U.N.O.
REINFORCING IN SLABS ON GRADE MAY BE GRADE 40 (fy = 40 KSI) DEFORMED BARS FOR ALL
BARS #4 AND SMALLER U.N.O. ON PLANS OR DETAILS.
2.
ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED AS "CLEAR" OR
"CLR." ARE TO CENTER OF STEEL. CLEAR COVER FOR NON-PRESTRESSED CONCRETE
REINFORCING SHALL BE AS NOTED BELOW, U.N.O. ON PLANS OR DETAILS. CLEAR COVER FOR
PRESTRESSED CONCRETE AND FOR PRECAST CONCRETE MANUFACTURED UNDER PLANT
CONTROL CONDITIONS SHALL BE PER ACI 318, SECTIONS 20.6.1.3.2 AND 20.6.1.3.3, RESPECTIVELY.
EXPOSURE CONDITION: COVER:
CAST AGAINST AND PERMANENTLY 3"
EXPOSED TO EARTH
EXPOSED TO EARTH OR WEATHER
(INCLUDING SLABS ON GRADE)
NO. 5 AND SMALLER 1 1/2"
NO. 6 AND LARGER 2"
NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND
STRUCTURAL SLABS, WALLS, JOISTS
NO. 11 AND SMALLER 3/4"
NO. 14 AND LARGER 1 1/2"
BEAMS, COLUMNS (PRIMARY REINFORCEMENT, 1 1/2"
TIES, STIRRUPS, SPIRALS)
3.
LAP SPLICES OF REINFORCING STEEL SHALL CONFORM TO TYPICAL REBAR LAP SCHEDULE U.N.O.
NO TACK WELDING OF REINFORCING BARS ALLOWED. LATEST ACI CODE AND DETAILING MANUAL
APPLY. AT WALLS AND FOOTINGS, PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH
HORIZ. BARS AT ALL CORNERS AND INTERSECTIONS U.N.O. VERT. WALL BARS SHALL BE SPLICED AT OR NEAR FLOOR LINES. SPLICE TOP BARS AT CENTER LINE OF SPAN AND BOTTOM BARS AT
THE SUPPORT IN SPANDRELS, BEAMS, GRADE BEAMS, ETC., U.N.O. ON PLANS OR DETAILS.
4.
MECHANICAL SPLICE COUPLERS SHALL HAVE CURRENT ICC APPROVAL AND SHALL BE CAPABLE
OF DEVELOPING 125% OF THE SPLICED BAR'S YIELD STRENGTH.
5.
ALL REINFORCING SHALL BE BENT COLD. BARS SHALL NOT BE UN-BENT AND RE-BENT. FIELD
BENDING OF REBAR SHALL NOT BE ALLOWED UNLESS SPECIFICALLY NOTED.
6.
WELDING OF REINFORCING BARS, METAL INSERTS, AND CONNECTIONS SHALL BE MADE ONLY AT LOCATIONS SHOWN ON PLANS OR DETAILS. SEE WELDING SECTION OF G.S.N. FOR ADDITIONAL
REQUIREMENTS.
7.
REINFORCING BAR SPACINGS SHOWN ON PLANS ARE MAX. ON CENTER DIMENSIONS. DOWEL ALL
VERT. REINFORCING TO FOUNDATION. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING
CONCRETE. MIN. CLEAR SPACING BETWEEN PARALLEL REINFORCEMENT SHALL BE THE LARGER
OF 1-1/2 TIMES NOMINAL BAR DIA. OR 1-1/3 TIMES MAX. AGGREGATE SIZE OR 1-1/2". CLEAR SPACING LIMITATION APPLIES ALSO TO CLEAR DISTANCE BETWEEN A CONTACT LAP SPLICE AND
ADJACENT SPLICES OR BARS.
8.
F. STRUCTURAL STEEL
SHAPE: STANDARD: Fy:
ROLLED WIDE FLANGE SECTIONS ASTM A992 50 KSI
OTHER STANDARD STEEL SHAPES ASTM A36 36 KSI
AND ROLLED SECTIONS
BARS AND PLATES ASTM A36 36 KSI
OR
ASTM A572, GRADE 50 (WHERE NOTED) 50 KSI
PIPES ASTM A53, GRADE B 35 KSI
HSS (RECT.) ASTM A500, GRADE C OR ASTM A1085 50 KSI
HSS (ROUND) ASTM A500, GRADE C OR ASTM A1085 46 KSI
STRUCTURAL STEEL MEMBERS SHALL CONFORM TO THE FOLLOWING STANDARDS AND
MATERIAL PROPERTIES U.N.O:
1.
ALL STRUCTURAL AND MISC. STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH
AISC 303 AND SHALL BE COMPLETED BY AN "APPROVED STEEL FABRICATOR." SHOP DRAWINGS
AND ERECTION DRAWINGS SHALL INCLUDE ALL ITEMS AS REQUIRED BY AISC 360, SECTION M1.
2.
G. STRUCTURAL STEEL WELDING
ALL WELDING OF STRUCTURAL STEEL SHALL CONFORM TO AISC 360, SECTION J2 AND FOLLOW
THE PREQUALIFIED JOINT DETAILS INCLUDED THEREIN. WELDING OF JOINTS THAT INCLUDE
REINFORCING STEEL SHALL CONFORM TO AWS D1.4.
1.
WELDING SHALL BE PERFORMED BY WELDERS HOLDING VALID CERTIFICATES AND HAVING
CURRENT EXPERIENCE IN THE TYPE OF WELD SHOWN ON THE DRAWINGS. CONTRACTOR MAY
SHOP WELD OR FIELD WELD AT HIS DISCRETION. ALL COMPLETE-JOINT-PENETRATION (CJP)
WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTING LABORATORY.
2.
ALL WELDING SHALL USE PREQUALIFIED MATCHING FILLER METALS PER AWS D1.1, TABLE 3.1, WITH A MIN. TENSILE STRENGTH OF 70 KSI U.N.O. WELDS BETWEEN REINFORCING BARS SHALL USE PREQUALIFIED MATCHING FILLER METALS PER AWS D1.4, TABLE 5.1, WITH A MIN. TENSILE STRENGTH OF 90 KSI U.N.O. (MIN. TENSILE STRENGTHS FOR FILLER METALS USED IN WELDS
BETWEEN REINFORCING BARS AND STRUCTURAL STEEL MAY BE 70 KSI).
3.
WELDING SHALL BE PERFORMED IN ACCORDANCE WITH A WELDING PROCEDURE SPECIFICATION
(WPS) AS REQUIRED IN AWS D1.1. THE WPS VARIABLES SHALL BE WITHIN THE PARAMETERS
ESTABLISHED BY THE FILLER METAL MANUFACTURER. THE WPS SHALL BE SUBMITTED TO THE
OWNER'S TESTING AGENCY FOR REVIEW PRIOR TO FABRICATION AND ERECTION. COPIES OF
THE WPS SHALL BE ON SITE AND AVAILABLE TO ALL WELDERS AND THE SPECIAL INSPECTOR.
4.
WELD LENGTHS CALLED OUT ON PLANS OR DETAILS ARE MINIMUM NET EFFECTIVE LENGTHS
U.N.O.
5.
ALL MISC. FILLET WELDS NOT NOTED, INCLUDING THOSE FOR STIFFENERS, MISC. PLATES, ETC., SHALL BE PER AISC 360, TABLE J2.4.
6.
WELDS SHALL BE SEQUENCED TO MINIMIZE RESIDUAL STRESS DUE TO WELD SHRINKAGE.7.
H. STRUCTURAL STEEL BOLTS, ANCHORS, HEADED STUDS
COMPONENT: STANDARD: Fy:
BOLTS ASTM F3125, GRADE A325 ---
OR GRADE A490 WHERE NOTED ---
NUTS ASTM A563 ---
WASHERS ASTM F436 ---
ANCHOR RODS ASTM F1554, GRADE 36 36 KSI
OR GRADE 55 WHERE NOTED 55 KSI
OR GRADE 105 WHERE NOTED 105 KSI
(GRADE 55 RODS SHALL
COMPLY WITH WELDABILITY
SUPPLEMENT S1)
WASHERS (AT ANCHOR RODS) ASTM A36 36 KSI
OR ASTM F844 (USS STANDARD) ---
(F844 WASHERS PERMITTED ONLY
FOR 3/4" DIA. RODS AT 1 1/16" MAX.
DIA. PUNCHED HOLES IN BASE PLATE
WHERE NO WELD REQ'D BETWEEN
WASHER AND BASE PLATE)
STRUCTURAL STEEL BOLTS, ANCHORS, ETC., SHALL CONFORM TO THE FOLLOWING STANDARDS
AND MATERIAL PROPERTIES U.N.O:
1.
ALL BOLTS SHALL BE INSTALLED AS SNUG-TIGHTENED JOINTS WITH THREADS EXCLUDED FROM
SHEAR PLANE (TYPE "X" CONNECTION) U.N.O. HIGH-STRENGTH BOLT ASSEMBLIES SHALL BE IN
ACCORDANCE WITH THE RCSC "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-
STRENGTH BOLTS" AND SHALL BE SNUG TIGHTENED USING ANY AISC APPROVED METHOD U.N.O.
ALL BOLTS IN SLOTTED OR OVERSIZED HOLES AND ALL HIGH-STRENGTH BOLTS SHALL BE
INSTALLED WITH HARDENED WASHERS.
2.
ALL ANCHOR RODS AT STEEL COLUMN BASE PLATES SHALL BE RODS WITH THREADS BOTH ENDS
WITH HEAVY HEX NUT FULLY THREADED ONTO EMBEDDED END. TACK WELD NUT TO ROD OR
SPOIL THREADS TO PREVENT NUT FROM BACKING OFF. ANCHOR RODS SHALL NOT BE REPAIRED, REPLACED OR FIELD-MODIFIED WITHOUT WRITTEN APPROVAL FROM THE ENGINEER OF RECORD.
3.
I. SPECIAL INSPECTION
IN ADDITION TO STANDARD INSPECTIONS BY THE BUILDING OFFICIAL REQUIRED PER IBC SECTION
110, THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS WHO SHALL PROVIDE
INSPECTIONS DURING CONSTRUCTION FOR THE TYPES OF WORK LISTED IN THIS SECTION.
1.
THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE
COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL, FOR INSPECTION OF THE
PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.
2.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE SPECIAL INSPECTOR AT LEAST
24 HOURS NOTICE PRIOR TO PERFORMING ANY WORK REQUIRING SPECIAL INSPECTION.
3.
THE SPECIAL INSPECTOR SHALL INSPECT THE WORK ASSIGNED FOR CONFORMANCE WITH THE
APPROVED CONTRACT DRAWINGS AND SPEC'S. THE SPECIAL INSPECTOR SHALL FURNISH
INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE ENGINEER OF RECORD, AND OTHER
DESIGNATED PERSONS. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION
OF THE CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, TO THE ENGINEER AND THE
BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE INSPECTOR'S
KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPEC'S AND THE APPLICABLE
CODE PROVISIONS.
4.
INSPECTORS SHALL INSPECT FROM AN APPROVED SET OF CONTRACT DRAWINGS. SHOP
DRAWINGS SHALL NOT BE USED IN LIEU OF THE APPROVED CONTRACT DRAWINGS FOR
INSPECTION PURPOSES.
5.
TYPES OF WORK TO BE INSPECTED BY THE SPECIAL INSPECTOR ARE AS FOLLOWS:6.
STEEL CONSTRUCTION SPECIAL INSPECTIONS
INSPECTION OF WELDING
INSPECTION TASKS PRIOR TO WELDING CONTINUOUS PERIODIC
WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE X -
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMBALES
AVAILABLE
X -
MATERIAL IDENTIFICATION (TYPE/GRADE) - X
WELDER IDENTIFICATION SYSTEM * - X
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
JOINT PREPARATION
DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE,
BEVEL)
CLEANLINESS (CONDITION OF STEEL SURFACES)
TACKING (TACK WELD QUALITY AND LOCATION)
BACKING TYPE AND FIT (IF APPLICABLE)
- X
CONFIGURATION AND FINISH OF ACCESS HOLES - X
FIT-UP OF FILLET WELDS
DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
CLEANLINESS (CONDITION OF STEEL SURFACES)
TACKING (TACK WELD QUALITY AND LOCATION)
- X
CHECKING WELD EQUIPMENT - X
* THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A
WELDER WHO HAS WELDED A JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL
BE THE LOW-STRESS TYPE.
INSPECTION TASKS DURING WELDING CONTINUOUS PERIODIC
USE OF QUALIFIED WELDERS - X
CONTROL AND HANDLING OF WELDING CONSUMABLES
PACKAGING
EXPOSURE CONTROL
- X
NO WELDING OVER CRACKED TACK WELDS - X
ENVIRONMENTAL CONDITIONS
WIND SPEEDS WITHIN LIMITS
PRECIPITATION AND TEMPERATURE
- X
WPS FOLLOWED
SETTINGS ON WELD EQUIPMENT
TRAVEL SPEED
SELECTED WELDING MATERIALS
SHIELDING GAS TYPE/FLOW RATE
PREHEAT APPLIED
INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
PROPER POSITION (F, V, H, OH)
INTERMIX OF FILLER METALS AVOIDED UNLESS
APPROVED
- X
WELDING TECHNIQUES
INTERPASS AND FINAL CLEANING
EACH PASS WITHIN PROFILE LIMITATIONS
EACH PASS MEETS QUALITY REQUIREMENTS
- X
SINGLE-PASS FILLET WELDS GREATER THAN 5/16" X -
MULTI-PASS FILLET WELDS X -
COMPLETE AND PARTIAL PENETRATION WELDS X -
PLUG AND SLOT WELDS X -
SINGLE-PASS FILLET WELDS EQUAL TO OR LESS THAN 5/16" - X
FLOOR AND ROOF DECK WELDS - X
INSPECTION TASKS AFTER WELDING CONTINUOUS PERIODIC
WELDS CLEANED - X
SIZE, LENGTH AND LOCATION OF WELDS X -
WELDS MUST MEET VISUAL ACCEPTANCE CRITERIA
CRACK PROHIBITION
WELD/BASE-METAL FUSION
CRATER CROSS SECTION
WELD PROFILES
WELD SIZE
UNDERCUT
POROSITY
X -
ARC STRIKES X -
k-AREA ** X -
PLACEMENT OF REINFORCING OR CONTOURING FILLET WELDS (IF
REQUIRED)
X -
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) X -
REPAIR ACTIVITIES X -
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR
MEMBER
X -
** WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN
PERFORMED IN THE k-AREA, VISUALLY INSPECT THE WEB k-AREA FOR CRACKS WITHIN 3 IN. OF
THE WELD.
6.1.
CERTIFICATE OF APPROVAL REGARDING MATERIALS AND INSPECTION OF PREFABRICATED ITEMS
SHALL BE PROVIDED IN ACCORDANCE WITH IBC SECTION 1704.
7.
J. SUBMITTALS
SHOP DRAWINGS OR REPORTS FOR THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER OF RECORD PRIOR TO FABRICATION OR CONSTRUCTION (AS
APPLICABLE) U.N.O.
REINFORCING STEEL
STRUCTURAL STEEL
1.
CONTRACTOR SHALL REVIEW AND STAMP SHOP DRAWINGS PRIOR TO SUBMITTING.
CONTRACTOR'S REVIEW SHALL CHECK FOR COMPLETENESS/COMPLIANCE WITH CONTRACT
DOCUMENTS.
2.
SHOP DRAWINGS ARE REVIEWED BY ENGINEER ONLY FOR GENERAL COMPLIANCE WITH THE
STRUCTURAL DRAWINGS. RESPONSIBILITY FOR CORRECTNESS SHALL REST WITH THE
CONTRACTOR. SHOP DRAWINGS DO NOT SUPERSEDE OR REPLACE THE CONTRACT DRAWINGS
OR SPECIFICATIONS. CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM CONTRACT DRAWINGS
AND/OR SPECIFICATIONS WILL NOT BE ACCEPTED VIA SHOP DRAWING REVIEW. ALL SUCH
MODIFICATIONS SHALL BE SUBMITTED SEPARATELY FOR ENGINEER'S REVIEW.
3.
PREFABRICATED COMPONENTS, SPECIALTY ITEMS, OR DESIGN-BUILD ELEMENTS NOTED ON THE
STRUCTURAL DRAWINGS, BUT WHICH REQUIRE THE MFR. OR SUPPLIER TO PROVIDE THE
DESIGN, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ARCHITECT AND/OR ENGINEER FOR
REVIEW AS A DEFERRED SUBMITTAL. DEFERRED SUBMITTALS REQ'D. BY THE STRUCTURAL
ENGINEER OF RECORD SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
CONCRETE MIX DESIGNS
4.
DEFERRED SUBMITTALS SHALL INCLUDE CALCULATIONS AND DRAWINGS PREPARED AND
STAMPED BY AN APPROPRIATELY LICENSED ENGINEER (SPECIALTY ENGINEER) SHOWING
LOCATION AND MAGNITUDE OF LOADS, CONFIGURATION AND SIZE OF MEMBERS, AND
COMPATIBILITY OF SUBMITTAL ITEM WITH THE PRIMARY STRUCTURAL SYSTEM.
5.
THE PURPOSE OF THE STRUCTURAL ENGINEER'S REVIEW OF DEFERRED SUBMITTALS SHALL BE
LIMITED TO DETERMINING THAT THE DRAWINGS AND CALCULATIONS HAVE BEEN PROPERLY
SEALED, THAT THE LOAD CRITERIA IS IN GENERAL CONFORMANCE WITH THE CONTRACT
DOCUMENTS AND WITH THE REFERENCED BUILDING CODE, THAT CONNECTIONS TO THE
PRIMARY STRUCTURE ARE COMPATIBLE WITH THE PRIMARY DESIGN, AND THAT THE PRIMARY
STRUCTURE IS CAPABLE OF SUPPORTING THE IMPOSED LOADS.
6.
THE STRUCTURAL ENGINEER WILL RELY UPON THE SPECIALTY ENGINEER'S SEAL AS
CERTIFICATION THAT THE ITEMS DESIGNED BY THE SPECIALTY ENGINEER COMPLY WITH THE
CRITERIA SET FORTH IN THE CONTRACT DOCUMENTS AND APPLICABLE CODES AND STANDARDS.
THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE ADEQUACY OF DESIGNS
PROVIDED BY OTHERS.
7.
FOR ALL SUBMITTALS, ANY CORRECTIONS NOTED WILL BE MARKED ON ONE (1) COPY SET ONLY
AND RETURNED. ADDITIONAL COPIES OF ANY SUBMITTAL WILL BE RETURNED UNMARKED.
CONTRACTOR SHALL BE RESPONSIBLE FOR REPRODUCING ENGINEER'S CORRECTIONS ON
ADDITIONAL COPIES REQ'D. ONE COPY SET MAY BE RETAINED FOR THE ENGINEER'S RECORDS.
ALLOW FIVE (5) TO TEN (10) WORKING DAYS FOR THE ENGINEER'S REVIEW.
8.
REFER TO APPLICABLE G.S.N. SECTIONS FOR FURTHER REQUIREMENTS SPECIFIC TO INDIVIDUAL
SUBMITTALS.
9.
5'-5"
TYP.
25'-0" MAX.
5'-5"
HSS4x4x1/2 MIN.
1 2 12
HSS4x4x1/2 MIN.
S0.01
S0.01
1 EXISTING HSS4X4 POST TO REMAIN
2 EXISTING GATE TO REMAIN.
3 NEW GATE MOTOR PER ARCH'L
4 GATE SHALL HAVE WHEEL AT END.
1 COLUMN PER PLAN
2 (3) #3 TIES AT 2" o.c.
3 (8) #5 VERT. EVENLY SPACED. PROVIDE
STANDARD HOOK AT TOP
4 #3 TIES AT 12" o.c.
5 1'-0" MIN.
6 1/2"x10"x0'-10" BASEPLATE w/ (4) 3/4" DIA. A.R. w/ 7 1/2" EMBEDMENT
8 CONSTRUCTION JOINT
9 CONCRETE SLAB ON GRADE PER
ARCH'L
DIA.
1'-6"
'-9
C L
R
C L
R .5
SF01-26A 200519
7 1/4" OR MIN. WELD SIZE PER AISC 360,
TABLE J24, WHICHEVER IS GREATER
SEE TABLE 14-2 OF AISC STEEL
CONSTRUCTION MANUAL FOR MAX.
ANCHOR ROD HOLE DIA. IN BASE
PLATE AND MIN. WASHER SIZE/THICKNESS.
HOLE DIA. IN WASHERS SHALL BE 1/16"
GREATER THAN ANCHOR ROD DIA.
A.
EQ EQ
TYP TYP 7
/2
M
IN
3" CLR.
1645 Village Center Circle, Suite 10 Las Vegas, NV 89134 phone (702) 933-7000 NV@wrightengineers.com wrightengineers.com
ENGIN EEER D
IN THE USA
Atlanta | Dallas | Denver | Las Vegas | Orange County | Phoenix | Salt Lake City
P R
O J E
C T
N A
M E
O W
N E
R
S H
E E
T T
IT
L
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
06/05/2026
SNL250797
S0.01
G E
N E
R A
L S
T R
U C
T U
R A
L N
O T
E S
A
B B
R E
V
IA
T
IO
N S
P
L A
N A
N D
D E
T A
IL
S
A N
T H
O N
Y C
O M
E T
A C
O M
P L
E X
G A
T E
R E
P L
A C
E M
E N
T
BID SET
N E
V A
D A
A R
M Y
N A
T
IO
N A
L G
U A
R D
GENERAL STRUCTURAL NOTES
SCALE: 1/8" = 1'-0"1
ENLARGED GATE PLAN
NO SCALE
COLUMN AT CAISSON FOOTING01
05/28/2026
Digital Signature www.tjkengineers.com tjk consulting engineers, inc.
8728 Spanish Ridge Avenue, Las Vegas, NV 89148
P: 702.871.3621
Suite 100
N O T F
R
C
N S
TR
U C
TIO
N
P R
O J E
C T
N A
M E
O W
N E
R
S H
E E
T T
IT
L
E
151 E. Warm Springs Rd.
Las Vegas, NV 89119 702-435-1150 www.simpsoncoulter.com
REVISIONS
CONSULTANT
STAMP
DATE
PROJECT NO.
SUBMITTAL
SHEET NO.
Simpson Coulter | STUDIO
TJK# 24110
06/05/2026
SCS-2024015
E0.01
G E
N E
R A
L I N
F O
R M
A T
IO
N
A N
T H
O N
Y C
O M
E T
A C
O M
P L
E X
G A
T E
R E
P L
A C
E M
E N
T
BID SET
N E
V A
D A
A R
M Y
N A
T
IO
N A
L G
U A
R D
GENERAL NOTES
1. WORK ASSOCIATED WITH THE ELECTRICAL CONTRACTOR'S TRADE SHALL BE SHOWN ON
OTHER DISCIPLINE'S DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL
DRAWINGS ASSOCIATED WITH THIS PROJECT, INCLUDING BUT NOT LIMITED TO
ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, AND LOW VOLTAGE. ANY ADDITIONAL
COST RESULTING FROM THE FAILURE TO INCLUDE ALL SUCH ITEMS SHALL BE INCURRED
BY THE CONTRACTOR.
2. THE CONTRACTOR IS RESPONSIBLE FOR FIELD COORDINATING WITH OTHER TRADES
PRIOR TO ROUGH-IN TO AVOID INSTALLATION CONFLICTS. EQUIPMENT AND DEVICE
LOCATION ADJUSTMENTS IN ANY DIRECTION FROM THAT OF WHAT IS SHOWN ON
DRAWINGS SHALL BE MADE AT NO ADDITIONAL COST TO THE PROJECT.
3. THE INTENT OF THE PROJECT DRAWINGS AND SPECIFICATIONS IS TO ESTABLISH A
STANDARD OF QUALITY. THE ENGINEER RESERVES THE RIGHT TO APPROVE OR
DISAPPROVE INSTALLATION METHODS AND MATERIALS PROPOSED BY THE CONTRACTOR
WHICH DEVIATE FROM THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL INCUR ALL
ADDITIONAL EXPENSES ASSOCIATED WITH REVISIONS TO PROJECT DRAWINGS OR
SPECIFICATIONS WHERE REQUIRED TO ACCOMMODATE THE CONTRACTOR'S PROPOSED
CHANGES. THE PROJECT AS-BUILT DRAWINGS SHALL BE UPDATED TO ACCURATELY
REFLECT ANY INSTALLATIONS THAT DEVIATE FROM THE ORIGINAL CONSTRUCTION
DRAWING SET.
4. ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE NECA STANDARDS AND
TO THE SATISFACTION OF THE ARCHITECT, AND ENGINEER.
5. THE CONTRACTOR SHALL VISIT THE JOB SITE TO VERIFY EXISTING CONDITIONS PRIOR TO
SUBMITTING BID (WHERE APPLICABLE).
6. DRAWINGS ARE BASED ON THE MOST ACCURATE INFORMATION AVAILABLE DURING THE
PLANNING AND DESIGN PHASE OF THE PROJECT. HOWEVER, THE CONTRACTOR IS
RESPONSIBLE FOR VERIFYING FINAL LOCATIONS OF ALL EQUIPMENT, DEVICES (INCLUDING
LIGHTING FIXTURES AND MECHANICAL EQUIPMENT) WITH THE ARCHITECT AND ENGINEER
PRIOR TO ROUGH-IN. EQUIPMENT AND DEVICE LOCATION ADJUSTMENTS IN ANY
DIRECTION FROM THAT OF WHAT IS SHOWN ON THE DRAWINGS, SHALL BE MADE AT NO
ADDITIONAL COST TO THE PROJECT.
7. DO NOT SCALE THE ELECTRICAL DRAWINGS. FIELD VERIFY LOCATIONS AND DIMENSIONS
PRIOR TO ROUGH-IN.
8. ROUTING OF RACEWAYS WHERE SHOWN ON DRAWINGS IS DIAGRAMMATIC. FINAL
ROUTING OF RACEWAYS SHALL BE DETERMINED BY THE CONTRACTOR BASED ON ACTUAL
FIELD CONDITIONS.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING AND PATCHING SURFACES AS
REQUIRED WHERE NEW DEVICES OR EQUIPMENT WILL BE INSTALLED. PATCHING SHALL
MATCH EXISTING ADJACENT SURFACES. PATCHING MATERIAL AND FINISH TYPE SHALL BE
APPROVED BY THE ARCHITECT.
10. THE CONTRACTOR SHALL PROVIDE SHORT CIRCUIT AND OVERCURRENT PROTECTION FOR
MECHANICAL EQUIPMENT PER THE EQUIPMENT NAMEPLATE AND MANUFACTURER'S
RECOMMENDATIONS. SHOULD THE ACTUAL EQUIPMENT BEING PROVIDED DIFFER FROM
INFORMATION SHOWN ON THE ELECTRICAL DRAWINGS, THE CONTRACTOR SHALL NOTIFY
THE ENGINEER OF RECORD IN WRITING (PRIOR TO THE PURCHASING AND INSTALLING)
FOR FURTHER DIRECTION.
11. PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS SHALL BE SEALED TO
MAINTAIN ORIGINAL RATING. PROVIDE FIRE RATED CAULKING FOR CONDUIT
PENETRATIONS THAT PENETRATE RATED WALLS, AND FIRE RATED PUTTY PADS OR OTHER
APPROVED MEANS FOR RECESSED BOXES THAT PENETRATE RATED WALLS.
12. WHERE SHUT-DOWNS OF EXISTING FACILITY POWER SYSTEMS ARE REQUIRED, THE
CONTRACTOR SHALL SUBMIT A REQUEST IN WRITING TO THE ARCHITECT AND ENGINEER A
MINIMUM OF 5 WORKING DAYS IN ADVANCE.
ABBREVIATIONS
A AMPERE
AL ALUMINUM
AFCI ARC FAULT CURRENT INTERRUPTER
AIC AMPERE INTERRUPTING CAPACITY
ANSI AMERICAN NATIONAL STANDARD
INSTITUTE
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CLG CEILING
(E) EXISTING
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
GFCI GROUND-FAULT CIRCUIT
INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL
(CONDUIT)
HP HORSEPOWER
HVAC HEATING, VENTILATION AND AIR
CONDITIONING
J-BOX JUNCTION BOX
K KELVIN(S)
KAIC KILO AMPERE INTERRUPTING
CAPACITY
KV KILOVOLT(S)
KVA KILOVOLT AMPERE
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT(S)
KWH KILOWATT HOUR(S)
LTG LIGHT, LIGHTING
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
MCS MOLDED CASE SWITCH
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MOP MAXIMUM OVERLOAD PROTECTION
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NIC NOT IN CONTRACT
OH OVERHEAD
PH, Ø PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
RCPT RECEPTACLE
REF REFERENCE
RM ROOM
SF SQUARE FOOT
SPEC SPECIFICATION
(SPLT-CKT) SPLIT CIRCUIT
SWBD SWITCHBOARD
TBD TO BE DETERMINED
T-STAT THERMOSTAT
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
USB UNIVERSAL SERIAL BUS
V VOLT(S)
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATT(S)
WP WEATHER PROOF
XFMR TRANSFORMER
FT, ' FEET
IN, " INCH(ES)
NO., # NUMBER
20 SINGLE POLE CIRCUIT BREAKER
20/2 TWO POLE CIRCUIT BREAKER
20/3 THREE POLE CIRCUIT BREAKER
20G GFCI CIRCUIT BREAKER
20AG ARC FAULT GFCI COMBINATION
CIRCUIT BREAKER
20C CONTROLLABLE CIRCUIT BREAKER
CO CONDUIT ONLY WITH PULL STRING
SCCR SHORT CIRCUIT CURRENT RATING
NECA NATIONAL ELECTRIC
CONTRACTORS ASSOCIATION
WP
F
0-00"
0-00"
0-00"
0-00"
0-00"
P
PP
JJ J
LEGEND
NOTE: REFER TO ELECTRICAL PLANS AND SPECIFICATIONS FOR MOUNTING HEIGHTS.
NOT ALL SYMBOLS MAY BE USED.
POWER
EXISTING WORK SHOWN WITH SOLID LIGHTWEIGHT LINES
NEW WORK SHOWN WITH SOLID HEAVYWEIGHT LINES
EXISTING BELOW FLOOR / GRADE WORK SHOWN WITH DASHED
LIGHTWEIGHT LINES
NEW BELOW FLOOR / GRADE WORK SHOWN WITH DASHED
HEAVYWEIGHT LINES
DEMO WORK SHOWN WITH DASHED HEAVYWEIGHT LINES
SHEET NOTE DESIGNATION
REVISION DELTA TAG
MECHANICAL EQUIPMENT CROSS REFERENCE
DIAGRAM…