2025_55140_Exhibit_A_PlanSet_Part2.pdf

PDF 2 MB Posted

Attached to
2025-55140 Tolmie Lift Station Improvements
Solicitation number
2025-55140
Issued by
Adams County, Asotin County, Benton County, Chelan County, Clallam County, Clark County, Columbia County, Cowlitz County, Douglas County, Ferry County, Franklin County, Garfield County, Grant County, Grays Harbor County, Island County, Jefferson County, King County, Kitsap County, Kittitas County, Klickitat County, Lewis County, Lincoln County, Mason County, Okanogan County, Pacific County, Pend Oreille County, Pierce County, San Juan County, Skagit County, Skamania County, Snohomish County, Spokane County, Stevens County, Thurston County, Wahkiakum County, Walla Walla County, Whatcom County, Whitman County, Yakima County, Asotin City, Clarkston City, Clarkston Heights-Vineland CDP, West Clarkston-Highland CDP, Benton City, Chelan City, Chelan Falls CDP, Clallam Bay CDP, Lewisville CDP, Rock Island City, Pacific Beach CDP, Whidbey Island Station CDP, Mercer Island City, Pacific City, Bainbridge Island City, Kingston CDP, Kitsap Lake CDP, Kittitas City, Klickitat CDP, Okanogan City, Anderson Island CDP, Fort Lewis CDP, Fox Island CDP, Herron Island CDP, Ketron Island CDP, North Fort Lewis CDP, Raft Island CDP, Stevenson City, Hat Island CDP, Lake Stevens City, Snohomish City, Spokane City, Spokane Valley City, Puget Island CDP, Garfield Town, Yakima City, Washington

About this file

This document is a General Notes specification sheet for the Victaulic AWWA Grooved Piping System, prepared by the Washington State Parks and Recreation Commission for the Tolmie State Park Wastewater Lift Station Retrofit project. The specification provides detailed technical requirements for piping materials, including ductile iron pipes, mechanical couplings, fittings, and valves, with a focus on Victaulic brand products. The document outlines precise technical standards for pipe installation, including specific references to ASTM, ANSI, and AWWA standards, and details the requirements for pipe materials, coupling configurations, valve types, and installation procedures.

The specification emphasizes quality assurance by requiring that all grooved joint components be from a single manufacturer and that a Victaulic factory-trained representative provide on-site training for installation personnel. The technical requirements cover a comprehensive range of product specifications, including pipe classes (minimum Class 53), coupling materials (ductile iron with synthetic rubber gaskets), valve pressure ratings, and specific performance characteristics for different valve types such as plug valves, check valves, and gate valves. The document is part of a 100% design plan set marked as preliminary and intended for review, indicating it is a detailed technical specification for the lift station retrofit project at Tolmie State Park.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL

NOTES

G-04

NO SCALE

40525-070_G-03_GENERAL NOTES

PARKS FILE#

SCALE

PARKS

STATE

RECREATION

WASHINGTON

COMMISSION

AND

R E V I S I O

N S

CHECKED (HDQTS.)

REGISTERED STAMP

DESIGNED

CHECKED (FIELD)

DRAWN

ACTION BY

DATE

N O

CAD NO.

A P P

I N

T

D A T E

04/21/23JP/CS

04/21/23PCB

TOLMIE

STATE PARK

WASTEWATER

LIFT STATION

RETROFIT

AE 123-168

100% DESIGN PLAN SET (REVIEW ONLY)

SHEET OF 24

PRELIMINARY

VICTAULIC AWWA GROOVED PIPING SYSTEM:

1. GENERAL:

1.1. SECTION INCLUDES:

1.1.1. GENERAL.

1.1.2. MATERIALS:

1.1.2.1.PIPE.

1.1.2.2.VICTAULIC COUPLINGS.

1.1.2.3.VICTAULIC FITTINGS.

1.1.2.4.VICTAULIC VALVES.

1.1.3. EXECUTION.

1.1. SUBMITTALS

1.1.1. AWWA GROOVED PIPING PRODUCTS SHALL BE SHOWN ON DRAWINGS AND PRODUCT SUBMITTALS AND SHALL BE SPECIFICALLY

IDENTIFIED WITH THE APPLICABLE VICTAULIC SERIES OR STYLE DESIGNATION.

1.2. REFERENCES:

1.2.1. AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)

1.2.1.1.ASTM A-126 - GRAY IRON CASTINGS FOR VALVES, FLANGES, AND PIPE FITTING

1.2.1.2.ASTM A-183 - CARBON STEEL TRACK BOLTS AND NUTS

1.2.1.3.ASTM A-449 - QUENCHED AND TEMPERED STEEL BOLTS AND STUDS

1.2.1.4.ASTM A-536 - DUCTILE IRON CASTINGS

1.2.1.5.ASTM B-633 - ELECTRODEPOSITED COATINGS OF ZINC ON IRON AND STEEL

1.2.1.6.ASTM D2000 - STANDARD CLASSIFICATION SYSTEM FOR RUBBER PRODUCTS IN AUTOMOTIVE APPLICATIONS

1.2.2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI):

1.2.2.1.ANSI A21.10 - DUCTILE AND GRAY IRON FITTINGS

1.2.3. AMERICAN WATER WORKS ASSOCIATION

1.2.3.1.AWWA C-110 - DUCTILE AND GRAY IRON FITTINGS

1.2.3.2.AWWA C-153 - DUCTILE IRON COMPACT FITTINGS 3 IN. THROUGH 24 IN. AND 54 IN. THROUGH 65 IN., FOR WATER SERVICE.

1.2.3.3.AWWA C-606 - GROOVED AND SHOULDERED JOINTS.

1.2.4. QUALITY ASSURANCE:

1.2.4.1.ALL GROOVED JOINT COUPLINGS, FITTINGS, VALVES, AND SPECIALTIES SHALL BE THE PRODUCTS OF A SINGLE MANUFACTURER.

2.MATERIALS:

2.1. PIPE: AWWA DUCTILE IRON PIPE, MINIMUM CLASS 53, GROOVED IN ACCORDANCE WITH AWWA C606. RIGID RADIUS GROOVE DIMENSIONS

SHALL BE UTILIZED WHERE FLEXIBILITY IS NEITHER REQUIRED NOR DESIRED. PIPE ENDS SHALL BE FACTORY GROOVED. .

2.2. MECHANICAL COUPLINGS:

2.2.1. VICTAULIC COUPLINGS: MANUFACTURED IN TWO OR MORE SEGMENTS OF CAST DUCTILE IRON, CONFORMING TO A-536, GRADE

65-45-12. GASKETS SHALL BE PRESSURE-RESPONSIVE SYNTHETIC RUBBER, FLUSHSEAL® TYPE. MECHANICAL COUPLING BOLTS SHALL BE

ZINC PLATED (ASTM B-633) HEAT TREATED CARBON STEEL TRACK HEAD CONFORMING TO PHYSICAL PROPERTIES OF ASTM A-183, MINIMUM TENSILE STRENGTH 110,000 PSI (758450 KPA) AS PROVIDED STANDARD VICTAULIC. VICTAULIC STYLE 31.

2.2.2. TRANSITION COUPLINGS: FOR TRANSITION BETWEEN IPS STEEL AND AWWA DUCTILE IRON SIZED PIPE. HOUSINGS CAST WITH

OFFSETTING, ANGLE-PATTERN, BOLT PADS. VICTAULIC STYLE 307.

2.2.3. COUPLING GASKETS: SYNTHETIC RUBBER, FLUSHSEAL® CONFIGURATION, CONFORMING TO AWWA PIPE OUTSIDE DIAMETER AND

COUPLING HOUSING, MANUFACTURED OF ELASTOMERS AS DESIGNATED IN ASTM D-2000.

2.2.3.1.REFERENCE SHALL ALWAYS BE MADE TO THE LATEST PUBLISHED SELECTION GUIDE FOR VICTAULIC GASKETS FOR PROPER GASKET

SELECTION FOR THE INTENDED SERVICE.

2.2.4. FLANGE ADAPTERS: FOR USE WITH AWWA GROOVED END PIPE AND FITTINGS, FOR MATING TO ANSI CLASS 125 FLANGED

COMPONENTS. VICTAULIC STYLE 341.

2.3. VICTAULIC GROOVED END FITTINGS FOR AWWA DUCTILE IRON PIPE: FITTINGS SHALL BE CAST OF DUCTILE IRON CONFORMING TO A-536, GRADE 65-45-12. FITTINGS CONFORM TO ANSI A21.10/AWWA C-110 FOR CENTER-TO-END DIMENSIONS AND WALL THICKNESS, AND

AWWA C-153 FOR WALL THICKNESS. GROOVED ENDS SHALL CONFORM TO AWWA C606.

2.4. VICTAULIC GROOVED END VALVES FOR AWWA DUCTILE IRON PIPE:

2.4.1. PLUG VALVES: 175 PSI (2”(DN50) THROUGH 12”(DN300)) AND 150 PSI (14”(DN350) THROUGH 18”(DN450)) BUBBLE-TIGHT, BI-DIRECTIONAL

SEALING. DUCTILE IRON BODY CONFORMING TO ASTM A-536, GRADE 65-45-12, SYNTHETIC RUBBER ENCAPSULATED DUCTILE IRON

PLUG, GRADE TO SUIT THE INTENDED SERVICE, WITH WELDED-IN NICKEL SEAT. VICTAULIC SERIES 365.

2.4.1. AWWA CHECK VALVES: 175 PSI WORKING PRESSURE, CAST IRON BODY CONFORMING TO ASTM A-126, CLASS B, BRONZE DISC

CONFORMING TO ASTM B-584 OR DUCTILE IRON CONFORMING TO ASTM A-536, GRADE 65-45-12, DUCTILE IRON HINGE, STAINLESS

STEEL SHAFT, BRONZE SEAT. SPRING AND LEVER, WEIGHT AND LEVER, OR LEVER WITH AIR CUSHION ACTUATOR. VICTAULIC SERIES

317.

2.4.2. OS&Y GATE VALVES: 250 PSI (1725 KPA), OGS GROOVED ENDS TO 12” (DN300) OR AGS GROOVED ENDS FOR 14” AND 16” (DN350 AND

DN400) SIZES; FOR OPERATING TEMPERATURES TO +180 DEG F (+82 DEG C). DUCTILE IRON BODY, DISC, YOKE, AND HANDWHEEL

CONFORMING TO ASTM A-536, ASTM D2000 COMPLIANT EPDM DISC COATING; ASTM B150 ALUMINUM BRONZE RISING STEM; FUSION

BONDED EPOXY COATED BODY AND BONNET CONFORMING TO AWWA C550; EPDM O-RING STEM SEALS AND BODY GASKET.

VICTAULIC SERIES 371 AND W371.

2.4.3. NON-RISING STEM GATE VALVES: 250 PSI (1725 KPA), OGS GROOVED ENDS TO 12” (DN300) OR AGS GROOVED ENDS

FOR 14” AND 16” (DN350 AND DN400) SIZES; FOR OPERATING TEMPERATURES TO +180 DEG F (+82 DEG C). DUCTILE IRON

BODY, DISC, YOKE, AND HANDWHEEL CONFORMING TO ASTM A-536, ASTM D2000 COMPLIANT EPDM DISC COATING; ASTM B-150

ALUMINUM BRONZE NON-RISING STEM; FUSION BONDED EPOXY COATED BODY AND BONNET CONFORMING TO AWWA C550; EPDM

O-RING STEM STEALS AND BODY GASKET. VICTAULIC SERIES 372 AND W372.

3. EXECUTION:

3.1. INSTALLATION:

3.1.1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S LATEST RECOMMENDATIONS. FOLLOW THE INSTRUCTIONS LISTED IN THE LATEST

VICTAULIC I-300 ASSEMBLY MANUAL.

3.1.2. PIPE ENDS SHALL BE CLEAN AND FREE FROM INDENTATIONS AND PROJECTIONS IN THE AREA FROM PIPE END TO GROOVE.

3.1.3. HE GASKET STYLE AND ELASTOMERIC MATERIAL (GRADE) SHALL BE VERIFIED AS SUITABLE FOR THE INTENDED SERVICE AS SPECIFIED.

3.2. TRAINING:

3.2.1. A VICTAULIC FACTORY TRAINED FIELD REPRESENTATIVE (DIRECT EMPLOYEE) SHALL PROVIDE ON-SITE TRAINING FOR CONTRACTOR'S

FIELD PERSONNEL IN THE PROPER USE OF GROOVING TOOLS, APPLICATION OF GROOVE, AND INSTALLATION OF GROOVED PIPING

PRODUCTS.

3.3. APPLICATION:

3.3.1. VICTAULIC GROOVED PRODUCTS MAY BE USED IN LIEU OF FLANGED COUPLINGS AND FITTINGS IN APPLICABLE PIPING

SYSTEMS 3”(DN75) THROUGH 36”(DN900). GASKETS USED ON POTABLE WATER SYSTEMS SHALL BE UL CLASSIFIED IN ACCORDANCE

WITH ANSI/NSF-61.

3.3.2. VICTAULIC'S FACTORY TRAINED REPRESENTATIVE SHALL PERIODICALLY VISIT THE JOB SITE AND REVIEW INSTALLATION. CONTRACTOR

SHALL REMOVE AND REPLACE ANY IMPROPERLY INSTALLED PRODUCTS.

Sheets and Views
G-04 GENERAL NOTES

File details come from the government source that posted it. Updated .