2025 11 13 Civil Site Plan.pdf
PDF 7 MB Posted
- Attached to
- White Marsh Park Comfort Station
- Solicitation number
- BPM054342
- Issued by
- Queen Anne's County, Maryland
About this file
This is a Civil Site Plan document prepared for Queen Anne's County Department of Parks and Recreation for the construction of a comfort station at White Marsh Park in Centreville, Maryland. The project encompasses design execution, permit acquisition, site work, stormwater facilities, and construction of a 900-square-foot split-face concrete masonry unit comfort station with peripheral improvements. Electronic bids are due January 15, 2026 at 1:00 p.m., with a pre-bid meeting and site visit scheduled for December 17, 2025 at 9:00 a.m. Questions must be submitted by December 31, 2025 at 4:00 p.m. The contract will be awarded to the lowest responsive, responsible bidder, with contract time established at 180 calendar days from Notice to Proceed to Substantial Completion, plus an additional 30 calendar days to Final Completion. Bids must remain open for 60 days following opening.
The contractor is responsible for obtaining all building and trade permits within 21 days of Notice to Proceed, with permit review delays exceeding 30 calendar days considered excusable but non-compensable. Liquidated damages are assessed at $500 per calendar day for delays beyond completion dates. Bid security of 5 percent of total bid is required, along with Performance and Payment Bonds of 100 percent of contract price for contracts exceeding $100,000. Comprehensive General Liability Insurance with a minimum of $1 million per occurrence and $2 million aggregate is required. The project is not federally funded and therefore not subject to Davis-Bacon Act prevailing wage requirements. Local vendor preference does not apply as not all project funds are County funds. The contractor supplies temporary power until permanent transformer installation, while the County coordinates and pays all Delmarva Power transformer service fees. Specific material requirements include Schedule 40 PVC grey electrical conduit, Kawneer 601T system windows or equivalent, aluminum storefront doors with Vitro Solarban 60 glazing, standing seam metal roof in Hartford Green finish, duplex grinder pump system, and Contech A-2000 corrugated PVC dual-wall culvert pipe.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF PURPOSE AND INTENT
THIS SITE PLAN HAS BEEN PREPARED TO SERVICE AS THE SITE-RELATED COMPONENT
OF BID DOCUMENTS FOR THE PROPOSED PROJECT AND TO ACCOMPANY A PUBLIC
SERVICE WAIVER APPLICATION FOR THE PROJECT. THE PROJECT CONSISTS OF A 716
SQUARE FOOT PUBLIC COMFORT STATION BUILDING WITH FOUR PARKING SPACES
PROVIDED IN A NEW PARKING AREA. THE BUILDING IS CONSISTENT WITH THE EXISTING
LAND USE AS A PUBLIC PARK. PEDESTRIAN SAFETY IS ACCOMMODATED WITH
PROPOSED SIGNAGE, STRIPED CROSSWALK, AND PERVIOUS WOODCHIP PATH. NOTE
THAT POSSIBLE FUTURE AMENITIES FOR PARKING, FOOD TRUCK(S), AND A
CONCESSION STAND ARE SHOWN CONCEPTUALLY FOR REFERENCE AND ARE NOT
INCLUDED ON THE PUBLIC SERVICE WAIVER OR THE PROPOSED CONSTRUCTION
PROJECT.
SHEET NO.:
FILE NO.:
DATE
SEAL
NOVEMBER 13, 2025
25-012
FOR:
TAX MAP 36D, GRID 2, PARCEL 4
PREPARED FOR: QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS
3rd ELECTION DISTRICT, QUEEN ANNE'S COUNTY, MARYLAND
WHITE MARSH PARK
5OF
P L O
T T
E D
N o v p m
V
I
N
C
I
T
O
M N I
A
V
E
R
I
T
A
S
Q
U
E
E
N
A
N
N E
S
C
O
U
N
T
Y
SEL
D M y
D o c u m e n t s D u m b
H o m e P r o j e c t s
Q
A C
C o m f o r t
S t a t i o n C
A D
S i t e
P l a n d w g T a b T
I
REVISIONS
DATEREV. # DESCRIPTION
FOLDER REF:
APPROVED BY:
SCALE:
DATE:
JOB NUMBER:
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE
APPROVED BY:
DATE
DEPT. OF PUBLIC WORKS
SOIL CONSERVATION SERVICE
QA Co.
QA Co. Pr of es si on al
C er tif ic at io n.
I he re by c er tif y th at th es e do cu m en ts w er e pr ep ar ed o r a pp ro ve d by m e, a nd th at I am a d ul y lic en se d un de r t he la w s o f t he
S ta te o f M ar yl an d, L ic en se N o.
, E xp ir at io n D at e:
P r o f e s s i o n a l
E n g i n e e r
COMFORT STATION
PO Box 103
Centreville, MD 21617
301-529-2368 compacthomeplans.com steve@select-engineer.com
COPYRIGHT 2025
C e c t
Engineering
25-006 FM P&P.dwg
APPROVED BY:
DATE
APPROVED BY:
DATE
1" = 300'
SEL
SEL
TITLE SHEET & EXISTING CONDITIONS PLAN
WHITE MARSH PARK COMFORT STATION
FOR THE
SITE AND UTILITY PLANS
NORTH
OWNER
COUNTY COMMISSIONERS OF
QUEEN ANNE'S COUNTY
107 N LIBERTY ST
CENTREVILLE, MD 21617
PHONE: (410) 758-4098
DEVELOPER
QUEEN ANNE'S COUNTY
DEPARTMENT OF PARKS AND REC
1945 4-H PARK RD
CENTREVILLE, MD 21617
(410) 758-0835
PREMISE ADDRESS
200 BLOOMFIELD FARM LN
CENTREVILLE, MD 21617
SITE NOTES
1. PROPERTY SHOWN HEREON IS DESIGNATED AS TAX MAP 36D, GRID 2, PARCEL 4.
2. DEED REFERENCE: 1568/609. AND PLAT REFERENCE:
3. THIS SITE IS ZONED AG - AGRICULTURAL. PER 18:1-14 E.(2)(c), REQUIRED SETBACKS ARE:
FRONT = 35', ARTERIAL = 75' (MD RTE 213), SIDE = 10', REAR = 10'.
4. EXISTING AND PROPOSED USE: QUEEN ANNE'S COUNTY PUBLIC PARK.
5. PROPERTY LINES SHOWN HEREON ARE BASED ON AN EXISTING CONDITIONS PLAN
PREPARED BY LANE ENGINEERIN,G INC. AND PROVIDED BY THE DEVELOPER IN MAY 2025.
6. TOPOGRAPHY WAS OBTAINED FROM THE PREVIOUSLY DESCRIBED EXISTING CONDTIONS
PLAN AND WAS SUPPLEMENTED AS NEEDED BY QUEEN ANNE'S COUNTY GRAPHIC
INFORMATION SYSTEMS LIDAR CONTOURS.
7. THE PROPERTY IS NOT LOCATED IN A FLOODPLAIN ACCORDING TO THE FEDERAL
EMERGENCY MANAGEMENT AGENCY'S F.I.R.M. MAP FOR QUEEN ANNE'S COUNTY, PANEL
NO. 24035C0210D, DATED: 11/05/2014. THE PROPERTY IS LOCATED IN ZONE X, AREA OF
MINIMAL FLOODING.
8. THE PROPERTY IS NOT LOCATED WITHIN THE CHESAPEAKE BAY CRITICAL AREA.
9. THE PROPERTY DOES NOT CONTAIN MAPPED TIDAL OR NONTIDAL WETLAND RESOURCES
AS INDICATED BY THE QAC PROPERTY VIEWER ON MAY 13, 2025.
10. THERE ARE EXISTING FOREST AREAS ON THE PROPERTY, BUT NO FOREST FALLS WITHIN
THE PROPOSED LIMIT OF DISTURBANCE.
11. THE SITE AMENITIES WILL CONTINUE TO BE SERVED BY A PROPOSED PRIVATE WATER
WELLS, WITH THE PUBLIC SEWER (NEW IN 2025) GRADUALLY REPLACING THE EXISTING
SEPTIC SYSTEMS. THE PROPOSED COMFORT STATION WILL BE SERVICED BY A NEW WELL
AND WILL BE CONNECTED TO PUBLIC SEWER.
12. A PORTION OF THE PROPERTY IS LOCATED WITHIN A SENSITIVE SPECIES PROJECT AREA
ACCORDING TO THE QUEEN ANNE'S COUNTY PROPERTY VIEWER ON 5/13/2025. THE LIMIT
OF DISTURBANCE DOES NOT IMPACT THE SENSITIVE SPECIES AREA.
13. THE LIMIT OF DISTURBANCE FOR THE PROPOSED COMFORT STATION IS LESS THAN 5,000
SQUARE FEET. AS A RESULT, A SEDIMENT AN ENGINEERED EROSION CONTROL PLAN AND
A STORMWATER MANAGEMENT PLAN ARE NOT REQUIRED. SEE GENERAL NOTE #11
BELOW REGARDING UTILITY INSTALLATION.
14. CONSTRUCTION ACTIVITIES ARE ROUGHLY 950 FEET FROM THE CLOSEST PROPERTY LINE.
VICINITY MAP
SCALE: 1" = 2000'
SITE
ENGINEER
SELECT ENGINEERING
PO BOX 103
CENTREVILLE, MD 21617
PHONE: (301) 529-2368
200 BLOOMFIELD FARM LANE, CENTREVILLE, MARYLAND
D
R
T
O
C
H
U
R
I
L
L
S
H
O
P
R
D
W
H
I
E
M
A
R
S
R
WHITE
MARSH
PARK
L I N
E
O
L
D
S
P
A
N
I
A
K
W
A
T
S
B
U
R
R
I
S
V
I
L
L
R D
C
H
U
R
C
H
H
I L
L
H
O
P
INDEX OF DRAWINGS
10-SCALE SITE AND UTILITY PLAN
TITLE SHEET & EXISTING CONDITIONS PLAN1
DESCRIPTIONSHEET #
30-SCALE SITE PLAN AND DETAILS
CALL MISS UTILITY THREE WORKING
DAYS BEFORE THE START OF WORK
AT 800-257-7777 OR DIAL 811
WARNING: UNDERGROUND UTILITIES SHOWN ON THESE PLANS
ARE APPROXIMATE ONLY AND ARE BASED ON LIMITED AVAILABLE
INFORMATION. CONTRACTOR SHALL TEST PIT AND LOCATE THE
EXACT LOCATION OF UNDERGROUND UTILITIES PRIOR TO
COMMENCING WORK. THE CONTRACTOR SHALL NOTIFY THE
OWNER AND ENGINEER OF ANY POSSIBLE DISCREPANCIES OR
CONFLICTS PRIOR TO CONTINUING WITH CONSTRUCTION.1 inch = ft.300
N
O
R
T
H
SITE AND LIGHTING DETAILS3
5 UTILITY DETAILS
TOTAL SITE AREA = 11,786,641 SF ± 263.697 AC. ±
MAXIMUM IMPERVIOUS AREA ALLOWED (40%) = 4,597,647 SF ± 105.479 AC. ±
18:1-14 E.(2)(a)[3]
EXISTING IMPERVIOUS AREA (2.3%) = 269,417 SF ± 6.185 AC. ±
IMPERVIOUS AREA TO BE REMOVED = 127 SF ± 0.003 AC. ±
PROPOSED IMPERVIOUS AREA = 3,402 SF ± 0.078 AC. ±
TOTAL IMPERVIOUS AREA (2.4%) = 272,692 SF ± 6.260 AC. ±
MAXIMUM FLOOR AREA RATIO (12%) 18:1-14 D.(2)(C) = 1,378,396 SF± 31.644 AC. ±
EXISTING FLOOR AREA (0.001%)= 10,897 SF± 0.250 AC. ±
(MANOR HOUSE + RENTAL HOUSE + P&R SHOP)
NEW FLOOR AREA = 716 SF ± 0.016 AC. ±
PROPOSED FLOOR AREA (0.001%) = 11,613 SF ± 0.267 AC. ±
MAXIMUM BUILDING HEIGHT 18:1-14 E.(2)(d)[4] = 45'
PROPOSED BUILDING HEIGHT 15'-0"± (
WAY UP SLOPED ROOF)
21'-0" (TOP OF CUPOLA)
SITE STATISTICS
LEGEND
x 13.00 13x00
E
W
C/O
S
FM
SS
E
LIMIT OF DISTURBANCE
LOD
W
W
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
5'x5' CONCRETE
PAD PER DETAIL
THIS SHEET
PROPOSED 22+22+12.5
LF 12" CONTECH
D-2000 CULVERT WITH
CMP FLARED ENDS
PROPOSED
COMFORT STATION
FF = 65.60 (SEE NOTE 2)
716 SQ.FT.
24.0'
10' WIDE
CROSSWALK PER
DETAIL THIS SHEET
HVAC
CONDENSER
PROPOSED E-ONE
DH-152-93 GRINDER PUMP
PER DETAIL SHEET 5
GRADE ASSUMED 64.4±
E
E
E
E
E
E
E
E
E
E
E
E
18.0'
LOD/SF
L
O
D
S
F
L
O
D
S
F
LOD
LOD
LOD
LOD LOD
LOD
L O
D S
F
L O
D S
F
L O
D S
F L
O D
S
F L
O D
S
F
LOD/SF LOD/SF LOD/SF
L
O
D
S
F
L
O
D
S
F
L
O
D
S
F
L
O
D
S
F
C
S
BEGIN 275 LF SILT
FENCE PER DETAIL
E-1 ON SHEET 4
END SILT FENCE
PROVIDE STABILIZED
CONSTRUCTION ENTRANCE
PER DETAIL B-1 ON SHEET 4
(SCE NOT SHOWN FOR CLARITY)
R
R
R
4,999 SQFT LIMIT
OF DISTURBANCE
PROPOSED
METER SOCKET
E-ONE CONTROL
PANEL PER
DETAIL SHEET 5
43 LF 4" PVC
(SDR-35) @ 2%
MIN. SLOPE
CONNECT E-ONE
FORCE MAIN TO
EX. CURB STOP
4" INV = 59.8±
x
4" INV = 62.0±
45 LF 1" PE PIPE
(DR-9), 30" DEEP MIN.
BY OTHERS TO WITHIN
5' OF BUILDING WITH
15' MIN PIGTAIL
300 LF OF 4" PVC PRIMARY
ELECTRICAL CONDUIT WITH
32" MIN. COVER, MULE TAPE
STAKED AT BOTH ENDS, AND
METALLIC LOCATION TAPE
INV = 62.7
STABILIZE SOIL WITH STABILIZATION
MATTING PER DETAIL D-4-6-A, SHEET 4
INV = 62.9
STABILIZE SOIL WITH STABILIZATION
MATTING PER D-4-6-A, SHEET 4
NOTE: PAVEMENT SPOT
GRADES REPRESENT TOP
COURSE (BY OTHERS)
65.52 x
HANDICAP PARKING SIGN
PER DETAIL SHEET 3
SAWCUT TO CLEAN
PAVEMENT AND
PROVIDE SMOOTH
TRANSITION TO
NEW ASPHALT
4' LONG 4"
STUB & CAP
SEE PAVEMENT
SECTION THIS SHEET.
SS
SS
C
/O
S
E E
32 LF OF 1
ELECTRICAL CONDUIT
HANDICAP STRIPING PER
DETAIL SHEET 3
4" WHITE STRIPING
(TPYICAL)
RUN CONDUIT TO WITHIN
36" OF THE EXISTING
TRANSFORMER
PEDESTRIAN AHEAD
SIGN (W11-2 & W16-7P)
PER DETAIL SHEET 3
PEDESTRIAN AHEAD
SIGN (W11-2 & W16-7P)
PER DETAIL SHEET 3
PEDESTRIAN R1-1
STOP SIGN PER
DETAIL SHEET 3
PEDESTRIAN R1-1
STOP SIGN PER
DETAIL SHEET 3
100 LF OF 1
" ELECTRICAL
CONDUIT WITH 24" MIN. COVER
AND METALLIC LOCATION
TAPE FOR FUTURE LIGHTING
POWER SUPPLY.
E
E
E
E
E
E
E
E
6' ASPHLAT SIDEWALK,
CONTINUOUS W/ PARKING
12"x18" SIGN "15 MINUTE
PARKING" (TYP. OF 3)
4' CONCRETE LANDING
@ 1.5% MAX. SLOPE
CLEANOUT DETAIL
THIS SHEET
COMMON FILL AROUND
BUILDING SHALL BE STABILIZED
WITH 4" TOPSOIL, PERMANENT
SEED AND MULCH. SPEC TO BE
PROVIDED BY OWNER
N O
R T
H
SHEET NO.:
FILE NO.:
DATE
SEAL
NOVEMBER 13, 2025
25-012
FOR:
TAX MAP 36D, GRID 2, PARCEL 4
PREPARED FOR: QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS
3rd ELECTION DISTRICT, QUEEN ANNE'S COUNTY, MARYLAND
WHITE MARSH PARK
5OF
P L O
T T
E v p m
V
I
N
C
I
T
O
M N I
A
V
E
R
I
T
A
S
Q
U
E
E
N
A
N
N E
S
C
O
U
N
T
Y
SEL
D M y
D o c u m e n t s D u m b
H o m e P r o j e c t s
Q
A C
C o m f o r t
S t a t i o n C
A D
S i t e
P l a n d w g T a b S
P
REVISIONS
DATEREV. # DESCRIPTION
FOLDER REF:
APPROVED BY:
SCALE:
DATE:
JOB NUMBER:
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE
APPROVED BY:
DATE
DEPT. OF PUBLIC WORKS
SOIL CONSERVATION SERVICE
QA Co.
QA Co. Pr of es si on al
C er tif ic at io n.
I he re by c er tif y th at th es e do cu m en ts w er e pr ep ar ed o r a pp ro ve d by m e, a nd th at I am a d ul y lic en se d un de r t he la w s o f t he
S ta te o f M ar yl an d, L ic en se N o.
, E xp ir at io n D at e:
P r o f e s s i o n a l
E n g i n e e r
COMFORT STATION
PO Box 103
Centreville, MD 21617
301-529-2368 compacthomeplans.com steve@select-engineer.com
COPYRIGHT 2025
C e c t
Engineering
25-006 FM P&P.dwg
APPROVED BY:
DATE
APPROVED BY:
DATE
1" = 10'
SEL
SEL
10-SCALE SITE AND UTILITY PLAN
1. THE EXISTING UTILITIES SHOWN IN THESE DRAWINGS IS BASED ON BEST AVAILABLE
INFORMATION, AND WE HAVE NOT CONTRACTED WITH A PRIVATE UTILITY LOCATING
COMPANY TO MAP POSSIBLE UNDERGROUND UTILITIES WITHIN THE LIMIT OF
DISTURBANCE. NO GUARANTEE TO THE ACCURACY OF THE LOCATION (HORIZONTAL
OR VERTICAL) IS MADE BY THE ENGINEER. CONTRACTOR TO FIELD VERIFY AND TEST
PIT AS NEEDED TO VERIFY THE LOCATION OF THE EXISTING UTILITIES. THIS SHALL BE
DONE AS PART OF THE CONTRACT FOR THE WORK SHOWN IN THESE DRAWINGS. ANY
DAMAGE INCURRED TO SUCH UTILITIES SHALL BE REPAIRED IMMEDIATELY AT THE
CONTRACTOR'S EXPENSE.
2. THE CONTRACTOR SHALL NOTIFY THE FOLLOWING TWO (2) WEEKS PRIOR TO THE
START OF CONSTRUCTION TO SCHEDULE A PRE-CONSTRUCTION MEETING:
3. ALL CONSTRUCTION WITHIN PUBLIC AND PRIVATE ROADS SHALL BE MARKED FOR
TRAFFIC AND PEDESTRIAN SAFETY. ALL SIGNS SHALL BE PLACED IN ACCORDANCE
WITH SECTION VI OF THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
4. ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL BE IN CONFORMANCE WITH
THE QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS.
5. THE CONTRACTOR ASSUMES ALL RESPONSIBILITIES FOR ANY DEVIATIONS FROM
THESE PLANS, UNLESS SAID DEVIATION IS APPROVED BY THE ENGINEER. THE
CONTRACTOR SHALL RECEIVE WRITTEN PERMISSION FROM THE ENGINEER IF A
DEVIATION OF THE PLAN IS NECESSARY.
6. ALL DISTURBED AREAS SHALL BE SMOOTHLY GRADED TO PROVIDE POSITIVE
DRAINAGE THAT MIMICS THE EXISTING CONDITIONS QS IN THE DIRECTION OF FLOW
ARROWS HEREIN AND STABILIZED WITH TOPSOIL, SEED, AND MULCH. IF SETTLEMENT
OCCURS, TOPSOIL, SEEDING AND MULCHING SHALL BE REPEATED UNTIL SETTLEMENT
SUBSIDES (SEE EROSION AND SEDIMENT CONTROL SPECIFICATIONS).
7. ALL TRASH, TREES, DEMOLITION DEBRIS, AND UNDERBRUSH ARE TO BE CLEARED AND
REMOVED OFF SITE TO AN APPROVED DUMP SITE BY THE CONTRACTOR.
8. ANY EXCESS EXCAVATED MATERIAL PLACED OUTSIDE OF THOSE AREAS DESIGNATED
ON THIS PLAN SHALL MEET APPROVAL OF THE QUEEN ANNE'S COUNTY INSPECTORS
AND ENGINEER.
9. ANY EXISTING SURVEY MONUMENTATION THAT IS DISTURBED DURING
CONSTRUCTION SHALL BE REPLACED BY A REGISTERED SURVEYOR AT THE
CONTRACTOR'S EXPENSE.
10. ALL FILL AREAS WITHIN LIMITS OF PAVEMENT AND OTHER AREAS AS DESIGNATED ON
THESE PLANS SHALL BE COMPACTED TO 95% MODIFIED PROCTOR DENSITY AND LAID
AND COMPACTED IN 8" MAXIMUM LIFTS.
11. SEWER, WATER, AND ELECTRIC SERVICE LINES ARE TO BE CONSTRUCTED, TRENCHES
FILLED, AND DISTURBANCE STABILIZED AT THE END OF EACH WORKING DAY. IN THIS
FASHION, THE UTILITIES ARE NOT COUNTED AS DISTURBANCE IN THE OVERALL LIMIT
OF DISTURBANCE CALCULATION.
GENERAL NOTES
1 inch = ft.10
PER PLAN
4" THICK
4" CR-6
GRADE
FINISHED
5' OR 6' PER PLAN
S.H.A. MIX NO. 2
3000 PSI 28 DAY
COMPRESSIVE
STRENGTH
SUBGRADE AND CR-6
TO BE COMPACTED TO
95% MODIFIED
PROCTOR DENSITY
CONCRETE WALK DETAIL
NOT TO SCALE
1. STOCKPILED TOPSOIL, CUT/FILL MATERIALS, AND AGGREGATE SHALL BE REMOVED
FROM THE SITE WITHIN 3 CALENDAR DAYS, OR SHALL BE COVERED WITH TARPS OR
SURROUNDED BY SILT FENCE.
2. CONTRACTOR SHALL VERIFY THE EXISTING GRADE AT THE BUILDING CENTER IS 64.4.
CONTACT ENGINEER IF ACTUAL ELEVATION IS DIFFERENT BY MORE OR LESS THAN 0.3'
FOR A REVISED GRADING PLAN.
CONSTRUCTION NOTES
LIGHT PAVEMENT SECTION
NOT TO SCALE
1. PAVEMENT - 1-1/2" compacted bituminous concrete surface course (SHA mix design
9.5mm) ON 2.5" compacted bituminous concrete base course (SHA mix design 19mm).
2. STABILIZED SUB-BASE - Shall be 6" minimum of CR-6 aggregate laid and compacted in one lift. Compaction shall meet or exceed 95% of the modified proctor density for the material. Other alternatives to stabilized sub-base must be approved by the Engineer prior to initiation of construction.
3. SUB-GRADE - All unsuitable materials shall be removed to a point 12" below subgrade of the stabilization. If unsuitable material is encountered at or below this point, the unsuitable material shall be removed as directed by the Engineer. The unsuitable material shall be replaced with select borrow and compacted to 95% of the modified proctor density for the material.
COMPACTED FILL OR SUBGRADE PER GEOTECHNICAL
ENGINEER SPECIFICATION. SEE GEOTECHNICAL
ENGINEER REPORT FOR ADDITIONAL SPECIFICATIONS.
P A
V E
M E
N T
1" RADIUS NOSING
SCORE
FIN
IS
HED G
RADE
6"
4" THICK
OR B
UILDIN
G
SEE SITE PLAN
CONCRETE MD.
S.H.A. MIX NO. 2
3000 PSI 28 DAY
COMPRESSIVE
STRENGTH
CONCRETE SIDEWALK DETAIL
O F A
S P
H A
LT
2% MAX.
NOTES:
1) PROVIDE CONTROL JOINTS EVERY 5' AND EXPANSION JOINTS
EVERY 15'.
2) PROVIDE A BROOM FINISH.
3) ALL WALKS SHALL MEET APPLICABLE ADA STANDARDS.
4) THIS SECTION IS NOT APPROPRIATE FOR TRAFFIC BEARING
LOCATIONS.
5) NOTE THAT WITH PAVEMENT NO TOP COAT, 7" OF MONOLITHIC
WALK WILL BE EXPOSED AT THE END OF THIS CONTRACT.
4"
6"
SUBGRADE AND CR-6
TO BE COMPACTED TO
95% MODIFIED
PROCTOR DENSITY
4" CR-6
TO
P
C O
U R
S E
F A
F
B
U I L D
I N
G
NOTES:
1) MOW LIMIT OF PATH AND REMOVE TURF OR OTHER
ORGANIC MATERIAL PRIOR TO SPREADING MULCH.
2) AFTER PLACEMENT OF MULCH, COMPACT USING A
VIBRATORY TAMPER, ROLLER, OR SIMILAR.
3) MAINTAIN SHEET FLOW TO THE MAXIMUM EXTENT
PRACTICAL ACROSS TRAIL.
4) PROVIDE CULLVERTS SIZED FOR 2-YEAR STORM FLOW
AT LOCATIONS OF CONCENTRATED FLOW.
5% M
AX S
LO
PE
EXISTING GROUND
FIRM NATIVE GRADE FREE OF
EXCESSIVE ORGANIC
MATERIAL OR CLAYEY SOILS
3-4'' MIN. HARDWOOD
MULCH OR ENGINEERED
WOOD FIBER
SEE PLAN
FOR WIDTH
WOODCHIP PATH DETAIL - BY OTHERS
NOT TO SCALE
2' STUB
FINISHED GRADE
4" SCH 40 PVC PIPE
4"X4" SCH 40 PVC 45°
VERT. WYE BRANCH
FLOW
TO GRINDER
PUMP
4" SCH 40 PVC PIPE @ 1.0% MIN.
NOTE: FOR GRAVITY SEWER APPLICATIONS ONLY
LONG TURN
45° BEND
SEWER CLEANOUT DETAIL
NOT TO SCALE
8 GUAGE TRACER WIRE
CLEANOUT PLUG
3" COVER.
PROVIDE 12" OF #4
REBAR FOR MAGNETIC
LOCATION OF CAP
SOLVENT
WELD CAP
7'-0" LONG, 370 LBS., TWO 5/8" X 18" ANCHOR PINS.
SPECIFICATIONS FOR QUALITY: SMOOTH STEEL FORM
FINISH, HIGH STRENGTH - 4500 P.S.I.
TYPICAL PARKING BLOCK DETAIL
NOT TO SCALE
SHEET NO.:
FILE NO.:
DATE
SEAL
NOVEMBER 13, 2025
25-012
FOR:
TAX MAP 36D, GRID 2, PARCEL 4
PREPARED FOR: QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS
3rd ELECTION DISTRICT, QUEEN ANNE'S COUNTY, MARYLAND
WHITE MARSH PARK
5OF
P L O
T T
E v p m
V
I
N
C
I
T
O
M N I
A
V
E
R
I
T
A
S
Q
U
E
E
N
A
N
N E
S
C
O
U
N
T
Y
SEL
D M y
D o c u m e n t s D u m b
H o m e P r o j e c t s
Q
A C
C o m f o r t
S t a t i o n C
A D
S i t e
P l a n d w g T a b D
T
REVISIONS
DATEREV. # DESCRIPTION
FOLDER REF:
APPROVED BY:
SCALE:
DATE:
JOB NUMBER:
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE
APPROVED BY:
DATE
DEPT. OF PUBLIC WORKS
SOIL CONSERVATION SERVICE
QA Co.
QA Co. Pr of es si on al
C er tif ic at io n.
I he re by c er tif y th at th es e do cu m en ts w er e pr ep ar ed o r a pp ro ve d by m e, a nd th at I am a d ul y lic en se d un de r t he la w s o f t he
S ta te o f M ar yl an d, L ic en se N o.
, E xp ir at io n D at e:
P r o f e s s i o n a l
E n g i n e e r
COMFORT STATION
PO Box 103
Centreville, MD 21617
301-529-2368 compacthomeplans.com steve@select-engineer.com
COPYRIGHT 2025
C e c t
Engineering
25-006 FM P&P.dwg
APPROVED BY:
DATE
APPROVED BY:
DATE
1" = 30'
SEL
SEL
SITE AND LIGHTING DETAILS
MARKINGS SHALL BE 125 MIL. WHITE THERMOPLASTIC.
CROSSWALK STRIPING DETAIL
NOT TO SCALE
F R
O N
T
D
E P
T H
G
E
A T
E R
M
I N
M
I N
I M
U M
10"
C
D
E S
M
I N
STRIPING & SIGNAGE DETAILS
DISABLED PARKING STALL
9' OR
5' - CARS
POST SECTION
MOUNTING
3 1/2"
1 1/4"
9' OR
S E
E
S
I T
E
P
L
PARTIAL ELEVATION
1' - 0"
SIGN
4" PAINTED STRIPING
1'-6" O.C. AT 45° IN
FRONT OF RAMP.
(WHITE REFLECTIVE)
PAVEMENT
MAXIMUM SLOPE
2% IN ALL
DIRECTIONS.
NATIONAL STANDARD
ACCESSIBILITY SYMBOL
PAINTED ON PAVEMENT.
(WHITE ON BLUE
BACKGROUND)
FACE OF
WALK OR
CURB
SIGN
NOT TO SCALE
ALUMINUM SIGN
STOCK WITH
GRAPHICS PER
ADA REQ'TS
4 LB/FT "U"
CHANNEL
(GALVANIZED)
5/16" MACHINE
SCREW OR
BOLT
NUT AND
LOCK
WASHER
SIGN
(IF SHOWN
ON PLAN)
HANDICAP, NO PARKING
SIGN INSTALLED IN
LANDSCAPE AREA
POST & MOUNTING
PER DETAILS AT LEFT
MOWING
EDGE
CONCRETE
FOOTING
8' - VANS
PER PLAN
PER PLAN
POST
15-MIN. PARKING SIGN DETAIL
1' - 0"
NOT TO SCALE
ALUMINUM SIGN STOCK
WITH WHITE BACK-
GROUND AND RED
LETTERING, SIMILAR TO
MUTCD R8-3
1. REFER TO THE DISABLED PARKING STALL
STRIPING AND SIGNAGE DETAIL FOR POST
AND MOUNTING INFORMATION.
2. SIGN SHALL BE LOCATED 8" TO 12" BEHIND
WALK OR CURB.
3. BOTTOM OF SIGN HEIGHT SHALL BE 5'-0" OR TO
MATCH HANDICAP PARKING SIGNS, IF PRESENT.
REVISE AS NECESSARY FOR DIRECT-BURY POLE.
ONLY. COORDINATE WITH POLE MANUFACTURER.
THE DETAILS SHOWN BELOW ARE FOR MINIMUM DESIGN
NOTE:
TO DIVISION 3 OF SPECIFICATIONS.
NOTE: ALL CONCRETE WORK SHALL CONFORM
REBAR
CONTINUOUS
FINISHED GRADE
15'-0" FIBERGLASS
SCHED. 40 P.V.C.
RIGID STEEL
SET ANCHOR BOLTS FURNISHED
w/ POLE USING TEMPLATE
SUPPLIED BY MANUFACTURER
M
I N
24" DIA.
LIGHT POLE FOUNDATION DETAIL
NOT TO SCALE
POLE
W11-2 PEDESTRIAN SIGN DETAIL
NOT TO SCALE
1. SIGN SHALL BE LOCATED 3' TO 4' BEHIND EDGE OF
PAVEMENT OR CURB.
2. BOTTOM OF SIGN HEIGHT SHALL BE 5'-0" TO 6'-0"
ABOVE THE ADJACENT ROAD SURFACE..
3. W11-2 PEDESTRIAN SIGN TO BE 30" x 30", MOUNTED ON A 45° ANGLE, AND CONSTRUCTED
TO MUTCD STANDARDS.
4. W16-7P ARROW SIGN TO BE 12" x 24" AND
CONSTRUCTED TO MUTCD STANDARDS.
POST SECTION
MOUNTING
3 1/2"
1 1/4"
4 LB/FT "U"
CHANNEL
(GALVANIZED)
5/16" MACHINE
SCREW OR
BOLT
NUT AND
LOCK
WASHER
SIGN
F R
O N
T
D
E P
T H
E
A T
E R
M
I N
M
I N
I M
U M
10"
C
D
E S
T
O
M
I N
HANDICAP, NO PARKING
SIGN INSTALLED IN
LANDSCAPE AREA
POST & MOUNTING
PER DETAILS AT LEFT
MOWING
EDGE
CONCRETE
FOOTING
POST
SIGN GRAPHIC
W11-2
W16-7P
NOTES:
1. PROVIDE DOUBLE HEAD POLE MOUNT WITH BOTH
UNITS SIDE BY SIDE AND FACING NORTH TO
ILLUMINATE THE PARKING SPACES. BOTH
2. UNITS SHALL BE ANGLED 30° FROM HORIZONTAL.
3. PROVIDE ONE SET OF EXPANSION SOLAR PANELS.
R1-1 STOP SIGN DETAIL - TRAILS
NOT TO SCALE
1. SIGN SHALL BE LOCATED 2' TO 3' BEHIND EDGE OF
PEDESTRIAN PATH.
2. BOTTOM OF SIGN HEIGHT SHALL BE 4'-0" TO 4'-8"
ABOVE THE ADJACENT PATH SURFACE..
3. R1-1 STOP SIGN TO BE 18" x 18" METAL.
4. POST, FOOTING, AND MOUNTING HARDWARE SHALL
MATCH SIMILAR STOP SIGNS ALONG THE CROSS
ISLAND AND SOUTH ISLAND TRAILS ON KENT ISLAND.
POST SECTION
MOUNTING
"U" CHANNEL
(GALVANIZED)
MACHINE
SCREW OR
BOLT
NUT AND
LOCK
WASHER
SIGN
F R
O N
T
D
E P
T H
E
A T
E R
M
I N
M
I N
I M
U M
10"
C
D
E S
T
O
M
I N
POST & MOUNTING
PER DETAILS AT LEFT
MOWING
EDGE
CONCRETE
FOOTING
POST
SIGN GRAPHIC
PHOTOMETRIC PLAN
SCALE: 1" = 10'
Pole Shaft - Manufactured on computer-controlled equipment to customer specifications using filament wound technology. Strict control of glass, fiber and resin ensures a consistent product.
Less electrically conductive than steel, aluminum or wood.
Pole Top - Poles can be provided with tenon top construction or capped/drilled to customer specifications. Tenons on all poles are made of high-strength corrosion resistant aluminum.
Anchor Base / Cover - Anchor bases on poles are made of high-strength corrosion resistant aluminum. The anchor base is primed, painted, and factory bonded to the pole. Standard base cover is included.
Anchor Bolts - Carbon steel conforming to AASHTO M314 Grade - 55 or ASTM F1554 Grade - 55.
Bolts are "L" shaped and are galvanized a minimum of 12" on the threaded end. Each pole includes four bolts each with two nuts and two flat washers.
Hand Hole - 2.5"x 5" hand hole is provided at the base end of the pole assembly. Each hand hole includes a cover and the cover attachment hardware.
Finish - Rust-proof and corrosion-resistant for low lifetime maintenance. We finish our smooth and natural poles with a special finishing resin applied at 12 - 15 mils thick which provides a superior finish to the normal 1.5 mil thick paint. Resin is pigmented and fortified with ultraviolet inhibitors to produce a long-lasting, reliable product.
Engineering & Compliance - Poles are constructed to comply with specifications of ANSI, AASHTO and ASTM standards.
LIGHT POLE DETAIL
NOT TO SCALE
OVERALL LIGHT POLEHAND HOLE ANCHOR BOLTS
ANCHOR BOLTS DETAIL
PROVIDE: 15' Tall, Round Tapered Fiberglass, Anchor Base Light Pole (Quantity per plan)
Light Fixture Mounting: Top Cap Only w/ No Side Drilling
Finish and Color: Black Painted
Hand Hole & Cover: HHC - Qty 1
Anchor Bolt Kit: Ship with Pole
NOTE::
THE BACKGROUND SITE IMPROVEMETNS, CALLOUTS, ETC. HAVE
BEEN SUPERSEDED SINCE THIS PHOTOMETRIC PLAN WAS
PREPARED. SOLE PURPOSE OF THIS DETAIL IS TO DEMONSTRATE
FOOTCANDLE VALUES OVER THE PARKING LOT AND NEARBY AREAS.
DATE
SEAL
NOVEMBER 13, 2025
25-012
FOR:
TAX MAP 36D, GRID 2, PARCEL 4
PREPARED FOR: QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS
3rd ELECTION DISTRICT, QUEEN ANNE'S COUNTY, MARYLAND
WHITE MARSH PARK
5OF
P L O
T T
E v p m
V
I
N
C
I
T
O
M N I
A
V
E
R
I
T
A
S
Q
U
E
E
N
A
N
N E
S
C
O
U
N
T
Y
SEL
D M y
D o c u m e n t s D u m b
H o m e P r o j e c t s
Q
A C
C o m f o r t
S t a t i o n C
A D
S i t e
P l a n d w g T a b P
K G
REVISIONS
DATEREV. # DESCRIPTION
FOLDER REF:
APPROVED BY:
SCALE:
DATE:
JOB NUMBER:
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE
APPROVED BY:
DATE
DEPT. OF PUBLIC WORKS
SOIL CONSERVATION SERVICE
QA Co.
QA Co. Pr of es si on al
C er tif ic at io n.
I he re by c er tif y th at th es e do cu m en ts w er e pr ep ar ed o r a pp ro ve d by m e, a nd th at I am a d ul y lic en se d un de r t he la w s o f t he
S ta te o f M ar yl an d, L ic en se N o.
, E xp ir at io n D at e:
P r o f e s s i o n a l
E n g i n e e r
COMFORT STATION
PO Box 103
Centreville, MD 21617
301-529-2368 compacthomeplans.com steve@select-engineer.com
COPYRIGHT 2025
C e c t
Engineering
25-006 FM P&P.dwg
APPROVED BY:
DATE
APPROVED BY:
DATE
1" = 30'
SEL
SEL
30-SCALE SITE PLAN AND DETAILS
N O
R T
H
1 inch = ft.30
AIR RELEASE CONSTRUCTION DETAIL
SCALE: 1" = 30'
F L O
W
POSTS
CROSS SECTION
STEP 1
STEP 2
STEP 3
STAPLESTAPLE
STAPLE
STAPLE
STAPLE
STAPLE
STAPLESTAPLE
SF
STANDARD SYMBOL
FINAL
CONFIGURATION
SF
CONSTRUCTION SPECIFICATIONS
1. USE WOOD POSTS 1
X 1
INCH (MINIMUM) SQUARE CUT OF SOUND QUALITY HARDWOOD. AS AN
ALTERNATIVE TO WOODEN POST USE STANDARD "T" OR "U" SECTION STEEL POSTS WEIGHING NOT LESS THAN 1
POUND PER LINEAR FOOT.
2. USE 36 INCH MINIMUM POSTS DRIVEN 16 INCH MINIMUM INTO GROUND NO MORE THAN 6 FEET APART.
3. USE WOVEN SLIT FILM GEOTEXTILE AS SPECIFIED IN SECTION H-1 MATERIALS AND FASTEN GEOTEXTILE
SECURELY TO UPSLOPE SIDE OF FENCE POSTS WITH WIRE TIES OR STAPLES AT TOP AND MID-SECTION.
4. PROVIDE MANUFACTURER CERTIFICATION TO THE AUTHORIZED REPRESENTATIVE OF THE
INSPECTION/ENFORCEMENT AUTHORITY SHOWING THAT THE GEOTEXTILE USED MEETS THE REQUIREMENTS IN
SECTION H-1 MATERIALS.
5. EMBED GEOTEXTILE A MINIMUM OF 8 INCHES VERTICALLY INTO THE GROUND. BACKFILL AND COMPACT THE SOIL
ON BOTH SIDES OF FABRIC.
6. WHERE TWO SECTIONS OF GEOTEXTILE ADJOIN: OVERLAP, TWIST, AND STAPLE TO POST IN ACCORDANCE WITH
THIS DETAIL.
7. EXTEND BOTH ENDS OF THE SILT FENCE A MINIMUM OF FIVE HORIZONTAL FEET UPSLOPE AT
45 DEGREES TO THE MAIN FENCE ALIGNMENT TO PREVENT RUNOFF FROM GOING AROUND THE ENDS OF THE SILT
FENCE.
8. REMOVE ACCUMULATED SEDIMENT AND DEBRIS WHEN BULGES DEVELOP IN SILT FENCE OR WHEN SEDIMENT
REACHES 25% OF FENCE HEIGHT. REPLACE GEOTEXTILE IF TORN. IF UNDERMINING OCCURS, REINSTALL FENCE.
STANDARD SYMBOL
DETAIL B-4-6-A
TEMPORARY SOIL STABILIZATION
MATTING CHANNEL APPLICATION
DATE
SEAL
NOVEMBER 13, 2025
25-012
FOR:
TAX MAP 36D, GRID 2, PARCEL 4
PREPARED FOR: QUEEN ANNE'S COUNTY DEPARTMENT OF PUBLIC WORKS
3rd ELECTION DISTRICT, QUEEN ANNE'S COUNTY, MARYLAND
WHITE MARSH PARK
5OF
P L O
T T
E v p m
V
I
N
C
I
T
O
M N I
A
V
E
R
I
T
A
S
Q
U
E
E
N
A
N
N E
S
C
O
U
N
T
Y
SEL
D M y
D o c u m e n t s D u m b
H o m e P r o j e c t s
Q
A C
C o m f o r t
S t a t i o n C
A D
S i t e
P l a n d w g T a b D
T
REVISIONS
DATEREV. # DESCRIPTION
FOLDER REF:
APPROVED BY:
SCALE:
DATE:
JOB NUMBER:
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE
APPROVED BY:
DATE
DEPT. OF PUBLIC WORKS
SOIL CONSERVATION SERVICE
QA Co.
QA Co. Pr of es si on al
C er tif ic at io n.
I he re by c er tif y th at th es e do cu m en ts w er e pr ep ar ed o r a pp ro ve d by m e, a nd th at I am a d ul y lic en se d un de r t he la w s o f t he
S ta te o f M ar yl an d, L ic en se N o.
, E xp ir at io n D at e:
P r o f e s s i o n a l
E n g i n e e r
COMFORT STATION
PO Box 103
Centreville, MD 21617
301-529-2368 compacthomeplans.com steve@select-engineer.com
COPYRIGHT 2025
C e c t
Engineering
25-006 FM P&P.dwg
APPROVED BY:
DATE
APPROVED BY:
DATE
1" = 30'
SEL
SEL
UTILITY DETAILS
NOTE: CURB STOP IS EXISTING
(INSTALLED SUMMER 2025)
File details come from the government source that posted it. Updated .