2023-10-20_Elec_(Permit)_Central_Intake_-_Elevator_Modernization.pdf
PDF 2 MB Posted
- Solicitation number
- 24-0301-ITB-C
- Issued by
- Pinellas County, Florida
About this file
The documents are detailed electrical design and construction plans for the Pinellas County Jail Lobby Elevator Modernization project located in Clearwater, Florida. The project involves comprehensive electrical upgrades and modernization for three elevators in a seven-story detention facility: one simplex elevator (Serial Number 55710) and one duplex elevator with two cabs in a single shaft (Serial Numbers 55711 & 55712). The plans include extensive electrical demolition and new construction floor plans, electrical riser diagrams, legends, abbreviations, and specific technical specifications for the elevator systems.
The design documents provide intricate details on electrical infrastructure, including power legends, lighting controls, fire alarm systems, and communication infrastructure. The plans outline specific requirements for electrical demolition, new construction, and precise modifications to the existing elevator systems. Technical specifications cover aspects such as panel configurations, wiring diagrams, and compliance with applicable electrical codes. The project appears to be a comprehensive modernization effort focused on upgrading the electrical systems and elevator infrastructure to improve functionality and safety within the Pinellas County Jail's central intake building.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PI
NE
LL
AS
C O
UN
TY
J
AI
L
LO
BB
Y
EL
EV
AT
O
R M
O
DE
RN
IZ
AT
IO
N
AutoCAD SHX Text
%%UDRAWING INDEX
AutoCAD SHX Text E0.1 LEGEND, ABBREVIATIONS AND GENERAL NOTES E1.0 OVERALL BUILDING FLOOR PLAN OVERALL BUILDING FLOOR PLAN E2.1 ELECTRICAL DEMOLITION FLOOR PLAN ELECTRICAL DEMOLITION FLOOR PLAN E3.1 ELECTRICAL CONSTRUCTION FLOOR PLAN ELECTRICAL CONSTRUCTION FLOOR PLAN E4.1 ELECTRICAL RISER DIAGRAM AND DETAILSELECTRICAL RISER DIAGRAM AND DETAILS
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
FIRE SERVICE HANDSET
AutoCAD SHX Text
UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
FIRE SERVICE JACK
AutoCAD SHX Text
UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
FCP
AutoCAD SHX Text
RA
AutoCAD SHX Text R
AutoCAD SHX Text
SHUT-DOWN RELAY
AutoCAD SHX Text
TAMPER SWITCH
AutoCAD SHX Text
UON MOUNT TOP OF ENCLOSURE 72" AFF.
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL.
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text
SMOKE DETECTOR CEILING MOUNTED
AutoCAD SHX Text
HEAT DETECTOR CEILING MOUNTED
AutoCAD SHX Text
UON CENTERLINE MOUNTED 18" AFF, U.O.N.
AutoCAD SHX Text
WALL MOUNTED TELEPHONE OUTLET.
AutoCAD SHX Text
%%UCOMMUNICATIONS LEGEND
AutoCAD SHX Text
%%UFIRE ALARM LEGEND
AutoCAD SHX Text
REMOTE ALARM INDICATOR WITH TEST SWITCH. FLUSH
AutoCAD SHX Text
CEILING MOUNTED. (WALL MOUNTED, CENTER LINE 48"
AutoCAD SHX Text
AFF IN MECHANICAL ROOMS).
AutoCAD SHX Text
%%UABBREVIATIONS
AutoCAD SHX Text A AMPERE AMPERE AC ABOVE COUNTER ABOVE COUNTER AF AMPERE FRAME AMPERE FRAME AFCI ARC FAULT CIRCUIT INTERRUPTER ARC FAULT CIRCUIT INTERRUPTER AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT AIR HANDLING UNIT AIC AMPERAGE INTERRUPTING CAPACITY AMPERAGE INTERRUPTING CAPACITY AL ALUMINUM ALUMINUM ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AV AUDIO VISUAL AUDIO VISUAL AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BOB BOTTOM OF BOX BOTTOM OF BOX C CONDUIT CONDUIT CAT CATEGORY CATEGORY CB CIRCUIT BREAKER CIRCUIT BREAKER CH CHILLER CHILLER CKT CIRCUIT CIRCUIT CL CENTER LINE CENTER LINE CLG CEILING CEILING COB CENTER OF BOX CENTER OF BOX CU COPPER COPPER DEG DEGREE DEGREE DS DISCONNECT SWITCH DISCONNECT SWITCH EG EQUIPMENT GROUND BAR EQUIPMENT GROUND BAR EC ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR EF EXHAUST FAN EXHAUST FAN EM EMERGENCY EMERGENCY EMT ELECTRICAL METALLIC TUBING ELECTRICAL METALLIC TUBING ENCL ENCLOSURE ENCLOSURE EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER EX EXISTING EXISTING FA FIRE ALARM FIRE ALARM FBO FURNISHED BY OTHERS FURNISHED BY OTHERS FCP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FCC FIRE CONTROL CENTER FIRE CONTROL CENTER FATC FIRE ALARM TERMINAL CABINET FIRE ALARM TERMINAL CABINET FO FIBER OPTIC FIBER OPTIC GFI GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER G GROUND GROUND HOA HAND-OFF-AUTOMATIC HAND-OFF-AUTOMATIC HACR HEATING/AIR CONDITIONING RATED HEATING/AIR CONDITIONING RATED HPF HIGH POWER FACTOR HIGH POWER FACTOR HP HORSEPOWER HORSEPOWER HPS HIGH PRESSURE SODIUM HIGH PRESSURE SODIUM IG ISOLATED GROUND ISOLATED GROUND IPTV INTERNET PROTOCOL TELEVISION INTERNET PROTOCOL TELEVISION J, JB JUNCTION BOX JUNCTION BOX KCMIL THOUSAND CIRCULAR MILLS THOUSAND CIRCULAR MILLS kVA KILOVOLT AMPERER KILOVOLT AMPERER kW KILOWATT KILOWATT MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MDU A/V & WIFI CABINET MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MLO MAINT LUGS ONLY MAINT LUGS ONLY MTD MOUNTED MOUNTED MTS MANUAL TRANSFER SWITCH MANUAL TRANSFER SWITCH MW MICROWAVE MICROWAVE NA NOT APPLICABLE NOT APPLICABLE NC NORMALLY CLOSED NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUF. ASSOC. NATIONAL ELECTRICAL MANUF. ASSOC. NF NON FUSED NON FUSED NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NOT IN CONTRACT NL NIGHT LIGHT NIGHT LIGHT NO NORMALLY OPEN NORMALLY OPEN NTE NOT TO EXCEED NOT TO EXCEED PB PUSHBUTTON PUSHBUTTON PC PHOTOCELL PHOTOCELL PHASE POE POWER OVER ETHERNET POWER OVER ETHERNET P&I PROVIDE AND INSTALL PROVIDE AND INSTALL PNL PANEL PANEL POTS PLAIN ORDINARY TELEPHONE SYSTEM PLAIN ORDINARY TELEPHONE SYSTEM PVC POLY VINYL CHLORIDE POLY VINYL CHLORIDE RGS RIGID GALVANIZED STEEL RIGID GALVANIZED STEEL SCA SHORT CIRCUIT AMPS SHORT CIRCUIT AMPS SG SINGLE GANG SINGLE GANG SPD SURGE PROTECTIVE DEVICE SURGE PROTECTIVE DEVICE STP SHIELDED TWISTED PAIR SHIELDED TWISTED PAIR STR STRANDED STRANDED SW SWITCH SWITCH SWBD SWITCHBOARD SWITCHBOARD TC TIME CLOCK TIME CLOCK TOB TOP OF BOX TOP OF BOX TP TWISTED PAIR TWISTED PAIR TR TAMPER RESISTANT TAMPER RESISTANT TS TIME SWITCH TIME SWITCH TYP TYPICAL TYPICAL UC UNDER COUNTER UNDER COUNTER UG UNDERGROUND UNDERGROUND UH UNIT HEATER UNIT HEATER UPS UNINTERRUPTIBLE POWER SUPPLY UNINTERRUPTIBLE POWER SUPPLY UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED VAV VARIABLE AIR VOLUME VARIABLE AIR VOLUME V VOLT VOLT WP WEATHERPROOF WEATHERPROOF WR WEATHER RESISTANT WEATHER RESISTANT XFMR TRANSFORMER TRANSFORMER 2G TWO GANG TWO GANG
AutoCAD SHX Text
%%UAPPLICABLE CODES
AutoCAD SHX Text
FOUR WAY WALL MOUNTED SWITCH - UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
SINGLE POLE SWITCH 20A 120/277V UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
THREE WAY 20A 120/277V SWITCH - UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
%%ULIGHTING CONTROLS
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text K
AutoCAD SHX Text a
AutoCAD SHX Text
EMERGENCY LIGHTING FIXTURE WITH BATTERY BACK-UP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIT SIGN. SINGLE OR DOUBLE FACE
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
CEILING MOUNTED LIGHT FIXTURE
AutoCAD SHX Text
WALL MOUNTED LIGHT FIXTURE
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text a
AutoCAD SHX Text a
AutoCAD SHX Text
%%ULIGHTING LEGEND
AutoCAD SHX Text
208/120V, PANELBOARD.
AutoCAD SHX Text
480/277V, PANELBOARD.
AutoCAD SHX Text
FLOOR MOUNTED COMBINATION (20A 120V) DUPLEX RECEPTACLE/DATA
AutoCAD SHX Text
SEE SPECIFICATIONS. UON MOUNT TOP OF ENCLOSURE 66" AFF.
AutoCAD SHX Text
HEAVY DUTY FUSIBLE COMBINATION STARTER/DISCONNECT SWITCH.
AutoCAD SHX Text
HEAVY DUTY FUSIBLE DISCONNECT SWITCH. FUSED AS INDICATED ON
AutoCAD SHX Text
FLOOR MOUTNED COMBINATION (20A 120V) DOUBLE DUPLEX
AutoCAD SHX Text
HEAVY DUTY DISCONNECT SWITCH, NON FUSIBLE. SEE SPECIFICATIONS.
AutoCAD SHX Text
PUSH PLATE. UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE.
AutoCAD SHX Text
BUSWAY. SEE SPECIFICATIONS.
AutoCAD SHX Text
DUCT HEATER. (FURNISHED UNDER DIV. 15). (WIRED UNDER DIVISION 16).
AutoCAD SHX Text
MULTI OUTLET STRIP OR POWER/DATA COMMUNICATION
AutoCAD SHX Text
MAGNETIC MOTOR STARTER. UON MOUNT TOP OF ENCLOSURE 66" AFF.
AutoCAD SHX Text
SEE SPECIFICATIONS.
AutoCAD SHX Text
ENCLOSED CIRCUIT BREAKER. AS INDICATED.
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE AS INDICATED. UON MOUNT TOP OF
AutoCAD SHX Text
FLOOR MOUNTED DUPLEX RECEPTACLE.
AutoCAD SHX Text
SPECIAL RECEPTACLE, AS INDICATED. UON CENTERLINE MOUNTED 18" AFF.
AutoCAD SHX Text
50A 1%%C 240V RECEPTACLE. UON CENTERLINE MOUNTED 18" AFF
AutoCAD SHX Text
DUPLEX RECEPTACLE. 20A 120V UON CENTERLINE MOUNTED 42" AFF
AutoCAD SHX Text
DUPLEX RECEPTACLE. 20A 120V UON CENTERLINE MOUNTED 18" AFF
AutoCAD SHX Text
SINGLE RECEPTACLE. 20A 120V UON CENTERLINE MOUNTED 18" AFF
AutoCAD SHX Text
DOUBLE DUPLEX RECEPTACLE OUTLET. 20A 120V UON CENTERLINE
AutoCAD SHX Text
ENCLOSURE 72" AFF
AutoCAD SHX Text
PLANS. SEE SPECIFICATIONS. UON MOUNT TOP OF ENCLOSURE 66" AFF.
AutoCAD SHX Text
MISCELLANEOUS PANELBOARD. AS INDICATED.
AutoCAD SHX Text
UON MOUNT TOP OF ENCLOSURE 66" AFF
AutoCAD SHX Text
DRY TYPE TRANSFORMER. AS INDICATED.
AutoCAD SHX Text
MANHOLE. SEE SPECIFICATIONS.
AutoCAD SHX Text
HAND HOLE. SEE SPECIFICATIONS.
AutoCAD SHX Text
MOTOR. AS INDICATED.
AutoCAD SHX Text
SINGLE PUSHBUTTON. UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text
TRANSIENT VOLTAGE SURGE SUPPRESSION AS INDICATED
AutoCAD SHX Text
FLOOR MOUNTED JUNCTION BOX. UON SIZE AS REQUIRED BY NEC.
AutoCAD SHX Text
208/120V, DISTRIBUTION PANELBOARD.
AutoCAD SHX Text T
AutoCAD SHX Text
MH
AutoCAD SHX Text
HH
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
PP
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
%%UPOWER LEGEND
AutoCAD SHX Text
DOUBLE DUPLEX RECEPTACLE OUTLET. 20A 120V UON CENTERLINE
AutoCAD SHX Text
MOUNTED 18" AFF.
AutoCAD SHX Text
MOUNTED 42" AFF.
AutoCAD SHX Text
COMMUNICATION OUTLET.
AutoCAD SHX Text
RECEPTACLE/DATA COMMUNICATION OUTLET.
AutoCAD SHX Text
RACEWAY AS INDICATED.
AutoCAD SHX Text
CEILING OR WALL MOUNTED JUNCTION BOX. UON SIZE AS REQUIRED
AutoCAD SHX Text
BY NEC.
AutoCAD SHX Text
480/277V, DISTRIBUTION PANELBOARD.
AutoCAD SHX Text
SPLIT RECEPTACLE. 20A 120V UON CENTERLINE MOUNTED 18" AFF
AutoCAD SHX Text
CONTROLLED DUPLEX RECEPTACLE. 20A 120V UON CENTERLINE MOUNTED 18" AFF
AutoCAD SHX Text
CONTROLLED QUAD RECEPTACLE OUTLET. 20A 120V UON CENTERLINE
AutoCAD SHX Text
MOUNTED 18" AFF.
AutoCAD SHX Text
CONTROLLED DUPLEX RECEPTACLE OUTLET. 20A 120V UON CENTERLINE MOUNTED
AutoCAD SHX Text
CONTROLLED QUAD RECEPTACLE OUTLET. 20A 120V UON CENTERLINE
AutoCAD SHX Text
MOUNTED 42" AFF.
AutoCAD SHX Text
MOTOR STARTING SWITCH - UON CENTERLINE MOUNTED 48" AFF
AutoCAD SHX Text M
AutoCAD SHX Text
42" AFF
AutoCAD SHX Text
%%UDEVICES
AutoCAD SHX Text
- ALL DEVICES ARE WHITE W/PLASTIC COVERS UON. - ALL SWITCHES & ABOVE COUNTER DEVICES ARE @ 48" TOB - ALL RECEPTACLES & DATA OUTLETS ARE @ 20" TOB - A DIFFERENT MOUNTING HEIGHT IS @ TOB - EXTERIOR RECEPTACLES ARE GFCI AND WEATHER RESISTANT. - ALL RECEPTACLES SERVICING LOCATIONS ACCESSIBLE TO CHILDREN SHALL BE TAMPER RESISTANT.
AutoCAD SHX Text THESE ARE STANDARD SYMBOLS AND GENERAL NOTES MAY NOT ALL APPEAR ON THE PROJECT DRAWINGS; HOWEVER WHEREVER THE SYMBOL APPEARS ON THE PROJECT DRAWINGS, THE ITEM SHALL BE PROVIDED AND INSTALLED.
AutoCAD SHX Text
1. CONTRACTOR SHALL BE QUALIFIED TO PERFORM THE WORK SPECIFIED HEREIN CONTRACTOR SHALL BE QUALIFIED TO PERFORM THE WORK SPECIFIED HEREIN AND SHALL BE REGISTERED OR LICENSED IN ACCORDANCE WITH THE LOCAL JURISDICTION REQUIREMENTS. 2. CONTRACTOR SHALL PROVIDE FOR AND ACQUIRE ALL NECESSARY PERMIT(S) AND CONTRACTOR SHALL PROVIDE FOR AND ACQUIRE ALL NECESSARY PERMIT(S) AND INSPECTIONS AS MAY BE REQUIRED BY THE AUTHORITY(IES) HAVING JURISDICTION. 3. INSTALLATION SHALL MEET OR EXCEED THE MINIMUM REQUIREMENTS OF THE INSTALLATION SHALL MEET OR EXCEED THE MINIMUM REQUIREMENTS OF THE APPLICABLE CODES ENFORCE OR ADOPTED BY THE AUTHORITIES HAVING JURISDICTION. 4. NO CHANGE ORDERS - THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND NO CHANGE ORDERS - THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR NECESSARY FOR THE INSTALLATION OF A COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEM MEETING THE INTENDED PURPOSE OF THE PROJECT. 5. THE CONTRACTOR SHALL MAKE A THOROUGH EXAMINATION OF THE SITE THE CONTRACTOR SHALL MAKE A THOROUGH EXAMINATION OF THE SITE CONDITIONS AND CONTRACT DOCUMENTS. 6. PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL COORDINATE WITH THE PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE UTILITIES FOR METERING, TRANSFORMER AND SERVICE CONNECTION REQUIREMENTS. 7. CONDUIT SHALL BE INSTALLED CONCEALED OR RECESSED IN A NEAT AND CONDUIT SHALL BE INSTALLED CONCEALED OR RECESSED IN A NEAT AND WORKMANLIKE MANNER. ALL CONDUIT SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO BUILDING LINES UNLESS OTHERWISE APPROVED BY OWNER. EXPOSED CONDUIT ON EXTERIOR WALLS OF FINISHED WALLS IS PROHIBITED UNLESS OTHERWISE REVIEWED AND APPROVED BY OWNER. 8. CONDUIT SHALL BE EMT AND FITTINGS SHALL BE STEEL. FOR UNDERGROUND AND CONDUIT SHALL BE EMT AND FITTINGS SHALL BE STEEL. FOR UNDERGROUND AND UNDER SLAB INSTALLATIONS, CONDUIT SHALL BE PVC OR IMC W/AN ASPHALTIC OR OTHER APPROVED CORROSION INHIBITING COATING. 9. TO LIMIT WATER INTRUSION, SEAL ALL CONDUITS WHERE THE CONDUIT CONNECTS TO LIMIT WATER INTRUSION, SEAL ALL CONDUITS WHERE THE CONDUIT CONNECTS AN INTERIOR CONDUIT BODY TO AN EXTERIOR CONDUIT BODY OR LUMINAIRE. 10. PROVIDE AN INDEPENDENT MEANS OF SUPPORT FOR CONDUIT INSTALLED ABOVE PROVIDE AN INDEPENDENT MEANS OF SUPPORT FOR CONDUIT INSTALLED ABOVE A CEILING WHERE THEY ARE DISTINGUISHABLE BY COLOR, TAGGING OR OTHER EFFECTIVE MEANS. THE CEILING SUPPORT SYSTEM SHALL BE PERMITTED TO SUPPORT BRANCH CIRCUIT WIRING WHERE INSTALLED IN ACCORDANCE WITH THE CEILING MANUFACTURER'S INSTRUCTIONS. 11. PROVIDE AN INSULATED THROAT FITTING OR PLASTIC BUSHING FOR ALL 1" AND PROVIDE AN INSULATED THROAT FITTING OR PLASTIC BUSHING FOR ALL 1" AND LARGER CONDUIT TERMINATIONS IN PANEL BOARDS, LOAD CENTERS, WIREWAYS AND DISCONNECT SWITCHES. 12. PROVIDE GROUNDING BUSHINGS FOR ANY CONDUIT TERMINATIONS AT ECCENTRIC PROVIDE GROUNDING BUSHINGS FOR ANY CONDUIT TERMINATIONS AT ECCENTRIC AND CONCENTRIC KNOCKOUTS IN DISCONNECTS, PANELBOARDS AND LOAD CENTERS OR WHEN REDUCING WASHERS ARE USED. BOND ALL JUNCTION AND PULL BOXES TO GROUND. 13. WIRE/CABLES SHALL BE COPPER OR ALUMINUM AS ALLOWED BY CODE AND WIRE/CABLES SHALL BE COPPER OR ALUMINUM AS ALLOWED BY CODE AND LISTED FROM THE INTENDED USE AND ENVIRONMENT. AMPACITIES ARE CALCULATED USING THE 75°C COLUMN. 14. REFER TO BRANCH CIRCUIT SCHEDULE FOR MAXIMUM LENGTHS OF CONDUCTOR REFER TO BRANCH CIRCUIT SCHEDULE FOR MAXIMUM LENGTHS OF CONDUCTOR SIZE FOR HOMERUNS. 15. ALL WIRING DEVICES SHALL BE TERMINATED AT THE SCREW IN A CLOCKWISE ALL WIRING DEVICES SHALL BE TERMINATED AT THE SCREW IN A CLOCKWISE DIRECTION. THE PUSH-IN TERMINATIONS SHALL NOT BE USED. 16. VERIFY DOOR SWINGS AND BACKSPLASH HEIGHTS AT ROUGH IN. VERIFY DOOR SWINGS AND BACKSPLASH HEIGHTS AT ROUGH IN. 17. STAGGER WALL BOXES IN ALL WALLS BY AT LEAST ONE STUD FOR SOUND STAGGER WALL BOXES IN ALL WALLS BY AT LEAST ONE STUD FOR SOUND ATTENUATION. APPLY NECESSARY FIRE PROOFING OR SOUND INSULATION AS REQUIRED OR AS LISTED ON ARCHITECTURAL PLANS. 18. PROVIDE A TYPED PANEL SCHEDULE REFLECTING INSTALLED CONDITIONS FOR ALL PROVIDE A TYPED PANEL SCHEDULE REFLECTING INSTALLED CONDITIONS FOR ALL PANEL BOARDS WITH "SPACE" OR "SPARE" PERMANENTLY WRITTEN. 19. SUPPORT WIRES FOR ELECTRICAL EQUIPMENT SHALL BE FASTENED AT BOTH ENDS SUPPORT WIRES FOR ELECTRICAL EQUIPMENT SHALL BE FASTENED AT BOTH ENDS SO AS TO BE TAUT. INSTALLATION OF ELECTRICAL CABLES AND CONDUIT SHALL BE SUCH THAT UNDULATIONS ARE KEPT TO A MINIMUM. 20. "TYPICAL" NOTES APPLY TO ALL SIMILAR SITUATIONS. "TYPICAL" NOTES APPLY TO ALL SIMILAR SITUATIONS. 21. PERMANENTLY LABEL ALL JUNCTION BOX COVERS WITH CIRCUITS DESIGNATION PERMANENTLY LABEL ALL JUNCTION BOX COVERS WITH CIRCUITS DESIGNATION (SOURCE, PHASE, ETC.) CONTAINED WITHIN. 22. AT CONCLUSION OF PROJECT, PROVIDE OPERATING, INSTALLATION INSTRUCTIONS, AT CONCLUSION OF PROJECT, PROVIDE OPERATING, INSTALLATION INSTRUCTIONS, AND WARRANTY DOCUMENTS TO THE OWNER FOR ALL INSTALLED EQUIPMENT. OPERATING, INSTALLATION, AND WARRANTY DOCUMENTS SHALL BE BOUND TOGETHER WITH INDEX INDICATING WHERE TO FIND INFORMATION ON THE VARIOUS EQUIPMENT. 23. PROVIDE THE APPROPRIATE FIRE STOP SYSTEM AND/OR FIRE CAULK AT ANY PROVIDE THE APPROPRIATE FIRE STOP SYSTEM AND/OR FIRE CAULK AT ANY PENETRATION BETWEEN RATED ASSEMBLIES. 24. CONDUIT TERMINATION AT NEMA3R ENCLOSURES SHALL BE WITH MYERS HUBS CONDUIT TERMINATION AT NEMA3R ENCLOSURES SHALL BE WITH MYERS HUBS FOR TOP PENETRATIONS AND LIQUID TIGHT SEALING RINGS OR SEALING LOCKNUTS FOR SIDE PENETRATIONS. 25. FOR ALL LED LUMINAIRES, PERMANENTLY MARK EACH FIXTURE WITH TAG #, FOR ALL LED LUMINAIRES, PERMANENTLY MARK EACH FIXTURE WITH TAG #, MANUFACTURER, MODEL NUMBER, INSTALLATION DATE, INSTALLING CONTRACTOR AND LENGTH OF MANUFACTURER'S WARRANTY. 26. COORDINATE INSTALLATION OF RECEPTACLES SHOWN ADJACENT TO MILLWORK WITH COORDINATE INSTALLATION OF RECEPTACLES SHOWN ADJACENT TO MILLWORK WITH ARCHITECTURAL ELEVATIONS SO THEY ARE ACCESSIBLE. LOCATIONS SHOWN ON PLAN ARE DIAGRAMMATIC. 27. INSTALL ELECTRICAL HARDWARE SUPPORTING ELECTRICAL FED AND OTHER INSTALL ELECTRICAL HARDWARE SUPPORTING ELECTRICAL FED AND OTHER EQUIPMENT IN ACCORDANCE WITH THE WEIGHT REQUIREMENTS OF THE EQUIPMENT, FIXTURE, APPLIANCE, ETC. 28. ALL EXHAUST FANS SHALL BE POWERED FROM NEAREST LIGHTING CIRCUIT UON, ALL EXHAUST FANS SHALL BE POWERED FROM NEAREST LIGHTING CIRCUIT UON, AND SHALL HAVE A 20A MOTOR RATED TOGGLE DISCONNECT SWITCH IN A NEMA 1 RATED ENCLOSURE. 29. ALL CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS. ALL CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS. 120/208V 277/480V 277/480V PHASE A BLACK BROWN BLACK BROWN BROWN PHASE B RED ORANGE RED ORANGE ORANGE PHASE C BLUE YELLOWBLUE YELLOWYELLOW
AutoCAD SHX Text
%%UELECTRIC NOTES
AutoCAD SHX Text 2020 FLORIDA BUILDING CODE 7TH EDITION 2020 FLORIDA FIRE PREVENTION CODE 7TH EDITION WITH NFPA 1 AND 101 AMENDMENTS NFPA 70, 2017 NATIONAL ELECTRICAL CODE NFPA 72, 2016 FIRE ALARM & SIGNALING NFPA 101, 2018 LIFE SAFETY CODE, FL EDITION NFPA 110, 2016 EMERGENCY & STANDBY SYSTEMS ASME A17.1/CSA B44, 2016 ASME A17.2, 2017 , 2017 ASME A17.3, 2015 FLORIDA ELEVATOR SAFETY CODE RULE:61C-5,FLORIDA ADMINISTRATIVE CODE 2021 FLORIDA STATUTE CHAPTER 399, ELEVATOR SAFETY 2021 FLORIDA STATUTE CHAPTER 553, BUILDING CONSTRUCTION STANDARDS ADAAG, AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES NFPA 80, FIRE DOORS AND WINDOWS ANSI/UL 10B, FIRE TESTS OF DOOR ASSEMBLIES O.S.H.A. REQUIREMENTS FOR CONSTRUCTION AND REPAIRS OF EXISTING BUILDINGS ELEVATOR INDUSTRY FIELD EMPLOYEES' SAFETY HANDBOOK 2015
AutoCAD SHX Text
14400 49TH STREET N.
AutoCAD SHX Text
CLEARWATER, FL 33762
AutoCAD SHX Text 12-01-2022
AutoCAD SHX Text 231119
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS
AutoCAD SHX Text Drawing Progress:
AutoCAD SHX Text
DRAWING TITLE :
AutoCAD SHX Text
DESIGNED BY: JO/SN
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
CHECKED BY: LV/SJ
AutoCAD SHX Text
CADDED BY: SS
AutoCAD SHX Text
PLOT SIZE:
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
COMMENTS:
AutoCAD SHX Text
REVISION
AutoCAD SHX Text Board of Professional Engineers - License # 27336
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
FAX (813) 241-6498
AutoCAD SHX Text
3203 QUEEN PALM DRIVE
AutoCAD SHX Text
TAMPA, FLORIDA 33619
AutoCAD SHX Text
PHONE (813) 241-6488
AutoCAD SHX Text
PROFESSIONAL ENGINEERS
AutoCAD SHX Text Signature
AutoCAD SHX Text Date
AutoCAD SHX Text
KPI ENGINEERING, INC.
AutoCAD SHX Text
LUIS G. VARGAS JR, P.E.
AutoCAD SHX Text FL. Lic. No. 52139 Exp 02-28-2025
AutoCAD SHX Text
ALL RIGHTS RESERVED
AutoCAD SHX Text
2022 KPI ENGINEERING, INCORPORATED
AutoCAD SHX Text C
AutoCAD SHX Text
LEGENDS, ABBREVIATIONS
AutoCAD SHX Text
AND GENERAL NOTES
AutoCAD SHX Text E0.1
LL
AS
C O
UN
TY
J
AI
L
LO
BB
Y
EL
EV
AT
O
R M
O
DE
RN
IZ
AT
IO
N
AutoCAD SHX Text
EXISTING DUPLEX INMATE PASSENGER ELEVATOR TO BE REPLACED
AutoCAD SHX Text
EXISTING SINGLE PUBLIC PASSENGER ELEVATOR TO BE REPLACED
AutoCAD SHX Text
MCC-1
AutoCAD SHX Text T-2
AutoCAD SHX Text
TRANSFER
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
FEH1
AutoCAD SHX Text T-1
AutoCAD SHX Text
1LEC1
AutoCAD SHX Text
1LN1
AutoCAD SHX Text
1LN2
AutoCAD SHX Text
FEH2
AutoCAD SHX Text T-9
AutoCAD SHX Text
1LC1
AutoCAD SHX Text
1LC2
AutoCAD SHX Text
EH1
AutoCAD SHX Text
SWBD
AutoCAD SHX Text
EHC1
AutoCAD SHX Text
SWBD-1
AutoCAD SHX Text
SWBD-2
AutoCAD SHX Text
MCC-2
AutoCAD SHX Text
14400 49TH STREET N.
AutoCAD SHX Text
CLEARWATER, FL 33762
AutoCAD SHX Text 12-01-2022
AutoCAD SHX Text 231119
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS
AutoCAD SHX Text Drawing Progress:
AutoCAD SHX Text
DRAWING TITLE :
AutoCAD SHX Text
DESIGNED BY: JO/SN
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
CHECKED BY: LV/SJ
AutoCAD SHX Text
CADDED BY: SS
AutoCAD SHX Text
PLOT SIZE:
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
COMMENTS:
AutoCAD SHX Text
REVISION
AutoCAD SHX Text Board of Professional Engineers - License # 27336
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
FAX (813) 241-6498
AutoCAD SHX Text
3203 QUEEN PALM DRIVE
AutoCAD SHX Text
TAMPA, FLORIDA 33619
AutoCAD SHX Text
PHONE (813) 241-6488
AutoCAD SHX Text
PROFESSIONAL ENGINEERS
AutoCAD SHX Text Signature
AutoCAD SHX Text Date
AutoCAD SHX Text
KPI ENGINEERING, INC.
AutoCAD SHX Text
LUIS G. VARGAS JR, P.E.
AutoCAD SHX Text FL. Lic. No. 52139 Exp 02-28-2025
AutoCAD SHX Text
ALL RIGHTS RESERVED
AutoCAD SHX Text
2022 KPI ENGINEERING, INCORPORATED
AutoCAD SHX Text C
AutoCAD SHX Text
OVERALL 1ST FLOOR PLAN
AutoCAD SHX Text E1.0
AutoCAD SHX Text
OVERALL BUILDING FLOOR PLAN
NOT TO SCALE
LL
AS
C O
UN
TY
J
AI
L
LO
BB
Y
EL
EV
AT
O
R M
O
DE
RN
IZ
AT
IO
N
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
FCU P-2
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
FCU P-1
AutoCAD SHX Text P
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EXISTING PANEL 'HR1' FED FROM SWBD-1 TO REMAIN
AutoCAD SHX Text
EXISTING ELEV. EQUIPMENT ROOM FAN COIL UNIT DISC. TO REMAIN.
AutoCAD SHX Text EXISTING ELEV. CAB #1 LIGHTING DISC. TO REMAIN. CONTRACTOR SHALL VERIFY WORKING CONDITION OF EQ.
AutoCAD SHX Text EXISTING ELEV. CAB #2 LIGHTING DISC. TO REMAIN. CONTRACTOR SHALL VERIFY WORKING CONDITION OF EQ.
AutoCAD SHX Text
EXISTING FREIGHT ELEVATOR CAB CARD ACCESS CABINET #1 TO REMAIN
AutoCAD SHX Text
ELEVATOR CAR #1 TO BE DEMOLISHED
AutoCAD SHX Text
ELEVATOR CAR #2 TO BE DEMOLISHED
AutoCAD SHX Text EXISTING 60HP ELEV. CAB #2 (SN#55712) MOTOR AND PULLEY ASSEMBLY TO BE DEMOLISHED.
AutoCAD SHX Text
EXISTING PASSENGER ELEVATOR CAB DATA/PHONE WIREWAY TO REMAIN.
AutoCAD SHX Text EXISTING 60HP ELEV. CAB #1 (SN#55711) MOTOR AND PULLEY ASSEMBLY TO BE DEMOLISHED.
AutoCAD SHX Text
EXISTING FCU P-1 TO REMAIN.
AutoCAD SHX Text
ELEVATOR CAR #4 TO BE DEMOLISHED
AutoCAD SHX Text EXISTING 30HP ELEV. CAB #4 (SN#55710) MOTOR AND PULLEY ASSEMBLY TO BE DEMOLISHED.
AutoCAD SHX Text
EXISTING ELEV. EQUIPMENT ROOM FAN COIL UNIT DISC. TO REMAIN
AutoCAD SHX Text EXISTING ELEV. CAB #4 LIGHTING DISC. TO REMAIN. CONTRACTOR SHALL VERIFY WORKING CONDITION OF EQ.
AutoCAD SHX Text EXISTING ELEV. CAB #4 DISC. TO REMAIN. CONTRACTOR SHALL VERIFY WORKING CONDITION OF EQ.
AutoCAD SHX Text
EXISTING PASSENGER ELEVATOR CAB DATA/PHONE WIREWAY TO REMAIN.
AutoCAD SHX Text
EXISTING FCU P-2 TO REMAIN.
AutoCAD SHX Text
(NOT IN SCOPE OR WORK)
AutoCAD SHX Text
14400 49TH STREET N.
AutoCAD SHX Text
CLEARWATER, FL 33762
AutoCAD SHX Text 12-01-2022
AutoCAD SHX Text 231119
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS
AutoCAD SHX Text Drawing Progress:
AutoCAD SHX Text
DRAWING TITLE :
AutoCAD SHX Text
DESIGNED BY: JO/SN
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
CHECKED BY: LV/SJ
AutoCAD SHX Text
CADDED BY: SS
AutoCAD SHX Text
PLOT SIZE:
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
COMMENTS:
AutoCAD SHX Text
REVISION
AutoCAD SHX Text Board of Professional Engineers - License # 27336
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
FAX (813) 241-6498
AutoCAD SHX Text
3203 QUEEN PALM DRIVE
AutoCAD SHX Text
TAMPA, FLORIDA 33619
AutoCAD SHX Text
PHONE (813) 241-6488
AutoCAD SHX Text
PROFESSIONAL ENGINEERS
AutoCAD SHX Text Signature
AutoCAD SHX Text Date
AutoCAD SHX Text
KPI ENGINEERING, INC.
AutoCAD SHX Text
LUIS G. VARGAS JR, P.E.
AutoCAD SHX Text FL. Lic. No. 52139 Exp 02-28-2025
AutoCAD SHX Text
ALL RIGHTS RESERVED
AutoCAD SHX Text
2022 KPI ENGINEERING, INCORPORATED
AutoCAD SHX Text C
AutoCAD SHX Text
ELECTRICAL DEMOLITION
AutoCAD SHX Text
FLOOR PLAN
AutoCAD SHX Text E2.1
AutoCAD SHX Text
ELECTRICAL DEMOLITION FLOOR PLAN
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
%%UGENERAL DEMOLITION NOTES
1. INFORMATION SHOWN HERE REFLECTS EXISTING RECORDS AND RECENT ON-SITE OBSERVATIONS. THE INFORMATION SHOWN HERE REFLECTS EXISTING RECORDS AND RECENT ON-SITE OBSERVATIONS. THE DEMOLITION WORK SHOWN IS INTENDED TO CONVEY THE GENERAL NATURE AND SCOPE OF THE WORK REQUIRED. SOME EXISTING BUILDING CONDITIONS FOR ELECTRICAL, PLUMBING, MECHANICAL AND FIRE PROTECTION SYSTEMS USED IN THE DESIGN OF THIS PROJECT ARE ASSUMED. ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED BY THE INSTALLING CONTRACTOR PRIOR TO COMMENCEMENT OF WORK. THE CONTRACTOR SHALL PERFORM ALL DEMOLITION WORK NECESSARY TO PROPERLY COMPLETE THE NEW WORK SHOWN ELSEWHERE. ALL NEW WORK AND EXISTING SYSTEMS OR EQUIPMENT INDICATED TO REMAIN OR BE RELOCATED SHALL BE IN COMPLIANCE WITH OWNER REQUIREMENTS AND COORDINATED WITH THE OWNER'S REPRESENTATIVE. ANY DISCREPANCIES SHALL BE REPORTED TO OWNER'S REPRESENTATIVE. 2. PROVIDE TEMPORARY MECHANICAL, ELECTRICAL AND LIGHTING EQUIPMENT AS NECESSARY TO MAINTAIN PROVIDE TEMPORARY MECHANICAL, ELECTRICAL AND LIGHTING EQUIPMENT AS NECESSARY TO MAINTAIN PROPER OPERATION OF ALL SYSTEMS AND PROVIDE FOR WORKER SAFETY. 3. PATCH AND REPAIR EXISTING SURFACES TO REMAIN THAT MAY BE DAMAGED BY THE PERFORMANCE OF PATCH AND REPAIR EXISTING SURFACES TO REMAIN THAT MAY BE DAMAGED BY THE PERFORMANCE OF THE DEMOLITION WORK. 4. PROTECT REMAINING EQUIPMENT, PIPING, DUCTWORK, CONDUIT ETC. FROM THE ENTRANCE OF FOREIGN PROTECT REMAINING EQUIPMENT, PIPING, DUCTWORK, CONDUIT ETC. FROM THE ENTRANCE OF FOREIGN MATERIALS. 5. PROVIDE PLASTIC SHEETING AND SEALING AROUND DOORS AND OPENINGS TO PROTECT ADJACENT AREAS PROVIDE PLASTIC SHEETING AND SEALING AROUND DOORS AND OPENINGS TO PROTECT ADJACENT AREAS FROM THE SPREAD OF DUST AND DEMOLITION DEBRIS TO OCCUPIED AREAS OF THE BUILDING. KEEP ALL ADJOINING AREAS ADJACENT TO THE WORK AREA CLEAN AND FREE OF DEBRIS. 6. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL SYSTEMS BEING REMOVED. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL SYSTEMS BEING REMOVED. 7. REMOVE ALL EXISTING CONDUIT, WIRING, ETC. THAT IS NOT REQUIRED TO SUPPORT THE PROPER REMOVE ALL EXISTING CONDUIT, WIRING, ETC. THAT IS NOT REQUIRED TO SUPPORT THE PROPER OPERATION OF THE NEW SYSTEMS AND EXISTING SYSTEMS TO REMAIN. INCLUSIVE OF ALL WALL THAT HAVE RECEPTACLES OR DATA JACKS SHOWN TO BE DEMOLISHED.
LL
AS
C O
UN
TY
J
AI
L
LO
BB
Y
EL
EV
AT
O
R M
O
DE
RN
IZ
AT
IO
N
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
FCU P-2
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
ELEVATOR PULLEY
AutoCAD SHX Text
FCU P-1
AutoCAD SHX Text
NOTE: ALL EMERGENCY LIGHTING SHALL BE TESTED FOR PROPER OPERATION, TYPICAL
AutoCAD SHX Text P
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
EXISTING ELEV. EQUIPMENT ROOM FAN COIL UNIT DISC. TO REMAIN.
AutoCAD SHX Text
EXISTING PASSENGER ELEVATOR CAB DATA/PHONE WIREWAY TO REMAIN.
AutoCAD SHX Text
EXISTING ELEV. EQUIPMENT ROOM FAN COIL UNIT DISC. TO REMAIN
AutoCAD SHX Text
EXISTING PASSENGER ELEVATOR CAB DATA/PHONE WIREWAY TO REMAIN.
AutoCAD SHX Text
EXISTING CAB#2 LIGHTING DISC. (LOCKABLE) NEMA 1 30/1/20 7LC1-13
AutoCAD SHX Text
EXISTING CAB#1 LIGHTING DISC. (LOCKABLE) NEMA 1 30/1/20 7LC1-11
AutoCAD SHX Text
ELEVATOR MAIN SAFETY SWITCH(EXISTING)
AutoCAD SHX Text PROVIDE NEW FEEDER TO NEW ELEVATOR HOIST MOTOR AND SAFETY DISCONNECT IN HOISTWAY, REFER TO RISER DIAGRAM FOR FEEDER INFORMATION. PROVIDE NEW FUSES AS REQUIRED
AutoCAD SHX Text
ELEVATOR CAB SAFETY SWITCH(EX) 30/1/20 (LOCKABLE) NEMA 1 7LC1-12
AutoCAD SHX Text ELEVATOR CONTROLLER (NEW) PROVIDE NEW ELEVATOR CONTROLLER CAPABLE OF REQUIRED EMERGENCY POWER OPERATION
AutoCAD SHX Text ELEVATOR CONTROLLER (NEW) PROVIDE PROVIDE NEW ELEVATOR CONTROLLER CAPABLE OF REQUIRED EMERGENCY POWER OPERATION. CONTRACTOR SHALL COORDINATE WITH FINAL SHOP DRAWINGS TO MAINTAIN ALL WORKING CLEARANCES BETWEEN EQUIPMENT (TYP).
AutoCAD SHX Text EXTEND EXISTING WIREWAY AS REQUIRED. COORDINATE WITH IT DEPARTMENT FOR REQUIREMENTS
AutoCAD SHX Text EXTEND EXISTING WIREWAY AS REQUIRED. COORDINATE WITH IT DEPARTMENT REQUIREMENTS FOR REQUIREMENTS
AutoCAD SHX Text
EXISTING FREIGHT ELEVATOR CAB CARD ACCESS CABINET #1 TO REMAIN
AutoCAD SHX Text
60HP
AutoCAD SHX Text
60HP
AutoCAD SHX Text
30HP
AutoCAD SHX Text
NEW ELEV. MOTOR/ PULLEY CAR #1
AutoCAD SHX Text
NEW ELEV. MOTOR/ PULLEY CAR #2
AutoCAD SHX Text
ELEV. CAR #1
AutoCAD SHX Text
ELEV. CAR #2
AutoCAD SHX Text
NEW ELEV. #1 CONTROLLER
AutoCAD SHX Text
NEW ELEV. #2 CONTROLLER
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text PROVIDE NEW DEVICES FOR ELEVATOR RECALL AND MONITORING SYSTEM IS SIMPLEX #4002 CONNECT TO F/A EXISTING ZONE
AutoCAD SHX Text
FIRE ALARM EQUIPMENT (NEW)
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text PROVIDE NEW DEVICES FOR ELEVATOR RECALL AND MONITORING SYSTEM IS SIMPLEX #4002 CONNECT TO F/A EXISTING ZONE
AutoCAD SHX Text
FIRE ALARM EQUIPMENT (NEW)
AutoCAD SHX Text
WP/GFI
AutoCAD SHX Text
WP/GFI
AutoCAD SHX Text
%%USP
AutoCAD SHX Text
(EXISTING CIRCUIT)
AutoCAD SHX Text
%%UELEVATOR PIT PLAN
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
WP
AutoCAD SHX Text
'PL'
AutoCAD SHX Text
'PL'
AutoCAD SHX Text
EQUAL REPLACEMENT
AutoCAD SHX Text
%%UNEW SUMP PUMP W/ CORD AND PLUG
AutoCAD SHX Text
LEVITON #G5362-WTR OR EQUAL
AutoCAD SHX Text
%%UNEW GFCI TYPE RECEPTACLES W/ WEATHERPROOF COVER (TYPICAL)
AutoCAD SHX Text
NOTE: ELEVATOR PIT IS NOT SPRINKLERED.
AutoCAD SHX Text
WP/GFI
AutoCAD SHX Text
%%UELEVATOR TOP SHAFT PLAN
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
WP
AutoCAD SHX Text
'PL'
AutoCAD SHX Text
NOTE: ELEVATOR HOISTWAY IS NOT SPRINKLERED.
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
LEVITON #1221-2R OR EQUAL
AutoCAD SHX Text
%%UNEW MANUAL TOGGLE SWITCH W/ WEATHERPROOF COVER (TYPICAL)
AutoCAD SHX Text
LEVITON #1221-2R OR EQUAL
AutoCAD SHX Text
%%UNEW MANUAL TOGGLE SWITCH W/ WEATHERPROOF COVER (TYPICAL)
AutoCAD SHX Text
NEW FEEDER, 2-#12 CU+#12 CU GND IN 3/4" CONDUIT
AutoCAD SHX Text
NEW FEEDER, 2-#12 CU+#12 CU GND IN 3/4" CONDUIT
AutoCAD SHX Text min 19fc
AutoCAD SHX Text min 19fc
AutoCAD SHX Text NOTE: ELEVATOR CONTRACTOR SHALL PROVIDE NEW ELEVATOR HOISTWAY ACCESS SWITCH PER ASME A17.1.
AutoCAD SHX Text NOTE: ELEVATOR CONTRACTOR SHALL PROVIDE NEW ELEVATOR HOISTWAY ACCESS SWITCH PER ASME A17.1.
AutoCAD SHX Text NOTE: ELEVATOR HALL STATIONS AND ALL CONTROLS SHALL BE PROVIDED NEW PER FINAL CONTRACT.
AutoCAD SHX Text NOTE: ELEVATOR HALL STATIONS AND ALL CONTROLS SHALL BE PROVIDED NEW PER FINAL CONTRACT.
AutoCAD SHX Text NEW VAPORTIGHT FIXTURE (TYPICAL) CREE #C-VT-B-SMWL-19L-50K-GR OR EQUAL VERTICAL SPACING NOT TO EXCEED 7FT
AutoCAD SHX Text NEW VAPORTIGHT FIXTURE (TYPICAL) CREE #C-VT-B-SMWL-19L-50K-GR OR EQUAL VERTICAL SPACING NOT TO EXCEED 7FT
AutoCAD SHX Text
SMOKE DETECTOR (EXISTING) F/A EXISTING ZONE
AutoCAD SHX Text P
AutoCAD SHX Text
TYPICAL ELEVATOR HALL LANTER TO BE REPALCED WITH NEW PER ELEVATOR SPECS.
AutoCAD SHX Text
EXISTING PULL STATION TO REMAIN
AutoCAD SHX Text
TYPICAL ELEVATOR FLOOR INDICATOR LIGHT TO BE REPLACED PER ELEVATOR SPECS.
AutoCAD SHX Text
EXISTING KEYED ELEVATOR ACCESS CALL SWITCH TO BE REPLACED
AutoCAD SHX Text EXISTING CARD READER TO REMAIN, COORDINATE WORK COUNTY IT DEPARTMENT FOR RECONNECTION.
AutoCAD SHX Text P
AutoCAD SHX Text
TYPICAL ELEVATOR HALL LANTER TO BE REPALCED WITH NEW PER ELEVATOR SPECS.
AutoCAD SHX Text
EXISTING PULL STATION TO REMAIN
AutoCAD SHX Text
TYPICAL ELEVATOR FLOOR INDICATOR LIGHT TO BE REPLACED PER ELEVATOR SPECS.
AutoCAD SHX Text
EXISTING KEYED ELEVATOR ACCESS CALL SWITCH TO BE REPLACED
AutoCAD SHX Text
14400 49TH STREET N.
AutoCAD SHX Text
CLEARWATER, FL 33762
AutoCAD SHX Text 12-01-2022
AutoCAD SHX Text 231119
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS
AutoCAD SHX Text Drawing Progress:
AutoCAD SHX Text
DRAWING TITLE :
AutoCAD SHX Text
DESIGNED BY: JO/SN
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
CHECKED BY: LV/SJ
AutoCAD SHX Text
CADDED BY: SS
AutoCAD SHX Text
PLOT SIZE:
AutoCAD SHX Text
FILE NAME:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
COMMENTS:
AutoCAD SHX Text
REVISION
AutoCAD SHX Text Board of Professional Engineers - License # 27336
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
FAX (813) 241-6498
AutoCAD SHX Text
3203 QUEEN PALM DRIVE
AutoCAD SHX Text
TAMPA, FLORIDA 33619
AutoCAD SHX Text
PHONE (813) 241-6488
AutoCAD SHX Text
PROFESSIONAL ENGINEERS
AutoCAD SHX Text Signature
AutoCAD SHX Text Date
AutoCAD SHX Text
KPI ENGINEERING, INC.
AutoCAD SHX Text
LUIS G. VARGAS JR, P.E.
AutoCAD SHX Text FL. Lic. No. 52139 Exp 02-28-2025
AutoCAD SHX Text
ALL RIGHTS RESERVED
AutoCAD SHX Text
2022 KPI ENGINEERING, INCORPORATED
AutoCAD SHX Text C
AutoCAD SHX Text
ELECTRICAL CONSTRUCTION
AutoCAD SHX Text
FLOOR PLAN
AutoCAD SHX Text E3.1
AutoCAD SHX Text
ELECTRICAL CONSTRUCTION FLOOR PLAN
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
%%UGENERAL NEW CONSTRUCTION NOTES
AutoCAD SHX Text
1. TRACE ALL EXISTING CIRCUITS AND RECORD PANEL NAME AND CIRCUIT ON EACH JUNCTION BOX. UPDATE ALL TRACE ALL EXISTING CIRCUITS AND RECORD PANEL NAME AND CIRCUIT ON EACH JUNCTION BOX. UPDATE ALL PANELBOARD DIRECTORIES AS CIRCUITS ARE IDENTIFIED 2. ALL EQUIPMENT SHALL BE PROVIDED NEW EXCEPT WHERE SHOWN TO BE RELOCATED ALL EQUIPMENT SHALL BE PROVIDED NEW EXCEPT WHERE SHOWN TO BE RELOCATED 3. COORDINATE ALL INSTALLATION REQUIREMENTS OF EQUIPMENT ADJACENT OR WITHIN CASEWORK/MILLWORK WITH VENDOR COORDINATE ALL INSTALLATION REQUIREMENTS OF EQUIPMENT ADJACENT OR WITHIN CASEWORK/MILLWORK WITH VENDOR SHOP DRAWINGS PRIOR TO ROUGH-IN 4. NEW DEVICES SHALL UTILIZE EXISTING RACEWAYS WHERE AVAILABLE NEW DEVICES SHALL UTILIZE EXISTING RACEWAYS WHERE AVAILABLE 5. LIGHTING FIXTURES AND CONTROLS SHALL BE COORDINATED WITH EXISTING CIRCUITING SERVING EACH ROOM - LIGHTING FIXTURES AND CONTROLS SHALL BE COORDINATED WITH EXISTING CIRCUITING SERVING EACH ROOM - OCCUPANCY SENSORS SHALL BE FAIL SAFE DEVICES (IF INOPERABLE, LIGHTS WILL BE ON) 5.1. PROVIDE MARKED UP DRAWINGS SHOWING CIRCUIT SERVING EACH ROOM FOR DOCUMENTATION OF AS-BUILT PROVIDE MARKED UP DRAWINGS SHOWING CIRCUIT SERVING EACH ROOM FOR DOCUMENTATION OF AS-BUILT CONDITIONS 5.2. NEW COMPATIBLE FEEDER AND CONTROL WIRING SHALL BE PROVIDED WHERE REQUIRED BY NEW APPROVED NEW COMPATIBLE FEEDER AND CONTROL WIRING SHALL BE PROVIDED WHERE REQUIRED BY NEW APPROVED EQUIPMENT 6. FINAL COMMISSIONING REPORT, OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE BUILDING OWNER FINAL COMMISSIONING REPORT, OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE BUILDING OWNER OR OWNER'S AUTHORIZED AGENT WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY PER FBC ENERGY CONSERVATION SECTION C408.3.2. 7. TESTING OF ALL EMERGENCY LIGHTING EQUIPMENT SHALL BE PERFORMED IN ACCORDANCE WITH 2018 NFPA 101 CH. TESTING OF ALL EMERGENCY LIGHTING EQUIPMENT SHALL BE PERFORMED IN ACCORDANCE WITH 2018 NFPA 101 CH. 7.9.3. - ENSURE EMERGENCY LIGHTS ARE SERVED FROM LOCAL (WITHIN ROOM OR AREA) CIRCUIT SUCH THAT IN THE EVENT OF AN OUTAGE TO THE CIRCUIT, EMERGENCY LIGHTS WILL OPERATE IN ACCORDANCE WITH NEC 700.12(F). 8. ALL EXTERIOR EGRESS LIGHTING IS EXISTING TO REMAINALL EXTERIOR EGRESS LIGHTING IS EXISTING TO REMAIN
AutoCAD SHX Text
%%UGENERAL NEW CONSTRUCTION NOTES
AutoCAD SHX Text
TYPICAL PUBLIC ELEVATOR LOBBY PLAN
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
TYPICAL INMATE ELEVATOR LOBBY PLAN
SCALE: 1/4"=1'-0"
METER
L
N
E
WHERE DISCREPANCIES BETWEEN ARCHITECTURAL AND ELECTRICAL NOTES OCCUR, THE MORE STRINGENT SHALL APPLY.
PI
NE
LL
AS
C O
UN
TY
J
AI
L
LO
BB
Y
EL
EV
AT
O
R M
O
DE
RN
IZ
AT
IO
N
AutoCAD SHX Text
PAD MOUNTED UTILITY TRANSFORMER 277/480/3 /4W
AutoCAD SHX Text
UTILITY PRIMARY
AutoCAD SHX Text
SECTION 2
AutoCAD SHX Text NOTE: ALL ELECTRICAL EQUIPMENT AND FEEDERS ARE EXISTING TO REMAIN, U.O.N. DISTRIBUTION IS SHOWN FOR REFERENCE ONLY. WHERE ANY DISCREPANCY IS OBSERVED IT SHALL BE COORDINATED WITH FINAL RECORD AS-BUILT DOCUMENTATION.
AutoCAD SHX Text
AUTOMATIC TRANSFER SWITCH 'ATS-E' 1200A MCB 120/208/3 /3W
AutoCAD SHX Text
FROM MAIN/ GEN (EPSS)
AutoCAD SHX Text
EXISTING 277/480/3 /3WDIESEL STATIONARY GENERATOR
AutoCAD SHX Text
(GEN)
AutoCAD SHX Text
MAIN SERVICE DISCONNECT 120/208/3 /4W3000A 3 3000AF
AutoCAD SHX Text
FROM UTILITY
AutoCAD SHX Text
'SERVICE DISCONNECT"
AutoCAD SHX Text
ATS-OS
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
EXISTING NEMA 1 60/3/NF DISC. 30HP PUBLIC PASS. ELEV. (CAR #4)
AutoCAD SHX Text LOAD STATEMENT SCOPE OF WORK SHALL RESULT IN REDUCTION OF LOADS AS INDICATED AT PANELBOARD SCHEDULES ABOVE.
AutoCAD SHX Text
SECTION 3
AutoCAD SHX Text 277/480/3%%C
AutoCAD SHX Text
400A MCB
AutoCAD SHX Text
'HR1'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING FEEDER TO REMAIN
AutoCAD SHX Text
NEW 60HP TRACTION ELEVATOR (CAR #1)
AutoCAD SHX Text
NEW 60HP TRACTION ELEVATOR (CAR #2)
AutoCAD SHX Text EXISTING FEEDERS TO REMAIN, IF FOUND TO BE DAMAGED REPLACE AS NOTED: (4) #3 CU + (1) #6 CU GND IN (1) 2" CONDUIT
AutoCAD SHX Text EXISTING FEEDERS TO REMAIN, IF FOUND TO BE DAMAGED REPLACE AS NOTED: (4) #6 CU + (1) #8 CU GND IN (1) 1" CONDUIT
AutoCAD SHX Text 120/208/3%%C
AutoCAD SHX Text
225A MCB
AutoCAD SHX Text
'7LC1'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISITNG NEMA 1 30/1/20 DISC. CAB LIGHTING DISC. (CAR #2)
AutoCAD SHX Text
EXISITNG NEMA 1 30/1/20 DISC. CAB LIGHTING DISC. (CAR #1)
AutoCAD SHX Text
EXISITNG NEMA 1 30/1/20 DISC. CAB LIGHTING DISC. (CAR #4)
AutoCAD SHX Text EXISTING FEEDERS TO REMAIN, IF FOUND TO BE DAMAGED REPLACE AS NOTED: (3) #12 CU + #12G IN 3/4" CONDUIT.
AutoCAD SHX Text
MAIN ELECTRICAL ROOM
AutoCAD SHX Text
ELEC./MECH. ROOM - N711
AutoCAD SHX Text
FROM 'EH76'
AutoCAD SHX Text
ROOF PENTHOUSE
AutoCAD SHX Text
ROOF PENTHOUSE
AutoCAD SHX Text
%%UGENERAL NOTES
AutoCAD SHX Text COMMERCIAL ELEVATOR MODERNIZATION FOR STANDARD ELECTRIC TRACTION ELEVATOR EQUIPMENT AND CONSTRUCTION: 1. CONSTRUCTION SERVICES: CONSTRUCTION SERVICES: a. REQUIRED ENGINEERING, EQUIPMENT, LABOR, MACHINES, CONTROL SYSTEMS, DEVICES AND ACCESSORIES AS REQUIRED FOR SAFELY OPERATING THE REQUIRED ENGINEERING, EQUIPMENT, LABOR, MACHINES, CONTROL SYSTEMS, DEVICES AND ACCESSORIES AS REQUIRED FOR SAFELY OPERATING THE SPECIFIED ELEVATOR AT RATED SPEED WITH RATED CAPACITIES. REFER TO "SPECIFICATIONS FOR ELEVATOR MODERNIZATION, PINELLAS COUNTY 14 SOUTH FT. HARRISON", PROVIDED BY LIBERTY ELEVATOR CONSULTANTS FOR ADDITIONAL INFORMATION. b. REQUIRED DELIVERY, STAGING, AND HOISTING OF NEW EQUIPMENT. HOISTING, DISMANTLING, REMOVAL AND DISPOSAL OF EXISTING EQUIPMENT. REPAIR, REQUIRED DELIVERY, STAGING, AND HOISTING OF NEW EQUIPMENT. HOISTING, DISMANTLING, REMOVAL AND DISPOSAL OF EXISTING EQUIPMENT. REPAIR, CLEANING AND PAINTING OF REUSABLE EQUIPMENT. c. REQUIRED MATERIALS AND ACCESSORIES AS REQUIRED FOR COMPLETING THE ELEVATOR MODERNIZATION. REQUIRED MATERIALS AND ACCESSORIES AS REQUIRED FOR COMPLETING THE ELEVATOR MODERNIZATION. d. REQUIRED HOISTWAY, PIT AND MACHINE ROOM BARRICADES FOR SAFETY AS REQUIRED. REQUIRED HOISTWAY, PIT AND MACHINE ROOM BARRICADES FOR SAFETY AS REQUIRED. e. REQUIRED HOISTING, HOISTING PERMITS AND TRAFFIC COORDINATION AND/OR PERMITS WITH LOCAL JURISDICTIONS AND THE STATE OF FLORIDA AS REQUIRED HOISTING, HOISTING PERMITS AND TRAFFIC COORDINATION AND/OR PERMITS WITH LOCAL JURISDICTIONS AND THE STATE OF FLORIDA AS REQUIRED. f. REQUIRED PERMITS AND COORDINATION AND/OR PERMITS WITH LOCAL JURISDICTIONS, BUREAU OF ELEVATOR SAFETY AND THE STATE OF FLORIDA AS REQUIRED PERMITS AND COORDINATION AND/OR PERMITS WITH LOCAL JURISDICTIONS, BUREAU OF ELEVATOR SAFETY AND THE STATE OF FLORIDA AS REQUIRED. 2. ELEVATOR CAR AND HOIST WAY SIGNAL EQUIPMENT: ELEVATOR CAR AND HOIST WAY SIGNAL EQUIPMENT: a. CONTRACTOR SHALL PROVIDE NEW ELEVATOR CONTROLLER CAPABLE OF REQUIRED EMERGENCY POWER OPERATIONS AS DETAILED IN THIS SECTION FOR CONTRACTOR SHALL PROVIDE NEW ELEVATOR CONTROLLER CAPABLE OF REQUIRED EMERGENCY POWER OPERATIONS AS DETAILED IN THIS SECTION FOR CONFORMANCE WITH THE REQUIREMENT DETAILED IN THE APPLICABLE BUILDING CODE. b. CONTRACTOR SHALL VERIFY TELEPHONE LINES AND WIRING TO ELEVATOR CONTROLLERS FOR TELEPHONE SYSTEM INCLUDING ALL WIRING IN MACHINE CONTRACTOR SHALL VERIFY TELEPHONE LINES AND WIRING TO ELEVATOR CONTROLLERS FOR TELEPHONE SYSTEM INCLUDING ALL WIRING IN MACHINE ROOM TO BE INSTALLED INSIDE CONDUIT AS PER NFPA 70 NEC. 3. ELEVATOR MACHINE ROOM: ELEVATOR MACHINE ROOM: a. CONTRACTOR SHALL VERIFY HVAC MUST BE POSITIONED AS APPROVED BY THE ELEVATOR CONTRACTOR AND CONSULTANT. PROVIDE NEW ELECTRICAL CONTRACTOR SHALL VERIFY HVAC MUST BE POSITIONED AS APPROVED BY THE ELEVATOR CONTRACTOR AND CONSULTANT. PROVIDE NEW ELECTRICAL DISCONNECTS WHERE NEW EQUIPMENT IS REQUIRED (LOCKABLE). b. CONTRACTOR SHALL VERIFY THAT PROPER CONNECTIONS EXIST FOR FIRE RECALL DEVICES TO THE ELEVATOR CONTROLLERS. CONTRACTOR SHALL VERIFY THAT PROPER CONNECTIONS EXIST FOR FIRE RECALL DEVICES TO THE ELEVATOR CONTROLLERS. c. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR MACHINE ROOM. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR MACHINE ROOM. d. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR LANDINGS. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR LANDINGS. e. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR HOIST WAY. CONTRACTOR SHALL VERIFY THAT PROPER EQUIPMENT EXIST FOR FIRE ALARM INITIATION DEVICES TO THE ELEVATOR HOIST WAY. f. CONTRACTOR SHALL VERIFY PROPER EQUIPMENT EXIST FOR GFCI RECEPTACLES. CONTRACTOR SHALL VERIFY PROPER EQUIPMENT EXIST FOR GFCI RECEPTACLES. g. CONTRACTOR SHALL VERIFY THAT DISCONNECTS ARE LABELED ACCORDING TO NFPA 70 NATIONAL ELECTRICAL CODE INCLUDING SOURCE OF POWER, STATE CONTRACTOR SHALL VERIFY THAT DISCONNECTS ARE LABELED ACCORDING TO NFPA 70 NATIONAL ELECTRICAL CODE INCLUDING SOURCE OF POWER, STATE OF FLORIDA ELEVATOR SERIAL NUMBER, ELEVATOR NUMBER AND ALL REQUIRED WARNING SIGNS. h. CONTRACTOR SHALL VERIFY DISCONNECTS ARE INSTALLED WITH PROPER CLEARANCES IN ACCORDANCE TO THE APPLICABLE PROVISIONS OF NFPA 70 CONTRACTOR SHALL VERIFY DISCONNECTS ARE INSTALLED WITH PROPER CLEARANCES IN ACCORDANCE TO THE APPLICABLE PROVISIONS OF NFPA 70 NATIONAL ELECTRICAL CODE i. CONTRACTOR SHALL PROVIDE NEW ELEVATOR PIT LIGHTING. LIGHTING SHALL BE ENCLOSED TYPE AND SUITABLE FOR USE. MACHINE ROOM LIGHTING CONTRACTOR SHALL PROVIDE NEW ELEVATOR PIT LIGHTING. LIGHTING SHALL BE ENCLOSED TYPE AND SUITABLE FOR USE. MACHINE ROOM LIGHTING LEVELS SHALL BE GREATER THAN OR EQUAL TO 19FC. AND SERVED BY EMERGENCY SOURCE. 4. OPERATION AND CONTROL SYSTEMS: OPERATION AND CONTROL SYSTEMS: a. CONTRACTOR SHALL VERIFY THE SIGNALING FROM CODE COMPLIANT EMERGENCY POWER SUPPLY TRANSFER SWITCH. CONTRACTOR SHALL VERIFY THE SIGNALING FROM CODE COMPLIANT EMERGENCY POWER SUPPLY TRANSFER SWITCH. b. CONTRACTOR SHALL PROVIDE WIRING AND AUXILIARY CONTACTS AS REQUIRED BY APPLICABLE BUILDING CODE AND NFPA 70 NATIONAL ELECTRICAL CODE. CONTRACTOR SHALL PROVIDE WIRING AND AUXILIARY CONTACTS AS REQUIRED BY APPLICABLE BUILDING CODE AND NFPA 70 NATIONAL ELECTRICAL CODE. c. EMERGENCY POWER SYSTEMS SHALL BE TESTED AND INSPECTED BY EMERGENCY GENERATOR SERVICE CONTRACTOR. EMERGENCY POWER SYSTEMS SHALL BE TESTED AND INSPECTED BY EMERGENCY GENERATOR SERVICE CONTRACTOR. d. CONTRACTOR SHALL PROVIDE AN ILLUMINATED SIGNAL MARKED “ELEVATOR EMERGENCY POWER” SHALL BE PROVIDED IN THE ELEVATOR LOBBY AT THE CONTRACTOR SHALL PROVIDE AN ILLUMINATED SIGNAL MARKED “ELEVATOR EMERGENCY POWER” SHALL BE PROVIDED IN THE ELEVATOR LOBBY AT THE ELEVATOR EMERGENCY POWER” SHALL BE PROVIDED IN THE ELEVATOR LOBBY AT THE SHALL BE PROVIDED IN THE ELEVATOR LOBBY AT THE DESIGNATED LEVEL TO INDICATE THAT THE NORMAL POWER SUPPLY HAS FAILED AND THE EMERGENCY OR STANDBY POWER IS IN EFFECT FOR THE ELEVATOR. e. CONTRACTOR SHALL PROVIDE SIGNAL IN TRANSFER SWITCH TO ELEVATOR CONTROLLER THAT THE BUILDING IS ON EMERGENCY STANDBY POWER. CONTRACTOR SHALL PROVIDE SIGNAL IN TRANSFER SWITCH TO ELEVATOR CONTROLLER THAT THE BUILDING IS ON EMERGENCY STANDBY POWER. f. CONTRACTOR SHALL VERIFY EMERGENCY POWER HAS BEEN VERIFIED TO BE CAPABLE OF OPERATING THE ELEVATOR IN THE BUILDING AND OTHER CONTRACTOR SHALL VERIFY EMERGENCY POWER HAS BEEN VERIFIED TO BE CAPABLE OF OPERATING THE ELEVATOR IN THE BUILDING AND OTHER BUILDING LOADS CONCURRENTLY. g. CONTRACTOR SHALL VERIFY ALL EMERGENCY TELEPHONE DEVICES SHALL INCLUDE A MINIMUM OF 4 HOURS EMERGENCY BACKUP POWER INCLUDING CONTRACTOR SHALL VERIFY ALL EMERGENCY TELEPHONE DEVICES SHALL INCLUDE A MINIMUM OF 4 HOURS EMERGENCY BACKUP POWER INCLUDING POWER FROM EMERGENCY GENERATOR. h. CONTRACTOR SHALL PROVIDE ALL TELEPHONE LINES AND WIRING TO ELEVATOR CONTROLLERS FOR TELEPHONE SYSTEM INCLUDING ALL WIRING IN CONTRACTOR SHALL PROVIDE ALL TELEPHONE LINES AND WIRING TO ELEVATOR CONTROLLERS FOR TELEPHONE SYSTEM INCLUDING ALL WIRING IN MACHINE ROOM TO BE INSTALLED INSIDE CONDUIT AS PER NFPA 70 NEC. i. CONTRACTOR SHALL VERIFY THE MAIN LINE DISCONNECTING MEANS SIZE, FUSED MOTOR CIRCUIT SWITCH AND CAPABLE OF BEING LOCKED IN THE OPEN CONTRACTOR SHALL VERIFY THE MAIN LINE DISCONNECTING MEANS SIZE, FUSED MOTOR CIRCUIT SWITCH AND CAPABLE OF BEING LOCKED IN THE OPEN POSITION. j. CONTRACTOR SHALL VERIFY THE CAB LINE DISCONNECTING MEANS SIZE, FUSED MOTOR CIRCUIT SWITCH AND CAPABLE OF BEING LOCKED IN THE OPEN CONTRACTOR SHALL VERIFY THE CAB LINE DISCONNECTING MEANS SIZE, FUSED MOTOR CIRCUIT SWITCH AND CAPABLE OF BEING LOCKED IN THE OPEN POSITION. 5. ELEVATOR HOISTWAY AND PIT EQUIPMENT: ELEVATOR HOISTWAY AND PIT EQUIPMENT: a. CONTRACTOR SHALL VERIFY PROPER EQUIPMENT EXISTS FOR GFCI RECEPTACLES. CONTRACTOR SHALL VERIFY PROPER EQUIPMENT EXISTS FOR GFCI RECEPTACLES. b. ALL EQUIPMENT WITHIN 48" OF FLOOR SHALL BE NEMA 4 TYPE IDENTIFIED FOR USE IN WET LOCATIONS. ALL EQUIPMENT WITHIN 48" OF FLOOR SHALL BE NEMA 4 TYPE IDENTIFIED FOR USE IN WET LOCATIONS. c. CONTRACTOR SHALL VERIFY PIT LIGHTING LEVELS ARE SERVED BY EMERGENCY SOURCE AND SEPARATE CIRCUIT FROM OTHER EQUIPMENT, LIGHT SWITCH CONTRACTOR SHALL VERIFY PIT LIGHTING LEVELS ARE SERVED BY EMERGENCY SOURCE AND SEPARATE CIRCUIT FROM OTHER EQUIPMENT, LIGHT SWITCH IS READILY ACCESSIBLE AND PIT LIGHTING LEVELS GREATER THAN OR EQUAL TO 10FC. d. ALL CONDUIT AND WIRING IN THE HOIST WAY SHALL BE CHECKED FOR PROPER INSTALLATION AND PROPERLY MOUNTED IN ACCORDANCE WITH ALL CONDUIT AND WIRING IN THE HOIST WAY SHALL BE CHECKED FOR PROPER INSTALLATION AND PROPERLY MOUNTED IN ACCORDANCE WITH APPLICABLE PROVISIONS OF NFPA 70 NATIONAL ELECTRICAL CODE. e. ALL EQUIPMENT GROUNDING AND BONDING SHALL BE PROVIDED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70 NATIONAL ELECTRICAL CODE. ALL EQUIPMENT GROUNDING AND BONDING SHALL BE PROVIDED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70 NATIONAL ELECTRICAL CODE. f. ALL NEW ELEVATOR HOIST WAY AND PIT LIGHTING TO BE ENCLOSED TYPE AND SUITABLE FOR USE. ALL NEW ELEVATOR HOIST WAY AND PIT LIGHTING TO BE ENCLOSED TYPE AND SUITABLE FOR USE. g. CONTRACTOR SHALL PROVIDE PIT LIGHTING SWITCHES AND EMERGENCY STOP SWITCHES AND SHALL BE INSTALLED APPROXIMATELY 18” ABOVE FIRST CONTRACTOR SHALL PROVIDE PIT LIGHTING SWITCHES AND EMERGENCY STOP SWITCHES AND SHALL BE INSTALLED APPROXIMATELY 18” ABOVE FIRST ABOVE FIRST FLOOR LANDING ADJACENT TO OPENING AND OPERABLE FROM SIDE OF PIT ACCESS WHERE PIT LADDER IS INSTALLED. h. CONTRACTOR SHALL PROVIDE NEW ELECTRIC WIRING FROM DISCONNECT SWITCHES TO THE TERMINALS OF THE NEW ELEVATOR CONTROLLERS IN THEIR CONTRACTOR SHALL PROVIDE NEW ELECTRIC WIRING FROM DISCONNECT SWITCHES TO THE TERMINALS OF THE NEW ELEVATOR CONTROLLERS IN THEIR NEW LOCATIONS, INCLUSIVE OF A NORMAL 120 VAC, 15 AMP SUPPLY AT EACH CONTROLLER. 6. PATCHING, PAINTING ETC. AS INDICATED: PATCHING, PAINTING ETC. AS INDICATED: a. CONTRACTOR SHALL VERIFY PROPER INSTALLATION OF 1 ½ HOUR “B-LABEL” DOOR TO MACHINE ROOM TO INCLUDE SELF-CLOSING AND SELF-LOCKING CONTRACTOR SHALL VERIFY PROPER INSTALLATION OF 1 ½ HOUR “B-LABEL” DOOR TO MACHINE ROOM TO INCLUDE SELF-CLOSING AND SELF-LOCKING B-LABEL” DOOR TO MACHINE ROOM TO INCLUDE SELF-CLOSING AND SELF-LOCKING DOOR TO MACHINE ROOM TO INCLUDE SELF-CLOSING AND SELF-LOCKING REQUIREMENTS. b. CONTRACTOR SHALL VERIFY PROPER CLASS ABC FIRE EXTINGUISHER IN MACHINE ROOM PERMANENTLY MOUNTED AND CONVENIENTLY LOCATED TO THE CONTRACTOR SHALL VERIFY PROPER CLASS ABC FIRE EXTINGUISHER IN MACHINE ROOM PERMANENTLY MOUNTED AND CONVENIENTLY LOCATED TO THE ACCESS DOOR AS REQUIRED BY ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS. c. CONTRACTOR SHALL VERIFY THAT ALL NON-ELEVATOR RELATED PIPES, WIRING, CONDUIT HAVE BEEN REMOVED AND OPENINGS IN MACHINE ROOMS AND CONTRACTOR SHALL VERIFY THAT ALL NON-ELEVATOR RELATED PIPES, WIRING, CONDUIT HAVE BEEN REMOVED AND OPENINGS IN MACHINE ROOMS AND HOIST WAYS TO INCLUDE A 2 HOUR FIRE RATING. ALL FOREIGN PIPES, WIRING OR CONDUIT NOT IN USE OR DIRECTLY RELATED TO THE ELEVATOR SYSTEM SHALL BE REMOVED FROM MACHINE ROOMS AND HOIST WAYS. d. CONTRACTOR SHALL VERIFY ALL SILLS MUST BE SUBSTANTIALLY LEVEL TO ALL ADJACENT FINISHED FLOORING SURFACES. CONTRACTOR SHALL VERIFY ALL SILLS MUST BE SUBSTANTIALLY LEVEL TO ALL ADJACENT FINISHED FLOORING SURFACES. e. CONTRACTOR SHALL PROVIDE MACHINE ROOM WARNING SIGN “DANGER AUTHORIZED PERSONNEL ONLY” LOCATED ON THE MACHINE ROOM DOOR AS CONTRACTOR SHALL PROVIDE MACHINE ROOM WARNING SIGN “DANGER AUTHORIZED PERSONNEL ONLY” LOCATED ON THE MACHINE ROOM DOOR AS DANGER AUTHORIZED PERSONNEL ONLY” LOCATED ON THE MACHINE ROOM DOOR AS LOCATED ON THE MACHINE ROOM DOOR AS REQUIRED BY NFPA 70 NEC. f. CONTRACTOR SHALL PROVIDE ANY CUTTING, PATCHING INCLUDING PAINTING TO MATCH EXISTING FINISHES OF BUILDING. CONTRACTOR SHALL PROVIDE ANY CUTTING, PATCHING INCLUDING PAINTING TO MATCH EXISTING FINISHES OF BUILDING. g. CONTRACTOR SHALL PROVIDE ANY PATCHING OF ALL MASONRY OPENINGS AND DRYWALL SURFACES AS REQUIRED BY ELEVATOR INSTALLATION WORK AS CONTRACTOR SHALL PROVIDE ANY PATCHING OF ALL MASONRY OPENINGS AND DRYWALL SURFACES AS REQUIRED BY ELEVATOR INSTALLATION WORK AS DETAILED BELOW WILL BE THE RESPONSIBILITY OF THE ELEVATOR CONTRACTOR. h. ALL OPENINGS LEFT FROM THE REMOVAL OF ANY SURFACE MOUNTED DEVICES WILL BE PATCHED APPROPRIATELY AND SURFACE RESTORATION ALL OPENINGS LEFT FROM THE REMOVAL OF ANY SURFACE MOUNTED DEVICES WILL BE PATCHED APPROPRIATELY AND SURFACE RESTORATION PERFORMED BY THE CONTRACTOR. INCLUDED IN THIS WILL BE THE REMOVAL OF OLD POSITION INDICATORS AND DIRECTIONAL INDICATORS. i.