JACKSONVILLE
Job Corps Center Jacksonville, FL
Facility Planning Report Volume II
Supporting Data
Final June 2017
Department of Labor/ Office of Job Corps
JACKSONVILLE
Job Corps Center Jacksonville, FL
Facility Planning Report Volume II
Supporting Data
Final June 2017
Bridge over the large pond
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Existing Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The Program Year 2016 Facility Survey for Jacksonville Job Corps Center was completed the week of February 27, 2017. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
JACKSONVILLE
JOB CORPS CENTER
JACKSONVILLE, FLORIDA
JACKSONVILLE
JCC
10 MI50
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00410 JACKSONVILLE 06/21/2017
1Page: of Date:
A - ADMINISTRATION/MEDICAL-DENTAL
B - EDUCATION
C - HARD VOCATION
D - DINING
E - RECREATION
F - DORMITORY
G - DORMITORY
H - MAINTENANCE/WAREHOUSING
I - CHILD DEVELOPMENT CENTER
K - BALL FIELD DUGOUT (24Ft x 8Ft) L - BALL FIELD DUGOUT (24Ft x 8Ft) M - STORAGE CONTAINER (8Ft x 40Ft) N - STORAGE SHED (18Ft x 40Ft) O - SHED (6Ft x 6Ft) P - GAZEBO (24Ft x 30Ft) Q - GAZEBO (24Ft x 30Ft) R - GAZEBO (24Ft x 30Ft)
Name GSF
14,772 20,763 20,131 11,183 22,137 26,925 26,925 7,221 5,850
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business Business Business Assembly Assembly Residential Residential Storage Day Care Assembly Assembly Storage Storage Storage Assembly Assembly Assembly
1 3
Good Good Fair
Good Fair
Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0041008091 0041008092 0041008093 0041008094 0041008095 0041008096 0041008097 0041008098 0041008099 0041008101 0041008102 0041008103 0041008104 0041008105 0041008106 0041008107 0041008109
9 155,907
8 3,598
17 159,505
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/21/2017
Space Utilization By Function 00410 Jacksonville Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 238 Non Residents 37
275Total Students
(238)
(350)
(275)
DIFFERENCE
25,704
22,330
4,950
38,544
29,461
8,642
Lounge Other Shower/Toilet Sleeping excl. SPD(72 rooms; 272 beds) Storage
Academic (350) Non-Academic
4 -- ACT (Off-Ctr) 24 -- Carpentry + 30 -- Cert. Nursing Asst.
24 -- Computer Service Tech.
24 -- Electrical + 24 -- Facilities Maint. and Const. +
24 -- HVAC +
30 -- Material Handler 30 -- Medical Assistant 30 -- Office Administration 30 -- Pharmacy Tech +
Vocational Theory (126)
Dining (2 Servings) Food Preparation Food Storage
11,859 2,859 4,082
18,767
3,349 4,406
3,361 1,100
2,568 3,599 2,117 3,616
1,843
3,711 3,791 1,140
2,380 1,904 2,856
17,136 1,428
3,500 3,500
1,800 1,200
1,200 1,800 1,800 1,950
1,350 1,350
1,260
2,200 1,650 1,100
9,479
1,226 1,631
-451
-151
1,561 -100
1,368 1,799
1,666
-13 -486 -463
1,511 2,141
Vocations
12,840
7,131
3,692
06/21/2017
Space Utilization By Function 00410 Jacksonville Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 294.85 81,084 115,799
(275)
(275)
(275)
(275)
(0)
DIFFERENCE
155,907
0.74
TOTAL GSF
NET TO GROSS RATIO
12,455
1,445
8,700
5,500
16,798
3,029
11,112
6,129
2,084
Arts & Crafts Gymnasium Hair Salon Miscellaneous Recreation Recreation Hall Recreation Office Recreation Storage Snack Bar Theater Weight Room
Medical/Dental
Administration Child Development Center (40)
Operations & Maintenance Warehouse
Vacant
5.25
8,532
2,273 1,035
1,659
3,029
6,813 4,299
2,679 3,450
2,084
1,445
5,500 3,200
2,200 3,300
1,584
1,313 1,099
RESIDENT
NON-RESIDENT
(238)
(37) 15
50 11,900
4,343
1,584
2,412
2,084
34,715
Net Square Footage By Building Date: 06/21/2017 Page: 1
Center: JACKSONVILLE (00410) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
8,037 10,730
7,234 4,625
2,130 1,952
1,960
G - DORMITORY
F - DORMITORY
G - DORMITORY
F - DORMITORY
F - DORMITORY
G - DORMITORY
F - DORMITORY
G - DORMITORY
F - DORMITORY
G - DORMITORY
Bldg Name Actual NSF Difference
18,767
11,859
4,082
2,859
Sub Total: 38,544
17,136
2,380
1,428
2,856
1,904
25,704
1,631
9,479
-451
1,226
( 238
12,840
36 rooms; 136 beds 36 rooms; 136 beds
Page: 2
Center: JACKSONVILLE (00410) of 4
EDUCATION
Academic
Vocational Theory (126)
Carpentry
Electrical
Computer Service Tech.
HVAC
Facilities Maint. and Const.
Medical Assistant
Non-Academic
Material Handler
Pharmacy Tech
Office Administration
Cert. Nursing Asst.
Function Suggested
NSF
1,189
1,843
3,361
2,568
2,117
3,599
1,320
2,137
3,616
1,100
B - EDUCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
C - HARD VOCATION
C - HARD VOCATION
C - HARD VOCATION
B - EDUCATION
C - HARD VOCATION
C - HARD VOCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
G - DORMITORY
C - HARD VOCATION
B - EDUCATION
B - EDUCATION
B - EDUCATION
Bldg Name Actual NSF Difference
3,349
1,843
3,361
2,568
2,117
3,599
4,406
3,616
1,100
Sub Total: 29,461
3,500
1,260
1,800
1,200
1,800
1,800
3,500
1,950
1,350
1,350
1,200
22,330
-151
1,561
1,368
1,799
-13
1,666
-463
-486
-100
( 350
7,131
Page: 3
Center: JACKSONVILLE (00410) of 4
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Dining (2 Servings)
Food Preparation
Food Storage
Recreation Hall
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Theater
Miscellaneous Recreation
Hair Salon
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
3,711
3,791
1,140
2,273
8,532
1,659
1,035
3,029
D - DINING
D - DINING
D - DINING
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
E - RECREATION
A - ADMINISTRATION/MEDICAL-DENTAL
Bldg Name Actual NSF Difference
3,711
3,791
1,140
2,273
8,532
1,659
1,035
3,029
Sub Total:
Sub Total:
Sub Total:
8,642
16,798
3,029
2,200
1,650
1,100
1,445
4,950
12,455
1,445
1,511
2,141
1,584
3,692
4,343
1,584
Page: 4
Center: JACKSONVILLE (00410) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Child Development Center
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
6,525
4,299
3,450
2,679
1,440
A - ADMINISTRATION/MEDICAL-DENTAL
H - MAINTENANCE/WAREHOUSING
I - CHILD DEVELOPMENT CENTER
H - MAINTENANCE/WAREHOUSING
H - MAINTENANCE/WAREHOUSING
B - EDUCATION
B - EDUCATION
C - HARD VOCATION
Bldg Name Actual NSF Difference
6,813
4,299
3,450
2,679
2,084
Sub Total:
Sub Total:
Sub Total:
11,112
6,129
2,084
5,500
3,200
3,300
2,200
8,700
5,500
1,313
1,099
2,084
2,412
2,084
Environmental Management Report Center: JACKSONVILLE (00410)
Page: 1 Date: 06/21/2017 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
N/A
No
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Management No
N/A N/A
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
No Survey Required due to Age of Buildings None
N/A N/A N/A No No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Radon
Date: 06/21/2017Center : Jacksonville (00410) Page: 1 of 1
A - ADMINISTRATION/MEDICAL-DENTAL
B - EDUCATION
C - HARD VOCATION
D - DINING
E - RECREATION
F - DORMITORY
G - DORMITORY
H - MAINTENANCE/WAREHOUSING
I - CHILD DEVELOPMENT CENTER
Bldg Name
03/28/2008
03/28/2008
03/28/2008
03/28/2008
03/28/2008
03/28/2008
03/28/2008
03/28/2008
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Residential Campus
View from the bridge towards Education Building B
Page: 1 Date: 06/21/2017 of 5
Comments:
Paving Type for Roads & Parking
Vehicular access is limited to the Center perimeter and delivery routes to the Dining Building D and Maintenance Building H delivery areas. Site internal traffic is pedestrian only on concrete walks as well as a bridge connector to the dormitories and Recreation Building E. There is a large wooden terrace with wooden walkway that connects Hard Vocation Building C to the rest of the center.
Paving Type for Sidewalks
Concrete Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. The Center utilizes off-center public athletic and aquatic facilities. There are two man-made ponds. A pedestrian bridge crosses the larger pond for access to the dormitories and Recreation Building E from the rest of the Center. A smaller pond is located directly behind Administration/Medical-Dental Building A. The water level has been steadily declining over the years and the pond banks are slowly eroding contributing to deterioration of retaining walls. A terrace overlooks the pond from the rear of Building A. Wetlands flank the site to the east, and also traverse the site in front of Hard Vocation Building C. Chain-link fencing surrounds the outdoor play area behind Child Development Center Building I, and the center maintenance vehicle parking lot behind Maintenance Building H. There is also chain-link fencing at the railroad right of way along the site's northeast property line. There is a wood fence to restrict access on a vacant side of one of the ponds.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualJacksonville Water AuthorityPublic Water Authority
None 0None
Number of Deficiencies = 1
Number of Deficiencies = 1
Number of Deficiencies = 4
SITE FEATURES
UTILITIES
Buildings Structures9 8Flat
Surrounding
Outdoor Recreation
Golfcourse, Light Commercial, Urban
Basketball, Soft/Baseball CDC Playground, Ponds
Ball Field Dug-out Enclosures
Common Area
Entire Site
Outdoor HVAC Equipment
Chain Link
Wood
Chain Link
CMU
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Utility Center Yes Good Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition
Fencing
Other Features
Page: 2 Date: 06/21/2017 of 5
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 5None Municipal
Fire hydrants with adequate water pressure are fully functional. Jacksonville Fire and Rescue is located about one mile away at the intersection of Myrtle Avenue and Moncrief Road. Response time is five minutes or less.
Comments:
Sewage Treatment Flow
The lift station is utilized to pump up to service main of the Publicly Owned Treatment Works Utility company.
Utility
Publicly Owned Treatment Works
Utility
Gravity and Lift Stations
Maintenance ResponsibilityOwnership
TECO Peoples Gas
Number of Deficiencies = 1
Number of Deficiencies = 13. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
2. Fire Protection System
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 7
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
None
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
6. Central Plant: None
Page: 3 Date: 06/21/2017 of 5
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Jacksonville Electric Authority
Radial configured primary service enters the center from two Jacksonville Electric Authority (JEA) riser poles located at the southeast corner of the property near Golfair Boulevard and Walgreen road. Underground primary service is distributed to JEA pad-mounted step-down transformers with corresponding cabinet-mounted secondary utility meters. Each transformer with the corresponding meter serves two buildings, with exception of Buildings F and I. These buildings are served by separate transformers and meters. Building D is metered together with the sanitary pump station. This pump station is backed up with a 20 kW stand-by gas powered generator with a 100A automatic transfer switch.
Pad Utility
Utility Utility
No
26.4 kV, 3-phase, 4 wire
120/208V, 3-Phase, 4 WireUnderground
UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 37. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Natural Gas
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole, bollard Building Sport Light
Photocell Photocell Photocell Photocell, Time Clock Photocell, Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: Site lighting is provided by building-mounted and pole-mounted HID lights. In addition, sports lighting is provided at the baseball field and decorative bollards are installed at the pedestrian bridge across a large man-made pond between the two dormitory buildings and Buildings B and D. Site lighting is controlled by photocells and time clock, is owned and maintained by the Center. Night lighting is insufficient at the Center perimeter. Athletic field lights stay on all night as security lights.
ATS MTS
Yes No
Number of Deficiencies = 2
Metering Individual
Page: 4 Date: 06/21/2017 of 5
Comments:
Telephone Company
On-site Line Owner
AT&T is providing local telephone services. JCDC provides long distance, FAX and phones, and Verizon provides cell phone services. Four T1 lines are provided for the Center's need and (5) T1 lines ((4) for internet and one for VoIP) are provided for SIA Tech program to the DEMARK point at the main data closet in Adm./Medical/Dental Building A. There are three land lines (to Security, Dorm and Finance department). Sub-closet is located in Education Building B. There are two Compaq UPS batteries, in each of Buildings A and B, to buffer power surges and drops in the line voltage and maintain the power requirements of the system up to 8 hours. Optical fiber cabling is utilized for inter-building connection, and CAT 5 is utilized for interconnection of data switch to outlets in the buildings. The Center fire alarm panel Edwards EST-2, located in the security office of Building A monitors all fire alarm devices, power booster panels and annunciator panels throughout the Center. The remote annunciator panels in the buildings are disabled during the upgrade of the Center's fire alarm system. Last fire alarm inspection was done by Jacksonville Sound and communication ((904) 737-3511) at 10/03/2016. The fire alarm lines connected buildings were provided by surge protection system. A color TVs in the security office and in the data closet in Building A monitors all activities recorded from the 16 exterior dome type pole-mounted cameras strategically installed throughout the center.
Bell South Telephone Company (AT&T)
Maint. Responsibility
Center Center
Electric Gate Operator, CCTV Cameras, Color Monitors, Door Alarms
N/AN/AN/A N/AN/A NoN/A
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
9. Electrical (Communication/Alarm/Security)
N/A
Purpose
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 7
Fire Alarm Security
Page: 5 Date: 06/21/2017 of 5
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk Low Medium LowHigh LowIBC High
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
N/AYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
The water level in both ponds has dropped in the past few years causing ground erosion at the pond banks. The retaining wall along the north side of Administration Building A is deteriorating and splitting. Rain water ponds frequently in a few locations on campus.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
Yes
Yes
Yes
NO
Yes
Yes
Yes
3 %
Building Descriptions and Structures
BUILDING A - ADMINISTRATION/MEDICAL-DENTAL
Building Descriptions
Page: 1 of 50
Building: A - ADMINISTRATION/MEDICAL-DENTAL
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Loadbearing Masonry Wood
Brick Masonry EIFS
Comments:
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 14,772 9,554 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 2004 8 Hip Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 50
Building: A - ADMINISTRATION/MEDICAL-DENTAL
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall
Comments: The bathrooms have ceramic tile base.
Metal Unit - Metal Frame Wood Unit - Metal Frame
Mechanical
Mechanical
Restroom
Janitor's Closet
Ventilation Area Served
VERTICAL CIRCULATION
Slopped sidewalk Comments: The entrance sidewalks are sloped up to the entrance doors.
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Exhaust Ventilation
Number of Deficiencies = 3
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are nine outdoor heat pumps (on grade), each one is matched to an indoor air handler unit. The outdoor units were manufactured by Trane and built in 2002. The heat pumps' capacities range from 4-tons to 12 tons. The typical model numbers are TWA048 through TWA120.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Ventilation2.
Ceilings
Page: 3 of 50
Building: A - ADMINISTRATION/MEDICAL-DENTAL
Domestic water is provided by a gas-fired water heater located in the mechanical room in the medical/dental area. The gas-fired water heater is manufactured by A.O. Smith, model BTR 250 110, with a capacity of 100 gallons, an input of 250,000 BTU/Hr and a recovery rating of 242 gallons/hour, circulated by an in-line pump. There is also a small electric water heater located in the janitor closet manufactured by A.O. Smith, model DEL30104, with a capacity of 30 gallons and 6 kW.
Comments:
Cast Iron/PVC None None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Shower Shower/Bathtub Sink Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Fan Coil
Refrigerant
Refrigerant
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Electronic Equipment
Room
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
There are nine air handler units, each one matched to an outdoor heat pump. The indoor units were built by Trane in 2002 and range in capacities from 48,000 BTU/Hr to 120,000 BTU/Hr and located in the mechanical rooms. The typical model numbers for the indoor units are TWE048 through TWE120.
They are furnished with a DX coil on the discharge that draws in outdoor air.
Cooling is provided to the computer room by a ductless mini split system, manufactured by Trane, model TTK524E5, with a capacity of 2 tons, built in 2003.
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
3. Air Conditioning
Page: 4 of 50
Building: A - ADMINISTRATION/MEDICAL-DENTAL
Comments: Service is brought from a 300 kVA pad-mounted utility-owned transformer with a utility meter located northwest of the building. The transformer and meter additionally serve Education Building B. Service terminates in an 800A main distribution panel (MDP) with 800A main circuit breaker (MCB) located in the utility room. The MDP has one 150A, two 250A and two 400A circuit breakers which serve distribution panels in the building.
FIRE ALARM
Comments: The center's main fire alarm control/annunciator panel is an Edwards Systems model EST-2, located in the security office. It monitors booster power supply panels and remote annunciator panels throughout the center. The remote annunciator panel for this building was found to be incompatible with the new fire alarm system and was disabled during the new fire alarm upgrade.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded foot-candle levels include natural light contribution. In addition to grid lay-in fluorescent lights, a combination of track lights, recessed downlights and decorative pendant-mounted compact fluorescent lights are provided in the vestibule and lobby.
Comments: The tritium gas exit signs expire in July 2022.
Compact Fluorescent High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact and T8 - Fluorescent
Offices
Medical/Dental
Wards (Patient)
Storage Rooms
Corridors & Stairs
Lounges
Equipment Rooms (Elec/Mech)
Toilets
Reception
Conference Rooms
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Tritium Gas
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 2
ELECTRICAL SERVICES Number of Deficiencies = 6
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
LIGHTING
Page: 5 of 50
Building: A - ADMINISTRATION/MEDICAL-DENTAL
Comments: The Center's main telephone/data communication equipment is located in the main server closet (MC) in the building. The CCTV cameras site wide are controlled and monitored from a color monitor located in the security office. The building door alarms are also monitored from this location.
Connected to Main System Magnetic Door/Alarm Connected to Main System TV with VCR Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location None None
The detectors are needed, since there are gas water heater in the mechanical room in the Medical/Dental department.
CARBON MONOXIDE DETECTION
Detection Required Yes
Number of Deficiencies = 1
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING B - EDUCATION
Page: 6 of 50
Building: B - EDUCATION
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Loadbearing Masonry Wood
Brick Masonry EIFS
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 20,763 13,842 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 2004 8 Hip Entire Building
3. Roof
Page: 7 of 50
Building: B - EDUCATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Comments: During the March 2017 Facility Survey the vinyl composition tile (VCT) covered concrete subfloor displayed structural cracks in three locations: two in the main corridor on either side of student bathrooms and one in the Advanced Math Classroom. The cracks are continuous and spanning the full width of the corridor. They did not present a safety hazard at the time of the survey. They may be caused by the movement of inadequately compacted soil under the concrete floor slab. The Center staff is to monitor the cracks. If the cracks increase then advise the ESC PM for consulting ESC structural engineer.
CMU Drywall Plaster
Comments: Bathrooms have ceramic tile base.
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
None
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Page: 8 of 50
Building: B - EDUCATION
Mechanical
Natural
Restroom
Mechanical Equipment Room
Comments: These rooms are ventilated by exterior wall louvers.
Ventilation Area Served
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Fan Coil
Refrigerant
Refrigerant
Electric
Electric
Mechanical
Natural
Heat Recovery
None
Entire Building
Electronic Equipment
Room
Exhaust Ventilation
There are ten outdoor heat pumps (on grade), each one is matched to an indoor air handler unit located in three mechanical rooms. The outdoor units are manufactured by Trane, built in 2002 with a capacity range of 4-tons to 10-tons. The typical model numbers are TWA048 through TWA120. Each indoor unit is also manufactured by Trane, built in 2002 and the typical model numbers are TWE048 through TWE120 furnished with a supplemental heating coil. The heating coil capacity ranges from 7.5 kW to 18.5 kW. Each indoor unit also has a DX coil on their discharge and draws in outdoor air. The typical model number is TWE048 through TWE120. There are two energy recovery units manufactured by Venmar, model ERV300END1XG11SNHEEBXXR1 that are no longer in use.
Cooling is provided to the main server room by a ductless mini split system, manufactured by Mitsubishi, model MUY-D36NA, with a capacity of 2.5 ton and uses R-410A.
Comments:
Comments:
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are ten outdoor heat pumps (on grade), each one is matched to an indoor air handler unit located in three mechanical rooms. The outdoor units are manufactured by Trane, built in 2002 with a capacity range of 4-tons to 10-tons. The typical model numbers are TWA048 through TWA120. Each indoor unit is also manufactured by Trane, built in 2002 and furnished with a supplemental heating coil.
The heating coil capacity ranges from 7.5 kW to 18.5 kW. Each indoor unit also has a DX coil on their discharge and draws in outdoor air. The typical model number is TWE048 through TWE120. There are two energy recovery units manufactured by Venmar, model ERV300END1XG11SNHEEBXXR1 that are no longer in use.
There are four split ductless heat pump units manufactured by Quietside in 2014 with typical outdoor unit model number QSCC-243. The indoor units have typical model number QSCE-243/QSOC-243.
They serve four classrooms in northeast side of the building. These units have 24,000 BTU/HR heating and cooling capacities.
A split ductless air conditioning unit manufactured by Mitsubishi in 2013 with outdoor model number MUY-D36NA that serves Electrical/Server Room. It has 36,000 BTU/HR cooling capacity. The indoor unit model number is MSY-D36NA.
Comments:
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Single Duct
None
Refrigerant
Refrigerant
Electric
Electronic
Mechanical
Natural
None
None
Entire Building
Classrooms and Offices
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Number of Deficiencies = 1Air Conditioning
Page: 9 of 50
Building: B - EDUCATION
Domestic hot water is provided by a gas-fired water heater manufactured by A.O. Smith, model BTR 154 110, with a capacity of 81 gallons, an input 154,000 BTU/Hr and a recovery rating of 149 gallons/hour, circulated by an in-line pump.
Comments:
Cast Iron/PVC None None
Electric Water Cooler Lavatory Mop Sink Portable Bottled Water Cooler Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 300 kVA pad-mounted utility-owned transformer with a utility meter located southwest of the building. The transformer and meter additionally serve Administration/Medical-Dental Building A. Service terminates in a 1600A switchboard with 1200A main circuit breaker (MCB) located in the Mechanical/Electrical Room. The switchboard has one 150A, two 225A, two 400A circuit breakers and one 225A spare breakers. Except the spare, the breakers are associated with distribution panels in the building.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Compact Fluorescent High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 7
Exterior Lighting1. Number of Deficiencies = 1
Page: 10 of 50
Building: B - EDUCATION
FIRE ALARM
Comments: The remote annunciator panel (EST LSRA) located in the reception area had been disabled during the fire alarm system upgrade. The building fire alarm system also includes a fire alarm booster power supply (EST BPS10) located adjacent to the remote fire alarm control panel.
Comments: The center's second server closet for telephone/data communication equipment is located in this building. This server room is connected with the main server closet in Administration Building A by underground fiber optics. Most classrooms are provided with computer work stations and TV with VCRs.
Audible Alarm Duct Smoke Detector Heat Detector Manual Pull Station Power Booster Panel Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm Connected to Main System Satellite Dish Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. In addition to grid lay-in fluorescent lights, the vestibule and the main lobby are provided with recessed downlight and decorative pendant-mounted compact fluorescent light fixtures. Indirect HID lights are also utilized at the cupola along the corridor.
Comments: The tritium gas exit signs expire in July 2022.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Classrooms
Lounges
Storage Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Tritium Gas Emergency Exit
Number of Deficiencies = 2
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Electric Water Gas Yes YesZone
BUILDING UTILITY METERING
Type Location 120V w/Battery Backup Mechanical Room
Stand-alone 120V carbon monoxide alarm is provided in the mechanical room housing gas water heater.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
Page: 11 of 50
Building: B - EDUCATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
HVAC systems are old, inefficient and have reached their life expectancy.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING C - HARD VOCATION
Page: 12 of 50
Building: C - HARD VOCATION
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Loadbearing Masonry Steel
Brick Masonry EIFS
Wall Roof Rigid Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 20,131 17,449 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Material
Some of the lower eaves also have surface runoff drainage. The roof condition was poor during the March 2017 Facility Survey. The incorrectly installed upper edge flashing caused extensive leaks along the entire lenght of the building. The plywood roof sheathing is deteriorated as well as the gypsum board rating assembly and acoustical ceiling tiles in classrooms and offices.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles
EPDM
Gutters and Downspouts
Surface Run-off
Hip
Barrel
Classrooms & Offices
Shop Area
Number of Deficiencies = 1
Comments:
3. Roof
Page: 13 of 50
Building: C - HARD VOCATION
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
CMU
Metal Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Metal Ladder Wood Pull-Down Stairs Comments: Each vocational shop has a metal ladder to the storage mezzanine.
Metal Rollup - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Exterior Doors5. Number of Deficiencies = 3
Windows6.
Floors1.
Interior Walls2.
3.
Page: 14 of 50
Building: C - HARD VOCATION
Mechanical
Mechanical
Mechanical
Shop Area
Storage
Restroom
Comments:
Comments:
Four wall-mounted exhaust fans ventilate each of the five shop areas with a total of 20 fans.
Eight storage and tool rooms are ventilated by wall exhaust fans.
Ventilation Area Served
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Classrooms and Offices
Exhaust Ventilation
There are five outdoor heat pumps (on grade), each one is matched to an indoor air handler unit located in individual mechanical rooms. The outdoor units are manufactured by Trane, built in 2002 with a capacity of 3 tons each. The typical model number is TWA036. Each indoor unit is also manufactured by Trane, built in 2002 and furnished with a 7.5 kW supplemental heating coil. Each indoor unit has a DX coil on their discharge and draws in outdoor air. The typical model number is TWE042 with an input capacity of 42,000 BTU/Hr.
Comments:
Number of Deficiencies = 2
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are five outdoor heat pumps (on grade), each one is matched to an indoor air handler unit located in individual mechanical rooms. The outdoor units are manufactured by Trane, built in 2002 with a capacity of 3 tons each. The typical model number is TWA036. Each indoor unit is also manufactured by Trane, built in 2002 and furnished with a 7.5 kW supplemental heating coil. Each indoor unit has a DX coil on their discharge and draws in outdoor air. The typical model number is TWE042 with an input capacity of 42,000 BTU/hr.
Storage and tool rooms are heated by electric unit heaters, manufactured by Trane, model UHEC031AACA with a capacity of 3.3 kW.
The five shops are each heated by two medium-size gas-fired unit heaters, manufactured by Trane.
Each restroom is heated by an electric unit heater mounted in the ceiling, manufactured by Trane, model UHCA021A8A with a capacity of 2 kW.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Electric Resistance
Gas-Fired
Electric Resistance
Single Duct
Unit Heater
Unit Heater
Unit Heater
Refrigerant
None
None
None
Electric
Electric
Electric
Electric
Mechanical
Natural
Natural
Natural
None
None
None
None
Classrooms and Offices
Storage
Shop Area
Rest Rooms
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area
Page: 15 of 50
Building: C - HARD VOCATION
Domestic water is provided by two electric water heaters located in two individual mechanical rooms, one is manufactured by A.O. Smith, model DEL 20102 with a capacity of 19 gallons and 6 kW input.
Comments:
Cast Iron/PVC None None
Electric Water Cooler Fixed Emergency Eyewash Lavatory Service Sink Wall Hydrant Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 300 kVA pad-mounted utility-owned transformer with a utility meter located southeast of the building. The transformer and meter additionally serve Maintenance/Warehousing Building H. Service terminates in an 800A main distribution panel (MDP) with 800A main circuit breaker located in the Storage Room in the Material Handler Shop. The MDP has two 150A and three 225A circuit breakers for Carpentry, Electrical, BAM, HVAC, and Material Handler Shop, respectively. The MDP also has one 250A spare breaker. Three, mushroom type emergency power off (EPO) buttons are utilized to shut down power in each of the vocational shops.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by photocells, through a lighting contactor with over ride switch.
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard, Load centers Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 2
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 5
Exterior Lighting1. Number of Deficiencies = 1
Page: 16 of 50
Building: C - HARD VOCATION
FIRE ALARM
Comments: All fire alarm devices in the building are controlled by the main fire alarm panel in Building A. The remote annunciator panel (EST LSRA) located in the BAM Shop had been disabled during the fire alarm system upgrade. The building fire alarm system also includes a fire alarm booster power supply (EST BPS10) located adjacent to the Storage Room in the BAM Shop.
Comments: The building is connected to the center LAN system.
Audible Alarm Duct Smoke Detector Heat Detector Manual Pull Station Power Booster Panel Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded foot-candle levels include natural light contribution. Low bay industrial light fixtures with metal halide lamps are utilized in the vocational areas. Selected HID fixtures in the shop areas have quartz restrike features.
Comments: The tritium gas exit signs expire in July 2022.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
T8 - Fluorescent
T8 - Fluorescent
Classrooms
Offices
Storage Rooms
Vocational
Toilets
Equipment Rooms (Elec/Mech)
Area Recommended Level
Recorded Level Light Type
Battery Backup Tritium Gas Emergency Exit
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
COMMUNICATION
Electric Water Gas Yes N/AZone
BUILDING UTILITY METERING
Type Location None None
CARBON MONOXIDE DETECTION
Detection Required
Page: 17 of 50
Building: C - HARD VOCATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The split heat pump HVAC system for HVAC Vocational Shop is no longer operational.
No make-up air is provided to the Hard Vocational Shops. Shingle roof is leaking along the entire length of the high roof wall due to inadequate flashing installation. Roof sheathing is damaged.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Fair Interior: Good Mechanical: Fair Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING D - DINING
Page: 18 of 50
Building: D - DINING
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Loadbearing Masonry Wood
Brick Masonry EIFS
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Assembly 11,183 8,642 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 2
Material
Loading dock has gutters and downspouts
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Surface Run-off 2004 8 Hip Entire Building
Comments:
3. Roof
Page: 19 of 50
Building: D - DINING
INTERIOR FINISH
Ceramic Tile Quarry Tile
CMU Drywall
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
None
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Gypsum Board
Number of Deficiencies = 1
Windows6. Number of Deficiencies = 1
Floors1.
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two gas-fired duct heaters, manufactured by Trane, with an output capacity of 280,000 BTU/Hr mounted horizontally at the discharge of an air handler unit, manufactured by Trane, model MCCB021UA with 10 HP provide heating to the dining and servery areas. The system provides a significant quantity of outdoor air.
An outdoor heat pump manufactured by Trane, model TWA120A3, with a capacity of 10-tons built in 2015 provides heat to an indoor air handler manufactured by Trane, model TWE120A3, has a capacity of 120,000 BTU/Hr with 2 HP, built in 2015 that serves the kitchen. The air handler is furnished with a supplemental electric heating coil and draws in minimal outdoor air.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Indirect
Split Heat Pump (Air
Source)
Single Duct
Single Duct
None
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Dining Hall
Kitchen
Page: 20 of 50
Building: D - DINING
Mechanical
Mechanical
Mechanical
Kitchen
Kitchen
Restroom
Comments:
Comments:
Comments:
The three kitchen hoods are exhausted by rooftop fans (one Loren-Cook #195VH9B, 2 HP, servery hood & two #330VX11B, 5 HP, main hood) with the make-up air provided by rooftop units (one Loren- Cook #120KSPB, 1 HP & two #180KSPB, 2 HP).
The dishwasher is ventilated by a rooftop exhaust fan (Loren Cook #135R3B, 1/4 HP).
The restrooms are ventilated by a rooftop exhaust fan (Loren Cook #165C4B, 1/3 HP).
Ventilation Area Served
Split Direct Expansion (Air
Source)
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
Fan Coil
Refrigerant
Refrigerant
Refrigerant
Electric
Electric
Electric
Mechanical
Mechanical
Natural
None
None
None
Dining Hall
Kitchen
Vestibules
Exhaust Ventilation
A condensing unit, manufactured by Trane, model RAUJC40EBC03, with a capacity of 40 tons, on grade provides cooling to a DX coil module in an indoor air handler unit, manufactured by Trane, model MCCB021UA, with 10 HP that serves the dining and the servery areas. The system provides a significant quantity of outdoor air.
An outdoor heat pump manufactured by Trane in 2015, with model number of TWA120D30RAA, with a capacity of 10 tons, on grade provides cooling to a DX coil in an indoor air handler, manufactured by Trane, model TWE120D300AB, with a capacity of 10-tons and 2 HP, built 2015 that serves the kitchen.
The system provides minimal outdoor air.
Cooling is provided to the south vestibule of the dining area by a mini split ductless system, manufactured by Mitsubishi, model MU-A09WA, with a capacity of 3/4 ton and uses R-410A.
Comments:
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area
Page: 21 of 50
Building: D - DINING
Domestic hot water is provided by two gas-fired heaters. Both are manufactured by A.O. Smith. The first water heater has model number BTP 300-800 with a capacity of 300 gallons and an input capacity of 800,000 BTU/Hr. The second water heater has model number BTR 250-110 with a capacity of 100 gallons and an input capacity of 250,000 BTU/Hr. This arrangement is accompanied by an in-line circulating pump, manufactured by Grundfos, model UP1518SF. A water softener system is provided to treat the water system.
Comments:
Cast Iron/PVC Outdoor None
Drinking Fountain Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Sink Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: A type K fire extinguisher is provided in the food preparation area. Type ABC fire extinguishers are provided in the dining room. The kitchen hoods have automatic wet chemical fire suppression systems (three Ansul R-102).
Copper Copper Gas-Fired Building Water Softener No
Hot Water Cold Water Water…