1605706_Dwgs_7of13.pdf
PDF 2 MB Posted
- Solicitation number
- N4008519R9103
About this file
This document package includes architectural drawings and specifications for a chemical storage building project. Key details include:
-
The project involves replacing an existing wastewater treatment plant at the Naval Weapons Station Earle in New Jersey. Architectural drawings show plans, elevations, sections and details for a precast concrete chemical storage building to house sodium hydroxide and polyaluminum chloride solutions. The 1,220 square foot building features a chemical storage room, telecom room, electrical room and eyewash/safety shower.
-
Specifications cover interior and exterior finishes for the precast walls and roof, including paint coatings and floor treatments. Mechanical systems include wall-mounted HVAC and an exhaust fan. Plumbing includes a sink. Life safety provisions include fire extinguishers and exit signage. The drawings also provide code compliance reviews for building, energy, plumbing and life safety codes.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N A
V A
L F
A C
IL
IT
IE
S E
N G
IN
E E
R
IN
G C
O M
M A
N D M
ID
-A
T L
A N
T
IC
P U
B L
IC
W O
R K
S
D E
P A
R T
M E
T
R L E
N
R L
C
L
C K
N E
W
J E
R S
Y
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
S
T E
W A
T E
R T
R E
A T
M E
N T P
L A
R
P
A
IR
B
Y R
E P
L A
C E
M E
N T S
N A
V
A P
O
A T
IO
R L E
C O
L
C K
N E
W
J E
R S
E
1605706
P A
R T
M E
F
H
V Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V
C
IL
IT
IE
G
IN
E E
R
IN
G
M M
A N
D
DES DRW
S Y
M D
E S
C R
IP
T
IO
N D
A T E
A P
P R
DRAWFORM REVISION: 12 APRIL 2018
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
UNCLASSIFIED
ARLINGTON,VA 22201
SUITE 500
1100 N GLEBE ROAD,
APRIL 2020
AS
DM
AZ
ML
P
O T D
A T
E
P L
O T T
IM
E
-A
P R -2
:1
F
IL
E N
A M
E
B L
D G
-1
-A -0
.d g n
CONCRETE
RIGID INSULATION
BATT INSULATION
STEEL
PLYWOOD
WOOD, ROUGH NON-CONTINUOUS
WOOD, ROUGH CONTINUOUS
WOOD, FINISHED
ALUMINUM
CHECKERED PLATE
GRATING, SPAN DIRECTION INDICATED
GRANULAR FILL
EARTH OR FINISH GRADE
SYMBOL LEGEND SYMBOL LEGEND
GENERAL ARCHITECTURAL NOTES
ACOUSTICAL CEILING TILE
GYPSUM BOARD
CMU
BRICK
GROUT, MORTAR
ARCHITECTURAL / STRUCTURAL MATERIAL SYMBOLS
FULL HEIGHT WALL
OR
110.50
A
XX101
ROOM IDENTIFIER
DOOR IDENTIFIER
WINDOW IDENTIFIER
RELIGHT IDENTIFIER
LOUVER IDENTIFIER
W-1
A
E
B
C
D
XX-A-301
R-1
LV-1
INTERIOR ELEVATION INDICATOR
A
P-1 PRECAST PANEL IDENTIFIER
WALL TYPE INDICATOR
DOOR LETTER
ROOM NUMBER
HINGE SIDE
INACTIVEACTIVE
REQUIRED
POINTERS AS
DIRECTION OF
QUANTITY AND
(IF SHOWN)
INDICATOR
"XX" = FACILITY
X X
A
ROOM NAMEROOM NAME
SYMBOL LEGEND
HATCH SWING INDICATOR
X X
A
SPOT ELEVATION INDICATOR (IN FEET)
ELEVATION DATUM (IN FEET)
GRID / COLUMN INDICATOR
EL XX.XX
XXXX
S-X
W-X
B-X
SLAB INDICATOR
COLUMN INDICATOR
WALL INDICATOR
BEAM INDICATOR
X
ARCHITECTURAL/STRUCTURAL LEGEND
DOORS
INDICATES PAIR OF
(DOOR # ON ACTIVE)
CONTROL JOINT
EXPANSION JOINT
CJ
X" EJ
X" = DIMENSION
TOLERANCE AND 1/4" TOTAL HEIGHT TOLERANCE DURING CONSTRUCTION.
ALL OPENINGS DIMENSIONED IN THE CONCRETE STRUCTURAL WALLS ARE SHOWN NOMINALLY. PROVIDE ADDITIONAL 1/2" TOTAL WIDTH 10.
EQUIPMENT.
ANCHORS, AND INSERTS. PROVIDE ALL BASES AND BLOCKING REQUIRED FOR ACCESSORIES, MECHANICAL, ELECTRICAL AND OTHER
VERIFY SIZE AND LOCATION OF, AND PROVIDE: REQUIRED OPENINGS THROUGH FLOORS AND WALLS, ACCESS DOORS, FURRING, CURBS, 9.
REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL AND OTHER CATEGORIES OR DRAWINGS FOR ADDITIONAL NOTES.8.
VERIFY ALL ROUGH-IN DIMENSIONS FOR EQUIPMENT PROVIDED IN THIS CONTRACT, OR BY OTHERS.7.
FACE, OR ON THE SECTION END EXCEPT AS NOTED.
LINE OF EXISTING GRADES, AS SHOWN ON THE BUILDING ELEVATIONS AND SECTIONS ARE APPROXIMATE. THEY ARE AT THE BUILDING 6.
SEALANT; TOP, BOTTOM, INTERSECTION, DOOR FRAMES, GLAZED OPENING FRAMES, AND OTHER PENETRATIONS.
AT WALLS INDICATED TO HAVE SOUND ATTENUATION BATT, FULL HEIGHT PARTITIONS SHALL BE SEALED BOTH SIDES WITH ACOUSTIC 5.
OPENING AT CONCRETE WALLS, 8" AT CMU WALLS.
3-INCHES FROM FACE OF STUD (WALL) TO FACE OF ROUGH OPENING. DIMENSION SHALL BE 6" FROM FACE OF ALL TO EDGE OF ROUGH
WHERE DOOR IS LOCATED NEAR CORNER OF ROOM AND IS NOT LOCATED BY DIMENSION ON PLAN OR DETAILS, DIMENSION SHALL BE 4.
REPETITIVE FEATURES ARE NOT DRAWN IN THEIR ENTIRETY AND SHALL BE COMPLETELY PROVIDED AS IF DRAWN IN FULL.3.
AND CURBS, SEE STRUCTURAL DRAWINGS.
"FLOOR LINE" REFERS TO TOP OF CONCRETE SLABS. FINISH FLOORING IS INSTALLED ABOVE THE FLOOR LINE. FOR DEPRESSED FLOORS 2.
STUDS AND FACE OF CONCRETE WALLS.
UNLESS OTHERWISE INDICATED, PLAN DIMENSIONS ARE TO COLUMN GRID ON CENTERLINES, NOMINAL SURFACE OF MASONRY, FACE OF 1.
APPLICABLE CODES AND STANDARDS
ACCESSIBILITY: 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS.
BUILDINGS.
ENERGY CONSERVATION: 2014 ANSI/ASHRAE/USGBC/IES STANDARD 189.1 STANDARD FOR THE DESIGN OF HIGH-PERFORMANCE GREEN
PORTABLE FIRE EXTINGUISHERS: 2018 NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS.
LIFE SAFETY: 2018 NFPA 101 LIFE SAFETY CODE.
FIRE: 2018 NFPA 1 FIRE CODE.
PLUMBING: 2018 INTERNATIONAL PLUMBING CODE (IPC).
EXISTING BUILDING: 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC).
BUILDING: 2015 INTERNATIONAL BUILDING CODE (IBC).
REFERENCE: UNITED FACILITIES CRITERIA (UFC) 1-200-01, DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS)
0000-A-001
TD PD
044 134
A R
C H
IT
E C
T U
R A
L
L E
G E
N D
AD
12795335
NONE
ADIR
OLF FO ETATS
T C
E
TI
H
CRA DERE
T
SI
G E
R
E G
D
OD .M YHT
O
MI
T
DIGITALLY SIGNED
AR 15126
V A
L F
A C
IL
IT
IE
S E
N G
IN
E E
R
IN
G C
O M
M A
N D M
ID
-A
T L
A N
T
IC
P U
B
R
P A
R T
M E
R L E
N
R L
L
C K
N E
W
J E
R S
S
T E
W A
T E
R T
R E
A T
M E
N T P
L A
P
A
IR
B
Y R
E P
L A
C E
M E
N T S
N A
V
A P
O
A T
R L E
C O
L
C K
N E
W
J E
R S
E
P A
R T
M E
V Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V
C
IL
IT
G
IN
E E
R
M M
A N
D
DES DRW
S Y
M D
E S
C R
IP
T
IO
N D
A T E
A P
P R
DRAWFORM REVISION: 12 APRIL 2018
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
UNCLASSIFIED
ARLINGTON,VA 22201
SUITE 500
1100 N GLEBE ROAD,
APRIL 2020
AS
DM
ADTD PD
O T D
A T
E
P L
O T T
IM
E
-A
P R -2
:1
F
IL
E N
A M
E
B L
D G
-1
-A -1
.d g n
N
LIFE SAFETY / FLOOR PLAN
SCALE: 1/4"=1'-0"
30'-0"
3'-4"4'-8"
16'-0"
ROOM
CHEMICAL
ROOM
ELECTRICAL
600-101
600-103
600-102 600-101A
-1
A
600-102B
600-103A
A-201
72" EXIT LIGHT, ONE SIDED
LIFE SAFETY LEGEND
X'
EGRESS WIDTH (IN INCHES)
X"
ROOM
ELECTRICAL
400-101
GENERAL NOTESSHEET KEYNOTES
TO EXIT IN FEET)
TRAVEL DISTANCE (X = TOTAL DISTANCE
ROOM NAME
ROOM NUMBER
CODE REVIEW - BUILDING CODE REQUIREMENTS
i.
h.
g.
f.
e.
d.
c.
b.
a.
AND STANDARDS
APPLICABLE CODES
BUILDING SEPARATION EXCEPT AS MODIFIED BY UFC 3-600-01.
REQUIREMENTS, ALLOWABLE FLOOR AREA, BUILDING HEIGHT &
IBC 2015: INTERNATIONAL BUILDING CODE FOR FIRE RESISTANCE
(IBC CHAPTER 3)
OCCUPANCY CLASSIFICATION
(IBC CHAPTER 6)
CONSTRUCTION TYPE
NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS.
FACTORY INDUSTRIAL F-2
VB
(IBC SECTION 508)
OCCUPANCY SEPARATION NOT APPLICABLE
NOT APPLICABLE
(IBC SECTION 503, 506, 507)
AREA LIMITATIONS/MODIFICATION
8,500 SF
(IBC TABLE 504.3 & 504.4)
ALLOWABLE HEIGHT 40'-0", 1 STORY
ACTUAL BUILDING HEIGHT 13'-0", 1 STORY
ROOF AND CEILINGS
FLOORS AND CEILINGS
EXT & INT NON-BEARING WALLS
INTERIOR BEARING WALLS
EXTERIOR BEARING WALLS
STRUCTURAL FRAME
(IBC TABLE 601 & SECTION 602)
FIRE-RESISTIVE REQUIREMENTS
0 HOURS
0 HOURS
0 HOURS
0 HOURS
0 HOURS
0 HOURS
l.
k.
j. FIRE SEPARATION REQUIREMENTS
ALLOWABLE FLOOR AREA
ACTUAL BUILDING AREA
10 FEET+ = 0 HOUR RATING
FIRE PROTECTION SYSTEM
FIRE EXTINGUISHERS PROVIDED PER NFPA 10.
FIRE SPRINKLERS NOT REQUIRED, NOT PROVIDED.
TOILET FIXTURES PROVIDED ON SITE WITHIN 500 FEET.
CODE REVIEW - LIFE SAFETY REQUIREMENTS
AND STANDARDS
APPLICABLE CODES
NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS.
(NFPA 101: CHAPTERS 6 & 40)
CLASSIFICATION OF OCCUPANCY
SPECIAL PURPOSE INDUSTRIAL OCCUPANCY NFPA 3.3.168.8.3
LOW HAZARD INDUSTRIAL, NFPA 6.1.12.1 & 6.2.2.2
(NFPA: CHAPTER 7)
OCCUPANT LOAD
OF EGRESS
CAPACITY OF THE MEANS
(NFPA 101: CHAPTERS 7 & 40)
NUMBER OF EXITS
(NFPA 101: CHAPTER 7 & 40)
TRAVEL DISTANCE TO EXITS
(NFPA: TABLE 7.3.12)
MAXIMUM PROBABLE OCCUPANTS = 3
OCCUPANT LOAD FACTOR = NOT APPLICABLEb.
a.
e.
d.
c.
MINIMUM WIDTH PROVIDED = 44"
3 x .20" / PERSON = 0.6" (NFPA 101, 7.3.3.1)
ELECTRICAL ROOM: 2 EXITS REQUIRED (NFPA 70, 110.26 (5)(C)(2))
1 EXIT REQUIRED (NFPA: 40.2.4.1.2)
(NFPA: TABLE 40.2.6.1)
SPECIAL PURPOSE INDUSTRIAL OCCUPANCY: 300 FEET
MAXIMUM TRAVEL DISTANCE TO EXITS (WITHOUT SPRINKLERS)
(NFPA: TABLE 40.2.5.1)
SPECIAL PURPOSE INDUSTRIAL OCCUPANCY: 50 FEET
MAXIMUM COMMON PATH OF TRAVEL (WITHOUT SPRINKLERS)
CODE REVIEW - ENERGY CODE REQUIREMENTS, ASHRAE 90.1
ROOFS MINIMUM R-35 C.I.
SAFETY EXCEPT AS MODIFIED IN UFC 3-600-01.
NFPA 101 LIFE SAFETY CODE, FOR BUILDING EGRESS AND LIFE
e.
d.
c.
b.
a.
SLAB ON GRADE
SWING DOORS
GLAZING, DOOR
MINIMUM R-20 FOR 48 INCHES
MINIMUM U-0.450
SHGC S-0.40, E&W-0.36, N-0.50
U-0.69
MINIMUM
PROVIDED R-35 C.I.
PROVIDED U-0.450
SHGC S-0.40, E&W-0.36, N-0.50
U-0.69
PROVIDED MINIMUM
48 INCHES
PROVIDED R-20 FOR
STORAGE AND DISTRIBUTION OF HAZARDOUS CHEMICALS
CHEMICAL BUILDING
SODIUM HYDROXIDE
SOLUTION FORM HAZMAT TRIANGLE
HEALTH FLAM REACT (SP)
BLUE RED YELLOW WHITE (GAL)
QTY
STORED
CLASS
USE
CODE
DRUM
DRUM
LIQUID
LIQUID
TOTAL
500 GAL 230
230 H-4
H-4
1 HOUR RATED WALL
1,220 SF
>32"
>32"
>32"
32'
14'
16'
12'-0"
0600-A-101
A R
C H
IT
E C
T U
R A
L
C H
E M
IC
A L B
U
IL
D
IN
G P
L A
045 134
STRUCTURE. SEE SPECIFICATION SECTION 13 34 23.
THE CHEMICAL BUILDING IS A PRECAST CONCRETE2.
LEGEND.
SEE SHEET 0000-A-001 FOR GENERAL ARCHITECTURAL 1.
SEE SPECIFICATION SECTION 13 34 00
WALL MOUNTED FIRE EXTINGUISHER
(CONTROL AREA)
CHEMICAL ROOM 600-101
CHEMICALS STORED IN
BELOW GRADE WALLS
ABOVE GRADE WALLS
MINIMUM R-10 C.I.
MINIMUM R-11.4 C.I.
PROVIDER R-10 C.I.
PROVIDED R-11.4 C.I.
1 2
ROOM
TELECOM/DATA
1/4"=1'-0"
16'
12795336
STORAGE
6'0 3' 12'
SCALE: 1/4" = 1'-0"
EYEWASH / SAFETY SHOWER.8.
SINK, SEE PLUMBING.7.
SIDEWALK, SEE CIVIL.6.
EXHAUST FAN.5.
WALL MOUNTED AC UNIT.4.
DRAWINGS.
CONCRETE DOOR STOOP. SEE STRUCTURAL 3.
AND COATING.
SPECIFICATION SECTION 09 90 00 PAINTING
ALL WALLS AND CEILING SURFACES. SEE
PRECAST BUILDING MANUFACTURER. PAINT
INTERIOR PRECAST CONCRETE WALLS BY 2.
HIGH-PERFORMANCE COATINGS.
COATING. SEE SPECIFICATION SECTION 09 96 00
FLOOR AND TRENCH SYSTEM NO.HP-17 SPECIAL1.
AREA
CONTROL
QTY FOR
ALLOWABLE
POLYALUMINUM CHLORIDE 50
25 - 50
COR
ADIR
OLF FO ETATS
T C
E
TI
H
CRA DERE
T
SI
G E
R
E G
D
OD .M YHT
O
MI
T
V A
L F
A C
IL
IT
IE
S E
N G
IN
E E
R
IN
G C
O M
M A
N D M
ID
-A
T L
A N
T
IC
P U
B
R
P A
R T
M E
R L E
N
R L
L
C K
N E
W
J E
R S
S
T E
W A
T E
R T
R E
A T
M E
N T P
L A
P
A
IR
B
Y R
E P
L A
C E
M E
N T S
N A
V
A P
O
A T
R L E
C O
L
C K
N E
W
J E
R S
E
P A
R T
M E
V Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V
C
IL
IT
G
IN
E E
R
M M
A N
D
DES DRW
S Y
M D
E S
C R
IP
T
IO
N D
A T E
A P
P R
DRAWFORM REVISION: 12 APRIL 2018
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
UNCLASSIFIED
ARLINGTON,VA 22201
SUITE 500
1100 N GLEBE ROAD,
APRIL 2020
AS
DM
O T D
A T
E
P L
O T T
IM
E
\0
\0
:3
:2
P
M F
IL
E N
A M
E
B L
D G
-1
-A -2
.d
NORTH ELEVATION
SCALE: 1/4"=1'-0"
SOUTH ELEVATION
SCALE: 1/4"=1'-0"
SCALE: 1/4"=1'-0"
SCALE: 1/4"=1'-0"
EAST ELEVATION
WEST ELEVATION A
BUILDING SECTION
SCALE: 3/8"=1'-0"
600-102 600-101
ROOM
ELECTRICAL
ROOM
CHEMICAL
STANDARD ROOF SLOPE
BUILDING MANUFACTURER'S
STANDARD ROOF SLOPE
BUILDING MANUFACTURER'S
B1
S-501
8 7
A-501
E L E
V A
T
IO
N S
TD PD
0600-A-201
A R
C H
IT
E C
T U
R A
L
C H
E M
IC
A L B
U
IL
D
IN
G
046 134
SHEET KEY NOTES
15'-0"
4'-0"
SCALE: 3/16"=1'-0"
ROOF PLAN
SLOPESLOPE
30'-8"
N
AD
12795337
AS NOTED
8'0 4' 16'
4'0 2' 8'
6'0 3' 12'
SCALE: 1/4" = 1'-0"
6'0 3' 12'
SCALE: 1/4" = 1'-0"
6'0 3' 12'
SCALE: 1/4" = 1'-0"
6'0 3' 12'
SCALE: 1/4" = 1'-0"
SCALE: 3/8" = 1'-0"
SCALE: 3/8" = 1'-0"
9'-6"
3'-0"
15'-0"
20'-4"
15'-0"
FIN FLOOR
EL 94.33
EYEWASH / SAFETY SHOWER.19.
AND 08 71 00.
SPECIFICATION SECTIONS 08 22 20
FRP SINGLE DOOR ASSEMBLY. SEE 18.
SHEET 0900-A-501.
PIPE WALL PENETRATION. SEE DETAILS,17.
EXHAUST FAN.16.
WALL MOUNTED AC UNIT.15.
DETAILS, SHEET 0900-A-501.
ROOF VENT PIPE PENETRATION. SEE 14.
LIGHT FIXTURE. SEE ELECTRICAL DRAWINGS.13.
SECTION 08 91 00 LOUVERS.
24" W x 24" H LOUVER. SEE SPECIFICATION 12.
AND COATING.
SPECIFICATION SECTION 09 90 00 PAINTING
ALL WALLS AND CEILING SURFACES. SEE
PRECAST BUILDING MANUFACTURER. PAINT
INTERIOR PRECAST CONCRETE WALLS BY 11.
HIGH-PERFORMANCE COATINGS.
SPECIFICATION SECTION 09 96 00
NO. HP-17 SPECIAL COATING. SEE
FLOOR AND TRENCH TO RECEIVE SYSTEM10.
SPECIFICATION SECTION 07 21 13.
VAPOR RETARDER. SEE 9.
SPECIFICATION SECTION 07 21 13.
R-20 RIGID XPS INSULATION. SEE 8.
SPECIFICATION SECTION 07 21 13.
R-10 RIGID XPS INSULATION. SEE 7.
AND 08 71 00.
SPECIFICATION SECTIONS 08 22 20
FRP DOUBLE DOOR ASSEMBLY. SEE 6.
08 71 00.
TRANSOM PANEL. SEE SPECS 08 22 20 AND
FRP DOOR ASSEMBLY WITH REMOVABLE 5.
SYSTEM.
R-11.4 INSULATED PRECAST CONCRETE WALL 4.
DECK.
INSULATION OVER PRECAST CONCRETE ROOF
MAT GYP COVERBOARD OVER R-35 RIGID
TPO ROOF MEMBRANE OVER 1/2" FIBERGLASS 3.
SIMULATED BRICK WALL PATTERN, TYP.2.
METAL FASCIA WITH DRIP EDGE.1.
FLR VARIES)
(CHEM RM
0600-A-101
ADIR
OLF FO ETATS
T C
E
TI
H
CRA DERE
T
SI
G E
R
E G
D
OD .M YHT
O
MI
T
V A
L F
A C
IL
IT
IE
S E
N G
IN
E E
R
IN
G C
O M
M A
N D M
ID
-A
T L
A N
T
IC
P U
B
R
P A
R T
M E
R L E
N
R L
L
C K
N E
W
J E
R S
S
T E
W A
T E
R T
R E
A T
M E
N T P
L A
P
A
IR
B
Y R
E P
L A
C E
M E
N T S
N A
V
A P
O
A T
R L E
C O
L
C K
N E
W
J E
R S
E
P A
R T
M E
V Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V
C
IL
IT
G
IN
E E
R
M M
A N
D
DES DRW
S Y
M D
E S
C R
IP
T
IO
N D
A T E
A P
P R
DRAWFORM REVISION: 12 APRIL 2018
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
UNCLASSIFIED
ARLINGTON,VA 22201
SUITE 500
1100 N GLEBE ROAD,
APRIL 2020
AS
DM
AZ
ML
PIPE SEAL
PREFABRICATED
FACTORY
MANUFACTURER'S
ROOFING
PIPE
CUT-OFF MASTIC
SST DRAW BAND
ROOFING
EPDM MEMBRANE
RIGID ROOF INSULATION
TOP OF ROOF DECK
PIPE
PIPE SEAL
PREFABRICATED
FACTORY
MANUFACTURER'S
ROOFING
SEALANT
FLASHING
EPDM MEMBRANE
CUT-OFF MASTIC
SST DRAW BAND
TOP OF ROOF DECK
ROOFING
EPDM MEMBRANE
RIGID ROOF INSULATION
O T D
A T
E
P L
O T T
IM
E
-A
P R -2
:1
F
IL
E N
A M
E
B L
D G
-1
-A -5
.d
ROOF EDGE DETAIL
SCALE: 1 1/2" = 1'-0"
EDGE AND CONTINUOUS CLIP
METAL FASCIA WITH DRIP
SANDWICH WALL PANEL
INSULATED PRECAST CONCRETE
HIGH VOLTAGE
PERSONNEL ONLY
AUTHORIZED
DANGER SIGN
NTS
1.
2.
NOTES:
0 NORMAL MATERIALS
1 SLIGHTLY HAZARDOUS
2 HAZARDOUS
3 EXTREME DANGER
4 DEADLY
RADIATION HAZARD
USE NO WATER
CORROSIVE
ALKALI
ACID
OXIDIZER
W
COR
ALK
ACID
OXY
0 WILL NOT BURN
1 ABOVE 200 F
2 BELOW 200 F
3 BELOW 100 F
4 BELOW 73 F
FLASH POINTS
0 STABLE
1 UNSTABLE IF HEATED
2 VIOLENT CHEMICAL CHANGE
3 SHOCK & HEAT MAY DETONATE
4 MAY DETONATE
LETTER COLOR: BLACK
LETTER HEIGHT: 4"
BLUE BACKGROUND
HEALTH HAZARD -
WHITE BACKGROUND
SPECIAL HAZARD -
RED BACKGROUND
FLAMMABILITY HAZARD -
YELLOW BACKGROUND
INSTABILITY HAZARD -
NTS
FOR REQUIREMENTS ON THIS PROJECT.
ARE EXAMPLES ONLY. SEE SPECIFICATION 10 14 00
NUMBERS AND LETTERS ON ABOVE SIGNAL DETAIL
HAZARDOUS MATERIAL SIGNAL
RED
WHITE
BLACK
047 134
TD KB
C H
IT
E C
T U
R A
L
S T
A N
D A
R D D
E T
A
IL
S
0900-A-501
S
IZ
E A
S S
C H
E D
U L E
D
SIZE AS SCHEDULED
10"10
SCALE: 1 1/2" = 1'-0"
ROOF PENETRATION DETAIL
TAPERED EDGE STRIP
PIPE SLEEVE AND FLANGE
HOT PIPE
AD
12795338
1' 2'0 6"
SCALE: 1 1/2" = 1'-0"
1' 2'0 6"
SCALE: 1 1/2" = 1'-0"
ROOF DECK
PRECAST CONCRETE
CAST DRIP
3/4" CONTINUOUS
GYP COVERBOARD
1/2" FIBERGLASS MAT
TPO ROOF MEMBRANE
SEALANT
THICKNESS
REQUIRED FOR INSULATION
2X PT WOOD BLOCKING AS
WALL PENETRATION DETAIL
INSECT SCREENS
GUIDE LUGS
AT 3 POINTS
MECHANICAL ANCHORS
COUNTERFLASHING
MECHANICAL
WELDED SHEET METAL
TO SLEEVE
VAPOR RETARDER, SEAL
PRECAST CONCRETE WALL PANEL
FABRICATED STRUCTURE INSULATED CORE DRILL
AND SEALANT
WITH BACKER ROD
3/8" ANNULAR SPACE
PANEL INSULATION
MATCHING WALL
FOAM INSULATION
CLOSED CELL SPRAY
SCALE: FULL SCALE: 1"=1"
3"0 3/4" 1-1/2"
ROOF PENETRATION DETAIL
NTS
0600-A-201
0600-A-201 0600-A-201 0600-A-201
TYPICAL
TYPICAL
ADIR
OLF FO ETATS
T C
E
TI
H
CRA DERE
T
SI
G E
R
E G
D
OD .M YHT
O
MI
T
| ARCHITECTURAL |
| 0000-A-001 - ARCHITECTURAL LEGEND |
| 0600-A-101 - ARCHITECTURAL CHEMICAL BUILDING PLAN |
| 0600-A-201 - ARCHITECTURAL CHEMICAL BUILDING ELEVATIONS |
| 0900-A-501 - ARCHITECTURAL STANDARD DETAILS |
| 2020-04-01T15:17:48-0400 | |
| Timothy Dodge |
| 2020-04-01T15:22:00-0400 | |
| Timothy Dodge |
| 2020-04-01T15:22:00-0400 | |
| Timothy Dodge |
| 2020-04-01T15:22:00-0400 | |
| Timothy Dodge |
File details come from the government source that posted it. Updated .