This document is a Questions and Answers (Q&A) file for Solicitation 15B10625Q00000023, concerning Powerhouse Water Treatment at FCC Butner in North Carolina. The Q&A provides critical details for potential bidders, including a mandatory site visit scheduled for July 22, 2025 at 9:00 a.m. EST at the Training Center, with a requirement to submit NCIC documentation by July 17th at 2:00 p.m. EST. The deadline for submitting questions about the Statement of Work is July 24, 2025 at 12:00 p.m. EST.
The document includes technical details about the facility's boiler and chiller systems, noting that the FMC has 3 boilers providing a constant 100 lbs. of steam, typically operating with 1 boiler year-round and 2 during winter months, and 4 chillers with 1 running year-round. The LSCI has 3 boilers supplying heat to FCI-1 and LSCI, with 2 typically online during winter, and 3 chillers providing cooling. The solicitation is a Total Small Business Set-Aside with a NAICS code of 221310 and a small business size standard of $41,000,000, targeting water treatment services for the Federal Correctional Complex.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
15B10625Q00000023 Q&A
POWERHOUSE WATER TREATMENT AT FCC BUTNER
1. Are you planning to have a site visit to see the equipment listed in the Statement of work?
Yes, a site visit will be held on July 22, 2025 at 9:00 a.m. EST. at FCC Butner, Training Center – Old NC Highway 75, Butner, North Carolina 27509.
2. Will there be a deadline for questions pertaining to the Statement of Work, if so, can you post what the deadline due date will be to submit questions?
Yes, the deadline for questions pertaining to the Statement of Work is July 24, 2025, 12:00 p.m. EST.
3. Are there any credentials, forms or Identification requirements for the site visit?
Yes, driver’s license will be required. A NCIC document is required to be completed and emailed to a1huffman@bop.gov and bmckeown@bop.gov by July 17th, 2:00 p.m. EST.
4. What are the boiler hours of operation and the pounds of steam produced per hour?
What are the chiller hours of operation, and approximately how much makeup water is used?
Please be advised that the FMC has (3) boilers that provide a constant 100 lbs. of steam. Under normal conditions it is satisfied with (1) boiler year-round, in some cases (2) boilers during winter months. FMC has (4) chillers of which (1) chiller runs year-round. The amount of makeup water is unknown at this point.
The LSCI has (3) boilers that supply heat to the FCI-1 and the LSCI. In most cases (2) are online at once during winter months. There are (3) chillers that provide cooling to the FCI-1 and the LSCI. Make up water is unknown at this point in time.
The FCI-2 boiler provides heat to the institution.
mailto:a1huffman@bop.gov mailto:bmckeown@bop.gov