This document package includes drawings and specifications for a SCADA, security, and telephone system for the Cle Elum Dam Fish Passage Facility Adult Facility project. The drawings show equipment placement and network diagrams for the juvenile facility, dam gate house, and site. Notes provide requirements for fiber optic panels, future expansion capacity, and responsibility for components. The related federal contract opportunity is a solicitation from the Bureau of Reclamation for the Cle Elum Dam Fish Passage Facility Adult Facility project in the Yakima River Basin Water Enhancement Project in Washington. The solicitation number is 140R1023R0003.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LAR M TA IOCE N
Master Station
Juvenile Facility
Level 3
Level 4
Level 6
Alarm Dialler
Level 7
Level 8
SCADA Cabinet
UPS
Level 5
Level 1
Cameras
24 Pair Fiber
Level 2
Dam Gate House
F.O.
Panel
Note 2 Note 2
Note 1
To Door Controllers
TO Telephone Media Converter
(33-D-60534)
Digital Video Recorder
To POE Switch (33-D-60534)
Facility Security Controllers
Level 1 Main PLC
Crest Gate Controller
Level 6 Remote I/O
To Site Security System
To Reservoir Level Interface
Remote Workstation
To Adult Facility (Future)
24 Pair Fiber (Future) Tunnel Output
F.O.
Panel
6 Pair Fiber (Future)
Network Switch
Network Switch Network
Switch
OIT
Panel
OIT
Panel
Serial to Fiber Converter
Flow Meter (Modbus)
Note 3
Fiber to Serial Converter
F.O.
Panel
PLC Programmable Logic Controller
Uninterruptible Power Supply
Fiber Optic
UPS
Single Mode Fiber Optic Cable Cat6 Ethernet Cable Serial Connection
LEGEND
LAR M TA IOCE N
NOTES
1. Additional fibers in multi-pair fiber optic cable intended for future use.
2. F.O. Patch Panels shall allow termination of all fibers in the multi-pair fiber optic cables which terminate there.
3. Components included in the cloud will be provided by Others in the future. The Flow Meter shall be provided by the Contractor.
4. Size F.O. panels to include sufficient space and termination points to terminate all cables marked as "Future".
5. Drawings are based on "Typical" equipment information and do not represent final design information or drawing details.
Contractor to update and complete design as required.
EXPLANATION
REFERENCE DRAWINGS
Electrical - SCADA SCADA, Security and Telephone Equipment Placement - Facility
33-D-60532
Electrical - SCADA Telephone System Riser Diagram 33-D-60534
Electrical - SCADA SCADA, Security and Telephone Cabinet Layouts
33-D-60537
Electrical - SCADA SCADA, Security and Telephone Equipment Placement - Site
33-D-60868
F.O.
R el ea se d
Juvenile Facility
Dam Gate House NOTES
1. Contractor to verify the location of the Demarcation Point of the POTS lines from the phone company.
2. Provide a life safety POTS line from the Gate House to the Juvenile Facility for 911 services to the Juvenile elevator emergency phones. Provide a POTS line from the Gate House to the Juvenile Facility for the Alarm Dialer. All other telephones shall have individual numbers connected through the IP PBX.
3. Phone communication system shall be Cat 6 Ethernet. All phone connections shall be through a central POE switch located in the Juvenile Facility SCADA Cabinet. Typical POE switch arrangement shown.
4. Drawings are based on "Typical" equipment information and do not represent final design information or drawing details.
Contractor to update and complete design as required.
AOR Area of Rescue PBX Private Branch Exchange POTS Plain Old Telephone System IP PBX Voice Over Internet Protocol
PBX
Single Data/Telephone Connection
Dual Data/Telephone Connection
LEGEND
Single Mode Fiber Optic Cable Cat6 Ethernet Cable Cat3 Cable
EXPLANATION
POE SWITCH
CAT6 HOMERUNS
F.O.Media Converter
To F.O. Panel (33-D-60533)
POTS Lines Note 1
Roof Deck Gate Chamber Exit Door
(Exterior)
(Exterior)
To F.O. Panel (33-D-60533)
Network Switch (33-D-60533)
Roof Deck Gate Chamber AOR
Level 1 Gate Chamber
Level 1 Gate Chamber AOR
Level 2 Gate Chamber AOR
Gate Elevator Helix Elevator Alarm Dialler
Level 3 Gate Chamber AOR
Level 4 Gate Chamber AOR
Level 5 Gate Chamber AOR
Level 6 Gate Chamber AOR
IP-PBX
Roof Deck Helix Chamber Exit Door
Roof Deck Helix Chamber AOR
Level 1 Helix Chamber AOR
Level 2 Helix Chamber AOR
Level 3 Helix Chamber AOR
Level 4 Helix Chamber AOR
Level 5 Helix Chamber AOR
Level 6 Helix Chamber AOR
Level 7 Helix ChamberAOR
Level 8 Helix Chamber AOR
REFERENCE DRAWINGS
Electrical - SCADA SCADA, Security and Telephone Equipment Placement - Facility
33-D-60532
Electrical - SCADA SCADA, Security and Telephone Networks Overview
33-D-60533
Electrical - SCADA SCADA, Security and Telephone Cabinet Layouts
33-D-60537
Electrical - SCADA SCADA, Security and Telephone Equipment Placement - Site
33-D-60868
R el ea se
R el ea se
REV NO
2016-03-31 D C.F.S.
FIXED OFFICIAL RENDITION, FONT SPACING AND OTHER VISUAL ONLY
ASPECTS.
R el ea se
File details come from the government source that posted it. Updated .