B08_Attach_02_North_Rim_Final_CDs_Volume_12_20261012.pdf
PDF 4 MB Posted
- Solicitation number
- 140PP027R0005
- Issued by
- Not on record
About this file
This document is a set of architectural and engineering drawings for the rehabilitation of North Rim infrastructure at Grand Canyon National Park, specifically focusing on Volume 12: Power System – Cottonwood Campground, which includes a photovoltaic (PV) system with a solar shade canopy structure.
The project involves construction of a 5.16kW photovoltaic system with 12 modules arranged in 4 strings, a battery energy storage system (BESS) consisting of 6 modules totaling 11.9kWh and 22.8kWh capacity at 48VDC, and associated electrical infrastructure including two inverters, charge controllers, combiner boxes, disconnects, and grounding systems. The solar shade canopy structure comprises steel framing (HSS columns and beams, C5 channel purlins) supported on 18-inch diameter concrete piers with corrugated Corten roof panels, a composite deck bench, and associated architectural details. Design criteria include wind speed (VULT 101 MPH, VASD 79 MPH), seismic design category C, snow load of 62 PSF ground load with 44 PSF sloped roof load, and a frost depth of 24 inches. Concrete design strength is 4,500 PSI with 60,000 PSI rebar; structural steel uses 50 KSI wide flange members. The drawings specify PVC conduit routing, grounding details with exothermic welds, warning labels and signage for electrical components, and modular equipment racks with shade covers. Delegated design submittals are required for solar panels and solar panel supports, with all work coordinated through HDR Engineering, Inc. as the prime A/E firm, with design dated August 2026 and technical review completed in May 2026.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOLUME # DESCRIPTION
VOLUME 0 GENERAL
VOLUME 1 PIPELINES - NORTH RIM
VOLUME 2 PIPELINES - NORTH RIM TO ROARING SPRINGS PUMPHOUSE (RSPH)
VOLUME 3 PIPELINES - NORTH RIM TO SUPAI TUNNEL
VOLUME 4 PIPELINES - ROARING SPRINGS CAVE TO ROARING SPRINGS PUMPHOUSE (RSPH)
VOLUME 5 ROARING SPRINGS PUMPHOUSE (RSPH)
VOLUME 6 NORTH RIM WATER TREATMENT PLANT
VOLUME 7 NOT USED
VOLUME 8 NORTH RIM WASTEWATER COLLECTION SYSTEM
VOLUME 9 POWER DISTRIBUTION - NORTH RIM
VOLUME 10 POWER DISTRIBUTION - NORTH RIM TO ROARING SPRINGS PUMPHOUSE (RSPH)
VOLUME 11 POWER DISTRIBUTION - ROARING SPRINGS PUMPHOUSE (RSPH) TO MANZANITA
VOLUME 12 POWER SYSTEM - COTTONWOOD CAMPGROUND
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
A/E FIRM
PRIME:
DENVER, CO 80202
HDR ENGINEERING, INC.
A u to d e s k D o c s /1
N P
S
G R
C A
N
R im U ti lit y
/1
G
E N
E R
A L
.r v t
/7
/2
:0
:2
P M
G001
NORTH RIM - GRAND CANYON NATIONAL PARK
318719
SHEET INDEX
M. KUCHLE
A. KANER
AUG 2026
N. LYNCH
182752120
GENERAL
REHABILITATE NORTH RIM
INFRASTRUCTURE
VOLUME 12 POWER SYSTEM - COTTONWOOD CAMPGROUND
WORLD HERITAGE SITE
GRAND CANYON NATIONAL PARK
UNESCO
SHEET SUB SHEET SUB AREA TITLE OF SHEET
1 120G001 GENERAL SHEET INDEX
2 121X101 PHOTOVOLTAIC SYSTEM DEMOLITION PLAN
3 121C101 PHOTOVOLTAIC SYSTEM SITE PLAN
4 121S001 PHOTOVOLTAIC SYSTEM SOLAR SHADE CANOPY GENERAL NOTES
5 121S101 PHOTOVOLTAIC SYSTEM SOLAR SHADE CANOPY FOUNDATION AND ROOF PLANS
6 121S501 PHOTOVOLTAIC SYSTEM SOLAR SHADE CANOPY SECTION AND DETAILS
7 121A101 PHOTOVOLTAIC SYSTEM SOLAR SHADE CANOPY ARCHITECTURAL PLAN AND SECTION
8 121E501 PHOTOVOLTAIC SYSTEM GROUNDING AND TRENCH DETAILS
9 121E502 PHOTOVOLTAIC SYSTEM SOLAR / BATTERY DETAILS
10 121E503 PHOTOVOLTAIC SYSTEM PV CONNECTION DETAILS
11 121E601 PHOTOVOLTAIC SYSTEM DC / AC ONE-LINE DIAGRAM
M. GOUGH
NORTH RIM - GRAND CANYON NATIONAL PARK
DENVER, CO 80202
HDR ENGINEERING, INC.
NORTH RIM - GRAND CANYON NATIONAL PARK
GENERAL
G1. SCOPE
THE NOTES ON THIS SHEET AND THE STANDARD STRUCTURAL DETAILS ARE GENERAL AND
APPLY TO THE ENTIRE PROJECT WHETHER SPECIFICALLY CALLED OUT OR NOT, EXCEPT
WHERE THERE ARE SPECIFIC INDICATIONS TO THE CONTRARY ON STRUCTURAL SHEETS. IF
THERE ARE QUESTIONS, THEY SHALL BE SUBMITTED TO THE CONTRACTING OFFCIER AND
ANSWERED IN WRITING PRIOR TO CONSTRUCTION.
G2. APPLICABLE SPECIFICATIONS AND CODES
A. INTERNATIONAL BUILDING CODE, IBC 2024, WITH APPLICABLE EDITIONS OF THE CODE
REFERENCED STANDARDS.
B. AUTHORITY HAVING JURISTICTION: NATIONAL PARK SERVICE (WIND, SNOW, AND SEISMIC DESIGN
CRITERIA IN ACCORDANCE WITH THE MORE CONSERVATIVE OF COCONINI COUNTY, AZ AND
NATIONAL PARK SERVICE).
C. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, ACI 318-19.
D. MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES, ASCE 7-22.
E. AMERICAN INSTITUTE OF STEEL CONSTRUCTION STEEL CONSTRUCTION MANUAL, 15TH ED.
F. AMERICAN WELDING SOCIETY, AWS D1.1.
G. ASTM MATERIAL STANDARDS AS NOTED.
G3. DESIGN CRITERIA
1. APPLIES TO ALL STRUCTURES
A. DEAD LOAD:
1. ACTUAL TRIBUTARY STRUCTURE WEIGHT
2. SUPERIMPOSED DEAD LOAD: 3 PSF (SOLAR PANELS)
B. LIVE LOAD:
1. ROOF: 20 PSF (NOT REDUCIBLE)
C. WIND:
1. ULTIMATE WIND SPEED (VULT): 101 MPH
2. TORNADO SPEED (VT): NOT APPLICABLE PER ASCE 7
FIGURES 32.1-1 & 1-2
3. NOMINAL WIND SPEED (VASD): 79 MPH
4. RISK CATEGORY: II
5. EFFECTIVE PLAN AREA (AE): NOT APPLICABLE
6. EXPOSURE CATEGORY: C
7. ENCLOSURE CLASSIFICATION: OPEN
D. SEISMIC:
1. ABOVE GRADE, CANOPY STRUCTURE:
a. RISK CATEGORY, II
b. IMPORTANCE FACTOR: 1.00
c. SPECTRAL RESPONSE ACCELERATION, SS = 0.42 g
d. SPECTRAL RESPONSE ACCELERATION, S1 = 0.11 g
e. SITE CLASS: D
f. SEISMIC DESIGN CATEGORY: C
g. SPECTRAL RESPONSE ACCELERATION, SDS = 0.38 g
h. SPECTRAL RESPONSE ACCELERATION, SD1 = 0.2 g
i. BASIC SEISMIC FORCE RESISTING SYSTEM: STEEL SYSTEMS NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE,
j. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
k. DESIGN BASE SHEAR: 0.10 KIPS
l. SEISMIC RESPONSE COEFFICIENT, Cs = 0.07
m. RESPONSE MODIFICATION FACTOR, R = 3.0
E. SNOW LOAD:
1. GROUND SNOW LOAD = 62 PSF
2. SLOPED ROOF SNOW LOAD = 44 PSF
3. EXPOSURE FACTOR = 0.90
4. IMPORTANCE FACTOR = 1.00
5. THERMAL FACTOR = 1.20
6. FROST DEPTH: = 24 IN
7. WINTER WIND PARAMETER (W2) = 0.35
G4. THE FOLLOWING NON-CONTRACTUAL GEOTECHNICAL REPORT WAS DEVELOPED FOR THIS
PROJECT AND IS THE BASIS OF THIS STRUCTURAL DESIGN:
GEOTECHNICAL FIRM NAME: LITHOS ENGINEERING
ADDRESS: 2750 S. WADSWORTH BLVD, SUITE D-200
DENVER, CO 80227
REPORT NUMBER: 21186
REPORT DATE: JANUARY 30, 2024
NET ALLOWABLE BEARING PRESSURE: 2000 PSF
G5. SAFETY
SAFETY AND STRUCTURE STABILITY DURING CONSTRUCTION ARE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR. STRUCTURES HAVE BEEN DESIGNED TO RESIST THE DESIGN LIVE
LOADS ONLY AS A COMPLETED STRUCTURE.
G6. OPENINGS
OPENINGS FOR PIPES, DUCTS, CONDUITS, ETC. ARE NOT ALL SHOWN ON THE
STRUCTURAL DRAWINGS. COORDINATE AND PROVIDE OPENINGS AS REQUIRED TO
ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND
OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT.
REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE
SHOWN.
G7. SPECIAL INSPECTIONS
SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH CHAPTER 1 AND CHAPTER 17
OF THE IBC. THE CONTRACTOR IS RESPONSIBLE FOR SPECIAL INSPECTIONS (STSI) BY QUALIFIED
PERSONNEL. THE CONTRACTOR SHALL PROVIDE FOR FULL ACCESS TO THE WORK
BY STSI AGENTS AND SHALL PROVIDE FOR THESE INSPECTIONS IN THEIR
CONSTRUCTION SCHEDULE IN ACCORDANCE WITH THE SPECIFICATIONS. THE SPECIAL
INSPECTION PROGRAM AND STATEMENT OF SPECIAL INSPECTIONS SHALL BE IN ACCORDANCE
WITH 01 45 33.
G8. STANDARD DETAILS
THE STANDARD DETAILS DEPICT TYPICAL DETAILING TO BE USED ON THIS PROJECT. IF
CONDITIONS ARE NOT EXPLICITLY SHOWN ON THE DRAWINGS THEY SHALL BE MADE
SIMILAR TO THE STANDARD DETAILS. OBTAIN APPROVAL OF THE CONTRACTING OFFICER IN
WRITING FOR SIMILAR CONDITIONS PRIOR TO CONSTRUCTION.
G9. FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED
CHANGES FOR APPROVAL.
G10. SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING WEIGHTS, VIBRATION FORCES,
SUPPORT LOCATIONS, ALONG WITH ANY FLOOR OPENINGS, NOTCHES, AND RECESSES
REQUIRED BY SUCH EQUIPMENT. CONCRETE SUPPORT PADS AND/OR FRAMING REQUIRED
TO SUPPORT SAID EQUIPMENT SHALL NOT BE FABRICATED AND PLACED UNTIL THE CONCRETE
SUPPORT PADS AND/OR FRAMING IS APPROVED TO SUPPORT THE EQUIPMENT.
CONCRETE
C1. DESIGN STRENGTHS:
F'c = 4,500 PSI REBAR Fy = 60,000 PSI PRECAST F'c = 5,000 PSI
C2. CONCRETE COVER
UNLESS OTHERWISE NOTED, PROVIDE CONCRETE COVER FOR REINFORCING AS FOLLOWS:
CONCRETE DEPOSITED AGAINST EARTH: 3"
ALL OTHER: 2"
WATERSTOPS: 3"
SEE DRAWINGS FOR EXCEPTIONS
C3. SEE SPECIFICATIONS FOR REINFORCING PLACEMENT REQUIREMENTS.
C4. REFER TO OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION FOR EMBEDDED ITEMS
AND PENETRATIONS NOT SHOWN ON STRUCTURAL DRAWINGS. AS REQUIRED TO
ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND
OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT.
REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE
SHOWN.
C5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED EDGES. NOT ALL CHAMFERS MAY BE SHOWN
ON DRAWINGS.
C6. FIELD ADJUST REINFORCING AT OPENINGS AND EMBEDDED ITEMS AS INDICATED.
C7. ANCHOR BOLTS NOT SPECIFIED BY CONTRACTING OFFICER SHALL BE DESIGNED AND CERTIFIED BY A
REGISTERED PROFESSIONAL ENGINEER LICENSED IN THE STATE OF ARIZONA, RETAINED
BY THE CONTRACTOR, IN ACCORDANCE WITH APPLICABLE PROJECT AND CODE REQUIREMENTS.
SUBMIT AS A SHOP DRAWING FOR REVIEW AND APPROVAL BY THE CONTRACTING OFFICER. COORDINATE
LOCATION, SIZE AND EMBEDMENT PRIOR TO CASTING CONCRETE.
C8. CONTINUOUS WATERSTOP SHALL BE INSTALLED IN JOINTS SUBJECT TO STATIC WATER
PRESSURE.
C9. ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND REINFORCING
BARS SHALL BE ALLOWED WITHOUT SPECIFIC APPROVAL FROM THE CONTRACTING OFFICER.
C10. CONTRACTOR SHALL SUBMIT A CONCRETE PLACEMENT PLAN PER SPECIFICATION 03 31 31
IDENTIFYING JOINT TYPES, JOINT LOCATIONS AND CONCRETE PLACEMENT SEQUENCE.
C11. ALL CAST IN PLACE AND POST-INSTALLED ANCHORS INDICATED IN THE STRUCTURAL
DOCUMENTS SHALL COMPLY WITH CHAPTER 17 OF ACI 318 AND CHAPTER 19 OF THE
IBC. ALL EXPANSION AND ADHESIVE ANCHORS SHALL HAVE THE ICC REPORT SHOWING
EQUIVALENT LOAD CAPACITY. SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
STEEL
S1. DESIGN STRENGTHS:
WIDE FLANGE AND TEES: Fy=50 KSI PIPES: Fy=35 KSI STAINLESS STEEL: Fy=33 KSI HSS SECTIONS: Fy=50 KSI ALL OTHER PLATES AND SHAPES: Fy=36 KSI ANCHOR RODS: Fy=36 KSI
S2. DIMENSIONS:
TO CENTERLINES OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND TUBES AND
BACKS OF CHANNELS AND ANGLES UNO.
S3. ELEVATIONS:
TOP OF STEEL REFERS TO TOP SURFACE OF MEMBER OR FLANGE UNO.
S4. WHEN FILLET WELD SIZE IS NOT INDICATED, PROVIDE MAXIMUM WELD SIZE BASED ON
MATERIAL THICKNESS IN ACCORDANCE WITH AISC SPECIFICATIONS.
S5. ALL BOLTED STRUCTURAL CONNECTIONS ARE BEARING TYPE CONNECTIONS UNLESS
OTHERWISE SPECIFIED TO BE SLIP-CRITICAL. PROVIDE LOAD INDICATING WASHERS AT
SLIP-CRITICAL CONNECTIONS.
S6. CONFORM TO AISC 360, STEEL CONSTRUCTION MANUAL AND AISC 341, SEISMIC DESIGN
MANUAL.
S7. THE SEISMIC LOAD RESISTING SYSTEM (SLRS) IS DENOTED ON THE FRAMING PLANS AND
FRAME ELEVATIONS. THE SLRS DESIGNATION INCLUDES THE MEMBER AND CONNECTIONS
AT EACH END. FRAMES ARE DENOTED AS FOLLOWS:
A. MOMENT FRAME:
FOR SLRS SYSTEMS OR PARTS OF SYSTEMS THAT ARE NOT INCLUDED IN FRAMES,
(SLRS) IS PLACED NEXT TO THE BEAM SIZE ON THE FRAMING PLAN (eg: ON A
COLLECTOR ELEMENT (DRAG STRUT):
S8. ALL STEEL BEAMS SHALL RECEIVE STANDARD CAMBER PER THE SPECIFICATIONS UNLESS
NOTED OTHERWISE ON THE PLANS. BEAMS REQUIRING SPECIAL CAMBER ARE DENOTED
ON THE BEAMS SHOWN ON THE FRAMING PLANS. EXAMPLE: (+1/2") INDICATES ½".
S9. PROVIDE 1/4" CAP PL AT ALL OPEN ENDS OF HSS FRAMING MEMBERS AND SEAL WELD.
(SLRS)
EARTHWORK
E1. ALL EARTHWORK AND SITE PREPARATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH
THE SPECIFICATIONS. ALL FOUNDATION EXCAVATIONS SHALL BE OBSERVED AND APPROVED BY
THE GEOTECHNICAL ENGINEER.
E2. ANY EXISTING FILLS OR UNSUITABLE SOILS AS DETERMINED BY THE GEOTECHNICAL ENGINEER
SHALL BE EXCAVATED AND REPLACED WITH PROPERLY COMPACTED SELECT FILL PER
SPECIFICATIONS.
E3. CONTRACTOR SHALL EXERCISE EXTREME CARE WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING STRUCTURES SO AS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS, WALLS, SLABS, OR
UTILITIES, ETC.
E4. DO NOT EXCAVATE BELOW THE BEARING ELEVATION OF ANY COMPLETED FOOTING NOR ANY
CLOSER TO THE FOOTING THAN A SLOPE OF TWO HORIZONTAL (MEASURED FROM EDGE OF
FOOTING TO NEAREST POINT IN EXCAVATION) TO ONE VERTICAL.
E5. ALL FOUNDATIONS AND SLABS ON GRADE SHALL BE PLACED ON A MINIMUM OF 12" OF SELECT FILL PER
SPECIFICATIONS.
DELEGATED SUBMITALS
D1. DEFINITION:
DELEGATED DESIGN SUBMITTALS ARE ITEMS FOR WHICH THE FINAL DESIGN OF A SPECIFIC
ELEMENT OF THE PERMANENT CONSTRUCTION WORK EXPRESSLY DELEGATED TO A PROPERLY
LICENSED AND REGISTERED DESIGN PROFESSIONAL RETAINED OR EMPLOYED BY THE
CONTRACTOR, SUBCONTRACTOR, SUPPLIER OF ANY TIER. "DELEGATED DESIGN" APPLIES ONLY TO PERMANENT WORK THAT WILL BE PART OF THE COMPLETED PROJECT AS A FUNCTIONING WHOLE.
D2. DELEGATED DESIGN LIST:
THE FOLLOWING IS A LIST OF DELEGATED DESIGN SUBMITTALS THAT ARE EXPECTED TO CONTAIN
STRUCTURAL CALCULATIONS OF SAFETY-RELATED SYSTEM INFORMATION FOR REVIEW. THESE
SUBMITTALS APPLY TO DELEGATED DESIGNED SYSTEMS PRIOR TO INSTALLATION OF THE
INDICATED STRUCTURAL ELEMENT, EQUIPMENT, DISTRIBUTION SYSTEM, COMPONENT, OR ITS
ANCHORAGE. THE CONTRACTOR SHALL SUBMIT THE REQUIRED ENGINEER CERTIFICATION,
SUPPORTING DATA, AND DRAWINGS FOR REVIEW AND ACCEPTANCE BY THE CONTRACTING
OFFICER.
D3. DELEGATED DESIGN SUBMITTAL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
1. SOLAR PANELS
2. SOLAR PANEL SUPPORTS
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
A/E FIRM
PRIME:
PM: MATTHEW GOUGH
DENVER, CO
HDR ENGINEERING, INC.
A u to d e s k D o c s /1
N
P S
G
R C
A N
R im
U ti lit y
/1
C A
N O
P Y
U
.r v t
/1
/2
:5
:0
P M
S001
NORTH RIM - GRAND CANYON NATIONAL PARK
318719
SOLAR SHADE CANOPY
GENERAL NOTES
J. PEREZ
J. CORONADO
MAY 2026
J. PEREZ
182752121
PHOTOVOLTAIC SYSTEM
NORTH RIM - GRAND CANYON NATIONAL PARK
A
121S501
A
B
1 2 3
12'-8"
6'-4" 6'-4"
18" DIAMETER CONCRETE PIER TYPICAL TOP OF
CONC = 4028.00
A
121S501
A
B
1 2 3
HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4
C5X6.7
C5X6.7
H S
S
X X
/4
H S
S
X X
/4
HSS4X4X1/4HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4
H S
S
X X
/4
H S
S
X X
/4
H S
S
X X
/4
HSS6X4X1/4
HSS6X4X1/4
18'-4"
121S501
2'-10" 6'-4" 6'-4" 2'-10"
R O
O F
S L O
P E
W/ C5X6.7 ATOP
W/ C5X6.7 ATOP
HSS 4X2X1/4 BRACE
HSS 4X2X1/4 BRACE
HSS 4X2X1/4 BRACE
HSS 4X2X1/4 BRACE
ASCALE 1/2" = 1'-0"
2 0 2 4
SCALE OF FEET
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
A/E FIRM
PRIME:
PM: MATTHEW GOUGH
DENVER, CO
HDR ENGINEERING, INC.
A u to d e s k D o c s /1
N
P S
G
R C
A N
R im
U ti lit y
/1
C A
N O
P Y
U
.r v t
/1
/2
:5
:0
P M
S101
NORTH RIM - GRAND CANYON NATIONAL PARK
318719
SOLAR SHADE CANOPY
FOUNDATION AND ROOF
PLANS
J. PEREZ
J. CORONADO
MAY 2026
J. PEREZ
182752121
PHOTOVOLTAIC SYSTEM
SCALE A121S101
1 FOUNDATION PLAN
SCALE A121S101
2 ROOF PLAN
GENERAL NOTES
A. COORDINATE THE STRUCTURAL DRAWINGS WITH
ALL OTHER DISCIPLINE DRAWINGS FOR PIPING.
EQUIPMENT, ANCHORS, CONDUITS, HOUSEKEEPING
PADS, AND ANY OTHER ITEMS ATTACHED TO OR
EMBEDDED IN STRUCTURAL ELEMENTS THAT MAY
NOT BE SHOWN.
B. ALL STEEL SHALL BE SHOP PRIMED AND PAINTED IN
ACCORDANCE WITH SPEC. 09 96 00.
KEYNOTES
1 CORRUGATED CORETEN ROOF PER
ARCHITECTURE. FASTENING PER MFR.
2 TYPICAL COLUMN AND BASE PLATE:HSS
4x4x1/4 W/ BASE PL3/4x9x9 W/ (4) 1/2" DIA x
12" EMBEDMENT ANCHOR RODS. RODS
TO BE F1554, GR 36, GALVANIZED.
NORTH RIM - GRAND CANYON NATIONAL PARK
TO GRADE
4027.50
AB
121S501
121S501
121S501
EL 4036.59
EL 4039.94
30°
EL 4035.69
WORK POINT
WORK POINT
WORK POINT
WORK POINT
RIDGE
EAVE
TO WP
WORK POINTWORK POINT
121S501
HSS COL PER PLAN
C5 PER PLAN
HSS PER PLAN
CORRUGATED CORETEN
ROOF, SEE ARCH. DRAWINGS
HSS PER PLAN
1/4
TYP
CAP PL 1/2"x6"x0'-6", TYP
1/4
TYP
WORK POINT
HSS COL. PER PLAN
HSS PER PLAN
C5 PER PLAN
1/4
TYP
1/4
TYP
1/4
TYP
3/8
TYP
L2x2x1/4
1"
WORK POINT
2'-5"
WORK POINT
7"
3"
6"
1/4"x12" BENT PLATE, SPACE AT 4'-0" INTERVALS.
HSS COL. PER PLAN
PL 1/2"X9"X0'-9"
w/(4) - 1/2" Ø ANCHOR BOLTS
5" EMBEDED
TYPICAL PIER:
18" DIAMETER CONCRETE PIER
W/ (6) #6 VERTS AND #3 TIES @ 12".
PLACE (4) TIES AT 3" SPACING AT
THE TOP OF PIER.
1 1/2" NON-SHRINK GROUT
1'-6"
HSS 4X2X1/2
1/4
TYP
"FINISHED GRADE
L2X2X1/4X 1'-4" ANGLE,
FOR BENCH. SINGLE ANGLE
ON THE ENDS AND DOUBLE
ON THE CENTER MEMBER
3/16
WORK POINT
3/16
HSS 4X2X1/4
4 INCH FACE VERTICAL
6"
1/4
TYP
WORK POINT
WORK POINT
ROOF PER PLAN
HSS COL PER PLAN
2'-10"
1/4
TYP
WORK POINT
HSS COLUMN PER PLAN HSS4X4X1/4
30°
CORETEN ROOF PER ARCH.
C5X6.7
BSCALE
ASCALE
3/4" = 1'-0"
SCALE OF FEET
0 1 2 3
1/2" = 1'-0" 2 0 2 4
SCALE OF FEET
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
A/E FIRM
PRIME:
PM: MATTHEW GOUGH
DENVER, CO
HDR ENGINEERING, INC.
A u to d e s k D o c s /1
N
P S
G
R C
A N
R im
U ti lit y
/1
C A
N O
P Y
U
.r v t
/1
/2
:5
:1
P M
S501
NORTH RIM - GRAND CANYON NATIONAL PARK
318719
SOLAR SHADE CANOPY
SECTION AND DETAILS
J. PEREZ
J. CORONADO
MAY 2026
J. PEREZ
182752121
PHOTOVOLTAIC SYSTEM
SCALE A121S501
A SECTION
SCALE B121S501
1 RIDGE DETAIL
SCALE B121S501
2 EAVE DETAIL
SCALE B121S501
3 CONCRETE PIER DETAIL
GENERAL NOTES
A. COORDINATE THE STRUCTURAL DRAWINGS WITH
ALL OTHER DISCIPLINE DRAWINGS FOR PIPING.
EQUIPMENT, ANCHORS. CONDUITS, HOUSEKEEPING
PADS, AND ANY OTHER ITEMS ATTACHED TO OR
EMBEDDED IN STRUCTURAL ELEMENTS THAT MAY
NOT BE SHOWN.
B. ATTACHMENT OF SOLAR ARRAY TO STRUCTURAL STEEL
BY SOLAR PANEL MANUFACTURER.
C. PROVIDE CAP 1/4 AT ENDS OF ALL EXPOSED HSS ENDS.
PROVIDE WEEP HOLES AT COLUMN BASES AS NEEDED.
SCALE A121S501
4 OVERHANG KICKBACK, TYP
SCALE A121S501
5 BRACE CONNECTION DETAIL
NORTH RIM - GRAND CANYON NATIONAL PARK
A 121A101
A
B
1 2 3
6'-4" 6'-4"
12'-8"
9' -0
COMPOSITE DECK BENCH
STEEL COLUMN STEEL BEAMS
COLUMN FOUNDATION
TO GRADE
4027.50
EAVE
4036.87
RIDGE
4040.20
AB
COMPOSITE DECK BOARD
BENCH2'-0" 2'-6" 2'-6" 2'-0"
PURLIN
TURN DOWN CORTEN ROOF PANEL
4' -0
COMPOSITE DECK
SPACER
CORRUGATED CORTEN ROOF PANEL;
UNFINISHED FOR NATURAL AGING
1"
1"
4" TS BRACE; SEE STRUCTURAL
4" TS BRACE; SEE STRUCTURAL
4" TS BRACE; SEE STRUCTURAL
9'-0"
MOUNTING
ANGLE
121A101
CHANNEL PURLIN; SEE FRAMING PLAN
5" / 1'-0"
2'-10"
NOTE: PAINT ALL STEEL
FRAME PER 09 98 00. DO NOT
PAINT CORTEN PANELS
MFR STANDARD
EDGE CLOSURE
TRIM
MFR STANDARD EDGE
CLOSURE TRIM
MFR STANDARD DRIP EDGE
CLOSURE TRIM
121A101
TO GRADE
4027.50
A
2" (1.3" x 3.4"x cont)
SQUARE EDGE
COMPOSITE DECK BOARD
1" (.94"x 2.75 x 4" @ 24"o.c. ) RIPPED SQUARE
EDGE COMPOSITE DECK
SPACER
2"x2"x1/4"x1'-4"
MOUNTING ANGLE W/
SLOTTED HOLES FOR
BENCH MOUNTING
2'-0"
(3) 1/4" CARRAGE BOLT
THRU MOUNTING ANGLE
AT EACH POST
SUPPORT
3" 1'
-2
MOUNTING PLATE;
SEE STRUCTURAL
NAIL THRU EACH VERT
MOUNT DECK BOARDS AT
SPACER FOR COMPOSITE
SLATTED BENCH SEAT
CUT AND CAP
OUTRIGGER END
DRILL (2) WEEP
HOLES AT
BOTTOM
17" - 19" SEAT
HEIGHT (ADA)
EAVE
4036.87
8"
PURLIN
TURN DOWN CORTEN ROOF
PANEL, ANCHOR W/ EXPOSED
ANCHORS PER MFR REQUIREMENT
CORRUGATED CORTEN ROOF PANEL;
UNFINISHED FOR NATURAL AGING
4" TS BRACE; SEE STRUCTURAL
MFR STANDARD DRIP EDGE
CLOSURE TRIM
BENT PLATE EDGE TRIM ANCHOR TRIM
BSCALE
ASCALE
SCALE OF FEET
12 6 12 1-1/2" = 1'-0"
1/2" = 1'-0" 2 0 2 4
SCALE OF FEET
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
A/E FIRM
PRIME:
PM: MATTHEW GOUGH
DENVER, CO
HDR ENGINEERING, INC.
C :\U se rs
\jg ol dm an
\A pp
D at a\ Lo ca l\A ut od es k\
R ev it\ Au to de sk R ev it
\C ol la bo ra tio nC ac he \Q
W M
U
H 9P
6P 3K
G M
7\ d0
0f d9 -8
2-
-8 5b b-f4 a9 be 8b c9 \3 b2 a4 f5 0-be 1d
-4 fe d-ac
-1 e2 b4 de c5 e.
rv t
4/
/2
9:
:2
AM
A101 NORTH RIM - GRAND CANYON NATIONAL PARK
318719
SOLAR SHADE CANOPY
ARCHITECTURAL PLAN AND
SECTION
R. McKINLEY
S. HEANEY
MAY 2026
D. SPERRY
182752121
PHOTOVOLTAIC SYSTEM
SCALE A121A101
1 SHADE STRUCTURE PLAN
SCALE A121A101
A A101/2 SHADE STRUCTURE SECTION
SCALE B121A101
2 BENCH DETAIL
SCALE B121A101
3 EAVE DETAIL
2026.05.01
GRADE
1" SCH. 40 PVC CONDUIT
(TYP.)
COMPACTED NATIVE SOIL
DC CONDUCTOR
(TYP.)
GROUND
CONDUCTOR
SCALE
GROUNDING DIAGRAM
NTS
121E501
SCALE
TRENCH SECTION - PV DC CIRCUIT
NTS
121E501
6" (MIN)
NOTES:
1. SHADE STRUCTURE SHALL BE CONTINUOUSLY BONDED BY SEPARATE
GROUND BONDS OR MECHANICAL CONNECTIONS UL-LISTED FOR THE
PURPOSE. BOND ALL STRUCTURAL MEMBERS, SUPPORT PILES, AND
CONCRETE REBAR.
2. BOND PV MODULE FRAMES TO MODULE RACKING AND STRUCTURE
WITH "WEEB" CLIPS OR EQUIVALENT.
3. BURIED GROUND CONNECTIONS SHALL BE EXOTHERMIC WELDS OR
OTHER IRREVERSIBLE CONNECTION.
4. BOND EQUIPMENT GROUND TO EQUIPMENT PAD REBAR WHERE
APPLICABLE.
2" (MIN)
#4/0 AWG GROUND RING
PLACED 1' FROM SHADE
STRUCTURE GROUND ROD CONNECTED
TO GROUND RING
NOTE 2
NOTE 3
#10 AWG TO
INVERTER
#6 AWG TO BATTERY
ENCLOSURE
#4/0 AWG TO
GROUND RING
#8 AWG TO
GROUND ROD
FRAME
CONNECTION
(TYP.)
GRADE
2" SCH. 40 PVC CONDUIT
(TYP.)
COMPACTED NATIVE SOIL
DC CONDUCTOR
(TYP.)
SCALE
TRENCH SECTION - BESS DC CIRCUIT
NTS
121E501
6" (MIN)
GRADE
1" SCH. 40 PVC CONDUIT
(TYP.)
COMPACTED NATIVE SOIL
AC CONDUCTOR
(TYP.)
GROUND
CONDUCTOR
SCALE
TRENCH SECTION - AC CIRCUIT
NTS
121E501
6" (MIN)
#10 AWG TO SERVICE
DISCONNECT
#2 AWG TO
GROUND ROD
EXIST GROUND TO
SERVICE DISCONNECT
NORTH RIM - GRAND CANYON NATIONAL PARK
PV PANELS
1" SCH 80 PVC CONDUIT CLAMP
1" SCH 80 PVC CONDUIT
SHADE STRUCTURE SUPPORT
FINISHED GRADE
TO COMBINER BOXES
DC (+) CONDUCTOR
BATTERY
ENCLOSURE
LI-ION
BATTERY
DC (-)
CONDUCTOR
ENCLOSURE GROUND CONDUCTOR
2" SCH 40 PVC (TYP)
TO INVERTER
CONCRETE PAD
PER STD DETAIL
3/003S501
GRADE
WEATHERHEAD
INVERTER A
DC
BREAKER
BOX
CHARGE
CONTROLLER
A
INVERTER B
" M
IN
IM
U M
" M
AX
IM
U M
COMBINER A COMBINER B
2" SCH 80 PVC FROM
BATTERY ENCLOSURE
72" MINIMUM
1" SCH 80 PVC FROM PV ARRAY
1" SCH 80 PVC FROM PV ARRAY
2" SCH 80 PVC TO MAIN RANGER
STATION DISCONNECT.
MODULAR EQUIPMENT
RACK
NEMA 3R ENCLOSURE
SEE GROUNDING DETAIL
ON SHEET 000E502
GRADE
RANGER STATION WALL
MAIN RANGER STATION
SERVICE DISCONNECT
SECURE CONDUIT TO WALL
WITH CONDUIT CLAMP
WHERE NECESSARY
SCH80 PVC
SCH40 PVC
36" 24" MINIMUM
NOTE E
48" MINIMUM
" M
IN
IM
U
M CHARGE
CONTROLLER
B
AC
BREAKER
BOX
INVERTER SYSTEM
SIDE VIEWFRONT VIEW
MODULAR STRUT
SHADE COVER
CONCRETE PAD
FLAT PLATE FITTING (TYP.)
NEMA 3R ENCLOSURE
1/2 HEIGHT MODULAR
STRUT
ANGULAR FITTING (TYP.)
GRADE
SHADE COVER
NORTH RIM - GRAND CANYON NATIONAL PARK
TO COMBINER BOX 1
TO COMBINER BOX 1
TO COMBINER BOX 2
TO COMBINER BOX 2
SCALE
PV MODULE CONNECTOR DETAIL
NTS
121E503 SCALE
PV DISCONNECT SWITCH WARNING SIGN
NTS
121E503 SCALE
PV DISCONNECT SWITCH WARNING SIGN
NTS
121E503
CONNECTORS SHALL BE:
1. OF THE SAME MANUFACTURER
2. LOCKING TYPE, 1000VDC
3. COMPATIBLE WITH MANUFACTURER'S SUPPLIED CONNECTORS
4. CRIMPED ONTO THE SOURCE CIRCUIT WIRE USING PROCEDURE
5. TOOLS RECOMMENDED BY MANUFACTURER
6. SECURED SO NOT SUBJECTED TO RAIN DIRECTLY
SCALE
TYPICAL PV WIRE MANAGEMENT
NTS
121E503
DETAILS NOTES:
1. DO NOT STRAIN MANUFACTURER INSTALLED MODULE LEADS.
2. SECURE WIRES TO MODULE FRAME WITH STAINLESS STEEL METAL
CLIP. CLIPS SHALL BE SIZED APPROPRIATELY TO SECURELY FASTEN
THE CABLE SIZE/QUANTITY AS SPECIFIED IN THE DESIGN.
3. ENSURE CONNECTORS ARE UNDER THE MODULES, PROTECTED FROM
ELEMENTS, NOT IN THE GAP BETWEEN MODULES.
PHOTOVOLTAIC
DISCONNECT SWITCH
WARNING:
ELECTRIC SHOCK HAZARD. DO NOT TOUCH
TERMINALS. TERMINALS ON BOTH THE
LINE AND LOAD SIDE MAY ENERGIZED IN
THE OPEN POSITION.
OPERATING CURRENT: 26 AMPS
OPERATING VOLTAGE: 98.2V DC
MAXIMUM CURRENT: 27.5 AMPS
MAXIMUM VOLTAGE: 117.1V DC
ELECTRIC SHOCK HAZARD. DO NOT
TOUCH TERMINALS. TERMINALS ON
BOTH THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN
POSITION.
WARNING:
DETAILS NOTES:
1. PROVIDE WARNING SIGN FOR EACH PV COMBINER/DISCONNECT.
DETAILS NOTES:
1. PROVIDE WARNING LABEL FOR BATTERY ENCLOSURE AND INVERTER UNIT.
NORTH RIM - GRAND CANYON NATIONAL PARK
DC NEGATIVE
BUS BAR
DC POSITIVE
BUS BAR
2 #4/0 AWG CU
1 #6 AWG CU GW
2"C
4 #10 AWG CU
2 #10 AWG CU
1"C
2 #6 AWG CU
1 #8 AWG CU GW
1"C
NOTE I (TYP.)
4#10 AWG CU
1#10 AWG GW
2"C
SHUNT (TYP.)
NORTH RIM - GRAND CANYON NATIONAL PARK
| VOLUME 12 - POWER SYSTEM COTTONNWOOD CAMPGROUND |
| 120 GENERAL SHEETS |
| 120 G001 - SHEET INDEX |
| 121 PHOTOVOLTAIC SYSTEM SHEETS |
| 121 X101 - DEMOLITION PLAN |
| 121 C101 - SITE PLAN |
| 121 S001 - SOLAR SHADE CANOPY GENERAL NOTES |
| 121 S101 - SOLAR SHADE CANOPY FOUNDATION AND ROOF PLANS |
| 121 S501 - SOLAR SHADE CANOPY SECTION AND DETAILS |
| 121 A101 - SOLAR SHADE CANOPY ARCHITECTURAL PLAN AND SECTION |
| 121 E501 - GROUNDING AND TRENCH DETAILS |
| 121 E502 - SOLAR / BATTERY DETAILS |
| 121 E503 - PV CONNECTION DETAILS |
| 121 E601 - DC/AC SCHEMATIC DIAGRAM |
File details come from the government source that posted it. Updated .