This document is a mechanical drawing for a Fan Coil Unit Replacement project at the First Ladies National Historic Site in Canton, OH. The drawing depicts the third floor mechanical plan, showing the locations of multiple fan coil units (FCUs) to be removed and replaced. Key specifications include:
The project involves a like-for-like replacement of existing fan coil units, with no changes to electrical gear or circuits expected. Contractors must carefully disconnect and remove existing units, photo-document any pre-existing damage, and install new fan coil units connected to existing isolation valves. The new thermostats will be wireless and positioned as directed by the Contracting Officer Representative. The work is part of a solicitation (140P6425B0004) valued between $500,000 and $750,000, set aside 100% for small businesses, with anticipated work beginning in June 2025.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site_Visit_Attendees_List_0001.pdf | ||
| Sol_140P6425B0004_Amd_0001.pdf | ||
| Questions_and_Answers_0001.pdf | ||
| Wage_Determination_-_Stark_Co.pdf | ||
| Attachment_-_Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| Attachment_-_Submittal_List.pdf | ||
| Bid_Schedule_-_Fan_Coil_Replace.xlsx | XLSX spreadsheet | |
| Specifications_-_Fan_Coil_Replace.pdf | ||
| Sol_140P6425B0004.pdf | ||
| Bid_Schedule_-_Fan_Coil_Replace.pdf | ||
| Attachment_-_Construction_Contract_Admin.pdf | ||
| Attachment_-_Drawings-Pictures.pdf | ||
| Attachment_-_Notice_to_Contractors.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEY NOTES:
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0
NOTES:
FCU3-1
FCU3-1
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-2
NOT USEDFCU3-3
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-4
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-5
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-6
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH VERTICAL CABINET FCU SHEET M2-0FCU3-7
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-8
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-9
REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-10
FCU3-11REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0
FCU3-12REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0
FCU3-2
FCU3-4
FCU3-5
FCU3-6
FCU3-7
FCU3-9
FCU3-8
FCU3-11
FCU3-12
FCU3-10
ELECTRICAL NOTES:
1.NO CHANGES TO EXISTING ELECTRICAL GEAR OR CIRCUITS TO BE EXPECTED.
REPLACEMENT OF FAN COIL UNITS IS LIKE FOR LIKE IN PLACE. THERE ARE NO EXPECTED
CHANGES TO ELECTRICAL LOAD.
2. ELECTRICAL CONTRACTOR TO DISCONNECT EACH RESPECTIVE FAN COIL UNIT AND PULL
BACK CONDUCTORS /CONDUIT TO AN ACCESSIBLE LOCATION TO RE-CONNECT WHEN
PLACING NEW FAN COIL UNITS.
1.AREAS OF SCOPE OF WORK ARE CLOUDED FOR REFERENCE. ONLY KEYNOTES IDENTIFIED
IN KEYNOTE SECTION BELOW ARE INCLUDED IN THIS SCOPE OF WORK. ALL OTHER
NOTATIONS ARE FROM ORIGINAL BUILDING CONSTRUCTION DOCUMENTS USED AS
BACKGROUND FOR THIS SCOPE OF WORK AND ARE NOT APPLICABLE.
2. TERM "ISOLATION VALVE" SHALL MEAN NEXUS COIL PACK INSTALLED UNDER PREVIOUS
CONTRACT. UNLESS NOTED OTHERWISE.
3. FOR EACH EXISTING FAN COIL UNIT WHICH HAS A LABEL FOR NEWLY SCHEDULED FAN COIL UNIT (FCU X-X), CLEANLY DISCONNECT FROM ISOLATION VALVE, REMOVE FROM THE FACILITY, AND LAWFULLY DISPOSE OF.
4. UPON REMOVAL OF EACH RESPECTIVE UNIT, THE CONTRACTOR SHALL PHOTO DOCUMENT
AND IDENTIFY TO THE CONTRACTING OFFICER REPRESENTATIVE ANY EXISTING DAMAGE TO
WALLS, FLOORS, OR ANY OTHER SURFACES MARRED, SCRATCHED, OR WORN BY THE
EXISTING UNIT, AND NOT CAUSED BY CONTRACTOR'S METHODS OF REMOVAL, PRIOR TO
INSTALLATION OF NEW FAN COIL UNIT. AVOID MIS-INTERPRETING EXISTING DAMAGE OR
WEAR AS CREATED BY CONTRACTOR OPERATIONS.
5. PROVIDE AND INSTALL IN ACCORDANCE WITH THESE CONTRACT DOCUMENT
SPECIFICATIONS, MANUFACTURER RECOMMENDATIONS AND ASTM INDUSTRY STANDARDS
NEW FAN COIL UNITS. CONNECT AND TEST UNIT'S PROPER FUNCTION TO EXISTING ISOLATION
VALVES.
NEW THERMOSTAT TO BE LOCATED WHERE DIRECTED BY COR. LOCATIONS SHOW ARE
APPROXIMATION. SEE SPECIFICATIONS FOR THE WIRELESS CONTROL THERMOSTAT UNITS.
NO DIRECT WIRE TO FAN COIL UNITS AND GREATER DISTURBANCE THAN SINGLE MOUNTING
POINT SHALL BE ALLOWED UNLESS APPROVED BY THE CO IN WRITING.
AutoCAD SHX Text
THIRD FLOOR FAN COIL UNIT REPLACEMENT
AutoCAD SHX Text
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text 01/31/25
AutoCAD SHX Text
ZR
AutoCAD SHX Text
ZR
AutoCAD SHX Text
TB
AutoCAD SHX Text
FIRST LADIES NATIONAL HISTORIC SITE
AutoCAD SHX Text M:\Groups\Maint\Archives\FILA\80024-FILA-Research Center Fan Coil Units\258437C Fan Coil Unit Replacement_FPI\FILA 258437C_CD SHEET SET.dwg 1/30/2025 5:03 PM BY Bentley, Thomas Lee 1/30/2025 5:03 PM BY Bentley, Thomas Lee1/30/2025 5:03 PM BY Bentley, Thomas Lee BY Bentley, Thomas LeeBentley, Thomas Lee
AutoCAD SHX Text Date
AutoCAD SHX Text Mark
AutoCAD SHX Text Sheet
AutoCAD SHX Text
REVISION
AutoCAD SHX Text Initial
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text 495 80026
AutoCAD SHX Text
AutoCAD SHX Text 258437C
AutoCAD SHX Text
THIRD FLOOR MECHANICAL PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1.3
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text
MEP 1.3
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
%%UF3-2
AutoCAD SHX Text
%%UF3-4
AutoCAD SHX Text F3-1 F3-2 F3-4
AutoCAD SHX Text T
AutoCAD SHX Text F3-6
AutoCAD SHX Text T
AutoCAD SHX Text F3-5
AutoCAD SHX Text T
AutoCAD SHX Text F3-7
AutoCAD SHX Text T
AutoCAD SHX Text F3-8
AutoCAD SHX Text T
AutoCAD SHX Text F3-9
AutoCAD SHX Text T
AutoCAD SHX Text F3-10 F3-11 F3-12 zrohloff Rectangle zrohloff Text Box
REMOVE EXISTING FAN COIL UNIT. NOT TO BE REPLACED.
zrohloff Cloud zrohloff Snapshot zrohloff Cloud zrohloff Text Box
MEP1.3
zrohloff Text Box
ADDENDUM #1
zrohloff Text Box zrohloff Text Box 05/12/2025 zrohloff Text Box
ZR
zrohloff Polygon Sketch to Scale
0.67 sf zrohloff Text Box zrohloff Text Box