Revised_Drawings_-_12_May_2025_0001.pdf

PDF 1 MB Posted

Attached to
Fan Coil Unit Replacement Federal contract opportunity
Solicitation number
140P6425B0004
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document is a mechanical drawing for a Fan Coil Unit Replacement project at the First Ladies National Historic Site in Canton, OH. The drawing depicts the third floor mechanical plan, showing the locations of multiple fan coil units (FCUs) to be removed and replaced. Key specifications include:

The project involves a like-for-like replacement of existing fan coil units, with no changes to electrical gear or circuits expected. Contractors must carefully disconnect and remove existing units, photo-document any pre-existing damage, and install new fan coil units connected to existing isolation valves. The new thermostats will be wireless and positioned as directed by the Contracting Officer Representative. The work is part of a solicitation (140P6425B0004) valued between $500,000 and $750,000, set aside 100% for small businesses, with anticipated work beginning in June 2025.

View the file

Other files for this federal contract opportunity

Other files attached to Fan Coil Unit Replacement, newest first.
File Type Posted
Site_Visit_Attendees_List_0001.pdf PDF
Sol_140P6425B0004_Amd_0001.pdf PDF
Questions_and_Answers_0001.pdf PDF
Wage_Determination_-_Stark_Co.pdf PDF
Attachment_-_Limitations_on_Subcontracting_Report.xlsx XLSX spreadsheet
Attachment_-_Submittal_List.pdf PDF
Bid_Schedule_-_Fan_Coil_Replace.xlsx XLSX spreadsheet
Specifications_-_Fan_Coil_Replace.pdf PDF
Sol_140P6425B0004.pdf PDF
Bid_Schedule_-_Fan_Coil_Replace.pdf PDF
Attachment_-_Construction_Contract_Admin.pdf PDF
Attachment_-_Drawings-Pictures.pdf PDF
Attachment_-_Notice_to_Contractors.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEY NOTES:

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0

NOTES:

FCU3-1

FCU3-1

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-2

NOT USEDFCU3-3

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-4

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-5

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-6

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH VERTICAL CABINET FCU SHEET M2-0FCU3-7

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-8

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-9

REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0FCU3-10

FCU3-11REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0

FCU3-12REMOVE EXISTING FAN COIL UNIT AND REPLACE WITH LOW VERTICAL CABINET FCU SHEET M2-0

FCU3-2

FCU3-4

FCU3-5

FCU3-6

FCU3-7

FCU3-9

FCU3-8

FCU3-11

FCU3-12

FCU3-10

ELECTRICAL NOTES:

1.NO CHANGES TO EXISTING ELECTRICAL GEAR OR CIRCUITS TO BE EXPECTED.

REPLACEMENT OF FAN COIL UNITS IS LIKE FOR LIKE IN PLACE. THERE ARE NO EXPECTED

CHANGES TO ELECTRICAL LOAD.

2. ELECTRICAL CONTRACTOR TO DISCONNECT EACH RESPECTIVE FAN COIL UNIT AND PULL

BACK CONDUCTORS /CONDUIT TO AN ACCESSIBLE LOCATION TO RE-CONNECT WHEN

PLACING NEW FAN COIL UNITS.

1.AREAS OF SCOPE OF WORK ARE CLOUDED FOR REFERENCE. ONLY KEYNOTES IDENTIFIED

IN KEYNOTE SECTION BELOW ARE INCLUDED IN THIS SCOPE OF WORK. ALL OTHER

NOTATIONS ARE FROM ORIGINAL BUILDING CONSTRUCTION DOCUMENTS USED AS

BACKGROUND FOR THIS SCOPE OF WORK AND ARE NOT APPLICABLE.

2. TERM "ISOLATION VALVE" SHALL MEAN NEXUS COIL PACK INSTALLED UNDER PREVIOUS

CONTRACT. UNLESS NOTED OTHERWISE.

3. FOR EACH EXISTING FAN COIL UNIT WHICH HAS A LABEL FOR NEWLY SCHEDULED FAN COIL UNIT (FCU X-X), CLEANLY DISCONNECT FROM ISOLATION VALVE, REMOVE FROM THE FACILITY, AND LAWFULLY DISPOSE OF.

4. UPON REMOVAL OF EACH RESPECTIVE UNIT, THE CONTRACTOR SHALL PHOTO DOCUMENT

AND IDENTIFY TO THE CONTRACTING OFFICER REPRESENTATIVE ANY EXISTING DAMAGE TO

WALLS, FLOORS, OR ANY OTHER SURFACES MARRED, SCRATCHED, OR WORN BY THE

EXISTING UNIT, AND NOT CAUSED BY CONTRACTOR'S METHODS OF REMOVAL, PRIOR TO

INSTALLATION OF NEW FAN COIL UNIT. AVOID MIS-INTERPRETING EXISTING DAMAGE OR

WEAR AS CREATED BY CONTRACTOR OPERATIONS.

5. PROVIDE AND INSTALL IN ACCORDANCE WITH THESE CONTRACT DOCUMENT

SPECIFICATIONS, MANUFACTURER RECOMMENDATIONS AND ASTM INDUSTRY STANDARDS

NEW FAN COIL UNITS. CONNECT AND TEST UNIT'S PROPER FUNCTION TO EXISTING ISOLATION

VALVES.

NEW THERMOSTAT TO BE LOCATED WHERE DIRECTED BY COR. LOCATIONS SHOW ARE

APPROXIMATION. SEE SPECIFICATIONS FOR THE WIRELESS CONTROL THERMOSTAT UNITS.

NO DIRECT WIRE TO FAN COIL UNITS AND GREATER DISTURBANCE THAN SINGLE MOUNTING

POINT SHALL BE ALLOWED UNLESS APPROVED BY THE CO IN WRITING.

AutoCAD SHX Text

THIRD FLOOR FAN COIL UNIT REPLACEMENT

AutoCAD SHX Text

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text 01/31/25

AutoCAD SHX Text

ZR

AutoCAD SHX Text

ZR

AutoCAD SHX Text

TB

AutoCAD SHX Text

FIRST LADIES NATIONAL HISTORIC SITE

AutoCAD SHX Text M:\Groups\Maint\Archives\FILA\80024-FILA-Research Center Fan Coil Units\258437C Fan Coil Unit Replacement_FPI\FILA 258437C_CD SHEET SET.dwg 1/30/2025 5:03 PM BY Bentley, Thomas Lee 1/30/2025 5:03 PM BY Bentley, Thomas Lee1/30/2025 5:03 PM BY Bentley, Thomas Lee BY Bentley, Thomas LeeBentley, Thomas Lee

AutoCAD SHX Text Date

AutoCAD SHX Text Mark

AutoCAD SHX Text Sheet

AutoCAD SHX Text

REVISION

AutoCAD SHX Text Initial

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text 495 80026

AutoCAD SHX Text

AutoCAD SHX Text 258437C

AutoCAD SHX Text

THIRD FLOOR MECHANICAL PLAN

AutoCAD SHX Text

AutoCAD SHX Text 1.3

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

MEP 1.3

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

%%UF3-2

AutoCAD SHX Text

%%UF3-4

AutoCAD SHX Text F3-1 F3-2 F3-4

AutoCAD SHX Text T

AutoCAD SHX Text F3-6

AutoCAD SHX Text T

AutoCAD SHX Text F3-5

AutoCAD SHX Text T

AutoCAD SHX Text F3-7

AutoCAD SHX Text T

AutoCAD SHX Text F3-8

AutoCAD SHX Text T

AutoCAD SHX Text F3-9

AutoCAD SHX Text T

AutoCAD SHX Text F3-10 F3-11 F3-12 zrohloff Rectangle zrohloff Text Box

REMOVE EXISTING FAN COIL UNIT. NOT TO BE REPLACED.

zrohloff Cloud zrohloff Snapshot zrohloff Cloud zrohloff Text Box

MEP1.3

zrohloff Text Box

ADDENDUM #1

zrohloff Text Box zrohloff Text Box 05/12/2025 zrohloff Text Box

ZR

zrohloff Polygon Sketch to Scale

0.67 sf zrohloff Text Box zrohloff Text Box