This is a Questions and Answers document (Amendment 1) for federal contract 140P5326R0016 regarding BISO Maintenance to Bandy Creek Water Tank. The document addresses six key inquiries from potential contractors regarding project specifications and logistics.
Surface preparation requirements clarify that interior surfaces must be cleaned and prepared to meet SSPC-SP10/NACE No. 2 standards with abrasive blasting as needed, while exterior surfaces are to be pressure washed and prepared for coating without abrasive blasting unless specifically required. Tank isolation will be accomplished using existing shutoff valves in both directions, with contractor coordination required with the Government. Water service continuity during rehabilitation is a Government responsibility; the park will determine and manage temporary water supply methods while the contractor coordinates work activities accordingly. The Government has identified the most recent tank inspection on record dated August 23, 2021, with additional documentation available upon request. The water tank was constructed in 1985, and the last known rehabilitation occurred circa 2006, with scope details being confirmed and to be provided if available.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
Amendment 1 - 140P5326R0016
BISO Maint to Bandy Creek Water Tank
Surface Preparation
Q1: Is the intent to sandblast both the interior and exterior of the water tank, or is it to only pressure wash the exterior and sand blast the interior?
A1: Interior surfaces shall be cleaned and prepared in accordance with specified standards, including abrasive blasting as required to meet SSPC-SP10 / NACE No. 2. Exterior surfaces are intended to be pressure washed and prepared for coating; abrasive blasting of exterior surfaces is not anticipated unless specifically required to achieve proper surface preparation.
Tank Isolation
Q2: How would the tank need to be isolated? Is there a valve to cut water flow off to the tank?
A2: The tank can be isolated using existing shutoff valves in both directions. The contractor shall coordinate isolation activities with the Government.
Maintaining Water Service
Q3: How would the park maintain water during the tank rehabilitation? Would the contractor or owner be responsible for this?
A3: Continuity of water service will be a Government responsibility. The contractor shall coordinate work activities accordingly, but temporary water supply methods will be determined and managed by the park.
Inspection Reports
Q4: Are there any past inspection reports for this tank?
A4: The most recent inspection on record is dated August 23, 2021. Additional documentation can be provided upon request.
Tank Construction Date
Q5: When was the tank built?
A5: The tank was constructed in 1985.
Last Rehabilitation
Q6: When was the last rehabilitation performed on the tank and what did it consist of?
A6: The last known rehabilitation occurred circa 2006. The scope of that effort is being confirmed, and additional details will be provided if available.