Big_South_Fork_NRRA_TN_-_Bandy_Creek_Inspection_Report_2026_0003.pdf

PDF 5 MB Posted

Attached to
BISO MAINT TO BANDY CREEK WATER TANK
Solicitation number
140P5326R0016
Issued by

About this file

This is a Tank Inspection Report prepared by Southeastern Tank, Inc. for the Bandy Creek water storage facility operated by Big South Fork NRRA TN in Oneida, Tennessee.

The inspection was conducted on May 13, 2026, by Inspector Maxwell Plank on a 75,000-gallon welded ground-level steel tank (Serial Number 9770) measuring 23.6 feet in diameter and 25 feet in height. The exterior assessment identified good overall condition for the roof, roof vent, and roof manway, though the panel coating was rated fair with significant mildew growth and faded, chalking paint on the sidewalls. A recently welded patch was noted on the exterior sidewall. The tank shell exhibited good vertical and horizontal welds with good sidewall panels, but the overall condition was rated fair due to missing coating and minor corrosion. The concrete foundation curb is in good condition with no erosion, cracking, or settlement. The exterior ladder/cage assembly is in good condition with no damage or corrosion, the level indicator is operational with readable marks, and the grounds and perimeter include a gated, locked fence in good condition.

Interior inspection revealed fair condition overall with good welded seams but fair panel condition, missing coating, and minor corrosion on the tank shell and floor. The interior roof exhibited moderate corrosion on structural support beams with fair panel and welded seam conditions. The fixed steel inside ladder is in fair condition with safety climb installed. The floor contains less than one inch of silt with corrosion spots partially blocked by sediment at the critical floor-to-wall joint. The tank is equipped with cathodic protection using five magnesium anode blocks. Water temperatures ranged from 64.6°F to 65.8°F. Piping components including overflow (4-inch ductile iron with screen and flapper), inlet (4-inch), and outlet (6-inch) are in fair condition with a silt stop present. Maintenance recommendations include exterior pressure washing and repainting, inspecting and coating the exterior patch, removing floor silt, inspecting floor-to-wall joints with ultrasonic thickness testing, remediating interior patch corrosion, servicing cathodic protection anodes, and repairing roof structural supports. Evidence of vandalism (graffiti) was documented near the overflow piping.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T A N K I N S P E C T I O N R E P O R T

BANDY CREEK

Prepared for Big South Fork NRRA TN

CLIENT Big South Fork NRRA TN

ASSET Bandy Creek

LOCATION Oneida, Tennessee 37841

TANK TYPE Welded Ground Level Steel Tank

DATE OF

INSPECTION

May 13, 2026

INSPECTOR Maxwell Plank

PREPARED BY SOUTHEASTERN TANK, INC.

Prepared Exclusively for Big South Fork NRRA TN

INSPECTION DETAILS

GENERAL INFORMATION

Date Inspected: 2026-05-13

Tank Identifier: Distribution

Type: Ground Storage Welded Steel

Tank S/N: 9770

Diameter (ft): 23.6

Height (ft): 25

Capacity (gal): 75000

Weather: Light Rain , 82°F , 51% humidity , wind 7 mph SW

Tank Overview Photos

Tank Overview

Tank Overview

TANK ID PLATE & SAFETY PLACARDS

Tank ID Plate

Installed: Yes

Readable: Yes

Tank ID Plate Photos

Tank ID Plate

Safety Placards

Installed: Yes

Readable: Yes

Safety Placards Photos

Safety Placards

TANK EXTERIOR

Roof (Welded Steel)

Panels: Good

Panel Coating: Fair

Welded Seams: Good

Overall Condition: Good

Roof Photos

Roof Roof

Roof Roof

Roof Vent

Screen Installed: Yes

Overall Condition: Good

Roof Vent Photos

Roof Vent Roof Vent

Roof Manway

Overall Condition: Good

Pad Lock Installed: Yes

Roof Manway Photos

Roof Manway Roof Manway

Roof Manway

SIDEWALL & ACCESSORIES

Tank Shell

Vertical Welds: Good

Horizontal Welds: Good

Sidewall Panels: Good

Coating Missing: Yes

Overall Condition: Fair

Tank Shell Photos

Tank Shell Tank Shell

Tank Shell Tank Shell

Tank Shell

Sidewall Manway

Size (inches): 24

Quantity: 2

Neck Weldment: Good

Gasket Condition: Good

Corrosion Present: Yes

Overall Condition: Fair

Sidewall Manway Photos

Sidewall Manway Sidewall Manway

Sidewall Manway Sidewall Manway

Tank Foundation

Concrete Curb: Good

Erosion, Cracking or Settlement:

No

Anchor Bolts Present: N/A

Foundation Photos

Foundation Foundation

Foundation Foundation

Foundation

Exterior Ladder / Cage Assembly

Any Damage: No

Corrosion Present: No

Ladder Gate Installed:

Yes

Padlock Installed: Yes

Overall Condition: Good

Exterior Ladder / Cage Photos

Exterior Ladder / Cage

Exterior Ladder / Cage

Exterior Ladder / Cage Exterior Ladder / Cage

Level Indicator

Level Marks Readable:

Yes

Cable & Pulley Assembly:

Good

Float Assembly: Good

Operational: Yes

Level Indicator Photos

Level Indicator Level Indicator

Level Indicator Level Indicator

Level Indicator

Exterior Summary / Notes

1. There is significant mildew growth on the tank sidewall.

2. The paint is faded and chalking.

3. A patch was recently welded onto the tank sidewall near the bottom.

TANK INTERIOR

Tank Shell

Vertical Welds: Good

Horizontal Welds: Good

Panel Condition: Fair

Coating Missing: Yes

Corrosion Present: Yes

If Corrosion Present, Degree:

Minor

Overall Condition: Fair

Interior Shell Photos

Interior Shell Interior Shell

Interior Shell

Roof

Panels: Fair

Panel Coating: Poor

Support Beams: Fair

Support Beams Coating:

Poor

Welded Seams: Fair

Coating Missing: Yes

Corrosion Present: Yes

If Corrosion Present, Degree:

Moderate

Overall Condition: Fair

Interior Roof Photos

Interior Roof Interior Roof

Inside Ladder

Type: Fixed Steel

Quantity: 1

Overall Condition: Fair

Safety Climb Installed:

Yes

Inside Ladder Photos

Inside Ladder

Inside Ladder

Inside Ladder Inside Ladder

Welded Steel Floor Condition

Silt: Present

Welded Seams: Good

Floor Panels: Fair

Coating Missing: Yes

Corrosion Present: Yes

If Corrosion Present, Degree:

Minor

Overall Condition: Fair

Floor Photos

Floor Floor

Floor Floor

Floor Floor

Water Temperature (°F)

Surface: 65.8°F

10 ft: 65.4°F

20 ft: 64.6°F

Interior Summary / Notes

1. The floor has less than 1" of silt on the floor.

2. The area where the floor meets the sidewall has some corroded spots that are partially blocked by silt preventing a clear view for examination of the corrosion.

3. The patch plate that was welded to the exterior of the tank's sidewall has created corrosion on the interior side.

4. The tank is equipped with cathodic protection around 10' off the floor in the form of 5 blocks of metal. (most likely magnesium)

5. The underside of the roof has moderate corrosion to its structural support beams.

PIPING

Overflow

Location: Exterior

Pipe Size (inches): 4

Pipe Type: Ductile Iron

Screen Installed: Yes

Flapper Installed: Yes

Pipe Brackets: Good

Overall Condition: Fair

Overflow Piping Photos

Overflow Piping Overflow Piping

Overflow Piping Overflow Piping

Overflow Piping Overflow Piping

Inlet / Outlet

Inlet Type: Ductile Iron

Inlet Size (inches): 4

Outlet Type: Ductile Iron

Outlet Size (inches): 6

Silt Stop: Present

Inlet / Outlet Photos

Inlet / Outlet Inlet / Outlet

Inlet / Outlet Inlet / Outlet

Inlet / Outlet

Drain

Drain Type: Ductile Iron

Drain Condition: N/A

Drain Photos

Drain

GROUNDS

Grounds & Perimeter

Fence: Good

Gate: Good

Lock: Present

Grounds & Perimeter Photos

Grounds & Perimeter Grounds & Perimeter

Vandalism

Evidence of Vandalism or Trespassing:

Yes

Details: Graffiti by Overflow

Vandalism / Damage Photos

Vandalism / Damage

RECOMMENDED MAINTENANCE

Detailed Maintenance Recommendations

Exterior Work

Pressure wash/Soft wash exterior sidewalls: to remove mildew growth to prevent surface degradation.

Repaint exterior surfaces: to address chalking and restore UV protection.

Inspect and coat exterior patch: to verify weld integrity of the new patch and apply a protective coating to prevent rust.

Interior Work

Remove floor silt: Clean out the silt to allow for a comprehensive inspection of the floor and joints.

Inspect floor-to-wall joint: Once silt is removed, perform a detailed visual and ultrasonic thickness (UT) inspection of the corroded spots at the critical joint.

Remediate interior patch corrosion: Clean, blast, and apply an internal coating to the interior side of the patch plate to arrest localized corrosion.

Service cathodic protection: Inspect the five magnesium anode blocks for depletion and replace them if they are no longer providing adequate protection.

Repair roof structural supports: Abrasive blast and recoat the underside structural beams to halt corrosion and maintain structural integrity.

ROV Sterilization Method – Southeastern Tank Inc.

Prior to all tank inspections, the ROV is spray disinfected with a 200ppm chlorine solution per AWWA C652, 4.3.2 Chlorination Method 2, prior to tank entry. Chlorine dosage was per C652, Table 8.2.

All inspections are in accordance with the Tennessee Division of Water Supply Rule 0400-45-01-.17(33) and American Water Works Association standards for inspections of potable water storage facilities.

Chris Dowdy Project Manager Southeastern Tank

Storage Tank Inspection Worksheet

System/PWSID: Date: Inspector:

Tank General Information

Tank Name /Location: Storage Capacity: Year Built:

Tank Type: Ground Level (Standpipe) Elevated Other:

Availability: Emergency Interim Permanent Seasonal Other:

Professional Tank Inspection Records/Maintenance Records Last professional tank inspection or in service date: Tank inspection conducted by:

Type of inspection activity: Draining (100%) Diver Robotic Camera Disinfection per AWWA Standard Method: ONE TWO THREE NONE Disinfection Info Present: YES NO Bacteriological sample(s) results: YES NO Are lead paint analyses applicable: YES NO Exterior paint results: Interior paint results:

Noteworthy Deficiencies / Recommendations:

Maintenance activity in or around tank since last survey:

On-site Tank Inspection (Exterior, Grounds, Security)

Condition of Tank, Foundation(s), and Appurtances Comments Overall Condition of Tank: *G / Need Att Overflow drain piped to ground: YES NO -Screened (24 mesh): YES NO -Protected: YES NO Flap Gate Red Valve Other Paint Condition: *G / Need Att Rust Present: YES NO Telemetry/ Float Gauge Operational YES NO Leaks Present: YES NO Locations:

Foundation Condition *G / Need Att Evidence of Vandalism: YES NO Ladder / Stairs Secure: YES NO -Removed to 8 Feet YES NO -Anti-Climb Device: YES NO Condition of Grounds / Altitude Valve Pit / Other Perimeter: (Circle all that apply) Gated Fenced Locked Grounds Mowed: YES NO -Trees or Debris near tank: YES NO Altitude Valve Pit: YES NO Condition:

-Secure: YES NO -Drained: YES NO -Leaks Present: YES NO Booster Station: YES NO On-site Off-site:

-Secure: YES NO -Duplicate Pumps: YES NO -Condition: *G / Need Att

*Notes: G (Good), Need Att (Needs Attention) Additional Comments:

Latitude: Longitude:

(Revised: January 2010)