This is a Fire Alarm Signaling System Inspection Report for Valley Forge National Historical Park's Administration Building located at 1400 North Outer Line Drive in King of Prussia, Pennsylvania (Zip: 19406). The system is a remote station fire alarm monitored off-site by Mega Center (215-521-2189) using a DACT-Radionics monitoring system with System ID: Main FACP. The facility is equipped with a Radionics D7212 addressable control unit using Class B circuit style with sealed lead-acid battery backup rated at 13.6V/6.25Ah.

The inspection identified multiple deficiencies requiring corrective action: a smoke detector on the 2nd floor at the top of stairs failed to trigger; five heat detectors in the attic are beyond their service life; one heat detector in the basement failed to report to the FACP; and one wheelock bell is non-functional. Of 12 smoke detectors tested, one failed; of eight heat detectors tested, six showed deficiencies. The Device Test Log documents individual testing results across multiple locations, including heat detectors in attics and the basement, smoke detectors throughout the facility, and duct detectors. Most devices passed functional testing, though several heat detectors were noted as visually inspected but likely outside their service life. Battery systems, charger tests, load voltage, discharge tests, and all control unit components passed inspection according to NFPA standards.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Slide 1

Slide 2
Slide 3

File details come from the government source that posted it. Updated .