This document contains specifications for gypsum board installation for the GOGA 212511D Repair West Wing of Fort Mason Building 201 project. The specifications cover gypsum board products and materials, including types of wallboard, backing materials, trim accessories, and joint compounds. It provides instructions for substrate preparation, installation methods, finishing, and protection. Products are to meet or exceed standards for fire resistance, STC ratings, mold resistance, and impact resistance. The related federal contract opportunity is for seismic strengthening repairs to the West Wing of Building 201 at Fort Mason in the Golden Gate National Recreation Area for the Department of the Interior National Park Service National Office.

View the file

Other files

File Type Posted
B09_Wage_Determination_SF_1_19_23_0010.pdf PDF
Sol_140P2022R0072_Amd_0010.pdf PDF
B09_Wage_Determination_Updated_11_4_22_0009.txt TXT text file
AS-CONST_GOGA_Ft_Mason_Bldg_201_Elect_Rehab_0009.pdf PDF
B09_Amd_9_Schedule_of_Changes_Q_A_0009.pdf PDF
Sol_140P2022R0072_Amd_0009.pdf PDF
B09_Amd_8_Schedule_of_Changes_Q_A_Respones_0008.pdf PDF
Sol_140P2022R0072_Amd_0008.pdf PDF
Sol_140P2022R0072_Amd_0007.pdf PDF
B09_Amd_7_Schedule_of_Changes_Q_A_0007.pdf PDF
GOGA_212511D_Virtual_Project_Overview-20221014_100154-Meeting_Recording_0006.mp4 MP4 file
Sol_140P2022R0072_Amd_0006.pdf PDF
Image_0006.jpeg JPEG file
Sol_140P2022R0072_Amd_0005.pdf PDF
14_October_MS_Teams_Invite_0005.pdf PDF
140P2022R0072_Virtual_Project_Review_Presentation_0004.pptx PPTX presentation
Sol_140P2022R0072_Amd_0004.pdf PDF
01_27_00_DEFINITION_OF_CONTRACT_LINE_ITEMS_ADDEN3_0003.pdf PDF
01_33_23a_SubmittalList-ReviewEstimate_rev_0003.xlsx XLSX spreadsheet
Sol_140P2022R0072_Amd_0003.pdf PDF
03_31_00_CAST-IN-PLACE_CONCRETE_ADDEN3_0003.pdf PDF
_22_0922_GOGA_FM201_West_FINAL_CD_combined_rev2_0003.pdf PDF
B09_Amd_2_Schedule_of_Changes_Q_A_0002.pdf PDF
Sol_140P2022R0072_Amd_0002.pdf PDF
IMG_7944_0001.JPG JPG image
DSCN0951_0001.JPG JPG image
IMG_7798_0001.JPG JPG image
IMG_7945_0001.JPG JPG image
IMG_7801_0001.JPG JPG image
DSCN0622_0001.JPG JPG image
DSCN0903_0001.JPG JPG image
DSCN0914_0001.JPG JPG image
IMG_7950_0001.JPG JPG image
DSCN0952_0001.JPG JPG image
DSCN0895_0001.JPG JPG image
IMG_7803_0001.JPG JPG image
DSCN1048_0001.JPG JPG image
IMG_7739_0001.JPG JPG image
DSCN0944_0001.JPG JPG image
IMG_7937_0001.JPG JPG image
DSCN0611_0001.JPG JPG image
IMG_7746_0001.JPG JPG image
IMG_7768_0001.JPG JPG image
IMG_7938_0001.JPG JPG image
DSCN0915_0001.JPG JPG image
DSCN1053_0001.JPG JPG image
DSCN0919_0001.JPG JPG image
DSCN0938_0001.JPG JPG image
DSCN0912_0001.JPG JPG image
B201_BASEMENT_0001.zip ZIP file
Show 40 more

Latest 50 of 195 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GOGA – 212511D 09 29 00 -1 GYPSUM BOARD

SECTION 092900 - GYPSUM BOARD

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplement Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Interior gypsum board.

2. Sound attenuation Insulation.

B. Related Requirements:

1. Section 092216 "Non-Structural Metal Framing" for non-structural steel framing and suspension systems that support gypsum board panels.

1.3 SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: For casing beads, moldings, panel transitions and closure profiles.

1. Include elevations showing typical and unique conditions, openings, reveals, panel edges, control and expansion joints and transitions.

2. Show details of special conditions and Project specific details.

3. Show details of wall closures and terminations, including acoustical wall closures.

1.4 DELIVERY, STORAGE AND HANDLING

A. Store materials inside under cover and keep them dry and protected against weather, condensation, direct sunlight, construction traffic, and other potential causes of damage. Stack panels flat and supported on risers on a flat platform to prevent sagging.

1.5 FIELD CONDITIONS

A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.

GOGA – 212511D 09 29 00 -2 GYPSUM BOARD

B. Do not install paper-faced gypsum panels until installation areas are enclosed and conditioned.

C. Do not install panels that are wet, moisture damaged, and mold damaged.

1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape.

2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Fire-Resistance-Rated Assemblies: For fire-resistance-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119 by an independent testing agency.

B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 90 and classified according to ASTM E 413 by an independent testing agency.

C. Lightweight gypsum panels are not allowed.

2.2 GYPSUM BOARD, GENERAL

A. Size: Provide maximum lengths and widths available that will minimize joints in each area and that correspond with support system indicated.

2.3 INTERIOR GYPSUM BOARD

A. Gypsum Wallboard: ASTM C 1396/C 1396M.

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. American Gypsum; www.americangypsum.com.

2. CertainTeed, div. of Saint-Gobain; www.certainteed.com.

3. Georgia-Pacific Gypsum LLC; www.buildgp.com.

4. National Gypsum Properties, LLC; www.nationalgypsum.com.

5. PABCO Gypsum, div. of PABCO Building Products, LLC; www.pabcogypsum.com.

6. Temple-Inland; www.templeinland.com.

GOGA – 212511D 09 29 00 -3 GYPSUM BOARD

7. USG Corp.; www.usg.com.

C. Gypsum Board, Type X: ASTM C 1396/C 1396M.

1. Thickness: 5/8 inch (15.9 mm).

2. Long Edges: Tapered.

D. Gypsum Ceiling Board: ASTM C 1396/C 1396M.

1. Thickness: 1/2 inch (12.7 mm).

2. Long Edges: Tapered.

E. Impact-Resistant Gypsum Board: ASTM C 1396/C 1396M gypsum board, tested according to

ASTM C 1629/C 1629M.

1. Core: 5/8 inch (15.9 mm), Type X.

2. Surface Abrasion: ASTM C 1629/C 1629M, meets or exceeds Level 2 requirements.

3. Indentation: ASTM C 1629/C 1629M, meets or exceeds Level 2requirements.

4. Soft-Body Impact: ASTM C 1629/C 1629M, meets or exceeds Level 2requirements.

5. Long Edges: Tapered.

6. Mold Resistance: ASTM D 3273, score of 10 as rated according to ASTM D 3274.

7. Basis-of-Design Product: DensArmor Plus, Georgia-Pacific.

F. Type C gypsum board has fire-resistive capability greater than that of Type X. Design designations of independent testing agencies indicated on Drawings generally determine product requirements for Type C gypsum board. Type C gypsum board from different manufacturers cannot be intermixed because the ratings apply only to assemblies identical in materials and construction to those tested.

G. Water-Resistant Gypsum Backing Board: ASTM C 1396/C 1396M, with manufacturer's standard edges.

1. Core: As indicated on Drawings.

2.4 TRIM ACCESSORIES

A. Interior Trim: ASTM C 1047.

1. Material: Galvanized or aluminum-coated steel sheet or rolled zinc

GOGA – 212511D 09 29 00 -4 GYPSUM BOARD

2. Shapes:

a. Cornerbead.

b. L-Bead: L-shaped; exposed long flange receives joint compound.

c. Expansion (control) joint.

B. Aluminum Trim, Interior and Exterior: Extruded accessories for aesthetic and functional uses.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Basis-of-Design Manufacturer: Fry Reglet Corp.; www.fryreglet.com.

b. Other Approved:

1) Clark-Dietrich Building Systems LLC; www.clarkdietrich.com.

2) Flannery, Inc; www.flannerytrim.com.

3) Gordon, Inc; www.gordon-inc.com.

4) Pittcon Industries; www.pittconindustries.com.

5) Tamlyn; www.tamlyn.com.

2. Aluminum: Alloy and temper with not less than the strength and durability properties of ASTM B221, Alloy 6063-T5.

3. Finish: Corrosion-resistant primer compatible with joint compound and finish materials specified.

4. Profiles: Provide trim of profiles indicated.

2.5 JOINT TREATMENT MATERIALS

A. General: Comply with ASTM C 475/C 475M.

B. Joint Tape:

1. Interior Gypsum Board: Paper.

2. Exterior Gypsum Soffit Board: Paper.

3. Glass-Mat Gypsum Sheathing Board: 10-by-10 glass mesh.

GOGA – 212511D 09 29 00 -5 GYPSUM BOARD

4. Tile Backing Panels: As recommended by panel manufacturer.

C. Joint Compound for Interior Gypsum Board: For each coat, use formulation that is compatible with other compounds applied on previous or for successive coats.

1. Prefilling: At open joints, rounded or beveled panel edges, and damaged surface areas, use setting-type taping compound.

2. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim flanges, use drying-type, all-purpose compound.

a. Use setting-type compound for installing paper-faced metal trim accessories.

3. Fill Coat: For second coat, use drying-type, all-purpose compound.

4. Finish Coat: For third coat, use drying-type, all-purpose compound.

5. Skim Coat: For final coat of Level 5 finish, use drying-type, all-purpose compound.

2.6 AUXILIARY MATERIALS

A. General: Provide auxiliary materials that comply with referenced installation standards and manufacturer's written instructions.

B. Steel Drill Screws: ASTM C 1002 unless otherwise indicated.

1. Use screws complying with ASTM C 954 for fastening panels to steel members from

0.033 to 0.112 inch (0.84 to 2.84 mm) thick.

2. For fastening cementitious backer units, use screws of type and size recommended by panel manufacturer.

C. Sound-Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing) produced by combining thermosetting resins with mineral fibers manufactured from glass, slag wool, or rock wool.

1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of assembly.

D. Acoustical Sealant: Manufacturer's standard nonsag, paintable, nonstaining latex sealant complying with ASTM C 834. Product effectively reduces airborne sound transmission through perimeter joints and openings in building construction as demonstrated by testing representative assemblies according to ASTM E 90.

E. Thermal Insulation: As specified in Section 072100 "Thermal Insulation."

F. Vapor Retarder: As specified in Section 072600 "Vapor Retarders."

GOGA – 212511D 09 29 00 -6 GYPSUM BOARD

G. Sound-Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing) produced by combining thermosetting resins with mineral fibers manufactured from glass, slag wool, or rock wool.

1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of assembly.

2. Basis-of-Design Product: Safe’n’Sound by Rockwool; www.rockwool.com.

a. Thickness: As required to fill stud cavity in friction-fit application.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and substrates including welded hollow-metal frames and support framing, with Installer present, for compliance with requirements and other conditions affecting performance of the Work.

B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold damaged.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 APPLYING AND FINISHING PANELS, GENERAL

A. Comply with ASTM C 840.

B. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels not less than one framing member.

C. Install panels with face side out. Butt panels together for a light contact at edges and ends with not more than 1/16 inch (1.5 mm) of open space between panels. Do not force into place.

D. Locate edge and end joints over supports, except in ceiling applications where intermediate supports or gypsum board back-blocking is provided behind end joints. Do not place tapered edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other than control joints at corners of framed openings.

E. Form control and expansion joints with space between edges of adjoining gypsum panels.

F. Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings, etc.), except in chases braced internally.

GOGA – 212511D 09 29 00 -7 GYPSUM BOARD

1. Unless concealed application is indicated or required for sound, fire, air, or smoke ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. (0.7 sq. m) in area.

2. Fit gypsum panels around ducts, pipes, and conduits.

3. Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4- to 3/8-inch- (6.4- to 9.5-mm-) wide joints to install sealant.

G. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments. Provide 1/4- to 1/2-inch- (6.4- to 12.7-mm-) wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant.

H. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first.

I. Wood Framing: Install gypsum panels over wood framing, with floating internal corner construction. Do not attach gypsum panels across the flat grain of wide-dimension lumber, including floor joists and headers. Float gypsum panels over these members or provide control joints to counteract wood shrinkage.

J. STC-Rated Assemblies: Seal construction at perimeters, behind control joints, and at openings and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both faces of partitions at perimeters and through penetrations. Comply with ASTM C 919 and with manufacturer's written instructions for locating edge trim and closing off sound-flanking paths around or through assemblies, including sealing partitions above acoustical ceilings.

K. Install sound attenuation blankets before installing gypsum panels unless blankets are readily installed after panels have been installed on one side.

3.3 APPLYING INTERIOR GYPSUM BOARD

A. Install interior gypsum board in the following locations:

1. Wallboard Type: As indicated on Drawings

2. Type X: As indicated on Drawings

3. Ceiling Type: Ceiling surfaces

4. Abuse-Resistant Type: In Gymnasium

5. Impact-Resistant Type: As indicated on drawings.

GOGA – 212511D 09 29 00 -8 GYPSUM BOARD

6. Mold-Resistant Type: Minimum 3’ in all directions centered on plumbing fixtures.

Required both sides of walls containing fixtures.

7. Glass-Mat Interior Type: As indicated on Drawings.

B. Single-Layer Application:

1. On ceilings, apply gypsum panels before wall/partition board application to greatest extent possible and at right angles to framing unless otherwise indicated.

2. On partitions/walls, apply gypsum panels horizontally (perpendicular to framing) unless otherwise indicated or required by fire-resistance-rated assembly, and minimize end joints.

a. Stagger abutting end joints not less than one framing member in alternate courses of panels.

b. At stairwells and other high walls, install panels horizontally unless otherwise indicated or required by fire-resistance-rated assembly.

3. On Z-shaped furring members, apply gypsum panels vertically (parallel to framing) with no end joints. Locate edge joints over furring members.

4. Fastening Methods: Apply gypsum panels to supports with steel drill screws.

C. Multilayer Application:

1. On ceilings, apply gypsum board indicated for base layers before applying base layers on walls/partitions; apply face layers in same sequence. Apply base layers at right angles to framing members and offset face-layer joints one framing member, 16 inches (400 mm) minimum, from parallel base-layer joints, unless otherwise indicated or required by fire-resistance-rated assembly.

2. On partitions/walls, apply gypsum board indicated for base layers and face layers vertically (parallel to framing) with joints of base layers located over stud or furring member and face-layer joints offset at least one stud or furring member with base-layer joints unless otherwise indicated or required by fire-resistance-rated assembly. Stagger joints on opposite sides of partitions.

3. On Z-shaped furring members, apply base layer vertically (parallel to framing) and face layer either vertically (parallel to framing) or horizontally (perpendicular to framing) with vertical joints offset at least one furring member. Locate edge joints of base layer over furring members.

4. Fastening Methods: Fasten base layers with screws; fasten face layers with adhesive and supplementary fasteners

GOGA – 212511D 09 29 00 -9 GYPSUM BOARD

3.4 INSTALLING TRIM ACCESSORIES

A. General: For trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions.

B. Control Joints: Install control joints according to ASTM C 840 and in specific locations approved by Architect for visual effect.

C. Interior Trim: Install in the following locations:

1. Cornerbead: Use at outside corners

2. L-Bead: Use where indicated or recommended by manufacturer.

3. J-trim: Use at exposed edges of boards and where boards abut caulked joints with dissimilar materials.

3.5 FINISHING GYPSUM BOARD

A. General: Treat gypsum board joints, interior angles, edge trim, control joints, penetrations, fastener heads, surface defects, and elsewhere as required to prepare gypsum board surfaces for decoration. Promptly remove residual joint compound from adjacent surfaces.

B. Apply joint tape over gypsum board joints, except for trim products specifically indicated as not intended to receive tape.

C. Gypsum Board Finish Levels: Finish panels to levels indicated below and according to

ASTM C 840:

1. Level 1: Ceiling plenum areas, concealed areas, and where indicated.

2. Level 2: Panels that are substrate for tile

a. Primer and its application to surfaces are specified in Section 099123 "Interior Painting."

3. Level 3: Mechanical, electrical rooms, custodial closets, and storage rooms

4. Level 4: Classrooms

5. Level 5: Corridors, gymnasiums, cafeteria/Commons, offices, high traffic/public areas.

D. Glass-Mat Gypsum Sheathing Board: Finish according to manufacturer's written instructions for use as exposed soffit board.

E. Cementitious Backer Units: Finish according to manufacturer's written instructions.

GOGA – 212511D 09 29 00 -10 GYPSUM BOARD

F. Clean gypsum board of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants.

3.6 PROTECTION

A. Protect adjacent surfaces from drywall compound and promptly remove from floors and other non-drywall surfaces. Repair surfaces stained, marred, or otherwise damaged during drywall application.

B. Protect installed products from damage from weather, condensation, direct sunlight, construction, and other causes during remainder of the construction period.

C. Provide Vapor retarder (minimum: 4 mil) behind gypsum board on all shower walls, behind slop sinks, in dishwash rooms, and exterior walls of walk-in coolers

D. Remove and replace panels that are wet, moisture damaged, and mold damaged.

1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape.

2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.

END OF SECTION