This document outlines a federal solicitation for rehabilitation services at the Hurricane Ridge Day Lodge. The project requires renovations to electrical, plumbing and fire systems, elevator modernization, roof replacement, window and door replacements, accessibility improvements, and HVAC system upgrades. The work will bring the lodge into compliance with current codes and resolve structural issues. Proposals are due by July 18, 2022 to the National Park Service. Evaluation criteria focus on management approach, technical approach, key personnel, project experience and past performance. The contract is to be awarded based on best value and will have a performance period from notice to proceed through 600 calendar days after, with liquidated damages of $1,482 per day for delays.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140P2022R0068 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

PDS

Denver CO 80225-0287 P.O. Box 25287 12795 W. Alameda Pkwy DOI, NPS, DSC Contracting Services

PDS

Denver CO 80225-0287 P.O. Box 25287 12795 W. Alameda Pkwy NPS, DSC Contracting Services Div

07/01/20220001

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

06/17/2022

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

The purpose of Amendment 0001 is to:

1) Incorporate the Specifications Appendices. Refer to the attached "B09_Amd Specs

Apendecies.pdf" document for complete details.

2) Incorporate the Updated Specifications Table of Contents, Section 14 24 00 - "Hydraulic

Elevator Modernization," and Updated Drawings. Refer to the attached "B09_Amd 1

Continuation Sheet.pdf" document for complete details.

3) Provide the Pre-Proposal Site Visit Sign-In Sheet and Informational Tri-Fold Hand-Out.

Refer to the attached "B09_Amd 1 Continuation Sheet.pdf" document for complete details.

Continued ...

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Amber Hughes

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

2 28

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

140P2022R0068/0001

All other terms and conditions remain unchanged by this Amendment 0001.

*Solicitation 140P2022R0068 - Issued 6/17/2022.

*Amendment 0001 - Issued 7/1/2022.

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

OLYM - 184745 TOC-1

TABLE OF CONTENTS

DIVISION 00

00 01 07 SEALS PAGE

DIVISION 01 - GENERAL REQUIREMENTS

01 11 00 SUMMARY OF WORK

01 26 01 CONTRACT MODIFICATION PROCEDURES

01 27 00 DEFINITION OF CONTRACT LINE ITEMS

01 31 00 PROJECT MANAGEMENT & COORDINATION

01 32 16 CONSTRUCTION SCHEDULE

01 32 33 PHOTOGRAPHIC DOCUMENTATION

01 33 23 SUBMITTAL PROCEDURES

• SUBMITTAL LIST

01 35 13.22 ARCHEOLOGICAL PROTECTION

01 35 23 SAFETY REQUIREMENTS

01 40 00 QUALITY REQUIREMENTS

01 42 00 REFERENCE STANDARDS

01 50 00 TEMPORARY FACILITIES AND CONTROLS

01 57 19.11 INDOOR AIR QUALITY MANAGEMENT

01 57 19.12 NOISE & ACOUSTICS MANAGEMENT

01 57 23 UNDER AN ACRE STORM WATER POLLUTION PREVENTION

01 67 00 PRODUCT REQUIREMENTS

01 73 29 CUTTING AND PATCHING

01 73 40 EXECUTION

01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

• WASTE MANAGEMENT PLAN WORKSHEET

01 77 00 CLOSEOUT PROCEDURES

01 78 23 OPERATION AND MAINTENANCE DATA

• O&M SPREADSHEET

01 79 00 DEMONSTRATION AND TRAINING

01 81 13 SUSTAINABLE DESIGN REQUIREMENTS FOR NON-LEED PROJECTS

01 91 13 GENERAL COMMISSIONING REQUIREMENTS

DIVISION 02 – EXISTING CONDITIONS

02 41 13 SELECTIVE SITE DEMOLITION

02 41 19 SELECTIVE DEMOLITION

OLYM - 184745 TOC-2

02 81 01 OFFSITE TRANSPORTATION AND DISPOSAL

02 82 13 ASBESTOS ABATEMENT

02 83 13 REMOVAL AND DISPOSAL OF MATERIAL CONTAINING LEAD

02 84 16 HANDLING OF LIGHT BALLAST, LAMPS AND MERCURY

02 85 00 MOLD REMEDIATION

DIVISION 03 – CONCRETE

03 01 30 MAINTENANCE OF CAST-IN-PLACE CONCRETE

03 31 00 CAST-IN-PLACE CONCRETE

DIVISION 04 – MASONRY

04 01 40 STONE REPAIR

DIVISION 05 – METALS

05 10 00 STRUCTURAL STEEL FRAMING

05 52 13 PIPE AND TUBE RAILINGS

DIVISION 06 – WOOD, PLASTIC, COMPOSITES

06 03 12 WOOD REPAIR

06 05 33.91 ACETYLATED WOOD SIDING

06 10 00 ROUGH CARPENTRY

06 40 23 INTERIOR ARCHITECTURAL WOODWORK

06 64 00 PLASTIC PANELING

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

07 14 16 COLD FLUID APPLIED WATERPROOFING

07 21 00 THERMAL & ACOUSTIC INSULATION

07 21 19 FOAMED IN PLACE INSULATION

07 26 00 VAPOR RETARDERS

07 41 13 SHEET METAL ROOF PANELS

07 60 00 SHEET METAL FLASHING AND TRIM

07 92 00 JOINT SEALANTS & FIRESTOPPING

DIVISION 08 – OPENINGS

08 11 13 HOLLOW METAL DOORS AND FRAMES

08 14 16 FLUSH WOOD DOORS

08 31 13 ACCESS DOORS AND FRAMES

08 36 13 SECTIONAL OVERHEAD DOORS

08 52 00 ALUMINUM CLAD WOOD WINDOWS

08 71 00 DOOR HARDWARE

08 80 00 GLAZING

OLYM - 184745 TOC-3

DIVISION 09 – FINISHES

09 21 16 GYPSUM BOARD ASSEMBLIES

09 24 00 CEMENTITIOUS STUCCO

09 30 13 CERAMIC TILE

09 51 13 ACOUSTIC PANEL CEILINGS

09 54 46 FABRIC WRAPPED CEILING PANELS

09 65 19 RESILIENT FLOORING

09 67 00 FLUID APPLIED FLOORING

09 68 13 TILE CARPETING

09 91 13 EXTERIOR PAINTING

09 91 23 INTERIOR PAINTING

09 93 00 STAINING AND TRANSPARENT FINISHING

09 96 00 HIGH PERFORMANCE COATINGS

DIVISION 10 - SPECIALTIES

10 14 23.16 PANEL SIGNAGE

10 21 13.19 PLASTIC TOILET COMPARTMENTS

10 28 00 TOILET AND BATH ACCESSORIES

10 44 00 FIRE PROTECTION SPECIALTIES

10 81 19 RODENT CONTROL

DIVISION 11 - EQUIPMENT

11 30 13 RESIDENTIAL APPLIANCES

DIVISION 12 – FURNISHINGS

12 32 13 MANUFACTURED WOOD VENEER FACED CASEWORK

12 36 61.16 QUARTZ COUNTERTOPS

12 48 16 ENTRANCE FLOOR GRILLES

DIVISIONS 13 – NOT USED

DIVISIONS 14 – CONVEYING EQUIPMENT

14 24 00 HYDRAULIC ELEVATOR MODERNIZATION

DIVISIONS 15:21 – NOT USED

DIVISION 22 – PLUMBING

22 00 00 PLUMBING BASIC REQUIREMENTS

22 05 13 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

22 05 16 EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING

22 05 19 PLUMBING DEVICES

OLYM - 184745 TOC-4

22 05 23 GENERAL-DUTY VALVES FOR PLUMBING PIPING

22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

22 05 48 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND

EQUIPMENT

22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

22 07 00 PLUMBING INSULATION

22 08 00 COMMISSIONING OF PLUMBING

22 10 00 PLUMBING PIPING

22 30 00 PLUMBING EQUIPMENT

22 40 00 PLUMBING FIXTURES

DIVISION 23 – HVAC

23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) BASIC

REQUIREMENTS

23 05 13 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

23 05 19 METERS AND GAUGES FOR HVAC PIPING

23 05 23 GENERAL-DUTY VALVES FOR HVAC PIPING

23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING, DUCTWORK AND EQUIPMENT

23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC EQUIPMENT

23 05 53 IDENTIFICATION FOR HVAC PIPING, DUCTWORK AND EQUIPMENT

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 00 HVAC INSULATION

23 08 00 COMMISSIONING OF HVAC

23 09 00 INSTRUMENTATION AND CONTROL PERFORMANCE SPECIFICATIONS

23 09 13 VARIABLE FREQUENCY DRIVES

23 11 13 FACILITY FUEL - OIL PIPING AND SYSTEMS

23 13 13.23 GLASS FIBER REINFORCED PLASTIC UNDERGROUND FUEL OILE STORAGE

TANKS.

23 21 13 HVAC PIPING

23 21 16 HYDRONIC PIPING SPECIALTIES

23 21 23 HYDRONIC PUMPS

23 25 00 HVAC WATER TREATMENT

23 31 00 HVAC DUCTS AND CASINGS

23 33 00 AIR DUCT ACCESSORIES

23 34 00 HVAC FANS

OLYM - 184745 TOC-5

23 37 00 AIR OUTLETS AND INLETS

23 40 00 HVAC AIR CLEANING DEVICES

23 51 00 BREECHINGS, CHIMNEYS AND STACKS

23 52 00 HEATING BOILERS

23 57 00 HEAT EXCHANGERS FOR HVAC

23 82 00 TERMINAL HEAT TRANSFER EQUIPMENT

DIVISION 26 – ELECTRICAL

26 00 00 ELECTRICAL BASIC REQUIREMENTS

26 05 09 EQUIPMENT WIRING

26 05 19 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

26 05 21 SNOW MELTING HEAT TRACING SYSTEM

26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS AND EQUIPMENT

26 05 33 RACEWAYS

26 05 34 BOXES

26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS

26 05 73 ELECTRICAL DISTRIBUTION SYSTEM STUDIES

26 08 00 COMMISSIONING OF ELECTRICAL

26 09 23 OCCUPANCY AND VACANCY SENSORS

26 09 24 DAYLIGHTING CONTROLS

26 09 25 DIGITAL LIGHTING CONTROLS

26 24 16 PANELBOARDS

26 27 13 ELECTRICAL METERING/MONITORING

26 27 26 WIRING DEVICES

26 28 00 OVERCURRENT PROTECTIVE DEVICES

26 28 16 ENCLOSED SWITCHES AND CIRCUIT BREAKERS

26 32 13 ENGINE GENERATORS

26 43 00 SURGE PROTECTIVE DEVICES

26 51 00 LIGHTING

DIVISION 27: NOT USED

DIVISION 28: ELECTRONIC SAFETY AND SECURITY

OLYM - 184745 TOC-6

28 00 01 ELECTRONIC SAFETY BASIC REQUIREMENTS

28 31 00 FIRE DETECTION AND ALARM

28 33 00 FUEL OIL MONITORING SYSTEM

DIVISION 31: EARTHWORK

31 10 00 SITE CLEARING

31 20 00 EARTH MOVING

31 25 00 EROSION AND SEDIMENT CONTROL

DIVISION 32: EXTERIOR IMPROVEMENTS

32 12 16 ASPHALT PAVING

32 13 20 SITE CONCRETE

32 14 00 UNIT PAVING

32 17 00 PAVING SPECIALTIES

DIVISION 33: SITE UTILITIES

33 40 00 STORM DRAINAGE

APPENDIX:

1. HAZARDOUS MATERIALS REPORT, LANDMARK ENVIRONMENTAL, DATED 7/30/21

2. ACCESSIBILITY AND UNIVERSAL DESIGN SCOPING FORM

3. ACCESSIBILITY INSPECTION FORM

4. CONSTRUCTION PHASING NARRATIVE, DATED 4/25/22

5. HURRICANE RIDGE DAY LODGE AMM: FIRE SUPPRESSION, DATED 10/14/21

6. HURRICANE RIDGE DAY LODGE AMM: EXIT SEPARATION, DATED 5/24/22

7. HURRICANE RIDGE DAY LODGE AMM: NUMBER OF EXITS, DATED 5/24/22

OLYM - 184745 HYDRAULIC ELEVATORS

14 24 00 - 1

SECTION 14 24 00 HYDRAULIC ELEVATORS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Modernization of existing hydraulic elevator systems.

1. Passenger type.

1.02 RELATED REQUIREMENTS

A. Division 26 - Conduit for Electrical Systems:

B. Furnish, provide and install car station, hall stations, controller/selector, electrical wiring in machine room/car/hoistway, car door operator, car top inspection station, hoistway interlocks/door gibs, intercoms, Firefighters' Emergency Operation, all requirements of the

Americans with Disability Act (ADA), Architectural Barriers Act (ABAAS) and all other elevator components as listed in this Elevator Specification.

C. Retain existing car speed, capacity, elevator entrance size, cab shell (or enclosure, car sling, etc), jack assembly, rails, buffers, pit channels, hoistway doors tracks and hangers

D. Any provision that requires facilitating removal of existing equipment and installation of new equipment in the machine rooms, lobbies, pits, hoistways, cabs and repair thereof shall be the total responsibility of Elevator Contractor.

E. All holes/cracks in the hoistways shall be sealed. All hoistway sides of the hall station boxes shall be sealed with Fire Retardant material.

F. Elevator Contractor shall verify, in writing, of their Electrical Power Requirements.

1.03 REFERENCE STANDARDS

A. ABAAS Standards -Architectural Barriers Act Accessibility Standards.

B. AISC 360 - Specification for Structural Steel Buildings.

C. ASME A17.1 - Safety Code for Elevators and Escalators.

D. ASME A17.2 - Guide for Inspection of Elevators, Escalators, and Moving Walks.

E. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or

Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.

F. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.

G. ASTM B221M - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric).

H. AWS D1.1/D1.1M - Structural Welding Code – Steel.

I. ITS (DIR) - Directory of Listed Products; current edition.

J. NEMA MG 1 - Motors and Generators.

K. NFPA 13 - Standard for the Installation of Sprinkler Systems; Most Recent Edition Adopted by

Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

L. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

M. NFPA 80 - Standard for Fire Doors and Other Opening Protectives.

N. UL (DIR) - Online Certifications Directory; current listings at database.ul.com.

http://www.ada.gov/ https://www.aisc.org/publications/steel-standards/#30666 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASME%20A17.1 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASME%20A17.2 https://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20A653/A653M http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20B221 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20B221M https://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=AWS%20D1.1/D1.1M http://www.intertek-etlsemko.com/ http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NEMA%20MG%201 https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and-standards/detail?code=13 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NFPA%2070 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NFPA%2080 http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.html

14 24 00 - 2

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate work with other installers to provide conduits necessary for installation of wiring including but not limited to:

a. Elevator equipment devices remote from elevator machine room or hoistway.

b. Telephone service for machine room.

c. Fire alarm panel from controller cabinet.

d. Emergency generator wiring from ATS to elevator room controller.

B. Preinstallation Meeting: Convene meeting at least one week prior to start of this work.

1. Review schedule of installation, proper procedures and conditions, and coordination with related work.

C. Construction Use of Elevator: not permitted.

D. Material and equipment shall be suitably protected against corrosion, dirt, mechanical damage, weather and chemical damage before and during modernization as recommended by the manufacturer.

E. All existing elevator equipment that is not being retained shall be removed from the job-site by the Elevator Contractor at the sole cost to the Elevator Contractor. This includes all existing machine room, hoistway and car elevator equipment.

1.05 SUBMITTALS

A. See Section 01 33 23 – Submittal Procedures.

B. Product Data: Submit data on following items:

1. Signal and operating fixtures, operating panels, and indicators.

2. Electrical characteristics and connection requirements.

C. Shop Drawings: Include appropriate plans, elevations, sections, diagrams, and details on following items:

1. Calculated heat dissipation of elevator equipment in machine room.

2. Electrical characteristics and connection requirements.

3. Indicate arrangement of elevator equipment and allow for clear passage of equipment through access openings. Drawings shall show but is not limited to: tank unit, controller, mainline disconnect, oil line, electrical penetrations, power data.

D. Manufacturer's Qualification Statement.

E. Installer's Qualification Statement.

F. Testing Agency's Qualification Statement.

G. Warranty Documentation: Submit manufacturer warranty and ensure that forms have been completed in Government's name and registered with manufacturer.

H. Operation and Maintenance Data:

1. Parts catalog with complete list of equipment replacement parts; identify each entry with equipment description and identifying code.

2. Operation and maintenance manual.

1.06 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum ten years documented experience.

B. Installer Qualifications: Trained personnel and supervisor on staff of elevator equipment manufacturer.

14 24 00 - 3

C. Testing Agency Qualifications: Independent firm specializing in performing testing and inspections of type specified in this section.

D. Products Requiring Fire Resistance Rating: Listed and classified by ITS (DIR), UL (DIR), or testing agency acceptable to authorities having jurisdiction.

E. Products Requiring Electrical Connection: Listed and classified by UL (DIR) or testing agency acceptable to authorities having jurisdiction as suitable for the purpose indicated in construction documents.

1.07 WARRANTY

A. See Section 01 77 00 - Closeout Submittals, for additional warranty requirements.

B. Provide manufacturer's warranty for elevator operating equipment and devices for one year from Date of Substantial Completion.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Basis of Design - Hydraulic Elevators: TKE; H-Power Tac32

B. The completed elevator modernization shall conform to the Elevator Safety Code except as specifically otherwise indicated or specified. The elevator modernization, including equipment, material, workmanship, design, and tests shall be in accordance with the standards, rules and

Specifications referenced. All material and equipment shall be new. Electrical materials shall meet and bear evidence of meeting the requirements of Underwriter's Laboratories. The equipment shall be the product of a manufacturer regularly engaged in the manufacture and modernization of this type of equipment. Working parts shall be accessible for inspection, servicing and repair. Adequate means shall be provided for the lubrication of all wearing parts that require lubrication.

2.02 HYDRAULIC ELEVATORS

A. Hydraulic Passenger Elevator:

1. Hydraulic Elevator Equipment:

a. Ground hydraulic jack retain existing.

2. Operation Control Type:

a. Single Automatic (Push Button) Operation Control..

3. Service Control Type:

a. Standard service control only.

4. Interior Car Height: 95 inch: retain existing

5. Electrical Power: retain existing, new Variable Frequency Drive phase converter: single to three phase conversion. This work is specified in Division 26.

6. Rated Net Capacity: 2000 pounds: retain existing

7. Rated Speed: 50 Feet per minute: retain existing

8. Hoistway Size: retain existing

9. Interior Car Platform Size: retain existing

10. Elevator Pit Depth: 24 inch retain existing

11. Overhead Clearance at Top Floor: retain existing

13. Travel Distance: retain existing

14. Number of Stops: 2 retain existing

15. Number of Openings: 2 front: retain existing

2.03 COMPONENTS

A. Elevator Equipment:

14 24 00 - 4

1. Motors, Hydraulic Equipment, Controllers, Controls, Buttons, Wiring, Devices, and

Indicators: Comply with NFPA 70. Refer to Division 26.

2. Guide Rails, Cables, Buffers, Attachment Brackets and Anchors: Retain existing

3. Buffers: Retain existing

4. Lubrication Equipment:

a. Provide grease fittings for periodic lubrication of bearings.

b. Lubrication Points: Visible and easily accessible.

B. Electrical Equipment:

1. Motors: NEMA MG 1.

2. Boxes, Conduit, Wiring, and Devices: As required by NFPA 70. Refer to Division 26.

3. Spare Conductors: Provide ten percent in extra conductors and two pairs of shielded audio cables in traveling cables.

4. Include wiring and connections to elevator devices remote from hoistway and between elevator machine room. Provide additional components and wiring to suit machine room layout.

2.04 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Comply with ASME A17.1, applicable local codes, authorities having jurisdiction (AHJ).

B. Accessibility Requirements: All new components to comply with ABAAS Standards.

C. Perform welding of steel in accordance with AWS D1.1/D1.1M.

D. Perform electrical work in accordance with NFPA 70.

E. Electrical equipment and wiring shall conform to NFPA 70 - National Electrical Code, current adopted edition.

2.05 OPERATION CONTROLS

A. Elevator Controls: Provide landing operating panels and landing indicator panels.

1. Landing Operating Panels: Metallic type, one for originating "Up" and one for originating "Down" calls, one button only at terminating landings; with illuminating indicators.

2. Landing Indicator Panels: Illuminating.

3. Comply with ABAAS Standards for elevator controls.

B. Interconnect elevator control system with building security, fire alarm, smoke alarm, and building management control systems.

C. Door Operation Controls:

1. Program door control to open doors automatically when car arrives at floor landing.

2. Render "Door Close" button inoperative when car is standing at dispatch landing with doors open.

3. Door Safety Devices: Moveable, retractable safety edges, quiet in operation; equipped with photo-electric light rays.

D. Provide "Firefighter's Emergency Operation" in accordance with ASME A17.1, applicable building codes, authorities having jurisdiction (AHJ).

1. Designated Landing: Second landing.

2.06 OPERATION CONTROL TYPE

A. Simplex Selective/Collective Operation Automatic Control:

1. Refer to description provided in ASME A17.1.

http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NFPA%2070 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NFPA%2070 http://www.ada.gov/ https://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=AWS%20D1.1/D1.1M http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=NFPA%2070 http://www.ada.gov/ http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASME%20A17.1

14 24 00 - 5

2. Provide system in car so that momentary pressure on one or more of car buttons causes car to start moving in direction of registered call.

3. If a car stops for a landing call, and car button matching direction the car was traveling is pressed within a predetermined time interval after a landing stop, proceed in same direction regardless of other landing calls that are registered.

4. Hold car for a predetermined time interval at landings when stops are made to enable passengers to enter or leave the car.

5. Program system to minimize delays caused by registration of car calls disproportionate to number of persons in car.

6. Program door operating sequence to minimize car and landing door open and close time periods.

7. Include independent service control where indicated, as follows:

a. Doors open automatically upon arrival at landing.

b. Set landing indicator panels as inoperative when in independent service mode.

B. Door Operation:

1. Open doors automatically when the car arrives at a floor to permit transfer of passengers.

Automatically close doors after a timed interval.

C. Automatic Stopping Accuracy:

1. Two-way automatic leveling feature shall stop the car within 1/4" regardless of load or direction of travel. Landing level will be maintained within the leveling zone irrespective of the hoistway doors being open or closed.

D. Hydraulic Control System:

1. The hydraulic control system shall be designed suitable for operation under the required pressure and shall be mounted in the storage tank. The control valve will be a unit type with

UP, DOWN and check valve included. All of the functions shall be fully adjustable for maximum smoothness and to meet contract conditions.

2. A manual-lowering valve will be provided to lower the elevator at slow speed.

3. The hydraulic valve shall have the capability of providing a smooth, comfortable acceleration, retardation and final stop.

E. Emergency Car Lighting and Alarm:

1. Car-mounted, battery unit with solid-state charger to operate alarm bell and lighting, per

Code. Battery to be rechargeable with 5-year minimum life expectancy. Provide test button in service cabinet of car station, which causes illumination of standby lighting bulbs.

2. Emergency lighting fixture shall be integral part of car operating station.

2.07 MACHINE ROOM EQUIPMENT

A. Controller:

1. Provide reduced voltage (solid state) motor starting circuits.

2. Provide Independent Service feature.

3. Provide viscosity control unit.

4. Provide emergency power operation tied into existing building generator ATS to provide full operation of the car on power loss.

a. If normal electrical building power is not in operation the car shall close the doors and return to the main lobby and open the doors. All safety circuits shall be monitored.

b. Car shall remain out of service until normal electrical building power is restored.

5. Firefighter's Emergency Operation:

14 24 00 - 6

a. Operate and recall elevator to designated floor during fire. Provide sensor signal wiring from hoistway or machine room connection point to controller terminals. Operate visual/audible signal until return is complete or automatic operation restored. Provide Phase I key switch with engraved instruction at main recall floor hall station.

6. Low-Oil Control:

a. In the event hydraulic oil level is insufficient for travel to the top floor, provide controls to return elevator to the main level and park with car doors open, until oil is added and elevator is manually re-set.

B. Hydraulic Pump Unit:

1. Assembled unit consisting "wet type" of positive-displacement pump, induction motor, master-type control valves combining safety features, holding, direction, bypass, stopping and manual-lowering functions, shut-off valve, oil reservoir with protected-vent opening, oil gauge and outlet strainer, drip pan and connections all mounted on isolating pads.

C. Shutoff Valve:

1. Provide a new shutoff ball valve in the elevator machine room.

D. Keys

1. Key Box

a. Provide approved key lock box, located as per requirements of Washington State

Elevator Inspector and Local Fire Department. Provide in this lock box, one (1)

Phase I re-call key, one (1) Phase II operation key, and one (1) machine room key and any other keys required by Washington State Elevator Inspector and Local Fire

Department.

2. Provide all required sets of keys with marking tags as required by the Washington State

Elevator Inspector and ASME A17.1-2010/CSA B44-10, Section 8.1.

3. Keys shall be separated into groups as required by ASME A17.1-2010/CSA B44-10, Section 8.1.

2.08 MATERIALS

A. Sheet Steel: Hot-dipped galvanized steel sheet, ASTM A653/A653M, with G90/Z275 coating.

B. Extruded Aluminum: ASTM B221 (ASTM B221M), natural anodized finish unless otherwise indicated.

C. Resilient Flooring: Rubber tile flooring, as specified in Section 09 65 19.

2.09 HOISTWAY EQUIPMENT

A. Guide Rails:

1. Existing guide rails shall be retained.

B. Guide Rail Fishplates:

1. Retain existing

C. Spring Buffers:

1. Retain existing.

D. Jack Assembly:

1. Retain existing

E. Hydraulic Jack Support:

1. Retain existing

F. Pit Stop Switch:

https://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20A653/A653M http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20B221 http://global.ihs.com/doc_detail.cfm?rid=BSD&document_name=ASTM%20B221M

14 24 00 - 7

1. An emergency type stop switch shall be located in the pit as to be accessible from the hoistway access door, per ASME A17.1/CSA B44. Locate stop switch adjacent to the pit ladder.

G. Seismic Safety Valve:

1. Provide Seismic Safety Valve in oil line in pit area.

2. Install Seismic Safety Valve adjacent to hydraulic cylinder inlet-outlet connection.

3. Provide seal on Seismic Safety Valve after adjusting for correct setting.

H. Shutoff Valve:

1. Provide shutoff ball valve in oil line in elevator pit.

I. Pit Ladder:

1. Extend the vertical pit ladder to a height of 48" above the hoistway sill of lowest level/landing. Maintain rung spacing and spacing from pit wall.

2. Provide a horizontal hand-hold at the top of the ladder.

2.10 HOISTWAY ENTRANCES

A. Frames

1. Retain existing

B. Door Panels

1. Retain existing

C. Door Closers:

1. New heavy duty spirator type.

D. Door Tracks & Hangers:

1. Retain existing.

E. Sills:

1. Retain existing.

2. Clean and remove all debris and build-up.

F. Fascia, and Hanger Covers:

1. Retain existing. Clean and touch up paint only.

G. Headers

1. Retain existing

2.11 CAR EQUIPMENT AND MATERIALS

A. Car Sling:

1. Retain existing. Replace any missing or broken components.

B. Buffer Striking Plates:

1. Retain existing. Ensure plates are securely mounted to bolster channel.

C. Platform:

1. Retain existing platform. Replace any damaged or missing component.

D. Car Doors:

1. Provide new stainless steel #4 finish door panels.

E. Car Door Hangers, Rollers, Up thrust and Tracks:

1. Provide new.

F. Header:

1. Provide New.

G. Car Door Electrical Contact:

1. Provide New.

2. Provide door restrictors.

H. Door Edge Protective Device:

1. Provide car door with infrared type reopening device extending the full height of the car door.

I. Car Door Clutch:

14 24 00 - 8

1. Provide New.

2. Provide the door anti-egress device.

J. Door Operator:

1. Provide new heavy-duty, linear door operator. Car door operator shall mechanically drive the car doors.

a. Open doors automatically when car arrives at a floor to permit egress of passengers.

b. Close doors automatically after a timed interval.

K. Elevator Car Station:

1. Provide one (1) vandal resistant elevator control station with faceplate, consisting of a metal box containing the operating fixtures, mounted behind the non-swing car enclosure front panel. Install in-car emergency light as part of the new station.

2. Provide car position indicators, four inches (4") high digital type together with directional arrows located in the top area of the car operating stations. Provide 1/4" thick clear Lexan lens cover or a type that shall be vandal resistant. Existing position indicators (over car doors) shall be covered with a #4 stainless steel plate.

3. Provide emergency lighting unit. Device shall be built in, and part of the front main car operating station at the upper section of the station cover. Provide vandal resistant

Lexan clear lens over device. Device shall provide lighting of .02 ftc at a distance of four feet (4') above the car floor and one foot (1') in front of the car operating station.

The emergency lighting shall maintain the light intensity for a period of at least four

(4) hours

4. Suitably identify floor buttons, lighted alarm button, door open button, door close button and keyed emergency stop switch by engraved and painted letters or symbols per Local Handicapped Standards and ABAAS and ADA requirements. Provide flush inset, back-fastened handicapped markings. Locate operating controls location as required by ABAAS and ADA requirements. Locate keyed stop switch and alarm button thirty-five (35") above car floor. Engrave below door open, door close, stop switch and alarm in one-quarter inch (¼") letters-"Door Open", "Door Close", "Alarm" and "Run-Stop".

5. Provide one eighth of an inch (1/8") raised floor pushbuttons which illuminate to indicate LED call registration. Provide floor designation engraved plates to the left of each button.

6. Provide illuminated alarm button at bottom of station to sound distress signal alarm located on the car top. Provide a signal to the elevator controller at a terminal strip for monitoring purposes of alarm at a remote location.

7. Provide keyed stop switch in panel faceplate with markings to show "Run" and

"Stop" positions.

8. Provide door open button to stop and reopen closing doors. Make button operable while car is stopped at landing, regardless of special operational features, except

Firefighters' Service.

9. Provide one (1) Firefighters' Service Phase II key switch with engraved instructions, light jewel, buzzer and call cancel button. Provide Firefighter's phone jack plug in car station with electrical conductors to elevator controller devices located per ASME

A17.1/CSA B44 code.

10. Provide lockable service panel with recessed flush cover plate. Include the following controls, with purpose and operating positions identified by engraved letters painted black.

a. Car light switch and emergency light test switch. Test switch shall disconnect the electrical power to the main car lighting circuit.

b. Three position fan switch-Low Speed-High Speed-Off.

14 24 00 - 9

c. Independent service switch to permit selection of independent or automatic operation.

d. Start button for closing doors and starting elevator when operating on independent service. Floor pushbuttons may be used for this function.

e. Duplex 120 VAC electrical convenience outlet. Provide GFCI protection.

11. Provide black paint filled engraving as follows.

a. Elevator number and capacity

b. “Permit on File with Building Manager”

12. Telephone Cabinet:

a. Emergency communication device shall be mounted as part of the car operating panel. Provide all required electrical wiring from the in car station to the elevator controller. Phone shall be mounted such that it is easily removable for servicing. Provide all required programming including labor and material for placing device in operation.

13. Faceplate Material and Finish: #4 stainless steel.

L. Car Top Control Station:

1. Operating fixture shall be provided containing continuous pressure Up, Down and Safe buttons, emergency stop switch, inspection/run switch, and 110 VAC duplex outlet with

GFCI protection.

2. Toggle switches shall not be provided for the Stop, Run and Inspection switches unless the switches are guarded against accidental activation. Fasten car top station to car crosshead.

2.12 LANDING CONTROL STATIONS

A. Pushbuttons:

1. Provide "Surface Mounted" vandal resistant fixtures at each landing. Include pushbuttons for direction of travel, which illuminate LEDs to indicate call registration.

Engrave safety message, "In Case of Fire..." (Ref. ASME A17.1-2010/CSA B44-10, 2.27.9) in pushbutton faceplate and fill black. Center of buttons to be 42" from finish floor.

2. Provide UP or DOWN markings to the left of each button together with Braille markings. Marking plates shall be built into the cover plates.

3. Provide Firefighter's Emergency Operation Phase I key switch with engraved instructions at main Recall floor hall station.

4. Provide visual and audible signals for communication device to comply with ASME

A17.1/CSA B44, 2.27.1.1.6.

B. Faceplate Material and Finish:

1. Hall Pushbutton Station: Surface mount #4 Brushed Stainless Steel. Provide vandal resistant Stainless Steel fastening devices. Must be field measured and verified by elevator contractor so new fixture covers existing cutouts and buttons are placed at code height.

2.13 SIGNALS

A. Car Position Indicator:

1. Include as integral part of car station. Provide 2" high digital-type indications representing the floor served. Provide a floor passing audible signal. Signal shall be no less than 20 decibels with a frequency no higher than 1500 Hz.

2. Provide stainless steel #4 cover plate for existing car position indicator over door.

14 24 00 - 10

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting this work.

B. Verify that hoistway, pit, machine room are ready for work of this section.

C. Verify hoistway shaft and openings are of correct size and within tolerance.

E. Verify that electrical power is available and of correct characteristics.

3.02 PREPARATION

A. Arrange for temporary electrical power for installation work and testing of elevator components, and comply with requirements of Section 01 50 00 - Temporary Facilities and

Controls.

B. Retain the jack assembly as existing.

C. Maintain elevator pit excavation free of water.

D. Maintain in-ground elevator shaft excavation free of water.

3.03 INSTALLATION

A. Coordinate this work with the existing hoistway.

B. Install system components, and connect equipment to building utilities.

C. Provide conduit, electrical boxes, wiring, and accessories. Refer to Division 26.

D. Structural Metal Surfaces: Clean surfaces of rust, oil or grease; wipe clean with solvent; prime two coats.

E. Adjust equipment for smooth and quiet operation.

3.04 TOLERANCES

A. Guide Rail Alignment: Plumb and parallel to each other in accordance with ASME A17.1 and

ASME A17.2.

B. Car Movement on Aligned Guide Rails: Smooth movement, without any objectionable lateral or oscillating movement or vibration.

3.05 FIELD QUALITY CONTROL

A. See Section 01 40 00 - Quality Requirements, for additional requirements.

B. Testing and inspection by regulatory agencies certified in accordance with ASME QEI-1 will be performed at their discretion.

1. Schedule tests with agencies and notify Contracting Officer.

2. Obtain permits as required to perform tests.

3. Document regulatory agency tests and inspections in accordance with requirements.

4. Perform tests required by regulatory agencies.

5. Furnish test and approval certificates issued by authorities having jurisdiction.

3.06 ADJUSTING

A. Adjust for smooth acceleration and deceleration of car to minimize passenger discomfort.

B. Adjust with automatic floor leveling feature at each floor landing to reach 1/4 inch maximum from flush with sill.

3.07 CLEANING

A. Remove protective coverings from finished surfaces.

14 24 00 - 11

B. Clean surfaces and components in accordance with manufacturers written instructions.

3.08 CLOSEOUT ACTIVITIES

A. See Section 01 78 00 - Closeout Submittals, for closeout submittals.

B. See Section 01 79 00 - Demonstration and Training, for additional requirements.

C. Demonstrate proper operation of equipment to Contracting Officer's designated representative.

D. Training: Train NPS personnel on cleaning and operation and maintenance of system.

1. Use operation and maintenance manual as training reference, supplemented with additional training materials as required.

2. Provide minimum of two hours of training.

3. Instructor: Manufacturer's training personnel.

4. Location: At project site, unless noted otherwise.

3.09 PROTECTION

A. Do not permit construction traffic within car after cleaning.

B. Protect installed products until Date of Substantial Completion.

C. Touch-up, repair, or replace damaged products and materials prior to Date of Substantial

Completion.

3.10 RELATED WORK PERFORMED BY OTHERS

A. The Elevator Contractor shall submit its proposal based on acceptance of the hoistways and machine room as exists. The Elevator Contractor shall notify Contracting Officer of any changes to the hoistways and/or machine room, which are necessary to accommodate the

Elevator Contractor’s equipment or to comply with Code prior to the submission of the bid for the elevator modernization.

B. The Elevator Contractor shall assist the General Contractor with coordination of the work to be performed which is not part of the Elevator Contract, as required, during the course of the project to assure that all work required of the other trades is completed in such a manner and in such time as will be required to permit the Elevator Contractor to commence and complete the

Contract work within the project schedule requirements.

3.11 INSPECTIONS

A. Accessibility Inspection: Accessibility inspection shall be performed by the Contractor.

Inspections shall be scheduled at the conclusion of each work sequence and in conjunction with updated construction schedules. Contractor shall utilize the National Park Service CQC

Accessibility Inspection Report as basis for recording findings. Any non-compliant conditions shall be documented. Supplement Report with digital images, notation, red-line drawings, sketches and dimensions, product literature, submittal, etc. to explain installed work. Submit completed Report to CO within 24 hours of commencing inspection.

END OF SECTION

T

EXISTING VAULT

ROUTE CONDUIT ALONG TRENCH

BETWEEN PULL VAULTS IN MEADOW.

REFER TO CIVIL DRAWINGS FOR

ROUTING OF CONDUIT AND TRENCH

DETAIL.

BORE CONDUIT UNDER

RETAINING WALL BETWEEN

THE PARKING LOT AND

MEADOW.

ROUTE CONDUIT THROUGH

TRENCH IN PARKING LOT.

REFER TO AND COORDINATE

WITH CIVIL FOR PAVEMENT.

ROUTE CONDUIT

ALONG TRENCH

BETWEEN PULL VAULT

IN MEADOW AND

GENERATOR BUILDING.

REFER TO CIVIL

DRAWINGS FOR

ROUTING OF CONDUIT

AND TRENCH DETAIL.

RADIO / GENERATOR BUILDING

HURRICANE RIDGE

DAY-USE LODGE

E1.0

PROVIDE (2) 1-INCH CONDUITS. ONE FROM MAIN

DISTRIBUTION PANEL IN ELECTRICAL ROOM 20

FOR POWER AND SECOND FROM ELECTRICAL

ROOM 20 FOR FUTURE SIGNAL, STUB-OUT AND

CAP IN ROOM. STUB-OUT BENEATH SIDEWALK.

PROVIDE FLUSH BRONZE MARKER IN SIDEWALK

INDICATING FUTURE EV CHARGER CONDUIT

STUB-OUTS. LABEL CONDUITS IN ELECTRICAL

ROOM INDICATING FUTURE EV CHARGER

CONDUIT, SEE MARKER IN SIDE WALK.

GENERATOR DOCKING STATION

PROVIDE BONDING TO

NEW PEDESTAL MOUNTED

FUEL FILL CABINET.

(E) NATIONAL

PARK SERVICE

TRANSFORMER

100 KVA

GENERATOR ROOM

RADIO ROOM

'GDS'

250 A, 240/120 V, 2P

NEMA 3R

GENERATOR DOCKING STATION,

WALL-MOUNTED

COORDINATE EXACT LOCATION

WITH CONTRACTING OFFICER.

(E) DIESEL GENERATOR

PANEL 'G' (E)

REPLACE EXISTING 200A GENERATOR

DISCONNECT WITH NEW 250A

DISCONNECT. REFER TO SHEET E5.1 FOR

CIRCUIT BREAKER INFORMATION.

(E) PULL BOX FOR

GENERATOR FEEDER

(E) LOAD BANK IN

CEILING SPACE

(E) GENERATOR-ON ALARM

CIRCUIT BREAKER DISCONNECT

(E) 70A CIRCUIT BREAKER

DISCONNECT TO LOAD BANK

PROVIDE NEMA 3R EMERGENCY POWER OFF RED

MUSHROOM PUSH BUTTON AT BUILDING EXTERIOR WITH

WEATHER PROTECTED COVER FOR EMERGENCY SHUTDOWN

OF THE GENERATOR. TIE-IN 2-WIRE SIGNAL CONTROL WITH

EXISTING GENERATOR CONTROLLER EMERGENCY STOP

CONTROL CIRCUIT. MAINTAIN UL-COMPLIANT SYSTEM,

INSTALL PER MANUFACTURER REQUIREMENTS. ADD

ENGRAVED LABEL ABOVE PUSH BUTTON: "GENERATOR

EMERGENCY POWER OFF"

MTS-SITE DISCONNECT

NEMA-3R

250A, 240/120V, 2P

DESIGNED:

TECH REVIEW:

DATE:

SUB SHEET NO. TITLE OF SHEET

SHEET

PMIS/PKG NO.

DRAWING NO.

SCALE: B

SCALE: A

152859

HURRICANE RIDGE

OLYMPIC NATIONAL PARK OF 126

B

IM

/2

-1

N

P S

O L Y

M D

D C

D

H U

R R

IC

A

N E

R

ID

G E

/H u rr ic a n e R id g e

M

E P v

.r v t

/1

/2

:1

:5

A

M

E1.0

KM

KM

MKO

05/25/2022

SITE PLAN -

ELECTRICAL

184745

300 60

SCALE: AE1.0

1 SITE PLAN - ELECTRICAL

SCALE OF FEET

GENERAL SHEET NOTES

A. ROUTE THE FOLLOWING CONDUIT BETWEEN THE DAY LODGE AND

GENERATOR BUILDING.

(2) 4" CONDUIT FOR GENERATOR POWER, REFER TO 1/E5.1 FOR

ADDITIONAL INFORMATION

(1) 3" CONDUIT FOR COMMUNICATIONS. PROVIDE 6 STRAND SINGLE MODE

FIBER OPTIC RADIO COMMUNICATION LINE FROM RADIO ROOM TO DAY-

USE LODGE ATTIC TELECOM RACK, SHIELDED 2-WIRE BELDEN 3500 OR

EQUAL CABLE FOR NEW GENERATOR ANNUNCIATOR PANEL, AND 2-WIRE

#12 CU THWN-2 FOR EXISTING TRANSFER SWITCH CONTROL GENERATOR

START SIGNAL AT DAY-USE LODGE. CONNECT GENERATOR

ANNUNCIATOR CABLE AND START SIGNAL AT BOTH GENERATOR

DOCKING STATION AND GENERATOR CONTROL PANEL AT GENERATOR

BUILDING. COORDINATE WITH CONTRACTING OFFICER FOR EXACT

TERMINATION LOCATIONS OF RADIO COMMUNICATION LINE. TERMINATE

AT EXISTING RACK AND MATCH EXISTING CONNECTORS. PROVIDE

INNERDUCT FOR UNARMORED CABLES. DEMOLISH EXISTING GENERATOR

START SIGNAL CONTROL WIRE.

(1) 3" CONDUIT WITH PULL STRING FOR FUTURE VERIZON SERVICE

(1) 3" SPARE CONDUIT WITH PULL STRING

B. REFER TO DETAIL 3/C5.3 FOR TRENCHING REQUIREMENTS / DETAIL.

C. CLALLAM PUD (COLIN YOUNG, 360-565-3250 X250,

CYOUNG@CLALLAMPUD.NET) TAKES NO ISSUE WITH A TEMPORARY

SERVICE ADDED ON SERVICE, HOWEVER PRIMARY / SECONDARY

FEEDERS AND TRANSFORMERS ARE PROPERTY OF NATIONAL PARK

SERVICE AT THIS PROJECT LOCATION. COORDINATE WITH CONTRACTING

OFFICER FOR CONSTRUCTION TEMPORARY SERVICES. IF UTILIZING

EXISTING 100 KVA BUILDING TRANSFORMER, ENSURE TRANSFORMER IS

NOT OVERLOADED.

SCALE: BE1.0

2 FIRST FLOOR POWER PLAN - RADIO / GENERATOR BUILDING

40 84

SCALE OF FEET

(E) MAXIMUM DEMAND: 51.21 KW

POWER FACTOR (0.9): 56.90 KVA

+25% SAFETY FACTOR: 71.13 KVA

SUBTRACTED (X) LIGHTING LOAD -20.00 KVA

+ADDED (NEW) DEMAND LOAD: 36.21 KVA

TOTAL NEW DEMAND LOAD: 87.34 KVA

TOTAL AMPS (240V, 1PHASE): 363.90 AMPS

SPARE CAPACITY AT

100 KVA TRANSFORMER: 12.67 %

LOAD SUMMARY

AT EXISTING MAIN DISCONNECT

PEAK DEMAND MEASURED BETWEEN 12/13/2019 AND 01/17/2020 WAS

51.21 KW

*EXISTING LIGHTING LOAD CALCULATED AT 20kVA, NEW LED LIGHTING

LOAD IS 9.73 KVA

G

LOWER LEVEL

MAIN LEVEL

(E) 300 AMP

SQUARE-D TYPE

LAL 263001436

(X)

200A 2P

800 AMP BUS

(E) 60 KW / KVA DIESEL GENERATOR

BALDOR/ STAMFORD SERIAL NUMBER

M09i330802, MODEL #IDLC60-3JU

(X) MAIN SERVICE PANEL 'MC'

(E) 600A, 3P, 4W AUTOMATIC

TRANSFER SWITCH

N

E

L

(E) 800A 240V / 2P

(E) NATIONAL PARK SERVICE TRANSFORMER

100 kVA (PRIMARY METERED SYSTEM)

TRANSFORMER #13597, 7.2KV/120-240V,

1.9% IMPEDANCE

(E) 2 - 5/8" X 96" GROUND ROD WITH 1/0 CU GROUND.

M

(E) BOOSTER

WATER HEATER

36 KW

(X)

100A 2P

M

(E)PANEL

'K'

(X)

200A 2P

M

(E)PANEL

'A'

(X)

225A 2P

M

(E)PANEL

'XB'

(E) 150A / 2P

(E)PANEL

'XA'

200A MCB

(E) 100A / 2P

(X)

100A 2P

M

(E)PANEL

'B'

(X)

70A 2P

M

(E) ELEVATOR

GENERATOR BUILDING

(E)PANEL

'G'

100A

MCB

(X) 200A / 2P

(E)

(X)

(X)2003AE 2003AE 2003AE

8003E (X)(E)

(X)

(E)

(X)

(X)

(E) MAIN BUILDING DISCONNECT

120/240V, 800A, 1 PH, 3 WIRE

AIC RATING: 22000

(E) STANDBY

BUILDING

DISCONNECT

(X)(X)(X)(X)(X)(X)

(X) 200 AMP

(X)

(E) GENERATOR-ON

ALARM VIA CIRCUIT

BREAKER

(E) LOAD BANK VIA

CIRCUIT BREAKER

T

(E) SNOW TOW

OPERATOR

(E)

(E) 100A 2P

(X)

(E) 1/0 AWG AL, PRYSMIAN CABLE

EPR DOUBLE SEAL15kV 133% AL

SINGLE PHASE - FULL NEUTRAL

(X)

(X)

(X) PHASE-A-MATIC

SAFETY SWITCH

(X) PHASE-A-MATIC

F

(E) 200A FUSED

ELEVATOR DISCONNECT

703E

G

LOWER LEVEL

MAIN LEVEL

(N) 400AF/250AT, 2P

LSI ELECTRONIC-TYPE

200A 2P

800 AMP BUS

(E) 60 KW / KVA DIESEL GENERATOR

BALDOR/ STAMFORD SERIAL NUMBER M09i330802, MODEL #IDLC60-3JU

MINIMUM GENERATOR SIZE REQUIRED FOR STARTUP OF ELEVATOR

BASED ON SPECIFIED SINGLE PHASE INPUT, THREE PHASE OUTPUT VFD

(DRIVE AMP RATING x 160% x 1.732 x 230V ELEVATOR RATING: 38,880 W

MAIN DISTRIBUTION PANEL 'MDP'

AVAILABLE FAULT CURRENT: 22,508 A

SSCR: 42,000 A

(E) 600A, 3P, 4W AUTOMATIC

TRANSFER SWITCH

AVAILABLE FAULT CURRENT: 19,236 A

SCCR: 22,000 A

N

E

L

(E) 800A 240V / 2P

(E) 2 - 5/8" X 96" GROUND ROD WITH 1/0 CU GROUND.

(E) BOOSTER

WATER HEATER

36 KW

200A 2P

(E)PANEL

'K'

200A 2P

(E)PANEL

'A'

400AF/

250AT

LSI

2P

(E)PANEL

'XB'

(E) 150A / 2P

(E)PANEL

'XA'

225A MCB

(E) 100A / 2P

225A 2P

(E)PANEL

'B'

(E) ELEVATOR

7.5 HP 3-PHASE

GENERATOR BUILDING

(E)PANEL

'G'

100A

MCB

(N) 400AF/250AT, 2P

LSI ELECTRONIC-TYPE

(E)

25032003AE 2253

8003(E)

(E) SEE SITE PLAN, SHEET E1.0 FOR ROUTING

OF CONDUIT THROUGH MEADOW.

PANEL

'E'

SPD

SPD

60A 2P

(E) MAIN BUILDING DISCONNECT

120/240V, 800A, 1 PH, 3 WIRE

AIC RATING: 24,176 A

SCCR: 42,000 A

STANDBY

BUILDING

DISCONNECT

E5.1

2503V

NEMA 3R, 250A, 240/120V, 1PH, 2P

WALL MOUNTED GENERATOR

DOCKING STATION 'GDS'. REFER

TO SPECIFICATION 26 32 13.

TO TEMPORARY GENERATOR

MTS-SITE

250V / 2-POLE

AVAILABLE FAULT CURRENT: 4,850 A

SCCR: 10,000 A

8003E

2003AE2003AE

(E) GENERATOR-

ON ALARM

(E) LOAD BANK

N

L

E

(E) NATIONAL PARK SERVICE TRANSFORMER

100 kVA (PRIMARY METERED SYSTEM)

TRANSFORMER #13597, 7.2KV/120-240V,

1.9% IMPEDANCE

T

(E) SNOW TOW

OPERATOR

(E)

(E) 100A 2P

MTS- SITE DISCONNECT

240V/2P, 250A

NEMA-3R

(E) 300 AMP

SQUARE-D TYPE

LAL 263001436

250 W

LIGHTING

INVERTER

TWO (2): 100A

BUSSED

SPACES

200A

BUSSED

SPACE

(E) 1/0 AWG AL, PRYSMIAN CABLE

EPR DOUBLE SEAL15kV 133% AL

SINGLE PHASE - FULL NEUTRAL

12 VFD

F

(E) 200A FUSED ELEVATOR

DISCONNECT. REPLACE EXISTING

FUSES WITH 50A FUSE.

703E

12"

GROUND ROD, 3/4" x 10'-0".

COPPER ALLOY CONNECTOR

#4/0 COPPER GROUND WIRE.

FINISHED GRADE

PRE-CAST CONCRETE GROUND ROD

BOX, CHRISTY #F1 OR EQUAL.

CAST CONCRETE COVER MARKED

"GROUND".

36" MIN.

DESIGNED:

TECH REVIEW:

DATE:

SUB SHEET NO. TITLE OF SHEET

SHEET

PMIS/PKG NO.

DRAWING NO.

152859

OF 126

B

IM

/2

-1

N

P S

O L Y

M D

D C

D

H U

R R

IC

A

N E

R

ID

G E

/H u rr ic a n e R id g e

M

E P v

.r v t

/1

/2

:5

:0

A

M

E5.1

KM

KM

MKO

05/25/2022

SINGLE LINE DIAGRAMS

- ELECTRICAL

HURRICANE RIDGE DAY LODGE

OLYMPIC NATIONAL PARK

184745

A,C,S,V,X C=Conduit only E=Existing S=Service secondary V=Upsized for voltage drop X=Seperately derived system

FEEDER SCHEDULE

(E) FEEDER IS EXISTING TO REMAIN

(X) DEMOLISH FEEDER

202 2 #12 CU, 1 #12 CU GND., IN 3/4" C

503 3 #6 CU, 1 #10 CU GND., IN 3/4" C.

703E 3 #4 CU, 1 #8 CU GND., IN 1" C.

803 3 #2 CU, 1 #8 CU GND., IN 1 1/4" C.

2003AE 2 - 250 kcmil AL, 1 - #6 AL NEUTRAL, 1 #6 CU GND., IN 2" C.

2253 3 #4/0 CU, 1 #4 CU GND., IN 2" C.

2503 3 - 250 kcmil CU, 1 #4 CU GND., IN 2 1/2" C.

2503V 2 SETS OF (3 -500 kcmil CU, 1 #3/0 CU GND., IN 4" C.)

3003 3 - 350 kcmil CU, 1 #4 CU GND., IN 2 1/2" C.

8003 3 SETS OF (3 -300 kcmil CU, 1 #1/0 CU GND., IN 2 1/2" C.)

8003E 2 SETS OF (3 - 500 kcmil CU) IN (2) 4" C.)

NO SCALEE5.1

1 ONE-LINE POWER DISTRIBUTION DIAGRAM - DEMO

NO SCALEE5.1

2 ONE-LINE POWER DISTRIBUTION DIAGRAM - NEW

NO SCALEE5.1

3 GROUND ROD IN WELL

SHEET KEYNOTES

1. REPLACE EXISTING MAIN SERVICE METER CENTER WITH 800A MAIN DISTRIBUTION PANEL.

DEMOLISH METERS IN EXISTING MAIN SERVICE PANEL 'MC'. METERS ARE NON-REVENUE

METERS USED FOR INTERNAL ACCOUNTING PURPOSES.

2. GROUNDING ELECTRODE CONDUCTOR CONNECTIONS AND MAIN BONDING JUMPER

EXISTING TO REMAIN AT MAIN BUILDING DISCONNECT.

3. SELECTIVELY COORDINATE TO 0.1 SECONDS FOR ELEVATOR PER SPECIFICATION 26 05 73, ELECTRICAL DISTRIBUTION SYSTEM STUDIES. VERIFY BREAKER TYPE OF CIRCUIT

BREAKER IN THE SQUARE-D MAIN BUILDING SERVICE CIRCUIT BREAKER DISCONNECT FOR

USE IN COORDINATION STUDY. SUBMIT STUDY PRIOR TO OR WITH ELECTRICAL

PANELBOARD / GEAR SUBMITTAL.

4. VERIFY TRANSFER SWITCH IS SET TO TURN EMERGENCY SYSTEM ON WITHIN 60

SECONDS PER NEC 701 FOR ELEVATOR. REVISE SETTINGS IF NOT. ADJUST SETTINGS FOR

SIGNALING ELEVATOR TO PREVENT INTERRUPTION OF POWER DURING ELEVATOR

OPERATION. SET WARMUP TIMER TO DELAY TRANSFER UNTIL GENERATOR POWER IS

FOUND ACCEPTABLE BY ATS FOR FULL LOAD TRANSITION.

5. CONFIRM EXISTING AUTOMATIC TRANSFER SWITCH IS SWITCHED NEUTRAL

CONFIGURATION. ENSURE NEUTRAL TO GROUNDING BONDING JUMPER IS MINIMUM #2/0

CU MINIMUM. PROVIDE OR REPLACE JUMPER IF NOT. IF EXISTING AUTOMATIC TRANSFER

SWITCH IS NOT A SWITCHED NEUTRAL, ENSURE THE NEUTRAL TO GROUND BONDING

JUMPER IS REMOVED FROM GENERATOR. EXISTING UL LABEL TO BE MAINTAINED.

6. PROVIDE NEW GROUNDING ELECTRODE AT EXISTING GENERATOR. SEE DETAIL 3/E5.1.

7. PROVIDE SUB-METERING AT MAIN…