Attach_21_As-Built_Drawings_5_29_25_0002.pdf
PDF 28 MB Posted
- Solicitation number
- 140A1626R0002
About this file
This is a set of as-built record drawings for the Mescalero Adult Detention Center located at 386 Saw Mill Road, Mescalero, New Mexico 88340. The drawings were prepared by Garver, LLC in joint venture with Walga Ross Group and issued for construction on March 31, 2023, with record drawings dated May 29, 2025. The document serves as the official record of the completed facility design and construction, prepared under Project Number 21B00385. The drawings are comprehensive and include architectural, structural, fire protection, plumbing, mechanical, electrical, and interior sheets covering all aspects of the detention center facility.
The complete drawing set comprises over 100 detailed sheets organized by discipline, including architectural general notes and symbols, floor plans (first and second floors), reflected ceiling plans, roof plans, exterior and interior elevations, building sections, wall sections, door and window schedules and details, life safety plans, smoke compartment and inmate relocation plans, fire rating information, structural foundation and framing plans, concrete and steel details, fire alarm and sprinkler system plans, plumbing sanitary sewer and domestic water plans, HVAC zone and sensor plans with ductwork and piping details, electrical lighting and power plans with systems diagrams, and furniture and kitchen equipment plans. The drawings include comprehensive abbreviations and symbology references to ensure clear interpretation of all technical specifications and building systems throughout the detention facility.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Garver, LLC www.GarverUSA.com 501-376-3633 North Little Rock, AR 72118 4701 Northshore Drive
Walga Ross Group JV
Tulsa, OK 74169-0960 P.O. Box 690960
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
ISSUE DATE:
VOLUME:
PROJECT STATUS:
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-001
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: SLB
DRAWN BY: SLB
COVER SHEET
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IC
O
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
BUREAU OF INDIAN AFFAIRS
MESCALERO ADULT DETENTION CENTER
386 SAW MILL ROAD
MESCALERO, NEW MEXICO 88340
PROJECT NUMBER: 21B00385
MAR. 31, 2023
BUILDING CONSTRUCTION (2 OF 2)
ISSUED FOR CONSTRUCTION
ARCHITECTURAL SHEETS
A-001 ARCHITECTURAL GENERAL NOTES, SYMBOLS AND STANDARD DETAILS
A-101 OVERALL FIRST FLOOR PLAN
A-102 DIMENSIONED FIRST FLOOR PLAN - EAST
A-103 DIMENSIONED FIRST FLOOR PLAN - WEST
A-104 SECOND FLOOR PLAN & REFLECTED CEILING PLAN
A-105 FIRST FLOOR REFLECTED CEILING PLAN
A-106 ROOF PLAN
A-201 EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-310 WALL SECTIONS
A-311 WALL SECTIONS
A-312 WALL SECTIONS
A-401 ENLARGED PLANS
A-402 ENLARGED PLANS & SECTIONS
A-403 INTERIOR ELEVATIONS
A-404 INTERIOR ELEVATIONS
A-405 MILLWORK SECTIONS
A-501 SECTION DETAILS
A-502 SECTION DETAILS
A-503 SECTION DETAILS
A-504 DOOR AND WINDOWS DETAILS
A-505 DOOR AND WINDOW DETAILS
A-506 MISCELLANEOUS DETAILS
A-601 DOOR SCHEDULE
A-602 DOOR SCHEDULE AND ELEVATIONS
A-603 WINDOW ELEVATIONS
A-604 ROOM FINISH SCHEDULE
A-605 MATERIAL LEGEND
A-606 FIRST FLOOR SIGNAGE PLAN
GENERAL SHEETS
G-001 COVER SHEET
G-002 DETENTION CENTER RENDERING
G-003 PROJECT ABBREVIATIONS (A - N)
G-004 PROJECT ABBREVIATIONS (Q - Z) AND PROJECT SYMBOLOGY
G-101 FIRST FLOOR LIFE SAFETY PLAN
G-102 SECOND LOOR LIFE SAFETY PLAN
G-103 FIRST FLOOR SMOKE COMPARTMENT/ INMATE RELOCATION PLAN
G-104 SECOND FLOOR SMOKE COMPARTMENT/ INMATE RELOCATION PLAN
G-105 FIRE RATING AND SMOKE COMPARTMENT INFORMATION
G-106 FIRE RATING AND SMOKE COMPARTMENT INFORMATION
STRUCTURAL SHEETS
S-001 STRUCTURAL GENERAL NOTES
S-002 STRUCTURAL GENERAL NOTES
S-003 ROOF WIND UPLIFT DIAGRAM
S-004 ROOF SNOW DRIFT DIAGRAM
S-005 OVERALL ISOMETRIC VIEW
S-101 FOUNDATION PLAN
S-102 LOW ROOF AND SECOND FLOOR FRAMING PLAN
S-103 HIGH ROOF FRAMING
S-104 PARTIAL STAIR FRAMING PLAN
S-301 TYPICAL CONCRETE DETAILS
S-310 CONCRETE DETAILS
S-311 CONCRETE DETAILS
S-401 TYPICAL CONCRETE MASONRY WALL AND LINTEL DETAILS
S-501 TYPICAL STEEL DETAILS
S-510 STEEL DETAILS
S-511 STEEL DETAILS
S-512 STAIR FRAMING DETAILS
FIRE PROTECTION SHEETS
FA001 GENERAL NOTES, SYMBOLS LEGEND, TYPICAL MOUNTING HEIGHTS
FA002 FIRE ALARM LOGIC MATRIX
FA101 FIRST FLOOR FIRE ALARM DEVICE PLAN
FA102 SECOND FLOOR FIRE ALARM DEVICE PLAN
FX101 FIRST FLOOR HAZARD CLASSIFICATION PLAN
FX102 SECOND FLOOR HAZARD CLASSIFICATION PLAN
FX103 FIRST FLOOR SPRINKLER ZONING PLAN
FX104 SECOND FLOOR SPRINKLER ZONING PLAN
FX601 SCHEDULES AND HYDRAULIC INFORMATION
PLUMBING SHEETS
P-001 PLUMBING LEGEND, ABBREVIATIONS AND NOTES
P-101 OVERALL FIRST FLOOR SANITARY SEWER PLAN
P-102 OVERALL SECOND FLOOR SEWER, DOMESTIC WATER & PROPANE GAS PLAN
P-103 OVERALL FIRST FLOOR DOMESTIC WATER & PROPANE GAS PLAN
P-401 ENLARGED SANITARY SEWER PLANS
P-402 ENLARGED SANITARY SEWER PLANS
P-403 ENLARGED DOMESTIC WATER PLANS
P-404 ENLARGED DOMESTIC WATER PLANS
P-405 ENLARGED DOMESTIC WATER PLANS
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
P-602 PLUMBING SCHEDULES
P-603 SANITARY SEWER RISER DIAGRAMS
P-604 SANITARY SEWER RISER DIAGRAMS
P-605 DOMESTIC WATER RISER DIAGRAMS
P-606 DOMESTIC WATER RISER DIAGRAMS
P-607 PROPANE GAS RISER DIAGRAM
MECHANICAL SHEETS
M-001 GENERAL NOTES AND LEGEND
M-101 FIRST FLOOR HVAC ZONE PLAN
M-102 SECOND FLOOR HVAC ZONE PLAN
M-103 FIRST FLOOR HVAC SENSOR PLAN
M-104 SECOND FLOOR HVAC SENSOR PLAN
MH101 FIRST FLOOR HVAC PLAN
MH102 SECOND FLOOR HVAC PLAN
MP101 HYDRONIC PIPING PLAN
MP102 CONDENSATE PIPING PLAN
M-301 SECTION VIEWS
MH401 ENLARGED PLANS
MH402 ENLARGED PLANS
MH403 ENLARGED PLANS
MH404 ENLARGED PLANS
MP401 ENLARGED PIPING PLANS
M-501 DETAILS
M-502 DETAILS
M-601 HVAC SCHEDULES
M-602 HVAC SCHEDULES
M-603 HVAC SCHEDULES
M-604 HVAC SCHEDULES
M-901 HVAC CONTROLS SCHEMATICS AND SEQUENCES OF OPERATION
M-902 HVAC CONTROLS SCHEMATICS
M-903 HVAC CONTROLS POINTS LIST
M-904 DUCTWORK ISOMETRIC DIAGRAM
M-905 HYDRONIC PIPING ISOMETRIC DIAGRAM
ELECTRICAL SHEETS
E-001 ELECTRICAL GENERAL NOTES AND LEGENDS
E-100 ELECTRICAL SITE PLAN
E-101 ELECTRICAL LIGHTING PLAN
E-102 LEVEL 1 - ELECTRICAL POWER PLAN
E-103 LEVEL 2/ROOF - ELECTRICAL POWER PLAN
E-104 ELECTRICAL SYSTEMS PLAN
E-105 ELECTRICAL SYSTEMS PLAN
E-106 LIGHTNING PROTECTION PLAN
E-401 ENLARGED ELECTRICAL PLANS
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
E-602 ELECTRICAL SCHEDULES
E-603 ELECTRICAL DIAGRAMS
E-604 ELECTRICAL DIAGRAMS
INTERIORS SHEETS
I-101 FURNITURE PLAN
KITCHEN SHEETS
K-101 KITCHEN EQUIPMENT PLAN
PROJECT SITE
NEW MEXICO
NTS
PROJECT AREA
NTS
PROJECT LIMITS OF
CONSTRUCTION
PROJECT SITE
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-002
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JCF
DRAWN BY: SLB
DETENTION CENTER
RENDERING
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
AMPERES
ABOVE COUNTER
AIR CONDITIONER (ING)
AIR CONDITIONING UNIT
ANCHOR BOLT
ABOVE
ALTERNATING CURRENT
ACCESSIBLE, AIR-COOLED CHILLER
AIR-COOLED CONDENSING UNIT
AMERICAN CONCRETE INSTITUTE
ACRYLIC PLASTIC
ACCESS CONTROL SYSTEM
ACCESS DOOR
ACCESS PANEL
ALUMINUM CABLE STEEL REINFORCED
ACOUSTIC(AL)
ACOUSTICAL CEILING TILE
AIR CONDITIONING UNIT
AREA DRAIN
ADDITIONAL
ADDENDUM
ADHESIVE
ADJACENT, ADJOINING, ADJUSTABLE
AUTOMATIC DOOR OPERATOR
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AGGREGATE
ANCHOR
AIR HANDLING UNIT
AREA INLET
AMPERE INTERRUPTING CAPACITY
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AMERICAN IRON AND STEEL INSTITUTE
ACTIVE LEAF
ALTERNATE
ALUMINUM
AMPERES METER
AMBIENT
AMPERE(S)
ANNUNCIATOR
ANODIZE
AMERICAN NATIONAL STANDARDS INSTITUTE
ACCESS PANEL, AERIAL PRIMARY
AIR PRESSURE DROP
APPROVED
APPROXIMATE(LY)
ANCHOR ROD(S)
ARCHITECT(URAL)
AMERICAN REFRIGERATION INSTITUTE
AERIAL SECONDARY
ASBESTOS
ABOVE SUSPENDED CEILING
AMERICAN SOCIETY OF CIVIL ENGINEERS
AMERICAN SOCIETY OF HEATING, REFRIGERATING &
ENGINEERS
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPHALT
AMERICAN SOCIETY FOR TESTING AND MATERIALS
ACOUSTICAL TILE
ACOUSTICAL TILE CEILING
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AVERAGE
AMERICAN WIRE GAUGE
ACOUSTICAL WALL TREATMENT
AMERICAN WATER WORKS ASSOCIATION
BULLETIN BOARD
BOOKCASE
BOARD, BACKDRAFT DAMPER
BOUNDARY
BRICK EXPANSION JOINT
BEVEL
BELOW FINISHED FLOOR
BACKFLOW PREVENTER
BLOWN FUSE INDICATOR
BOILER FEED WATER
BYPASS ISOLATION
BITUMINOUS
BED JOINT
BREAKER
BUILDING LINE
BUILDING
BLOCK(S)
BLOCKING
BELOW
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CUBIC FEET PER SECOND
CORNER GUARD
PVC COATED GALVANIZED RIGID STEEL
COAT HOOK
CHALKBOARD
CHANNEL
CHAMFER
CHIMNEY
CHECK
CHILLED WATER RETURN
CHROME PLATED
CHILLED WATER SUPPLY
CAST IRON, CURB INLET
CAST-IN-PLACE, CAST IRON PIPE
CIRCULAR, CIRCULATING
CONSTRUCTION JOINT
COMPLETE JOINT PENETRATION
CIRCUIT
CIRCUIT BREAKER
CENTER LINE
CEILING
CEILING HEIGHT
CLEAR GLASS
CLOCK
CAULKING
CONTRACT LIMIT LINE
CLEANING
CLOSET
CLOSURE
CLEAR(ANCE), COLOR
CLEAR WIRED GLASS
CENTIMETER(S)
CORRUGATED METAL PIPE
COMPOSITE
CONCRETE MASONRY UNIT(S)
CONDUIT
CONDUCTIVE NEOPRENE LATEX
CORNER
COUNTER
CLEANOUT
CARBON DIOXIDE
COLUMN(S)
COMMON
COMBUSTION
COMPARTMENT
CONCRETE
CONNECT, CONNECTION(S)
CONSTRUCTION
CONTINUE, CONTINUOUS(LY)
CONTRACTOR, CONTRACTION
CORRIDOR
CLEANOUT TO GRADE
COVER
CONTROL PANEL
COMPRESSIBLE
CARPET, CONTROL POWER TRANSFORMER
CHLORINATED POLYVINYL CHLORIDE
CONTROL RELAY
CIRCUMFERENCE
CORROSIVE RESISTANT STEEL
CROSS GRAIN
COLOR RENDERING INDEX
COURSE(S)
CONCRETE REINFORCING STEEL INSTITUTE
CAST STONE, CORD SET
COUNTERSUNK
CASEMENT
CENTER-TO-CENTER
CERAMIC TILE, CURRENT TRANSFORMER
COATING
CENTER
CENTERED
COEFFICIENT OF UTILIZATION, CONDENSING UNIT
CU FT
CUH
CU YD
CV
CVH
CW
CYL
d
DAT
DB
dB
DBA
DBL
DBL ACT DR
DCJ
DCJT
DDC
DEB
DEG
DEMO
DEPR
DEPT
DET
DF
DH
DIA
DIAG
DIM
DIP
DISC
DISP
DISTR PNL
DIV
DL
DMPF
DMPR
DMT
DN
DR
DRB
DR CL
DS
DT
DVTL
DWG
DWLS
DWR
DWTR
DWV
DX
EFD
EG
EJ
EL
ELAST
ELEC
ELEV
ENG
EM
EMD
EMER
EMT
ENCL
ENTR
EP
EPRF
EPY
EQ
EQUIP
ES
ESCAL
ESP
EST
ETM
EVTR
EWB
EWC
EWH
EWT
EXC
EXH
EXH A
EXST
EXP
EXP BT
EXT
F/ F
FA
FAC
FACP
FAI
F BRK
FBO
FC
FC BRK
FCG
FCJ
FCO
FCU
FD
FDMPR
FDN
FDS
FDTN
FE
FEB
FEC
FED
FDC
FF
FFE
FG
FGL
FH
FHC
FHMS
FHR
FHS
FHWS
FIG
FIN
FIN FLR
FIXT
FJT
FLA
FLASH
FLR
FLEX
FLG
FLR PL
FLUOR
FN
FOB
FOC
FOF
FOM
FOS
FOT
FP
FPM
FR
FRG
FRMG
FRT
FS
FSTNR
FT
FTG
FUR
FURN
FURG
FUT
FVNR
FVR
FW
FWC
A
ABC
A/C
A/C UNIT
AB
ABV
AC
ACC
ACCU
ACI
ACR
ACS
ACS DR
ACS PNL
ACSR
ACST
ACT
ACU
AD
ADDL
ADDM
ADH
ADJ
ADO
AFF
AFG
AGGR
AHR
AHU
AI
AIC
AISC
AISI
A.L.
ALT
ALUM
AM
AMB
AMP
ANN
ANOD
ANSI
AP
APD
APPD
APPROX
AR
ARCH
ARI
AS
ASB
ASC
ASCE
ASHRAE
ASME
ASPH
ASTM
AT
ATC
ATS
AUTO
AUX
AVG
AWG
AWT
AWW
BB
BC
BD
BDRY
BEJ
BEV
BFF
BFP
BFI
BFW
BI
BITUM
BJT
BKR
BL
BLDG
BLK
BLKG
BLW
CFH
CFM
CFS
CG
CGRS
CH
CH BD
CHAN
CHFR
CHIM
CHK
CHR
CHR PL
CHS
CI
CIP
CIRC
CJ
CJP
CKT
CKT BRKR
CL
CLG
CLG HT
CLGL
CLK
CLKG
CLL
CLNG
CLO
CLOS
CLR
CLWG
cm
CMP
CMPST
CMU
CND
CNL
CNR
CNTR
CO
CO2
COL
COM
COMB
COMPT
CONC
CONN
CONSTR
CONT
CONTR
CORR
COTG
COV
CP
CPRS
CPT
CPVC
CR
CRCMF
CRES
CRG
CRI
CRS
CRSI
CS
CSK
CSMT
C TO C
CT
CTG
CTR
CTRD
CU
CUBIC FEET
CABINET UNIT HEATER
CUBIC YARDS
CEILING VENT
CONDUCTIVE VINYL HOMOGENEOUS (SHEET TYPE)
DOMESTIC COLD WATER
CYLINDER
PENNY (AS IN NAIL - 10d)
DATUM
DRY BULB
DECIBLE
DOWEL BAR ANCHOR, DEFORMED BAR ANCHOR
DOUBLE
DOUBLE ACTING DOOR
DOWELED CONTROL JOINT
DUMMY CONTROL JOINT
DIRECT DIGITAL CONTROL(S)
DIRECT EARTH BURIED
DEGREE
DEMOLITION
DEPRESSION
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DOUBLE HUNG, DUCT HEATER
DIAMETER
DIAGONAL, DIAGRAM
DIMENSION(S)
DUCTILE IRON PIPE
DISCONNECT
DISPENSER
DISTRIBUTION PANEL
DIVISION
DEAD LOAD
DAMPPROOFING
DAMPER
DEMOUNTABLE
DOWN
DOOR, DRAIN
DRAINBOARD
DOOR CLOSER
DOUBLE STRENGTH (GLASS), DOWNSPOUT
DRAIN TILE
DOVETAIL
DRAWING(S)
DOWEL(S)
DRAWER
DUMBWAITER
DRAIN WASTE AND VENT
DIRECT EXPANSION
EXISTING FLOOR DRAIN
EQUIPMENT GROUND, EXISTING GRADE
EXPANSION JOINT
ELEVATION (GRADE OR BUILDING), EMERGENCY LIGHT
ELASTOMERIC
ELECTRIC(AL)
ELEVATOR, ELEVATION (DRAWING VIEW)
ENGINEER(ED)
EXPANDED METAL
ESTIMATED MAXIMUM DEMAND
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSE(URE)
ENTRANCE, ENTERING
ELECTRICAL PANELBOARD
EXPLOSION PROOF
EPOXY COATING
EQUAL
EQUIPMENT
EQUALLY SPACE(D)
ESCALATOR
EXTERNAL STATIC PRESSURE
ESTIMATE(D)
ELAPSED TIME METER
EXISTING VENT THROUGH ROOF
ENTERING WET BULB
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ENTERING WATER TEMPERATURE
EXCAVATE
EXHAUST
EXHAUST AIR
EXISTING
EXPANSION, EXPOSED
EXPANSION BOLT
EXTERIOR
FACE OF
FLOWLINE
FIRE ALARM, FRESH AIR
FIRE APPARATUS CLOSET
FIRE ALARM CONTROL PANEL
FRESH AIR INTAKE
FIRE BRICK
FURNISHED BY OTHERS
FAN COIL, FOOT CANDLE
FACE BRICK
FACING
FLOOR CONSTRUCTION JOINT
FLOOR CLEANOUT
FAN COIL UNIT
FLOOR DRAIN, FRENCH DRAIN
FIRE DAMPER
FOUND
FUSED DISCONNECT SWITCH
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
FEDERAL
FIRE DEPARTMENT CONNECTION
FACTORY FINISH
FINISHED FLOOR ELEVATION
FINISHED GRADE
FIBERGLASS
FIRE HYDRANT, FLAT HEAD
FIRE HOSE CABINET
FLAT HEAD MACHINE SCREW
FIRE HOSE RACK
FIRE HOSE STATION
FLAT HEAD WOOD SCREW
FIGURE
FINAL, FINISH(ED) (ES)
FINISHED FLOOR
FIXTURE
FLUSH JOINT
FULL LOAD AMPERES
FLASHING
FLOOR
FLEXIBLE
FLOORING
FLOOR PLATE
FLUORESCENT
FENCE
FACE-OF-BRICK, FLAT-ON-BOTTOM
FACE-OF-CONCRETE, FIBER OPTIC CABLE
FACE-OF-FINISH
FACE-OF-MASONRY
FACE-OF-STUD
FLAT-ON-TOP
FIRE PARTITION, FIREPROOF
FEET PER MINUTE
FIRE RESISTANT, FRAME
FORGED
FRAMING
FIRE-RETARDANT
FAR SIDE, FLOOR SINK, FOOTING STEP, FULL SIZE,
FASTEN(ER)
FEET
FOOTING(S), FORWARD TEST CONNECTION
FURNACE
FURNITURE
FURRING
FUTURE
FULL VOLTAGE NON-REVERSING STARTER
FULL VOLTAGE REVERSING STARTER
FIRE WATER
FABRIC WALL COVERING
FES FLARED-END SECTION
ASPHALT CONCRETE HOT MIXACHM
AND
AT
DIAMETER, PHASE
POUNDS
DEGREES CELSIUS
DEGREES FAHRENHEIT
Ø °C °F
SYMBOLS
A
B
C (continued)
COPPERCu
E (continued)
F
G (continued)
FLOAT SWITCHBEAM, BENCHMARK
BOTTOM-OF
BOTTOM-OF-DUCT
BOTTOM-OF-FOOTING
BOTTOM-OF-PIPE
BOTTOM-OF-STRUCTURE
BOTTOM
BASE-OF-WALL
BEDROOM
BRACING
BRIDGING
BEARING
BEARING PLATE
BRICK
BRACKET
BRONZE
BOTH SIDES
BASEMENT
BRITISH THERMAL UNIT
BTU PER HOUR
BETWEEN
BUILT-UP
BUILT-UP ROOFING
BOTH WAYS
BM
BO
BOD
BOF
BOP
BOS
BOT
BOW
BR
BRCG
BRDG
BRG
BRG PL
BRK
BRKT
BRZ
BS
BSMT
Btu BtuH
BTWN
BU
BUR
BW
C
CHANNEL, CONDUIT
CABINET
CAPACITY
CATCH BASIN, CIRCUIT BREAKER
CRACK CONTROL JOINT
CUBICLE CURTAIN TRACK
CLOSED CIRCUIT TELEVISION
COVER ELEVATION
CEMENT
CEMENT PLASTER
CERAMIC
CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CONDUCTIVE FLOORING
C
CAB
CAP
CB
CCJ
CCT
CCTV
CE
CEM
CEM PLAS
CER
CF/CI
CFI
D
E E
EA
EAT
EBC
EC
ECC
ECM
EDB
EF
EAST
EACH, EXHAUST AIR
ENTERING AIR TEMPERATURE
EXTENDED BOTTOM CHORD
EMPTY OR EMBEDDED CONDUIT
ECCENTRIC
ELECTRONICALLY COMMUTATED MOTOR
ENTERING DRY BULB
EACH FACE, EXHAUST FAN
G
GWB
GWT
GYP
GYP BD
GYP PLAS
H
HB
HC
HCD
HCP
HD
HDBD
HD JT
HDR
HDW
HDWD
HES
HEX
HH
HK
HM
HNDRL
HOA
HORIZ
HP
HPT
HR
HS
HSD
HSGYP
HSKPG
HSS
HSTAT
HT
HTG
HTR
HVAC
HW
HWR
HYD
HYDR
Hz
IBC
IC
ID
IE
IESNA
IG
ILK
IN
IN WC
INCIN
INCL
GYPSUM WALLBOARD
GLAZED WALL TILE
GYPSUM
GYPSUM BOARD
GYPSUM PLASTER
HEIGHT
HOSE BIBB
HOLLOW CORE
HALON CONTAINMENT DAMPER
HANDICAPPED
HEAD, HEAVY DUTY, HUB DRAIN
HARDBOARD
HEAD JOINT
HEADER
HARDWARE
HARDWOOD
HIGH EARLY-STRENGTH CEMENT
HEXAGON
HANDHOLE
HOOK(S)
HOLLOW METAL
HANDRAIL
HAND-OFF-AUTOMATIC
HORIZONTAL(LY)
HEAT PUMP, HIGH PRESSURE, HORSEPOWER
HIGH POINT
HOUR
HIGH-STRENGTH
HEADED STUD
HIGH-STRENGTH GYPSUM PLASTER
HOUSEKEEPING
HOLLOW STEEL SECTION
HUMIDISTAT
HEIGHT
HEATING
HEATER
HEATING, VENTILATION, AND AIR-CONDITIONING
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
HYDRANT
HYDRAULIC
HERTZ
INTERNATIONAL BUILDING CODE
INTERCOM
INSIDE DIAMETER
INVERT ELEVATION
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA
ISOLATED GROUND
INTERLOCK
INCH(ES)
INCHES OF WATER COLUMN
INCINERATOR
INCLUDED
GSU
GT
GLAZED STRUCTURAL UNITS
GREASE TRAP, GROUT
GRADE LINE
GALVANIZED RIGID STEEL
GRATING
GLAZED STRUCTURAL TILE
GR LN
GRS
GRTG
GST
H
I
GPF
GPH
GPM
GPT
GR
GRAN
GR BM
GALLONS PER FLUSH
GALLONS PER HOUR
GALLONS PER MINUTE
GYPSUM TILE
GRADE
GRANITE
GRADE BEAM
G
GA
GAL
GALV
GALV STL
GB
GC
GEN
GF
GF/CI
GF/GI
GFCI
GFE
GFE/CI
GFI
GI
GIP
GKT
GL
GL BLK
GLF
GLZ
GLZ CMU
GND
GOVT
NATURAL GAS
GAGE, GAUGE
GALLON(S)
GALVANIZED
GALVANIZED STEEL
GRAB BAR, GYPSUM WALLBOARD
GAS COCK, GENERAL CONTRACTOR
GENERAL
GROUND FACE
GOVERNMENT FURNISHED/CONTRACTOR INSTALLED
GOVERNMENT FURNISHED/GOVERNMENT INSTALLED
GROUND FAULT CIRCUIT INTERRUPTER
GOVERNMENT-FURNISHED EQUIPMENT
GOVERNMENT-FURNISHED EQUIPMENT CONTRACTOR
GROUND FAULT INTERRUPTER
GALVANIZED IRON
GALVANIZED IRON PIPE
GASKET(ED)
GLASS
GLASS BLOCK
GLASS FIBER
GLAZING
GLAZED CONCRETE MASONRY UNITS
GROUND
GOVERNMENT
INSTALLED
INSF
INSUL
INT
INTM
INV
IP
IPS
I.P.S.
ISP
INSULATING FILL
INSULATE (D) (ION)
INTERIOR
INTERMEDIATE
INVERT
IRON PIPE
IRON PIPE SIZE
INSIDE PIPE SIZE
INDIVIDUALLY SHIELDED PAIR
J
LLF
LM
LMST
LNTL
LO
LONG
LOR
LP
LPD
LPL
LRA
LPT
LR
LS
LSI
LSIG
LT
LT WT
LTG
LTNG
LV
LVR
LWB
LWC
LWT
m M&B
MACH
LIGHT LOSS FACTOR
LUMEN
LIMESTONE
LINTEL
LUGS ONLY
LONGITUDINAL
LOCAL-OFF-REMOTE
LIGHTPROOF, LOW PRESSURE
LIGHTPROOF DOOR
LIGHTPROOF LOUVER
LOCKED ROTOR AMPERES
LOW POINT
LIVING ROOM
LAWN SPRINKLER, LUMP SUM
LONG, SHORT, INSTANTANEOUS
LONG, SHORT, INSTANTANEOUS, GROUND
LIGHT
LIGHTWEIGHT
LIGHTING
LIGHTNING
LOW VOLTAGE
LOUVE (R) (D)
LEAVING WET BULB
LIGHTWEIGHT CONCRETE
LEAVING WET TEMPERATURE
METER(S)
MATCHED AND BEADED
MACHINE
L
M
LIN
LKR
LL
J-BOX
JAN CLO
JB
JBE
JCT
JST
JT
K
KIP
KIT
KO
KOBB
KOP
KPL
kV kVA kVAR kW kWH
KWY
L
LA
LAB
LAD
LAM
LAT
LAU
LAV
LB
LBL
LBR
LC
LD
LDB
LDG
LDH
LDO
LDV
LF
LG
LH
JUNCTION BOX
JANITOR’S CLOSET
JUNCTION BOX
JOIST BEARING ELEVATION
JUNCTION
JOIST(S)
JOINT(S)
KIP(S) (1,000 POUNDS)
KILOPOUND(S) (1,000 POUNDS)
KITCHEN
KNOCK-OUT
KNOCK-OUT BOND BEAM
KNOCK-OUT PANEL
KICKPLATE
KILOVOLTS
KILOVOLT AMPERES
KILOVOLT AMPERES REACTIVE
KILOWATT
KILOWATT HOUR
KEYWAY
ANGLE, LENGTH
LIGHTNING ARRESTER
LABORATORY
LADDER
LAMINATE
LEAVING AIR TEMPERATURE
LAUNDRY
LAVATORY
LAG BOLT, POUND(S)
LABEL
LUMBER
LIGHT CONTROL, LIGHTING CONTACTOR
LOAD
LEAVING DRY BULB
LOADING
LONG-DIMENSION HORIZONTAL
LONG-DIMENSION OUTSTANDING
LONG-DIMENSION VERTICAL
LINEAR FEET (FOOT)
LENGTH, LONG
LEFT HAND(ED)
LINEAR
LOCKER
LIVE LOAD
K
L
(continued)
NFPA
Ni
NIC
NL
N.L.
NM
NO
NOM
NR
NRC
NREQD
NS
NSG
NTS
MAINT
MAS
MATL
MAX
MB
MBH
MBMA
MBR
MBTU
MC
MCA
MCB
MCC
MCJ
MCO
MCP
MD
MDP
MDS
MECH
MECH RM
MED
MEMB
MES
MET
MEZZ
MFD
MFG
MFR
MFRD
MG
MGT
MH
MI
MIN
MIRR
MISC
MK
ML
MLDG
MLO
MLWK
mm
MN
MNIC
MO
MOCP
MOD
MON
MOT
MP
MPH
MR
MRB
MRD
MS
MT
MTD
MTFR
MTL
MTS
MVBL
MULL
MWP
N N/A
NAT
NC
MAINTENANCE
MASONRY
MATERIAL(S)
MAXIMUM
MACHINE BOLTS
THOUSAND BTU PER HOUR
METAL BUILDING MANUFACTURERS ASSOCIATION
MEMBER
THOUSAND BTU PER HOUR
MEDICINE CABINET
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MASONRY CONTROL JOINT
METAL-CASED OPENING
MOTOR CIRCUIT PROTECTOR
MOTORIZED DAMPER
MAIN DISTRIBUTION PANEL
METAL DIVIDER STRIP
MECHANICAL
MECHANICAL ROOM
MEDIUM
MEMBRANE
METAL EDGE STRIP
METAL
MEZZANINE
METAL FLOOR DECKING
MANUFACTURING
MANUFACTURER
MANUFACTURED
MIRROR GLASS, MOTOR GENERATOR
MATTE-GLAZED TILE
MANHOLE, METAL HALIDE
MALLEABLE IRON
MINIMUM
MIRROR
MISCELLANEOUS
MARK
METAL LATH, MONOLITHIC
MOULDING
MAIN LUGS ONLY
MILLWORK
MILLIMETER(S)
MASS NOTIFICATION
MATERIAL NOT IN CONTRACT (INSTALLATION BY
MASONRY OPENING(S)
MAXIMUM OVER CURRENT PROTECTION
MODULAR, MODIFIED
MONACO
MOTOR
MOVABLE PARTITION
MILES PER HOUR
MOP RECEPTOR
MARBLE BASE
METAL ROOF DECKING
MACHINE SCREWS, MOTOR STARTER
METAL THRESHOLD, MOUNT
MOUNTED
METAL FURRING
METAL
MANUAL TRANSFER SWITCH
MOVABLE
MULLION
MEMBRANE WATERPROOFING
NEUTRAL, NORTH
NOT APPLICABLE
NATURAL
NOISE CRITERIA, NON-CORROSIVE, NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
NICKEL
NOT-IN-CONTRACT
NAILABLE, NIGHT LIGHT
NEOPRENE LATEX
NONMETALLIC
NORMALLY OPEN, NUMBER
NOMINAL
NOISE REDUCTION
NOISE REDUCTION COEFFICIENT
NOT REQUIRED
NEAR SIDE
NON-SHRINK GROUT
NOT-TO-SCALE
NFDS NON-FUSED DISCONNECT SWITCH
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEC NATIONAL ELECTRICAL CODE
NEMA
CONTRACTOR)
N
LLD LEAD-LINED DOORGPD GALLONS PER DAYEFCO EXISTING FLOOR CLEANOUTCOUNTERFLASHINGCFLG
BACK PLASTER(ED), BASE PLATEBP
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-003
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: SLB
DRAWN BY: SLB
PROJECT
ABBREVIATIONS
(A - N)
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
PTD
PTN
PTR
PTT
PTZ
PV
PVC
PVG
PVMT
PW
OFC
OF/CI
OFF
OGL
OH
OHE
OHMS
OHP
OHS
OHWS
OJ
OL
OPH
OPNG
OPP
OPQ
OPS
OR
OS&Y
OSHA
OWGL
OZ
P
PA
PAR
PARA
PB
PBD
PBS
PC
PCC
PCF
PCP
PCT
PD
PEC
PED
PEMB
PERF
PERIM
PF
PFCC
PH
PHAR
PI
PIPU
PIV
PJP
PL
PLAM
PLAS
PLAT
PLBG
PLF
PLG
PL GL
PLYWD
PMR
PNL
PNT
POL
PORC
PORT
PPGL
PPM
PR
PREFAB
PREFIN
PREFMD
PRELIM
PRKG
PROJ
PRV
PS
P.S.
PS CONC
PSF
PSI
OFFICE
OWNER FURNISHED/CONTRACTOR INSTALLED
OFFICE
OBSCURE GLASS
OVERHEAD
OVERHEAD ELECTRIC
OVAL-HEAD MACHINE SCREW
OVERHEAD PRIMARY
OVERHEAD SECONDARY
OVAL-HEAD WOOD SCREW
OPEN-WEB JOIST
OVERLOAD
OPPOSITE HAND
OPENING
OPPOSITE
OPAQUE
OPERATIONS
OUTSIDE RADIUS
OUTSIDE SCREW AND YOKE
OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
OBSCURE WIRED GLASS
OUNCE(S)
PIPE, POLE
PUBLIC ADDRESS
PARALLEL
PARAGRAPH
PANIC BAR, PUSH BUTTON
PARTICLE BOARD
PUSH BUTTON STATION
PIECE
PRECAST CONCRETE, PORTLAND CEMENT CONCRETE
POUNDS PER CUBIC FOOT
CEMENT PLASTER (PORTLAND)
PERCENT
PAVEMENT DRAIN, PRESSURE DROP
PHOTO ELECTRIC CELL
PEDESTAL
PRE-ENGINEERED METAL BUILDING
PERFORATE(D)
PERIMETER
POWER FACTOR
POWER FACTOR CORRECTION CAPACITOR
PHASE
PHARMACY
POINT OF INTERSECTION
PREFAB ISOLATION POWER UNIT
POST INDICATING VALVE
PARTIAL JOINT PENETRATION
PILOT LIGHT, PLACE, PLATE(S), PROPERTY LINE
PLASTIC LAMINATE
PLASTER
PLATFORM
PLUMBING
POUNDS PER LINEAR FOOT
PILING
PLATE GLASS
PLYWOOD
PHASE MONITOR RELAY
PANEL(S)
PAINT(ED)
POLISHED
PORCELAIN
PORTABLE
POLISHED PLATE GLASS
PARTS PER MILLION
PAIR
PREFABRICATE(D)
PREFINISHED
PREFORMED
PRELIMINARY
PARKING
PROJECT(ION)
PRESSURE-REGULATING VALVE
PIPE SPACE
PRESSED STEEL
PRESTRESSED CONCRETE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PAPER TOWEL DISPENSER
PARTITION
PAPER TOWEL RECEPTACLE
PUSH-TO-TEST
PAN-TILT-ZOOM
PAVED
POLYVINYL CHLORIDE, (ELECTRICAL ONLY SCHEDULE 40
PAVING
PAVEMENT
PASS WINDOW
POST-TENSIONED CONCRETE
PNEUMATIC TUBE, POINT
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH ABSOLUTE
PT CONC
PT
PSIG
PSIA
PE POLYETHYLENE
O T (continued)
OSB ORIENTED STRAND BOARD
POLYVINYL CHLORIDE)
OA
OBD
OBSC
OBW
OC
OCEW
OD
OUTSIDE AIR
OPPOSED BLADE DAMPER
OBSCURE
OBSERVATION WINDOW
ON-CENTER
ON-CENTER EACH WAY
OUTSIDE DIAMETER, OUTSIDE DIMENSION
P
SND
SNTD
SOV
SP
SPC
SPCL
SPD
SPEC
SPF
SP FIN
SPH
SPKR
SQ
SQHD
S&R
SS
SSL
SSM
SST
ST
STA
STC
STD
STF
STG
STL
STOR
ST PR
STR
STRUCT
STS
STWY
SUB FL
SURF
SUSP
SV
SW
SWBD
SYMM
SYNTH
SYS
T T/ T&B T&G
TAN
TB
TC
TCX
TD
TDD
TDE
TEL
TEMP
TER
TERM
TGB
TGL
TH
THD
THK
THRD
THRES
THRU
TK BD
TKS
TM
TMGB
TOB
TOC
TOD
TOF
TOL
TOM
TOPO
TOS
TOW
TP
TPD
TPTN
TR
TRANS
TSP
TSTAT
TTD
TV
TVB
TWCOTG
TYP
U/F U/G
UGP
UGS
UGT
UH
ULUNEX
UV
VVA
VAC
VAR
VAV
VB
VCT
VD
VENT
VERT
VEST
VF
VFD
VG
VH
VJ
VM
VNR
VOL
VPCT
VR
VRM
VS
VT
VTR
VWC
WW/
W/C W/O W/W
WAINS
WAP
WB
WBL
WC
WCO
WD
WDSP
WDW
WF
WGL
WH
WHB
WHM
WI
WIFS
WKSH
WM
WMP
WP
WPD
WR
WRB
WS
W.S.
WSCT
WT
WTH
WTR
WWR
SANITARY NAPKIN DISPENSER
SANITARY NAPKIN AND TAMPON DISPOSER
SHUT OFF VALVE
SPACE(S), STATIC PRESSURE, SOUTHERN PINE
SPACER
SPECIAL
SOUNDPROOF DOOR, SURGE PROTECTIVE DEVICE
SPECIFICATION(S)
SOUNDPROOF
SPECIAL FINISH
SPACE HEATER
SPEAKER
SQUARE
SQUARE HEAD
SHELF AND ROD
SANITARY SEWER, SERVICE SINK
SHORT-SLOTTED HOLE
STANDING SEAM METAL ROOF
STAINLESS STEEL
SOUND TRAP, STEAM TRAP
STATION
SOUND TRANSMISSION CLASS
STANDARD
STIFFENER
SEATING
STEEL
STORAGE
STATIC PRESSURE
STRINGER
STRUCTURAL
STORM SEWER
STAIRWAY
SUBFLOOR
SURFACE
SUSPEND(ED)
SHEET VINYL
SWITCH, SIDEWALK
SWITCHBOARD
SYMMETRICAL
SYNTHETIC
SYSTEM
TANGENT, TELEPHONE, TILE, TOILET, TOP, TREAD
TOP OF
TOP-AND-BOTTOM
TONGUE-AND-GROOVE
TANGENT
TOWEL BAR
TERRA COTTA, TIME CLOCK, TOP-OF-CURB
TOP CHORD EXTENSION
TILE DRAIN, TIME DELAY
TIME DELAY ON DE-ENERGIZATION
TIME DELAY ON ENERGIZATION
TELEPHONE
TEMPERATURE, TEMPERED, TEMPORARY
TERRAZZO
TERMINAL
TELECOMMUNICATIONS GROUND BAR
TOGGLE
TRUSS HEAD
TOTAL HARMONIC DISTORTION
THICK(NESS)
THREAD(ED)
THRESHOLD
THROUGH
TACKBOARD
TACKSTRIP
TOP-OF-MASONRY
TELECOMMUNICATIONS MAIN GROUND BAR
TOP-OF-BEAM
TOP-OF-CONCRETE
TOP-OF-DUCT
TOP-OF-FOOTING
TOLERANCE
TOP-OF-MASONRY
TOPOGRAPHY
TOP-OF-SLAB, TOP-OF-STEEL, TOP-OF-STONE
TOP-OF-WALL
TOP-OF-PARAPET, TOTAL PRESSURE
TOILET PAPER DISPENSER
TOILET PARTITION
TAMPER RESISTANT
TRANSOM, TRANSVERSE
TOTAL STATIC PRESSURE
THERMOSTAT
TOILET TISSUE DISPENSER
TELEVISION
TELEVISION BRACKET
TWO-WAY CLEANOUT TO GRADE
TYPICAL
UNDER FLOOR
UNDERGROUND
UNDERGROUND PRIMARY
UNDERGROUND SECONDARY
UNDERGROUND TELEPHONE
UNIT HEATER
UNDERWRITERS LABORATORIESUNEXCAVATED
UNIT VENTILATOR
VENT, VOLT
VOLT-AMPERE
VACUUM
VARNISH
VARIABLE AIR VOLUME
VINYL BASE
VINYL COMPOSITION TILE, VITRIFIED CLAY TILE
VAULT DOOR, VOLUME DAMPER
VENTILAT (ING) (ION) (OR)
VERTICAL (LY)
VESTIBULE
VINYL FABRIC
VARIABLE FREQUENCY DRIVE
VERTICAL GRAIN
VINYL HOMOGENEOUS
V-JOINT(ED)
VOLT-METER
VENEER
VOLUME
VAULTED PARALLEL CHORD TRUSS
VAPOR RETARDER
VERMICULITE
VENT STACK
VOLTAGE TRANSFORMER
VENT THROUGH ROOF
VINYL WALL COVERING
WATER, WATT, WEST, WIDTH, WIRE
WITH
WHEELCHAIR
WITHOUT
WALL-TO-WALL
WAINSCOT
WIRELESS ACCESS POINT
WET BULB
WOOD BLOCKING
WATER CLOSET, WATER COLUMN
WALL CLEANOUT, WOOD-CASED OPENING
WINDOW DIMENSION, WOOD, WOOD DOOR
WASTE DISPOSER
WINDOW
WIDE FLANGE
WIRED GLASS
WALL HUNG, WATER HEATER, WEATHER HEAD
WHEEL BUMPER
WATT-HOUR METER
WROUGHT IRON
WALL INSULATION & FINISH SYSTEM(S)
WORK SHOP
WATT METER, WIRE MESH
WIRE MESH PARTITION
WATERPROOF(ING), WEATHERPROOF, WORKING POINT
WATER PRESSURE DROP
WASTE RECEPTACLE
WARDROBE
WATERSTOP
WASTE STACK
WAINSCOT
WATERTIGHT, WEIGHT
WIDTH
WATER
WELDED-WIRE-REINFORCEMENT
UTP UNSHIELDED TWISTED PAIR
SY SQUARE YARD
UTIL UTILITY
UR URINAL
UNINTERRUPTIBLE POWER SUPPLY
UNO UNLESS NOTED OTHERWISE
UPS
SN
SMS SHEET METAL SCREWS
SM SHEET METAL
SLV SLEEVE
SOLID NEUTRAL
UNFIN UNFINISHED
SA
SAN
SB
SC
SCH
SCHED
SCR
SCRN
SCT
SD
SDBC
SDI
SE
SECT
SEP
SERV
SEQ
SF
SFGL
SFTU
SFU
SG
SGR
SGS
SH
SHLDR
SHT
SHTHG
SHV
SIM
SJI
SK
SKLT
SUPPLY AIR, SURGE ARRESTER
SANITARY
SECURITY BARS, SPLASH BLOCK
SHOWER CURTAIN, SOLID CORE, SLIP-CRITICAL (PER AISC)
SCHEDULE
SCHEDULE
SHOWER CURTAIN RAIL
SCREEN
STRUCTURAL CLAY TILE
SMOKE DAMPER, SOAP DISPENSER, STORM DRAIN
SOFT DRAWN BARE COPPER
STEEL DOOR INSTITUTE
SERVICE ENTRANCE
SECTION
SEPERATE
SERVICE
SEQUENCE
SQUARE FEET (FOOT)
SAFETY GLASS
STRUCTURAL FACING TILE UNIT
STRUCTURAL FACING UNIT
SEMI-GLOSS, SHEET GLASS
SOAP AND GRAB BAR COMBINATION (RECESSED)
SOAP AND GRAB BAR COMBINATION (SURFACE)
SOAP HOLDER
SHOULDER
SHEET
SHEATHING
SHELF, SHELVES, SHELVING
SIMILAR
STEEL JOIST INSTITUTE
SHEAR KEY
SKYLIGHT
SLNT SEALANT
S
S SECOND, SOUTH
T
V V
W
W
XFMR
X
YD
Y
TRANSFORMER
YARD, YARD DRAIN
REQD
RESIL
RET
REV
RFG
RH
RHG
RL
RK
RLA
RLG
RM
RND
RO
ROW
RP
RPM
RPRT
RPZ
RS
RTF
RVAT
RVS
RVT
RWC
REQUIRED
RESILIENT
RETAIN (ING), RETURN
REVISION
ROOFING
RELATIVE HUMIDITY, RIGHT HAND, ROBE HOOK,
ROOF HATCH, ROUND HEAD, ROUND HOLE
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
RACK
RUNNING LOAD AMPERES
RAILING
ROOM(S)
ROUND
ROUGH OPENING
RIGHT-OF-WAY
RETRACTABLE PARTITION
REVOLUTIONS PER MINUTE
RAISED PATTERN RUBBER TILE
REDUCED PRESSURE ZONE BACKFLOW PREVENTER
REFRIGERANT SUCTION
RUBBER TILE FLOOR
REDUCED VOLTAGE AUTO-TRANSFORMER STARTER
REVERSE
RIVET
RAINWATER CONDUCTOR
TMB TELECOMMUNICATIONS MOUNTING BOARD
UGE UNDERGROUND ELECTRICAL
Q
QT
QTR
1/4 RND
QTY
RA
RAB
RA GR
RAR
RB
RBL
RBR
RC
RCP
RCVR
RD
RDG INS
REBAR
RECIRC
RECPT
REC ROOM
RECT
REF
REFL
REFR
REG
REINF
REM
QUARRY TILE, QUART
QUARTER
QUARTER ROUND
QUANTITY
RADIUS, RANGE, RISER
RETURN AIR
RABBETED
RETURN AIR GRILLE
RETURN AIR REGISTER
RUBBER BASE, RESILIENT BASE
RUBBLE STONE
RUBBER
REMOTE CONTROL
REFLECTED CEILING PLAN, REINFORCED CONCRETE PIPE
RECEIVER
ROOF DRAIN
RIGID INSULATION
REINFORCING BAR
RECIRCULATE
RECEPTACLE
RECREATION ROOM
RECTIFIER
REFER, REFERENCE
REFLECT
REFRIGERATION
REGISTER, REGLET, REGULATOR
REINFORCE (ING) (MENT)
REMOVE(ABLE)
RCB REINFORCED CONCRETE BOX
R
R
R (continued)
U
TW TOP-OF-WALL
SHEET REFERENCE NUMBER
WHERE VIEW IS DRAWN
VIEW IDENTIFIER
AREA OF ENLARGEMENT
A-101 A1
A-101 A1
A-101 A1
SHEET REFERENCE NUMBER
WHERE VIEW IS DRAWN
VIEW DIRECTION
VIEW IDENTIFIER
SHEET REFERENCE NUMBER
WHERE VIEW IS DRAWN
VIEW DIRECTION
VIEW IDENTIFIER
VIEW MODIFIER
VIEW IDENTIFIER
TYP
REFERENCING VIEWS
EXTERIOR ELEVATION CUTENLARGED PLAN CALLOUT
INTERIOR ELEVATION CUTSECTION CUT
REFERENCED VIEWS
DETAIL TITLE, PLAN TITLE
SYMBOLS
PLAN
NORTH
NORTH ARROW
PLAN NORTH
TRUE NORTH
BAR SCALE
0 16'4' 8'
SCALE: 1/8" = 1'-0"
DIMENSIONS
(UNITS VARIES)
REPRESENTATIVE
FRACTION
UNREFERENCED VIEWS
A1
TITLE
SCALE
VIEW SCALE
VIEW TITLE
VIEW IDENTIFIER
ENLARGED PLAN TITLE, SECTION TITLE, EXTERIOR
ELEVATION TITLE, INTERIOR ELEVATION TITLE
A1
TITLE
SCALE
VIEW SCALE
VIEW TITLE
VIEW IDENTIFIER
A-101
SHEET REFERENCE NUMBER
WHERE VIEW IS DRAWN
VIEW IDENTIFIER
VIEW DIRECTION
A1
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-004
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: SLB
DRAWN BY: SLB
PROJECT
ABBREVIATIONS
(Q - Z) AND PROJECT
SYMBOLOGY
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
UP
FEMALE OUTDOOR
RECREATION AREA
MALE OUTDOOR
RECREATION AREA
020304
81' (<200')
77'-8" (<200')
103' - 4" (<200')
82' (<200')
76' (<200')
148' (<200')
120' (<200')
111' (<200')
111' (<200')
69 SF
VESTIBULE
OCC120 SF
DOUBLE CELL (ONE
ADA)
164 1
OCC98 SF
CELL
165 1
OCC40 SF
ADA SHOWER
168 0
OCC109 SF
CELL
167 1
OCC320 SF
MALE DAYROOM
166 3
OCC52 SF
SHWR/TLT
142 0
OCC41 SF
TOILET
143 0
OCC53 SF
ADA SHWR/TLT
144 0
OCC53 SF
ADA SHWR/TLT
145 0
OCC34 SF
SHOWER
146 0
OCC116 SF
CELL
159 1
OCC62 SF
ADA SHWR/TLT
150 0
OCC40 SF
ADA SHWR
151 0
OCC56 SF
TOILET
152 0
OCC783 SF
KITCHEN
125 7
OCC81 SF
OFFICE
126 1
225 SF
RECEIVING
OCC62 SF
ADA TOILET
123 0
OCC415 SF
LAUNDRY
121 4
OCC
128 SF
JANITOR / CHEM.
STORAGE
OCC143 SF
UTILITY
120 2
OCC59 SF
MEDICAL STORAGE
133 1
OCC
274 SF
VIDEO
OCC
69 SF
INTERVIEW
101 SF
CORRIDOR
46 SF
VESTIBULE
410 SF
CORRIDOR
115 SF
CORRIDOR
OCC
140 SF
SUPERVISOR
OCC78 SF
ADA TOILET
111 0
OCC303 SF
CONFERENCE
110 3
OCC268 SF
ADMIN/SUPPORT
109 3
OCC
212 SF
BREAK
OCC102 SF
VESTIBULE
101 1
OCC
92 SF
RECEPTION
OCC53 SF
SCREENING
106 1
OCC87 SF
NC VIS
104 1
OCC102 SF
NC VIS
105 1 OCC45 SF
ADA TOILET
103 0
OCC217 SF
LOBBY
102 2
OCC186 SF
ELECTRICAL
191 2
OCC414 SF
MECHANICAL
189 4
OCC76 SF
ADA MEDIUM
HOLDING F
183 1
OCC76 SF
SPECIAL MNGT
CHANGING
184 1
66 SF
VESTIBULE
OCC299 SF
PROCESSING
182 3
OCC76 SF
ADA MEDIUM
HOLDING M
179 1
OCC238 SF
GRP HOLDING M
172 2
OCC122 SF
GRP HOLDING M
175 2
OCC121 SF
GRP HOLDING M
174 2
OCC47 SF
JANITOR
149 1
OCC
36 SF
JANITOR
OCC1460 SF
SALLYPORT
188 13
OCC
99 SF
IT
OCC54 SF
ADA TOILET
132 0
OCC138 SF
STORAGE
119 2
754 SF
CORRIDOR
OCC156 SF
STORAGE
128 3
OCC
191 SF
MEDICAL
TREATMENT
2 OCC
188 SF
FILING
OCC
69 SF
COPY
OCC
166 SF
GRP HOLDING F
OCC
134 SF
CLOTHING &
PROPERTY
CHASE
183A
OCC
117 SF
INDIVIDUAL
HOLDING F
OCC76 SF
SPECIAL MNGT
CHANGING
178 1
OCC
314 SF
RESOURCE /
MULTI-PURPOSE
224 SF
VESTIBULE
OCC120 SF
DOUBLE CELL (ONE
ADA)
160 1
OCC488 SF
FEMALE DAYROOM
156 5
OCC42 SF
ADA SHOWER
158 0
OCC224 SF
GROUP THERAPY
136 2
46 SF
VESTIBULE
591 SF
CORRIDOR
65 SF
VESTIBULE
167 SF
VESTIBULE
OCC1336 SF
MALE DAYROOM
147 12
OCC34 SF
JAN.
171 1
OCC1013 SF
FEMALE DAYROOM
153 9
OCC1078 SF
INDOOR
RECREATION
148 9
OCC42 SF
ADA SHOWER
157 0
224 SF
CORRIDOR
154 SF
CORRIDOR
91 SF
SERVICE
139A
CHASE
167A
CHASE
164A
11 SF
CHASE
160A
CHASE
174A
OCC792 SF
CENTRAL CONTROL
163 8
OCC68 SF
ADA TOILET
161 0
OCC149 SF
DRY STO.
124 2
55 SF
SERVICE
157A
28 SF
SERVICE
168A
OCC161 SF
ELECTRICAL
162 1
52 SF
SERVICE
121A
126 SF
SERVICE
140A
CHASE
178A
OCC
116 SF
INDIVIDUAL
HOLDING M
OCC68 SF
SHWR/TLT
177 0
730 SF
CORRIDOR
AREA OF REFUGE PER NFPA 5000 (21.3.7.1.2 (3))
MIN REQUIRED AREA = 40 PEOPLE X 15 SF = 600 SF
ACTUAL PROVIDED: 600 SF
AREA OF REFUGE PER NFPA 5000 (21.3.7.1.2 (3))
MIN REQUIRED AREA = 18 PEOPLE X 15 SF = 270 SF
ACTUAL PROVIDED: 300 SF
128'<250'
EXIT NUMBER
TRAVEL DISTANCE
AND ALLOWANCE
EXIT DISCHARGE PATH
FEC FIRE EXTINGUISHER / CABINET
1-HR RATED WALL
SMOKE COMPARTMENT
BOUNDARY
SEE SHEET G-103/104 FOR SMOKE
COMPARTMENT / INMATE RELOCATION PLAN
FEB FIRE EXTINGUISHER / BRACKET
SMOKE COMPARTMENT
CEILING; REFER TO G-105
BUILDING CODE INVESTIGATION
PRIMARY APPLICABLE CODES:
2021 NFPA 5000: BUILDING CONSTRUCTION AND SAFETY CODE
2011 JUSTICE/DETENTION FACILITIES DESIGN HANDBOOK
2020 NATIONAL ELECTRICAL CODE
2004 AMERICANS WITH DISABILTIES ACT AND ARCHITECTURAL BARRIERS ACT ACCESIBILITY GUIDELINES
2021 UNIFORM PLUMBING CODE
2021 UNIFORM MECHANICAL CODE
2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS
BIA MESCALERO DETENTION FACILITY - MESCALERO, NEW MEXICO
GENERAL:
THIS PROJECT IS FOR THE CONSTRUCTION OF A NEW MESCALERO ADULT DETENTION CENTER.
SPECIAL INSPECTIONS:
TBD (NFPA 5000, CHAPTER 40)
OCCUPANCY CLASSIFCATION:
DETENTION AND CORRECTIONAL (NFPA 5000, 6.1.7.1)
OCCUPANCY SEPARATION:
MIXED USE - NO FIRE SEPARATION
REQUIRED
(NFPA 5000, 7.4.1.2.1)
TYPE OF CONSTRUCTION:
TYPE II (000) UNPROTECTED (NFPA 5000, TABLE 7.2.1.1)
SPRINKLERED (NFPA 5000, 21.3.5.2)
ALLOWABLE HEIGHT:
ALLOWABLE 75 FEET (NFPA 5000 TABLE 7.4.1)
ACTUAL 28 FEET
ALLOWABLE STORIES:
ALLOWED 2 STORIES (NFPA 5000 TABLE 7.4.1)
ACTUAL 2 STORIES
ALLOWABLE BUILDING AREA:
ALLOWED 10,000 SF/FLOOR (NFPA 5000 TABLE 7.4.1 FOR D&C OCCUPANCY)
WITH SPRINKLER 20,000 SF/FLOOR (NFPA 5000, 7.6.2.2, 200% SPRINKLER INCREASE)
WITH FRONTAGE 7,500 SF/FLOOR (NFPA 5000, 7.6.2.1, 75% FRONTAGE INCREASE)
TOTAL ALLOWED 27,500 SF/FLOOR (55,000 SF/TWO FLOORS)
ACTUAL 22,262 SF MAIN FLOOR
1,631 SF SECOND FLOOR
TOTAL
ACTUAL 23,893 SF/TWO FLOORS
FIRE SEPARATION:
MIXED USE - NO FIRE SEPARATION
REQUIRED
(NFPA 5000, 7.4.1.2.1)
OCCUPANT LOAD: (NFPA 5000, TABLE 11.3.1.2)
DETENTION AND CORRECTIONAL 200 OCCUPANTS (23,893 SF/120 SF/PERSON)
TOTAL OCCUPANT LOAD 200 OCCUPANTS
MEANS OF EGRESS:
NUMBER OF EXITS
REQUIRED 2 EXITS FIRST FLOOR (NFPA 5000, 11.4.1.1)
1 EXIT SECOND FLOOR (NFPA 5000, 11.4.1.1, EXCEPTION (2))
PROVIDED 6 EXITS FIRST FLOOR
1 EXIT SECOND FLOOR
COMMON PATH OF EGRESS TRAVEL
ALLOWED 100' MAXIMUM (NFPA 5000, 21.2.5.2)
ACTUAL VARIES (LESS THAN 30')
EXIT ACCESS TRAVEL DISTANCE:
ALLOWED 200 FT (NFPA 5000, 21.2.6.3)
ACTUAL LESS THAN 160 FT
DEAD END CORRIDOR:
ALLOWED 50 FEET, CONDITION II-IV (NFPA 5000, 21.2.5.3)
20 FEET, CONDITION V (NFPA 5000, 21.2.5.3)
ACTUAL 25 FEET (MAX.)
EXIT LOAD:
200 OCCUPANTS/6 EXITS PROVIDED: 34 OCCUPANTS PER EXIT
EXIT CORRIDORS:
MINIMUM WIDTH 48 INCHES (NFPA 5000, 21.2.3.2)
PROVIDED WIDTH 60 INCHES MINIMUM
STAIRWAY ENCLOSURE FIRE
RESISTANCE RATING:
NA (NFPA 5000, 8.12.2)
EXIT CORRIDOR FIRE RESISTANCE
RATING :
NA (NFPA 21.3.8)
EXIT DOORS:
MINIMUM CLEAR WIDTH PER DOOR 32 INCHES (NFPA 5000, 11.2.1.2.3.2)
PROVIDED WIDTH PER DOOR 34 INCHES (MIN)
TOTAL PROVIDED WIDTH (6 EXITS) 208 INCHES (MIN)
USE CONDITION IV – IMPEDED EGRESS (NFPA 5000, 21.1.2.1.4)
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-101
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JSR
DRAWN BY: AMB
FIRST FLOOR LIFE
SAFETY PLAN
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/8" = 1'-0"F7
FIRST FLOOR LIFE SAFETY PLAN
BAR SCALES & NORTH ARROW
PLAN
NORTH
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
LIFE SAFETY SYMBOL LEGEND
FEC
FEC
(TYPE K)
FEC
FEC
FEC
FEB
FEB
FEB
NO CEILING
REFER TO G-102
7/
/2
A
S I-
JC
F
2/
4/
A S
I-
JC
F
DN
128'<250'
EXIT NUMBER
TRAVEL DISTANCE
AND ALLOWANCE
EXIT DISCHARGE PATH
FEC FIRE EXTINGUISHER / CABINET
1-HR RATED WALL
SMOKE COMPARTMENT
BOUNDARY
SEE SHEET G-103/104 FOR SMOKE
COMPARTMENT / INMATE RELOCATION PLAN
FEB FIRE EXTINGUISHER / BRACKET
SMOKE COMPARTMENT
CEILING; REFER TO G-105
OCC1239 SF
DORM
201 11
105' - 6" (<200')
OPEN TO INDOOR
RECREATION ROOM BELOW
NO CEILING, EXPOSED
TO STRUCTURE
REFER G-105
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-102
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JSR
DRAWN BY: AMB
SECOND LOOR LIFE
SAFETY PLAN
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
BAR SCALES & NORTH ARROW
PLAN
NORTH
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
LIFE SAFETY SYMBOL LEGEND
1/8" = 1'-0"F9
SECOND FLOOR LIFE SAFETY PLAN
7/
/2
A
S I-
1 2 4 7 8 9
A
B
H
J
E
D
C
F
G
DOUBLE CELL
(ONE ADA)
CELL
CELL
MALE DAYROOM
SHWR/TLT
CELL
KITCHEN
RECEIVING
ADA TOILET
LAUNDRY
JANITOR / CHEM.
STORAGE
VIDEO
INTERVIEW
CORRIDOR
VESTIBULE
CORRIDOR
CORRIDOR
CONFERENCE
ADMIN/SUPPORT
BREAK
VESTIBULE
RECEPTION
SCREENING
ADA TOILET
LOBBY
ELECTRICAL
MECHANICAL
SPECIAL MNGT
CHANGING
PROCESSING
ADA MEDIUM
HOLDING M
GRP HOLDING M
GRP HOLDING M
GRP HOLDING M
SALLYPORT
IT
STORAGE
CORRIDOR
STORAGE
COPY
GRP HOLDING F
CLOTHING &
PROPERTY
INDIVIDUAL
HOLDING F
SPECIAL MNGT
CHANGING
RESOURCE /
MULTI-PURPOSE
DOUBLE CELL
(ONE ADA)
FEMALE
DAYROOM
GROUP THERAPY
VESTIBULE
CORRIDOR
VESTIBULE
VESTIBULE
MALE DAYROOM
FEMALE
DAYROOM
CORRIDOR
INDOOR
RECREATION
CORRIDOR
DRY STO.
SC-1
SC-2
SC-2
SUPERVISOR
ADA TOILET
SERVICE
121A
OFFICE
ELECTRICAL
ADA TOILET
CENTRAL
CONTROL
VESTIBULE
VESTIBULE
INDIVIDUAL
HOLDING M
ADA MEDIUM
HOLDING F
NC VIS
NC VIS
ADA TOILET
UTILITY
STORAGE
MEDICAL
STORAGE
SERVICE
157A TOILET
MEDICAL
TREATMENT
FILING
NON-INMATE AREAS
47' (<50')
148' (<200')
64' (>50')
130' (<150'), 148' (<200')
42' (<50')
30' (<50')
0' (<50')
0' (<50')
55' (>50')
SC-2
74' (<150'), 92' (<200')
26' (<150')
60' (<150'), 78' (<200')
SC-3
SC-2
AREA OF REFUGE PER NFPA 5000 (21.3.7.1.2 (3))
MIN REQUIRED AREA = 18 PEOPLE X 15 SF = 270 SF
ACTUAL PROVIDED: 300 SF
B.8
NON-INMATE AREAS
INMATE AREAS
AREA OF REFUGE PER NFPA 5000 (21.3.7.1.2 (3))
MIN REQUIRED AREA = 40 PEOPLE X 15 SF = 600 SF
ACTUAL PROVIDED: 600 SF
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-103
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JCF
DRAWN BY: JCF
FIRST FLOOR SMOKE
COMPARTMENT/
INMATE RELOCATION
PLAN
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
BAR SCALES & NORTH ARROW
PLAN
NORTH
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NFPA 5000 NOTES
SMOKE CONTROL SYSTEMS: NOT REQUIRED
FOR THIS FACILITY (TABLE 21.3.8). USE
CONDITION IV (USE CONDITION IV IS THAT
USE CONDITION FOR WHICH FREE MOVEMENT
IS RESTRICTED FROM AN OCCUPIED SPACE,
AND FOR WHICH REMOTE-CONTROLLED
RELEASE IS PROVIDED TO ALLOW MOVEMENT
FROM ALL SLEEPING ROOMS, ACTIVITY
SPACES, AND OTHER OCCUPIED AREAS
WITHIN THE SMOKE COMPARTMENT TO
ANOTHER SMOKE COMPARTMENT).
SLEEPING ROOM SEPARATIONS (TABLE
21.3.8): SMOKE RATING REQUIRED BETWEEN
SLEEPING ROOM AND COMMON SPACE ONLY
WHERE THE TRAVEL DISTANCE FROM THE
SLEEPING ROOM THRU THE COMMON SPACE
TO AN EXIT ACCESS CORRIDOR EXCEEDS 50
FT.
1/8" = 1'-0"D1
FIRST FLOOR SMOKE COMPARTMENT/INMATE RELOCATION PLAN
1.
2.
ADDITIONAL SMOKE COMPARTMENTS: 21.3.7.1,
21.3.7.2: EACH FLOOR USED FOR SLEEPING
MUST BE SEPARATED INTO AT LEAST 2
SMOKE COMPARTMENTS. TRAVEL DISTANCE
TO OTHER SMOKE COMPARTMENT MAY NOT
EXCEED 150 FT DOOR-T0-DOOR OR 200 FT
ANY POINT-TO-DOOR.
MINIMUM SIZE OF ADDITIONAL SMOKE
COMPARTMENT FROM 21.3.7.1 (21.3.7.5): 6 SF
MINIMUM PER OCCUPANT REQUIRED. 6
SF/OCC X 48 OCC = 288 SF MINIMUM.
MEDICAL STORAGE 133: TABLE 23.3.2.1
REQUIRES SMOKE RATING FOR STORAGE
ROOMS BETWEEN 50 AND 100 SF SIZE.
3.
4.
5.
2/
4/
A S
I-
2 4
H
J
E
D
C
F
G
DORM
SC-1
OPEN TO INDOOR
RECREATION ROOM BELOW
B.8
© 2022 GARVER, LLC
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-104
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JCF
DRAWN BY: JCF
SECOND FLOOR
SMOKE
COMPARTMENT/
INMATE RELOCATION
PLAN
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
1/8" = 1'-0"D7
SECOND FLOOR SMOKE COMPARTMENT/INMATE RELOCATION PLAN
BAR SCALES & NORTH ARROW
PLAN
NORTH
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-105
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JSR
DRAWN BY: AMB
FIRE RATING AND
SMOKE
COMPARTMENT
INFORMATION
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
UL REFERENCES FOR FIRE RATED AND/OR SMOKE BARRIER CONSTRUCTION
(UL REFERENCES ARE REPRINTED IN THEIR ENTIRETY;
REPRINTED FROM PRODUCT IQ WITH PERMISSION FROM UL SOLUTIONS)
7/
/2
A
S I-
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
DRAWING NUMBER
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
WALGA ROSS GROUP
PO BOX 690960
TULSA, OK 74169-0960
R E
V D
A T
E D
E S
C R
IP
T
IO
N
B Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
T
U
V
M A
Y
9, R E
C O
R D
D R
A W
IN
G
S A
S -B
U
IL
T S
G-106
JOB NO.: 21B00385
DATE: MAR. 31, 2023
DESIGNED BY: JSR
DRAWN BY: AMB
FIRE RATING AND
SMOKE
COMPARTMENT
INFORMATION
B U
R E
A U
O F
IN
D
IA
N
A F
F A
IR
S
M E
S C
A
LE
R O
A D
U
LT
D E
T E
N T
IO
N
C E
N T
E R
S A
W M
IL
L
R O
A D
M E
S C
A
LE
R O
N
E W
M E
X
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
UL REFERENCES FOR FIRE RATED AND/OR SMOKE BARRIER CONSTRUCTION
(UL REFERENCES ARE REPRINTED IN THEIR ENTIRETY;
REPRINTED FROM PRODUCT IQ WITH PERMISSION FROM UL SOLUTIONS)
GENERAL NOTES
1. UL U906 MEETS BOTH FIRE RATING AND SMOKE BARRIER
REQUIREMENTS FOR WALLS.
2. UL HW-D-0022 MEETS FIRE RATING REQUIREMENTS FOR THE
INTERSECTION OF WALLS AND ROOF OR FLOOR.
3. UL W-J 8005 MEETS BOTH FIRE RATING AND SMOKE BARRIER
REQUIREMENTS FOR WALL PIPE PENETRATIONS.
4. UL C-AJ-7034 MEETS BOTH FIRE RATING AND SMOKE BARRIER
REQUIREMENTS FOR DUCT PENETRATIONS.
5. SMOKE BARRIERS/SMOKE COMPARTMENTS: AREAS DESIGNATED AS
SMOKE COMPARTMENTS SHALL BE CONSTRUCTION IN ACCORDANCE
WITH THE REQUIREMENTS OF NFPA 5000, 8.11, EXCERPTS BELOW:
8.11 Smoke Barriers
8.11.2 Continuity
8.11.2.3 A smoke barrier required for an occupied space below an interstitial space shall not be required to extend through the interstitial space, provided that the construction assembly forming the bottom of the interstitial space provides resistance to the passage of smoke equal to that provided by the smoke barrier.
8.11.4.4 * Doors in smoke barriers, shall be self-closing or automatic-closing in accordance with 11.2.1.8 and shall comply with the provisions of 11.2.1.
8.11.5.2 Through-penetrations for cables, cable trays, conduits, pipes, tubes, vents, wires, and similar items to accommodate electrical, mechanical, plumbing, and communications systems that pass through a wall, floor, or floor/ceiling assembly constructed as a smoke barrier, or through the ceiling membrane of the roof/ceiling of a smoke barrier, shall be protected by a listed system tested in accordance with the requirements of UL 1479, Fire Tests of Penetration Firestops, for air leakage and shall comply with one of the following:
(1) A maximum 5 ft3 min per ft2 (0.025 m3/s per m2) of penetration opening for each through-penetration firestop system
(2) A maximum total cumulative leakage of 50 ft3 min (0.024 m3/s) for any 100 ft2 (9.3 m2) of wall area or floor area
8.11.7.2 Joints made within, between, or at the perimeter of smoke barriers shall be protected with a listed joint system that is tested in accordance with the requirements of UL 2079, Tests for Fire Resistance of Building Joint Systems, for air leakage and the L rating of the joint system shall not exceed 5 ft3/min per ft (0.00775 m3/s per m) of the joint.
6. MEMBRANE PENETRATIONS: ELECTRICAL BOXES (4” X 4” OR
SMALLER) OR OTHER ITEMS RECESSED IN ONE SIDE OF A CMU WALL
DESIGNED AS A 1-HOUR FIRE BARRIER OR SMOKE BARRIER SHALL
BE FULLY GROUTED IN PLACE TO MEET THE REQUIREMENTS OF
NFPA 5000, 8.8.7, EXCERPTS BELOW:
8.8.7 Membrane Penetrations
8.8.7.3 Where walls or partitions are required to have a fire resistance rating of not less than 1 hour, recessed fixtures shall be installed in the wall or partition in such a manner that the required fire resistance is not reduced, unless one of the following criteria is met:
(1) Any steel electrical box not exceeding 16 in.2 (10,300 mm2) in area shall be permitted where the aggregate area of the openings provided for the boxes does not exceed 100 in.2 (64,520 mm2) in any 100 ft2 (9.3 m2) of wall area, and, where outlet boxes are installed on opposite sides of the wall, the boxes shall be separated by one of the following means:
(a) Horizontal distance of not less than 24 in. (610 mm)
(b) Horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose-fill, rock wool, or slag wool insulation
(c) Solid fireblocking in accordance with 8.14.2
(d) Other listed materials and methods
(2) Membrane penetrations for any listed electrical outlet box made of any material shall be permitted, provided that such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
(3) The annular space created by the membrane penetration of a fire sprinkler shall be permitted, provided that the space is covered by a metal escutcheon plate.
(4) Membrane penetrations by electrical boxes of any size or type, which have been listed as part of a wall opening protective material system for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing, shall be permitted.
7/
/2
A
S I-
1. IN CASE OF A CONFLICT BETWEEN THE GENERAL NOTES AND THE SPECIFICATIONS, CONSULT THE
STRUCTURAL ENGINEER FOR CLARIFICATION PRIOR TO WORK.
2. VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. THE STRUCTURAL ENGINEER SHALL
BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.
3. DO NOT SCALE DRAWINGS.
4. NOTES AND DETAILS ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THESE GENERAL NOTES
AND THE TYPICAL DETAILS.
5. INSPECT THE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FOUNDATION, UTILITIES, ETC. IF ANY UNKNOWN ITEMS ARE FOUND AND ALTER THE STRUCTURAL DRAWINGS, THE
STRUCTURAL ENGINEER SHALL BE NOTIFIED IMMEDIATELY.
6. SEE MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
A. PIPES, SLEEVES, HANGERS, TRENCHES, OPENINGS IN FLOORING, PUMPS, AND VALVES, ETC
EXCEPT AS SHOWN OR NOTED.
B. ELECTRICAL CONDUIT RUNS, BOXES, AND OUTLETS IN WALLS AND SLABS.
C. CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL, OR PLUMBING FIXTURES. SIZE AND
LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR CONNECTIONS TO SLABS.
7. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THE
METHOD OF CONSTRUCTION IS NOT INDICATED.
8. PROVIDE ADEQUATE SHORING OR BRACING WHERE STRUCTURE HAS NOT YET OBTAINED FINAL
DESIGN STRENGTH REQUIRED.
GENERAL NOTES
1. GENERAL BUILDING CODES (LATEST EDITION UNO):
A. 2021 NFPA 5000 BUILDING CONSTRUCTION AND SAFETY CODE
B. 2016 AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) / STRUCTURAL ENGINEERING INSTITUTE
(SEI) MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES (ASCE/SEI 7-16)
2. STRUCTURAL CONCRETE CODES (LATEST EDITION UNO):
A. 2019 AMERICAN CONCRETE INSTITUTE (ACI) BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318-19)
B. 2010 AMERICAN CONCRETE INSTITUTE SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR
BUILDINGS (ACI 301-10)
3. STRUCTURAL STEEL CODES (LATEST EDITION UNO):
A. 2016 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS (AISC 360-16)
B. 2016 AMERICAN IRON AND STEEL INSTITUTE (AISI-S100)
C. 2011 AMERICAN WELDING SOCIETY (AWS) STRUCTURAL WELDING CODE (D1.4)
4. STRUCTURAL MASONRY CODES (LATEST EDITION UNO):
A. 2013 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-13)
B. 2013 SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1-13)
PRIMARY CODES AND SPECIFICATIONS
1. DEAD LOADS (IN ADDITION TO STRUCTURE SELF-WEIGHT)
A. ROOF (TYP)
A. ROOFING SYSTEM. . . . . . . . . . . . . . 5 PSF
B. MECHANICAL . . . . . . . . . . . . . . . 7 PSF
C. CEILINGS. . . . . . . . . . . . . . . . . 3 PSF
B. ROOF ABOVE MECHANICAL ROOMS
A. ROOFING SYSTEM. . . . . . . . . . . . . . 5 PSF
B. MECHANICAL. . . . . . . . . . . . . . . . 25 PSF
C. CEILING.. . . . . . . . . . . . . . . . . 3 PSF
2. LIVE LOADS
A. ROOF. . . . . . . . . . . . . . . . . . . 20 PSF (UNREDUCIBLE)
B. FLOOR LIVE LOAD . . . . . . . . . . . . . . 100 PSF (UNREDUCIBLE)
3. SNOW LOAD DATA:
A. GROUND SNOW LOAD, Pg. . . . . . . . . . . . . 16 PSF B. FLAT-ROOF SNOW LOAD, Pf . . . . . . . . . . . 12.3 PSF C.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .