This is a technical drawing (D-60-022) showing the CO2 gas system diagram for the National Bureau of Standards Reactor (NBSR) at the National Institute of Standards and Technology's Reactor Radiation Division in Gaithersburg, Maryland. The drawing was originally created in 1968 and has undergone multiple revisions, with the latest revision occurring in July 2023.
The diagram details a complex CO2 gas system that includes a 4,043-gallon reactor vessel, an 800-gallon reserve tank, and various components such as controlled valves, pressure relief valves, pressure regulators, check valves, ball valves, diaphragm valves, gate valves, rotameters, and pressure gauges. The system features multiple flow paths, including connections to a Flexo Rabbit System (B-200), thermal shield, and irradiated air lines. Key pressure settings are specified, including 25 psig, 30 psig, and water column measurements of 5" and 8-9". The drawing includes detailed pipe sizing information and an embedded CO2 circular header with six nozzles.
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(4043 GAL.)
VESSEL
REACTOR
(800 GAL.)
RESERVE TANK
INNER
HOLDER
CO2 GAS
B-2
B-1 PROCESS
ROOM
C-100
FLEXO RABBIT
SYSTEM (B-200)
SET AT
25 psig
SET AT
30 psig
COV
COV
COV
COV
SET AT
8" TO 9"
WATER
SET AT
5" WATER
LI
LA
TO IRRADIATED AIR
4" LINE
TO RABBIT SYSTEM
AT BLOWER SUCTION
TO RABBIT SYSTEM
AT BLOWER DISCHARGE
TO IRRADIATED AIR
4" LINE
PNEUMATIC
RELIEF
THERMAL SHIELD
3"Ø
2"Ø
1/2"Ø
2"Ø
3/4"Ø 3/4"Ø
1"Ø
1 1/4"Ø
1/2"Ø
2"Ø
1/ 2"
Ø
EMBEDED CO 2
CIRCULAR HEADER
WITH SIX NOZZLES
C ELE. 442'-8"L
1" Ø
F L O W
TO CRYO. PURGE
1/ 2"
Ø
2"Ø
W O L F
1/
4" Ø
1/2"Ø
3/4"Ø
3/4"Ø
COV
3/4"Ø
W O L F
LEGEND:
CONTROLLED VALVE
PRESSURE RELIEF
PRESSURE REGULATOR
CHECK VALVE
BALL VALVE
DIAPHRAM VALVE
GATE VALVE
VALVE
ROTAMETER
PRESSURE GAUGE
BULK
TANK
1"Ø1"Ø
TO DWG 5937-M-3101, P-100A
TO DWG 5937-M-3101, P-100B
TO DWG 5937-M-3201, P-101A
TO DWG 5937-M-3201, P-101B
4"Ø
FLOWMETERS
(ROTAMETER
OMEGA
FL-4AA-05C-05C-05C-05C)
AN
3-28
PG
PIC
LT
LS
LS
3/4"Ø
4"Ø
COV
A B C D
LA
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
34 COV
COV
COV
COV
1 COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
COV
8 11
D-60-022
NATIONAL INSTITUTE OF STANDARDS & TECHNOLOGY
REACTOR RADIATION DIVISION
GAITHERSBURG, MARYLAND 20899
CO GAS SYSTEM
NBSR
DESIGNED BY:
DATE:
CHECKED BY:
DATE:
APPROVED BY:
DRAWN BY:
DATE:
DATE: 01/07/68
H. A. JACKSON
DIMENSIONS IN FEET AND INCHES DO NOT SCALE THIS DRAWING
DIV. 856
REACTOR ENGINEERING GROUP
ISSUE DATE:
DRAWING NO.
ORIGINAL DATE OF DRAWING
REVISIONS
NO. E.C.N. CHANGE INCORP. BY CHKD. BY APPR. BY DATE
JIM TORRENCE
01/08/69
01/08/69
6 REDRAWN ON CAD MAS PJL NB 09/10/96
7 NEW CO2 TANK PJL523 DF PJL 08/29/08
8 REMOVED OLD CO2 TANK (3/22/11)523 PJL
ADDED TEE & VALVE TO FLOW METER723
DF PJL 06/19/12
ADDED CONNECTION FOR THERMAL
SHIELD PUMP SEAL FLUSH SYSTEM9819 JJT TN PJL 04/25/2017
CHANGED AND REPLACED TEXT TO
CREATE TEXT SEARCHABLE PDF.N/A10 JJT PJL RLS 04/12/2020
INSTALLATION OF CO2 ISOLATION VALVE
COV-8126011 MSZ AWM PJL 07/12/2023