This is an Asbestos Survey Report prepared by Terracon Consultants, Inc. for the City of Olathe, Kansas, dated November 10, 2025, covering the property at 2003 East Santa Fe Street in Olathe, Kansas (Terracon Project No. 02237230). The survey was conducted on October 17, 2025, by Katie Burnham, a State of Kansas-accredited asbestos inspector, and examined the Smoker's Heaven, Metro by T-Mobile, and Project 10/20 spaces within an approximately 2,240 square-foot commercial building constructed in 1979. The survey included visual assessment of interior and exterior areas, physical assessment of friability, and collection of 109 bulk samples from 35 homogeneous areas of suspect asbestos-containing materials (ACM). Samples were analyzed by Eurofins International Asbestos Testing Laboratories using polarized light microscopy (PLM) with dispersion staining techniques in accordance with USEPA Method 600/R-93/116 and AHERA protocols. The survey assessed materials including ceiling tiles, gypsum wallboard with joint compound, mastics behind cove bases, sheet vinyl flooring with adhesives, ceramic tile with mastic and grout, interior and exterior caulks, carpet glue, and roofing materials and sealants.
The critical finding of this survey is that asbestos was not detected at any concentration in any of the 109 samples collected from the subject building. All laboratory analytical results returned negative for asbestos constituents across all homogeneous areas examined. The report notes that the survey was conducted in visually accessible areas only and did not include destructive activities such as equipment dismantling, sampling of confined spaces, materials in movable equipment, or insulation within doors. Terracon's assessment complies with the regulatory framework established by the USEPA NESHAP regulation (40 CFR Part 61, Subpart M) and the Kansas Department of Health and Environment's adoption of this standard through Kansas Administrative Regulations (K.A.R.) 28-19-735. The report explicitly states that results are valid only for the date of the survey and should not be relied upon to represent conditions at a later date, and that contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation.
View the file
Other files
Show 40 more
Latest 50 of 54 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facilities | Environmental | Geotechnical | Materials I
City of Olathe Public Improvements Asbestos Survey Smoker's Heaven, Metro by T Mobile, Project 10/20 2003 East Santa Fe Street
Olathe, Kansas 66062
November 10, 2025 | Terracon Project Number: 02237230
Prepared for:
City of Olathe Kansas 100 East Santa Fe Street Olathe, KS 66061
15620 W 113th Street
Lenexa, KS 66219
P (913) 492-7777
F (913) 492-7443
Terracon.com
Facilities | Environmental | Geotechnical | Materials i
November 10, 2025
City of Olathe, Kansas 100 East Santa Fe Street Olathe, KS 66061
Attn: Ms. Therese Vink P: (913) 971-9032
E: tmersmann@olatheks.org
Re: City of Olathe Public Improvements Asbestos Survey
Smoker's Heaven, Metro by T Mobile, Project 10/20 2003 East Santa Fe Street Olathe, KS 66062 Terracon Project No: 02237230
Dear Ms. Vink:
Terracon Consultants, Inc. (Terracon) is pleased to provide the City of Olathe, Kansas, with this report regarding an asbestos survey conducted at the above-referenced location in Olathe, Kansas.
Asbestos
Asbestos was not detected at any concentration in any samples collected from the subject building.
Please refer to Section 3.0 of the attached report for a detailed description of the asbestos survey, sampling activities, and findings.
Terracon appreciates the opportunity to provide this service to the City of Olathe, Kansas. If you have any questions regarding this report, please contact our office at 913-492-7777.
City of Olathe Public Improvements Asbestos Survey
Smoker's Heaven, Metro by T Mobile, Project 10/20 | Olathe, Kansas November 10, 2025 | Terracon Project No. 02237230
Facilities | Environmental | Geotechnical | Materials ii
Sincerely, Terracon
Katie Burnham Clark Grisell Staff Scientist Environmental Group Manager
Clark Grisell
Facilities | Environmental | Geotechnical | Materials iii
Table Of Contents
1.0 Introduction
1.1 Reliance
2.0 Building Description
3.0 Asbestos-Containing Materials Survey
3.1 Visual Assessment
3.2 Physical Assessment
3.3 Sample Collection
3.4 Sample Analysis
3.5 Regulatory Overview
3.6 Findings
4.0 General Comments
Appendices
Appendix A Asbestos Survey Sample Location Summary
Appendix B Asbestos Laboratory Analytical Results
Appendix C Certifications
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted an asbestos-containing material survey of the Smoker’s Heaven, Metro by T-Mobile, and Project 10/20 spaces located at 2003 East Santa Fe Street in Olathe, KS on October 17, 2025. Building areas were visually assessed for suspect asbestos-containing materials (ACM). A reasonable effort was made to inspect accessible areas. Additional suspect materials could be present in walls, voids, or other concealed areas.
1.1 Reliance
This report is for the exclusive use of the City of Olathe, Kansas, for the project being discussed. Reliance by any other party on this report is prohibited without the written authorization of Terracon and the City of Olathe, Kansas.
2.0 Building Description
The subject building is an approximately 2,240 square-foot commercial building reportedly constructed in 1979. Interior flooring finishes include concrete, sheet vinyl, wall to wall carpet, and vinyl plank flooring. Interior walls are drywall. Interior ceilings are drywall and suspended acoustical ceiling tiles beneath a metal deck. The building’s exterior is brick, with a flat membrane roof.
3.0 Asbestos-Containing Materials Survey
The survey was conducted by Ms. Katie Burnham, State of Kansas-accredited asbestos inspector. A copy of the asbestos inspector’s accreditation is attached as Appendix C.
The survey was conducted in general accordance with the sample collection protocols established in the United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E 763.86, the Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
3.1 Visual Assessment
Survey activities were initiated with visual observation of the interior and exterior of the building to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of a building material that appears similar throughout in terms of color and
Facilities | Environmental | Geotechnical | Materials 2 texture, with consideration given to the date of application. The assessment was conducted in visually accessible areas of the building.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry.
Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM samples were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods, as applicable, to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Rubber, wood products, plastic products, glass, and steel are not considered suspect ACM and were, therefore, not sampled. The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Terracon collected 109 bulk samples from 35 homogeneous areas of suspect ACM.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to Eurofins International Asbestos Testing Laboratories (Eurofins) of Mount Laurel, New Jersey, for analysis by PLM with dispersion staining techniques per USEPA Method 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), Accreditation No. 101165.
3.5 Regulatory Overview
The asbestos National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
Facilities | Environmental | Geotechnical | Materials 3
The asbestos NESHAP regulation classifies ACM as regulated asbestos-containing materials (RACM), Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
The Kansas Department of Health and Environment’s (KDHE) Asbestos Control Section within the Bureau of Air enforces the Asbestos NESHAP as adopted by reference at Kansas Administrative Regulations (K.A.R.) 28-19-735. The owner or operator must provide KDHE with written notification at least 10 working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 10 square feet or 25 linear feet.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for handling materials containing asbestos in concentrations less than or equal to one percent.
3.6 Findings
Asbestos was not detected at any concentration in any samples collected from the subject building.
A summary of sample locations is included in Appendix A. The laboratory analytical report is included in Appendix B.
4.0 General Comments
Terracon did not perform sampling that required demolition or destructive activities such as dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas that may pose a health or safety risk to
Facilities | Environmental | Geotechnical | Materials 4
Terracon personnel were not sampled. Sampling did not include suspect materials that could not be safely reached with available ladders or manlifts. Terracon did not sample suspect materials that may be present in movable equipment such as freezers, kitchen equipment, and hoods. Terracon typically investigates for flooring beneath carpeting by lifting small corner sections of carpet. If tiles or sheet vinyl were seen, they have been identified in the report. If tiles or sheet vinyl were not seen at corners under the carpet, it does not imply that there is none beneath the carpeted floor. Terracon did not conduct a destructive investigation of the doors in the building to determine if the doors were insulated for fire-rating purposes.
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during Terracon’s survey of the building. The information contained in this report is relevant to the date on which this survey was conducted and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by the City of Olathe, Kansas, and is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied, is made.
Facilities | Environmental | Geotechnical | Materials 1
Appendix A
Asbestos Survey Sample Location Summary
Facilities | Environmental | Geotechnical | Materials 2
Appendix A
Asbestos Survey Sample Location Summary 2003 E Santa Fe Street, Olathe, Kansas
Terracon Project No. 02237230
HA
No.
Material Description Sample Number
Sample Location Sample Layer Description
Lab Results
01 2”x4” Ceiling Tile 01-CT4-01 Suite A, Northwest Corner
White Ceiling Tile Not Detected 01-CT4-02 Suite B, South 01-CT4-03 Suite C, Restroom Center
Gypsum Wallboard with
Joint Compound
02-WB1-04 Suite A, Southeast Corner
White Drywall with Brown Paper
Not Detected
White Joint Compound White Tape
02-WB1-05 Suite B, Southeast Corner
White Drywall with Brown Paper White Joint Compound
02-WB1-06 Suite C, Southwest Corner
White Drywall with Brown Paper White Joint Compound
03 Mastic Behind Cove Base
03-MG3-07 Suite A Restroom, East Side Green Cove Base
Not Detected
Tan Mastic
03-MG3-08 Suite A Restroom, West Side Green Cove Base
Tan Mastic
03-MG3-09 Suite B/C Rear (South) Room Green Cove Base
Tan Mastic
04 Mastic Behind Cove Base 04-MG3-10 Suite B, East Side
Gray Cove Base
Not Detected Tan Mastic
04-MG3-11 Suite B, North Side Gray Cove Base
Tan Mastic
Facilities | Environmental | Geotechnical | Materials 3
HA
No.
Material Description Sample Number
Sample Location Sample Layer Description
Lab Results
04-MG3-12 Suite C, South Side Gray Cove Base
Tan Mastic
05 Mastic Behind Cove Base
05-MG3-13 Suite B Restroom, North Side Black Cove Base
Not Detected
Tan Mastic
05-MG3-14 Suite B Restroom, North Side Black Cove Base
Tan Mastic
05-MG3-15 Suite B Restroom, South Side Black Cove Base
Tan Mastic
06 Sheet Vinyl with Adhesive
06-FC1-16 Suite A, North Entryway Off-White Sheet
Flooring
Not Detected
Tan Mastic
06-FC1-17 Suite A, North Entryway Off-White Sheet
Flooring Tan Mastic
06-FC1-18 Suite A, North Entryway Off-White Sheet
Flooring Tan Mastic
07 Sheet Vinyl with Adhesive
07-FC1-19 Suite A Restroom, East Side Off-White Sheet
Flooring
Not Detected
Black/ Tan Mastic
07-FC1-20 Suite B Restroom, North Side Off-White Sheet
Flooring Black/ Tan Mastic
07-FC1-21
Suite B/C Rear (South) Room, North Side
Off-White Sheet Flooring
Black/ Tan Mastic
Mastic Under Faux Wood
Planks
08-MG5-22 Suite B, Southwest Side
Tan Mastic Not Detected 08-MG5-23 Suite B, Southwest Side
08-MG5-24 Suite B, North Side
6” x 6” Ceramic Tile with
Mastic and Grout
09-MA5-25
Suite A, Southwest Corner Sink Surround
White Ceramic Tile Not Detected White Grout
Yellow Mastic
Facilities | Environmental | Geotechnical | Materials 4
Material Description Sample Number
Sample Location Sample Layer Description
Lab Results
09-MA5-26
Suite A, Southwest Corner Sink
Surround
White Ceramic Tile White Grout Yellow Mastic White Joint Compound
09-MA5-27
Suite B/C Rear (South) Room, Mop
Sink Surround
White Ceramic Tile White Grout Yellow Mastic
10 Interior Door Caulk 10-CA2-28 Suite C, West Door White Caulk
Not Detected 10-CA2-29 Suite C, West Door White Caulk 10-CA2-30 Suite C, West Door Black Caulk
Exterior Brick Texture and
Mortar
11-MA1-31 North Side, Center Gray Grout w/ Textured Paint
Not Detected 11-MA1-32 West Side, Center 11-MA1-33 South Side, Center
Exterior Window and Door
Caulk
12-CA5-34 North Door, West End Dark Brown Caulk Not Detected 12-CA5-35 West Window, North End
12-CA5-36 West Window, South End
13 Exterior Foundation Caulk 13-CA6-37 South Wall
Gray Caulk Not Detected 13-CA6-38 West Wall 13-CA6-39 West Wall
14 Exterior Expansion Joint 14-XXX-40 North Wall, Center
Black Expansion Joint Not Detected 14-XXX-41 North Wall, Center 14-XXX-42 North Wall, East End
15 Exterior Door Caulk 15-CA2-43 South Door, West End
White Caulk Not Detected 15-CA2-44 South Door, West End 15-CA2-45 South Door, West End
16 Carpet Glue
16-MG7-46 Suite A, Center Multi-colored Carpet
Not Detected
Yellow Carpet Mastic
16-MG7-47 Suite A, North End Multi-colored Carpet Yellow Carpet Mastic
16-MG7-48 Suite A, North End Multi-colored Carpet Yellow Carpet Mastic
Facilities | Environmental | Geotechnical | Materials 5
Material Description Sample Number
Sample Location Sample Layer Description
Lab Results
17 Roofing
17-RF5-49 Roof, Northwest Area
Black/ Gray Roofing Membrane
Not Detected
Gray Roofing Felt Tan Mastic
Yellow Foam
17-RF5-50 Roof, South Center
Black/ Gray Roofing Membrane
Gray Roofing Felt Tan Mastic
Yellow Foam Black Tar
17-RF5-51 Roof, Northeast Area
Black/ Gray Roofing Membrane
Gray Roofing Felt Tan Mastic
Yellow Foam Black Tar
18 Roofing
18-RF5-52 Roof, West Perimeter, North Side
Black/White Roofing Membrane
Not Detected
Black Tar Black Roofing Material
Tan Glue
18-RF5-53 Roof, North Perimeter, East Side
Black/White Roofing Membrane Black Tar
Black Roofing Material Tan Glue
18-RF5-54 Roof, East Perimeter, Center
Black/White Roofing Membrane Black Tar
Black Roofing Material Tan Glue
Facilities | Environmental | Geotechnical | Materials 6
Material Description Sample Number
Sample Location Sample Layer Description
Lab Results
19 Roof Sealant 19-RF4-55 Roof, Southwest Area on Vent Pipe
Black Sealant
Not Detected Gray Caulk White Caulk
19-RF4-56 Roof, South Side on Conduit Black Sealant 19-RF4-57 Roof, Southeast Area on Conduit Black Sealant
20 Roof Caulk
20-MS5-58 Roof, Southeast Area on Vent Pipe White Caulk
Not Detected
Gray Caulk
20-MS5-59 Roof, Southeast Area on Vent Pipe White Caulk Gray Caulk
20-MS5-60 Roof, Southeast Area on Vent Pipe White Caulk Gray Caulk
Facilities | Environmental | Geotechnical | Materials 7
Appendix B
Asbestos Laboratory Analytical Results
Approved by:
Approved Signatory Frank Ehrenfeld
Report for:
Katie Burnham Terracon Consultants- Lenexa 15620 W. 113th St Lenexa, KS 66219
Regarding:
Eurofins Built Environment Testing East, LLC Project: 02237230 - Smoker's Heaven 2003 E Santa Fe
EML ID: 4275374
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing East, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM (Layer %): 10-22-2025
Service SOPs: Asbestos PLM (Layer %) (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EB-AS-S- 1267) NVLAP Lab Code 101165-0
EMLab ID: 4275374, Page 1 of 12Eurofins Built Environment Testing East, LLC
Eurofins Built Environment Testing East, LLC 9000 Commerce Parkway, Suite B, Mount Laurel, NJ 08054
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
01-CT4-01. 2"x4" Ceiling Tile; A, NW Corner 21391399-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose 20% Glass Fibers 20% Non-Fibrous Material
01-CT4-02. 2"x4" Ceiling Tile; B, S 21391400-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
01-CT4-03. 2"x4" Ceiling Tile; C, RR Center 21391401-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
02-WB1-04. Gypsum Wallboard w/ Joint Compound; A, SE Corner 21391402-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material 15% Cellulose
Layer 2 White Joint Compound Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Layer 3 White Tape Homogeneity:Good
Not Detected 100% Cellulose
02-WB1-05. Gypsum Wallboard w/ Joint Compound; B, SE Corner 21391403-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-WB1-06. Gypsum Wallboard w/ Joint Compound; C, SW Corner 21391404-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
03-MG3-07. Mastic behind Cove Base; A RR East 21391405-1
Layer 1 Green Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 2 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
03-MG3-08. Mastic behind Cove Base; A RR West 21391406-1
Layer 1 Green Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
03-MG3-09. Mastic behind Cove Base; B/C South Room 21391407-1
Layer 1 Green Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-MG3-10. Mastic behind Cove Base; B East 21391408-1
Layer 1 Gray Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-MG3-11. Mastic behind Cove Base; B North 21391409-1
Layer 1 Gray Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-MG3-12. Mastic behind Cove Base; C South 21391410-1
Layer 1 Gray Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
05-MG3-13. Mastic behind Cove Base; B RR North 21391411-1
Layer 1 Black Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 3 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
05-MG3-14. Mastic behind Cove Base; B RR North 21391412-1
Layer 1 Black Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
05-MG3-15. Mastic behind Cove Base; B RR South 21391413-1
Layer 1 Black Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-FC1-16. Sheet Vinyl w/ Adhesive;
A N Entryway 21391414-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Not Detected 85% Non-Fibrous Material 10% Cellulose 5% Glass Fibers
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-FC1-17. Sheet Vinyl w/ Adhesive;
A N Entryway 21391415-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Not Detected 85% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-FC1-18. Sheet Vinyl w/ Adhesive;
A N Entryway 21391416-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Not Detected 85% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
07-FC1-19. Sheet Vinyl w/ Adhesive;
A RR East 21391417-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Black/ Tan Mastic Homogeneity:Moderate
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 4 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
07-FC1-20. Sheet Vinyl w/ Adhesive;
B RR North 21391418-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Homogeneity:Moderate
Not Detected 100% Non-Fibrous Material
07-FC1-21. Sheet Vinyl w/ Adhesive;
B/C South Room, N 21391419-1
Layer 1 Off-White Sheet Flooring Homogeneity:Good
Homogeneity:Moderate
Not Detected 100% Non-Fibrous Material
08-MG5-22. Mastic under Faux Wood Plants; B SW 21391420-1
Layer 1 Tan Mastic Homogeneity:Good
Not Detected 100% Non-Fibrous Material
08-MG5-23. Mastic under Faux Wood Plants; B SW 21391421-1
Layer 1 Tan Mastic Homogeneity:Good
Not Detected 100% Non-Fibrous Material
08-MG5-24. Mastic under Faux Wood Plants; B N 21391422-1
Layer 1 Tan Mastic Homogeneity:Good
Not Detected 100% Non-Fibrous Material
09-MG5-25. 6"x6" Ceramic Tile w/ Mastic & Grout; A SW Corner Sink Surround 21391423-1
Layer 1 White Ceramic Tile
White Grout
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
09-MG5-26. 6"x6" Ceramic Tile w/ Mastic & Grout; A SW Corner Sink Surround 21391424-1
Layer 1 White Ceramic Tile
Comments:
EMLab ID: 4275374, Page 5 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
09-MG5-26. 6"x6" Ceramic Tile w/ Mastic & Grout; A SW Corner Sink Surround 21391424-1(cont.)
Layer 2 White Grout
Layer 4
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
09-MG5-27. 6"x6" Ceramic Tile w/ Mastic & Grout; B/C Mop Sink Surround 21391425-1
Layer 1 White Ceramic Tile
White Grout
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-CA2-28. Interior Door Caulk;
South Rear Door, W 21391426-1
Layer 1 White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-CA2-29. Interior Door Caulk;
South Rear Door, W 21391427-1
Layer 1 White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-CA2-30. Interior Door Caulk;
South Rear Door, W 21391428-1
Layer 1 Black Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
11-MA1-31. Exterior Brick Texture & Mortar; North Center 21391429-1
Layer 1 Gray Grout w/ Textured Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
11-MA1-32. Exterior Brick Texture & Mortar; West Center 21391430-1
Layer 1 Gray Grout w/ Textured Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
11-MA1-33. Exterior Brick Texture & Mortar; South Center 21391431-1
Layer 1 Gray Grout w/ Textured Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 6 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
12-CA5-34. Exterior Window & Door Caulk; North Door, W 21391432-1
Layer 1 Dark Brown Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
12-CA5-35. Exterior Window & Door Caulk; West Window, N 21391433-1
Layer 1 Dark Brown Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
12-CA5-36. Exterior Window & Door Caulk; West Window, S 21391434-1
Layer 1 Dark Brown Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
13-CA6-37. Exterior Foundation Caulk; South 21391435-1
Layer 1 Gray Caulk Homogeneity:Good
Not Detected 97% Non-Fibrous Material 3% Cellulose
13-CA6-38. Exterior Foundation Caulk; West 21391436-1
Layer 1 Gray Caulk Homogeneity:Good
13-CA6-39. Exterior Foundation Caulk; West 21391437-1
Layer 1 Gray Caulk Homogeneity:Good
14-MS5-40. Exterior Expansion Joint;
North Center 21391438-1
Layer 1 Black Expansion Joint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
14-MS541. Exterior Expansion Joint;
North Center 21391439-1
Layer 1 Black Expansion Joint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
14-MS5-42. Exterior Expansion Joint;
North East End 21391440-1
Layer 1 Black Expansion Joint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
15-CA2-43. Exterior Door Caulk;
South Door, West End 21391441-1
Layer 1 White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
15-CA2-44. Exterior Door Caulk;
South Door, West End 21391442-1
Layer 1 White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
15-CA2-45. Exterior Door Caulk;
South Door, West End 21391443-1
Layer 1 White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
16-MG7-46. Carpet Glue; A Center 21391444-1
Layer 1 Multi-colored Carpet Homogeneity:Good
Not Detected 80% Synthetic Fibers
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 7 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
16-MG7-47. Carpet Glue; A North 21391445-1(cont.)
Layer 1 Multi-colored Carpet Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
16-MG7-48. Carpet Glue; A North 21391446-1
Layer 1 Multi-colored Carpet Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
17-RF5-49. Roofing; Roof, NW 21391447-1
Layer 1 Black/ Gray Roofing Membrane Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Synthetic Fibers
Gray Roofing Felt Homogeneity:Good
Not Detected 50% Cellulose 30% Non-Fibrous Material
Yellow Foam Homogeneity:Good
Not Detected 100% Non-Fibrous Material
17-RF5-50. Roofing; Roof, S Center 21391448-1
Layer 1 Black/ Gray Roofing Membrane Homogeneity:Good
Homogeneity:Good
Not Detected 50% Cellulose
EMLab ID: 4275374, Page 8 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
17-RF5-50. Roofing; Roof, S Center 21391448-1(cont.)
Layer 3 Tan Mastic
Layer 5 Black Tar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
17-RF5-51. Roofing; Roof, NE 21391449-1
Layer 1 Black/ Gray Roofing Membrane Homogeneity:Good
Homogeneity:Good
Not Detected 50% Cellulose
Layer 5
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
18-RF5-52. Roofing; Roof, W Perimeter N 21391450-1
Layer 1 Black/White Roofing Membrane Homogeneity:Good
EMLab ID: 4275374, Page 9 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
18-RF5-52. Roofing; Roof, W Perimeter N 21391450-1(cont.)
Layer 3 Black Roofing Material Homogeneity:Good
Not Detected 75% Non-Fibrous Material 25% Cellulose
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
18-RF5-53. Roofing; Roof, N Perimeter E 21391451-1
Layer 1 Black/White Roofing Membrane Homogeneity:Good
Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
18-RF5-54. Roofing; Roof, E Perimeter Cent.
21391452-1
Layer 1 Black/White Roofing Membrane Homogeneity:Good
Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4275374, Page 10 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
19-RF4-55. Roof Sealant; Roof SW on Vent Pipe 21391453-1(cont.)
Layer 1 Black Sealant
White Caulk Homogeneity:Good
Not Detected 100% Non-Fibrous Material
19-RF4-56. Roof Sealant; Roof S on Conduit 21391454-1
Layer 1 Black Sealant Homogeneity:Good
Not Detected 100% Non-Fibrous Material
19-RF4-57. Roof Sealant; Roof SE on Conduit 21391455-1
Layer 1 Black Sealant Homogeneity:Good
Not Detected 100% Non-Fibrous Material
20-MS5-58. Roof Caulk; Roof SE on Vent Pipe 21391456-1
Layer 1 White Caulk
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
20-MS5-59. Roof Caulk; Roof SE on Vent Pipe 21391457-1
Layer 1 White Caulk
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
20-MS5-60. Roof Caulk; Roof SE on Vent Pipe 21391458-1
Layer 1 White Caulk
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
Analyst(s): Maxamillian Roselli
EMLab ID: 4275374, Page 11 of 12Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Katie Burnham Re: 02237230 - Smoker's Heaven 2003 E Santa Fe
Date of Receipt: 10-20-2025 Date of Report: 10-22-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Maxamillian Roselli
EMLab ID: 4275374, Page 12 of 12Eurofins Built Environment Testing East, LLC
Facilities | Environmental | Geotechnical | Materials 8
Appendix C
Certifications
Certificate # 000MO46911934
Katherine Burnham has on 03/07/2025 completed the requirements for asbestos accreditation under
Section 206 of TSCA Title II, 15 USC 2646
Online Asbestos Building Inspector Refresher (4 Hour) as approved by MO and the US EPA under 40 CFR 763 (AHERA) and passed the associated exam on 03/07/2025 with a score of at least 70%.
SSN: XXX-XX-0858
Expiration: 03/07/2026
PO BOX 786 – Lawrence, KS 66044 – 800.444.6382 www.metaenvironmental.net
| 1.0 Introduction |
| 1.1 Reliance |
| 2.0 Building Description |
| 3.0 Asbestos-Containing Materials Survey |
| 3.1 Visual Assessment |
| 3.2 Physical Assessment |
| 3.3 Sample Collection |
| 3.4 Sample Analysis |
| 3.5 Regulatory Overview |
| 3.6 Findings |
4.0 General Comments
| 2025-11-10T19:49:57+0000 | |
| Certified by Adobe Acrobat Sign |
File details come from the government source that posted it. Updated .