AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
1 9
2. AMENDMENT/MODIFICATION NUMBER
A0008
3. EFFECTIVE DATE
04/03/2019
4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE
USDA FOREST SERVICE
PACIFIC SOUTHWEST REGION
1323 CLUB DRIVE
VALLEJO, CA 94592-1110
SAME AS ITEM 6.
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER
1291S819R4002
9B. DATED (SEE ITEM 11)
02/22/2019
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return 1 copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Amendment A0008 is for the purpose of providing answers to RFIs 51-56 and corrects or clarifies previous responses for RFIs 7, 26, 32, 46.
This amendment also extends the proposal due date.
Supplemental Specification 09841 Acoustical Panels is attached. Incorporated as Attachment 9. Replacement Page 28 of 56, Section J List of Attachments is attached.
The offer/proposal due date is hereby extended to NLT Friday, April 12, 2019 - 1p/1300 PST
15A. NAME AND TITLE OF SIGNER (Type or print)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as her
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
Jeremy Bedner, Contracting Officer etofore changed, remains unchanged and in full force and effect.
15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
16C. DATE SIGNED
04/03/2019 (Signature of person authorized to sign)
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243
Amendment A0008 04/03/2019
RFP 1291S819R4002
LOS PRIETOS FIRE ENGINE GARAGE CONSTRUCTION
SANTA BARBARA RANGER DISTRICT, LOS PADRES NATIONAL FOREST
US FOREST SERVICE
The following are responses to Request for Information [RFIs] 51-56 and corrects or clarifies previous responses for RFIs 7, 26, 32, 46.
7. Please provide more information as to what hardware group pairs with door numbers.
REVISED ANSWER:
Contractor is to provide hardware schedule per Specifications Section 08 71 00 – Submittals and Substitutions
26. We have noticed that only the civil drawings are stamped and the architectural, electrical, structural and mechanical are not. Will this project require additional design and stamp by an engineer?
REVISED ANSWER:
Contract drawings provided are complete. Any additional design as required for project submittals, as delineated in the CONTRACT, will be the responsibility of the contractor.
32. Please provide preferred acoustical ceiling tile product to match for this project.
REVISED ANSWER:
Refer to Specification 09841 – Acoustical Panels. Specification and Replacement Page 28 of 58 – Section J List of Attachments – attached.
46. Site Visit question. Environmental assessment required by contractor? Environmentalist, biologist personnel required?
REVISED ANSWER:
Applies to building demolition only.
51. Can you please indicate what are the required amperages of the breakers for electrical panel F as these were not indicated on electrical plan E1.0.
ANSWER:
The circuit breaker required amperages were intentionally omitted from the drawings. The Panelboard schedule are estimated loads. Actual loads could vary in the field. Contractor shall submit proposed panelboard balanced schedule and circuit breaker sizing per 2017 NEC for approval.
52. Confirm the following. All windows in fire-prone areas including Santa Barbara Ranger District are required by law to be tempered glass
ANSWER:
Per window schedule note Sheet A5, Wildland Urban Interface requires all windows to be tempered glass
53. Per interior Finish Schedule on A5 and base on RFI 11, answered on Amendment 002 – Finish Schedule calls Sealer on different rooms. On the answered question 11: Related Sections as called out in Specification 09 65 13 changed to “Concrete” and “Chemically Stained Concrete Floor”. Eliminate “Polished Concrete Floor Finishing” and “Concrete Floor Sealer”. We still don’t have any Concrete Floor Sealer on the specifications, and if you changing to “concrete” and “concrete floor sealer” we didn’t receive the updated specification. I still need clarifications if require Stained Concrete Floor instead of sealer or get the sealer spec.
ANSWER:
Per Drawing 1, Sheet A4 provide colored concrete on Office/ Day Room wing (area defined between gridlines 1 and 3 and gridlines B and C ) follow color manufacturer recommendations (Davis or approved equal) for concrete sealer in these areas. The Cache Wing (between gridlines #4 and #5) and Engine bays are not colored concrete and are not to be provided sealer.
54. The specifications call for signage in the building, however aside from the requirements in the specs there are no details or a sign schedule. Is the design to be part of the contract? Will signage be a separate contract? If signage, but not design, is to be included in the bid, please supply a sign schedule.
Reference Attachment 1 Specifications, Section 10 14 00 – Signage, Page 10 14 00-1
ANSWER:
Provide signage as per Specification 10 14 00, section 2.3.
55. Specification 10 14 00, 2.2D speaks of room ID signage. This is not shown anywhere on the plans or in the sign schedule (paragraph 2.3). Please clarify how many rooms, if any, require room ID signage.
ANSWER:
Provide signage as stated in Specification 10 14 00, section 2.3A : “Provide all signage as required by code and listed below.”
56. Regarding the time needed for the Government to relocate operations from the (e) station to the (n) fire engine garage between base project completion and start of alternate scope: Please clarify whether the number of days allotted for this relocation is to be counted against the 360-calendar-day period of performance.
ANSWER:
The number of days allotted for relocating operations to the new building will not count toward the 360-calendar day period of performance.
Replacement Page 28 of 56
PART III--LIST OF DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
SECTION J – LIST OF ATTACHMENTS
NUMBER TITLE PAGES
1 Specifications 554
2 Supplemental Specifications Section 270000, Telecommunication Wiring Systems
3 Project Drawings and Plans 44
4 Geotechnical Design Memorandum, Bengal Engineering 24
5 DOL Wage Decision No. CA190023 01/04/2019 CA23 DOL General Decision No. CA190014 02/22/2019 CA14
6 Past Performance Questionnaire 5
7 Asbestos & Lead Survey Report, Environmental Consulting Services 39
8 Site Plan with Building Numbers 1
9 Supplemental Specification Section 09841, Acoustical Panels 4
Los Prietos Fire Engine Garage Construction
Attachment 9
Section 09841
ACOUSTICAL PANELS
SECTION 09841 – ACOUSTICAL PANELS
PART ONE - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1. Select products to obtain the following LEED credits as defined in section 01352:
a. MR Credit 4.1 and 4.2
b. EQ Credit 4.1
1.2 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.3 SUMMARY
A. This Section includes back mounted acoustical wall and ceiling panels.
1.4 SUBMITTALS
A. Product Data: For each type of panel edge, core material, and mounting indicated.
B. Shop Drawings: For acoustical wall panels. Include mounting devices and details.
Include elevations showing panel sizes and direction of fabric weave and pattern matching. Indicate panel edge and core materials.
C. Samples for Verification: For the following products. Prepare Samples from same material to be used for the Work.
1. Panel Edge: 12-inch- long Sample showing edge profile, corner, and finish.
2. Core Material: 12-inch- square Sample showing corner.
3. Mounting Device: Full-size Sample.
4. Colors: No larger than 12 by 12 inches.
D. Maintenance Data: For acoustical wall panels to include in maintenance manuals.
Include fabric manufacturers' written cleaning and stain-removal recommendations.
E. Warranty: Special warranty specified in this Section.
F. LEED Submittals:
1. Product Data for Credit MR 4.1 and 4.2: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content.
a. Include statement indicating costs for each product having recycled content.
2. Product Data for Credit EQ 4.1: For adhesives and sealants used in panel installation.
1.5 QUALITY ASSURANCE
A. Fire-Test-Response Characteristics: Provide acoustical wall panels with the following surface-burning characteristics as determined by testing identical products per UBC Standard 8-1, by UL or another testing and inspecting agency acceptable to authorities having jurisdiction:
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 450 or less.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Do not install acoustical wall panels until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
1. Installation of acoustical panels shall not begin until all wet work (plastering, concrete, etc.) is completed and dry. Building shall be properly enclosed and under standard occupancy conditions (temperature of 60-85 degrees F and not more than 70% relative humidity) before installation begins.
1.7 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of acoustical wall panels that fail in performance, materials, or workmanship within specified warranty period.
1. Failures in materials include, but are not limited to, fabric sagging, distorting, or releasing from panel edge; or warping of core.
2. Warranty Period: Two years from date of Substantial Completion.
1.8 EXTRA MATERIALS
A. Furnish extra materials described below, before installation begins, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Fabric: For each fabric, color, and pattern installed, provide length equal to 6 full size panels
2. Acoustical Wall Panel Mounting Devices: Full-size units as required to mount 6 full size panels.
PART 2 - PRODUCTS
2.1 GENERAL
A. Acoustical wall panels shall be Wall Technology, Inc., 2750 Industrial Lane / Broomfield, CO 80020. Phone (800) 359-3312 / Fax (800) 359-0106 or approved equal.
2.2 ACOUSTICAL WALL PANELS WITH GLASS-FIBER BOARD CORE
A. Glass-Fiber Board: Acoustical Panels shall be Wall Technology, New Dimensions Acoustical Wall Panels.
1. Thickness 1 1/16".
2. Sizes: As shown on drawings.
3. Edge profile shall be: Square.
4. Corner detail shall be: Factory square.
5. Edge treatment shall be: Resin hardened.
6. Panel finish shall be: Manufacturers standard acoustically transparent membrane fabric wrap:
a. Color to be selected by contracting officer. Fabric shall be applied directly to the face and edges of the panel and return to the back of the panel to provide a full finished edge. All corners are fully tailored.
7. Wall Mounting shall be: Impaling clips and adhesive as recommended by manufacturer.
8. Flammability - All panel components shall have a Class "A" flame spread rating of 25 or less in accordance with ASTM E-84
2.3 CLIP MOUNTED ACOUSTICAL CEILING PANELS WITH GLASS-FIBER BOARD
CORE
A. Glass-Fiber Board: Acoustical Panels shall be Wall Technology, New Dimensions Acoustical Wall Panels.
1. Thickness 1 1/16".
2. Sizes: As shown on drawings.
3. Edge profile shall be: Square.
4. Corner detail shall be: Factory square.
5. Edge treatment shall be: Resin hardened.
6. Panel finish shall be: Manufacturers standard acoustically transparent membrane fabric wrap:
a. Color to be selected by contracting officer. Fabric shall be applied directly to the face and edges of the panel and return to the back of the panel to provide a full finished edge. All corners are fully tailored.
7. Mounting shall be: Z-Clip, number as recommended by manufacturer for panel size.
8. Flammability - All panel components shall have a Class "A" flame spread rating of 25 or less in accordance with ASTM E-84
2.4 FABRICATION
A. Acoustical Wall Panels: Panel construction consisting of facing material adhered to face, edges and back border of dimensionally stable core; with rigid edges to reinforce panel perimeter against warpage and damage.
B. Fabric Facing: Stretched straight, on the grain, tight, square, and free from puckers, ripples, wrinkles, sags, blisters, seams, adhesive, or other foreign matter. Applied with visible surfaces fully covered.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fabric, substrates, blocking, and conditions, with Installer present, for compliance with requirements, installation tolerances, and other conditions affecting performance of acoustical wall panels.
1. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install acoustical panels in locations indicated with vertical surfaces and edges plumb, top edges level and in alignment with other panels, faces flush, and scribed to fit adjoining work accurately at borders and at penetrations.
1. Cut units to be at least 50 percent of unit width, with facing material extended over cut edge to match uncut edge. Scribe acoustical wall panels to fit adjacent work. Butt joints tightly.
B. Comply with acoustical panel manufacturer's written instructions for installation of panels using type of concealed mounting accessories indicated or, if not indicated, as recommended by manufacturer. Anchor panels securely to supporting substrate.
3.3 CLEANING
A. Clip loose threads; remove pills and extraneous materials.
B. Clean panels with fabric facing, on completion of installation, to remove dust and other foreign materials according to manufacturer's written instructions.
3.4 PROTECTION
A. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and Installer, to ensure that acoustical wall panels are without damage or deterioration at time of Substantial Completion.
B. Replace acoustical wall panels that cannot be cleaned and repaired, in a manner approved by Contracting officer, before time of Substantial Completion.
END OF SECTION 09841
| SF-30 A0008 |
| 11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS |
| 13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14. |
| E. IMPORTANT: Contractor is not is required to sign this document and return 1 copies to the issuing office. |
| Amendment A0008 is for the purpose of providing answers to RFIs 51-56 and corrects or clarifies previous responses for RFIs 7, 26, 32, 46. This amendment also extends the proposal due date. |
| Supplemental Specification 09841 Acoustical Panels is attached. Incorporated as Attachment 9. Replacement Page 28 of 56, Section J List of Attachments is attached. |
| RFIs + Responses for A8 |
| REPLACE PAGE A0008 - RFP 1291S819R4002 |
| PART III--LIST OF DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS |
| ATT 9 - Supp Spec 09841 Acoustical |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. |
| a. MR Credit 4.1 and 4.2 |
| b. EQ Credit 4.1 |
| 1.2 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. |
| 1.3 SUMMARY |
| A. This Section includes back mounted acoustical wall and ceiling panels. |
| 1.4 SUBMITTALS |
| A. Product Data: For each type of panel edge, core material, and mounting indicated. |
| B. Shop Drawings: For acoustical wall panels. Include mounting devices and details. Include elevations showing panel sizes and direction of fabric weave and pattern matching. Indicate panel edge and core materials. |
| C. Samples for Verification: For the following products. Prepare Samples from same material to be used for the Work. |
| D. Maintenance Data: For acoustical wall panels to include in maintenance manuals. Include fabric manufacturers' written cleaning and stain-removal recommendations. |
| E. Warranty: Special warranty specified in this Section. |
| F. LEED Submittals: |
| a. Include statement indicating costs for each product having recycled content. |
| 1.5 QUALITY ASSURANCE |
| A. Fire-Test-Response Characteristics: Provide acoustical wall panels with the following surface-burning characteristics as determined by testing identical products per UBC Standard 8-1, by UL or another testing and inspecting agency acceptable to au... |
| 1.6 PROJECT CONDITIONS |
| A. Environmental Limitations: Do not install acoustical wall panels until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at... |
| 1.7 WARRANTY |
| A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of acoustical wall panels that fail in performance, materials, or workmanship within specified warranty period. |
| 1.8 EXTRA MATERIALS |
| A. Furnish extra materials described below, before installation begins, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| PART 2 - PRODUCTS |
| 2.1 GENERAL |
| A. Acoustical wall panels shall be Wall Technology, Inc., 2750 Industrial Lane / Broomfield, CO 80020. Phone (800) 359-3312 / Fax (800) 359-0106 or approved equal. |
| 2.2 ACOUSTICAL WALL PANELS WITH GLASS-FIBER BOARD CORE |
| A. Glass-Fiber Board: Acoustical Panels shall be Wall Technology, New Dimensions Acoustical Wall Panels. |
| a. Color to be selected by contracting officer. Fabric shall be applied directly to the face and edges of the panel and return to the back of the panel to provide a full finished edge. All corners are fully tailored. |
| 2.3 CLIP MOUNTED ACOUSTICAL CEILING PANELS WITH GLASS-FIBER BOARD CORE |
| A. Glass-Fiber Board: Acoustical Panels shall be Wall Technology, New Dimensions Acoustical Wall Panels. |
| a. Color to be selected by contracting officer. Fabric shall be applied directly to the face and edges of the panel and return to the back of the panel to provide a full finished edge. All corners are fully tailored. |
| 2.4 FABRICATION |
| A. Acoustical Wall Panels: Panel construction consisting of facing material adhered to face, edges and back border of dimensionally stable core; with rigid edges to reinforce panel perimeter against warpage and damage. |
| B. Fabric Facing: Stretched straight, on the grain, tight, square, and free from puckers, ripples, wrinkles, sags, blisters, seams, adhesive, or other foreign matter. Applied with visible surfaces fully covered. |
| PART 3 - EXECUTION |
| 3.1 EXAMINATION |
| A. Examine fabric, substrates, blocking, and conditions, with Installer present, for compliance with requirements, installation tolerances, and other conditions affecting performance of acoustical wall panels. |
| 3.2 INSTALLATION |
| A. Install acoustical panels in locations indicated with vertical surfaces and edges plumb, top edges level and in alignment with other panels, faces flush, and scribed to fit adjoining work accurately at borders and at penetrations. |
| B. Comply with acoustical panel manufacturer's written instructions for installation of panels using type of concealed mounting accessories indicated or, if not indicated, as recommended by manufacturer. Anchor panels securely to supporting substrate. |
| 3.3 CLEANING |
| A. Clip loose threads; remove pills and extraneous materials. |
| B. Clean panels with fabric facing, on completion of installation, to remove dust and other foreign materials according to manufacturer's written instructions. |
| 3.4 PROTECTION |
| A. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and Installer, to ensure that acoustical wall panels are without damage or deterioration at time of Substantial Completion. |
| B. Replace acoustical wall panels that cannot be cleaned and repaired, in a manner approved by Contracting officer, before time of Substantial Completion. |
File details come from the government source that posted it.