Attachment 2 to Addendum 2_drawings.pdf

PDF 202 KB Posted

Attached to
Renovate Building 6403 Containment Lab
Solicitation number
12639526Q0184
Issued by

About this file

This document contains mechanical schedules for USDA/APHIS Containment Facility Building 6403 at Moore Air Base, Edinburg, Texas (Coffman Project #212431). The schedules detail specifications for HVAC equipment, controls, and related systems required for the facility's operation.

Air handling units (AHU-5 through AHU-12) manufactured by Enviro-Tec are specified with varying capacities ranging from 800 to 1,000 CFM, featuring 208V single-phase motors, cooling coils with 4-6 rows at 10-12 FPI, and stainless steel condensate pans with MERV 13 filters. An energy recovery ventilator (ERV-1) by Greenheck with 2,230-3,230 CFM supply capacity includes heat recovery core, chilled water cooling, electric resistance heating, and dehumidification capabilities. Exhaust fans (EF-3 through EF-12) provide general and specialty exhaust functions including fume hood exhaust (1,200 CFM at 4 inches WC), ranging from 1/10 to 3 HP motors at 120V or 208V. Two identical York air-cooled chillers (CHLR-1 and CHLR-2) each provide 67.25 tons of cooling capacity with 236.5 kW output, using R454B refrigerant with dual independent circuits, 208V three-phase power at 424 MCA, and integrated condenser controls. A Fulton steam boiler (B-1) rated for 100-600 MBh input provides 200 lb/hr steam output at 80 PSI for autoclave and lab operations. Four chilled water pumps (CHWP-1 through CHWP-4) including redundant secondary loop pumps operate at 100 GPM with 12% propylene glycol. Glycol feeder (GF-1), expansion tank (ET-1), buffer tank (BT-1), and air separator (AS-1) support the chilled water system. Air control valves (SCV-1 through SCV-7 and ECV-1 through ECV-7) with fast-acting actuators maintain room pressurization for laboratory and autoclave spaces. All equipment includes electrical requirements, unit weights, and manufacturer specifications; seismic design category is A with importance factor 1.0. Vibration control requirements and flexible connections are noted for rotating equipment and vibration-sensitive units.

View the file

Other files

File Type Posted
12639526Q0184-0005.pdf PDF
Attachment 2 to addendum 3_specs.pdf PDF
Attachment 1 to addendum 3_dwgs.pdf PDF
12639526Q0184-0004.pdf PDF
First asbestos test results.pdf PDF
A04_Attachment 5_Price Schedule for Add Alternates.docx DOCX document
12639526Q0184-0003.pdf PDF
USDA Building 6403 RFI Log.xlsx XLSX spreadsheet
Attachment 1 to Addendum 2_specs.pdf PDF
12639526Q0184-0002.pdf PDF
RFIs and Responses.docx DOCX document
USDA_Building_6403_RFI_Log.xlsx XLSX spreadsheet
12639526Q0184-0001.pdf PDF
Attachemnt 2 to Addendum 1_Specs.pdf PDF
Attachment 1 to Addendum 1_Drawings.pdf PDF
6403 Bldg Ronovation Walkthrough Sign In Sheet.pdf PDF
Attachment 5_Price Schedule for Add Alternates.docx DOCX document
12639526Q0184.docx DOCX document
Attachment 4_Federal Construction Wage Rates_Hidalgo County.txt TXT text file
Attachment 2_Specifications.pdf PDF
Attachment 3_Drawings.pdf PDF
Attachment 1_Statement of Work.doc DOC document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR HANDLING UNIT SCHEDULE

TAG

MANUFACTURER/

MODEL

SUPPLY FAN DUCT HEATER COOLING COIL

UNIT POWER REQMTS UNIT

WT.

(LBS)

REMARKSCOOLING

CFM

MIN OA

CFM

ESP

("WC)

TSP

("WC)

MOTOR DATA

TOTAL KW

POWER REQMTS

FLUID

TOTAL

MBh

SENS.

MBh

ROWS/

FPI

EAT (F) LAT (F) APD

(IN WC)

FLOW

(GPM)

EWT

(F)

LWT

(F)

WPD

(FT)HP RPM FLA VOLTS Ø DB WB DB WB VOLTS Ø MCA MOCP

AHU-5

ENVIRO-TEC/

CDVB16

800 155 .5 - (2) 1/3 - 5.6 5 208 1 12% PG 36 18 4/12 78 67 52.0 51.6 - 5.2 40 55 5.23 208 1 37 40 192 1, 2, 3, 5

AHU-6

ENVIRO-TEC/

CDVB16

1000 260 .5 - (2) 1/3 - 5.6 5 208 1 12% PG 36 18 4/10 77 64 51.9 50.9 - 5.3 40 55 11.75 208 1 37 40 192 1, 2, 3, 5

AHU-7

ENVIRO-TEC/

CDVB10

850 150 .5 - 1/3 - 2.8 3 208 1 12% PG 18 12 4/10 76 62 56.4 53.9 - 2.8 40 55 3.31 208 1 33.6 35 147 1, 2, 3, 5

AHU-8

ENVIRO-TEC/

VDD12

1000 100 .5 1.2 1/2 1385 2.49 5 208 1 12% PG 24 18 6/12 76 60 53.3 51.0 0.66 3.4 40 55 .86 208 1 36.3 40 333 1, 2, 3, 5

AHU-9

ENVIRO-TEC/

VDD12

1000 100 .5 1.2 1/2 1385 2.49 5 208 1 12% PG 24 18 6/12 76 60 53.3 51.0 0.66 3.4 40 55 .86 208 1 36.3 40 333 1, 2, 3, 5

AHU-10

ENVIRO-TEC/

VDD12

1000 100 .5 1.2 1/2 1385 2.49 5 208 1 12% PG 24 18 6/12 76 60 53.3 51.0 0.66 3.4 40 55 .86 208 1 36.3 40 333 1, 2, 3, 5

AHU-11

ENVIRO-TEC/

VDD12

1000 100 .5 1.2 1/2 1385 2.49 5 208 1 12% PG 24 18 6/12 76 60 53.3 51.0 0.66 3.4 40 55 .86 208 1 36.3 40 333 1, 2, 3, 5

AHU-12

ENVIRO-TEC/

VDD12

1000 100 .5 1.2 1/2 1385 2.49 5 208 1 12% PG 24 18 6/12 76 60 53.3 51.0 0.66 3.4 40 55 .86 208 1 36.3 40 333 1, 2, 3, 5

1. CONDENSATE PAN SHALL BE STAINLESS STEEL, CONDENSATE SHALL BE ROUTED TO NEAREST FLOOR DRAIN.

2. UNIT SHALL HAVE 2" MERV 13 FILTERS.

3. UNIT IS VERTICAL AIR HANDLING UNIT.

4. (NOT USED).

5. CONNECT OUTSIDE AIR DUCTWORK INTO RETURN AS SHOWN ON PLANS. BALANCE OUTSIDE AIR DAMPER TO MATCH MIN OA CFM LISTED IN THE SCHEDULE.

ENERGY RECOVERY VENTILATOR

TAG LOCATION SERVES

MANUFACTURER/

MODEL

SUPPLY FAN EXHAUST FAN ENERGY RECOVERY MODULE DUCT HEATER COOLING COIL UNIT ELECTRICAL

REQUIREMENTS

SUPPLY AIR FILTERS

SIZE (WxLxH)

UNIT

WT.

(LBS)

REMARKS

TOTAL CFM ESP

(IN. WC)

MOTOR DATA

TOTAL CFM ESP

(" WC)

MOTOR DATA SUMMER WINTER

CAPACITY

(KW)

EAT

(°F)

LAT

(°F)

FLUID

TOTAL

CAPACITY

(MBH)

SENS.

CAPACITY

(MBH)

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

EAT

DB/WB

(°F)

LAT

DB/WB

(°F)

BHP HP RPM DRIVE BHP HP RPM DRIVE OAT

DB/WB (°F)

LAT

DB/WB (°F)

TOTAL

EFF %

OAT

DB (°F)

LAT

DB (°F)

TOTAL

EFF %

VOLTS Ø MCA MOCP # TYPE SIZE (IN)

ERV-1 OUTSIDE LAB/AUTOCLAVE AIR

GREENHECK/

RVC-65-PH-CW-1-A1

2230-3230 3.5 4.80 5 1750 DIRECT 1990-2790 2.5 1.80 3 1165 DIRECT 82.9/78.9 78.2/72.3 73.5 36.5 43.8 80 28.7 51.8 77 12% PG 287.5 126.3 40 55 39.2 78.2/72.3 46.5/46.5 208 3 129 150 2 (1) MERV 8

(1) MERV 13

16x20x2 68"x197"x73" 4175 1,2,3

1. 100% OUTSIDE AIR AND EXHAUST UNIT WITH HEAT RECOVERY CORE.

2. UNIT TO BE SUPPLIED WITH CHILLED WATER COOLING AND ELECTRIC RESISTANCE HEATING.

3. UNIT TO BE SUPPLIED WITH DEHUMIDIFICATION CAPABILITIES.

4. EXHAUST FILTERS NOT INTEGRAL TO UNIT. SEE FILTER HOUSING SCHEDULE.

5. UNIT INLET AND OUTLET CONNECTIONS SHALL MATCH LOCATIONS SHOWN ON DRAWINGS.

SPECIALTY EXHAUST LABORATORY EQUIPMENT CONNECTION SCHEDULE

TAG EQUIPMENT SERVES SERVED BY MANUFACTURER / MODEL LENGTH (FT) TYPE EXHAUST

CONN. (IN)

S.P. AT COLLAR

(IN. WG.)

DESIGN CFM SASH

OPENING (IN)

UNIT POWER

REQUIREMENTS REMARKS

VOLTS Ø FLA

FH-1 FUME HOOD LAB #1 EF-12 BY OTHERS - - - - 1180 - - - - 1,2

1. NEW FUME HOOD PROVIDED BY OWNER AND INSTALLED BY DIVISION 23 CONTRACTOR.

2. THE LOCAL APHIS PROGRAM WILL HIRE THE FUME HOOD CERTIFIER. G.C. TO COORDINATE WITH THE SCHEDULE.

FAN SCHEDULE

TAG SERVES

MANUFACTURER/

MODEL

DESCRIPTION FAN PERFORMANCE MOTOR ELECTRICAL

REQUIREMENTS

UNIT

WT.

(LBS)

REMARKS

TYPE DRIVE FLOW

(CFM)

ESP

(" WC)

SPEED

(RPM)

NOISE

(SONES)

BHP

HP VOLTS Ø FLA

EF-3

GREEN HOUSE

GENERAL EXHAUST

GREENHECK/

SQ-140HP-VG

IN LINE

CENTRIFUGAL

DIRECT 500 2 2200 15.9 0.40 1 120 1 10.40 68 1, 2, 3

EF-4

GREEN HOUSE

PURGE

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 550 0.25 1413 6.3 0.05 1/10 120 1 1.38 64 1, 2

EF-5

GREEN HOUSE

PURGE

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 550 0.25 1413 6.3 0.05 1/10 120 1 1.38 64 1, 2

EF-6

GREEN HOUSE

PURGE

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 550 0.25 1413 6.3 0.05 1/10 120 1 1.38 64 1, 2

EF-7

GREEN HOUSE

PURGE

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 550 0.25 1413 6.3 0.05 1/10 120 1 1.38 64 1, 2

EF-8

GREEN HOUSE

PURGE

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 550 0.25 1413 6.3 0.05 1/10 120 1 1.38 64 1, 2

EF-9 ELEC. ROOM

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 300 0.25 1059 4.3 0.02 1/10 120 1 1.38 64 1, 2

EF-10 BOILER ROOM

GREENHECK/

G-090-VG

ROOF

CENTRIFUGAL

DIRECT 300 0.25 1059 4.3 0.02 1/10 120 1 1.38 64 1, 2

EF-11

AUTO CLAVE

& VH-1

GREENHECK/

USF-6

UTILITY UP

BLAST

DIRECT 600 2 2319 16.9 0.34 1/2 120 1 - 133 1, 2

EF-12 FUME HOOD

GREENHECK/

VEKTOR-H-12

FUME

EXHAUST

DIRECT 1200 4 3571 - 1.65 3 208 3 - 485 2, 4, 5

1. PROVIDE FAN WITH MOTORIZED DAMPER FOR INSTALLATION AT BUILDING ENVELOPE.

2. PROVIDE WITH 0-10VDC CONTROL MODULE.

3. PROVIDE ROOF CAP FOR EXTERIOR PENETRATION. SEE ROOF CAP SCHEDULE.

4. FAN TO BE LINKED TO SWITCH ON FUME HOOD (FH-1). FAN TO BE ENERGIZED WHEN FUME HOOD IS TURNED ON.

5. FAN TO BE SELECTED WITH SIDE WALL INLET.

DIFFUSER AND GRILLE SCHEDULE

TAG SYSTEM MFR MODEL MATERIAL DESCRIPTION FACE SIZE

(IN)

NECK

SIZE (IN)

MAX CFM REMARKS

1S SUPPLY AIR PRICE SCD STEEL T-BAR MOUNTED SQUARE DIFFUSER 24x24 8Ø 280 1,3

2S SUPPLY AIR PRICE SCD STEEL SURFACE MOUNTED SQUARE DIFFUSER 12x12 8Ø 250 2,3

3S SUPPLY AIR PRICE ASCD ALUM. SURFACE MOUNTED SQUARE DIFFUSER 12x12 8Ø 250 2,3

4S NOT USED

5S SUPPLY AIR PRICE 510 STEEL SURFACE MOUNTED RECTANGULAR DIFFUSER 8x6 8x6 180 2,3

6S SUPPLY AIR PRICE 510 STEEL SURFACE MOUNTED RECTANGULAR DIFFUSER 12x8 12x8 400 2,3

7S SUPPLY AIR PRICE 510 STEEL SURFACE MOUNTED RECTANGULAR DIFFUSER 20x16 20x16 1040 2,3

1R RETURN AIR PRICE 530 STEEL T-BAR MOUNTED RECTANGULAR GRILLE 24x12 24x12 535 1,3

2R RETURN AIR PRICE 530 STEEL SURFACE MOUNTED SQUARE GRILLE 12x12 12x12 240 2,3

3R RETURN AIR PRICE 530 STEEL SURFACE MOUNTED SQUARE GRILLE 24x16 24x16 1000 2,3

1E EXHAUST AIR PRICE 530 STEEL T-BAR MOUNTED RECTANGULAR GRILLE 24x12 24x12 530 1,3

2E EXHAUST AIR PRICE 530 STEEL SURFACE MOUNTED RECTANGULAR GRILLE 8x8 8x8 130 2,3

3E EXHAUST AIR PRICE 530 STEEL SURFACE MOUNTED RECTANGULAR GRILLE 16x12 16x12 475 2,3

4E EXHAUST AIR PRICE 530 STEEL SURFACE MOUNTED RECTANGULAR GRILLE 18x14 18x14 640 2,3

5E EXHAUST AIR PRICE 530 STEEL SURFACE MOUNTED RECTANGULAR GRILLE 24x16 24x16 1000 2,3

6E EXHAUST AIR PRICE 630 ALUM. SURFACE MOUNTED SQUARE GRILLE 8x8 8x8 160 2,3

7E EXHAUST AIR PRICE 630 ALUM. SURFACE MOUNTED SQUARE GRILLE 12x12 12x12 360 2,3

1. LAY-IN BORDER TYPE FOR T-BAR CEILING.

2. SURFACE MOUNT BORDER TYPE FOR HARD-LID CEILING OR DIRECT DUCT MOUNTING.

3. PROVIDE GRILLE/DIFFUSER WITH FILTER FRAME. CONTRACTOR TO FIELD INSTALL MESH 80 SCREEN ON GRILLE/DIFFUSER.

ROOF HOOD SCHEDULE

TAG LOCATION SERVES MANUFACTURER/MODEL TYPE AIRFLOW

(CFM)

THROAT SIZE

(IN)

THROAT AREA

(SF)

THROAT

VELOCITY

(FPM)

PRESS

DROP

(IN WC)

UNIT

WT.

(LBS)

REMARKS

RC-5 ROOF AHU-5

GREENHECK/

GRSI

INTAKE 155 8 0.37 419 0.028 7 1

RC-6 ROOF AHU-6

GREENHECK/

GRSI

INTAKE 260 8 0.37 703 0.028 7 1

RC-7 ROOF AHU-7

GREENHECK/

GRSI

INTAKE 150 8 0.37 405 0.028 7 1

RC-8 ROOF AHU-8

GREENHECK/

GRSI

INTAKE 100 8 0.37 270 0.013 7 1

1. PROVIDE ROOF CAP WITH INSECT SCREEN.

2. PROVIDE ROOF CAP WITH GPF ROOF CURB OR EQUIVALENT.

VENTILATION HOOD SCHEDULE

TAG MFR

EXHAUST

MODEL

LENGTH WIDTH HEIGHT

CFM

VELOCITY MOUNTING HOOD VENT OUTLET OUTLET WEIGHT

FUNCTION (IN) (IN) (IN) (FPM) HEIGHT MATERIAL MATERIAL LOCATION SIZE (LBS) NOTES

VH-1 GREENHECK TYPE II HOOD GD1 48 18 12 300 50 84" 430 STAINLESS STEEL SINGLE WALL SS TOP 12" RND 70 1

1. PROVIDE WITH CONDENSATE DRAIN ON LEFT SIDE AND 3" REAR AIR SPACE.

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

CEI PROJ. NO.

COFFMAN ENGINEERSC

A

B

C

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

USDA/APHIS

CONTAINMENT FACILITY

BUILDING 6403

MOORE AIR BASE

EDINBURG, TEXAS

COFFMAN PROJECT # 212431

/1

/2

:3

:0

P

M

10/17/2025

PJTM

DJP

212431

M-701

MECHANICAL

SCHEDULES

FINAL TURNOVER

REV DATE DESCRIPTION

1 08/12/26 ADDENDUM #1

2 08/19/26 ADDENDUM #2

10-14-25

AIR-COOLED CHILLER SCHEDULE

TAG LOCATION SERVES

MANUFACTURER/

MODEL

COMPRESSOR CAPACITY

CIRCUIT

COND.

TEMP.

FLUID FLOW

(GPM)

EWT

(F)

LWT

(F)

WPD

(FT)

EER

KW/

TON

AMBIENT

(F)

REF.

UNIT

WT.

(LBS)

SIZE

LxWxH

UNIT POWER REQUIREMENTS

REMARKS

QUANTITY TYPE COOLING

(TONS)

OUTPUT

(kW) VOLTS Ø MCA MOCP

CHLR-1 OUTSIDE

BLDG 6403 AIR

HANDLING UNITS

YORK/

YLAA0089SJ17XF

6 SCROLL 67.25 236.5 2 140 12% PG 100 55 40 7.18 7.3 1.541 112 R454B 4,517 116"x89"x90" 208 3 424 450 1-11

CHLR-2 OUTSIDE

BLDG 6403 AIR

HANDLING UNITS

YORK/

YLAA0089SJ17XF

6 SCROLL 67.25 236.5 2 140 12% PG 100 55 40 7.18 7.3 1.541 112 R454B 4,517 116"x89"x90" 208 3 424 450 1-11

1. PROVIDE WITH UNIT MOUNTED REPLACEABLE CORE FILTER DRIERS AND MOISTURE SENSORS (SIGHT GLASS) FOR EACH CIRCUIT.

2. PROVIDE INTEGRATED CONDENSER CONTROLS WITH ABILITY TO CYCLE UP TO 7 INDIVIDUAL CONDENSER FANS ON EACH REFRIGERATION CIRCUIT.

3. PROVIDE INTEGRATED AMBIENT AIR TEMPERATURE MONITORING AND FLOATING HEAD PRESSURE CONTROLS BASED ON INDIVIDUAL FAN CYCLING.

4. PROVIDE FACTORY-INSTALLED LOW AND HIGH SIDE OVER PRESSURE RELIEF VALVES.

5. PROVIDE WITH MINIMUM LOADING CONTROL DOWN TO 10% CAPACITY.

6. PROVIDE WITH SUCTION SERVICE VALVES.

7. PROVIDE WITH NON-FUSED DISCONNECT.

8. PROVIDE WITH BACNET COMMUNICATION OPTION.

9. PROVIDE WITH CHILLED WATER FLOW SWITCH.

10. PRIMARY PUMPS ARE SEPERATE FROM CHILLER AND SHOWN ON PUMP SCHEDULE.

11. PROVIDE WITH TWO INDEPENDENT REFRIGERANT CIRCUITS.

STEAM BOILER SCHEDULE

TAG LOCATION SERVES

MANUFACTURER/

MODEL

MIN.

INPUT

(MBh)

MAX.

INPUT

(MBh)

REQ'D

OUTPUT

(lb/hr)

CONNECTIONS (IN) GAS INLET

SUPPLY

(IN WC)

UNIT POWER

REQUIREMENTS

UNIT

WT.

(LBS)

REMARKS

WATER DRAIN RELIEF

FUEL

GAS

HPS @

80PSI

HPS @

20PSI

GAS

VENT VOLTS Ø FLA

B-1 BOILER ROOM 111

AUTO CLAVE/

LAB STEAM

FULTON/

VSRT-15

100 600 200 1 3 3/4 1 1 3/4 6 3 120 1 27 3850 1, 2, 3, 4, 5, 6, 7, 8, 9, 10

1. PROVIDE WITH CARBON STEEL FEEDWATER SYSTEM.

2. PROVIDE WITH BLOWDOWN TANK WITH THERMOSTATIC COOLING KIT.

3. PROVIDE WITH CALCITE FILTER.

4. PROVIDE WITH PREHEAT KIT.

5. BOILER TO BE PROVIDED AS PACKAGED SKID FROM FACTORY WITH EXTERNAL EQUIPMENT PREPIPED AND WIRED.

6. TRIM STEAM OUT OF BOILER DOWN TO 80 PSI. TAP 20 PSI LINE OFF OF PIPING TO PREHEAT KIT FOR LOWER PRESSURE EQUIPMENT.

7. PROVIDE BOILER WITH INTEGRAL CONTROLS. CONNECT BOILER TO BUILDING DDC AND MOORE AIR BASE NIAGRA BAS SYSTEM.

8. CO DETECTION IN BOILER ROOM PROVIDED IN LOCATIONS SHOWN ON ENLARGED PLAN.

9. PROVIDE WITH ASME CSD-1 CONTROLS AND COMPLIANT BOILER SHUTOFF SWITCH. SEE PLANS FOR SWITCH LOCATION.

10. SEE DETAIL 04/A-565 FOR BOILER FLUE ROOF PENETRATION.

PUMP SCHEDULE

TAG LOCATION SERVES

MANUFACTURER/

MODEL

TYPE FLOW

(GPM)

HEAD

(FT)

HP

PUMP

SPEED

(RPM)

UNIT POWER

REQUIREMENTS

UNIT

WT.

(LBS)

FLUID REMARKS

VOLTS Ø FLA

CHWP-1 MECH YARD

CHILLER

PRIMARY LOOP

TACO/

2009D

INLINE 100 30 2 1160 208 3 - 275

12% PROPYLENE

GLYCOL

CHWP-2 MECH YARD

CHILLER

PRIMARY LOOP

TACO/

2009D

INLINE 100 30 2 1160 208 3 - 275

12% PROPYLENE

GLYCOL

CHWP-3 MECH YARD

CHILLED WATER

SECONDARY LOOP

TACO/

2007D

INLINE 100 50 3 1760 208 3 - 200

12% PROPYLENE

GLYCOL

1, 2, 3

CHWP-4 MECH YARD

CHILLED WATER

SECONDARY LOOP

TACO/

2007D

INLINE 100 50 3 1760 208 3 - 200

12% PROPYLENE

GLYCOL

1, 2, 3

1. PROVIDE PUMPS WITH SUPPORT STAND.

2. CHILLED GLYCOL PUMPS OPERATE ON DEMAND FROM CHILLER. PUMPS ARE REDUNDANT.

3. PUMPS WITH VFDS SHALL BE BALANCED BETWEEN 55-60HZ. VFD SHALL NOT BE USED TO MANUALLY OR AUTOMATICALLY BALANCE THE SYSTEM.

GLYCOL FEEDER SCHEDULE

TAG LOCATION SERVES MANUFACTURER/ MODEL

TANK

CAPACITY

(GAL)

CONN

(IN)

UNIT POWER

REQUIREMENTS FLUID

UNIT

WT.

(LBS)

REMARKS

HP VOLTS Ø

GF-1 ELECTRICAL 113

CHILLED WATER

LOOP

AXIOM/

DMF300

17 1/2 - 120 1

12% PROPYLENE

GLYCOL

150 1,2

1. FEEDER LOOP SHALL BE CARBON STEEL RATED FOR 100 PSI AND 180°F.

2. PROVIDE WITH PAINTED STEEL STAND AND BACNET COMMUNICATIONS CARD (READ/WRITE).

EXPANSION/BUFFER TANK SCHEDULE

TAG LOCATION SERVES

MANUFACTURER/

MODEL

TYPE

SYSTEM

VOLUME

(GAL)

LOW

TEMP. (F)

HIGH

TEMP. (F)

REQ'D VOLUME (GAL) MAX WORKING

PRESS. (PSIG)

CONN.

SIZE (IN)

UNIT

WT.

(LBS)

FLUID REMARKS

TANK ACCEPTANCE

ET-1 MECH YARD

CHILLED

WATER LOOP

TACO/

CBX84-125

BLADDER

EXPANSION

575 40 115 22 12 32 3/4 205

12% PROPYLENE

GLYCOL

BT-1 MECH YARD

CHILLED

WATER LOOP

TACO/

BTH0300F4-150NN

- 575 40 115 300 - - 3 3322

12% PROPYLENE

GLYCOL

1. CHARGE TANKS TO SPECIFIED PRESSURE PRIOR TO FILLING THE PIPING SYSTEM. RECORD CHARGE PRESSURE ON TANK.

AIR SEPARATOR SCHEDULE

TAG LOCATION SERVES

MANUFACTURER/

MODEL

TYPE PIPE SIZE

(IN)

FLOW

(GPM)

WPD (FT)

UNIT

WT.

(LBS)

FLUID REMARKS

AS-1 MECH YARD

CHILLED

WATER LOOP

TACO/

4903AD-125

AIR/DIRT 3 100 0.8 85

12% PROPYLENE

GLYCOL

1. ASME STAMPED 150 PSI AT 240° F

VIBRATION CONTROL

ITEM / TAG ISOLATOR REQUIREMENTS CONNECTIONS

AIR-COOLED CHILLER (TYP.) NR FLEXIBLE PIPE CONNECTIONS

INLINE PUMP (TYP.) NR EXPANSION JOINT CONNECTION

EXPANSION TANK / ET-1 NR NR

BUFFER TANK / BT-1 NR NR

AIR SEPARATOR / AS-1 NR NR

GLYCOL FEEDER / GF-1 NR NR

ENERGY RECOVERY UNIT / ERV-1 NR FLEXIBLE DUCT AND PIPE CONNECTIONS

AIR HANDLING UNIT (TYP.) NR FLEXIBLE DUCT AND PIPE CONNECTIONS

AIR CURTAIN (TYP.) NR NR

ROOF CAP (TYP.) NR NR

AIR CONTROL VALVE (TYP.) NR NR

INLINE EXHAUST FAN / EF-3 NR FLEXIBLE DUCT CONNECTIONS

ROOF EXHAUST FAN (TYP.) NR NR

FUME EXHAUST FAN / EF-12 NR FLEXIBLE DUCT CONNECTIONS

FUME HOOD / FH-1 NR NR

BOILER / B-1 NR NR

VENTILATION HOOD / VH-1 NR NR

SEISMIC DESIGN CRITERIA

SEISMIC DESIGN CATEGORY = A

SITE CLASS = D

RISK CATEGORY = II

BUILDING SEISMIC IMPORTANCE FACTOR, I = 1.0

DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS (0.2 SECOND), Sds = 0.04

DESIGN SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD, Sd1 = 0.016

NOTES

NR = NOT REQUIRED

TYP. = REFERS TO ALL EQUIPMENT OF THAT TYPE, SPECIFIC TAGS NOT LISTED

AIR CONTROL VALVE SCHEDULE

TAG SERVES MANUFACTURER/ MODEL MATERIAL SIZE ORIENTATION

DUCT HEATER AIRFLOW

FAIL

POSITION

CONTROL

TYPE

ELECTRICAL

REMARKS

TAG TYPE

MIN FLOW

CFM

CAPACITY

(KW)

MAX

CFM

MIN

CFM

APD

(" WC)

Ø VOLTAGE

SCV-1 LAB #1 SUPPLY

ANTEC/

VV

GALVANIZED

STEEL

114 HORIZONTAL EDH-1 SCR 700 9 1200 400 0.12 IN PLACE VARIABLE 1 208 1, 2

ECV-1 LAB #1 EXHAUST

ANTEC/

VV

GALVANIZED

STEEL

112 VERTICAL - - - - 600 0 0.12 OPEN VARIABLE - - 1, 2

SCV-2 LAB #2 SUPPLY

ANTEC/

VV

GALVANIZED

STEEL

112 HORIZONTAL EDH-2 SCR 400 4.5 600 400 0.12 IN PLACE VARIABLE 1 208 1, 2

ECV-2 LAB #2 EXHAUST

ANTEC/

VV

GALVANIZED

STEEL

112 VERTICAL - - - - 600 0 0.12 OPEN VARIABLE - - 1, 2

SCV-3 LAB #3 SUPPLY

ANTEC/

VV

GALVANIZED

STEEL

112 HORIZONTAL EDH-3 SCR 400 4.5 600 400 0.12 IN PLACE VARIABLE 1 208 1, 2

ECV-3 LAB #3 EXHAUST

ANTEC/

VV

GALVANIZED

STEEL

112 VERTICAL - - - - 600 0 0.12 OPEN VARIABLE - - 1, 2

SCV-4 AUTOCLAVE SUPPLY

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL - - - - 600 0 0.12 IN PLACE VARIABLE - - 1, 3

ECV-4

AUTOCLAVE GENERAL

EXHAUST

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL - - - - 100 0 0.12 OPEN VARIABLE - - 1, 3

SCV-5 WOMEN'S DRESSING/TR

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL EDH-5 SCR 250 2 250 0 0.12 IN PLACE VARIABLE 1 208 1, 3

ECV-5 WOMEN'S DRESSING/TR

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL - - - - 250 0 0.12 OPEN CONSTANT - - -

SCV-6 MEN'S DRESSING/TR

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL EDH-6 SCR 250 2 250 0 0.12 IN PLACE VARIABLE 1 208 1, 3

ECV-6 MEN'S DRESSING/TR

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL - - - - 280 0 0.12 OPEN CONSTANT - - -

SCV-7 PASSAGE/VEST

ANTEC/

VV

GALVANIZED

STEEL

108 HORIZONTAL - - - - 130 0 0.12 IN PLACE CONSTANT - - -

ECV-7 CORRIDOR

ANTEC/

VV

GALVANIZED

STEEL

112 HORIZONTAL - - - - 560 0 0.12 OPEN CONSTANT - - -

1. AIR CONTROL VALVE PROVIDED WITH NECESSARY CONTROL MODULE TO MEASURE AND ADJUST TO MAINTAIN SET ROOM PRESSURIZATION.

2. VALVE SHALL BE PROVIDED WITH FAST ACTING ACTUATOR CAPABLE OF CLOSING WITHIN 2 SECONDS OF SIGNAL.

3. VALVE SHALL BE PROVIDED WITH STANDARD ACTUATOR.

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

CEI PROJ. NO.

COFFMAN ENGINEERSC

A

B

C

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

USDA/APHIS

CONTAINMENT FACILITY

BUILDING 6403

MOORE AIR BASE

EDINBURG, TEXAS

COFFMAN PROJECT # 212431

/1

/2

:3

:0

P

M

10/17/2025

PJTM

DJP

212431

M-702

MECHANICAL

SCHEDULES

FINAL TURNOVER

REV DATE DESCRIPTION

1 08/12/26 ADDENDUM #1

2 08/19/26 ADDENDUM #2

10-14-25

Sheets
M-701 - MECHANICAL SCHEDULES
M-702 - MECHANICAL SCHEDULES

File details come from the government source that posted it. Updated .