Attachment 1 to Addendum 1_Drawings.pdf
PDF 7 MB Posted
- Attached to
- Renovate Building 6403 Containment Lab
- Solicitation number
- 12639526Q0184
About this file
This document is a comprehensive set of construction design drawings and specifications for the USDA APHIS Containment Facility Building 6403 renovation at Moore Air Base in Edinburg, Texas.
The project involves complete mechanical, plumbing, and electrical system replacement and upgrades to an aging containment facility. The mechanical scope includes replacement of chilled water systems with air-cooled chillers using 12% glycol freeze protection, removal and replacement of 12 air handling units with 8 new units, replacement of 10 exhaust fans with 8 new units, new DDC controls integrating with campus-wide systems, steam boiler replacement, and removal of abandoned piping. Laboratory modifications include new fume hoods with emergency showers, variable volume 100% outside air makeup air units with energy recovery, and new plumbing fixtures with point-of-use instant water heaters. The plumbing work encompasses new chilled water and steam/condensate piping throughout, bathroom remodeling with new fixtures, floor drains, and trap primer systems. The electrical scope involves replacement of the entire electrical distribution system, new lighting and power circuits, new mechanical equipment disconnects and feeders, fire alarm system modifications, and access control systems. The facility is designated as a containment facility requiring specialized sealing and penetration requirements for pipes, conduits, electrical outlets, light fixtures, and joints to prevent pest infiltration. Construction documents include detailed floor plans, equipment schedules, control diagrams, mechanical piping schematics, electrical one-line diagrams, and demolition plans. The project appears to be in the final design phase with complete turnover documentation dated August 2026 and addendum updates through October 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12639526Q0184-0005.pdf | ||
| Attachment 2 to addendum 3_specs.pdf | ||
| Attachment 1 to addendum 3_dwgs.pdf | ||
| 12639526Q0184-0004.pdf | ||
| First asbestos test results.pdf | ||
| A04_Attachment 5_Price Schedule for Add Alternates.docx | DOCX document | |
| 12639526Q0184-0003.pdf | ||
| Attachment 2 to Addendum 2_drawings.pdf | ||
| USDA Building 6403 RFI Log.xlsx | XLSX spreadsheet | |
| Attachment 1 to Addendum 2_specs.pdf | ||
| 12639526Q0184-0002.pdf | ||
| RFIs and Responses.docx | DOCX document | |
| USDA_Building_6403_RFI_Log.xlsx | XLSX spreadsheet | |
| 12639526Q0184-0001.pdf | ||
| Attachemnt 2 to Addendum 1_Specs.pdf | ||
| 6403 Bldg Ronovation Walkthrough Sign In Sheet.pdf | ||
| Attachment 5_Price Schedule for Add Alternates.docx | DOCX document | |
| 12639526Q0184.docx | DOCX document | |
| Attachment 4_Federal Construction Wage Rates_Hidalgo County.txt | TXT text file | |
| Attachment 2_Specifications.pdf | ||
| Attachment 3_Drawings.pdf | ||
| Attachment 1_Statement of Work.doc | DOC document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
2:
:1
PM
10/17/2025
HENRY
HIGHFIELD
8050.07
G-000
COVER SHEET
FINAL TURNOVER
NUMBER TITLE
GENERAL
G-000 COVER SHEET
G-001 GENERAL NOTES
G-002 ACCESSIBILITY STANDARDS
LIFE SAFETY
LS101 FIRST FLOOR LIFE SAFETY PLAN
ARCHITECTURE
A-001 SYMBOLS & ABBREVIATIONS
A-002 TYPICAL MOUNTING HEIGHTS AND CLEARANCES
AD101 DEMOLITION FLOOR PLAN
AD110 DEMOLITION ROOF PLAN
AD111 DEMOLITION REFLECTED CEILING PLAN
A-101 FIRST FLOOR PLAN
A-110 ROOF PLAN
A-111 FIRST FLOOR REFLECTED CEILING PLAN
A-201 BUILDING ELEVATIONS
A-211 BUILDING SECTIONS
A-301 WALL SECTIONS
A-302 WALL SECTIONS
A-401 ENLARGED PLANS & ELEVATIONS - LABORATORY 1
A-402 ENLARGED PLANS & ELEVATIONS - LABORATORY 2
A-403 ENLARGED PLANS & ELEVATIONS - LABORATORY 3
A-405 ENLARGED PLAN AND ELEVS - RESTROOMS
A-406 INTERIOR ELEVATIONS AND DETAILS
A-410 INTERIOR ELEVATIONS
A-420 SHOWER DETAILS
A-501 PARTITION TYPES
A-505 CASEWORK DETAILS
A-506 STAINLESS STEEL CASEWORK
A-550 INTERIOR WALL PARTITION TYPICAL DETAILS
A-560 WALL TYPICAL DETAILS
A-561 TYPICAL DETAILS
A-565 TYPICAL ROOF DETAILS
A-566 TYPICAL ROOF DETAILS
A-567 EXTERIOR ROOF DETAILS
A-591 OPENING DETAILS
A-601 DOOR SCHEDULE
A-603 FINISH SCHEDULE
A-604 FINISH MATERIAL LEGEND
A-801 CEILING DETAILS
A-802 CEILING DETAILS
USDA APHIS MOORE AB - BUILDING 6403 RENOVATION
ARTHROPOD CONTAINMENT FACILITY
22675 N MOOREFIELD RD
EDINBURG, TEXAS 78541
AREA MAP
VICINITY MAP
PROJECT
LOCATION
PROJECT
LOCATION
CONSULTANT TEAM
ARCHITECTURAL:
KZF DESIGN
700 BROADWAY ST.
CINCINNATI, OH 45202
CONTACTS:
MATTHEW KING
MATTHEW.KING@KZF.COM
DANIELLE HENRY
DANIELLE HENRY@KZF.COM
ENGINEERING:
COFFMAN ENGINEERS
221 N. WALL STREET, SUITE 500
SPOKANE, WA 99201
CONTACTS:
MECHANICAL:
TRACI HANEGAN
TRACI.HANEGAN@COFFMAN.COM
PARKER MATTHEWS
PARKER.MATTHEWS@COFFMAN.COM
ELECTRICAL
MATTHEW VERHEUL
MATTHEW.VERHEUL@COFFMAN.COM
KURT NIVEN
KURT.NIVEN@COFFMAN.COM
PLUMBING
P-001 PLUMBING LEGENDS AND ABBREVIATIONS
PD101 UNDERSLAB PLUMBING DEMO PLAN
PD102 PLUMBING DEMO PLAN
P-101 UNDERSLAB PLUMBING PLAN
P-102 PLUMBING PLAN
P-401 ENLARGED PLUMBING PLANS
P-501 PLUMBING DETAILS
P-701 PLUMBING SCHEDULES
NUMBER TITLE
MECHANICAL
M-001 GENERAL MECHANICAL NOTES & ABBREVIATIONS
MD101 MECHANICAL DEMO PLAN
MD102 MECHANICAL PIPING DEMO PLAN
MD110 MECHANICAL DEMO ROOF PLAN
M-100 MECHANICAL ZONE PLAN
M-101 MECHANICAL PLAN
M-102 MECHANICAL PIPING PLAN
M-110 MECHANICAL ROOF PLAN
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-601 MECHANICAL DIAGRAMS
M-602 MECHANICAL DIAGRAMS
M-603 MECHANICAL DIAGRAMS
M-701 MECHANICAL SCHEDULES
M-702 MECHANICAL SCHEDULES
M-703 MECHANICAL SCHEDULES
ELECTRICAL
E-001 ABBREVIATIONS, GENERAL SYMBOLS, AND SHEET INDEX
E-002 GENERAL NOTES
ED101 DEMOLITION SITE PLAN - ELECTRICAL
ED111 DEMOLITION FLOOR PLAN - LIGHTING
ED121 DEMOLITION FLOOR PLAN - ELECTRICAL
ED122 DEMOLITION ROOF PLAN - ELECTRICAL
ED601 ONE-LINE - DEMO
ED721 EXISTING PANEL SCHEDULES
ED722 EXISTING PANEL SCHEDULES
E-101 SITE PLAN - ELECTRICAL
E-111 FIRST FLOOR PLAN - LIGHTING
E-121 FIRST FLOOR PLAN - POWER
E-122 ROOF PLAN - ELECTRICAL
E-131 FIRST FLOOR PLAN - SYSTEMS
E-132 ENLARGED FIRST FLOOR PLAN - SYSTEMS
E-601 ONE-LINE - NEW
E-701 LIGHTING SCHEDULE
E-711 EQUIPMENT CONNECTION SCHEDULE
E-721 REVISED PANEL SCHEDULES
E-722 REVISED PANEL SCHEDULES
DRAWING INDEX
N
REV DATE DESCRIPTION
01 8/12/26 ADDENDUM 1
12639526Q0184, Amendment 0001
PROJECT GENERAL NOTES
A.
B.
a.
b.
c.
d.
e.
f.
g.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
V.
W.
X.
ALL WORK SHOWN ON THESE DRAWINGS IS TO BE BY THE CONTRACTOR UNLESS
INDICATED OTHERWISE. CONTRACTOR TO VISIT SITE PRIOR TO BIDDING TO BECOME
FAMILIAR WITH EXISTING CONDITIONS.
DIMENSIONING:
DO NOT SCALE DRAWINGS - DIMENSIONS ON DRAWINGS WILL TAKE
PRECEDENCE OVER SCALED DIMENSIONS
LARGE SCALE DETAILS GOVERN OVER SMALLER SCALE DRAWINGS UNLESS
NOTED OTHERWISE
REFER TO ENLARGED PLANS FOR DIMENSIONS, CASEWORK, MATERIALS AND
WALL TYPES, UNLESS OTHERWISE SHOWN
ALL DIMENSIONS SHALL BE VERIFIED AND COORDINATED WITH ALL OF THE
WORK OF ALL TRADES
ALL NEW WALLS ARE DIMENSIONED FROM FACE OF STUD/MASONRY TO FACE
OF STUD/MASONRY UNLESS NOTED OTHERWISE
DIMENSIONS FROM EXISTING WORK ARE FROM FINISHED FACE OF WALLS OR
ITEMS
ALL DIMENSIONS SHALL BE VERIFIED & COORDINATED WITH ALL OF THE WORK
OF ALL TRADES.
THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS SHOWN ON THE
DRAWINGS AND AT THE JOB SITE AND NOTIFY THE ARCHITECT OF ALL DISCREPANCIES,
OMISSIONS AND CONFLICTS BEFORE BIDDING. THE CONTRACTOR SHALL VISIT THE SITE
AND BE KNOWLEDGEABLE OF CONDITIONS THEREON. HE OR SHE SHALL INVESTIGATE,
VERIFY, AND BE RESPONSIBLE FOR ALL CONDITIONS OF THE PROJECT AND SHALL
NOTIFY THE ARCHITECT OF ANY SITE CONDITIONS REQUIRING MODIFICATION BEFORE
PROCEEDING WITH THE WORK.ANY DETAILS, SYSTEMS, OR MATERIALS
(ARCHITECTURAL, ENGINEERING, ETC.) WHICH ARE PROPOSED TO BE CHANGED MUST
FIRST BE REVIEWED BY THE ARCHITECT, PRIOR TO BIDDING- NO SUBSTITUTIONS OR
DEVIATIONS FROM THE CONTRACT DOCUMENTS WILL BE ALLOWED WITHOUT PRIOR
WRITTEN APPROVAL FROM THE ARCHITECT AFTER BIDS ARE RECEIVED.
DIFFERING TRADE CONTRACTORS TO COORDINATE ALL BUILT-IN FIXTURES /
EQUIPMENT AND SUPPLY ALL NECESSARY INFORMATION FOR CUT-OUTS TO BE
PERFORMED.
THE ARCHITECTURAL AND ENGINEERING DRAWINGS ARE OF EQUAL IMPORTANCE IN
DEFINING THE WORK OF THE CONTRACT DOCUMENTS, HOWEVER, ALL ENGINEERING
DRAWINGS ARE SUPPLEMENTARY TO THE ARCHITECTURAL DRAWINGS. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR(S) AND SUB-CONTRACTOR(S) TO COORDINATE
WORK WITH THE ARCHITECTURAL DRAWINGS PRIOR TO PROCEEDING WITH THE
INSTALLATION OF ANY MECHANICAL, PLUMBING, LOW VOLTAGE, OR ELECTRICAL WORK.
ANY DISCREPANCY BETWEEN THE ARCHITECTURAL AND ENGINEERING DRAWINGS AND
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR
CLARIFICATION PRIOR TO BIDDING- ANY WORK INSTALLED IN CONFLICT WITH THE
ARCHITECTURAL DRAWINGS SHALL BE CORRECTED BY THE CONTRACTOR AT THE
CONTRACTOR'S EXPENSE AND AT NO ADDITIONAL EXPENSE TO THE OWNER OR
ARCHITECT.
NOTES ARE NOT INTENDED TO BE STRICTLY LIMITED TO THE AREAS IDENTIFIED AND
SHALL APPLY ELSEWHERE AS APPLICABLE. ALL NOTES AND TYPICAL DETAILS ARE TO
BE REVIEWED AND APPLIED TO RELATED BUILDING COMPONENTS. DETAILS MARKED
"TYPICAL" SHALL APPLY IN ALL SIMILAR CASES UNLESS OTHERWISE NOTED ON THE
DRAWINGS. NOTES MAY APPEAR ON VARIOUS SHEETS FOR DIFFERENT SYSTEMS AND
MATERIALS; NOTES ON ANY ONE SHEET ARE TO BE APPLIED TO RELATED DRAWING
SHEETS AND DETAILS. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE
SHOWN. WHERE SPECIFIC DIMENSIONS, DETAILS, OR DESIGN INTENT CANNOT BE
DETERMINED, CONSULT THE ARCHITECT BEFORE PROCEEDING WITH THE WORK.
CONTACT BETWEEN DISSIMILAR METALS SHALL BE PROTECTED TO PREVENT GALVANIC
CORROSION.
FASTENERS USED IN PRESSURE TREATED WOOD SHALL HAVE THE APPROPRIATE
FACTORY COATINGS TO PREVENT CORROSION DUE TO MOISTURE AND / OR THE
WOOD'S CHEMICAL PRESERVATIVES.
CONTRACTOR TO MAINTAIN BUILDING EGRESS AT ALL TIMES DURING CONSTRUCTION.
ALL CONSTRUCTION DEBRIS SHALL BE PROMPTLY REMOVED FROM PREMISES AND
DISPOSED OF OR RECYCLED IN AN APPROPRIATE AND LEGAL MANNER.
PROVIDE ACCESS PANELS AS REQUIRED BY APPLICABLE CODES AND AS REQUIRED
FOR MECHANICAL AND PLUMBING EQUIPMENT AND DEVICES. ACCESS PANELS
LOCATED IN FINISHED AREAS SHALL BE FACTORY FINISHED OR FIELD PAINTED TO
MATCH ADJACENT SURFACES.
NOTIFY THE DESIGNER OF RECORD OF ANY PRODUCTS THAT ARE DISCONTINUED OR
ARE NO LONGER AVAILABLE. ALL PRODUCT SUBSTITUTIONS SHALL ONLY BE APPROVED
BY THE DESIGNER, AND SHALL BE ACCOMPANIED WITH COST DATA SHOWING THE
POTENTIAL SAVINGS TO THE OWNER.
THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING DELIVERY OF LONG LEAD
TIME PRODUCTS TO ENSURE THAT THE PROJECT IS COMPLETED ON SCHEDULE.
ELECTRICAL (SUB-) CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL DRAWINGS
INCLUDING INTERIOR ELEVATIONS. PROVIDE ADEQUATE POWER AND DATA OUTLETS
FOR ALL REFRIGERATORS, FREEZERS, MICROWAVES, COFFEE MACHINES, ICE
MACHINES, ETC. AT LOCATIONS WHERE DEVICES SHOWN ON DRAWINGS. IF
CONFLICT/ISSUES ARISE BETWEEN THESE DRAWINGS AND ELECTRICAL DRAWINGS,
COORDINATE BETWEEN ARCHITECT AND ELECTRICAL ENGINEER BEFORE BIDDING
PROJECT.
ALL ELECTRICAL BOXES, CONTROL BOXES, TECHNOLOGY BOXES, FIRE EXTINGUISHER
CABINETS, ETC. SHALL BE OFFSET SO AS NOT TO ALIGN IN PARTITIONS WITH FIRE AND /
OR STC RATINGS.
PLUMBING AND MECHANICAL (SUB-) CONTRACTORS ARE RESPONSIBLE FOR
REVIEWING ALL DRAWINGS INCLUDING INTERIOR ELEVATIONS. PROVIDE ADEQUATE
SUPPLY, DRAINING, COOLING, ETC FOR ALL REFRIGERATORS, FREEZERS,
MICROWAVES, COFFEE MACHINES, ICE MACHINES, ETC. AT LOCATIONS WHERE
DEVICES SHOWN ON DRAWINGS. IF CONFLICT/ISSUES ARISE BETWEEN THESE
DRAWINGS AND ELECTRICAL DRAWINGS, COORDINATE BETWEEN ARCHITECT AND
MECHANICAL ENGINEER BEFORE BIDDING PROJECT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION AND CONTINUOUS
MAINTENANCE OF ALL WORK INCLUDING NEW AND EXISTING EQUIPMENT FROM
DAMAGE AND SHALL PROTECT THE OWNERS' PROPERTY FROM DAMAGE OR LOSS BY
DUST, DIRT, WATER, THEFT, FIRE OR ANY OTHER PHYSICAL DAMAGE IN CONNECTION
WITH THE CONTRACT. WORK SHALL BE COMPLETED DURING OCCUPANCY BY THE
OWNER AND PHASED IN A MANNER AS AGREED TO IN WRITING AND PHASING
DOCUMENTATION. ANY AREA OF WORK IN NEED OF ACCESS BY THE CONTRACTOR
BEYOND PHASED SCOPE AREA IS SHALL BE INFORMED TO THE OWNER PRIOR TO
INITIATION OF WORK INVOLVED.
THE ARCHITECT SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY, PRESENCE,
HANDLING, REMOVAL, DISPOSAL, OR EXPOSURE OF PEOPLE TO HAZARDOUS
MATERIALS IN ANY FORM, INCLUDING BUT NOT LIMITED TO ASBESTOS PRODUCTS,
POLYCHLORINATED BIPHENYL (PCB) OR OTHER TOXIC SUBSTANCES.
THE CONTRACTOR AND ALL SUBCONTRACTORS FOR EACH TRADE ARE ADVISED THAT
INFORMATION PERTINENT TO THEIR WORK MAY OCCUR IN OTHER PORTIONS OF THE
CONTRACT DOCUMENTS.
REFER TO ARCHITECTURAL, DEMOLITION & ENGINEERING DRAWINGS FOR ADDITIONAL
GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS.
DURING THE COURSE OF THE PROJECT, THE CONTRACTOR SHALL BE SOLELY AND
COMPLETELY RESPONSIBLE FOR CONDITIONS AT AND ADJACENT TO THE JOB
INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE
WORK. THE CONTRACTOR SHALL PROVIDE ALL LIGHTS, SIGNS, BARRICADES, OR OTHER
DEVICES NECESSARY TO PROVIDE FOR PUBLIC SAFETY. THIS REQUIREMENT SHALL
APPLY CONTINUOUSLY AND IS NOT LIMITED TO NORMAL WORKING HOURS. THE OWNER
AND/OR THE ARCHITECT EXERCISE NO CONTROLS OVER THE SAFETY OR ADEQUACY
OF ANY EQUIPMENT, BUILDING COMPONENTS, SCAFFOLDING, FORMS OR OTHER WORK
AIDS USED IN OR ABOUT THE PROJECT, OR IN THE SUPERINTENDING OF THE SAME.
THE CONTRACTOR SHALL DEFEND, INDEMNIFY AND HOLD HARMLESS FROM ANY AND
ALL LIABILITY, REAL AND ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF
WORK ON THIS PROJECT. THE OWNER AND/OR ARCHITECT ARE NOT RESPONSIBLE
FOR SAFETY IN, ON OR ABOUT THE PROJECT SITE, NOR FOR COMPLIANCE BY THE
APPROPRIATE PARTY OF ANY REGULATIONS RELATING THERETO.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO TAKE EVERY MEASURE
NECESSARY TO COMPLY WITH ANY OWNER DUST CONTROL ORDINANCE.
CONTRACTOR TO PROVIDE OWNER PROJECT MANAGER AND CONTRACT ENGINEER
WITH ACCESS TO ALL WORK ON THE JOBSITE AT ALL TIMES; INCLUDING THE
NECESSARY SAFETY EQUIPMENT FOR ACCESS AND/OR ANY LADDERS, LIFTS,
SCAFFOLDING, ETC. NEEDED FOR ACCESS.
CONTRACTOR TO VERIFY IN FIELD EXISTING EQUIPMENT AND COORDINATE WITH
OWNER BEST PRACTICE IN PROTECTING EQUIPMENT FROM DAMAGE DURING WORK.
PROJECT SUMMARY
THE USDA CONTAINMENT BUILDING 6403 AT MOORE AIR BASE HAS
AGING EQUIPMENT AND BUILDING COMPONENTS IN NEED OF
REPLACEMENT. THE BUILDING LABORATORY SPACES REQUIRE
MODIFICATIONS TO FLOOR AREA, CABINETRY, AND VENTILATION FOR
OPERATIONAL REQUIREMENTS.
THE ITEMS TO BE INCLUDED IN THE BASE BID VS ALTERNATES ARE
IDENTIFIED THROUGHOUT THE BID DOCUMENTS AND LISTED HERE:
BASE BID:
FACILITY
REPLACE AIR-COOLED CHILLERS, CHILLED WATER PUMPS, AND
FACILITY CHILLED WATER PIPING.
REMOVE ALL 12 AIR HANDLING UNITS, REPLACE WITH 8 NEW.
REMOVE AND REPLACE ALL DUCTWORK, GRILLES, REGISTERS,
DIFFUSERS, AND OUTSIDE AIR ROOF CAPS.
REMOVE ALL 10 EXHAUST FANS, REPLACE WITH 8 NEW.
REPLACE ALL BUILDING DDC CONTROLS.
REPLACE STEAM BOILER SYSTEM INCLUDING STEAM AND
CONDENSATE PIPING THROUGHOUT FACILITY. RELOCATE THE
EXISTING FEEDWATER TREATMENT SYSTEM WITHIN THE
MECHANICAL ROOM.
REMOVE ABANDONED MECHANICAL PIPING THROUGHOUT THE
FACILITY (VACUUM AND RO WATER PIPING).
REPLACE ACOUSTIC CEILING TILE AND LIGHTING IN OCCUPIED
SPACES THROUGHOUT THE FACILITY, EXCEPT FOR THE 4 ROOMS
IDENTIFIED AS ALTERNATE 01.
REPLACE THE BUILDING ROOFING TO INCLUDE ROOF SOFFITS
AND GUTTERS. INSTALL NEW FALL PROTECTION RAIL ALONG
ROOF PERIMETER.
DOOR MODIFICATIONS AND REPLACEMENTS, DOOR HARDWARE
REPLACEMENTS, ACCESS CONTROL MODIFICATIONS TO INCLUDE
DOOR INTERLOCKS.
REMODEL ENTRY AND BATHROOM TO INCLUDE NEW FLOOR
LAYOUT, PLUMBING FIXTURES, DOOR LOCATIONS, CEILINGS,
FLOORS, AND LIGHTING.
INSTALL NEW AIR CURTAINS AT LABORATORY ACCESS POINTS.
LABS
REMODEL LABORATORY 114 AND INFILL EXISTING EMERGENCY
EXIT. INSTALL NEW FUME HOOD AND EMERGENCY SHOWER WITH
FLOOR DRAIN.
INSTALL NEW ENERGY RECOVERY MAKEUP AIR HANDLING UNIT
TO SERVE LABORATORY SPACES INCLUDING EXTERIOR
DUCTWORK, AIR CONTROL VALVES, AND DUCT HEATERS.
REPLACE FLOORING IN LAB ROOMS AND HEAD HOUSE.
REPLACE CASEWORK AND MODIFY ELECTRICAL IN LABORATORY
ROOMS 114, 101, AND 107. REPLACE SINKS AND INSTALL NEW
POINT-OF-USE INSTANT WATER HEATERS.
HEADHOUSE
INSTALL HOOD AND FAN OVER AUTOCLAVE
NEW FLOOR SINK AND DRAINAGE PIPING NEAR AHU-12. NEW RO
PIPE AND FAUCET TO HEADHOUSE SINK AND NEW DRINKING
FOUNTAIN/ BOTTLE FILLER.
ALTERNATE 01:
REPLACE FLOORING AND WALL BASE.
REFINISH TEST ROOM 108, TEST INTAKE 109, AUTOCLAVE 110B
AND PASSAGEWAY 110C WALLS AND DOOR FRAMES COMPLETE.
REPAIR DAMAGED CEILING IN TEST ROOM 108 PRIOR TO
RE-FINISHING.
REPLACE LIGHTING AND LIGHTING CONTROLS.
ALTERNATE 02:
DEMO EXTERIOR ELECTRICAL PANEL ‘GREENHOUSE’ AND
ELECTRICAL METER. SEE ELECTRICL DRAWING FOR
REQUIREMENTS.”
REPAINT ENTIRE FACILITY EXTERIOR MASONRY WALLS, SILLS,
HOLLOW METAL DOORS AND FRAMES. PROVIDE RE-FINISH PAINT
TO METAL FASCIA TRIM, GUTTERS, DOWNSPOUTS AND NEW
UTILITY RAILING AS NEEDED TO MATCH PRE-FINISH COLOR.
ALTERNATE 03:
REPAIR SIX ENVIRONMENTAL GROWTH CHAMBERS TO INCLUDE
NEW CONTROLS, PUMP STANDS, AND CONNECTIONS TO NEW
CHILLED WATER AND STEAM/CONDENSATE PIPING.
ALTERNATE 04:
REMOVE EXISTING FLUSH SOLID-CORE WD DOOR, WD FRAME AND
DOOR HARDWARE AT SOUTH WALL OF MAINTENANCE 105 AND
RE-INSTALL DOOR AND DOOR HARDWARE WITH NEW HM FRAME
AT NORTH WALL. INFILL WALL OPENING AND FINISH BOTH SIDES
TO MATCH ADJACENT.
PROJECT CONTAINMENT NOTES
THIS FACILITY IS A CONTAINMENT FACILITY. THERE ARE ADDITIONAL SEALING
REQUIREMENTS TO PREVENT THE ESCAPE OF INSECTS FOR ALL ROOMS EXCEPT RM
227 ELECTRICAL, RM 111 BOILER RM, RM 112 BREAK ROOM AND RM 116 STORAGE.
PIPE AND CONDUIT PENETRATIONS
CORE DRILLED OPENINGS: ANNULAR SPACE MUST BE PACKED WITH
FIRESTOP OR MINERAL WOOL BACKING MATERIAL.
SEALANT APPLICATION: APPLY A CONTINUOUS 1/4-INCH BEAD OF
SILICONE AROUND THE ENTIRE PIPE-TO-WALL INTERFACE ON THE
CLEAN SIDE.
ESCUTCHEON PLATES: INSTALL STAINLESS STEEL SPLIT-PLATES OVER
PENETRATIONS AND SEAL THE INNER AND OUTER RIMS. FILL THE
ENTIRE INTERIOR CAVITY OF THE PLATE WITH RTV SILICONE BEFORE
PRESSING IT FLUSH AGAINST THE DRYWALL, FORCING THE SEALANT TO
COMPRESS TIGHTLY AROUND THE PIPE.
ELECTRICAL OUTLETS AND SWITCHES
GASKET BACKING: INSTALL MOLDED RUBBER OR NEOPRENE (NOT
CLOSED-CELL FOAM) GASKETS BEHIND THE ELECTRICAL BOX AND
DEVICE FACEPLATES BEFORE SCREWING THEM TO THE WALL.
FACEPLATE SEALING: CAULK THE OUTER PERIMETER OF THE WALL
PLATE WITH CLEAR OR WHITE SILICONE. SEAL ALL FOUR SIDES FOR
AIRTIGHT CONTAINMENT.
CONDUIT SEALS: SEAL CONDUITS WITH EXPANDING FOAM OR SEALING
COMPOUND AT THE BOX AFTER WIRING HAS BEEN PULLED AND PRIOR
TO MOUNTING DEVICES.
LIGHT FIXTURES
FIXTURES: PROVIDE SEALED AND GASKETED LIGHTING FIXTURES, WITH
A MINIMUM RATING ISO 8.
HOUSING-TO-CEILING SEAL: APPLY A CLEANROOM GRADE, NEUTRAL-
CURE SILICONE AROUND THE PERIMETER FLANGE OF THE LIGHT
FIXTURE WHERE IT MEETS THE CEILING GRID OR DRYWALL.
ACCESS PANELS: ADD GASKETS TO ALL ACCESS PANEL SCREWS,
WHERE NOT ALREADY PROVIDED BY MANUFACTURER, FOR FIXTURE
AND LIGHTING CONTROL DEVICES INCLUDING REMOTE BALLASTS,
POWER PACKS AND RELAYS, OCCUPANCY SENSORS, ETC.
THERMOSTATS AND SENSORS
WALL MOUNTS: MOUNT TEMPERATURE, HUMIDITY, AND PRESSURE
SENSORS OVER A CLOSED-CELL GASKET PAD.
WIRE ACCESS: SEAL THE HOLE WHERE LOW-VOLTAGE WIRES
PENETRATE THE DRYWALL BEHIND THE THERMOSTAT USING PUTTY OR
CAULK.
PERIMETER BEADING: RUN A NEAT BEAD OF WHITE OR CLEAR SILICONE
AROUND THE SENSOR BODY WHERE IT TOUCHES THE WALL.
JOINTS AND CORNERS
JOINTS WALL-TO-CEILING/WALL: SEAL ALL VERTICAL AND HORIZONTAL
DRYWALL AND CEILING JOINTS WITH A SMOOTH, CONCAVE BEAD OF
STRUCTURAL SILICONE.
WALL-TO-WALL JOINTS: SEAL ALL VERTICAL AND HORIZONTAL DRYWALL
JOINTS WITH A SMOOTH, CONCAVE BEAD OF STRUCTURAL SILICONE.
FLOOR-TO-WALL AND CORNER TRANSITIONS
FLOOR-TO-WALL RUBBER BASE: INSTALL BASE 1/8 ” ABOVE FLOOR
MATERIAL. SEAL WITH CONTINUOUS BEAD OF POLY URETHANE
SEALANT AT TOP AND BOTTOM. APPLY A 100% SOLID, CONTINUOUS
BED OF ADHESIVE TO THE BACK OF THE BASE MATERIAL. DO NOT SPOT-
APPLY ADHESIVE.
FLOOR-TO-WALL TILE BASE: SEAL WITH CONTINUOUS BEAD OF POLY
URETHANE SEALANT AT TOP. APPLY A 100% SOLID, FULL BED OF
ADHESIVE TO THE BACK OF THE BASE MATERIAL. DO NOT SPOT-APPLY
ADHESIVE.
CASEWORK/COUNTERS: RUN A CONTINUOUS BEAD OF HIGH-
MOVEMENT POLYURETHANE SEALANT ALONG BOTH THE TOP
BACKSPLASH (COUNTER-TO-DRYWALL) AND ALONG CASEWORK EDGES
(BASE-TO-FLOOR/WALL) TO TRAP ANY PESTS TRAVELING INSIDE THE
WALL CAVITIES.
COVE BASE SEALING: STANDARD VINYL COVE BASE CREATES A
HOLLOW INSECT RUNWAY BEHIND THE WALL. AND IS NOT PERMITTED IN
CONTAINMENT AREAS. YOU MUST USE AN INTEGRAL POURED EPOXY
COVE OR A SEALED SOLID STRAIGHT RESILIENT BASE.
ADHESIVE STANDARD: APPLY A 100% SOLID, CONTINUOUS BED OF
ADHESIVE TO THE BACK OF THE BASE MATERIAL. DO NOT SPOT-APPLY
ADHESIVE.
TOP AND BOTTOM BEADS: RUN A CONTINUOUS BEAD OF HIGH-
MOVEMENT POLYURETHANE SEALANT ALONG BOTH THE TOP LIP (BASE-
TO-DRYWALL) AND THE BOTTOM LIP (BASE-TO-FLOOR) TO TRAP ANY
PESTS TRAVELING INSIDE THE WALL CAVITIES.
DATA AND LOW-VOLTAGE
CABLE BUNDLES: BUNDLED WIRES INSIDE CONDUITS CREATE
MINIATURE TUNNELS FOR INSECTS. SEPARATE THE WIRES SLIGHTLY AT
THE CONDUIT OPENING AND PACK THE SPACES BETWEEN INDIVIDUAL
STRANDS WITH NON-HARDENING DUCT-SEALING PUTTY.
HVAC, VENTS, AND RETURNS
SUPPLY AND EXHAUST GRILLES: SEE DRAWING NOTES FOR MESH
SCREENS AND FILTERS. APPLY SILICONE SEALANT AROUND FRAMES OF
ALL GRILLES.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
COORDINATE ALL DEMOLITION WORK WITH NEW WORK PLANS.
DO NOT COMMENCE DEMOLITION WORK IN ANY AREA UNTIL ALL
UTILITIES HAVE BEEN CAPPED, PLUGGED, DISCONNECTED, OR
OTHERWISE MADE SAFE FOR WORK TO PROCEED.
DO NOT CUT OR DRILL EXISTING FLOOR JOISTS, BEAMS,
COLUMNS, OR OTHER STRUCTURAL ELEMENTS, UNLESS
SPECIFICALLY INDICATED IN DRAWINGS. VERIFY ALL
STRUCTURE LOCATIONS PRIOR TO COMMENCEMENT OF WORK.
CONTRACTOR IS RESPONSIBLE FOR REPAIR OF ALL SURFACES
AFFECTED BY DEMOLITION OR NEW WORK CARRIED OUT BY ALL
TRADES. REFER MECHANICAL-PLUMBING-ELECTRICAL
DRAWINGS TO VERIFY ALL LOCATIONS WHERE WORK OCCURS.
CONTRACTOR IS TO PAINT ALL WALL SURFACES AFFECTED BY
DEMOLITION OR NEW WORK UNLESS OTHER FINISH IS
INDICATED: REPAINT-REFINISH IS TO RUN FROM CORNER-TO-
CORNER OF AFFECTED WALL UNLESS OTHER LIMIT FOR
REFINISH IS SHOWN.
WHERE EXISTING EQUIPMENT, PIPING, DUCTS, & SIMILAR ITEMS
ARE REQUIRED TO BE REMOVED, SUCH REMOVAL SHALL BE
COMPLETE, INCLUDING BUT NOT LIMITED TO, ANCHORS,
HANGERS, FOUNDATIONS & ACCESSORIES AFTER REMOVAL.
REPAIR, MAKE SMOOTH, MATCH ADJACENT SURFACES AND
PREP FOR NEW FINISH TREATMENT AT ALL LOCATIONS WHERE
DEMOLITION HAS OCCURRED.
REMOVE EXISTING FLOORING MATERIAL & BASE IN AREAS
SCHEDULED TO RECEIVE NEW FINISHES UNLESS OTHERWISE
INDICATED. PATCH AND/OR REPAIR DAMAGED WALL MATERIALS
TO PROVIDE SUITABLE SUBSTRATE FOR NEW BASE. REFER TO
LIST OF ALTERNATES FOR ADDITIONAL INFORMATION.
ALL FLOORS SHALL BE LEVEL AND FREE OF IRREGULARITIES TO
ASSURE CONSISTENT FLOOR HEIGHT.
PROTECT ALL EXISTING FINISHES, EQUIPMENT, FURNITURE AND
FURNISHINGS TO REMAIN ON SITE FROM DAMAGE BY
DEMOLITION AND NEW WORK. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL DAMAGE TO EXISTING CONSTRUCTION,
EQUIPMENT AND FURNITURE THAT NEEDS TO REMAIN ON-SITE.
DO NOT DISABLE OR DISRUPT BUILDING FIRE OR LIFE SAFETY
SYSTEMS. DO NOT CLOSE OR BLOCK EGRESS TO ANY EXIT, AND
PROVIDE TEMPORARY SIGNAGE FOR EXIT AND BUILDING
EGRESS.
PROVIDE TEMPORARY PROTECTION TO EXTERIOR WALLS
DURING REMOVAL OF EXTERIOR DOOR AND FRAMES,
MECHANICAL AND PLUMBING PENETRATIONS.
PROVIDE TEMPORARY ROOF PROTECTION DURING REMOVAL OF
EXISTING ROOF SYSTEM AND EXTERIOR SOFFITS FOR
REPLACEMENT, NEW AND EXISTING ROOF OPENINGS FOR
MECHANICAL AND PLUMBING PENETRATIONS OR PATCHING,
AND OTHER ROOF INSTALLATIONS.
PROVIDE FIRE STOPPING INSULATION, CAULKING, OR FIRESTOP
SYSTEM AS REQUIRED TO MAINTAIN EXISTING FIRE RATINGS
OF HORIZONTAL OR VERTICAL ASSEMBLIES.
ALL WORK AREAS SHALL BE CLEANED DAILY, AND
CONSTRUCTION MATERIALS SCHEDULED FOR DEMOLITION AND
NOT INDICATED TO BE SALVAGED OR REUSED SHALL BE
PROMPTLY REMOVED FROM PREMISES.
ALL CONTRACTORS ARE RESPONSIBLE FOR FOLLOWING
OWNER’S REGULATIONS FOR USE OF THE SITE AND BUILDING
ACCESS. CONTRACTORS ARE TO COORDINATE WITH OWNER ’S
CONSTRUCTION MANAGER FOR WORK SCHEDULING AND AREAS
OF THE SITE THAT MAY BE OCCUPIED BY OWNER DURING
CONSTRUCTION.
SALVAGE FIRE ALARM AND SAFETY DEVICES, BUILDING
TECHNOLOGY OR SECURITY DEVICES, WALL MOUNTED
FURNISHINGS, FIRE EXTINGUISHERS, SIGNAGE, OR ANY OTHER
WALL/CEILING EQUIPMENT OR FURNISHINGS ON SURFACES
AFFECTED BY WORK. INSPECT ALL SALVAGED MATERIALS
PRIOR TO STORAGE OR REINSTALLATION. MINOR DAMAGE
REQUIRING PAINT TOUCH-UP TO BE COMPLETED BEFORE
REINSTALLATION. SALVAGE MATERIALS OR EQUIPMENT NOT
REINSTALLED ARE TO BE HANDED OVER TO OWNER.
PROVIDE TEMPORARY FIRE EXTINGUISHERS ON SITE AS
NECESSARY FOR FIRE SAFETY.
DEMOLITION GENERAL NOTES
www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
2:
:5
PM
10/17/2025
HENRY
HIGHFIELD
8050.07
G-001
GENERAL NOTES
FINAL TURNOVER
REV DATE DESCRIPTION
01 8/12/26 ADDENDUM 1
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
A. ALL INTERIOR PARTITIONS ARE TYPE A3F UNLESS
INDICATED OTHERWISE. SEE SHEET A-501 FOR
PARTITION TYPES.
B. ROOM NUMBERS ARE FOR CONSTRUCTION PURPOSES
ONLY.
C. ALL DIMENSIONS ARE FROM FACE TO FACE OF FINISH
CONSTRUCTION UNLESS INDICATED OTHERWISE.
D. USE ONLY WRITTEN DIMENSIONS - DO NOT SCALE
DRAWINGS.
E. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS ON THE SITE PRIOR TO COMMENCING
WORK. ALL INQUIRIES AND DISCREPANCIES SHALL BE
DIRECTED TO THE ARCHITECT.
F. ALL WORK SHOWN ON THESE DRAWINGS IS TO BE BY
THE CONTRACTOR UNLESS OTHERWISE INDICATED.
INTERIOR FURNISHINGS AND EQUIPMENT SHOWN FOR
REFERENCE ONLY. ALL CONTRACTORS ARE
RESPONSIBLE FOR LAYING OUT EQUIPMENT PLANS TO
AVOID INTERFERENCES BETWEEN BUILDING
COMPONENTS AND WORK BY OTHERS.
DOOR FRAMES IN GYPSUM BOARD WALLS SHALL BE
LOCATED MINIMUM 4" FROM ADJACENT WALLS, UNLESS
OTHERWISE INDICATED OR REQUIRED BY HARDWARE.
PROVIDE AND COORDINATE BACKING PLATES AND/OR
BLOCKING FOR ALL WALL MOUNTED ITEMS OR SECURED
EQUIPMENT, WALL AND BASE CABINETS, SHELVING,
RAILINGS, GRAB BARS, TOILET ACCESSORIES, LADDERS,
DOOR STOPS, MIRRORS, VISUAL DISPLAY SURFACES,
PLUMBING FIXTURES, LIGHT FIXTURES, ETC.
REPLACE EXISTING GYPSUM BD IN SHOWERS AND
PROVIDE TYPE 'X' MOISTURE-RESISTANT GYPSUM
BOARD AT ALL EXPOSED GYPSUM BOARD PARTITIONS &
CEILINGS.
PROVIDE CEMENT BOARD TILE BACKING PANELS WHERE
WALL TILE FINISHES ARE SCHEDULED.
PROVIDE TYPE 'X' FIRE RATED GYPSUM BOARD AT ALL
FIRE RATED ASSEMBLIES.
PROVIDE ACOUSTICAL SEALANT AT ALL PENETRATIONS
THROUGH WALLS INDICATED TO RECEIVE SOUND BATT
INSULATION.
FINISH ALL GYPSUM BOARD JOINTS AND SCREW HEADS
AT ALL SURFACES EXPOSED TO PUBLIC VIEW.
OPENINGS IN WALLS AND SLABS SHALL BE TIGHT TO
PENETRATING OBJECT- FIRE STOP AS REQUIRED.
ALL OUTSIDE CORNERS AT GYPSUM BOARD SHALL HAVE
CONTINUOUS CORNER BEAD PER SPECIFICATIONS.
ALL EXPOSED GYPSUM BOARD EDGES (AND AS NOTED)
SHALL HAVE CONTINUOUS J-BEAD UNLESS NOTED
OTHERWISE
THIS FACILITY IS A CONTAINMENT FACILITY. THERE ARE
ADDITIONAL SEALING REQUIREMENTS TO PREVENT THE
ESCAPE OF INSECTS FOR ALL ROOMS EXCEPT RM 227
ELECTRICAL, RM 111 BOILER RM, RM 112 BREAK ROOM
AND RM 116 STORAGE. APPLY SEALANT AT ALL JOINTS
BETWEEN FINISH MATERIALS.
A-201
A-201
A-201
A-201
VESTIBULE
100A
WOMEN'S TR
102B
PASSAGE
103A
VEST
100B
MEN'S TR
104B
MAINTENANCE
WOMEN'S
DRESSING
102ALABORATORY
#2
MEN'S
DRESSING
104A LABORATORY
#3
MAIN
LABORATORY
#1
CORRIDOR
C101
EGC 6
EGC6
EGC 5
EGC5
EGC 4
EGC4
EGC 12
EGC12
EGC 11
EGC11
EGC 10
EGC10
PASSAGE
C103
MECH/ELEC
BREAK RM
STORAGE
EGC 3
EGC3
EGC 9
EGC9
EGC 2
EGC2
EGC 8
EGC8
EGC 1
EGC1
EGC 7
EGC7
PASSAGE
C104
TEST ROOM
TEST INTAKE
PASSWAY
110C
AUTOCLAVE
110B
BOILER
ROOM
SERVICE
PASSAGE
GH 5
GH 4
GH 3
GH 2
GH 1
ELECTRICAL
HEADHOUSE
CORR
C102
MECH
103B
EVS
104C
VEST
C105
A-211
A-410
N10F
A-402
A-401
A-403
A-410
FE
FE
N10F 11
A-211
A-211
107'-4"
'-0
'-3
4'-8" 18'-8" 30'-6" 13'-0" 26'-6" 18'-8" 4'-0"
'-6
'-2
'-4
'-8
17'-10" 80'-0" 18'-2"
116'-0"
6'-3" 10'-6" 4'-0" 10'-6" 4'-0" 10'-6" 4'-0" 10'-6" 4'-0" 10'-6" 5'-3"
'-9
7'- 4"
'-6
'-8
A-405
GH5 GH4 GH3 GH2 GH1 C105A
0E
0D
0C
0B
0A
EGC12 EGC11 EGC10
EGC9 EGC8 EGC7
C104
109B
110B.2 110C.2 110C.1
109A
108A 108B
EGC1EGC2EGC3106EGC4EGC5EGC6
110B.1
100A
C102A
FEC FEC
A04
A10
A10
A21 A21 A21 A21 A21
101 107
104D
104B102B
104C
C105B
C103
102C
A34
6'- 7"
A03
A03
A03
PROJECT BASE BID AREA, UNO
ALTERNATE #01:
REPLACE FLOOR FINISH AND WALL BASE
FINISH.
REFINISH TEST ROOM 108, TEST INTAKE
109, AUTOCLAVE 110B AND PASSAGEWAY
110C WALLS AND DOOR FRAMES
COMPLETE.
REPAIR DAMAGED CEILING IN TEST ROOM
108 PRIOR TO RE-FINISHING
REPLACE LIGHTING AND LIGHTING
CONTROLS.
REFER TO MEP DRAWINGS FOR
ADDITIONAL INFORMATION
ALTERNATE #02:
DEMO EXTERIOR GREENHOUSE
PANEL BD
PAINT ENTIRE FACILITY EXTERIOR
ALTERNATE 03:
REPAIR SIX ENVIRONMENTAL
GROWTH CHAMBERS TO INCLUDE
NEW CONTROLS, PUMP STANDS,
AND CONNECTIONS TO NEW
CHILLED WATER AND
STEAM/CONDENSATE PIPING.
A03
A03
A07 A13
A12A12A12A12A12A12
A13A13
A04
A08
A08
A3 F
102A
104A
100B.2103B
100B.1
A35 A35
A35
A36 A36 A36 A36 A36 A37
'-6
A38
ALTERNATE #04:
REMOVE EXISTING FLUSH SOLID-CORE WD
DOOR, WD FRAME AND DOOR HARDWARE AT
SOUTH WALL OF MAINTENANCE 105 AND
RE-INSTALL DOOR AND DOOR HARDWARE
WITH NEW HM FRAME AT NORTH WALL.
INFILL WALL OPENING AND FINISH BOTH
SIDES TO MATCH ADJACENT.
www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
1:
:2
PM
10/17/2025
HENRY
HIGHFIELD
8050.07
A-101
FIRST FLOOR PLAN
FINAL TURNOVER
DRAWING NOTES
GENERAL NOTES
A03 PATCH EXISTING WALL AND FINISH TO MATCH ADJACENT
A04 PROVIDE 1'-0" THICK CONCRETE PAD AT NEW CHILLER
UNITS - REFER TO MECHANICAL DWGS
A07 EXISTING EXPANSION JOINT. REPAIR AND REPLACE
COVER PLATE AND ASSOCIATED PARTS AS NECESSARY
AFTER NEW FLOOR FINISH - MATCH EXISTING.
A08 INFILL EXISTING DOUBLE WYTHE BRICK VENEER WALL
AND FINISH TO MATCH ADJACENT BRICK SIZE, PATTERN
AND WALL FINISH ON BOTH SIDES. TOOTH BRICK IN
PLACE AT FULL HEIGHT OF WALL INFILL.
A10 NEW DOOR, FRAME AND HARDWARE
A12 RE-CAULK EXISTING GREENHOUSE FRAME AT WALL AND
ROOF PERIMETER,
A13 RE-CAULK EXISTING EXPANSION JOINT AT WALL AND
ROOF PERIMETER, BOTH SIDES. REPLACE BACK ROD
WHERE MISSING OR DAMAGED.
A21 EXISTING GREENHOUSE UNIT
A34 NEW HI-LOW ELECTRIC WATER COOLER WITH BOTTLE
FILLER
A35 MECHANICAL AIR CURTAIN - REFER TO MECHANICAL
DWGS
A36 NEW MECHANICAL LOUVER
A37 EXISTING LOUVER TO REMAIN
A38 ALTERNATE 04. NEW DOOR ROOM 105.
ROOM SCHEDULE
NO. ROOM NAME
100A VESTIBULE
100B VEST
101 LABORATORY #2
101A MECH 2
102A WOMEN'S DRESSING
102B WOMEN'S TR
103A PASSAGE
103B MECH
104A MEN'S DRESSING
104B MEN'S TR
104C EVS
105 MAINTENANCE
106 MECH/ELEC
107 LABORATORY #3
107A MECH 3
108 TEST ROOM
109 TEST INTAKE
110B AUTOCLAVE
110C PASSWAY
111 BOILER ROOM
112 BREAK RM
113 ELECTRICAL
114 MAIN LABORATORY #1
114A MECH 1
115 HEADHOUSE
116 STORAGE
120 SERVICE PASSAGE
121 GH 1
122 GH 2
123 GH 3
124 GH 4
125 GH 5
C101 CORRIDOR
C102 CORR
C103 PASSAGE
C104 PASSAGE
C105 VEST
EGC1 EGC 1
EGC2 EGC 2
EGC3 EGC 3
EGC4 EGC 4
EGC5 EGC 5
EGC6 EGC 6
EGC7 EGC 7
EGC8 EGC 8
EGC9 EGC 9
EGC10 EGC 10
EGC11 EGC 11
EGC12 EGC 12
1/8" = 1'-0"A-101
01 FIRST FLOOR PLAN - NEW WORK
NN
PLANTRUE
16'4' 8'
SCALE: 1/8"=1'-0"
PLAN LEGEND
EXISTING
NEW WORK
ALTERNATE #01 - SCOPE AREA AS SHOWN IN
PLAN - REFER TO SHEET G-001
ALTERNATE #03 - SCOPE AREA AS SHOWN IN
PLAN - REFER TO SHEET G-001
FLOOR LEVEL
100' - 0"
T/ ROOF
STRUCTURE
110' - 0"
'-6
" 15 '-0
A-211
A-211
E01E01
E04 E01E01
E60
E32
E03
E11
E12
E02E02
E13 E62
'-0
3'- 6"
9'- 9"
1'- 0"
E37
14'-7 3/4" 11'-5 1/4" 34'-1"
E05 E11E05 E22
FLOOR LEVEL
100' - 0"
T/ ROOF
STRUCTURE
110' - 0"
A-211
E01
8'- 0"
1'- 3 3
/4"
E04 E01 E60 E60
E05
E01E01E01 E60
E05
E50
E02E02
E37 E37
E05
E05
18'-4 5/8"
E23E60
FLOOR LEVEL
100' - 0"
T/ ROOF
STRUCTURE
110' - 0"
A-211
6'- 8"9'-
E60
E11 E12
E32
E11
E12
E05
E03
E03
E13 E03
E02E023'- 6"
E37 17'-6"80'-0"17'-0"3 1/2"
E09E09E09
TYP
E09E09
TYP
E37
E12
--- E63E63E63E63E63
01 01 01 01 01
FLOOR LEVEL
100' - 0"
T/ ROOF
STRUCTURE
110' - 0"
E01
A-211
A-211-
E01E01
E04
E32
E02E02
E03 E03
E02
E13E13
E61
E3717'-3"
'-1
3'- 6"
E11
E11
E05
E05 E05
E05 www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
:4 0:
A
M
10/17/2025
HENRY
HIGHFIELD
8050.07
A-201
BUILDING
ELEVATIONS
FINAL TURNOVER
DRAWING NOTES
E01 EXISTING GLASS BLOCK WINDOW
E02 EXISTING BRICK VENEER - REFER TO
ALTERNATE #02 - PAINT TO FINISH
E03 EXISTING CMU - REFER TO ALTERNATE #02 -
PAINT TO FINISH
E04 EXISTING ALUMINUM STOREFRONT
E05 NEW PRE-FINISHED METAL COPING AND
ALUMINUM WRAPPED TRIM BD
E09 NEW METAL LOUVER
E11 REPLACE METAL GUTTER AND CONNECT TO
EXISTING DOWNSPOUT
E12 EXISTING DOWNSPOUT
E13 EXISTING DECORATIVE BRICK WALL - REFER TO
ALTERNATE #02 - PAINT TO FINISH
E22 REPLACE FLASHING AND COUNTERFLASHING
AT ROOF EDGE
E23 REMOVE EXISTING DOOR AND FRAME. INFILL
OPENIING WITH DOUBLE WYTHE BRICK
MASONRY WALL. PROVIDE FLASHING AT HEAD
AND SILL. REFER TO MASONRY WALL INFILL
DETAILS ON SHEET A-560.
E32 EXISTING GREENHOUSE STRUCTURE OVER
CMU WALL, TYP
E37 NEW UTILITY SAFETY GUARD RAILING
E50 MECHANICAL EQUIPMENT - REFER TO
MECHANICAL DRAWINGS
E60 EXTERIOR LIGHT FIXTURE
E61 ELECTRICAL PANEL AND EQUIPMENT - REFER
TO ELECTRICAL DWGS
E62 EXISTING SECURITY CAMERA
E63 RE-CAULK EXISTING GREENHOUSE FRAME AND
WALL AND ROOF PERIMETER
3/16" = 1'-0"A-201
03 EAST ELEVATION
3/16" = 1'-0"A-201
01 NORTH ELEVATION
3/16" = 1'-0"A-201
02 SOUTH ELEVATION
3/16" = 1'-0"A-201
04 WEST ELEVATION
SCALE: 3/16"=1'-0"
4' 12'8'
ALTERNATE #02:
REPAINT ENTIRE FACILITY EXTERIOR
MASONRY WALLS, SILLS, HOLLOW METAL
DOORS AND FRAMES. PROVIDE RE-FINISH
PAINT TO METAL FASCIA TRIM, GUTTERS,
DOWNSPOUTS AND NEW UTILITY RAILING AS
NEEDED TO MATCH PRE-FINISH COLOR.
MAIN
LABORATORY
#1
A-40106
A-40107
C103
A3 F A3
F
N10F
N10F
A3F
F7 C
F7C
F7C
3'- 0"
9'- 9"
E36
E15
A03
A03
E15
A02A02
A30
2'- 7"
'-8
2'-7" 10'-9"
2'-0"
FI
LE
D
VE
RI
FY
8'- 0"
'-0
2'-7"
6'- 0"
6'- 0"
5'-8" 3'-0" 4'-0"
9'-5"
2'- 7"
E31
A06
A02
A08
A10
E16
FIELD VERIFY
17'-9 3/4" +/-
FI
EL
D
VE
RI
FY
'-0
3'-0" 5'-4"
6"
2'- 3 1
/2"
4'-2"
TA-H1
TA-B1
N10F
1'- 6"
1'- 6"
A08
A08
A-506
A-506
A-506
E20
E15
E15E16
E0816'-0"
2'-
3'-0" 3'-0" 3'-0"
3'- 4"
TA-H1TA-B1
E42
SINK
KNEE
SPACE
A-506
A-506
E61
E31
E16
E20
E15
5 1/2" FILLER 3'-0" 3'-0" 3'-0"
TA-B1
2'-
6"
E15
A-506
A-506
E42
E20
3'-0" 3'-0" 3'-0" 1'-9" 2'-6"
A-211
2'-
6"
E15
A-506
1'-11"E31E09
E29
4'- 6"
2'- 6"
E15
E20 E28 E20
E15
A-560
02 SIM
A-560
SIM
E36
7'-9"
MAIN
LABORATORY
#1
NO CEILING
C01
7' -0
7'-4"
C01
C04
9'- 9"
3'- 0"
.5' -9
'-9
1'- 6"
4'-2" 3'-0"
C05
C06
C4 A-802
C4 A-802
A.
B.
C.
D.
a.
b.
c.
d.
e.
REFER TO TOILET ACCESSORY SCHEDULE ON SHEET
A-401 FOR ADDITIONAL INFORMATION.
ALL METAL WALL AND BASE CABINETS WITHOUT SINKS
ARE OPEN SHELVED UNITS, UNO
EXPOSED SIDES AND BACKS OF CASE WORK TO BE
FINISHED TO MATCH FRONT SURFACE OF ALL CASE
WORK.
CASEWORK:
NO CAMLOCKS IN WALL OR BASE CABINETS.
KEYED PANEL LOCK TO BE PROVIDED FOR SERVICE
ACCESS AT UNDERSIDE OF SINK BASE CABINETS
WITH PLASTIC LAMINATE PANEL KNEE SPACE.
COORDINATE ALL CASEWORK WITH OTHER FIELDS.
REFER TO ELECTRICAL AND PLUMBING DRAWINGS
FOR CONDUIT/DATA, PIPING LOCATIONS,
CONTRACTOR TO REPORT ANY COORDINAITON
ISSUES BEFORE INSTALLATION BEGINS.
RETURN ALL BACKSPLASH AT END WALL
CONDITIONS U.N.O. SEAL PERIMETER OF
BACKSPLASH AT ADJACENT WALL WITH
CONTINUOUS BEAD TO CLOSE GAPS.
ALL OUTSIDE CORNERS OF COUNTERTOPS SHALL
PROJECT 1" PAST CABINET/SUPPORT AND SHALL
HAVE EASED EDGES CORNER EXCEPT WHERE
COUNTERTOP ABUTTS REFRIGERATORS AND
EQUIPMENT.
www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
2:
:0
PM
10/17/2025
HENRY
HENRY
8050.07
A-401
ENLARGED PLANS &
ELEVATIONS -
LABORATORY 1
FINAL TURNOVER
1/4" = 1'-0"A-401
01 ENLARGED PLAN - LAB 1 - RM 114
3/8" = 1'-0"A-401
05 INTERIOR ELEVATION - LAB 1 - RM 114 - EAST
3/8" = 1'-0"A-401
03 INTERIOR ELEVATION - LAB 1 - RM 114 - NORTH
3/8" = 1'-0"A-401
04 INTERIOR ELEVATION - LAB 1 - RM 114 - SOUTH
3/8" = 1'-0"A-401
06 INTERIOR ELEVATION - LAB 1- RM 114 - WEST
3/8" = 1'-0"A-401
07 INTERIOR ELEVATION - MAIN LAB 1 - ISLAND
1/4" = 1'-0"A-401
02 ENLARGED CEILING PLAN - LAB 1
DRAWING NOTES
GENERAL NOTESTOILET ACCESSORY SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL
TA-A1 MULTI-ROLL TOILET TISSUE DISPENSER - SURFACE MOUNTED Bobrick Washroom Equipment, Inc. B-4288 TA-B1 PAPER TOWEL DISPENSER - SURFACE MOUNTED Bobrick Washroom Equipment, Inc. B-2860 TA-D1 SANITARY NAPKIN DISPOSAL - SURFACE MOUNTED Bobrick Washroom Equipment, Inc. B-270 TA-F1 GLASS MIRROR WITH STAINLESS STEEL ANGLE FRAME Bobrick Washroom Equipment, Inc. B-165 TA-F2 GLASS MIRROR WITH STAINLESS STEEL ANGLE FRAME Bobrick Washroom Equipment, Inc. B-165 TA-G1 1-1/4" STAINLESS STEEL GRAB BAR (36") Bobrick Washroom Equipment, Inc. B-5806 TA-G2 1-1/4" STAINLESS STEEL GRAB BAR (42") Bobrick Washroom Equipment, Inc. B-5806 TA-H1 DISPENSER, FOAM SOAP - COORDINATE WITH OWNER Ecolab 92723188 TA-M1 STAINLESS STEEL MOP & BROOM HOLDER (24") Bobrick Washroom Equipment, Inc. B-223
E08 NEW DOOR, HOLLOW METAL FRAME AND
HARDWARE
E09 NEW METAL LOUVER
E15 METAL LABORATORY CASEWORK
E16 METAL LABORATORY CASEWORK WITH DEEP
DOUBLE SINK - COORD WITH PLUMBING DWGS
E20 NEW ST. STL. WALL CABINET WITH OPEN SHELVES
E28 NEW HORIZ ACCESS DOOR PANEL - REFER TO
REFLECTED CEILING PLAN
E29 NEW ACCESS DOOR PANEL
E31 FUME HOOD - OWNER FURNISHED, CONTRACTOR
INSTALLED (OFCI)
E36 NEW MOBILE ST. STL LABORATORY WORK TABLE
E42 EMERGENCY SHOWER/EYE WASH - REFER TO
PLUMBING DWGS
E61 ELECTRICAL PANEL AND EQUIPMENT - REFER TO
ELECTRICAL DWGS
A02 NEW FLOOR FINISH PER FINISH SCHEDULE
A03 PATCH EXISTING WALL AND FINISH TO
MATCH ADJACENT
A06 NEW FURRING WALL FROM FLOOR TO 6"
ABOVE CEILING
A08 INFILL EXISTING DOUBLE WYTHE BRICK
VENEER WALL AND FINISH TO MATCH
ADJACENT BRICK SIZE, PATTERN AND WALL
FINISH ON BOTH SIDES. TOOTH BRICK IN
PLACE AT FULL HEIGHT OF WALL INFILL.
A10 NEW DOOR, FRAME AND HARDWARE
A30 EMERGENCY SHOWER/EYE WASH. SLOPE
FLOOR TO FLOOR DRAIN 1/4" PER FOOT
C01 NEW GYPSUM BD CEILING
C04 NEW GYPSUM BD SOFFIT
C05 16" X 16" ACCESS PANEL
C06 16" X 22" ACCESS PANEL
SEALED CONCRETE FLOOR
SEAMLESS URETHANE FLOORING
CONCRETE SLAB
1/ 4"
3/
" 2"
7/
5/ 8"
DOOR
SEAMLESS URETHANE FLOORING
RESILIENT FLOORING
CONCRETE SLAB
METAL REDUCER: SCHLUTER-RENO-U,
COLOR: TBD OR EQUAL, ADA COMPLIANT
PORCELAIN TILE FLOORING
SEAMLESS URETHANE FLOORING
CONCRETE SLAB
METAL REDUCER: SCHLUTER-RENO-U,
COLOR: TBD OR EQUAL, ADA COMPLIANT
www.coffman.comwww.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
1:
:4
PM
10/17/2025
HENRY
HIGHFIELD
8050.07
A-603
FINISH SCHEDULE
FINAL TURNOVER
ROOM FINISH SCHEDULE
NUMBER ROOM NAME
BASE
FINISH FLOOR FINISH NORTH WALL EAST WALL SOUTH WALL WEST WALL CEILING FINISH REMARKS
100A VESTIBULE CT-4 CT-4 PT-1 PT-1 PT-1 PT-1 ACT-1
100B VEST CT-4 CT-4 PT-1 PT-1 PT-1 PT-1 ACT-1
101 LABORATORY #2 SUF-4 SUF-4 EP-1 EP-1 EP-1 EP-1 EXIST GYP / EP-1
102A WOMEN'S DRESSING CT-2B CT-2A CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 GYP / ACT-1 / PT-4 SHOWER FLOOR - CT-3
102B WOMEN'S TR CT-2B CT-2A CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 ACT-1
103A PASSAGE RB-1 SUF-4 PT-1 PT-1 PT-1 PT-1 ACT-1
103B MECH RB-1 SC PT-1 PT-1 PT-1 PT-1 NO CEILING
104A MEN'S DRESSING CT-2B CT-2A CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 GYP / ACT-1 / PT-4 SHOWER FLOOR - CT-3
104B MEN'S TR CT-2B CT-2A CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 CT-1/PT-1 ACT-1
104C EVS RB-1 SC EP-1 EP-1 EP-1 EP-1 EXIST GYP / EP-2
105 MAINTENANCE EXIST / RB EXIST SC EXIST / EP-1 EXIST / EP-1 EXIST / EP-1 EXIST / EP-1 EXIST GYP / EP-2 106 MECH/ELEC EXIST / RB EXIST SC EXIST CMU EXIST CMU EXIST CMU EXIST CMU EXIST GYP / EP-2
107 LABORATORY #3 SUF-4 SUF-4 EP-1 EP-1 EP-1 EP-1 EXIST GYP / EP-1
108 TEST ROOM EXIST / RB EXIST / VCT PT-1 PT-1 PT-1 PT-1 EXIST GYP / PT-4 REFER TO ALTERNATE #01 109 TEST INTAKE EXIST / RB EXIST / VCT PT-1 PT-1 EXIST CMU PT-1 EXIST GYP / PT-4 REFER TO ALTERNATE #01
110B AUTOCLAVE EXIST / RB EXIST / VCT EXIST CMU/ PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST GYP / PT-4 REFER TO ALTERNATE #01 110C PASSWAY EXIST / RB EXIST / VCT EXIST CMU/ PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST GYP / PT-4 REFER TO ALTERNATE #01 111 BOILER ROOM EXIST / RB EXIST SC EXIST CMU EXIST CMU EXIST CMU EXIST CMU EXIST GYP/ EP-2
112 BREAK RM RB-1 RF-1 PT-1 PT-1 PT-1 PT-1 EXIST GYP / PT-4
113 ELECTRICAL EXIST / RB EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST GYP / EP-2
114 MAIN LABORATORY #1 SUF-4 SUF-4 EP-1 EP-1 EP-1 EP-1 EXIST GYP / EP-1
115 HEADHOUSE SUF-4 SUF-4 EP-1 EP-1 EP-1 EP-1 ACT-2 / EP-2
116 STORAGE RB-1 RF-1 PT-1 PT-1 PT-1 PT-1 EXIST GYP / PT-4
120 SERVICE PASSAGE NO BASE EXIST SC PT-1 PT-1 PT-1 PT-1 NO CEILING / PT-4
121 GH 1 - EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 NO CEILING 122 GH 2 - EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 NO CEILING 123 GH 3 - EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 NO CEILING 124 GH 4 - EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 NO CEILING 125 GH 5 - EXIST SC EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 EXIST CMU / PT-1 NO CEILING
C101 CORRIDOR SUF-4 SUF-4 PT-1 PT-1 PT-1 PT-1 ACT-2
C102 CORR SUF-4 SUF-4 PT-1 PT-1 PT-1 PT-1 ACT-2
C103 PASSAGE SUF-4 SUF-4 PT-1 PT-1 PT-1 PT-1 ACT-2
C104 PASSAGE SUF-4 SUF-4 PT-1 PT-1 PT-1 PT-1 ACT-2
C105 VEST CT-4 CT-4 PT-1 PT-1 PT-1 PT-1 GYPSUM BD / PT-4
GENERAL NOTES
A. REFERENCE SHEET A-551 FOR FLOORING
TRANSITION DETAILS.
B. REFERENCE SHEET A-111 FOR FIRST FLOOR CEILING
PLAN FOR ADDITIONAL INFO.
C. REFERENCE LABORATORY METAL CASEWORK SHOP
DRAWINGS FOR ADDITIONAL INFO.
D. REFERENCE FINISH MATERIAL LEGEND FOR MANUF.,
MATERIAL AND FINISH COLORS.
E. PREPARE EXISTING CONCRETE FLOOR SURFACE AS
REQUIRED FOR NEW FLOOR FINISH.
F. REMOVE EXISTING GYPSUM BD CEILING, PATCH,
REPLACE AND RE-FINISH EXISTING GYPSUM CEILING.
G. PROVIDE CONCRETE SEALER AND FLOOR FINISH TO
EXPOSED CONCRETE FLOOR SURFACES.
H. REMOVE AND REPLACE EXISTING EXPANSION JOINT
COVER PLATES AT FLOOR TO FLOOR, FLOOR TO
WALL AND WALL TO WALL AS NEEDED FOR
REPLACEMENT DUE TO DAMAGE AND FOR INSTALL
OF NEW FLOOR FINISH. MATCH EXISTING EXPANSION
JOINT COVER DIMENSION AND MATERIAL FINISH.
1. REFERENCE INTERIOR ELEVATIONS FOR WALL TILE
LOCATIONS AND PATTERN.
2. EXISTING ROOM FINISH THROUGHOUT TO REMAIN
UNDISTURBED. PATCH AND REPLACE AND FINISH TO
MATCH ADACENT, ONLY AS NEEDED DUE TO OTHER
DISCIPLINE WORK.
3. HOLLOW METAL DOOR FRAMES PAINT PT-X.
CONTRACTOR TO COORDINATE PAINT FINISH WITH
OWNER.
REMARKS
INTERIOR FINISH ABBREVIATIONS
ACT ACOUSTICAL CEILING TILE
CMU CONCRETE MASONRY UNITS
CT CERAMIC TILE
EP EPOXY PAINT
FT FLOOR TILE
GYP GYPSUM BOARD
MFR MANUFACTURER
PL PLASTIC LAMINATE
PT PAINT
RB RESILIENT BASE
RF RESILIENT FLOOR
SC SEALED CONCRETE
SS SOLID SURFACE
SUF SEAMLESS URETHANE FLOORING
VCT VINYL COMPOSITION TILE
NTSA-603
03 RESINOUS FLOORING TO CONCRETE TRANSITION
NTSA-603
02 RUBBER FLOORING TO RESINOUS FLOORING TRANSITION
NTSA-603
01 PORCELAIN TILE TO RESINOUS FLOORING TRANSITION
www.coffman.comwww.coffman.com
Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
CEI PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
USDA/APHIS
CONTAINMENT FACILITY
BUILDING 6403
MOORE AIR BASE
EDINBURG, TEXAS
COFFMAN PROJECT # 212431
8/
/2
2:
:2
PM
10/17/2025
HENRY
HIGHFIELD
8050.07
A-604
FINISH MATERIAL
LEGEND
FINAL TURNOVER
REV DATE DESCRIPTION
GENERAL HVAC NOTES
1. SHEET METAL DUCTWORK AND COMPONENTS INCLUDING HANGING, SEALING, PLENUMS, & ACCESSORIES SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS FOR HVAC DUCT CONSTRUCTION, NFPA 90A, & 90B STANDARDS.
2. ALL DUCTWORK OPENINGS SHALL BE COVERED DURING CONSTRUCTION.
3. ALL DAMPERS SHALL BE SET FULLY OPEN PRIOR TO BALANCING.
4. CONTRACTOR TO PROVIDE TRANSITION TO CONNECT TO ALL MECHANICAL EQUIPMENT. PROVIDE FLEXIBLE CONNECTION ON INTAKE AND DISCHARGE
OF ALL MECHANICAL EQUIPMENT.
5. DUCT DIMENSIONS SHOWN ARE INSIDE SHEET METAL DIMENSIONS OR CLEAR OPENING INSIDE LINED DUCT.
6. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND
PROVIDE ALL NECESSARY OFFSETS.
7. ALL ELBOWS SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE, OR SHALL HAVE TURNING VANES WHERE INDICATED ON PLANS. NO SQUARE
THROAT OR ZERO RADIUS ELBOWS ALLOWED.
8. ALL DUCT BRANCH CONNECTIONS TO DIFFUSER OR GRILLES, TO OR FROM MAIN DUCTS, SHALL INCLUDE MANUAL VOLUME DAMPERS. ALL SPIN-IN FITTINGS SHALL BE CONICAL, RECTANGULAR BRANCH DUCT TAKEOFFS SHALL HAVE 45° TAKEOFFS.
9. PROVIDE CONCEALED DAMPER REGULATORS OR ACCESS DOORS FOR ALL MANUAL VOLUME DAMPERS LOCATED THAT ARE INACCESSIBLE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO
INSTALLATION.
10. 24"x24" ACCESS DOORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE GYPSUM BOARD CEILINGS. ALL FINAL ACCESS
DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
11. PROVIDE DIFFUSER AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES AND COORDINATE LOCATIONS WITH THE
ARCHITECTURAL REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING LAYOUT.
12. ALL DUCTWORK VISIBLE THROUGH RETURN OR SUPPLY GRILLES TO BE PAINTED FLAT BLACK.
13. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTS SHALL HAVE THE TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS
SEALED AIRTIGHT WITH DUCT SEALANT (SMACNA SEAL CLASS "A").
14. COORDINATE EXACT LOCATIONS OF ALL ROOM THERMOSTATS AND/OR ROOM TEMPERATURE SENSORS WITH ARCHITECT/OWNER PRIOR TO
INSTALLATION.
15. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A COPY OF THE BALANCE REPORT TO THE ENGINEER FOR REVIEW.
16. ALL PENETRATIONS ARE TO BE SEALED PER ARCHITECTURAL PLANS/SPECIFICATIONS.
17. THE MOORE AIR BASE NIAGRA SYSTEM SHALL MONITOR ALL MECHANICAL SYSTEMS AS SPECIFIED IN THE CONTROL DIAGRAMS. THE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING DEVICES AS NECESSARY (TO INCLUDE ADDITIONAL SENSORS AND/OR CONTROL MODULES)
FOR INTEGRATION WITH MAB NIAGRA SYSTEM.
GENERAL NOTES
1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED PERMITS, LICENSES, AND INSPECTIONS FOR DURATION OF WORK UNLESS
DIRECTED OTHERWISE.
2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL APPLICABLE STATE AND LOCAL CODES, OR AUTHORITY HAVING
JURISDICTION.
3. SUBSTITUTIONS OF EQUIPMENT OTHER THAN AS SPECIFIED SHALL BE THE COMPLETE RESPONSIBILITY OF THE CONTRACTOR, ANY ADDITIONAL ELECTRICAL, STRUCTURAL, MECHANICAL, OR ARCHITECTURAL REQUIREMENTS SHALL BE PROVIDED AT NO ADDITIONAL EXPENSE TO THE OWNER.
4. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE ALL NECESSARY OFFSETS. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION DETAILS.
5. REFER TO PROJECT MANUAL (SPECIFICATIONS) FOR ADDITIONAL REQUIREMENTS. PLANS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER.
PROVIDE ALL WORK CALLED FOR IN EITHER. IN CASE OF CONFLICT BETWEEN SPECIFICATIONS AND PLANS THE MORE STRINGENT SHALL APPLY.
6. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION SHALL BE COVERED AND PROTECTED FROM RAIN, DIRT, DUST, AND
DAMAGE.
7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/ GENERAL CONTRACTOR AND OTHER TRADES TO ALLOW FOR REQUIRED MECHANICAL EQUIPMENT CLEARANCES.
8. PROVIDE AN UNOBSTRUCTED PASSAGEWAY MEASURING NO LESS THAN 36" WIDE BY 80" HIGH FROM DOOR INTO THE SPACE TO SERVICEABLE MECHANICAL EQUIPMENT. A LEVEL WORKING SPACE MEASURING NO LESS THAN 30" WIDE BY 36" DEEP MUST BE PROVIDED IN FRONT OF CONTROL
SIDE OF EQUIPMENT FOR SERVICING.
9. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET
MECHANICAL WORK AS REQUIRED.
10. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION STANDARDS AND CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SHOP FABRICATION AND/OR FIELD INSTALLATION. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER.
11. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE PROVIDED BY THE CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE, INSTALLED, AND FULLY FUNCTIONAL PRIOR TO FINAL ACCEPTANCE OF THE WORK.
12. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. ANY CONFLICTS BETWEEN THE MANUFACTURERS DOCUMENTATION AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
13. DO NOT ALLOW ANY WORK TO BE COVERED UP OR ENCLOSED UNTIL INSPECTED, TESTED AND APPROVED BY OWNER'S REPRESENTATIVE OR
AUTHORITY HAVING JURISDICTION.
14. MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY HEATING OR COOLING DURING CONSTRUCTION.
15. PIPES AND WIRING IN PLENUM SHALL BE RATED FOR PLENUM USE. PVC, ABS, AND PLASTIC PIPING IS NOT ACCEPTABLE IN PLENUM APPLICATIONS.
16. ALL DETAILS ARE TYPICAL UNLESS NOTED OTHERWISE.
GENERAL ABBREVIATIONS
ø ROUND or DIAMETER
AAV AUTOMATIC AIR VENT
ABV ABOVE
ACV AIR CONTROL VALVE
AD ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AL ACOUSTIC LINED
AP ACCESS PANEL
APD AIR PRESSURE DROP
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AWT AVERAGE WATER TEMPERATURE
BAS BUILDING AUTOMATION SYSTEM
BB BASEBOARD
BBD BACKDRAFT DAMPER
BFF BELOW FINISH FLOOR
BHP BRAKE HORSEPOWER
BG BELOW GROUND/GRADE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
C CENTIGRADE
CC COOLING COIL
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CI CAST IRON
CLG CEILING
CO CLEANOUT
COG CLEANOUT TO GRADE
CMU CONCRETE MASONRY UNIT
CM CONDENSATE METER
CONC CONCRETE
CONN CONNECT or CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION
(D) DEMOLISH
DB DECIBEL or DRY BULB
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DOAS DEDICATED OUTDOOR AIR SYSTEM
DPR DAMPER
DP DIFFERENTIAL PRESSURE
DWG DRAWING
(E) EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
ECM ELECTRONICALLY COMMUTATED
MOTOR
ECV EXHAUST CONTROL VAVLE
EF EXHAUST FAN
EG EXHAUST GRILLE
ELEC ELECTRIC or ELECTRICAL
ELEV ELEVATION
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
ESH EMERGENCY SHOWER
EXH EXHAUST
EXST EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FD FLOOR DRAIN
FD FIRE DAMPER
FFD FUNNEL FLOOR DRAIN
FF FINAL FILTER
FLR FLOOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD COMBINATION FIRE/SMOKE DAMPER
FT FOOT/FEET
FV FACE VELOCITY
GA GAGE or GAUGE
GAL GALLON
GALV GALVANIZED
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRD GRILLE, REGISTER, OR DIFFUSER
H HEIGHT
HB HOSE BIBB
HD HEAD
HP HORSEPOWER
HTG HEATING
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
HWG HIGH WALL GRILLE
HWR HIGH WALL REGISTER
HZ HERTZ
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCH or INCHES
INSUL INSULATION
INV INVERT
KW KILOWATT
KWH KILOWATT HOUR
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FOOT/FEET
LVG LEAVING
LWG LOW WALL GRILLE
LWR LOW WALL REGISTER
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MAV MANUAL AIR VENT
MBH 1000 BRITISH THERMAL UNITS
PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MOP MAXIMUM OVERCURRENT
PROTECTION
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTG MOUNTING
(N) NEW
(NL) NEW LOCATION
N/A NOT APPLICABLE
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NC NOISE CRITERIA
N.I.C. NOT IN CONTRACT
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
O/C ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
PCV PRESSURE CONTROL VALVE
PD PRESSURE DROP
PH PHASE
PLCS PLACES
POC POINT OF CONNECTION
POUA POINT OF USE ALARM
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH (GAGE)
(REL) RELOCATE/RELOACTED
RA RETURN AIR
RAG RETURN AIR GRILLE
RC ROOF CAP
REQD REQUIRED
R.O. ROUGH OPENING
RPBP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SCV SUPPLY CONTROL VALVE
SD SMOKE DETECTOR
SF SUPPLY FAN
SHT SHEET
SIM SIMILAR
SL SOUNDLINING
SP STATIC PRESSURE
SQ SQUARE
SQ FT SQUARE FOOT/FEET
SS STAINLESS STEEL
STD STANDARD
TAB TESTING, ADJUSTING & BALANCING
THK THICK
TP TRAP PRIMER or TEST PLUG
TR TOILET ROOM
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
TU TERMINAL UNIT
UBC UNIFORM BUILDING CODE
UFC UNIFORM FIRE CODE
UMC UNIFORM MECHANICAL CODE
UPC UNIFORM PLUMBING CODE
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VA VALVE
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THRU ROOF
W WIDE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WT WEIGHT
DESIGN CONDITIONS
OUTDOORS
VENTILATION
INDOOR
ELEVATION
SUMMER 82.9°F DB / 78.9°F WB
WINTER 36.7°F DB
COOLING 75°F
HEATING 70°F
PER ASHRAE 62.1-2021
80 FT ABOVE SEA LEVEL
LOCATION EDINBURG, TEXAS
PROJECT SUMMARY
THE USDA CONTAINMENT BUILDING 6403 AT MOORE AIR BASE HAS AGING MECHANICAL
EQUIPMENT AND BUILDING COMPONENTS IN NEED OF REPLACEMENT, AND THE BUILDING
LABORATORY SPACES REQUIRE MODIFICATIONS TO VENTILATION FOR OPERATIONAL
REQUIREMENTS. THE FOLLOWING SCOPE ITEMS ARE A SUMMARY OF THE WORK TO BE
COMPLETED AS A PART OF THIS PROJECT, THE ITEMS TO BE…