Attachment 08 Grindstone_Lead_Asbestos_report.pdf
PDF 2 MB Posted
- Solicitation number
- 12445126B0007
About this file
This is a Pre-Demolition Asbestos-Containing Material and Lead Based Paint Inspection Report dated March 20, 2025, prepared by Hurt & Proffitt, Inc. for the US Forest Service regarding the Grindstone Campground Wastewater Treatment Plant Building located at 1946 Laurel Valley Road, Troutdale, VA 24378.
The inspection was conducted on February 27, 2025, by Virginia Asbestos Inspector Travis J. Wood (License #3303004688) in compliance with US OSHA and US EPA National Emission Standards for Hazardous Air Pollutants (NESHAPs). Five suspect asbestos-containing material bulk samples were collected and analyzed by SanAir Technologies Laboratory (NVLAP accredited) using EPA Methods 600/R-93/116 and 600/M4-82-020 (polarized light microscopy). All three asbestos samples—exterior white door caulk, interior white door caulk, and cementitious flashing from the shed—tested negative for asbestos. Three paint chip samples were analyzed via EPA Method SW 846/3051A/6010B and converted to percent lead by weight. Results identified one lead-based paint sample: the green door/frame with 2.732% lead content. Interior and exterior white CMU walls tested below the action level at 0.018% and 0.013% respectively. The report recommends that the facility owner submit an Asbestos Notification of Demolition and Renovation Form to the Virginia Department of Labor and Industry at least twenty calendar days prior to demolition start date. The contractor must comply with OSHA regulations 29 CFR 1926.62 (Lead in Construction), conduct negative exposure assessments, provide worker notification and training per EPA guidelines, and ensure proper waste disposal in accordance with 40 CFR Part 261.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
March 20, 2025
Mr. James Lowe Facilities Program Manager US Forest Service 5162 Valleypointe Parkway Roanoke, Virginia 24019
Re: Asbestos-Containing Material & Lead Based Paint Inspection
Grindstone Campground – Wastewater Treatment Plant Building 1946 Laurel Valley Road; Troutdale, VA 24378 Hurt & Proffitt Project Number: 20250244
Dear Mr. Lowe:
Hurt & Proffitt, Inc. (H&P) is pleased to provide this document and enclosures as the Pre-Demolition Asbestos-Containing Material and Lead Based Paint Inspection Report, specific to the structure located at 1946 Laurel Valley Road; Troutdale, VA 24378.
Inspection / assessment activities were performed in compliance with United States Occupational Safety and Health Administration (US OSHA) and United States Environmental Protection Agency (US EPA) National Emission Standards for Hazardous Air Pollutants (NESHAPs) on February 27, 2025, by Hurt & Proffitt representative, Mr. Travis J. Wood (Virginia Asbestos Inspector: 3303004688). A copy of Mr.
Wood’s Virginia Department of Professional and Occupational Regulation (VA DPOR) Asbestos Inspector License(s) are enclosed for your review.
1.0 Asbestos-Containing Material (ACM) Survey and Laboratory Procedures
Physical inspection/assessment was performed at the address as referenced above to determine the extent and locations of suspect asbestos-containing materials and potential degree of abatement activities to take place for the proposed demolition.
Suspect bulk samples were collected and logged on chain-of-custody forms as representative of suspect homogenous materials (based on material type, color, texture, etc.), from the functional spaces as they were determined by visual observations in the field.
Five (5) suspect asbestos-containing bulk material samples, including triplicate sets, were submitted for analysis by EPA Method No. 600/R-93/116 and 600/M4-82-020 (polarized light microscopy (PLM)). All samples were analyzed by SanAir Technologies Laboratory of Richmond, Virginia, a NVLAP accredited laboratory licensed to perform asbestos bulk analysis within the State of Virginia.
The following table (Table I) illustrates the sample identification, location, and analytical results as received from the laboratory. A copy of the laboratory results and sample chain-of-custody are additionally enclosed for your review.
Table I
Asbestos-Containing Bulk Material Sample Analysis Summary Grindstone Campground – Wastewater Treatment Plant Building
1946 Laurel Valley Road; Troutdale, VA 24378
Sample ID Material Description Location Estimated Quantity
Lab Results (% Asbestos)
Condition/ Friable Y/N
001-EXDC-AB
EXTERIOR WHITE
DOOR CAULK
SHED N/A NONE DETECTED N/A
002-INDC-AB
INTERIOR WHITE
DOOR CAULK
SHED N/A NONE DETECTED N/A
003-FLSH-A
CEMENTITIOUS
FLASHING
SHED N/A NONE DETECTED N/A
Table Notes:
1. (AB) following sample identification denotes multiple samples collected of the same homogenous material from various functional spaces of the structure.
A copy of the laboratory report of analysis are enclosed for your review.
Discussion and Recommendations
In order to obtain a building (demolition) permit, this report must accompany the application to the county, town and/or city for which the work is to take place. It is the responsibility of the contractor performing the abatement and/or building demolition activities that the proper permits are obtained and notifications for each type of activity be performed as required by state and federal guidelines.
The facility owner must submit an Asbestos Notification of Demolition and Renovation Form to the VA DOLI along with the appropriate fees within at least twenty (20) calendar days prior to the scheduled demolition start date by certified mail or hand delivery. Notifications should be sent to the following:
Department of Labor and Industry Attn: Accounting / Finance Main Street Centre 600 East Main Street, Suite 207 Richmond, Virginia 23219 Fax: 804.371.7634
Note: A United States Environmental Protection Agency (US EPA) Memorandum dated December 22, 2021, details that complete and timely notifications must be sent to the state or local authority where the work is occurring, however, does not need to be sent to US EPA. This statement applies to any demolition work occurring in Virginia.
Our recommendations are based on the guidelines presented by the United States Occupational Safety and Health Administration (US OSHA), United States Environmental Protection Agency (US EPA), and the Commonwealth of Virginia. Any conditions discovered which deviate from the data contained in this report should be presented to us for our evaluation.
Note: During the process of this inspection/assessment, bulk material sampling was limited to those materials which were safely accessible. As such, additional asbestos-containing materials (ACM) or presumed asbestos-containing materials (PACM) may exist, either undetected and/or inaccessible) within other areas of the structure. If additional suspect materials are discovered during either the asbestos-containing material abatement or demolition activities, all work on the site must stop and the newly identified material(s) sampled by a Virginia licensed asbestos inspector and evaluated for asbestos content.
2.0 Lead-Based (LBP) Survey and Laboratory Procedures
Sample collection was performed by collecting paint chip samples from components identified during the site inspection. The paint chip sample(s) were collected utilizing a manual paint scraper. The removed paint chips were collected in a piece of clean construction paper for transfer into plastic sample collection bags. Each container was sealed and labeled with a unique sample identification number. Pertinent information for each sample including date of collection, location, color, and condition of the surface coatings was recorded on a sampling log form. After sample collection, each sample location was cleaned of extraneous debris.
Three (3) paint-chip samples were collected during the assessment and logged onto chain-of-custody form(s), packaged with custody seals, and delivered by UPS to the analytical laboratory, SanAir Technologies Laboratory, Inc. of Richmond, Virginia. SanAir is licensed by the Commonwealth of Virginia for Lead analysis. SanAir analyzed the paint chip samples for Lead content following EPA’s Method SW 846/3051A/6010B (preparation by microwave-assisted acid digestion followed by analysis via inductively coupled plasma). Analytical results were reported as parts per million (ppm, ug/g) and converted to per-cent Lead by weight. A copy of the analytical laboratory report is enclosed for your review.
The following table (Table No. II) illustrates the analytical results and details regarding the paint chip sample(s) collected during the assessment:
Table II Paint Chip Sample Analytical Summary
Grindstone Campground – Wastewater Treatment Plant Building 1946 Laurel Valley Road; Troutdale, VA 24378
Sample Number Building Component /
Room Color Substrate Condition
Lead Content (% Weight)
L-001 Door/Frame Green Metal Peeling 2.732%
L-002 Interior Wall White CMU Peeling 0.018
L-003 Exterior Wall White CMU Peeling 0.013
Based upon the results of the laboratory analytical methods, the following paint/surface coatings were identified as lead-based: Door/Framing painted Green.
Discussion and Recommendations
Hurt & Proffitt recommends that the contractor adhere to all applicable United States Environmental Protection Agency (US EPA) regulations regarding disposal requirements and United States Occupational Safety and Health administration (US OSHA) regulations for employee exposure.
Where components tested below the designated action level of 1.0 mg/cm² for classifying the material as lead based paint, it is important to note that any painted or coated surface may contain concentrations of lead, which when disturbed, could generate lead in dust greater than the action level exposure concentration of 30 ug/m3 established by the OSHA “Lead Exposure in Construction Rule” (29
CFR 1926.62).
The OSHA standard gives no guidance on acceptable levels of lead in coatings at which no exposure to airborne lead (above the action level) would be expected; however, OSHA defines airborne concentrations and lists specific work practices which may create a lead hazard. Therefore, personnel exposure monitoring should be performed during any removal or demolition process to establish worker exposure levels which can be used to determine appropriate personnel protection and environmental controls for the specific work practice and material type. In accordance with OSHA requirements, the Contractor performing the work will be required to conduct this monitoring. The primary route of exposure OSHA regulations are concerned with is the inhalation of Lead-containing dust generated by demolition operations within the building. These hazards are assessed by measuring the Lead concentration in air when demolition operations are initiated; a procedure called a negative exposure assessment. The OSHA defined Permissible Exposure Limit (PEL) for Lead is 50 micro-grams (ug) of Lead per cubic-meter (m3) air.
Building demolition and/or renovation activities where LBP is present must comply with the OSHA regulation 29 CFR 1926.62, Lead in Construction; and US EPA waste disposal regulations found in 40 CFR Part 261. OSHA regulations are designed to limit exposure of the construction workforce to Lead, which is a well-documented toxic element.
It would be prudent for the Building Owner to implement and document the following in response to the likely presence of Lead-dust hazards and documented Lead-based paint hazards in the building:
• Prior to any large-scale effort to remove the contents of the building or disturb/demolish building surfaces where LBP is known or suspected to be present, conduct a negative exposure assessment using trained workers wearing respiratory protection and protective clothing in compliance with 29CFR1926.62.
• Notify any person employed by the Owner to work in the building about the potential Lead-dust hazard and the LBP hazards. Instruct such worker in the importance of the use of proper personal hygiene practices and work practices (use of wet methods and HEPA vacuums) by providing them with the EPA-approved pamphlet Renovate Right: Important Lead Hazard Information for Families, Child Care Providers and Schools.
• The US OSHA regulation 29 CFR 1910.1200-Hazard Communication, requires that employers must inform employees about chemical hazards in the workplace. Construction contractors employed to demolish the building components within the site must be furnished a copy of this report.
Waste disposal for concentrated LBP debris (paint chips and scrapings, HEPA vacuum contents, protective suits, drop cloths, etc.) and for building components coated with LBP is regulated under 40 CFR Part 261 and/or 29 CFR 1910.1200. For disposal of construction/demolition debris that contain Lead, the United States Environmental Protection Agency (US EPA) requires the generator perform testing for lead content of the waste stream to determine proper disposal in accordance with the requirements of 40 CFR 261.11, Criteria for Listing Hazardous Waste.
3.0 Limitations
This report summarizes the results of Hurt & Proffitt’s Asbestos-Containing Material and Lead Based Paint Inspection located at the above referenced project based upon our understanding of the requested scope of services. The findings prepared by Hurt & Proffitt are based upon our observations and the analytical analysis of the suspect bulk samples collected at the time of our field inspection. The services performed were provided in accordance with generally accepted environmental industry standard practices. No warranty, expressed or implied, are made. Our observations, conclusions, and recommendations are based upon conditions readily visible at the time of our field inspection, the results of analytical testing, and information provided to us by others.
Our conclusions and recommendations are based upon the guidelines presented to us by the United States Environmental Protection Agency (US EPA), United States Occupational Safety and Health Administration (US OSHA), and the Commonwealth of Virginia. Any conditions which deviate from the data contained within this report should be presented to Hurt & Proffitt for our evaluation and comment. This report has been prepared for the exclusive use of the US Forest Service and/or their agents, as Owner Representative(s).
During Hurt & Proffitt’s inspection, accessible areas were visually assessed for the presence of suspect asbestos-containing materials. Locations and areas reviewed were limited to those identified by the Client and those that could be readily and safely accessed. Our conclusions and recommendations are based on the results of our sampling and analysis activities and cannot be used to form a professional opinion of conditions in other areas beyond those from which the bulk material samples were collected.
It is possible that inaccessible areas, such as inside wall system(s) or substrate finishes, may not have been surveyed and therefore, conditions in these areas are unknown.
During this inspection, suspect asbestos-containing material samples were submitted for analysis at an NVLAP-accredited laboratory via polarized light microscopy (PLM) while suspect lead-based paint samples were submitted for analysis via US EPA’s Method SW 846/3051A/6010B (preparation by microwave-assisted acid digestion followed by analysis via inductively coupled plasma). As with any similar survey of this nature, actual conditions exist only at the precise locations from which the bulk material samples were collected. Certain inferences are based on the results of this sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected.
Hurt & Proffitt assumes no responsibility regarding response actions initiated as a result of our findings, nor liability for the duties and responsibilities of the Client or Building Owner with respect to compliance with applicable regulations. Compliance with local, state, and/or federal requirements / regulations are the responsibility of the Client or Building Owner.
3.0 Closing
Thank you for allowing Hurt & Proffitt the opportunity to provide consulting services. Should you have any questions and/or concerns, please contact Mr. Travis J. Wood via email (twood@handp.com) or via telephone at 434.522.7698. It was a pleasure working with you on this project and I hope we can be of service to you in the future.
Sincerely, HURT & PROFFITT, INC
Report Prepared By: Report Reviewed By:
Travis J. Wood Brian J. Trent Project Manager, Project Manager, Environmental/Industrial Hygiene Environmental Services twood@handp.com btrent@handp.com
Enclosures: Asbestos Inspector License(s) SanAir Technologies Laboratory Results Suspect Asbestos-Containing Material Bulk Samples Project Drawing Lead Risk Assessor License mailto:twood@handp.com mailto:btrent@handp.com twood Snapshot twood Snapshot
Asbestos/Lead Sample Location Drawing Grindstone Campground – Wastewater Treatment Plant Building 1946 Laurel Valley Road; Troutdale, VA 24378 Hurt & Proffitt Project Number: 20250244 Note: Drawing NOT to Scale
001-EXDC-AB
002-INDC-AB
003-FLSH-A
L-001
L-002
L-003
SanAir ID#: 25013698
Project #: 20250244 Project Name: Grindstone WWT Report Date: 3/10/2025
Analysis Report prepared for Hurt & Proffitt, Inc.
Dear T. Wood, We at SanAir would like to thank you for the work you recently submitted. The 5 sample(s) were received on Friday, February 28, 2025 via UPS. The final report(s) is enclosed for the following sample(s): 001-EXDC-A, 001-EXDC-B, 002-InDC-A, 002-InDC-B, 003-FLSH-A.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 5 samples in Good condition.
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
20250244Project Number:
P.O. Number:
Project Name: Grindstone WWT
2/27/2025Collected Date:
2/28/2025 10:40:00 AMReceived Date:
3/10/2025 9:20:53 AM
25013698 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
434-841-3893 (c)Phone:
Analyst: Forman, Sydney
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
001-EXDC-A / 25013698-001
Exterior Door Caulk
White Non-Fibrous
Homogeneous
2% Wollastonite 98% Other None Detected
001-EXDC-B / 25013698-002
Exterior Door Caulk
White Non-Fibrous
Homogeneous
2% Wollastonite 98% Other None Detected
002-InDC-A / 25013698-003 Interior Door Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
002-InDC-B / 25013698-004 Interior Door Caulk
White Non-Fibrous
Homogeneous
100% Other None Detected
003-FLSH-A / 25013698-005
Cementitious Flashing
Various Non-Fibrous
Heterogeneous
100% Other None Detected
Analyst:
Analysis Date: 3/10/2025 Date: 3/10/2025
Approved Signatory:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
20250244Project Number:
P.O. Number:
Project Name: Grindstone WWT
2/27/2025Collected Date:
2/28/2025 10:40:00 AMReceived Date:
3/10/2025 9:20:53 AM
25013698 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Disclaimer and Additional Information:
Asbestos Bulk PLM EPA 600/R-93/116
This report is the sole property of the client named on the chain-of-custody (COC) submitted to SanAir Technologies Laboratory, Inc. (SanAir). Results in the report are confidential information intended only for the use by the customer listed on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission. The final report shall not be reproduced, except in full, without written approval of the laboratory to assure that parts of the report are not taken out of context.
This report and any information contained within shall not be edited, altered, or modified in any way by any persons or agencies receiving, viewing, distributing, or otherwise possessing a copy of this final report. The laboratory reserves the right to perform amendments to any finalized report, of which shall supersede and make obsolete any previous editions. Such changes, modifications, additions, or deletions shall be effective immediately upon notice thereof, which may be given by means including but not limited to posting on the SanAir client portal website, electronic or conventional mail, or by any other means.
The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client on the COC. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample(s) in the condition received at the laboratory and information provided by the client on the COC, such as: project number, project name, collection dates, P.O. number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start-stop times that may affect the validity of the results in this report. Samples were received in good condition unless otherwise noted on the report. When the client requires samples to be tested that deviates from a specific method or condition, all reported results may be affected by the deviation. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted.
This report does not constitute nor shall not be used by the client to claim product, process, system, or person certification, approval, or endorsement by NVLAP, NIST, NELAC, AIHA LAP, LLC or any other U.S.
governmental agencies; all or somet tests contained in this report may not be accredited by every local, state, and federal regulatory agencies. Refer to the SanAir website at www.sanair.com for copies of current certificates and scopes of various accreditations, certifications, and licenses or contact the laboratory for inquiries regarding the status or scope of an accreditation or certification.
Samples are held for a period of 60 days. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. For NY state samples, method EPA 600/M4-82-020 is performed.
NYELAP Disclaimer:
Polarized-light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.
Asbestos Accreditations, Certifications, and Licenses National Voluntary Laboratory Accreditation Program (NVLAP) Lab Code 200870-0 City of Philadelphia Department of Public Health Air Management Services, Certification#ALL-460 Commonwealth of Pennsylvania Department of Environmental Protection Number 68-05397 California State Environmental Laboratory Accreditation Program Certificate Number 2915 Colorado Department of Public Health and Environment Registration Number AL-23143 Connecticut Department of Public Health Environmental Laboratory Registration Number PH-0105 Massachusetts Department of Labor Standards Asbestos Analytical Services License Number:
AA000222
State of Maine Department of Environmental Protection License Number: LB-0075 New York State Department of Health Laboratory ID: 11983 State of Rhode Island Department of Health Certification No.: PLM00126 Texas Department of State Health Services License Number: 300440 Commonwealth of Virginia Department of Professional and Occupational Regulation Number:
3333000323 State of Washington Department of Ecology Laboratory ID: C989 State of West Virginia Bureau for Public Health Analytical Laboratory Number: LT000616 Vermont Department of Health License Number: Asb-Co-An-000006 Louisiana Department of Environmental Quality AI Number 212253, LELAP Lab ID #05088
Revision#03, 10/3/2024 Page 4 of 5
SanAir ID#: 25013699
Project #: 20250244 Project Name: Grindstone WWT Report Date: 3/7/2025
Analysis Report prepared for Hurt & Proffitt, Inc.
Dear T. Wood, We at SanAir would like to thank you for the work you recently submitted. The 3 sample(s) were received on Friday, February 28, 2025 via UPS. The final report(s) is enclosed for the following sample(s): L-01, L-02, L-03.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Abisola Kasali Metals Laboratory Director SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Chemistry Analysis
- Disclaimers and Additional Information
Sample conditions:
- 3 samples in Good condition.
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
20250244Project Number:
P.O. Number:
Project Name: Grindstone WWT
2/27/2025Collected Date:
2/28/2025 10:40:00 AMReceived Date:
3/7/2025 9:59:41 AM
25013699 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Analyst: Templeton, Kat
Test Method: SW846/M3050B/7000B
Lead Paint Analysis PAINT µg Pb Sample Size Calculated Sample Sample
Sample Description In Sample (grams) RL Results Results
25013699 - 1 L-01 2759 0.101 99 27320 2.732 % Door Green µg/g (ppm) By Weight
25013699 - 2 L-02 19 0.1095 91.3 177.5 0.018 % CMU White (Interior) µg/g (ppm) By Weight
25013699 - 3 L-03 15 0.1127 88.7 132.2 0.013 % Exterior CMU White µg/g (ppm) By Weight
Method Reporting Limit <10 µg/0.1 g paint
Signature:
Date: 3/3/2025 Date: 3/3/2025
Sample L-01 matrix spike failed.
Reviewed:
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com
20250244Project Number:
P.O. Number:
Project Name: Grindstone WWT
2/27/2025Collected Date:
2/28/2025 10:40:00 AMReceived Date:
3/7/2025 9:59:41 AM
25013699 SanAir ID Number
FINAL REPORT
Hurt & Proffitt, Inc.Name:
Address: 2524 Langhorne Road
Lynchburg, VA 24501
Disclaimer
SanAir Technologies Laboratory, Inc. participates in the Environmental Lead Accreditation Program (ELAP) administered by AIHA LAP, LLC (Laboratory ID LAP-162952). Refer to our accreditation certificate and scope on our website or www.aihaaccreditedlabs.org for an up to date list of the Fields of Testing for which we are accredited.
SanAir also participates in the State of New York’s DOH-ELAP (Lab Id 11983), and has met the EPA's NLLAP program standards. This report does not constitute nor shall be used by the client to claim product, process, system, or person certification, approval, or endorsement by AIHA LAP, LLC, NELAC, NIST, and/or any other U.S.
governmental agencies; and test results in this report may not be accredited by every local, state or federal regulatory agency.
This report is the sole property of the client named on the SanAir Technologies Laboratory chain-of-custody (COC).
Results in the report are confidential information intended only for the use by the customer listed on the chain of custody. Neither results nor reports will be discussed with or released to any third party without our client’s written permission. Final reports cannot be reproduced, except in full, without written authorization from SanAir
Technologies Laboratory, Inc. This report and any information contained within shall not be edited, altered, or modified in any way by any persons or agencies receiving, viewing, distributing, or otherwise possessing a copy of this final report. The laboratory reserves the right to perform amendments to any finalized report, of which shall supersede and make obsolete any previous editions. Such changes, modifications, additions, or deletions shall be effective immediately upon notice thereof, which may be given by means including but not limited to posting on the SanAir client portal website, electronic or conventional mail, or by any other means. The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results of the analysis is dependent upon the method of sample procurement and information provided by the client on the COC. SanAir is not responsible for the method of sample procurement. SanAir assumes no responsibility for information provided by the client on the COC such as project number, project name, collection dates, po number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start stop times that may affect the validity of the results in this report. SanAir Technologies Laboratory, Inc only assures the precision and accuracy of the data it generates and assumes no responsibility for errors or biasing that occur during collection prior to SanAir’s receipt of the sample(s).
Evaluation reports are based solely on the sample(s) in the condition in which they arrived at the laboratory and on the information provided by the client on the COC. Sample(s) were received in good condition unless otherwise noted on the report. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted. SanAir’s Method Detection Limits (MDL) and Reporting Limits (RL) have been derived using various materials meeting each accrediting agencies’ standards. All quality control results are acceptable unless otherwise noted. SanAir does not make contamination corrections to reports based upon analysis of laboratory and/or field blanks. All samples are disposed of after 90 days unless otherwise requested by the client. For Lead Exposure
Limits, refer to HUD Guidelines for the Evaluation and Control of Lead-Based Paint Hazards and State and Federal
Regulations, where applicable. For Lead Exposure Limits in Air, refer to EPA National Ambient Air Quality Standards, OSHA Action Levels & Permissible Exposure Limits (General Industry & Construction), and relative state or federal requirements where applicable.
AIHA LAP, LLC Lab ID: LAP-162952 Commonwealth of VA Department of General Services DCLS, VELAP Laboratory ID#460251 New York State Department of Health Laboratory ID No: 11983 California State Environmental Laboratory Accreditation Program Certificate No: 2915 State of Connecticut Department of Public Health Environmental Laboratory Registration Number: PH-0105 New Jersey Department of Environment Protection Environmental Laboratory Certification ID# VA014 Ohio Department of Health Environmental Lead Laboratory Approval Number E10049 State of Rhode Island Department of Health Environmental Lead Laboratory No LAO00371
Revision Date 4/18/2023