AmendmentA0006.pdf

PDF 376 KB Posted

Attached to
GAOA Timberline Lodge Boiler
Solicitation number
1240BH21R0014
Issued by

About this file

This solicitation is for a multi-phase boiler replacement project at Timberline Lodge. The project includes removing old generators and boilers, installing new hot water boilers and circulation pumps, replacing fuel oil pumps and piping, designing and integrating new DDC control systems, and replacing room radiators. Phase 1 is due by late October 2021 and involves boiler room work. Optional Phase 2 would replace one steam boiler and install more radiators by May 2022. Optional Phase 3 replaces the second steam boiler and installs more radiators by May 2023. It also connects kitchens and pools to the new system. Optional Phase 4 replaces two hot water boilers by May 2023. The estimated budget is over $10 million. Responses are due through the SAM website. The work would be conducted by the Forest Service Pacific Northwest Region and impact lodge operations.

View the file

Other files

File Type Posted
AmendmentA0009.pdf PDF
AmendmentA0008.pdf PDF
AmendmentA0007.pdf PDF
Amendment0005.pdf PDF
Interested Vendors.pdf PDF
AmendmentA0004.pdf PDF
TimberlineBoilersErrataAmendment4-20210514.pdf PDF
260000A-ElectricalBasicRequirements-Testing-20210517.pdf PDF
AmendmentA0003.pdf PDF
AmendmentA0002.pdf PDF
AmendmentA0001.pdf PDF
MainAndWyEastDayLodge-Drawings-20210426.pdf PDF
CompleteSolicitation.pdf PDF
MainAndWyEastDayLodgeSpecs-20210426.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

1240BH21R0014

x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

40BH

PORTLAND OR 97204-2829

STE 310

1220 SW 3RD AVE

USDA-FS CSA NORTHWEST 6

GAOA05/19/20210006

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

04/26/2021

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

See attached.

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

DARCY J. RAPOZA

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

19 May 2021

5/19/2021 GAOA Timberline Lodge Boiler Amendment #6 Page - 1/2

1. AMENDMENT #6 GAOA TIMBERLINE LODGE BOILER 5/19/2021

1.01 RFI QUESTIONS (Q) ANSWERS (S)

A. Below are Q/A to control system questions:

1. Q: Please confirm all space sensor locations shown on the print are existing with a space sensor cable present at that location wired back to an existing DDC Panel?

a. A: It is assumed that existing space sensors are wired back to existing DDC control panels. Contractor will need to field verify locations and condition of wiring to be compatible with existing controls and any new controllers.

2. Q: Are existing DDC controls for room convectors to be reused or replaced (temp sensors w/setpoint adjustment & associated controllers (controllers show on MD drawings)?

a. A: Existing DDC system controllers may be reused for connection to room convector valves or new controllers may be installed. Contractor shall field verify existing wiring and DDC control system compatibility. Sheet MD2.4 shows existing DDC control panels to be demolished. These existing panels are not required to be demolished and may be reused if compatible with new design and additional control valves.

b. Sheet M2.4 show existing DDC control panel locations, which may be reused if compatible. There are other existing DDC control panels that are not shown on drawings.

3. Q: Please indicate where new DDC Panels are to be located for new DDC points?

a. A: These new DDC control panel locations are not shown. Contractor is to determine locations for new DDC control panels and power requirements for existing and new control panels. See specifications 23 09 00 and 26 09 00, 27 00 00 and 27 00 01 for power and connection details

4. Q: Please show locations for new space sensor locations not shown?

a. A: Contractor will determine location of new space sensors if not shown on drawings. Coordination with the historic preservation plan and other trades will be required.

5. Q: Can existing wiring to Convector and Space Sensor locations be reused?

a. A: Yes if wiring is compatible with the existing or new DDC control panels, new control valves and space sensors.

6. Q: How is contractor to access the wall locations for new Sensor and/or cabling locations for Space Sensors and Convectors that currently do not have existing wires? What is the process of determining an acceptable pathway/raceway route?

Who is responsible for opening & closing up the walls/paneling/etc that is required for new wiring/cabling?

a. A: Access, demolition and refinishing will need to be coordinated with other trades and meet the historic preservation requirements and be approved by the CO prior to demolition. If additional sensors are required beyond those shown on the mechanical drawings, the contractor shall provide these sensors, wiring and DDC controls.

7. Q: Please indicate which convectors share a common space sensor?

a. A: It is assumed that areas that have existing space sensors will control multiple control valves in that space.

5/19/2021 GAOA Timberline Lodge Boiler Amendment #6 Page - 2/2

8. Q: Is there an existing and available raceway for the new Control Security Network cabling between the Main Lodge & Day Lodge?

a. A: There are spare fiber optic cable pairs from the main lodge to the Day

Lodge to be used to separate the main Timberline Local area network from the new separate DDC control system Local area network. See 26 09 00, 27 00 00 and 27 00 01 for network wiring and security requirements.

END OF SECTION

Amendment6continuation.pdf
1. amendment #6 GAOA Timberline Lodge Boiler 5/19/2021
1.01 RFI questions (Q) answers (s)
A. Below are Q/A to control system questions:
1. Q: Please confirm all space sensor locations shown on the print are existing with a space sensor cable present at that location wired back to an existing DDC Panel?
a. A: It is assumed that existing space sensors are wired back to existing DDC control panels. Contractor will need to field verify locations and condition of wiring to be compatible with existing controls and any new controllers.
2. Q: Are existing DDC controls for room convectors to be reused or replaced (temp sensors w/setpoint adjustment & associated controllers (controllers show on MD drawings)?
a. A: Existing DDC system controllers may be reused for connection to room convector valves or new controllers may be installed. Contractor shall field verify existing wiring and DDC control system compatibility. Sheet MD2.4 shows existing DDC control...
b. Sheet M2.4 show existing DDC control panel locations, which may be reused if compatible. There are other existing DDC control panels that are not shown on drawings.
3. Q: Please indicate where new DDC Panels are to be located for new DDC points?
a. A: These new DDC control panel locations are not shown. Contractor is to determine locations for new DDC control panels and power requirements for existing and new control panels. See specifications 23 09 00 and 26 09 00, 27 00 00 and 27 00 01 for ...
4. Q: Please show locations for new space sensor locations not shown?
a. A: Contractor will determine location of new space sensors if not shown on drawings. Coordination with the historic preservation plan and other trades will be required.
5. Q: Can existing wiring to Convector and Space Sensor locations be reused?
a. A: Yes if wiring is compatible with the existing or new DDC control panels, new control valves and space sensors.
6. Q: How is contractor to access the wall locations for new Sensor and/or cabling locations for Space Sensors and Convectors that currently do not have existing wires? What is the process of determining an acceptable pathway/raceway route? Who is r...
a. A: Access, demolition and refinishing will need to be coordinated with other trades and meet the historic preservation requirements and be approved by the CO prior to demolition. If additional sensors are required beyond those shown on the mechani...
7. Q: Please indicate which convectors share a common space sensor?
a. A: It is assumed that areas that have existing space sensors will control multiple control valves in that space.
8. Q: Is there an existing and available raceway for the new Control Security Network cabling between the Main Lodge & Day Lodge?
a. A: There are spare fiber optic cable pairs from the main lodge to the Day Lodge to be used to separate the main Timberline Local area network from the new separate DDC control system Local area network. See 26 09 00, 27 00 00 and 27 00 01 for netw...