This document summarizes an inspection report for fire protection and alarm systems at a USDA facility in Athens, Georgia. The report details inspections of clean agent fire suppression systems and alarm panels in multiple server rooms in the facility's basement, sub-basement, and second floor. It identifies deficiencies with batteries in the sub-basement alarm panel, non-functional alarm panels in two second floor server rooms damaged by power surges, and recommends removing an unused alarm panel and suppression system from the second floor connector server room. The related federal contract opportunity is for O&M support services at the USNPRC in Athens, Georgia, issued by the USDA Agricultural Research Service.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Rev: 02-25-21 Job #: 25692562
USDA/Four Seasons Environment-Alarm system 027575U013 3200343
VSC Fire & Security
Atlanta 1780 Corporate Drive, Suite 425
Norcross
GA
30093
(678) 252-0600
N/A
Frequency Semi-Annual Inspection Type Clean Agent/Halon System Test & Inspection
Current State accepted NFPA Standard Edition: Georgia-NFPA 2001, 2018 Edition, Standard on Clean Agent Fire Extinguishing Systems
Technician's Name: Randy McIntyre Inspection Date 08/17/22 01:55:41 PM
Location Location Name USDA/Four Seasons Environment-Alarm system 027575U013 3200343
Street Address 950 College Station Rd
City Athens State GA Zip Code 30506
Billing Customer Name CAS / FSE JV, LLC (formerly Four Seasons)
Street Address 950 College Station Rd.
City Athens State GA Zip Code 30613
Contact Information Name Eric Baker Phone 706-546-3118
Email erbaker@fseinc.net
Notifications This inspection test requires disabling/restoring a Fire System and/or notifying a Monitoring Service.
Date(s) put on test: 8/17/22 Time(s) put on test: 8:00am
Date(s) restored: 8/17/22 Time(s) restored: 3:30pm
Monitoring Company and Operator Name(s) notified of test and restoral: Customer called
Name(s) of Owner, Owner's Rep., Occupants and/or Tenants notified of test, restoral and any deficiencies:
Rico
Local Emergency Services, AHJ, or Insurance Rep. notified of test, restoral, or any impairments, if required:
NA
TECHNICIAN'S COMMENTS
Any known adverse conditions noted which existed prior to this inspection and test:
Issues regarding restoral, or conditions which preclude restoral of Fire Protection Equipment/System(s):
Panels on 2nd Floor Room 208 Server Room and 2nd Floor Connector Server Room panels are not functional.
Same conditions after inspection as before inspection.
Clean Agent/Halon Suppression System
System Information, Inspection & Test ID # Area / Location Manufacturer Model Serial Agent Type Result
2nd Floor Connector Server Room Fenwal FM 200 AA265361 HFC 227ea: FM200 Fail
Actuator/Initiator new-replace date
Activation Delay Time Temperature in Cylinder storage area Flex Hose 5 Yr Date Hose Part #
NA NA 70 NA NA
Enclosure and protected area has remained unchanged since last Inspection or installation, and is acceptable? N/I
Notes The customer wants quote to demo panel, tank, piping, and devices
2nd Floor Room 208 Server Room Kiddie Fenwal FM 200 Sphere 10548 HFC 227ea: FM200 Fail
Actuator/Initiator new-replace date
Activation Delay Time Temperature in Cylinder storage area Flex Hose 5 Yr Date Hose Part #
NA NA 70 NA NA
Enclosure and protected area has remained unchanged since last Inspection or installation, and is acceptable? Yes
Seal any new penetrations in protected areas
Basement Server Room Kiddie Fenwal FM 200 Sphere 10547 HFC 227ea: FM200 Pass
Actuator/Initiator new-replace date
Activation Delay Time Temperature in Cylinder storage area Flex Hose 5 Yr Date Hose Part #
NA 30 70 NA NA
Enclosure and protected area has remained unchanged since last Inspection or installation, and is acceptable? Yes
Sub Basement Server Room Ansul FM 200 57005 HFC 227ea: FM200 Pass
Actuator/Initiator new-replace date
Activation Delay Time Temperature in Cylinder storage area Flex Hose 5 Yr Date Hose Part #
NA 30 70 NA NA
Enclosure and protected area has remained unchanged since last Inspection or installation, and is acceptable? Yes
Clean Agent/Halon Suppression System Container Information
ID # / Area /
Location Contents S/N
Gross Weight
Fill Weight
Tank psi
Liquid Level
% of Loss
Refillable Yes|No
Last Hydro Inspection
Pass / Fail / NI
Sub Basement Server Room
FM200 58412 100 50 Ok NA No Loss
No Loss 08/17/08 Pass
Basement Server Room
FM200 57005 68 33 Ok NA No Loss
No Loss 06/02/92 Pass
2nd Floor Server Room 208 Outside
Hallway Ceiling
FM200 10548 78 44 Ok NA No Loss
No Loss 06/02/92 Pass
2nd Floor Connector Server Room
FM200 AA265361 99 47 Ok NA No Loss
No Loss 06/02/92 Pass
Alarm System Panels [ ] Visual Inspection only performed this date. [x] Visual Inspection and Functional Test performed this date.
Panel Information ID # Area / Location Make Model Serial
Sub Basement Server Room Ansul 542R NA
Panel Use Type of System Software Revision Revision Date
Main FACP Conventional Unknown Unknown
Alarm Panel Visual Inspection Pass Alarm Panel Functional Test: Pass
Primary Power Supply Information Nominal Voltage Amp
Rating Overcurrent
Protection Type Overcurrent
Protection Rated Amps
Overcurrent Protection Location
(Panel #)
Disconnecting Means Location Breaker
120 4 Breaker 20 Unknown Unknown
Second Battery Power Supply Information & Test Manufacturer Model Battery Type Quantity Voltage
Rating Amp Hour
Rating Install Date
Power Rite PRB127 Sealed Lead Acid 2 12 7 2016-01-19
Load/Discharge Test: Fail Charger Test: Pass
Generator Power Supply or Emergency Power Supply System Information
Is there emergency standby power supply, i.e. dedicated generator or ESS secondary power supply? No
Basement Server Room Kiddie Fenwal 732 NA
Panel Use Type of System Software Revision Revision Date
Suppression System Release Panel Conventional Unknown Unknown
Alarm Panel Visual Inspection Pass Alarm Panel Functional Test: Pass
Primary Power Supply Information Nominal Voltage Amp
Rating Overcurrent
Protection Type Overcurrent
Protection Rated Amps
Overcurrent Protection Location
(Panel #)
Disconnecting Means Location Breaker
120 4 Breaker 20 ELPB 20
Second Battery Power Supply Information & Test Manufacturer Model Battery Type Quantity Voltage
Rating Amp Hour
Rating Install Date
Duracell Ultra DURA12-8F Sealed Lead Acid 2 12 8 2021-10-19
Load/Discharge Test: Pass Charger Test: Pass
ID # Area / Location Make Model Serial
2nd Floor Server Room 208 Kiddie Fenwal 732 NA
Panel Use Type of System Software Revision Revision Date
Suppression System Release Panel Conventional Unknown Unknown
Alarm Panel Visual Inspection Fail Alarm Panel Functional Test: N/A
Primary Power Supply Information Nominal Voltage Amp
Rating Overcurrent
Protection Type Overcurrent
Protection Rated Amps
Overcurrent Protection Location
(Panel #)
Disconnecting Means Location Breaker
120 4 Breaker 20 Computer Panel Breaker 13
Second Battery Power Supply Information & Test Manufacturer Model Battery Type Quantity Voltage
Rating Amp Hour
Rating Install Date
Duracell DURA12-8 Sealed Lead Acid 2 12 8 2021-05-19
Load/Discharge Test: Pass Charger Test: Pass
2nd Floor Connector Server Room Kiddie Fenwal 2320 NA
Panel Use Type of System Software Revision Revision Date
Suppression System Release Panel Conventional Unknown Unknown
Alarm Panel Visual Inspection Fail Alarm Panel Functional Test: N/A
Primary Power Supply Information Nominal Voltage Amp
Rating Overcurrent
Protection Type Overcurrent
Protection Rated Amps
Overcurrent Protection Location
(Panel #)
Disconnecting Means Location Breaker
0 2 Breaker 20 Unknown Unknown
Second Battery Power Supply Information & Test Manufacturer Model Battery Type Quantity Voltage
Rating Amp Hour
Rating Install Date
Ultratech UT 1213 Sealed Lead Acid 2 12 1.3 2021-05-03
Load/Discharge Test: N/A Charger Test: N/A
Initiating Device List
[ ] Visual Inspection only performed this date. [x] Visual Inspection and Functional Test performed this date.
Zone or Address ID # / Area / Location Manufacturer Model Device Type Pass / Fail / NI
Z3 Sub-Basement Server Room By Panel
Ansul Manual Release Manual Station Pass
Z3 Basement Server Room Below Panel
Fenwal Manual Release Manual Station Pass
Z3 2nd Floor Connector Server Room On Panel
Door
Fenwal Manual Release Manual Station NI
Z3 2nd Floor Room 208 Server Room Below
Panel
Fenwal Manual Release Manual Station NI
Audible/Visual Appliance List
[ ] Visual Inspection only performed this date. [x] Visual Inspection and Functional Test performed this date.
ID # / Area / Location Manufacturer Model Type Pass / Fail / NI
Above Sub Basement Panel Wheelock 24v 6” Bell Pass Above Sub Basement Panel Wheelock MT-241575W-FR Horn/Strobe Pass
Outside Sub Basement Server Room
Wheelock RSS-24MCW-FR Strobe Pass
Above Basement Panel Wheelock MT-241575W-FR Horn/Strobe Pass Outside Basement Server
Room Wheelock RSS-24MCW-FR Strobe Pass
Above Room 208 Panel Wheelock MT-241575W-FR Horn/Strobe NI Outside Server Room Door
Wheelock RSS-24MCW-FR Strobe NI
On Panel Door Wheelock MT-241575W-FR Horn/Strobe NI Outside 2nd Floor Connector
Server Room Door Wheelock RSS-25MCW-FR Strobe NI
Smoke Detection Inspection And Test
Note: Smoke Detection Device Sensitivity Testing performed only on a contracted basis at the frequency determined by the Customer/Building Owner. It is the
Customer's/Building Owner's responsibility to have these services performed in accordance with your State and Local requirements, and the applicable version of the NFPA 72 Standard.
For more information, and to arrange Sensitivity Testing of your Smoke Detection Devices, please call.
SMOKE DETECTION SENSITIVITY TEST LAST
PERFORMED:
Unknown SMOKE DETECTION SENSITIVITY TEST
PERFORMED THIS INSPECTION:
no
[ ] Visual Inspection only performed this date. [x] Visual Inspection and Functional Test performed this date.
Zone or Address
ID # / Area / Location
Manufacturer Model Type Pass / Fail / NI Sensitivity Range
Test Value
Z1 Sub-Basement Ceiling
System Sensor Photo Photo Pass
Z2 Sub-Basement Ceiling
System Sensor Ion Ion Pass
Z1 Basement Server Room Ceiling
Fenwal Photo Photo Pass
Z2 Basement Server Room Ceiling
Fenwal Photo Photo Pass
Z1 2nd Floor Connector Server Room Ceiling
Fenwal Photo Photo NI
Z2 2nd Floor Connector Server Room Ceiling
Fenwal Photo Photo NI
Z1 2nd Floor Room 208 Server Room Sub-
Floor
Fenwal Photo Photo NI
Z2 2nd Floor Room 208 Server Room Sub-
Floor
Fenwal Photo Photo NI
Z1 2nd Floor Room 208 Server Room Ceiling
Fenwal Photo Photo NI
Z2 2nd Floor Room 208 Server Room Ceiling
Fenwal Photo Photo NI
Supplementary Equipment List
[ ] Visual Inspection only performed this date. [x] Visual Inspection and Functional Test performed this date.
ID # / Area / Location Type Pass / Fail
Sub-Basement Server Room Below Panel Abort Station Pass
Basement Server Room Below Panel Abort Station Pass
2nd Floor Connector Server Room On Panel Door
Abort Station NI
2nd Floor Room 208 Server Room Below Panel
Abort Station NI
Clean Agent/Halon Suppression System Not Inspected
Location In Site Result Reason
2nd Floor Connector Server Room N/I System is not being used panel is red tagged
Alarm Panel Deficiencies
Location In Site Severity Issue
Sub Basement Server Room deficient Batteries in Sub-Basement Server Room Panel failed load test during inspection 2-22v7ah batteries
2nd Floor Server Room 208 inoperable 2nd Floor Room 208 Server Room Fenwal 732 Panel took a power surge and damaged board.
System is red tagged and we have quoted to replace FACP Board.
2nd Floor Connector Server Room deficient 2nd Floor Connector Server Room Fenwal Panel was powered down system is no longer in use.
We will quote to remove panel tank and all devices.
Initiating Device Not Tested
Location In Site Result Reason
2nd Floor Connector Server Room On Panel Door N/I Panel was powered down
2nd Floor Room 208 Server Room Below Panel N/I Panel damaged from power surge
Audible Visual Appliance Not Tested
Location In Site Severity Issue
Above Room 208 Panel N/I Panel damaged from power surge
Outside Server Room Door 208 N/I Panel damaged from power surge
On Panel Door N/I Panel powered down
Outside 2nd Floor Connector Server Room Door N/I Panel powered down
Supplementary Equipment Not Tested
Location In Site Result Reason
2nd Floor Connector Server Room On Panel Door N/I Panel was powered down no longer in use
2nd Floor Room 208 Server Room Below Panel N/I Panel was damaged by power surge we have quote for replacement