This document is an inspection report for a fire alarm system at a USDA facility in Athens, Georgia. The report provides details of the inspection and testing conducted on the system, including the control unit make and model, primary and secondary power sources, initiating and notification devices tested on different floors, interface equipment, supervising station functions, and public emergency reporting. Defects found include bypass conditions, devices requiring replacement, programming issues, and inoperable notification appliances. Test notifications were made to building occupants and management, monitoring and emergency response organizations. The system was restored to normal operation and certified as inspected according to NFPA 72 standards. Owner acceptance of the report is documented.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEVICE
MODEL
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
Heat Detector FDX-551R Serv. Bldg. SSB6A - Test Lab N3L1D20 Test Pass Heat Detector FST-851 Serv. Bldg. N3L1D71 Test Pass Heat Detector FST-851 Serv. Bldg. Warehouse North N3L1D72 Test Pass Heat Detector FST-851 Serv. Bldg. Generator Room N3L1D38 Test Pass Heat Detector FST-851 Serv. Bldg. A/C Equip. Room N3L1D30 Test Pass Heat Detector FST-851 Serv. Bldg. A/C Equip. Room N3L1D39 Test Pass Heat Detector FST-851 Serv. Bldg. A/C Equip. Room N3L1D31 Test Pass Heat Detector FST-851 Serv. Bldg. A/C Equip. Room N3L1D32 Test Pass Heat Detector FST-851 Serv. Bldg. Boiler Room N3L1D34 Test Pass Heat Detector FST-851 Serv. Bldg. Boiler Room N3L1D35 Test Pass Heat Detector FST-851 Serv. Bldg. Boiler Room N3L1D36 Test Pass Heat Detector FST-851 Serv. Bldg. Boiler Room N3L1D37 Test Pass Heat Detector FDX-551R Serv. Bldg. Machine Shop N3L1D01 Test Pass Heat Detector FDX-551R Serv. Bldg. Machine Shop N3L1D09 Test Pass Heat Detector FDX-551R Serv. Bldg. Pipe Shop N3L1D05 Test Pass Heat Detector FDX-551R Serv. Bldg. Pipe Shop N3L1D06 Test Pass Heat Detector FDX-551R Serv. Bldg. Pipe Shop N3L1D24 Test Pass Heat Detector FDX-551R Serv. Bldg. Implement N3L1D25 Untested Disabled Heat Detector FST-751 Serv. Bldg. Implement N3L1D26 Untested Disabled Heat Detector FDX-551R Serv. Bldg. Paint Shop N3L1D14 Test Pass Heat Detector FDX-551R Serv. Bldg. Paint Shop N3L1D76 Test Pass Heat Detector FDX-551R Serv. Bldg. Carpentry Shop N3L1D11 Test Pass Heat Detector FDX-551R Serv. Bldg. Carpentry Shop N3L1D12 Test Pass Heat Detector FDX-551R Serv. Bldg. Garage N3L1D18 Test Pass Heat Detector FDX-551R Serv. Bldg. Garage N3L1D19 Test Pass Heat Detector FDX-551R Serv. Bldg. Electric Shop N3L1D02 Test Pass Heat Detector FDX-551R Serv. Bldg. Locker Room N3L1D23 Test Pass Heat Detector FDX-551R Serv. Bldg. T&F Research N3L1D10 Test Pass Heat Detector FDX-551R Serv. Bldg. Bldg. Automotive N3L1D75 Test Pass
Photo Detector SDX-551 Serv. Bldg. Engineers Office N3L1D29 Test Pass Photo Detector SDX-551 Serv. Bldg. Electric Room N3L1D33 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D07 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D08 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D21 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D22 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D27 Test Pass Photo Detector SDX-551 Serv. Bldg. East Corr. N3L1D28 Test Pass Duct Detector FDX-551 Serv. Bldg. AHU-10 N3L1D15 Test Pass Duct Detector FDX-551 Serv. Bldg. AHU-10 N3L1D16 Test Pass Duct Detector FDX-551 Serv. Bldg. AHU-9 N3L1D03 Test Pass Duct Detector FDX-551 Serv. Bldg. AHU-9 N3L1D04 Test Pass
Manual Station NBG-12LX Serv. Bldg. East Corr. N3L1M03 Test Pass Manual Station BRG-1R Serv. Bldg. A/C Equip. Exit N3L1M01 Test Pass Manual Station NBG-12LX Serv. Bldg. East Corr. N3L1M02 Test Pass Manual Station NBG-12LX Serv. Bldg. Boiler Rm. N3L1M04 Test Pass Manual Station NBG-12LX Serv. Bldg. Warehouse Exit N3L1M18 Test Pass Manual Station NBG-12LX Serv. Bldg. South Stairwell Exit N3L1M19 Test Pass
INSPECTION REPORT BY DEVICE
Russell Research USDA
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Manual Station NBG-12LX Serv. Bldg. Pipe Shop Exit N3L1M20 Test Pass Manual Station NBG-12LX Serv. Bldg. Carpenters Shop N3L1M21 Test Pass Photo Detector SDX-551 Chicken Lab Electric Room N3L1D90 Test Pass Manual Station NBG-12LX Chicken Lab Feed Storage N3L1M36 Test Pass Manual Station BRG-1R Chicken Lab Anti-Room 45 N3L1M37 Test Pass Manual Station BRG-1R Chicken Lab Rear Door N3L1M38 Test Pass Manual Station BRG-1R Chicken Lab Roll-up door N3L1M39 Test Pass Manual Station NBG-12LX Chicken Lab Electric Room N3L1M40 Test Pass Photo Detector FSP-751 Elev. Mach. Rm Elevator Shaft N1L4D96 No Access See Comments Photo Detector FSP-751 Elev. Mach. Rm Elevator Shaft N1L4D98 No Access See Comments Photo Detector FSP-751 Elev. Mach. Rm Elevator Shaft East N1L4D97 No Access See Comments Photo Detector FSP-751 Elev. Mach. Rm Elevator Shaft West N1L4D99 No Access See Comments Photo Detector FSP-751 Elev. Mach. Rm Elev. Equip. Rm. N1L4D13 Test Pass Photo Detector FSP-751 Elev. Mach. Rm Elev. Equip. Rm. N1L4D15 Test Pass Photo Detector SDX-551 Elev. Mach. Rm Elev. Equip. Rm. N1L4D92 Test Pass Manual Station BRG-1R Elev. Mach. Rm Elev. Equip. Rm. N1L4M92 Test Pass Heat Detector FDX-551R Penthouse Penthouse N1L4D12 Test Pass
Photo Detector FSP-751 Penthouse Penthouse N1L4D14 Test See Comments Photo Detector SDX-551 Penthouse Converter Room N1L4D91 Test Pass Manual Station NBG-12LX Penthouse Converter Room N1L4M91 Test Pass Heat Detector FDX-551R 8th Floor Janitor Rm. 827 N1L4D72 Test Pass Heat Detector FDX-551R 8th Floor Gear Rm. 828 N1L4D73 Test Pass Heat Detector FDX-551R 8th Floor Storage Rm. 802 N1L4D78 Test Pass Heat Detector FDX-551R 8th Floor Mechanical Room N1L4D80 Test Pass Heat Detector FDX-551R 8th Floor Mechanical Room N1L4D82 Test Pass Heat Detector FDX-551R 8th Floor Storage Rm. 856 N1L4D84 Test Pass
Photo Detector FSP-751 8th Floor E. Electrical Rm. N1L4D07 Test Pass Photo Detector FSP-751 8th Floor E. Telephone Rm. N1L4D08 Test Pass Photo Detector FSP-751 8th Floor Electrical Room N1L4D09 Test Pass Photo Detector FSP-751 8th Floor W. Telephone Rm. N1L4D10 Test Pass Photo Detector FSP-751 8th Floor W. Electrical Rm. N1L4D11 Test Pass Photo Detector SDX-551 8th Floor East Stairwell N1L4D66 Test Pass Photo Detector SDX-551 8th Floor East Corr. N1L4D67 Test Pass Photo Detector FSP-851 8th Floor East Corr. N1L4D68 Test Pass Photo Detector SDX-551 8th Floor East Corr. N1L4D69 Test Pass Photo Detector SDX-551 8th Floor East Corr. N1L4D70 Test Pass Photo Detector SDX-551 8th Floor East Corr. N1L4D71 Test Pass Photo Detector SDX-551 8th Floor Mid-Stair N1L4D74 Test Pass Photo Detector SDX-551 8th Floor Elevator Lobby N1L4D75 Test Pass Photo Detector SDX-551 8th Floor Center Corr. N1L4D76 Test Pass Photo Detector SDX-551 8th Floor Center Corr. N1L4D77 Test Pass Photo Detector FSP-851 8th Floor West Corr. N1L4D85 Test Pass Photo Detector SDX-551 8th Floor West Corr. N1L4D86 Test Pass Photo Detector SDX-551 8th Floor West Corr. N1L4D87 Test Pass Photo Detector SDX-551 8th Floor West Corr. N1L4D88 Test Pass Photo Detector SDX-551 8th Floor West Corr. N1L4D89 Test Pass Photo Detector FDX-551 8th Floor West Stairwell N1L4D90 Test Pass Duct Detector FDX-551 8th Floor AHU-8 N1L4D79 Test Pass Duct Detector FDX-551 8th Floor AHU-8 N1L4D81 Test Pass Duct Detector FDX-551 8th Floor RF-8 N1L4D83 Test Pass
Manual Station BRG-1R 8th Floor East Corr. N1L4M40 Test Pass Manual Station BRG-1R 8th Floor Elevator Lobby N1L4M41 Test Pass Manual Station BRG-1R 8th Floor West Corr. N1L4M42 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Heat Detector FDX-551R 7th Floor Janitor Rm. 729 N1L4D49 Test Pass Heat Detector FDX-551R 7th Floor Gear Rm. 730 N1L4D50 Test Pass Heat Detector FDX-551R 7th Floor Storage Rm. 702 N1L4D54 Test Pass Heat Detector FDX-551R 7th Floor Mechanical Room N1L4D56 Test Pass Heat Detector FDX-551R 7th Floor Mechanical Room N1L4D58 Test Pass Heat Detector FDX-551R 7th Floor Dishwash Rm. 758 N1L4D60 Test Pass
Photo Detector FSP-751 7th Floor E. Telephone Rm. N1L4D01 No Access No Access Photo Detector FSP-751 7th Floor E. Electrical Rm. N1L4D02 Test Pass Photo Detector FSP-751 7th Floor Electrical Room N1L4D03 Test Pass Photo Detector FSP-751 7th Floor Medicine Room N1L4D04 Test Pass Photo Detector FSP-751 7th Floor W. Electrical Rm. N1L4D05 Test Pass Photo Detector FSP-751 7th Floor W. Telephone Rm. N1L4D06 Test Pass Photo Detector SDX-551 7th Floor East Corr. N1L4D44 Test Pass Photo Detector SDX-551 7th Floor East Corr. N1L4D45 Test Pass Photo Detector SDX-551 7th Floor East Corr. N1L4D46 Test Pass Photo Detector SDX-551 7th Floor East Corr. N1L4D47 Test Pass Photo Detector SDX-551 7th Floor East Corr. N1L4D48 Test Pass Photo Detector SDX-551 7th Floor Elevator Lobby N1L4D51 Test Pass Photo Detector SDX-551 7th Floor Center Corr. N1L4D52 Test Pass Photo Detector SDX-551 7th Floor Center Corr. N1L4D53 Test Pass Photo Detector SDX-551 7th Floor West Corr. N1L4D61 Test Pass Photo Detector SDX-551 7th Floor West Corr. N1L4D62 Test Pass Photo Detector SDX-551 7th Floor West Corr. N1L4D63 Test Pass Photo Detector SDX-551 7th Floor West Corr. N1L4D64 Test Pass Photo Detector SDX-551 7th Floor West Corr. N1L4D65 Test Pass Duct Detector FDX-551 7th Floor AH-7 N1L4D55 Test Pass Duct Detector FDX-551 7th Floor AH-7 N1L4D57 Test Pass Duct Detector FDX-551 7th Floor RF-7 N1L4D59 Test Pass
Manual Station BRG-1R 7th Floor East Stairwell N1L4M37 Test Pass Manual Station BRG-1R 7th Floor Elevator Lobby N1L4M38 Test Pass Manual Station BRG-1R 7th Floor West Corr. N1L4M39 Test Pass Heat Detector FDX-551R 6th Floor Janitor Rm. 627 N1L3D27 Test Pass Heat Detector FDX-551R 6th Floor Gear Rm. 628 N1L3D28 Test Pass Heat Detector FDX-551R 6th Floor Center Room N1L3D32 Test Pass Heat Detector FDX-551R 6th Floor Mechanical Room N1L3D35 Test Pass Heat Detector FDX-551R 6th Floor Mechanical Room N1L3D36 Test Pass Heat Detector FDX-551R 6th Floor Center Room N1L3D38 Test Pass
Photo Detector SDX-551 6th Floor East Corr. N1L3D22 Test Pass Photo Detector SDX-551 6th Floor East Corr. N1L3D23 Test Pass Photo Detector SDX-551 6th Floor East Corr. N1L3D24 Test Pass Photo Detector SDX-551 6th Floor East Corr. N1L3D25 Test Pass Photo Detector SDX-551 6th Floor East Corr. N1L3D26 Test Pass Photo Detector FSP-851 6th Floor Elevator Lobby N1L3D29 Test Pass Photo Detector SDX-551 6th Floor Center Corr. N1L3D30 Test Pass Photo Detector SDX-551 6th Floor Center Corr. N1L3D31 Test Pass Photo Detector SDX-551 6th Floor West Corr. N1L3D39 Test Pass Photo Detector SDX-551 6th Floor West Corr. N1L3D40 Test Pass Photo Detector SDX-551 6th Floor West Corr. N1L3D41 Test Pass Photo Detector SDX-551 6th Floor West Corr. N1L3D42 Test Pass Photo Detector SDX-551 6th Floor West Corr. N1L3D43 Test Pass Photo Detector FSP-751 6th Floor E. Telephone Rm. N1L3D50 No Access No Access Photo Detector FSP-751 6th Floor E. Electrical Rm. N1L3D51 Test Pass Photo Detector FSP-751 6th Floor Electrical Room N1L3D52 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector FSP-751 6th Floor W. Telephone Rm. N1L3D53 Test Pass Photo Detector FSP-751 6th Floor W. Electrical Rm. N1L3D54 Test Pass Duct Detector FDX-551 6th Floor AH-6 N1L3D33 Test Pass Duct Detector FDX-551 6th Floor AH-6 N1L3D34 Test Pass Duct Detector FDX-551 6th Floor RF-6 N1L3D37 Test Pass
Manual Station BRG-1R 6th Floor East Corr. N1L3M34 Test Pass Manual Station BRG-1R 6th Floor Elevator Lobby N1L3M35 Test Pass Manual Station BRG-1R 6th Floor West Corr. N1L3M36 Test Pass Heat Detector FDX-551R 5th Floor Janitor Rm. 520 N1L3D06 Test Pass Heat Detector FDX-551R 5th Floor Center Room N1L3D10 Test Pass Heat Detector FDX-551R 5th Floor Mechanical Room N1L3D13 Test Pass Heat Detector FDX-551R 5th Floor Mechanical Room N1L3D14 Test Pass Heat Detector FDX-551R 5th Floor Center Room N1L3D16 Test Pass
Photo Detector SDX-551 5th Floor East Corr. N1L3D01 Test Pass Photo Detector SDX-551 5th Floor East Corr. N1L3D02 Test Pass Photo Detector SDX-551 5th Floor East Corr. N1L3D03 Test Pass Photo Detector SDX-551 5th Floor East Corr. N1L3D04 Test Pass Photo Detector SDX-551 5th Floor East Corr. N1L3D05 Test Pass Photo Detector SDX-551 5th Floor Elevator Lobby N1L3D07 Test Pass Photo Detector SDX-551 5th Floor Center Corr. N1L3D08 Test Pass Photo Detector SDX-551 5th Floor Center Corr. N1L3D09 Test Pass Photo Detector SDX-551 5th Floor West Corr. N1L3D17 Test Pass Photo Detector SDX-551 5th Floor West Corr. N1L3D18 Test Pass Photo Detector SDX-551 5th Floor West Corr. N1L3D19 Test Pass Photo Detector SDX-551 5th Floor West Corr. N1L3D20 Test Pass Photo Detector SDX-551 5th Floor West Corr. N1L3D21 Test Pass Photo Detector FSP-751 5th Floor E. Telephone Rm. N1L3D44 Test Pass Photo Detector FSP-751 5th Floor E. Electrical Rm. N1L3D45 Test Pass Photo Detector FSP-751 5th Floor Electrical Room N1L3D46 Test Pass Photo Detector FSP-751 5th Floor Gear Room N1L3D47 Test Pass Photo Detector FSP-751 5th Floor W. Electrical Rm. N1L3D48 Test Pass Photo Detector FSP-751 5th Floor W. Telephone Rm. N1L3D49 Test Pass Duct Detector FDX-551 5th Floor AHU-5 N1L3D11 Test Pass Duct Detector FDX-551 5th Floor AHU-5 N1L3D12 Test Pass Duct Detector FDX-551 5th Floor RF-5 N1L3D15 Test Pass
Manual Station BRG-1R 5th Floor East Corr. N1L3M31 Test Pass Manual Station BRG-1R 5th Floor Elevator Lobby N1L3M32 Test Pass Manual Station BRG-1R 5th Floor West Corr. N1L3M33 Test Pass Heat Detector FDX-551R 4th Floor Janitor Rm. 427 N1L3D57 Test Pass Heat Detector FDX-551R 4th Floor Gear Rm. 428 N1L3D58 Test Pass Heat Detector FDX-551R 4th Floor Autoclave Room N1L3D62 Test Pass Heat Detector FDX-551R 4th Floor Center Mechanical N1L3D65 Test Pass Heat Detector FDX-551R 4th Floor Center Room N1L3D67 Test Pass Heat Detector FDX-551R 4th Floor Mechanical Room N1L3D73 Test Pass Heat Detector FDX-551R 4th Floor By Stairs N2L3D01 Test Pass Heat Detector FDX-551R 4th Floor Mechanical Room N2L3D71 Test Pass
Photo Detector SDX-551 4th Floor East Corr. N1L3D55 Test Pass Photo Detector SDX-551 4th Floor East Corr. N1L3D56 Test Pass Photo Detector SDX-551 4th Floor Elevator Lobby N1L3D59 Test Pass Photo Detector SDX-551 4th Floor Center Corr. N1L3D60 Test Pass Photo Detector SDX-551 4th Floor Center Corr. N1L3D61 Test Pass Photo Detector SDX-551 4th Floor West Corr. N1L3D68 Test Pass Photo Detector SDX-551 4th Floor West Corr. N1L3D69 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 4th Floor West Corr. N1L3D70 Test Pass Photo Detector SDX-551 4th Floor West Corr. N1L3D71 Test Pass Photo Detector SDX-551 4th Floor West Corr. N1L3D72 Test Pass Photo Detector FSP-751 4th Floor Electrical Room N1L3D74 Test Pass Photo Detector FSP-751 4th Floor W. Electrical Rm. N1L3D75 Test Pass Photo Detector SDX-551 4th Floor East Corr. N1L3D76 Test Pass Photo Detector SDX-551 4th Floor East Corr. N1L3D77 Test Pass Photo Detector SDX-551 4th Floor East Corr. N1L3D78 Test Pass Photo Detector FSP-751 4th Floor E. Electrical Rm. N1L3D79 Test Pass Photo Detector FSP-751 4th Floor W. Telephone Rm. N1L3D93 Test Pass Photo Detector FSP-751 4th Floor E. Telephone Rm. N1L3D99 Test Pass Photo Detector SDX-551 4th Floor P T 4 Corr. N2L3D72 Test Pass Photo Detector SDX-551 4th Floor P401 Elev. Mach. Rm. N2L3D73 Test Pass Duct Detector FDX-551 4th Floor AHU-4 N1L3D63 Test Pass Duct Detector FDX-551 4th Floor AHU-4 N1L3D64 Test Pass Duct Detector FDX-551 4th Floor RF-4 N1L3D66 Test Pass Duct Detector FDX-551 4th Floor Duct Ret. Mech. N2L3D99 Test Pass Duct Detector FDX-551 4th Floor Duct Sup. Mech. N2L3D88 Test Pass
Manual Station BRG-1R 4th Floor East Stairwell N1L3M28 Test Pass Manual Station BRG-1R 4th Floor Elevator Lobby N1L3M29 Test Pass Manual Station BRG-1R 4th Floor West Corr. N1L3M30 Test Pass Manual Station BRG-1R 4th Floor Stair 6 N2L3M16 Test Pass Heat Detector FDX-551R 3rd Floor Center Equip. Rm. N1L2D42 Test Pass Heat Detector FDX-551R 3rd Floor Center Equip. Rm. N1L2D44 Test Pass Heat Detector FDX-551R 3rd Floor Mid Lab/Storage N2L3D03 Test Pass
Photo Detector SDX-551 3rd Floor East Corr. N1L2D31 Test Pass Photo Detector SDX-551 3rd Floor East Corr. N1L2D32 Test Pass Photo Detector SDX-551 3rd Floor East Corr. N1L2D33 Test Pass Photo Detector SDX-551 3rd Floor East Corr. N1L2D34 Test Pass Photo Detector SDX-551 3rd Floor East Corr. N1L2D35 Test Pass Photo Detector SDX-551 3rd Floor Bio Storage N1L2D36 Test Pass Photo Detector SDX-551 3rd Floor Elevator Lobby N1L2D37 Test Pass Photo Detector SDX-551 3rd Floor Center Corr. N1L2D38 Test Pass Photo Detector SDX-551 3rd Floor Center Corr. N1L2D39 Test Pass Photo Detector SDX-551 3rd Floor West Corr. N1L2D47 Test Pass Photo Detector SDX-551 3rd Floor West Corr. N1L2D48 Test Pass Photo Detector SDX-551 3rd Floor West Corr. N1L2D49 Test Pass Photo Detector SDX-551 3rd Floor West Corr. N1L2D50 Test Pass Photo Detector SDX-551 3rd Floor West Corr. N1L2D51 Test Pass Photo Detector FSP-751 3rd Floor W. Electrical Rm. N1L2D78 Test Pass Photo Detector FSP-751 3rd Floor W. Telephone Rm. N1L2D79 Test Pass Photo Detector FSP-751 3rd Floor E. Telephone Rm. N1L2D96 Test Pass Photo Detector FSP-751 3rd Floor E. Electrical Rm. N1L2D97 Test Pass Photo Detector FSP-751 3rd Floor Electrical Room N1L2D98 Test Pass Photo Detector FSP-751 3rd Floor Storage Closet N2L3D74 Test Pass Photo Detector SDX-551 3rd Floor Electrical Room N3L3D02 Test Pass Photo Detector SDX-551 3rd Floor Rear Storage N2L3D05 No Access No Access Photo Detector SDX-551 3rd Floor North Corr. 331 N2L3D56 Test Pass Photo Detector SDX-551 3rd Floor North Corr. 331 N2L3D57 Test Pass Photo Detector SDX-551 3rd Floor North Corr. 331 N2L3D58 Test Pass Photo Detector SDX-551 3rd Floor Center Corr. N2L3D59 Test Pass Photo Detector SDX-551 3rd Floor Stair 5 N2L3D60 Test Pass Photo Detector SDX-551 3rd Floor Corr. 311 N2L3D61 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 3rd Floor Corr. 311 N2L3D62 Test Pass Photo Detector SDX-551 3rd Floor Corr. 311 N2L3D63 Test Pass Photo Detector SDX-551 3rd Floor South Corr. N2L3D64 Test Pass Photo Detector SDX-551 3rd Floor Elev. Lobby 6 N2L3D65 Test Pass Photo Detector SDX-551 3rd Floor South Corr. N2L3D66 Test Pass Duct Detector FSD-751P 3rd Floor AH-3A N1L2D40 Test Pass Duct Detector FSD-751P 3rd Floor AH-3A N1L2D41 Test Pass Duct Detector FDX-551 3rd Floor Center Duct N1L2D43 Test Pass Duct Detector FDX-551 3rd Floor Center Duct N1L2D45 Test Pass Duct Detector FDX-551 3rd Floor Duct Conn. Corr. N2L3D22 Test Pass
Manual Station BRG-1R 3rd Floor East Corr. N1L2M25 Test Pass Manual Station BRG-1R 3rd Floor Elevator Lobby N1L2M26 Test Pass Manual Station BRG-1R 3rd Floor West Corr. N1L2M27 Test Pass Manual Station BRG-1R 3rd Floor Stair 5 N2L3M14 Test Pass Manual Station BRG-1R 3rd Floor Stair 6 N2L3M15 Test Pass Heat Detector FDX-551R 2nd Floor Open Storage N2L3D07 Test Pass Heat Detector FDX-551R 2nd Floor Open Storage N2L3D08 No Access No Access Heat Detector FDX-551R 2nd Floor Open Storage N2L3D09 Test Pass Heat Detector FDX-551R 2nd Floor Open Storage N2L3D10 No Access No Access Heat Detector FDX-551R 2nd Floor Open Storage N2L3D11 Test Pass Heat Detector FDX-551R 2nd Floor Open Storage N2L3D12 Test Pass Heat Detector FDX-551R 2nd Floor Rear Utility Closet N2L3D13 Test Pass
Photo Detector SDX-551 2nd Floor East Corr. N1L2D15 Test Pass Photo Detector SDX-551 2nd Floor East Corr. N1L2D16 Test Pass Photo Detector SDX-551 2nd Floor East Corr. N1L2D17 Test Pass Photo Detector SDX-551 2nd Floor East Corr. N1L2D18 Test Pass Photo Detector SDX-551 2nd Floor East Corr. N1L2D19 Test Pass Photo Detector SDX-551 2nd Floor Janitor Rm. 217 N1L2D20 Test Pass Photo Detector SDX-551 2nd Floor Elevator Lobby N1L2D21 Test Pass Photo Detector SDX-551 2nd Floor Center Corr. N1L2D22 Test Pass Photo Detector SDX-551 2nd Floor Center Corr. N1L2D23 Test Pass Photo Detector SDX-551 2nd Floor West Corr. N1L2D26 Test Pass Photo Detector SDX-551 2nd Floor West Corr. N1L2D27 Test Pass Photo Detector SDX-551 2nd Floor West Corr. N1L2D28 Test Pass Photo Detector SDX-551 2nd Floor West Corr. N1L2D29 Test Pass Photo Detector SDX-551 2nd Floor West Corr. N1L2D30 Test Pass Photo Detector FSP-751 2nd Floor E. Telephone Rm. N1L2D89 Test Pass Photo Detector FSP-751 2nd Floor E. Electrical Rm. N1L2D90 Test Pass Photo Detector SDX-551 2nd Floor Break Room N1L2D91 Test Pass Photo Detector FSP-751 2nd Floor East Electrical Room N1L2D92 Test Pass Photo Detector FSP-751 2nd Floor W. Telephone Rm. N1L2D94 Test Pass Photo Detector FSP-751 2nd Floor W. Electrical Rm. N1L2D95 Test Pass Photo Detector FSP-751 2nd Floor Electrical Room N2L3D06 Test Pass Photo Detector SDX-551 2nd Floor North Corr. 219 N2L3D46 Test Pass Photo Detector SDX-551 2nd Floor North Corr. 219 N2L3D47 Test Pass Photo Detector SDX-551 2nd Floor North Corr. 219 N2L3D48 Test Pass Photo Detector SDX-551 2nd Floor Center Corr. N2L3D49 Test Pass Photo Detector SDX-551 2nd Floor Center Corr. N2L3D50 Test Pass Photo Detector SDX-551 2nd Floor South Corr. 207 N2L3D51 Test Pass Photo Detector SDX-551 2nd Floor South Corr. 207 N2L3D52 Test Pass Photo Detector SDX-551 2nd Floor South Corr. 207 N2L3D53 Test Pass Photo Detector SDX-551 2nd Floor South Corr. 207 N2L3D54 Test Pass Photo Detector SDX-551 2nd Floor South Corr. 207 N2L3D55 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Manual Station BRG-1R 2nd Floor East Corr. N1L2M22 Test Pass Manual Station BRG-1R 2nd Floor Elevator Lobby N1L2M23 Test Pass Manual Station BRG-1R 2nd Floor West Corr. N1L1M24 Test Pass Manual Station BRG-1R 2nd Floor Stair 5 N2L3M11 Test Pass Manual Station BRG-1R 2nd Floor Stair 6 N2L3M12 Test Pass Manual Station BRG-1R 2nd Floor West Exit N2L3M17 Test Pass Manual Station NBG-12LX 2nd Floor West Exit N2L3M18 Test Pass Heat Detector FDX-551R 1st Floor Cafeteria N1L2D01 Test Pass Heat Detector FDX-551R 1st Floor Cafeteria N1L2D02 Test Pass Heat Detector FDX-551R 1st Floor West Break Room N1L2D11 Test Pass Heat Detector FDX-551R 1st Floor West Office N1L2D14 Test Pass Heat Detector FDX-551R 1st Floor West Storage N1L2D60 Test Pass Heat Detector FDX-551R 1st Floor E. Program Office N1L2D61 Test Pass Heat Detector FDX-551R 1st Floor Exec. Office N1L2D62 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D52 Test Pass Heat Detector FDX-551R 1st Floor Storage Closet N2L1D53 Test Pass Heat Detector FDX-551R 1st Floor Utility Room N2L1D54 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D55 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D56 No Access See Comments Heat Detector FDX-551R 1st Floor Open Storage N2L1D57 No Access See Comments
Photo Detector SDX-551 1st Floor Closed Storage N2L1D58 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D59 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D60 Test Pass Heat Detector FDX-551R 1st Floor East Office N1L2D61 Test Pass Heat Detector FDX-551R 1st Floor Meeting Room N1L2D62 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D63 Test Pass Heat Detector FDX-551R 1st Floor Open Storage N2L1D64 Test Pass Heat Detector FDX-551R 1st Floor Mechanical Room N2L1D73 Test Pass
Photo Detector FSP-751 1st Floor Mechanical Room N1L2D03 Untested No Access Photo Detector FSP-751 1st Floor East Corr. N1L2D05 Test Pass Photo Detector FSP-751 1st Floor Center Corr. N1L2D06 Test Pass Photo Detector FSP-751 1st Floor Elevator Lobby N1L2D07 Test Pass Photo Detector FSP-751 1st Floor Center Corr. N1L2D08 Test Pass Photo Detector FSP-751 1st Floor Main Lobby N1L2D10 Test Pass Photo Detector FSP-751 1st Floor West Corr. N1L2D12 Test Pass Photo Detector FSP-751 1st Floor East Corr. N1L2D74 Test Pass Photo Detector FSP-751 1st Floor East Corr. N1L2D75 Test Pass Photo Detector FSP-751 1st Floor East Conference Room N1L2D76 Test Pass Photo Detector FSP-751 1st Floor West Corr. N1L2D80 Test Pass Photo Detector FSP-751 1st Floor West Corr. N1L2D81 Test Pass Photo Detector FSP-751 1st Floor West Corr. N1L2D82 Test Pass Photo Detector FSP-751 1st Floor Badge Room N1L2D83 Test Pass Photo Detector FSP-751 1st Floor Men's Room Foyer N1L2D84 Test Pass Photo Detector FSP-751 1st Floor E. Electrical Rm. N1L2D85 Test Pass Photo Detector FSP-751 1st Floor West Closet N1L2D86 Test Pass Photo Detector FSP-751 1st Floor W. Electrical Rm. N1L2D87 Test Pass Photo Detector FSP-751 1st Floor W. Telephone Rm. N1L2D88 Test Pass Photo Detector SDX-551 1st Floor North Corr. 111 N2L1D33 Test Pass Photo Detector SDX-551 1st Floor North Corr. 111 N2L1D34 Test Pass Photo Detector SDX-551 1st Floor North Corr. 111 N2L1D35 Test Pass Photo Detector SDX-551 1st Floor Center Corr. N2L1D36 Test Pass Photo Detector SDX-551 1st Floor Center Corr. N2L1D37 Test Pass Photo Detector SDX-551 1st Floor Center Corr. N2L1D38 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 1st Floor Center Corr. N2L1D40 Test Pass Photo Detector SDX-551 1st Floor South Corr. N2L1D41 Test Pass Photo Detector SDX-551 1st Floor South Corr. N2L1D42 Test Pass Photo Detector SDX-551 1st Floor South Corr. N2L1D43 Test Pass Photo Detector SDX-551 1st Floor South Corr. N2L1D44 Test Pass Photo Detector SDX-551 1st Floor South Corr. N2L1D45 Test Pass Photo Detector SDX-551 1st Floor P-104 Office N2L1D49 Test Pass Photo Detector FSP-751 1st Floor Electrical Room N2L1D51 Test Pass Photo Detector SDX-551 1st Floor P-104 Lab Closet N2L1D72 Test Pass Heat Detector FDX-551R 1st Floor Kitchen N2L1D74 Test Pass Duct Detector FDX-551 1st Floor W. Mechanical Duct N1L2D13 Test Pass Duct Detector FSD-751P 1st Floor AHP-3 N2L1D39 Test Pass Duct Detector FSD-751P 1st Floor P-104 Duct N2L1D86 Test Pass
Manual Station BRG-1R 1st Floor Cafeteria N1L2M17 Test Pass Manual Station BRG-1R 1st Floor Center Corr. N1L2M18 Test Pass Manual Station BRG-1R 1st Floor Elevator Lobby N1L2M19 Test Pass Manual Station BRG-1R 1st Floor Center N1L2M20 Test Pass Manual Station BRG-1R 1st Floor West Corr. N1L2M21 Test Pass Manual Station BRG-1R 1st Floor East Exit N1L2M43 Test Pass Manual Station BRG-1R 1st Floor Break Room N1L2M44 Test Pass Manual Station BRG-1R 1st Floor Stair 5 N2L1M08 Test Pass Manual Station BRG-1R 1st Floor Stair 6 N2L1M09 Test Pass Manual Station BRG-1R 1st Floor Stair 8 N2L1M10 Test Pass Manual Station NBG-12LX 1st Floor West Exit N2L1M14 Test Pass Manual Station NBG-12LX 1st Floor West Exit N2L1M15 Test Pass Heat Detector FDX-551R Basement B59 - Compressor N1L1D59 No Access No Access Heat Detector FDX-551R Basement B45 - Storage N1L1D61 No Access No Access
Photo Detector SDX-551 Basement East Janitor N1L1D62 Test Pass Heat Detector FDX-551R Basement B61 - Compressor N1L1D79 Test Pass Heat Detector FDX-551R Basement Utility Closet N2L1D47 Test Pass Heat Detector FDX-551R Basement PB6 - Storage N2L1D48 Test Pass Heat Detector FDX-551R Basement FSIS N2L1D99 Test Pass
Photo Detector SDX-551 Basement East Office N1L1D01 Test Pass Photo Detector SDX-551 Basement East Office N1L1D02 No Access No Access Photo Detector SDX-551 Basement Room B51 N1L1D03 No Access See Comments Photo Detector SDX-551 Basement Room B53 N1L1D04 Test Pass Photo Detector SDX-551 Basement East Office N1L1D05 No Access No Access Photo Detector SDX-551 Basement Room B55 N1L1D06 Test Pass Photo Detector FSP-751 Basement W. Electrical Rm. N1L1D08 Test Pass Photo Detector FSP-751 Basement W. Telephone Rm. N1L1D09 Test Pass Photo Detector FSP-751 Basement E. Electrical Rm. N1L1D14 Test Pass Photo Detector FSP-751 Basement E. Telephone Rm. N1L1D15 Test Pass Photo Detector FSP-751 Basement East Electrical Room N1L1D16 Test Pass Photo Detector SDX-551 Basement East Corr. N1L1D58 Test Pass Photo Detector SDX-551 Basement East Corr. N1L1D60 Test Pass Photo Detector SDX-551 Basement East Corr. N1L1D63 Test Pass Photo Detector SDX-551 Basement East Corr. N1L1D64 Test Pass Photo Detector SDX-551 Basement Electric Switchgear Room N1L1D65 Test Pass Photo Detector FSP-751 Basement B56 - Tele. Equip. N1L1D66 No Access No Access Photo Detector SDX-551 Basement East Corr. N1L1D67 Test Pass Photo Detector SDX-551 Basement Elevator Lobby N1L1D68 Test Pass Photo Detector SDX-551 Basement Center Corr. N1L1D69 Test Pass Photo Detector SDX-551 Basement Center Corr. N1L1D70 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 Basement Center Corr. N1L1D71 Test Pass Photo Detector SDX-551 Basement Center Corr. N1L1D72 Test Pass Photo Detector SDX-551 Basement West Corr. N1L1D73 Test Pass Photo Detector SDX-551 Basement West Corr. N1L1D75 Test Pass Photo Detector SDX-551 Basement West Corr. N1L1D76 Test Pass Photo Detector SDX-551 Basement West Corr. N1L1D77 Test Pass Photo Detector SDX-551 Basement West Corr. N1L1D78 Test Pass Photo Detector SDX-551 Basement North Corr. N2L1D21 Test Pass Photo Detector SDX-551 Basement North Corr. N2L1D22 Test Pass Photo Detector SDX-551 Basement North Corr. N2L1D23 Test Pass Photo Detector SDX-551 Basement Center Corr. N2L1D24 Test Pass Photo Detector SDX-551 Basement Corr. PB1 N2L1D25 Test Pass Photo Detector SDX-551 Basement PTB Corr. N2L1D26 Test Pass Photo Detector SDX-551 Basement South Corr. N2L1D27 Test Pass Photo Detector SDX-551 Basement South Corr. N2L1D28 Test Pass Photo Detector SDX-551 Basement South Corr. N2L1D29 Test Pass Photo Detector SDX-551 Basement South Corr. N2L1D30 Test Pass Photo Detector SDX-551 Basement PB7 Corr. N2L1D31 Test Fail Photo Detector SDX-551 Basement South-West Corr. N2L1D32 Test Pass Photo Detector FSP-751 Basement Electrical Room N2L1D50 Test Pass Photo Detector FSP-751 Basement Elec. Rm. B011 N2L1D65 Test Pass Photo Detector SDX-551 Basement Hepa Filter Rm. B008 N2L1D66 Test Pass Photo Detector SDX-551 Basement FSIS East N2L1D67 Test Pass Photo Detector SDX-551 Basement FSIS East N2L1D68 Test Pass Photo Detector SDX-551 Basement FSIS East N2L1D69 Test Pass Photo Detector SDX-551 Basement FSIS Mech. Rm. N2L1D70 Test Pass Photo Detector FSP-751 Basement BP-B Corridor N2L1D79 Test Pass Photo Detector FSP-751 Basement BP-B Corridor N2L1D80 Test Pass Photo Detector FSP-751 Basement BP-B Corridor N2L1D81 Test Pass Heat Detector SDX-551 Basement Break Room N2L1D82 Test Pass
Photo Detector SDX-551 Basement Lower South Corr. N2L1D97 Test Pass Photo Detector SDX-551 Basement Lower South Corr. N2L1D98 Test Pass Duct Detector FSD-751P Basement Duct on Roof N2L1D71 Test Pass Duct Detector FSD-751P Basement FSIS Duct N2L1D75 Test Pass Duct Detector FSD-751P Basement Office A Duct N2L1D76 Test Pass Duct Detector FSD-751P Basement Duct Det. AHU N2L1D83 Test Pass Duct Detector FSD-751P Basement Duct Det. AHU N2L1D84 Test Pass
Manual Station BRG-1R Basement East Corr. N1L1M13 Test Pass Manual Station BRG-1R Basement East Corr. N1L1M14 Test Pass Manual Station BRG-1R Basement Center Corr. N1L1M15 Test Pass Manual Station BRG-1R Basement West Corr. N1L1M16 Test Pass Manual Station BRG-1R Basement Center Lobby N1L1M17 Test Pass Manual Station BRG-1R Basement Center Lobby N1L1M18 Test Pass Manual Station BRG-1R Basement Center Corr. N2L1M05 Test Pass Manual Station BG-12 Basement South Corr. N2L1M06 Test Pass Manual Station BRG-1R Basement Stair 8 N2L1M30 Test Pass Manual Station BRG-1R Basement East Exit N2L1M16 Test Pass Manual Station BG-12 Basement PB-4 Corridor N2L1M24 Test Pass Manual Station BRG-1R Basement West Exit N2L1M25 Test Pass Heat Detector FDX-551R Auditorium Auditorium Mech. Rm. N3L1D62 Test Pass
Photo Detector SDX-551 Auditorium Auditorium Entrance N3L1D59 Test Pass Photo Detector SDX-551 Auditorium Projection Booth N3L1D60 Test Pass Photo Detector SDX-551 Auditorium Auditorium N3L1D61 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 Auditorium Auditorium Corr. N3L1D63 Test Pass Photo Detector SDX-551 Auditorium Auditorium Corr. N3L1D64 Test Pass Photo Detector SDX-551 Auditorium Auditorium N3L1D65 Test Pass Photo Detector SDX-551 Auditorium Auditorium Foyer N3L1D66 Test Pass Heat Detector FDX-551R Auditorium Auditorium Mech. Rm. N3L1D67 Test Pass
Photo Detector SDX-551 Auditorium Auditorium Corr. N3L1D68 Test Pass Photo Detector SDX-551 Auditorium Auditorium Corr. N3L1D69 Test Pass Photo Detector SDX-551 Auditorium Auditorium N3L1D70 Test Pass Duct Detector FSD-751P Auditorium Supply N3L1D88 Test Pass Duct Detector FSD-751P Auditorium Return N3L1D99 Test Pass
Manual Station BRG-1R Auditorium Auditorium N3L1M64 Test Pass Manual Station BRG-1R Auditorium Auditorium Corr. N3L1M65 Test Pass Manual Station BRG-1R Auditorium Auditorium N3L1M66 Test Pass Manual Station NBG-12LX Auditorium Auditorium Corr. N3L1M67 Test Pass Heat Detector FDX-551R Sub-Base Pump Room N1L1D32 Test Pass Heat Detector FDX-551R Sub-Base SB27 - Compresso N1L1D36 Test Pass Heat Detector FDX-551R Sub-Base Electric Storage Closet N1L1D39 Test Pass Heat Detector FDX-551R Sub-Base SB26 - Storage N1L1D40 Test Pass Heat Detector FDX-551R Sub-Base SB5 Chemical N1L1D51 Test Pass Heat Detector FDX-551R Sub-Base SB5 Chemical N1L1D52 Test Pass Heat Detector FDX-551R Sub-Base SB7 Shipping N1L1D54 Test Pass Heat Detector FDX-551R Sub-Base SB7 Shipping N1L1D55 Test Pass Heat Detector FDX-551R Sub-Base SB7 Shipping N1L1D56 Test Pass Heat Detector FDX-551R Sub-Base SB7 Shipping N1L1D57 Test Pass Heat Detector FDX-551R Sub-Base Mechanical Room N2L1D13 Test Pass Heat Detector FDX-551R Sub-Base Mech. Room 15 N2L1D16 Test Pass Heat Detector FDX-551R Sub-Base Mech. Room 15 N2L1D18 Test Pass
Photo Detector FSP-751 Sub-Base East Electric Room N1L1D10 Test Pass Photo Detector FSP-751 Sub-Base East Telephone Room N1L1D11 Test Pass Photo Detector FSP-751 Sub-Base W. Telephone Rm. N1L1D12 Test Pass Photo Detector FSP-751 Sub-Base W. Electrical Rm. N1L1D13 Test Pass Photo Detector FSP-751 Sub-Base East Electrical Room N1L1D17 Test Pass Photo Detector SDX-551 Sub-Base East Corr. N1L1D33 Test Pass Photo Detector SDX-551 Sub-Base East Corr. N1L1D34 Test Pass Photo Detector SDX-551 Sub-Base East Corr. N1L1D35 Test Pass Photo Detector SDX-551 Sub-Base East Corr. N1L1D38 Test Pass Photo Detector SDX-551 Sub-Base East Corr. N1L1D42 Test Pass Photo Detector SDX-551 Sub-Base Center Corr. N1L1D43 Test Pass Photo Detector SDX-551 Sub-Base Elevator Lobby N1L1D44 Test Pass Photo Detector SDX-551 Sub-Base Center Corr. N1L1D45 Test Pass Photo Detector SDX-551 Sub-Base West Corr. N1L1D46 Test Pass Photo Detector SDX-551 Sub-Base West Corr. N1L1D47 Test Pass Photo Detector SDX-551 Sub-Base West Corr. N1L1D48 Test Pass Photo Detector SDX-551 Sub-Base West Corr. N1L1D50 Test Pass Photo Detector SDX-551 Sub-Base West Corr. N1L1D53 Test Pass Photo Detector SDX-551 Sub-Base Electrical Room N2L1D01 Test Pass Photo Detector SDX-551 Sub-Base Center Corr. N2L1D02 Test Pass Photo Detector SDX-551 Sub-Base Center Corr. N2L1D03 Test Pass Photo Detector SDX-551 Sub-Base Center Corr. N2L1D04 Test Pass Photo Detector SDX-551 Sub-Base South Corr. N2L1D05 Test Pass Photo Detector SDX-551 Sub-Base South Corr. N2L1D06 Test Pass Photo Detector SDX-551 Sub-Base South Corr. N2L1D07 Test Pass Photo Detector SDX-551 Sub-Base South Corr. N2L1D08 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Photo Detector SDX-551 Sub-Base South Corr. N2L1D09 Test Pass Heat Detector FDX-551R Sub-Base Autoclave Room N2L1D10 Test Pass
Photo Detector SDX-551 Sub-Base South Stair to Tunnel N2L1D11 Test Pass Photo Detector SDX-551 Sub-Base North Corr. N2L1D12 Test Pass Photo Detector SDX-551 Sub-Base North Corr. N2L1D15 Test Fail Photo Detector SDX-551 Sub-Base North Corr. N2L1D17 Test Pass Duct Detector SDX-551 Sub-Base Autoclave N2L1D46 Untested Disabled
Photo Detector SDX-551 Sub-Base Computer Room N2L1D88 Test Pass Duct Detector FDX-551 Sub-Base AHU-1 N1L1D41 Test Pass Duct Detector FDX-551 Sub-Base AHU-11 N1L1D49 Test Pass Heat Detector FDX-551R Basement Mechanical Room N1L1D88 No Access Fail Duct Detector FDX-551 Sub-Base Mechanical Rm.15 DUC N2L1D19 Test Pass Duct Detector FDX-551 Sub-Base Mechanical Rm.15 DUC N2L1D20 Test Pass Duct Detector FDX-551 Sub-Base FSIS Lab N2L1D77 Test Pass Duct Detector FDX-551 Sub-Base FSIS Lab N2L1D78 Test Pass
Manual Station BRG-1R Sub-Base East Corr. N1L1M09 Test Pass Manual Station BRG-1R Sub-Base Elevator Lobby N1L1M10 Test Pass Manual Station BRG-1R Sub-Base West Corr. N1L1M11 Test Pass Manual Station BRG-1R Sub-Base West Corr. N1L1M12 Test Pass Manual Station BRG-1R Sub-Base Center Corr. N2L1M01 Test Pass Manual Station BRG-1R Sub-Base West Exit N2L1M02 Test Pass Manual Station BRG-1R Sub-Base South Exit N2L1M03 Test Pass Manual Station BRG-1R Sub-Base Outside S EXI N2L1M04 Test Pass Manual Station BRG-1R Sub-Base West Exit N2L1M11 Test Pass Manual Station BRG-1R Sub-Base West Exit N2L1M12 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D40 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D41 Untested Disabled Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D42 Untested Disabled Photo Detector SDX-551 Tunnel Below Pilot Plant N3L1D43 Test Pass Photo Detector SDX-551 Tunnel Below Pilot Plant N3L1D44 Test Pass Photo Detector SDX-551 Tunnel Below Pilot Plant N3L1D45 Test Pass Photo Detector SDX-551 Tunnel Below Pilot Plant N3L1D46 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D48 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D49 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D50 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D51 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D52 Test Pass Photo Detector SDX-551 Tunnel ST - Tunnel N3L1D53 Test Pass Photo Detector SDX-551 Tunnel ST - Below Lobby N3L1D54 Test Pass Photo Detector SDX-551 Tunnel ST - Below Lobby N3L1D55 Test Pass Photo Detector SDX-551 Tunnel ST - Below Lobby N3L1D56 Test Pass Photo Detector SDX-551 Tunnel ST - Below Lobby N3L1D57 Test Pass Photo Detector SDX-551 Tunnel ST - Below Lobby N3L1D58 Test Pass Photo Detector SDX-551 Tunnel SVC Tunnel Rm. SB001 N3L1D79 Test Pass Photo Detector SDX-551 Tunnel SVC Tunnel Rm. SB001 N3L1D80 Test Pass Manual Station BRG-1R Tunnel ST - Tunnel N3L1M60 Test Pass Manual Station BRG-1R Tunnel Tunnel Stair 7 N3L1M61 Test Pass Manual Station BRG-1R Tunnel ST - Tunnel @ Stair 5 N3L1M62 Test Pass Manual Station BRG-1R Tunnel ST - Below Lobby N3L1M63 Test Pass Manual Station NBG-12LX Tunnel SVC Tunnel Rm. SB001 N3L1M72 Test Pass Duct Detector FDX-551 Basement PB-8 AHU N2L1D85 Test Pass Heat Detector FDX-551R Tunnel Mech. Rm N3L1D74 Test Pass
Photo Detector SDX-551 Tunnel Mech. Rm N3L1D73 Test Pass
NUMBER FLOOR LOCATION ZONE
ACTION
TAKEN RESULT
INSPECTION REPORT BY DEVICE
Russell Research USDA
Heat Detector FDX-551R Penthouse Penthouse Upper N1D4D16 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D17 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D18 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D19 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D36 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D20 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D21 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D22 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D23 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D24 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D35 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D25 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D26 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D27 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D28 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D29 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D30 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D31 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D32 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D33 Test Pass Heat Detector FDX-551R Penthouse Penthouse Upper N1L4D34 Test Pass
Photo Detector SDX-551 2nd Floor West Office N1L2D63 Test Pass Heat Detector FDX-551R Basement Compressor N1L1D74 Test Pass Duct Detector SDX-551 3rd Floor MT-3 Right Duct N1L2D46 Test Pass Duct Detector SDX-551 1st Floor MT-1 Duct Det. N1L2M31 Test Pass
Photo Detector FSP-751 SRB Ground Electric Panel N8L1D02 Test Pass Photo Detector FSP-751 SRB 2nd Floor Electric Room N8L1D03 Test Pass Photo Detector FSP-751 SRB 2nd Floor Breakroom/Kitchen N8L1D04 Test Pass Photo Detector FSP-751 SRB 2nd Floor Elevator Lobby N8L1D05 Test Pass Photo Detector FSP-751 SRB Ground Elevator Lobby N8L1D06 Test Pass Photo Detector FSP-751 SRB 2nd Floor Fire Panel / Comm. Room N8L1D07 Test Pass Photo Detector FSP-751 SRB 2nd Floor Top Of Elevator Shaft N8L1D08 Test Pass Photo Detector FSP-751 SRB Ground Elevator Mach.Room N8L1D09 Test Pass Manual Station NBG-12LX SRB Ground Exit At Roll Up Door N8L1M01 Test Pass Manual Station NBG-12LX SRB Ground Exit At Side Door N8L1M02 Test Pass Manual Station NBG-12LX SRB 2nd Floor Exit At Front Stairs N8L1M03 Test Pass Manual Station NBG-12LX SRB 2nd Floor Exit At Side Door N8L1M04 Test Pass
FLOOR LOCATION
AMB
DB
ALARM
DB DEFECT DEVICE MOUNT COLOR SHAPE SOLUTION
8th Floor Corridor 48.5 90.5 7th Floor Corridor 48.5 90.5 6th Floor Corridor 48.5 90.5 5th Floor Corridor 48.5 90.5 4th Floor Corridor 48.5 90.5 3rd Floor Corridor 48.5 90.5 2nd Floor Corridor 48.5 90.5 1st Floor Corridor 51.8 91.8
Basement Corridor 46.8 93 Sub-Base Corridor 43.9 94.6
Tunnel Tunnel 47.5 91.4 Serv. Bldg. Boiler Room 88.7 90.8 Low Sound
Chicken Lab Main Floor 45.6 96.9 Receiving First Floor 48.3 93.7 Receiving Second Floor 49.7 94
SOUND TEST REPORT
FLOOR LOCATION PASS DEFECT DEVICE SOLUTION
3rd Floor Elevator lobby Pass 2nd Floor Elevator lobby Pass 1st Floor Elevator lobby Pass
DOOR HOLDER TEST REPORT
DEVICE MODEL NUMBER FLOOR LOCATION ZONE RESULT REASON LABEL CHANGE OR NOTES
Photo Detector SDX-551 Basement PB7 Corr. N2L1D31 Fail No Alarm Goes into trouble only Photo Detector SDX-551 Sub-Base North Corr. N2L1D15 Fail Heat Detector FDX-551R Basement Mechanical Room N1L1D88 Fail Electric
INITIATING DEVICE DEFICIENCY REPORT
BATTERY
SPEC'S IN
VOLTS /Ah VOLTAGE
AMP HOUR
READING LOCATION/FLOOR/CABINET RESULT
12V/26A 13.96 17 Fire Command/Service Building/left Pass 12V/26A 13.96 17.00 Fire Command/Service Building/right Pass
12V/7.0Ah 13.86 3.95 FCPS#1/Service Building/left Pass 12V/7.0Ah 13.93 6.52 FCPS#1/Service Building/right Pass 12V/7.0Ah 13.77 4 FCPS#2/Sub Basement Elec.Rm/left Pass 12V/7.0Ah 14.2 3.56 FCPS#2/Sub Basement Elec.Rm/right Pass
12V/8.00Ah low current FCPS#3/1st Fl.Elec.Rm/left Fail 12V/8.00Ah low current FCPS#3/1st Fl.Elec.Rm/right Fail 12V/7.0Ah 13.89 3.91 FCPS#4/1st Fl.Elec.Rm by middle stairs/left Pass 12V/7.0Ah 14.26 3.86 FCPS#4/1st Fl.Elec.Rm by middle stairs/right Pass 12V/7.0Ah 13.84 6.07 FCPS#5/3rd Fl.Elec.Rm/left Pass 12V/7.0Ah 14.3 6.52 FCPS#5/3rd Fl.Elec.Rm/right Pass 12V/7.0Ah 13.9 5.38 FCPS#6/3rd Fl Elec Rm/left Pass 12V/7.0Ah 14.32 6.07 FCPS#6/3rd Fl Elec Rm/right Pass
12V/8.00Ah 13.66 4 FCPS#7/5th Fl Elec Rm/left Pass 12V/8.00Ah 14.5 4.43 FCPS#7/5th Fl Elec Rm/right Pass 12V/7.0Ah 13.93 7.65 FCPS#8/7th Fl Elec Closet/left Pass 12V/7.0Ah 14.29 6.28 FCPS#8/7th Fl Elec Closet/right Pass 12V/26A low current Node 1 FACP/Sub Base left Fail 12V/26A low current Node 1 FACP/Sub Base right Fail
12V/26Ah 13.78 18.75 Node 2 PSB-2 /left Pass 12V/26Ah 13.74 18.75 Node 2 PSB-2/right Pass
12V/8.00Ah low current MPS24 in Node 1-left Fail 12V/8.00Ah low current MPS24 in Node 1-right Fail 12V/18Ah 13.8 8.65 FACP in SRB building-left Pass 12V/18Ah 13.95 2.8 FACP in SRB building-right Fail 12V/7.0Ah 13.75 3.73 Dailer in boiler room Pass 12V/7.0Ah low current FCPS in Monkey room-left Fail 12V/7.0Ah low current FCPS in Monkey room-right Fail 12V/7.0Ah 13.95 1.23 FCPS in Chicken bldg-left Fail 12V/7.0Ah 14.01 bad FCPS in Chicken bldg-right Fail
12V/8.00Ah 13.63 3.42 FCPS 10th floor-left Pass 12V/8.00Ah 13.89 3.91 FCPS 10th floor-right Pass
BATTERY TEST RESULTS
the work station speakers are turned off, there is only visual alarms avalible in the boiler room.
>Pilot house rm PB-23 has (2) duct detectors bypassed and hanging by wires. N2L1D75 & D76.
>Chicken house FCPS module N3L1M35 is not programmed correctly bypass with WS.
> 1st floor Tower can not find S/D N1L2D03 or H/D N1L2D60.
>7th floor of tower has (4) heat detectors that are hanging from wires.
COMMENTS ON INSPECTION
Russell Research USDA
>Pilot house 1st floor store room P104 has been built out and heat detectors have not been moved from deck to ceiling. Devices N2L1 D61, D62, D64, D63, & D73 heats. Need to change to smoke detectors.
>NCA next to FACP node 3 has broken sounder. This NCA is programmed for global annunciation and
>FCPS #3 in tower 1st floor electical room has a 'bad charger'. Also not reporting to FACP.
>FCPS #5 in Pilot building 1st floor electical room has wire disconnected that may be reason for no strobes in the area.
>Smoke detector in lower penthouse of tower N1L4D14 damaged need to replace.
>Auditorium smoke detector N3L1D68 bypassed because device is missing.
>In pilot house on basement level at the center stairwell area. Strobes not working.
>In service building at door that leads from boiler room to garage area has bad speaker/strobe >SRB building FACP has bad display.
>FCPS #1 in service building has batteries with corroded terminals.
Circuits, Sub Basement through 8th Floors.
>Note that all 4 fireman's phone circuits to elevators are in trouble. (The elevators were just upgraded) >Tower Room's B-45, B-54, B-51 & B-46 no access. N1L1D61, N1L1D05, N1L1D03 & N1L1D59.
>Note that we did not have access to all areas because some departments have locked certain areas.
COMMENTS ON INSPECTION
Russell Research USDA
>Voice evac micrphones did not overide alert announcement or message.
>During audio/visual testing, the system was showing multiple invalids on all speaker circuits.
>During the A/V, test found the Onyxworks Station Showing Troubles on the Tower Speaker
>6th floor Elec rm 648 no access. N1L3D50 Troubles on FACP after inspection.
>N1L4D52 MT-7-CENTER
>N1L3D36 MT-6 MECH RM
>N1L3D47 MT5FL GEAR RM SHADOW ZONE
>Penthouse Tower shunt trip relay not programmed in disable group.
>6th floor tower S/D's N1L3D02 & N1L3D05 hanging.
>2nd floor tower S/D N1L2D63 hanging.
>1st floor tower S/D's N1L2D84 & N1L2D87 hanging.
>7th floor Elec rm 750 no access. N1L4D01
>N3L1M35 FCPS control chicken lab GHOST ZONE
>N1L2D84 MT-1FL MENS RM FOYER
>N1L2M1 1FL FCPS TRIP
10:00am 2/4/2022
YES
Name of property:
Address:
Description of property:
Name of property representative:
Address:
Fax: E-mail:
Testing organization:
Fax: E-mail:
Monitoring organization:
Kennesaw GA
Fax: E-mail:
Account number: Phone line 1: Phone line 2:
Means of transmission:
Enitiy to which alarms are retransmitted: Phone:
Onsite location of the required record documents and site-specific software:
4.1
Manufacturer:
4.2
4.3
4.3.1
Amps: 20 Location:
Amps: 20
Supplemental Form(s) Attached:
PROPERTY INFORMATION
(yes/no)
706-546-3130 erbaker@fseinc.net
770-970-3002 afap.com 975 Cobb Place Blvd, Suite 308, Kennesaw, GA, 30144
770-794-9000
TESTING AND MONITORING INFORMATION
Eric Baker
USDA
Industrial
AFA Protective Systems
888-232-1873
26-1620
770-970-3001 rlopez@afap.com
950 College Station Rd., Athens, GA 30605
706-425-9331
AFA Protective Systems, Inc.
72-48 NATIONAL FIRE ALARM AND SIGNALING CODE
Attach additional sheets, data, or calculations as necessary to provide a complete record
2/1/2022 Inspection/Test Completion Date/Time:Inspection/Test Start Date/Time:
SYSTEM RECORD OF INSPECTION AND TESTING
This form is to be completed by the system inspection and testing contractor at the time of a system test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
9:00pm
Digital
120vac Main electrical room in boiler room
Notifier Node 1 NFS-3030Model number:
950 College Station Rd. Athens, Ga 30605
DESCRIPTION OF SYSTEM OR SERVICE
Control Unit
DOCUMENTATION
Nominal voltage:
Disconnecting means location:CBRKOvercurrent protection type:
©2012 National Fire Protection Association NFPA 72 (P. 1 of 4)
Address:
Phone:
Phone:
Address:
Phone:
975 Cobb Place Blvd, Suite 308, Kennesaw, GA, 30144 30144
Firmware revision number:
System Power
Primary (Main) Power
Software Firmware
Type: Location:
Time:
Time:
Time:
Time:
Time:
Functional Test
Functional Test
DESCRIPTION OF SYSTEM OR SERVICE (continued)
4.3.2 Secondary Power
Sealed Lead Acid Main electrical room in boiler room
DOCUMENTATION 72-49
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: AFA 10:00am
Battery type (if applicable):
Calculated capacity of batteries to drive the system:
10 In alarm mode (minutes): 24In standby mode (hours):
Authority having jurisdiction Contact:
Other, if required Contact:
Building management Contact: Eric Baker 10:00am Building occupants Contact: Secruity Dept 10:00am
Control unit Lamps/LEDs/LCDs
TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection Comments
Disconnect switches Ground-fault monitoring
Fuses Trouble signals
Remote annuciators Onyxworks at Boiler Room Remote power panels
Supervision Local annuciator
Comments Battery condition
6.2 Secondary Power
Description Visual Inspection
72-48 NATIONAL FIRE ALARM AND SIGNALING CODE
©2012 National Fire Protection Association NFPA 72 (P. 2 of 4)
FIGURE 7.8.2(g) Continued 2013 Edition
Charger test Remote panel batteries
Load voltage Discharge test
No Time
2:00pm
No Time
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
6.5 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
Circuit Interface / Signaling Line Circuit Interface / Fire Alarm Control Interface
6.6 Supervising Station Monitor
TESTING RESULTS (continued)
6.3 Alarm and Supervisory Alarm Initiating Device
Attach supplementary appliance test sheets for all initiating devices
6.4 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances
Alarm restoration Trouble signal
Description Yes Comments Alarm signal
Supervisory restoration
6.7 Public Emergency Alarm Reporting System
Trouble restoration Supervisor signal
Alarm restoration Trouble signal
Description Yes Comments Alarm signal
Supervisory restoration
©2012 National Fire Protection Association NFPA 72 (P. 3 of 4)
Trouble restoration Supervisor signal
FIGURE 7.8.2(g) Continued 2013 Edition