Product Data Sheet: YORK Model YLAA Air-Cooled Scroll Chillers

This document is a comprehensive product specification and technical data sheet for Johnson Controls' YORK Model YLAA air-cooled scroll chillers with brazed plate heat exchangers. The chillers are factory-assembled, outdoor-capable units available in capacities ranging from 55 to 230 tons (195 to 700 kW) and utilize R-410A refrigerant with zero ozone depletion potential. All units comply with AHRI Standards 550/590 and 551/591, ASME Boiler and Pressure Vessel Code Section VIII Division 1, ASHRAE 15 Safety Code, and UL 1995 standards.

The product line features hermetic scroll compressors with suction-gas cooling, compliant scroll design, and automatic pumpdown at shutdown. Evaporators utilize 316L stainless steel brazed plate construction with thermostatically controlled heating for freeze protection to -20°F ambient. Air-cooled condensers employ single-material aluminum or copper coils with low-sound fans, featuring vertical air discharge and individual fan compartments to prevent crossflow. Standard controls include a microprocessor-based system with native BACnet MS/TP, Modbus, and N2 communication capabilities, remote water temperature reset via analog input, and dual-stage demand load limiting. Available options include low/high ambient control kits, power factor correction capacitors, heat recovery condensers, variable-speed drives, factory-installed hydro-kits with single or dual pump configurations, sound attenuation packages, enclosure panels, and environmental protection coatings for corrosive settings. The document provides detailed electrical data, wiring diagrams, dimensional specifications, pressure drop curves, isolator locations and ratings, part load performance ratings, and application guidance for installation on roofs or ground level with specified foundation and clearance requirements.

View the file

Other files for this federal contract opportunity

Other files attached to Chiller Coil Replacement, newest first.
File Type Posted
Attachment 1- SF 1449- 1232SA26Q1195.pdf PDF
PXL_20260820_170453606.PORTRAIT.jpg JPG image
Questions and Answers 2.docx DOCX document
RFQ Q1195 Posted to SAM- ContractData-20260810-105753.pdf PDF
Questions and Answers 1.docx DOCX document
Newark Chiller Coil P1.jpg JPG image
Newark Chiller Coil P2.jpg JPG image
Attachment 2- Statement of Work.docx DOCX document
Attachment 1- SF 1449- 1232SA26Q1195.pdf PDF
Attachment 4- Wage Determination.pdf PDF
Attachment 3- Past Performance.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FORM 150.72-EG6 (1217)

MODEL YLAA

AIR-COOLED SCROLL CHILLERS

WITH BRAZED PLATE HEAT EXCHANGERS

STYLE B

55 – 230 TON

195 – 700 kW

60 Hz R-410A

JOHNSON CONTROLS

Approvals

• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1.

• AHRI Standard 550/590 and 551/591.

• UL 1995 – Heating and Cooling Equipment

• ASHRAE 15 – Safety Code for Mechanical Refrigeration

• ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems

• N.E.C. – National Electrical Code

• OSHA – Occupational Safety and Health Act

Nomenclature

YL A A 0125 H 46 X C B

YL = YORK CHILLER

A = AIR COOLED

S = STANDARD EFFICIENCY

H = HIGH EFFICIENCY

REFRIGERANT = R-410A

DESIGN SERIES

A = DESIGN SERIES

FOUR DIGIT UNIT

NUMBER

VOLTAGE CODE:

17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60

DEVELOPMENT

LEVEL = B (BPHX)

JOHNSON CONTROLS 3

Table Of Contents

INTRODUCTION

EQUIPMENT OVERVIEW

UNIT COMPONENTS

ACCESSORIES AND OPTIONS

DESIGN PARAMETERS

WATER PRESSURE DROP

PHYSICAL DATA AND NOMINAL RATINGS

PART LOAD RATINGS

UNIT DIMENSIONS

ISOLATOR LOCATIONS

ISOLATOR DETAILS

ELECTRICAL NOTES

VARIABLE SPEED PUMP ELECTRICAL DATA

WIRING LUGS

ELECTRICAL DATA WITHOUT PUMPS

WIRING DIAGRAM

USER CONTROL WIRING

APPLICATION DATA

GUIDE SPECIFICATIONS

SI METRIC CONVERSION

Performance data provided in this document was created in accordance with Johnson Controls software:

YORKworks version 17.06 and DXCHILL version 8_02

THIS PAGE INTENTIONALLY LEFT BLANK.

JOHNSON CONTROLS 5

Johnson Controls, the building efficiency leader, is proud to present the YORK Model YLAA Air-Cooled Scroll Chiller.

FEATURES AND BENEFITS

Installation

The YLAA chiller arrives as a factory-assembled package ready to be installed outdoors, either on the roof or at ground level. The air-cooled condensers eliminate the capital, in-stallation and maintenance costs of a cooling-tower circuit.

The YLAA weighs less and has s smaller footprint than other chillers in its class. In fact, it is 20-35% lighter weight than the market average chiller. When the chiller is roof-mounted in new construction, the cost of the support structure can be reduced. In building retrofits, the YLAA can provide the largest capacity in a given space and existing structure.

Power hook-up could not be any easier with the standard single-point connection. A ter-minal block, disconnect switch or circuit breaker is provided to meet the unique needs of every project and minimize installation time and labor. The factory-installed control trans-former steps down the power voltage to the control voltage.

Chilled-water piping is also simple. The water connections are factory-piped to the out-side of the unit, for ease of access. Factory-cut grooves, or optional flanges, make pip-ing connections simple. Optional factory-installed pump kits eliminate the time, cost, and mechanical-equipment room space necessary to install chilled-water pumps.

Press the start button with confidence – your YLAA has been run-tested at the factory to ensure that you will have a successful start-up.

Reliability

The YLAA chiller is proven and reliable, designed to reduce service calls. The scroll com-pressors have logged hundreds of thousands of operating hours in numerous different applications. The corrosive-resistant condenser heat exchangers have been specifically designed for stationary HVAC applications and have undergone extensive laboratory and field testing to extend chiller life and improve performance. They are also more rigid than standard condenser coils, making them less susceptible to damage during rigging, lifting, and installation of the chiller.

Components are designed to keep the chiller up-and-running. A factory-installed water strainer prevents debris from affecting unit flow and/or heat transfer. The rugged thermal-dispersion flow switch is factory-installed at the optimum location in the piping for su-perior flow sensing, reducing the potential for nuisance trips. Intelligent controls protect the chiller while keeping it online, for maximum uptime. Exterior panels of the chiller are powder-coated with highly durable corrosion-resistant paint.

Introduction

Efficiency

YLAA high-efficiency chillers, with their innovative control algorithms, offer industry-lead-ing energy efficiency. Real-world energy efficiency is measured by IPLV (off-design) per-formance, and YLAA chillers provide some of the best IPLVs in their class.

YLAA also offers an efficiency choice. In addition to the high-efficiency units, YLAA chillers are available in standard efficiency models with smaller footprints and lower capital costs.

Only pay for the chiller you need – the multi-efficiency levels of the YLAA allow you to decide the best investment for the job.

Flexibility

The YLAA chiller offers a number of options designed to operate reliably across a wide range of customer needs. It can cool glycol down to 10°F (-12°C). It can provide heat re-covery up to 140°F (60°C), with up to 85% of total heat rejection captured.

When factory-mounted pump kits are considered, there are now more pump sizes to choose from. The optional kits come standard with valves, pressure ports, flow switch, and strainer for quick hook-up, and frost protection to prevent freeze-up. There are also more pump options available: variable-speed drives, dual pumps, service shut-off valves, expansion tanks, and additional test ports for temperature and pressure sensing.

Standard low sound and multiple sound attenuation options allow flexibility in locating the chiller, and reduce the cost for field-constructed barriers.

Sustainability

The YLAA makes you a leader in sustainability through innovation, not added cost. With the combination of R-410A refrigerant, which has no ozone-depletion potential, and state-of-the-art heat exchanger technology that allows refrigerant charge to be reduced by as much as 30%, the YLAA chiller provides the most ecologically friendly equipment. Part-nered with its low-sound properties for noise pollution prevention, this chiller is a true earth-friendly offering.

Introduction (Cont'd)

JOHNSON CONTROLS 7

Communications

The YLAA chiller comes standard with native communication capability for BACnet (MS/ TP), Modbus, and N2, with optional capabilities available for LON. The standard unit ca-pabilities include built-in-scheduling, remote start-stop, remote water temperature reset and up to two steps of demand (load) limiting depending on model. The standard control panel can be directly connected to a Johnson Controls Building Automated System via the standard factory-installed RS232 communication port.

Serviceability

Minimal maintenance is required to keep the unit operating at maximum performance. If service should ever be required, the YLAA chiller has been designed to simplify the work, keeping costs down. The layout of the chiller locates all the major components that can be serviced near the outside edge. The condenser heat exchangers are light enough that no crane is required for replacement and when it’s time to clean them, city tap water, with water pressure typical of a spray from a common garden hose, is all that’s needed.

AHRI CERTIFICATION PROGRAM

YORK YLAA chillers have been tested and certified by Air-Conditioning, Heating and Re-frigeration Institute (AHRI) in accordance with the latest edition of AHRI Standard 550/590 (I-P). Under this Certification Program, chillers are regularly tested in strict compliance with this Standard. This provides an independent, third-party verification of chiller perfor-mance. Refer to the AHRI site at www.ahrinet.org/ for complete Program Scope, Inclu-sions, and Exclusions as some options listed herein fall outside the scope of the AHRI certification program. For verification of certification, go to the AHRI Directory at www.

ahridirectory.org.

Rated in accordance with the latest issuance of AHRI Standard 550/590 and 551/591.

Introduction (Cont'd) http://www.ahrinet.org http://www.ahridirectory.org http://www.ahridirectory.org

Equipment Overview

The 55 - 230 Ton (195 - 800 kW) YLAA models are shipped complete from the factory ready for installation and use. The unit is pressure-tested, evacuated, and fully charged with a zero Ozone Depletion Potential Refrigerant R-410A and includes an initial oil charge. After assembly, a complete operational test is performed with water flowing through the evapo-rator to assure that the refrigeration circuit operates correctly.

The unit structure is heavy-gauge, galvanized steel. This galvanized steel is coated with baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray test-ing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety code for mechanical refrig-eration, ASME and rated in accordance with AHRI Standard 550/590 and 551/591.

COMPRESSORS

The chiller has suction-gas cooled, hermetic scroll compressors. The YLAA compressors in-corporate a compliant scroll design in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir provides greater liquid tolerance. Compressor-crankcase heaters are also included for extra protection against liquid migration.

LD18425a

JOHNSON CONTROLS 9

BRAZED PLATE EVAPORATOR

The compact, high efficiency Brazed Plate Heat Exchanger (BPHE) is constructed with 316L stainless steel corrugated channel plates with a filler material between each plate. It offers excellent heat transfer performance with a compact size and low weight, reducing structural steel requirements on the job site.

LD18426

The heat exchanger is manufactured in a precisely controlled vacuum-brazing process that allows the filler material to form a brazed joint at every contact point between the plates, creating complex channels. The arrangement is similar to older plate and frame technology, but without gaskets and frame parts.

Water inlet and outlet connections are grooved for compatibility with field supplied ANSI/ AWWA C-606 couplings.

A 20 mesh wye-strainer is provided as standard to provide protection at the evaporator inlet, particularly at system start-up when construction debris may be present in the piping system.

The evaporator is equipped with a thermostat-controlled heater. The heater provides freeze protection for the evaporator down to -20°F (-29°C) ambient. The evaporator is covered with 3/4” flexible, closed-cell, foam insulation (K=0.25).

A factory-wired flow switch is standard, installed in a pipe section at the outlet of the evaporator.

Equipment Overview (Cont'd)

Equipment Overview (Cont'd)

CANADIAN REGISTRATION NUMBER (CRN) APPLICATION & PROOF OF

CONFORMANCE

Reference Table 1 for YLAA brazed plate evaporator Canadian Registration Numbers (CRN) for all Canadian Provinces. All YLAA brazed plate evaporators are categorized as pressure “H” fittings per CSA-B51.

Table 1 - CANADIAN REGISTRATION NUMBERS

CANADIAN PROVINCE CRN#

BC OH13953.51

AB OH13953.52

ON OH13953.5

PQ/MB/SK OH13953.56

NB OH13953.57

NS OH13953.58

PEI OH13953.59

NF OH13953.50

NU OH13953.5N

NWT OH13953.5T

YU OH13953.5Y

CONDENSER

Coils - Condenser coils are made of a single material to avoid galvanic corrosion due to dissimilar metals. Coils and headers are brazed as one piece. Integral sub cooling is included. The design working pressure of the coil is 650 PSIG (45 BarG). Condenser coil is easily washable with clear water up to 100 PSI (7 bar).

Fans – The condenser fans are composed of corrosion resistant aluminum hub and glass-fiber-reinforced polypropylene composite blades molded into a low-noise airfoil section.

They are designed for maximum efficiency and are statically and dynamically balanced for vibration-free operation. They are directly driven by independent motors, and positioned for vertical air discharge. The fan guards are constructed of heavy-gauge, rust-resistant, coated steel. All blades are statically and dynamically balanced for vibration-free opera-tion.

LD18427

JOHNSON CONTROLS 11

Equipment Overview (Cont'd)

Motors – The fans are driven by Totally Enclosed Air-Over, squirrel-cage type, current pro-tected motors. They feature ball bearings that are double-sealed and permanently lubricated.

UNIT CONTROL SYSTEM

The YLAA chiller is designed with an intelligent control system that operates the chiller automatically with maximum reliability, safety and ease of use. The controls are factory tested and with as little user input as a chilled liquid setpoint the chiller will operate to meet the load demand.

The control system includes native BACnet MS/TP, Modbus and N2 communications, with LON protocol served through an optional eLink communications card.

The operating program is stored in non-volatile memory (EPROM), so power failures and battery discharge will not require reprogramming the chiller. Programmed setpoints are retained in lithium battery-backed RTC memory for five years minimum.

Unit alarm contacts are standard. Contacts for remote chilled liquid temperature reset and two steps of demand load limiting are also standard, for projects without BAS or for redundancy.

FUSES

ON/OFF

SWITCH

TERMINAL

BLOCK

CONTROL

TRANSFORMER

MICROBOARD

KEYPAD

LD18429

LD18428

DISPLAY

Maximum reliability is achieved through intelligent control. Run hours and starts are av-eraged across all compressors automatically, and between both pumps of the optional dual pump hydro-kit. When compressors are cycled off, an anti-recycle timer ensures the motors have time to cool before starting again, for the maximum service life. At unit shutdown, the unit pumps down automatically to prevent liquid refrigerant from entering the compressors at restart, which can cause premature bearing wear and other compres-sor damage.

Liquid temperature sensors provide feedback to the controller, and logic predicts when additional capacity will be required based on how quickly the unit has loaded or unloaded in the past. This prevents unnecessary compressor cycling and helps maintain setpoint accurately.

If there is a problem that prevents the unit operating properly, the controls are designed to allow the unit to operate safely while making as much capacity as possible. For example, if airflow to the condenser coil is diminished due to a dirty coil, the chiller will unload slightly to provide maximum capacity possible while remaining within the unit operating envelope.

If a fault prevents the unit from starting or causes it to shutdown, the chiller will attempt to restart three times. If it cannot start, a manual reset is required to alert the operator about the fault condition. The fault history is stored in the unit controller RTC memory for the last six fault shutdown conditions. An RS-232 port provides capability to print hard copy reports (printer available separately).

All controls are contained in a NEMA 3R cabinet with a hinged outer door and includes a liquid crystal display (LCD) with light emitting diode (LED) backlighting for outdoor view-ing. There are two display lines, each with 20 text characters per line, and a color coded 12-button non-tactile keypad with sections for display, entry and printing.

DISPLAY/PRINT provides quick access to frequently needed information:

• Chilled liquid temperatures

• Ambient temperature

• System pressures (each circuit)

• Operating hours and starts (each compressor)

• Operating data for the systems

ENTRY section allows entering setpoints or modifying system values.

SETPOINTS updating can be performed to:

• Chilled liquid temperature setpoint and range

• Remote reset temperature range

• Set daily schedule/holiday for start/stop

• Manual override for servicing

• Low and high ambient cut-outs

• Number of compressors

• Low liquid temperature cut-out

• Low suction pressure cut-out

Equipment Overview (Cont'd)

JOHNSON CONTROLS 13

Equipment Overview (Cont'd)

• High discharge pressure cut-out

• Anti-recycle timer (compressor start cycle time)

• Anti-coincident timer (delay compressor starts)

UNIT section to:

• Set time

• Set unit options

In addition, the microprocessor control center is capable of displaying the following data points:

• Return and leaving liquid temperature

• Low leaving liquid temperature cut-out setting

• Low ambient temperature cut-out setting

• Outdoor air temperature

• English or Metric data

• Suction pressure cut-out setting

• Each system suction pressure

• Discharge pressure (optional)

• Anti-recycle timer status for each system

• Anti-coincident system start timer condition

• Compressor run status

• No cooling load condition

• Day, date and time

• Daily start/stop times

• Holiday status

• Automatic or manual system lead/lag control

• Lead system definition

• Compressor starts & operating hours (each compressor)

• Status of hot gas valves, evaporator heater and fan operation

• Run permissive status

• Number of compressors running

• Liquid solenoid valve status

• Load & unload timer status

• Water pump status

COMMUNICATIONS

• Native communication capability for BACnet (MS/TP), Modbus and N2

• Optional communication available for LON via eLink option

BUILDING AUTOMATION SYSTEM INTERFACE

In addition to native BACnet, Modbus and N2, the YLAA chiller accepts a 4-20 milliamp or 0-10VDC input to reset of the leaving chilled liquid temperature. The standard unit ca-pabilities include remote start-stop, remote water temperature reset via up to two steps of demand (load) limiting depending on model. The standard control panel can be directly connected to a Johnson Controls Building Automated System via the standard on-board RS232 communication port. (Factory- installed)

For connection with Johnson Controls Connected Services, an optional interface card (SC-EQUIP) is required and may be factory installed for easier field commissioning. Addi-tional hardware (SC-AP access point), field provided, must be installed remotely from the chiller to interface with the Connected Services remote operations center. Contact your local Johnson Controls office to learn more about Connected Service and to schedule installation during chiller commissioning.

POWER PANEL

Each panel contains:

• Compressor power terminals

• Compressor motor starting contactors per l.E.C.

• Control power terminals to accept incoming for 115-1-60 control power

• Fan contactors & overload current protection

The power wiring is routed through liquid-tight conduit to the compressors and fans.

Equipment Overview (Cont'd)

FAN

FUSE

FAN

CONTACTORS

DISCONNECT

SWITCH

FAN

FUSE

FAN

CONTACTORS

FAN

CONTACTORS

COMPRESSOR

CONTACTORS

GROUND

LUG

COMPRESSOR

CONTACTORS

FAN

CONTACTORS

XTBF1

LD18430A

JOHNSON CONTROLS 15

Unit Components

Figure 1 - GENERAL UNIT COMPONENTS

FAN DECK

MICROCHANNNEL

COILS

COIL

HEADERS

CONTROL

AND

POWER

PANELS

COMPRESSORS

BRAZED PLATE

EVAPORATOR

FORMED STEEL

BASE RAILS

HYDRO-KIT

PUMPS AND

MOTORS

(OPTIONAL)

LD18426

Accessories and Options

All options are factory installed unless otherwise noted.

POWER OPTIONS:

Unit Power Connections – Single-point terminal block connection(s) are provided as stan-dard. The following power connections are available as options. (See electrical data for specific voltage and options availability.)

Single-Point Supply Terminal Block – Includes enclosure, terminal-block and intercon-necting wiring to the compressors. Separate external protection must be supplied, by oth-ers, in the incoming compressor-power wiring. (Do not include this option if either the Sin-gle-Point Non-Fused Disconnect Switch or Single-Point Circuit Breaker options have been included.)

Single-Point Non-Fused Disconnect Switch – Unit-mounted disconnect switch(es) with external, lockable handle (in compliance with Article 440-14 of N.E.C.)can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied, by others in the power wiring, which must comply with the National Electrical Code and/or local codes.

Single-Point Circuit Breaker – A unit mounted circuit breaker with external, lockable han-dle (in compliance with NEC Article 440-14), can be supplied to isolate the power voltage for servicing. (This option includes the Single-Point Power connection.)

Multiple Point Supply With Individual System Circuit Breakers – Two unit-mounted cir-cuit breakers, with external lockable handles (in compliance with NEC Article 440-14), can be supplied to isolate the power voltage for servicing. (SQ only)

Control Transformer – Converts unit power voltage to 115-1-60 (0.5 or 1.0 kVA capacity).

Factory mounting includes primary and secondary wiring between the transformer and the control panel.

Power Factor Correction Capacitors – Will correct unit compressor power factors to a 0.90-0.95.

CONTROL OPTIONS:

High Ambient Kit – Allows units to operate when the ambient temperature is above 115°F (46°C). Includes sun shield panels and discharge pressure transducers.

Low Ambient Kit – Standard units will operate to 30°F (-1°C). This accessory includes all necessary components to permit chiller operation to 0°F (-18°C). (This option includes the discharge pressure transducer /readout capability option.) For proper head pressure control in applications below 30°F (-1°C) where wind gusts may exceed 5 mph, it is recommended that optional condenser louvered enclosure panels also be included.

Language LCD and Keypad Display – Spanish, French, German, and Italian unit LCD controls and keypad display available. Standard language is English.

JOHNSON CONTROLS 17

COMPRESSOR, PIPING, EVAPORATOR OPTIONS:

Low Temperature Glycol – Replaces standard Thermostatic Expansion Valves with Elec-tronic Expansion Valves to achieve leaving glycol temperatures as low as 10°F (-12°C). Re-quired for any leaving liquid temperature below 30°F (-1°C). Electronic Expansion Valves permit operation at both low temperatures and comfort cooling applications without a capac-ity loss or derate at either condition.

Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicago code requirements.

Service Suction Isolation Valve – Service suction discharge (ball-type) isolation valves are added to unit per system (discharge service ball-type isolation valve is standard on each circuit).

Hot Gas By-Pass – Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operating conditions) by introducing an artificial load on the evaporator. Hot gas by-pass is installed on only refrigerant system #1.

Thermal Dispersion Flow Switch – A thermal dispersion type flow switch provides accu-rate, low maintenance flow proving and is included standard. It is factory wired and installed in the extension pipe between evaporator outlet and edge of chiller. The extension pipe is secured to the chiller frame for shipping to avoid risk of damage to evaporator and is easily attached to the evaporator at startup using the supplied ANSI/AWWA C-606 connector. The flow switch can be deleted if alternate or existing flow switch is field supplied.

Evaporator Nozzle Extension Kit – Pipe and ANSI/AWWA C-606 fittings to extend the evaporator connections to the outside of the chiller. Includes the Thermal Dispersion Flow Switch. Provided as standard on all chillers but can be deleted if alternate or existing pip-ing and flow switch is field supplied. The extension pipe is secured to the chiller frame for shipping to avoid risk of damage to evaporator and is easily attached to the evaporator at startup using the supplied ANSI/AWWA C-606 connector. A support bracket for the exten-sion kit or field piping is standard on all chillers. Extension kit insulation and heat trace to be field provided if required.

Heat Recovery Condenser – A partially condensing refrigerant to liquid condenser recov-ers heat off both refrigerant circuits and rejects into a single liquid circuit. Factory installed between the compressor discharge and the condenser (air) coils to capture the maximum amount of heat. Capable of recovering up to 85% total heat of rejection (cooling load plus work input); temperatures as high as 140°F (60°C) are possible.

Hydro-Kit – Factory installed Hydro-Kit suitable for water glycol systems with up to 35% glycol at leaving temperatures down to 20°F (-6.7°C). The hydro-kit option is available in a single or dual configuration (dual as standby duty only), with totally enclosed permanently lubricated pump motors.

The hydro-kit comes standard with a variable speed drive, a balancing valve, discharge check valve, discharge shutoff valve, thermal dispersion flow switch, pressure ports, inlet wye-strainer, bleed and drain valves and frost protection.

Service shut off valves, additional pressure ports and taps for the expansion tank are op-tional within the hydro-kit option. Expansion tanks are available by request.

Accessories and Options (Cont'd)

CONDENSER AND CABINET OPTIONS:

Condenser coil protection against corrosive environments is available by choosing any of the following options. For additional application recommendations, refer to FORM

150.12-ES1.

Environment Guard Premium – Microchannel condenser coils coated with an elec-tro-deposited and baked flexible epoxy coating that is finished with a polyurethane UV resistant top-coat.

Environment Guard Basic – Microchannel condenser coils treated with immersion bath-applied chemical treatment.

Microchannel condenser shall be provided with a 5-year warranty against cor-rosion damage.

Enclosure Panels (Unit) – Tamperproof enclosure panels prevent unauthorized access to units. Enclosure panels can provide an aesthetically pleasing alternative to expensive fencing. Additionally, for proper head pressure control, Johnson Controls recommends the use of Condenser Louvered Panels for winter applications where wind gusts may exceed five miles per hour (8 kph). The following types of enclosure panels are available:

Wire Panels (Full Unit) – Consists of welded wire-mesh guards mounted on the exterior of the unit. Prevents unauthorized access, yet provides free air flow.

Wire/Louvered Panels – Consists of welded wire-mesh panels on the bottom part of unit and louvered panels on the condenser section of the unit.

Louvered Panels (Condenser Coil Only) – Louvered panels are mounted on the sides and ends of the condenser coils for protection.

Louvered Panels (Full Unit) – Louvered panels surround the front, back, and sides of the unit. They prevent unauthorized access and visually screen unit components. Unrestricted

JOHNSON CONTROLS 19

air flow is permitted through generously sized louvered openings. This option is applicable for any outdoor design ambient temperature up to 115°F (46°).

Coil End Hail Guard – Louvered panel attached to exposed coil end.

SOUND ATTENUATION:

One or both of the following sound attenuation options are recommended for residential or other similar sound sensitive locations.

Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absor-bent textile fiber of 5/8" (15mm) thickness; one layer of heavy duty anti-vibration material thickness of 1/8" (3mm). Both are closed by two sheets of welded PVC, reinforced for tem-perature and UV resistance.

Ultra Quiet Fans – Lower RPM, 8-pole fan motors are used with steeper-pitch fans.

Variable Speed Fans - Controls all the fans on the circuit. There is a drive installed for each circuit. Available on both low sound and ultra quiet fans.

VIBRATION ISOLATION

Vibration Isolators – Level adjusting, spring type 1 inch (25.4mm), 2 inch (50.8 mm) de-flection, or neoprene isolators for mounting under unit base rails. (Field installed)

NOMINAL EVAPORATOR WATER FLOW

YLAA TEMPERATURE (°F) WATER FLOW (GPM) AIR ON CONDENSER (°F)

MIN1 MAX2 MIN MAX MIN3 MAX4

STANDARD EFFICIENCY

0070SE 40 55 60 325 0 125

0080SE 40 55 100 350 0 125

0089SE 40 55 100 400 0 125

0100SE 40 55 100 400 0 125

0120SE 40 55 150 625 0 125

0136SE 40 55 115 530 0 125

0155SE 40 55 150 625 0 125

0170SE 40 55 138 525 0 125

HIGH EFFICIENCY

0058HE 40 55 60 325 0 125

0065HE 40 55 60 325 0 125

0081HE 40 55 115 530 0 125

0092HE 40 55 100 400 0 125

0101HE 40 55 100 400 0 125

0125HE 40 55 100 400 0 125

0142HE 40 55 150 530 0 125

0156HE 40 55 138 525 0 125

0175HE 40 55 200 650 0 125

0200HE 40 55 230 625 0 125

0230HE 40 55 220 625 0 125

NOTES:

1. For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]) optional low temperature glycol kit re-quired. Contact your nearest Johnson Controls Office for application requirements.

2. For leaving liquid temperature higher than 55°F (13°C), contact the nearest Johnson Controls Office for application guidelines.

3.The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.
4.For operation at temperatures above 115°F (46°C), the optional High Ambient Kit will need to be installed

on the system.

Design Parameters

JOHNSON CONTROLS 21

Water Pressure Drop

EVAPORATOR YLAA MODELS

A 0058HE, 0065HE, 0070SE

B 0080SE

C 0089SE, 0100SE, 0092HE, 0101HE, 0125HE

D 0081HE, 0136SE, 0170SE, 0156HE

E 0120SE, 0155SE, 0142HE

F 0175HE

G 0200HE

H 0230HE

LD21038a

A C E

D F

G

H

B

YLAA EVAPORATOR PRESSURE DROP CURVE

WATER FLOW RATE (GPM)

W

AT

ER

P

R

ES

SU

R

E D

R O

P (P

SI

Physical Data and Nominal Ratings

REFRIGERANT R-410A

YLAA

REFRIGERANT R-410A

YLAA

STANDARD EFFICIENCY UNITS HIGH EFFICIENCY UNITS

0070SE 0080SE 0089SE 0100SE 0120SE 0136SE 0155SE 0170SE 0058HE 0065HE 0081HE 0092HE 0101HE 0125HE 0142HE 0156HE 0175HE 0200HE 0230HE

NOMINAL RATINGS NOMINAL RATINGS

TONS 71.0 77.8 81.8 95.6 118.1 126.1 143.0 167.4 TONS 57.0 62.3 78.8 85.7 98.3 116.0 129.5 144.5 172.5 194.5 220.6 KW 77.5 86.3 93.0 111.5 134.6 142.6 165.0 192.1 KW 64.4 71.9 91.0 83.6 106.1 122.0 138.9 153.0 194.2 210.9 240.0 EER 10.4 10.0 9.8 9.7 9.8 9.7 9.7 9.7 EER 10.6 10.4 10.4 11.0 10.1 10.3 10.2 10.2 9.8 10.1 10.2 IPLV 16.1 15.6 15.8 14.5 15.0 15.8 15.8 15.6 IPLV 15.6 15.6 16.1 16.1 15.7 15.7 15.9 15.5 15.6 16.1 15.2

GENERAL UNIT DATA GENERAL UNIT DATA

Length, Inches 116.1 116.1 116.1 142.7 142.7 187.7 187.7 232.7 Length, Inches 100.2 100.2 100.2 142.7 142.7 187.7 187.7 232.7 232.7 274.4 274.4 Width, Inches 88 88 88 88 88 88 88 88 Width, Inches 88.0 88.0 88.0 88 88 88 88 88 88 88.3 88.3 Height, Inches 94.2 94.2 94.2 94.2 94 94.2 94.2 94.2 Height, Inches 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 Number of Refrigerant Circuits

2 2 2 2 2 2 2 2 Number of Refrigerant Circuits

2 2 2 2 2 2 2 2 2 2 2

REFRIGERANT CHARGE, OPERATING REFRIGERANT CHARGE, OPERATING

R-410A, Circuit 1 / Circuit 2, lbs

43/43 47/44 57/57 55/58 54/62 75/71 75/70 90/87 R-410A, Circuit 1 / Circuit 2, lbs

43/43 43/43 44/44 59/55 45/65 75/71 83/73 90/82 94/92 95/95 100/100

Oil Charge, Circuit 1 / Circuit 2, gallons

2.58/2.58 3.28/2.58 3.28/2.76 3.28/3.33 3.33/3.33 4.99/2.76 4.99/3.33 4.99/4.99 Oil Charge, Circuit 1 / Circuit 2, gallons

2.58/2.582.89/2.582.58/2.582.76/2.763.28/3.333.33/3.334.99/2.764.99/3.334.99/4.99 4.2/4.2 4.99/4.99

Shipping Weight, lbs 3578 3898 4168 4791 5183 6148 6414 7734 Shipping Weight, lbs 3508 3704 4061 4718 4953 5869 6259 7344 7882 9205 9690 Operating Weight, lbs 3623 3954 4241 4864 5293 6232 6524 7818 Operating Weight, lbs 3552 3748 4145 4791 5026 5942 6369 7428 8001 9333 9821

COMPRESSORS, SCROLL TYPE COMPRESSORS, SCROLL TYPE

Compressors per circuit 3/3 3/3 3/3 3/2 2/2 3/3 3/2 3/3 Compressors per circuit 2/2 3/2 3/3 3/3 3/2 2/2 3/3 3/2 3/3 3/3 3/3 Compressors per unit 6 6 6 5 4 6 5 6 Compressors per unit 4 5 6 6 5 4 6 5 6 6 6

NOMINAL TONS PER COMPRESSOR NOMINAL TONS PER COMPRESSOR

Circuit 1 13 15 15 15 32 32 32 32 Circuit 1 15 13 15 15 15 32 32 32 32 35 40 Circuit 2 13 13 15 32 32 15 32 32 Circuit 2 15 15 13 15 32 32 15 32 32 35 40

CONDENSER CONDENSER

Total Face Area ft2 106.9 106.9 106.9 133.6 160.3 213.8 213.8 267.2 Total Face Area ft2 106.9 106.9 106.9 160.3 160.3 213.8 213.8 267.2 267.2 320 320 Number of Rows 1 1 1 1 1 1 1 1 Number of Rows 1 1 1 1 1 1 1 1 1 1 1 Fins per Inch 20 20 20 20 20 20 20 20 Fins per Inch 20 20 20 20 20 20 20 20 20 20 20

CONDENSER FANS, LOW SOUND CONDENSER FANS, LOW SOUND

Number of Fans, Circuit 1/Circuit 2

2/2 2/2 2/2 3/2 3/3 4/4 4/4 5/5 Number of Fans, Circuit 1/Circuit 2

2/2 2/2 2/2 3/3 4/2 4/4 5/3 6/4 5/5 6/6 6/6

Fan hp 2 2 2 2 2 2 2 2 Fan hp 2 2 2 2 2 2 2 2 2 2 2 Fan RPM 1160 1160 1160 1160 1160 1160 1160 1160 Fan RPM 1160 1160 1160 1160 1160 1160 1160 1160 1160 1160 1160 Total Chiller CFM 62400 62400 62400 78000 93600 124800 124800 156000 Total Chiller CFM 62400 62400 62400 93600 93600 124800 124800 156000 156000 187200 187200

EVAPORATOR EVAPORATOR

Water Volume, Gallons 5.4 6.7 8.8 8.8 13.2 10.0 13.2 10.0 Water Volume, Gallons 5.4 5.4 10 8.8 8.8 8.8 13.2 10.0 14.3 12.6 14.3 Maximum Water Side Pressure, Psig

150 150 150 150 150 150 150 150 Maximum Water Side Pressure, PSIG

150 150 150 150 150 150 150 150 150 150 150

Maximum Refrigerant Side Pressure, Psig

450 450 450 450 450 450 450 450 Maximum Refrigerant Side Pressure, PSIG

450 450 450 450 450 450 450 450 450 450 450

Minimum Chiller Water Flow Rate, Gpm

60 100 140 100 150 150 150 150 Minimum Chiller Water Flow Rate, GPM

60 60 150 100 100 100 150 150 150 230 220

Maximum Chiller Water Flow Rate, Gpm

285 355 385 385 625 625 625 625 Maximum Chiller Water Flow Rate, GPM

285 285 625 385 385 385 625 625 625 625 625

Water Connections Size, Inches

3 3 3 3 3 4* 4* 4* Water Connections Size, Inches

3" 3 3 3 3 4* 4* 4* 4* 5" 5"

* Side extension kit (standard), evaporator nozzle remains 3”. * Side extension kit (standard), evaporator nozzle remains 3”.

JOHNSON CONTROLS 23

REFRIGERANT R-410A

YLAA

REFRIGERANT R-410A

YLAA

STANDARD EFFICIENCY UNITS HIGH EFFICIENCY UNITS

0070SE 0080SE 0089SE 0100SE 0120SE 0136SE 0155SE 0170SE 0058HE 0065HE 0081HE 0092HE 0101HE 0125HE 0142HE 0156HE 0175HE 0200HE 0230HE

NOMINAL RATINGS NOMINAL RATINGS

TONS 71.0 77.8 81.8 95.6 118.1 126.1 143.0 167.4 TONS 57.0 62.3 78.8 85.7 98.3 116.0 129.5 144.5 172.5 194.5 220.6 KW 77.5 86.3 93.0 111.5 134.6 142.6 165.0 192.1 KW 64.4 71.9 91.0 83.6 106.1 122.0 138.9 153.0 194.2 210.9 240.0 EER 10.4 10.0 9.8 9.7 9.8 9.7 9.7 9.7 EER 10.6 10.4 10.4 11.0 10.1 10.3 10.2 10.2 9.8 10.1 10.2 IPLV 16.1 15.6 15.8 14.5 15.0 15.8 15.8 15.6 IPLV 15.6 15.6 16.1 16.1 15.7 15.7 15.9 15.5 15.6 16.1 15.2

GENERAL UNIT DATA GENERAL UNIT DATA

Length, Inches 116.1 116.1 116.1 142.7 142.7 187.7 187.7 232.7 Length, Inches 100.2 100.2 100.2 142.7 142.7 187.7 187.7 232.7 232.7 274.4 274.4 Width, Inches 88 88 88 88 88 88 88 88 Width, Inches 88.0 88.0 88.0 88 88 88 88 88 88 88.3 88.3 Height, Inches 94.2 94.2 94.2 94.2 94 94.2 94.2 94.2 Height, Inches 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2 Number of Refrigerant Circuits

2 2 2 2 2 2 2 2 Number of Refrigerant Circuits

2 2 2 2 2 2 2 2 2 2 2

REFRIGERANT CHARGE, OPERATING REFRIGERANT CHARGE, OPERATING

R-410A, Circuit 1 / Circuit 2, lbs

43/43 47/44 57/57 55/58 54/62 75/71 75/70 90/87 R-410A, Circuit 1 / Circuit 2, lbs

43/43 43/43 44/44 59/55 45/65 75/71 83/73 90/82 94/92 95/95 100/100

Oil Charge, Circuit 1 / Circuit 2, gallons

2.58/2.58 3.28/2.58 3.28/2.76 3.28/3.33 3.33/3.33 4.99/2.76 4.99/3.33 4.99/4.99 Oil Charge, Circuit 1 / Circuit 2, gallons

2.58/2.582.89/2.582.58/2.582.76/2.763.28/3.333.33/3.334.99/2.764.99/3.334.99/4.99 4.2/4.2 4.99/4.99

Shipping Weight, lbs 3578 3898 4168 4791 5183 6148 6414 7734 Shipping Weight, lbs 3508 3704 4061 4718 4953 5869 6259 7344 7882 9205 9690 Operating Weight, lbs 3623 3954 4241 4864 5293 6232 6524 7818 Operating Weight, lbs 3552 3748 4145 4791 5026 5942 6369 7428 8001 9333 9821

COMPRESSORS, SCROLL TYPE COMPRESSORS, SCROLL TYPE

Compressors per circuit 3/3 3/3 3/3 3/2 2/2 3/3 3/2 3/3 Compressors per circuit 2/2 3/2 3/3 3/3 3/2 2/2 3/3 3/2 3/3 3/3 3/3 Compressors per unit 6 6 6 5 4 6 5 6 Compressors per unit 4 5 6 6 5 4 6 5 6 6 6

NOMINAL TONS PER COMPRESSOR NOMINAL TONS PER COMPRESSOR

Circuit 1 13 15 15 15 32 32 32 32 Circuit 1 15 13 15 15 15 32 32 32 32 35 40 Circuit 2 13 13 15 32 32 15 32 32 Circuit 2 15 15 13 15 32 32 15 32 32 35 40

CONDENSER CONDENSER

Total Face Area ft2 106.9 106.9 106.9 133.6 160.3 213.8 213.8 267.2 Total Face Area ft2 106.9 106.9 106.9 160.3 160.3 213.8 213.8 267.2 267.2 320 320 Number of Rows 1 1 1 1 1 1 1 1 Number of Rows 1 1 1 1 1 1 1 1 1 1 1 Fins per Inch 20 20 20 20 20 20 20 20 Fins per Inch 20 20 20 20 20 20 20 20 20 20 20

CONDENSER FANS, LOW SOUND CONDENSER FANS, LOW SOUND

Number of Fans, Circuit 1/Circuit 2

2/2 2/2 2/2 3/2 3/3 4/4 4/4 5/5 Number of Fans, Circuit 1/Circuit 2

2/2 2/2 2/2 3/3 4/2 4/4 5/3 6/4 5/5 6/6 6/6

Fan hp 2 2 2 2 2 2 2 2 Fan hp 2 2 2 2 2 2 2 2 2 2 2 Fan RPM 1160 1160 1160 1160 1160 1160 1160 1160 Fan RPM 1160 1160 1160 1160 1160 1160 1160 1160 1160 1160 1160 Total Chiller CFM 62400 62400 62400 78000 93600 124800 124800 156000 Total Chiller CFM 62400 62400 62400 93600 93600 124800 124800 156000 156000 187200 187200

EVAPORATOR EVAPORATOR

Water Volume, Gallons 5.4 6.7 8.8 8.8 13.2 10.0 13.2 10.0 Water Volume, Gallons 5.4 5.4 10 8.8 8.8 8.8 13.2 10.0 14.3 12.6 14.3 Maximum Water Side Pressure, Psig

150 150 150 150 150 150 150 150 Maximum Water Side Pressure, PSIG

150 150 150 150 150 150 150 150 150 150 150

Maximum Refrigerant Side Pressure, Psig

450 450 450 450 450 450 450 450 Maximum Refrigerant Side Pressure, PSIG

450 450 450 450 450 450 450 450 450 450 450

Minimum Chiller Water Flow Rate, Gpm

60 100 140 100 150 150 150 150 Minimum Chiller Water Flow Rate, GPM

60 60 150 100 100 100 150 150 150 230 220

Maximum Chiller Water Flow Rate, Gpm

285 355 385 385 625 625 625 625 Maximum Chiller Water Flow Rate, GPM

285 285 625 385 385 385 625 625 625 625 625

Water Connections Size, Inches

3 3 3 3 3 4* 4* 4* Water Connections Size, Inches

3" 3 3 3 3 4* 4* 4* 4* 5" 5"

* Side extension kit (standard), evaporator nozzle remains 3”. * Side extension kit (standard), evaporator nozzle remains 3”.

Physical Data and Nominal Ratings (Cont'd)

STANDARD EFFICIENCY

Part Load Ratings

YLAA0070SE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 71.0 75.5 95.0 10.4

83.3 62.8 56.2 88.1 12.0

66.7 53.7 39.4 80.4 14.0

50.0 42.1 26.4 70.5 16.0

33.3 29.2 15.6 59.6 18.5

16.7 14.4 7.4 55.0 19.1

IPLV 16.1

YLAA0080SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 77.8 86.3 95.0 10.0

83.6 69.5 68.2 88.6 11.1

66.7 59.2 46.2 80.6 13.4

50.3 47.3 32.3 71.5 15.2

33.3 32.0 17.9 59.7 18.1

16.9 16.9 9.1 55.0 18.9

IPLV 15.6

YLAA0089SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 81.8 93.0 95.0 9.8

83.3 72.6 69.7 88.2 11.4

66.7 62.3 48.7 80.7 13.5

50.0 49.1 31.8 71.0 15.3

33.3 33.3 18.5 59.1 18.3

16.7 16.4 8.6 55.0 19.1

IPLV 15.8

YLAA0100SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 95.6 111.5 95.0 9.7

86.1 86.5 88.5 89.3 10.7

57.0 64.5 45.4 75.5 14.4

43.0 47.4 34.4 64.7 15.1

13.9 16.0 8.5 55.0 18.7

IPLV 14.5

YLAA0120SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 118.1 134.6 95.0 9.8

75.0 96.6 84.1 84.1 12.3

50.0 71.0 43.1 71.1 16.0

25.0 33.0 22.0 55.0 16.7

IPLV 15.0

YLAA0136SE

%DISPL. TONS COMPR.

KW AMBIENT (°F) UNIT

EER

100.0 126.1 142.6 95.0 9.7

83.3 108.0 91.9 86.4 12.2

66.7 95.7 73.7 80.5 13.3

50.0 67.3 41.5 67.0 16.6

33.3 52.1 27.8 59.8 18.0

16.7 35.0 18.4 55.0 19.1

IPLV 15.8

YLAA0155SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 143.0 165.0 95.0 9.7

80.0 127.2 112.3 87.3 11.9

60.0 101.5 71.3 76.7 14.1

40.0 70.0 41.0 63.8 17.6

20.0 35.0 18.4 55.0 18.9

IPLV 15.8

YLAA0170SE

% DISPL. TONS

COMPR.

KW

AMBIENT (°F) UNIT

EER

100.0 167.4 192.1 95.0 9.7

83.3 148.5 142.3 88.2 11.2

66.7 127.9 98.8 80.8 13.3

50.0 101.5 64.3 71.4 15.0

33.3 69.5 38.9 59.9 18.3

16.7 34.5 18.2 55.0 19.2

IPLV 15.6

JOHNSON CONTROLS 25

HIGH EFFICIENCY

YLAA0058HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 57.0 57.7 95.0 10.6

75.0 46.2 36.6 83.7 12.8

50.0 32.4 20.9 69.1 16.0

25.0 16.6 8.8 55.0 19.0

IPLV 15.6

YLAA0065HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 62.3 65.2 95.0 10.4

80.0 54.3 46.8 87.3 12.2

60.0 42.5 28.9 75.9 14.3

40.0 30.0 17.7 63.9 17.1

20.0 13.8 7.3 55.0 18.5

IPLV 15.6

YLAA0081HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 78.8 84.3 95.0 10.4

83.6 70.2 64.9 88.4 11.8

66.7 59.5 43.9 80.3 14.1

50.3 47.7 30.2 71.3 15.5

33.3 31.7 16.9 59.2 18.8

16.7 16.8 8.6 55.0 19.6

IPLV 16.1

YLAA0092HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 85.7 83.6 95.0 11.0

83.3 74.9 64.0 87.4 12.4

66.7 62.7 46.3 78.9 14.2

50.0 48.7 30.9 69.1 16.3

33.3 33.2 17.7 58.3 18.9

16.7 16.3 8.1 55.0 19.4

IPLV 16.1

YLAA0101HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 98.3 106.1 95.0 10.1

86.1 89.3 82.8 89.5 11.5

57.0 65.6 43.7 75.1 14.6

43.0 50.3 30.5 65.7 17.0

13.9 16.0 8.5 55.0 19.0

IPLV 15.7

YLAA0125HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 116.0 112.0 95.0 10.3

75.0 94.6 76.8 83.9 12.6

50.0 67.2 43.5 69.7 16.0

25.0 34.9 18.3 55.0 19.3

IPLV 15.7

YLAA0142HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 129.5 138.9 95.0 10.2

83.3 109.7 90.1 85.8 12.7

66.7 97.4 71.1 80.1 13.8

50.0 67.4 39.6 66.2 16.9

33.3 51.4 27.1 58.8 18.3

16.7 34.4 18.1 55.0 19.2

IPLV 15.9

YLAA0156HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 144.5 153.0 95.0 10.2

80.0 124.8 108.4 86.8 12.0

60.0 97.8 72.4 75.6 14.2

40.0 70.4 39.9 64.2 16.9

20.0 34.6 18.5 55.0 19.0

IPLV 15.5

YLAA0175HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 172.5 194.2 95.0 9.8

83.3 152.6 143.5 88.1 11.4

66.7 130.8 99.2 80.5 13.5

50.0 102.7 64.2 70.7 15.2

33.3 69.2 38.6 59.1 18.3

16.7 34.1 18.3 55.0 18.9

IPLV 15.6

YLAA0200HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 194.5 210.9 95.0 10.1

88.9 172.9 156.5 88.4 11.8

76.7 149.2 108.7 81.0 13.9

60.6 117.9 71.6 71.4 16.0

42.9 83.3 41.1 60.7 18.3

20.4 39.6 20.9 55.0 19.6

IPLV = 16.1

YLAA0230HE

% DISPL. TONS COMPR. KW AMBIENT (°F) UNIT EER

100.0 220.6 240.0 95.0 10.2

88.9 196.2 190.5 88.4 11.2

76.7 169.2 134.9 81.0 13.1

60.6 133.7 91.0 71.4 14.9

42.8 94.4 53.9 60.7 16.8

20.2 44.6 27.4 55.0 17.4

IPLV = 16.1

Part Load Ratings (Cont'd)

3” INLET

3” OUTLET

LD18432

YLAA0058HE, YLAA0065HE, YLAA0081HE

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

Unit Dimensions

JOHNSON CONTROLS 27

LD18433

YLAA0070SE, YLAA0080SE, YLAA0089SE

Unit Dimensions (Cont'd)

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

LD18434

YLAA0100SE

Unit Dimensions (Cont'd)

JOHNSON CONTROLS 29

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

YLAA0120SE, YLAA0092HE, YLAA0101HE

LD18435

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

LD18436

YLAA0125HE, YLAA 0136SE, YLAA0155SE, YLAA0142HE

JOHNSON CONTROLS 31

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

LD18437

YLAA 0170SE, YLAA0156HE, YLAA0175HE

NOTE:

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;

however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';

top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.

YLAA0200HE, YLAA0230HE

LD21039

JOHNSON CONTROLS 33

Isolator Locations

FOUR FAN ISOLATOR LOCATIONS

YLAA0070SE, YLAA0080SE, YLAA0089SE

FOUR FAN ISOLATOR LOCATIONS

YLAA0058HE, YLAA0065HE, YLAA0081HE

LD19400

1.4

1.4

LD18438

All dimensions are inches unless otherwise specified.

Dimensions indicate isolator mounting centerlines.

FIVE & SIX FAN ISOLATOR LOCATIONS

YLAA0100SE, YLAA0120SE, YLAA0092HE, YLAA0101HE

Isolator Locations (Cont'd)

EIGHT FAN ISOLATOR LOCATIONS

YLAA0125HE, YLAA 0136SE, YLAA0155SE, YLAA0142HE

TOP

VIEW

LD18439

TOP

VIEW

LD18440

JOHNSON CONTROLS 35

TEN FAN ISOLATOR LOCATIONS

YLAA 0170SE, YLAA0156HE, YLAA0175HE

TWELVE FAN ISOLATOR LOCATIONS

YLAA0200HE, YLAA0230HE

Isolator Locations (Cont'd)

TOP

VIEW

LD18441

LD21040

TOP

VIEW

Isolator Details

TWO INCH DEFLECTION, SPRING ISOLATOR (Y2RS-)

3/4”

7/8”

3/8” GAP

3/4”

TYP. (4)

5/8” 2-3/4”

1-1/8”

2-3/4”

P

STOP &

8-3/8”

OPER.

HEIGHT

LD18442

MODEL Y2RSI-2D RESTRAINED VIBRATION ISOLATOR FOR 2" DEFLECTION

MOUNT RATED LOAD

LBS (KG)

RATED

DEFLECTION

IN (MM)

SPRING RATE

LBS/IN (N/M)

SOLID LOAD

LBS (KG) COLOR CODE

ALLOWABLE

G RATING

HORIZONTAL

Y2RSI-2D-150 150 (68) 2.4 (61) 62 (7) 234 (106) WHITE 34.7

Y2RSI-2D-320 320 (145) 2.3 (58) 140 (16) 490 (222) YELLOW 16.3

Y2RSI-2D-460 460 (209) 2.3 (58) 200 (23) 688 (312) GREEN 11.3

Y2RSI-2D-710 710 (322) 2.2 (56) 330 (37) 1072 (486) DK BROWN 7.3

Y2RSI-2D-870 870 (395) 1.9 (48) 460 (52) 1312 (595) RED 6

Y2RSI-2D-1200N 1200 (544) 1.9 (48) 638 (72) 1818 (825) RED/BLACK 4.3

Y2RSI-2D-1450 1450 (658) 1.8 (46) 900 (102) 2450 (1111) TAN 3.6

Y2RSI-2D-1690 1690 (767) 1.7 (43) 1140 (129) 2892 (1312) PINK 3.1

Y2RSI-2D-2000N 2000 (907) 1.7 (43) 1318 (149) 3342 (1516) PINK/BLACK 2.6

Y2RSI-2D-2640N 2640 (1197) 1.5 (38) 1854 (209) 4283 (1943) PINK/GRAY 2

Y2RSI-2D-2870N 3080 (1397) 1.5 (38) 2004 (226) 4629 (2100)

PINK/GRAY/

ORANGE

1.7

Y2RSI-2D-3280N 3740 (1696) 1.8 (46) 2134 (241) 4930 (2236)

PINK/GRAY/

DK. BROWN

1.4

JOHNSON CONTROLS 37

Isolator Details (Cont'd)

EQUIPMENT

BASE

(BY OTHERS)

POSITIONING

PIN

LD18443

ONE INCH DEFLECTION SPRING ISOLATOR (CPX-X-)

MOUNT

DIMENSION DATA INCHES (MM)

W D L B C T H

CP1 3 (76) 0.625 (16) 7.75 (197) 6.5 (165) 4.75 (121) 0.5 (13) 4.625 (117)

CP2 3 (76) 0.625 (16) 10.5 (267) 9.25 (235) 7.75 (197) 0.5625 (14) 6 (152)

MOUNT RATED CAPACITY

LBS (KG)

DEFLECTION

RATED IN (MM) COLOR CODE

CP1-1D-85 85 (39) 1020 (463) LT. PURPLE

CP1-1D-120 120 (54) 1.2 (30) DK. YELLOW

CP1-1D-175 175 (79) 1.17 (30) DK. BLUE

CP1-1D-250 250 (113) 1.4 (36) YELLOW

CP1-1D-340 340 (154) 1.13 (29) RED

CP1-1D-510 510 (231) 1.02 (26) BLACK

CP1-1D-675 675 (306) 1.32 (34) DK. PURPLE

CP1-1D-900 900…