Sprinkler Inspection Certificate.pdf

PDF 895 KB Posted

Attached to
NCCCWA Fire System Upgrades, Kearneysville, WV
Solicitation number
1232SA26Q0485
Issued by

About this file

This is a Sprinkler Inspection Certificate documenting the annual inspection of the fire suppression systems at the US Department of Agriculture NCCCWA facility located at 11861 Leetown Road, Kearneysille, WV 25430. The inspection was conducted by ARK Systems, Inc. on July 7, 2025, in accordance with NFPA 25 Standards. The facility operates two wet pipe fire sprinkler systems protecting 40 devices total: one primary wet pipe system with 39 devices and one domestic wet pipe system with one device. The inspection achieved an overall pass rate of 82.93%, with 34 of 41 items passing inspection and 7 items identified as failed or requiring attention.

The discrepancies identified include defective or unlocked control valves in the 1st pump room (#110), defective fire pump gauges, a defective test header with a damaged/worn gauge, and a pump requiring maintenance. Specific findings note that two OS&Y control valves (suction and discharge) are unsecured and require correction, the test header control valve requires replacement (Model 705W), both fire pump gauges require replacement, and the main pump requires maintenance due to a hole in test header piping (4" steel schedule 10, 18-1/4" length) and a defective casing relief valve. All proposed repairs are available on a time and materials basis. The facility's fire suppression infrastructure includes fire pumps, jockey pumps, alarm valves, backflow prevention devices, and various monitoring switches, with most major components installed between 1998 and 2010.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection Certificate For

US Dept of Agriculture NCCCWA 11861 Leetown Road Kearneysille, WV 25430

This Inspection was performed in accordance with applicable NFPA 25 Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Date Jul 7, 2025

Building: US Dept of Agriculture NCCCWA Company: ARK Systems, Inc.

Contact: Dennis Bennett Contact: Charles Everett Title: Facility Manager Title: Service Manager

ARK Systems, Inc. 1 Download Date: 07/09/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: US Dept of Agriculture NCCCWA Contact: Dennis Bennett

Address: 11861 Leetown Road Phone: 304-261-6235

Address: Fax:

City/State/ZIP Code: Kearneysille, WV 25430 Mobile:

Country: United States of America Email: Dennis.Bennett@usda.gov

Inspection Performed By Company: ARK Systems, Inc. Inspector: Troy Myers

Address: 9176 Red Branch Road Phone: 410-995-1220

Address: Fax:

City/State/ZIP Code: Columbia, Maryland 21045 Mobile:

Country: United States of America Email: tmyers@arksysinc.com

System Control Unit System Type System Location Protected Area Devices Wet Pipe 39 Wet Pipe (domestic) 1

ARK Systems, Inc. 2 Download Date: 07/09/2025

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Alarm 4 9.76% 4 100.00% 4 100.00% 0 0.00% Device 10 24.39% 10 100.00% 9 90.00% 1 10.00% Hose 1 2.44% 1 100.00% 1 100.00% 0 0.00% Pump 6 14.63% 6 100.00% 3 50.00% 3 50.00% Sprinkler 5 12.20% 5 100.00% 5 100.00% 0 0.00% Valve 15 36.59% 15 100.00% 12 80.00% 3 20.00%

Totals 41 100% 41 100.00

34 82.93% 7 17.07%

Certification

Company: ARK Systems, Inc. Building: US Dept of Agriculture NCCCWA

Inspector: Troy Myers Contact: Dennis Bennett

ARK Systems, Inc. 3 Download Date: 07/09/2025

Discrepancy Report

Building: US Dept of Agriculture NCCCWA The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe Control Valve

55165030 1st pump room #110 Unlocked/Unsealed NFPA25 13.3.2.2 (2) 55165032 1st pump room #110 Unlocked/Unsealed NFPA25 13.3.2.2 (2) 11668479 1st pump room #110 test header Defective NFPA25 4.1.5.1

Fire Pump Gauge 55165026 1st pump room #110 Defective NFPA25 8.4.1 55165027 1st pump room #110 Defective NFPA25 8.4.1

Gauge 55165038 1st pump room #110 Damaged/Worn NFPA25 4.1.5.1

Pump 11667705 1st pump room #110 Requires Maintenance NFPA25 8.5.1

ARK Systems, Inc. 4 Download Date: 07/09/2025

Proposed Solutions Report

Building: US Dept of Agriculture NCCCWA

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Control Valve

55165030 1st pump room #110 Correct

T/M

55165032 1st pump room #110 Correct

11668479 1st pump room #110 test header Replace 705W T/M

Fire Pump Gauge

55165026 1st pump room #110 Replace

55165027 1st pump room #110 Replace

Gauge

55165038 1st pump room #110 Replace

Pump

11667705 1st pump room #110 See Notes/Recommenda tions

284TS T/M

Customer WO/PO #:

(none)

Internal WO/PO #: (none)

ARK Systems, Inc. 5 Download Date: 07/09/2025

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Wet Pipe 1 Control Valve 1st pump room #110 test header Defective 11668479

It’s a 5” take out for the 4” control valve 2 Pump 1st pump room #110 Requires

Maintenance 11667705

Test header piping has hole in pipe steel schedule 10 (4”) length is 18-1/4” The casing relief valve is bad and needs to be replaced

ARK Systems, Inc. 6 Download Date: 07/09/2025

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Special Sprinkler Annual 10:26:16 AM 07/07/2025

Wet Pipe Tamper Switch 1st pump room #110 backflow 1 Annual 10:07:17 AM 07/07/2025 Tamper Switch 1st pump room #110 backflow 2 Annual 10:08:28 AM 07/07/2025 Waterflow Switch 1st pump room#110 system 2 lab bldg Annual 1:10:28 PM 07/07/2025 Waterflow Switch 1st pump room#110 system 1 tank bldg Annual 1:10:32 PM 07/07/2025 Drain 1st pump room #110 Annual 10:36:08 AM 07/07/2025 Drain 1st pump room #110 Annual 10:36:11 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:12:36 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:12:40 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:14:13 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:14:17 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:18:39 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:18:48 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:19:49 AM 07/07/2025 Fire Dep't Connection 1st pump room #110 Annual 10:25:58 AM 07/07/2025 Controller 1st pump room #110 Annual 10:36:31 AM 07/07/2025 Jockey Controller 1st pump room #110 Annual 10:18:57 AM 07/07/2025 Jockey Pump 1st pump room #110 Annual 10:19:07 AM 07/07/2025 Sprinkler Box 1st pump room #110 Annual 10:25:55 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:10 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:11 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:13 AM 07/07/2025 Alarm Valve 1st pump room #110 Annual 10:13:25 AM 07/07/2025 Alarm Valve 1st pump room #110 Annual 10:14:04 AM 07/07/2025 Backflow Prevention 1st pump room #110 Annual 1:10:11 PM 07/07/2025 Check Valve 1st pump room #110 Annual 10:19:26 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:09:24 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:09:32 AM 07/07/2025 Control Valve 1st pump room#110 system 2 lab bldg Annual 10:11:16 AM 07/07/2025 Control Valve 1st pump room#110 system 1 tank bldg Annual 10:11:57 AM 07/07/2025 Control Valve 1st pump room #110 fire pump discharge Annual 10:15:18 AM 07/07/2025 Inspector's Test 1st Inside Loading Dock Area Annual 12:57:32 PM 07/07/2025 Inspector's Test 1st Inside Wet Lab Area Annual 1:05:09 PM 07/07/2025

Wet Pipe, (domestic) Backflow Prevention 1st pump room #110 Annual 1:10:18 PM 07/07/2025

Failed/Other

ARK Systems, Inc. 7 Download Date: 07/09/2025

Device Type Location Service Time Date Gauge 1st pump room #110 Annual 10:35:14 AM 07/07/2025 Fire Pump Gauge 1st pump room #110 Annual 10:17:07 AM 07/07/2025 Fire Pump Gauge 1st pump room #110 Annual 10:18:02 AM 07/07/2025 Pump 1st pump room #110 Annual 10:34:56 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:15:50 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:16:30 AM 07/07/2025 Control Valve 1st pump room #110 test header Annual 10:22:04 AM 07/07/2025

ARK Systems, Inc. 8 Download Date: 07/09/2025

Wet Pipe Fire Sprinkler Systems

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller

Manufacturer Model # Description Location OK ScanID US Electrical Motors

C3B154-4TE4 Automatic 1st pump room #110 15037111

Serial # AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup 208881 Phase Reversal n/a 100 115 No Yes

Fire Pump Gauge

Location Type Discharge psi Suction psi OK ScanID 1st pump room #110 Suction 40 40 55165026

1st pump room #110 Discharge 40 40 55165027

Jockey Controller

Manufacturer Model # Location Install Date OK ScanID Joslyn Clark 1st pump room #110 06/24/2010 55165039

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 100 115 No Yes

Jockey Pump

Manufacturer Model # Location Install Date OK ScanID Franklin electric 1303007 150 1st pump room #110 06/24/2010 55165040

Serial # Type Horsepower Rated Speed Volts Amps On psi Off psi Automatic 100 115

Pump

Manufacturer Model # Location Install Date OK ScanID US Electrical Motors

284TS 1st pump room #110 06/24/2010 11667705

Type Orientation Aligned? Water Supply Impeller Size Startup Pump Primary Horizontal 6.750

Serial # D09 01059351-004R

Fire Pump Rating

Amps Volts

Net Pressure Gallons Per Minute

Rotations Per Minute A B C A-B B-C A-C

75.6 0 3560

75.6 0 3560

ARK Systems, Inc. 9 Download Date: 07/09/2025

85 0

65 500 3560

65 500

43.5 750 3530

43.5 750

Alarms Tamper Switch

Type Description Location # of Turns Zone/Address OK ScanID Control Valve Supervisory 1st pump room #110 backflow

1-2 40 11667700

Control Valve Supervisory 1st pump room #110 backflow

1-2 39 11668477

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD25 35.580

00183 10547

2.5” 1-2 26 11667784

Vane System Sensor WFD25 29.520 00045 77637

2.5” 1-2 25 11667783

Components

ARK Systems, Inc. 10 Download Date: 07/09/2025

Alarm Valve

Type Location Manufacturer Model # OK ScanID Grooved 1st pump room #110 Victaulic S/751 55165034

Position Status Size Internal Date 2.5" 08/01/2023

Alarm Valve

Type Location Manufacturer Model # OK ScanID Grooved 1st pump room #110 Victaulic S/751 55165036

Position Status Size Internal Date 2.5" 08/01/2023

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date OK ScanID Ames 2000 SE 6" 06/24/2000 55165024

Water Purveyor Location Meter Acct. # Serial # 1st pump room #110

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker Held At

Repairs or Notes

Final Test

Condition of Control Valve 1 Condition of Control Valve 2

Check Valve

Type Location Manufacturer Model # Internal Date Size OK ScanID Flanged by Grooved

1st pump room #110 Victaulic S/717 08/01/2023 4" 55165031

Control Valve

Type Location Manufacturer Model # OK ScanID Gate 1st pump room #110 Kennedy BF 2 55165023

Position Size Status Description Open 6" Supervised Main Control

Control Valve

Type Location Manufacturer Model # OK ScanID Gate 1st pump room #110 Kennedy BF 1 55165025

Position Size Status Description Open 6" Supervised Main Control

Control Valve

Type Location Manufacturer Model # OK ScanID

ARK Systems, Inc. 11 Download Date: 07/09/2025

Butterfly 1st pump room#110 system 2 lab bldg

Victaulic 705W 11668478

Position Size Status Description Open 2.5" Supervised Isolation

Control Valve

Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room#110 system 1 tank bldg Victaulic 705W 11667782

Position Size Status Description Open 2.5" Supervised Isolation

Control Valve

Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room #110 fire pump discharge Victaulic 705W 11668480

Position Size Status Description Open 4" Supervised Discharge

Control Valve

Type Location Manufacturer Model # OK ScanID OS&Y 1st pump room #110 NIBCO 55165032

Position Size Status Description Open 1" Unsecured Discharge

Control Valve

Type Location Manufacturer Model # OK ScanID OS&Y 1st pump room #110 NIBCO 55165030

Position Size Status Description Open 1" Unsecured Suction

Control Valve

Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room #110 test header Victaulic 705W 11668479

Position Size Status Description Closed 4" Supervised TEST HEADER

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID 78560063

Location 1st Inside Loading Dock Area

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID 41190382

Location 1st Inside Wet Lab Area

ARK Systems, Inc. 12 Download Date: 07/09/2025

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 150 155 140 55165035

Previous Inspections

September 12, 2024

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 120 120 105 3 55165035

May 22, 2023

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 110 120 100 5 55165035

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 158 155 140 55165033

Previous Inspections

September 12, 2024

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 120 120 105 3 55165033

May 22, 2023

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 110 120 100 5 55165033

Fire Dep't Connection

Location Type Size Qty BallDrip Rotating Swivels 5-Year Hydro OK ScanID 1st pump room #110 Wall 2.5" 12/13/1901 11667704

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/2 15037113

Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037112

Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037115

Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300

Gauge

ARK Systems, Inc. 13 Download Date: 07/09/2025

Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037114

Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 .300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165028

Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165037

Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165029

Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300

Gauge

Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165038

Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID 11 Yes 12 unit 1st pump room #110 11667701

Sprinkler Box Spares

Qty Type Location Manufacturer OK ScanID 5 Upright 1st pump room 110 Viking 55165022

Temperature KFactor Size Response Time Finish 155 Fast Response Chrome

Sprinkler Box Spares

Qty Type Location Manufacturer OK ScanID 2 Horizontal Sidewall 1st pump room 110 Viking 11668444

Temperature KFactor Size Response Time Finish 155 Fast Response Chrome

Sprinkler Box Spares

Qty Type Location Manufacturer OK ScanID 4 Pendant 1st pump room 110 Viking 55165021

Temperature KFactor Size Response Time Finish

ARK Systems, Inc. 14 Download Date: 07/09/2025

155 Standard Response Chrome

ARK Systems, Inc. 15 Download Date: 07/09/2025

Building: US Dept of Agriculture NCCCWA (domestic)

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date OK ScanID Wilkins 375 4" Reduced Pressure domestic 06/24/2000 45382437

Water Purveyor Location Meter Acct. # Serial # n/a 1st pump room #110 n/a

Initial Test

Repairs or Notes

Final Test

Condition of Control Valve 1 Condition of Control Valve 2 Closed Tight Closed Tight

ARK Systems, Inc. 16 Download Date: 07/09/2025

Inventory & Warranty Report

Building: US Dept of Agriculture NCCCWA

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Alarm Valve Valve 4.88% 2

Backflow Prevention Valve 4.88% 2

Check Valve Valve 2.44% 1

Control Valve Valve 19.51% 8

Controller Pump 2.44% 1

Drain Device 4.88% 2

Fire Dep't Connection Hose 2.44% 1

Fire Pump Gauge Pump 4.88% 2

Gauge Device 19.51% 8

Inspector's Test Valve 4.88% 2

Jockey Controller Pump 2.44% 1

Jockey Pump Pump 2.44% 1

Pump Pump 2.44% 1

Special Sprinkler Sprinkler 2.44% 1

Sprinkler Box Sprinkler 2.44% 1

Sprinkler Box Spares Sprinkler 7.32% 3

Tamper Switch Alarm 4.88% 2

Waterflow Switch Alarm 4.88% 2

Device Type

Qt y Model # Type Description Install Date

In Service - 2 Years to 3 Years

Gauge 4

05/22/2023

Gauge 4 35-W1005P System Pressure

05/22/2023

In Service - 5 Years to 10 Years

Special Sprinkler 1

01/29/2019

In Service - 15 Years to 25 Years

Fire Dep't Connection 1

Wall

06/24/2010

Inspector's Test 2

Sprinkler Box 1

Tamper Switch 1 OSY2 Control Valve Supervisory 06/24/2010

Jockey Pump 1 1303007 150 Automatic

Jockey Controller 1

Tamper Switch 1 OSY2 Control Valve Supervisory 06/24/2010

Waterflow Switch 2 WFD25 Vane Alarm 06/24/2010

Controller 1 C3B154-4TE4

Automatic 06/24/2010

Pump 1 284TS Pump Primary

Control Valve 1 705W Butterfly Discharge 06/24/2010

ARK Systems, Inc. 17 Download Date: 07/09/2025

Control Valve 2 705W Butterfly Isolation 06/24/2010

Control Valve 1 705W Butterfly TEST HEADER 06/24/2010

Sprinkler Box Spares 1 M Horizontal Sidewall

Sprinkler Box Spares 1 M Pendant

Sprinkler Box Spares 1 VK300 Upright

Alarm Valve 1 S/751 Grooved

06/24/2001

In Service - 25 Years or Older

Fire Pump Gauge 1

Discharge

06/24/2000

Fire Pump Gauge 1

Suction

Backflow Prevention 1 2000 SE

Control Valve 1 BF 1 Gate Main Control 06/24/2000

Control Valve 1 BF 2 Gate Main Control 06/24/2000

Check Valve 1 S/717 Flanged by Grooved

Wet Pipe, (domestic)

Backflow Prevention 1 375 Reduced Pressure

Control Valve 1

OS&Y Discharge 06/24/1998

Control Valve 1

OS&Y Suction 06/24/1998

Alarm Valve 1 S/751 Grooved

06/24/1998

Drain 2

Main

06/24/1998

ARK Systems, Inc. 18 Download Date: 07/09/2025

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.

Address Device Type Location Type ScanID

Control Panel 1 Zone/Address: 2

25 Waterflow Switch 1st pump room#110 system 1 tank bldg Vane 11667783 26 Waterflow Switch 1st pump room#110 system 2 lab bldg Vane 11667784 32 Control Valve 1st pump room #110 fire pump discharge Butterfly 11668480 34 Control Valve 1st pump room#110 system 2 lab bldg Butterfly 11668478 36 Control Valve 1st pump room#110 system 1 tank bldg Butterfly 11667782 39 Tamper Switch 1st pump room #110 backflow 2 Control Valve 11668477 40 Tamper Switch 1st pump room #110 backflow 1 Control Valve 11667700

File details come from the government source that posted it. Updated .