This is a Sprinkler Inspection Certificate documenting the annual inspection of the fire suppression systems at the US Department of Agriculture NCCCWA facility located at 11861 Leetown Road, Kearneysille, WV 25430. The inspection was conducted by ARK Systems, Inc. on July 7, 2025, in accordance with NFPA 25 Standards. The facility operates two wet pipe fire sprinkler systems protecting 40 devices total: one primary wet pipe system with 39 devices and one domestic wet pipe system with one device. The inspection achieved an overall pass rate of 82.93%, with 34 of 41 items passing inspection and 7 items identified as failed or requiring attention.
The discrepancies identified include defective or unlocked control valves in the 1st pump room (#110), defective fire pump gauges, a defective test header with a damaged/worn gauge, and a pump requiring maintenance. Specific findings note that two OS&Y control valves (suction and discharge) are unsecured and require correction, the test header control valve requires replacement (Model 705W), both fire pump gauges require replacement, and the main pump requires maintenance due to a hole in test header piping (4" steel schedule 10, 18-1/4" length) and a defective casing relief valve. All proposed repairs are available on a time and materials basis. The facility's fire suppression infrastructure includes fire pumps, jockey pumps, alarm valves, backflow prevention devices, and various monitoring switches, with most major components installed between 1998 and 2010.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection Certificate For
US Dept of Agriculture NCCCWA 11861 Leetown Road Kearneysille, WV 25430
This Inspection was performed in accordance with applicable NFPA 25 Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Date Jul 7, 2025
Building: US Dept of Agriculture NCCCWA Company: ARK Systems, Inc.
Contact: Dennis Bennett Contact: Charles Everett Title: Facility Manager Title: Service Manager
ARK Systems, Inc. 1 Download Date: 07/09/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: US Dept of Agriculture NCCCWA Contact: Dennis Bennett
Address: 11861 Leetown Road Phone: 304-261-6235
Address: Fax:
City/State/ZIP Code: Kearneysille, WV 25430 Mobile:
Country: United States of America Email: Dennis.Bennett@usda.gov
Inspection Performed By Company: ARK Systems, Inc. Inspector: Troy Myers
Address: 9176 Red Branch Road Phone: 410-995-1220
Address: Fax:
City/State/ZIP Code: Columbia, Maryland 21045 Mobile:
Country: United States of America Email: tmyers@arksysinc.com
System Control Unit System Type System Location Protected Area Devices Wet Pipe 39 Wet Pipe (domestic) 1
ARK Systems, Inc. 2 Download Date: 07/09/2025
Inspection Summary Category Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty % Alarm 4 9.76% 4 100.00% 4 100.00% 0 0.00% Device 10 24.39% 10 100.00% 9 90.00% 1 10.00% Hose 1 2.44% 1 100.00% 1 100.00% 0 0.00% Pump 6 14.63% 6 100.00% 3 50.00% 3 50.00% Sprinkler 5 12.20% 5 100.00% 5 100.00% 0 0.00% Valve 15 36.59% 15 100.00% 12 80.00% 3 20.00%
Totals 41 100% 41 100.00
34 82.93% 7 17.07%
Certification
Company: ARK Systems, Inc. Building: US Dept of Agriculture NCCCWA
Inspector: Troy Myers Contact: Dennis Bennett
ARK Systems, Inc. 3 Download Date: 07/09/2025
Discrepancy Report
Building: US Dept of Agriculture NCCCWA The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade No items found during this inspection.
ScanID Location Problem Reference
Wet Pipe Control Valve
55165030 1st pump room #110 Unlocked/Unsealed NFPA25 13.3.2.2 (2) 55165032 1st pump room #110 Unlocked/Unsealed NFPA25 13.3.2.2 (2) 11668479 1st pump room #110 test header Defective NFPA25 4.1.5.1
Fire Pump Gauge 55165026 1st pump room #110 Defective NFPA25 8.4.1 55165027 1st pump room #110 Defective NFPA25 8.4.1
Gauge 55165038 1st pump room #110 Damaged/Worn NFPA25 4.1.5.1
Pump 11667705 1st pump room #110 Requires Maintenance NFPA25 8.5.1
ARK Systems, Inc. 4 Download Date: 07/09/2025
Proposed Solutions Report
Building: US Dept of Agriculture NCCCWA
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Control Valve
55165030 1st pump room #110 Correct
T/M
55165032 1st pump room #110 Correct
11668479 1st pump room #110 test header Replace 705W T/M
Fire Pump Gauge
55165026 1st pump room #110 Replace
55165027 1st pump room #110 Replace
Gauge
55165038 1st pump room #110 Replace
Pump
11667705 1st pump room #110 See Notes/Recommenda tions
284TS T/M
Customer WO/PO #:
(none)
Internal WO/PO #: (none)
ARK Systems, Inc. 5 Download Date: 07/09/2025
Notes & Recommendations
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.
Note Device Type Location Comment ScanID
Wet Pipe 1 Control Valve 1st pump room #110 test header Defective 11668479
It’s a 5” take out for the 4” control valve 2 Pump 1st pump room #110 Requires
Maintenance 11667705
Test header piping has hole in pipe steel schedule 10 (4”) length is 18-1/4” The casing relief valve is bad and needs to be replaced
ARK Systems, Inc. 6 Download Date: 07/09/2025
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed Special Sprinkler Annual 10:26:16 AM 07/07/2025
Wet Pipe Tamper Switch 1st pump room #110 backflow 1 Annual 10:07:17 AM 07/07/2025 Tamper Switch 1st pump room #110 backflow 2 Annual 10:08:28 AM 07/07/2025 Waterflow Switch 1st pump room#110 system 2 lab bldg Annual 1:10:28 PM 07/07/2025 Waterflow Switch 1st pump room#110 system 1 tank bldg Annual 1:10:32 PM 07/07/2025 Drain 1st pump room #110 Annual 10:36:08 AM 07/07/2025 Drain 1st pump room #110 Annual 10:36:11 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:12:36 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:12:40 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:14:13 AM 07/07/2025 Gauge 1st Inside Pump Room Annual 10:14:17 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:18:39 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:18:48 AM 07/07/2025 Gauge 1st pump room #110 Annual 10:19:49 AM 07/07/2025 Fire Dep't Connection 1st pump room #110 Annual 10:25:58 AM 07/07/2025 Controller 1st pump room #110 Annual 10:36:31 AM 07/07/2025 Jockey Controller 1st pump room #110 Annual 10:18:57 AM 07/07/2025 Jockey Pump 1st pump room #110 Annual 10:19:07 AM 07/07/2025 Sprinkler Box 1st pump room #110 Annual 10:25:55 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:10 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:11 AM 07/07/2025 Sprinkler Box Spares 1st pump room 110 Annual 10:26:13 AM 07/07/2025 Alarm Valve 1st pump room #110 Annual 10:13:25 AM 07/07/2025 Alarm Valve 1st pump room #110 Annual 10:14:04 AM 07/07/2025 Backflow Prevention 1st pump room #110 Annual 1:10:11 PM 07/07/2025 Check Valve 1st pump room #110 Annual 10:19:26 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:09:24 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:09:32 AM 07/07/2025 Control Valve 1st pump room#110 system 2 lab bldg Annual 10:11:16 AM 07/07/2025 Control Valve 1st pump room#110 system 1 tank bldg Annual 10:11:57 AM 07/07/2025 Control Valve 1st pump room #110 fire pump discharge Annual 10:15:18 AM 07/07/2025 Inspector's Test 1st Inside Loading Dock Area Annual 12:57:32 PM 07/07/2025 Inspector's Test 1st Inside Wet Lab Area Annual 1:05:09 PM 07/07/2025
Wet Pipe, (domestic) Backflow Prevention 1st pump room #110 Annual 1:10:18 PM 07/07/2025
Failed/Other
ARK Systems, Inc. 7 Download Date: 07/09/2025
Device Type Location Service Time Date Gauge 1st pump room #110 Annual 10:35:14 AM 07/07/2025 Fire Pump Gauge 1st pump room #110 Annual 10:17:07 AM 07/07/2025 Fire Pump Gauge 1st pump room #110 Annual 10:18:02 AM 07/07/2025 Pump 1st pump room #110 Annual 10:34:56 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:15:50 AM 07/07/2025 Control Valve 1st pump room #110 Annual 10:16:30 AM 07/07/2025 Control Valve 1st pump room #110 test header Annual 10:22:04 AM 07/07/2025
ARK Systems, Inc. 8 Download Date: 07/09/2025
Wet Pipe Fire Sprinkler Systems
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Controller
Manufacturer Model # Description Location OK ScanID US Electrical Motors
C3B154-4TE4 Automatic 1st pump room #110 15037111
Serial # AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup 208881 Phase Reversal n/a 100 115 No Yes
Fire Pump Gauge
Location Type Discharge psi Suction psi OK ScanID 1st pump room #110 Suction 40 40 55165026
1st pump room #110 Discharge 40 40 55165027
Jockey Controller
Manufacturer Model # Location Install Date OK ScanID Joslyn Clark 1st pump room #110 06/24/2010 55165039
AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 100 115 No Yes
Jockey Pump
Manufacturer Model # Location Install Date OK ScanID Franklin electric 1303007 150 1st pump room #110 06/24/2010 55165040
Serial # Type Horsepower Rated Speed Volts Amps On psi Off psi Automatic 100 115
Pump
Manufacturer Model # Location Install Date OK ScanID US Electrical Motors
284TS 1st pump room #110 06/24/2010 11667705
Type Orientation Aligned? Water Supply Impeller Size Startup Pump Primary Horizontal 6.750
Serial # D09 01059351-004R
Fire Pump Rating
Amps Volts
Net Pressure Gallons Per Minute
Rotations Per Minute A B C A-B B-C A-C
75.6 0 3560
75.6 0 3560
ARK Systems, Inc. 9 Download Date: 07/09/2025
85 0
65 500 3560
65 500
43.5 750 3530
43.5 750
Alarms Tamper Switch
Type Description Location # of Turns Zone/Address OK ScanID Control Valve Supervisory 1st pump room #110 backflow
1-2 40 11667700
Control Valve Supervisory 1st pump room #110 backflow
1-2 39 11668477
Waterflow Switch
Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD25 35.580
00183 10547
2.5” 1-2 26 11667784
Vane System Sensor WFD25 29.520 00045 77637
2.5” 1-2 25 11667783
Components
ARK Systems, Inc. 10 Download Date: 07/09/2025
Alarm Valve
Type Location Manufacturer Model # OK ScanID Grooved 1st pump room #110 Victaulic S/751 55165034
Position Status Size Internal Date 2.5" 08/01/2023
Alarm Valve
Type Location Manufacturer Model # OK ScanID Grooved 1st pump room #110 Victaulic S/751 55165036
Position Status Size Internal Date 2.5" 08/01/2023
Backflow Prevention
Manufacturer Model # Size Type Service Type Install Date OK ScanID Ames 2000 SE 6" 06/24/2000 55165024
Water Purveyor Location Meter Acct. # Serial # 1st pump room #110
Initial Test
Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker Held At
Repairs or Notes
Final Test
Condition of Control Valve 1 Condition of Control Valve 2
Check Valve
Type Location Manufacturer Model # Internal Date Size OK ScanID Flanged by Grooved
1st pump room #110 Victaulic S/717 08/01/2023 4" 55165031
Control Valve
Type Location Manufacturer Model # OK ScanID Gate 1st pump room #110 Kennedy BF 2 55165023
Position Size Status Description Open 6" Supervised Main Control
Control Valve
Type Location Manufacturer Model # OK ScanID Gate 1st pump room #110 Kennedy BF 1 55165025
Position Size Status Description Open 6" Supervised Main Control
Control Valve
Type Location Manufacturer Model # OK ScanID
ARK Systems, Inc. 11 Download Date: 07/09/2025
Butterfly 1st pump room#110 system 2 lab bldg
Victaulic 705W 11668478
Position Size Status Description Open 2.5" Supervised Isolation
Control Valve
Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room#110 system 1 tank bldg Victaulic 705W 11667782
Position Size Status Description Open 2.5" Supervised Isolation
Control Valve
Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room #110 fire pump discharge Victaulic 705W 11668480
Position Size Status Description Open 4" Supervised Discharge
Control Valve
Type Location Manufacturer Model # OK ScanID OS&Y 1st pump room #110 NIBCO 55165032
Position Size Status Description Open 1" Unsecured Discharge
Control Valve
Type Location Manufacturer Model # OK ScanID OS&Y 1st pump room #110 NIBCO 55165030
Position Size Status Description Open 1" Unsecured Suction
Control Valve
Type Location Manufacturer Model # OK ScanID Butterfly 1st pump room #110 test header Victaulic 705W 11668479
Position Size Status Description Closed 4" Supervised TEST HEADER
Inspector's Test
Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID 78560063
Location 1st Inside Loading Dock Area
Inspector's Test
Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID 41190382
Location 1st Inside Wet Lab Area
ARK Systems, Inc. 12 Download Date: 07/09/2025
Devices Drain
Current Inspection
Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 150 155 140 55165035
Previous Inspections
September 12, 2024
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 120 120 105 3 55165035
May 22, 2023
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 110 120 100 5 55165035
Current Inspection
Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 158 155 140 55165033
Previous Inspections
September 12, 2024
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 120 120 105 3 55165033
May 22, 2023
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st pump room #110 1.25" 110 120 100 5 55165033
Fire Dep't Connection
Location Type Size Qty BallDrip Rotating Swivels 5-Year Hydro OK ScanID 1st pump room #110 Wall 2.5" 12/13/1901 11667704
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/2 15037113
Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037112
Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037115
Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 300
Gauge
ARK Systems, Inc. 13 Download Date: 07/09/2025
Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Victaulic 35-W1005P 1/4 15037114
Location Service Date Static psi Min. Range Max. Range 1st Inside Pump Room 05/22/2028 0 .300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165028
Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165037
Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165029
Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300
Gauge
Type Manufacturer Model # Size Fill Type OK ScanID 1/4 55165038
Location Service Date Static psi Min. Range Max. Range 1st pump room #110 05/22/2028 0 300
Sprinkler Box
Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID 11 Yes 12 unit 1st pump room #110 11667701
Sprinkler Box Spares
Qty Type Location Manufacturer OK ScanID 5 Upright 1st pump room 110 Viking 55165022
Temperature KFactor Size Response Time Finish 155 Fast Response Chrome
Sprinkler Box Spares
Qty Type Location Manufacturer OK ScanID 2 Horizontal Sidewall 1st pump room 110 Viking 11668444
Temperature KFactor Size Response Time Finish 155 Fast Response Chrome
Sprinkler Box Spares
Qty Type Location Manufacturer OK ScanID 4 Pendant 1st pump room 110 Viking 55165021
Temperature KFactor Size Response Time Finish
ARK Systems, Inc. 14 Download Date: 07/09/2025
155 Standard Response Chrome
ARK Systems, Inc. 15 Download Date: 07/09/2025
Building: US Dept of Agriculture NCCCWA (domestic)
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Components Backflow Prevention
Manufacturer Model # Size Type Service Type Install Date OK ScanID Wilkins 375 4" Reduced Pressure domestic 06/24/2000 45382437
Water Purveyor Location Meter Acct. # Serial # n/a 1st pump room #110 n/a
Initial Test
Repairs or Notes
Final Test
Condition of Control Valve 1 Condition of Control Valve 2 Closed Tight Closed Tight
ARK Systems, Inc. 16 Download Date: 07/09/2025
Inventory & Warranty Report
Building: US Dept of Agriculture NCCCWA
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Alarm Valve Valve 4.88% 2
Backflow Prevention Valve 4.88% 2
Check Valve Valve 2.44% 1
Control Valve Valve 19.51% 8
Controller Pump 2.44% 1
Drain Device 4.88% 2
Fire Dep't Connection Hose 2.44% 1
Fire Pump Gauge Pump 4.88% 2
Gauge Device 19.51% 8
Inspector's Test Valve 4.88% 2
Jockey Controller Pump 2.44% 1
Jockey Pump Pump 2.44% 1
Pump Pump 2.44% 1
Special Sprinkler Sprinkler 2.44% 1
Sprinkler Box Sprinkler 2.44% 1
Sprinkler Box Spares Sprinkler 7.32% 3
Tamper Switch Alarm 4.88% 2
Waterflow Switch Alarm 4.88% 2
Device Type
Qt y Model # Type Description Install Date
In Service - 2 Years to 3 Years
Gauge 4
05/22/2023
Gauge 4 35-W1005P System Pressure
05/22/2023
In Service - 5 Years to 10 Years
Special Sprinkler 1
01/29/2019
In Service - 15 Years to 25 Years
Fire Dep't Connection 1
Wall
06/24/2010
Inspector's Test 2
Sprinkler Box 1
Tamper Switch 1 OSY2 Control Valve Supervisory 06/24/2010
Jockey Pump 1 1303007 150 Automatic
Jockey Controller 1
Tamper Switch 1 OSY2 Control Valve Supervisory 06/24/2010
Waterflow Switch 2 WFD25 Vane Alarm 06/24/2010
Controller 1 C3B154-4TE4
Automatic 06/24/2010
Pump 1 284TS Pump Primary
Control Valve 1 705W Butterfly Discharge 06/24/2010
ARK Systems, Inc. 17 Download Date: 07/09/2025
Control Valve 2 705W Butterfly Isolation 06/24/2010
Control Valve 1 705W Butterfly TEST HEADER 06/24/2010
Sprinkler Box Spares 1 M Horizontal Sidewall
Sprinkler Box Spares 1 M Pendant
Sprinkler Box Spares 1 VK300 Upright
Alarm Valve 1 S/751 Grooved
06/24/2001
In Service - 25 Years or Older
Fire Pump Gauge 1
Discharge
06/24/2000
Fire Pump Gauge 1
Suction
Backflow Prevention 1 2000 SE
Control Valve 1 BF 1 Gate Main Control 06/24/2000
Control Valve 1 BF 2 Gate Main Control 06/24/2000
Check Valve 1 S/717 Flanged by Grooved
Wet Pipe, (domestic)
Backflow Prevention 1 375 Reduced Pressure
Control Valve 1
OS&Y Discharge 06/24/1998
Control Valve 1
OS&Y Suction 06/24/1998
Alarm Valve 1 S/751 Grooved
06/24/1998
Drain 2
Main
06/24/1998
ARK Systems, Inc. 18 Download Date: 07/09/2025
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.
Address Device Type Location Type ScanID
Control Panel 1 Zone/Address: 2
25 Waterflow Switch 1st pump room#110 system 1 tank bldg Vane 11667783 26 Waterflow Switch 1st pump room#110 system 2 lab bldg Vane 11667784 32 Control Valve 1st pump room #110 fire pump discharge Butterfly 11668480 34 Control Valve 1st pump room#110 system 2 lab bldg Butterfly 11668478 36 Control Valve 1st pump room#110 system 1 tank bldg Butterfly 11667782 39 Tamper Switch 1st pump room #110 backflow 2 Control Valve 11668477 40 Tamper Switch 1st pump room #110 backflow 1 Control Valve 11667700
File details come from the government source that posted it. Updated .