Annual Fire Alarm and Life Safety System Inspection Report.pdf

PDF 788 KB Posted

Attached to
NCCCWA Fire System Upgrades, Kearneysville, WV
Solicitation number
1232SA26Q0485
Issued by

About this file

This is an Annual Fire Alarm and Life Safety System Inspection Report for the US Department of Agriculture's National Center for Cool and Cold Water Aquaculture (NCCCWA) facility located in Kearneysville, West Virginia. The inspection was conducted by ARK Systems, Inc. on July 7, 2025, in accordance with NFPA 72 Standards.

The inspection covered two control panels with a total of 42 devices across four categories: Auxiliary (6 items), Control (8 items), Indicating (2 items), and Initiating (26 items). Overall results show 40 devices serviced with 37 passing (92.5%) and 3 failing (7.5%). The primary control unit is a Cerberus MXL-IQ system installed on June 24, 2010, located in the Facilities Manager's office (Room 24). Three discrepancies were identified: one Horn/Strobe device on the first floor failed testing due to being out of sync, and two Duct Detectors in the second-floor mechanical rooms above the loading dock (for AHU-1 and AHU-2 supply lines) were damaged and worn with moisture accumulation and stripped screw covers. All three items are proposed for correction on a Time and Materials basis using model FP-11 components. Two additional Fan Shutdown devices for the AHU-1 and AHU-2 supply lines could not be tested due to ducts being in trouble. Battery and power supply testing passed for all units, including sealed lead acid batteries rated at 7-26 amp-hours and 12 volts across both control panels.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Annual Fire Alarm and Life Safety System

Inspection Report For

US Dept of Agriculture NCCCWA 11861 Leetown Road Kearneysille, WV 25430

This Inspection was performed in accordance with applicable NFPA 72 Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Date Jul 7, 2025

Building: US Dept of Agriculture NCCCWA Company: ARK Systems, Inc.

Contact: Dennis Bennett Contact: Charles Everett Title: Facility Manager Title: Service Manager

ARK Systems, Inc. 1 Download Date: 07/09/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: US Dept of Agriculture NCCCWA Contact: Dennis Bennett

Address: 11861 Leetown Road Phone: 304-261-6235

Address: Fax:

City/State/ZIP Code: Kearneysille, WV 25430 Mobile:

Country: United States of America Email: Dennis.Bennett@usda.gov

Inspection Performed By Company: ARK Systems, Inc. Inspector: Troy Myers

Address: 9176 Red Branch Road Phone: 410-995-1220

Address: Fax:

City/State/ZIP Code: Columbia, Maryland 21045 Mobile:

Country: United States of America Email: tmyers@arksysinc.com

System Control Unit Manufacturer: Cerberus Inspection Date: 07/07/2025 IDC Style:

Model Number: MXL-IQ Install Date: 06/24/2010 SLC Style:

Software Version: Version Date: 06/24/2010 NAC Style:

Location: 1st Facilities manager office room 24 Current Protection: Breaker

Central Station Signal Verification

Type: Mfg: Radionics Model #: D9412

Test Time/Date: 7/7/25 10:48:18 AM Restore Time: Note:

ARK Systems, Inc. 2 Download Date: 07/09/2025

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Auxiliary 6 14.29% 4 66.67% 4 100.00% 0 0.00% Control 8 19.05% 8 100.00% 8 100.00% 0 0.00% Indicating 2 4.76% 2 100.00% 1 50.00% 1 50.00% Initiating 26 61.90% 26 100.00% 24 92.31% 2 7.69%

Totals 42 100% 40 95.24% 37 92.50% 3 7.50%

Certification

Company: ARK Systems, Inc. Building: US Dept of Agriculture NCCCWA

Inspector: Troy Myers Contact: Dennis Bennett

ARK Systems, Inc. 3 Download Date: 07/09/2025

Discrepancy Report

Building: US Dept of Agriculture NCCCWA Control Panel: 1 - Cerberus

MXL-IQ

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Address Reference

Indicating Horn/Strobe

15036367 1st Failed Test 1 NFPA 72 Table 10.4.2.2.14(a)

Initiating Duct Detector

15036392 2nd Mechanical room above loading dock AHU-1 supply

Damaged/Worn 1-21 NFPA 72 10.2.1.2

15036395 2nd Mechanical room above loading dock AHU-2 supply

Damaged/Worn 1-23 NFPA 72 10.2.1.2

ARK Systems, Inc. 4 Download Date: 07/09/2025

Proposed Solutions Report

Building: US Dept of Agriculture

NCCCWA

Control Panel: 1 - Cerberus MXL-IQ

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Indicating

Horn/Strobe

15036367 1st Correct

T/M

Initiating

Duct Detector

15036392 2nd Mechanical room above loading dock AHU-1 supply

Correct FP-11 T/M

15036395 2nd Mechanical room above loading dock

Correct FP-11 T/M

Customer WO/PO #:

(none)

Internal WO/PO #: (none)

T/M

ARK Systems, Inc. 5 Download Date: 07/09/2025

Notes & Recommendations

Building: US Dept of Agriculture NCCCWA Control Panel: 1 - Cerberus MXL-IQ

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Auxiliary 15036253 1 Fan Shutdown 2nd Mechanical room above loading dock

AHU-1 supply

Unable to test due to duct being in trouble 15036250 2 Fan Shutdown 2nd Mechanical room above loading dock

Unable to test due to duct being in trouble

Indicating 15036367 3 Horn/Strobe 1st Failed Test

Out of sync

Initiating 15036392 4 Duct Detector 2nd Mechanical room above loading dock

AHU-1 supply Damaged/Worn

Duct detector is full of moisture Came to panel as a trouble Screws are stripped out of cover

15036395 5 Duct Detector 2nd Mechanical room above loading dock AHU-2 supply

Damaged/Worn

Duct detector is full of moisture Came to panel as a trouble Screws are stripped out of cover

ARK Systems, Inc. 6 Download Date: 07/09/2025

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Auxiliary

Fan Shutdown 2nd Mechanical room above Aqua area AHU-3 Return

Annual 10:00:59 AM 07/07/2025

Fan Shutdown 2nd Mechanical room above Aqua area AHU-3 supply

Annual 10:02:58 AM 07/07/2025

Fan Shutdown 2nd Mechanical room above loading dock AHU-1 return

Annual 1:39:14 PM 07/07/2025

Fan Shutdown 2nd Mechanical room above loading dock AHU-2 return

Annual 1:39:33 PM 07/07/2025

Control Battery 1st Facilities manager office room 24 inside booster panel Annual 10:52:54 AM 07/07/2025

Battery 1st Facilities manager office room 24 inside booster panel

Annual 10:52:55 AM 07/07/2025

Control Panel 1st Facilities manager office room 24 Annual 8:44:01 AM 07/07/2025 Power Supply 1st Facilities manager office room 24 Annual 10:52:57 AM 07/07/2025

Indicating Horn/Strobe 2nd Annual 11:19:42 AM 07/07/2025

Initiating Duct Detector 2nd Mechanical room above Aqua area AHU-1 return Annual 10:02:49 AM 07/07/2025

Duct Detector 2nd Mechanical room above Aqua area AHU-2 Return

Annual 10:01:29 AM 07/07/2025

Pull Station 1st Exit by loading dock Annual 8:16:10 AM 07/07/2025 Pull Station 1st Exit by main lobby Annual 8:27:19 AM 07/07/2025 Pull Station 1st Exit by room 09 Annual 8:28:32 AM 07/07/2025 Pull Station 1st Exit by room 101 Annual 8:20:42 AM 07/07/2025 Pull Station 1st Exit by room 104 Annual 8:21:24 AM 07/07/2025 Pull Station 1st Exit by room 105 Annual 8:22:57 AM 07/07/2025 Pull Station 1st Exit by room 107 Annual 8:22:03 AM 07/07/2025 Pull Station 1st Exit by room 16 Annual 8:29:32 AM 07/07/2025 Pull Station 1st Exit by room 30 Annual 8:17:13 AM 07/07/2025 Pull Station 1st Exit by room 34 Annual 8:25:26 AM 07/07/2025 Pull Station 1st Exit by room 42 Annual 8:25:35 AM 07/07/2025 Pull Station 1st Exit by room 46 Annual 8:26:16 AM 07/07/2025 Pull Station 1st Exit in 2nd flr mechanical rm front Annual 8:38:55 AM 07/07/2025 Pull Station 1st Exit in 2nd flr mechanical rm rear Annual 8:40:16 AM 07/07/2025 Pull Station 1st Exit in room 101 Annual 8:19:21 AM 07/07/2025

ARK Systems, Inc. 7 Download Date: 07/09/2025

Pull Station 1st Exit in room 101 at double doors Annual 8:19:59 AM 07/07/2025 Pull Station 1st Exit in room 30 Annual 8:17:49 AM 07/07/2025 Pull Station 1st Inside Process Water Mechanical Room Annual 8:37:38 AM 07/07/2025 Pull Station 2nd Mechanical room above loading dock Annual 8:34:27 AM 07/07/2025 Pull Station 2nd Mechanical room above loading dock Annual 8:35:08 AM 07/07/2025 Pull Station 2nd Mechanical room above office area Annual 8:31:39 AM 07/07/2025 Pull Station 2nd Mechanical room above office area Annual 8:32:05 AM 07/07/2025

Failed/Other Indicating

Horn/Strobe 1st Annual 11:19:57 AM 07/07/2025

Initiating Duct Detector 2nd Mechanical room above loading dock

AHU-1 supply Annual 9:45:41 AM 07/07/2025

Duct Detector 2nd Mechanical room above loading dock

Annual 9:46:09 AM 07/07/2025

Untested Auxiliary

Fan Shutdown 2nd Mechanical room above loading dock

Fan Shutdown 2nd Mechanical room above loading dock

ARK Systems, Inc. 8 Download Date: 07/09/2025

Building: US Dept of Agriculture NCCCWA Control Panel: 2

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Control

Battery 1st Facilities manager office room 24 inside FACP E001 key

Annual 11:06:26 AM 07/07/2025

Battery 1st Facilities manager office room 24 inside FACP E001 key

Annual 11:06:27 AM 07/07/2025

Battery 1st Facilities manager office room 24 inside communicator

Annual 10:48:20 AM 07/07/2025

Communicator 1st Facilities manager office room 24 Annual 10:48:18 AM 07/07/2025

ARK Systems, Inc. 9 Download Date: 07/09/2025

Auxiliary Functions Testing

NCCCWA

Control Panel: 1 - Cerberus MXL-IQ

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Fan Shutdown

2nd Mechanical room above Aqua area AHU-3 Return

Passed 15036399

2nd Mechanical room above Aqua area AHU-3 supply

Passed 15036397

Return 2nd Mechanical room above loading dock AHU-1 return

Passed 15036252

2nd Mechanical room above loading dock AHU-2 return

Passed 15036251

Untested

Fan Shutdown

Supply 2nd Mechanical room above loading dock

15036253

Supply 2nd Mechanical room above loading dock

15036250

ARK Systems, Inc. 10 Download Date: 07/09/2025

Smoke Management Testing

The Smoke Management Testing section details the test and inspection of device items that are involved in controlling the spread of smoke in a building. Items are grouped by Passed or Failed/ Other.

Location Description Comment ScanID Simulated

Passed Fan Shutdown

2nd Mechanical room above Aqua area AHU-3 Return

Passed 15036399

2nd Mechanical room above Aqua area AHU-3 supply

Passed 15036397

2nd Mechanical room above loading dock AHU-1 return

Return Passed 15036252

2nd Mechanical room above loading dock AHU-2 return

Passed 15036251

Untested Fan Shutdown

2nd Mechanical room above loading dock AHU-1 supply

Supply 15036253

2nd Mechanical room above loading dock

Supply 15036250

ARK Systems, Inc. 11 Download Date: 07/09/2025

Battery & Power Supply Testing

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated Ah

Rated Volts

Pre Test

Post Test

Min Ah

Tested Ah

Passed Sealed Lead Acid 1st Facilities manager office room 24 inside booster panel 7 12

Sealed Lead Acid 1st Facilities manager office room 24 inside booster panel

7 12

Power Supply Protection Type Location Rated Ah Rated Volts Charging Voltage

Passed Breaker 1st Facilities manager office room 24 7 12

Building: US Dept of Agriculture NCCCWA Control Panel: 2

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated Ah

Rated Volts

Pre Test

Post Test

Min Ah

Tested Ah

Passed Sealed Lead Acid 1st Facilities manager office room 24 inside FACP E001 key 26 12

Sealed Lead Acid 1st Facilities manager office room 24 inside FACP E001 key

26 12

Sealed Lead Acid 1st Facilities manager office room 24 inside communicator

9 12

ARK Systems, Inc. 12 Download Date: 07/09/2025

Inventory & Warranty Report

Building: US Dept of Agriculture

NCCCWA

Control Panel: 1 - Cerberus MXL-IQ

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Battery Control 11.90% 5

Communicator Control 2.38% 1

Control Panel Control 2.38% 1

Duct Detector Initiating 9.52% 4

Fan Shutdown Auxiliary 14.29% 6

Horn/Strobe Indicating 4.76% 2

Power Supply Control 2.38% 1

Pull Station Initiating 52.38% 22

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years

Battery Mart

Battery 1 LP12-7.0 Sealed Lead Acid 05/22/2023

Power Sonic

Battery 1 LP12-7.0 Sealed Lead Acid 05/22/2023

In Service - 15 Years to 25 Years

Cerberus

Control Panel 1 MXL-IQ

06/24/2010

Duct Detector 1 FP-11

Duct Detector 3 FP-11 Photoelectric 06/24/2010

Fan Shutdown 3 FP-11

Fan Shutdown 1 FP-11 Return 06/24/2010

Fan Shutdown 2 FP-11 Supply 06/24/2010

Pull Station 22 MSI-10B Dual Action 06/24/2010

Siemens

Power Supply 1 PAD-2

Wheelock

Horn/Strobe 2

NCCCWA

Control Panel: 2

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years

ARK Systems, Inc. 13 Download Date: 07/09/2025

Ritar

Battery 1 RT12260 Sealed Lead Acid 05/22/2023

Universal Battery

Battery 1 UB12260 Sealed Lead Acid 05/22/2023

Battery 1 UB1290K Sealed Lead Acid 05/22/2023

In Service - 15 Years to 25 Years

Radionics

Communicator 1 D9412

ARK Systems, Inc. 14 Download Date: 07/09/2025

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Zone/Circuit: 2 52 Pull Station 1st Exit in 2nd flr mechanical rm front Dual Action 15036382 53 Pull Station 1st Exit in 2nd flr mechanical rm rear Dual Action 15036381 54 Pull Station 1st Exit by room 107 Dual Action 15036383 55 Pull Station 1st Exit by room 105 Dual Action 15036384 57 Pull Station 1st Exit by room 101 Dual Action 15036379 58 Pull Station 1st Inside Process Water Mechanical

Room Dual Action 15037116

59 Pull Station 1st Exit in room 101 Dual Action 15036385 21 Duct Detector 2nd Mechanical room above Aqua area

AHU-1 return Photoelectric 15036396

21 Fan Shutdown 2nd Mechanical room above Aqua area AHU-3 supply

15036397

21 Duct Detector 2nd Mechanical room above loading dock AHU-1 supply

Photoelectric 15036392

21 Fan Shutdown 2nd Mechanical room above loading dock AHU-1 supply

Supply 15036253

22 Duct Detector 2nd Mechanical room above Aqua area AHU-2 Return

15036398

22 Fan Shutdown 2nd Mechanical room above Aqua area AHU-3 Return

15036399

22 Fan Shutdown 2nd Mechanical room above loading dock AHU-1 return

Return 15036252

23 Duct Detector 2nd Mechanical room above loading dock AHU-2 supply

Photoelectric 15036395

23 Fan Shutdown 2nd Mechanical room above loading dock AHU-2 supply

Supply 15036250

24 Fan Shutdown 2nd Mechanical room above loading dock AHU-2 return

15036251

48 Pull Station 2nd Mechanical room above loading dock

Dual Action 15036390

49 Pull Station 2nd Mechanical room above loading dock

Dual Action 15036391

50 Pull Station 2nd Mechanical room above office area Dual Action 15036388 51 Pull Station 2nd Mechanical room above office area Dual Action 15036389 52 Pull Station 1st Exit by room 16 Dual Action 15036375 53 Pull Station 1st Exit by room 09 Dual Action 15036376 54 Pull Station 1st Exit by main lobby Dual Action 15036378 55 Pull Station 1st Exit by room 46 Dual Action 15036374 56 Pull Station 1st Exit by room 104 Dual Action 15036380

ARK Systems, Inc. 15 Download Date: 07/09/2025

56 Pull Station 1st Exit by room 42 Dual Action 15036401 57 Pull Station 1st Exit by room 30 Dual Action 15036372 58 Pull Station 1st Exit by room 34 Dual Action 15036373 59 Pull Station 1st Exit in room 30 Dual Action 15036387 60 Pull Station 1st Exit by loading dock Dual Action 15036377 60 Pull Station 1st Exit in room 101 at double doors Dual Action 15036386