This is Addendum #1 to a contract for Madison County, Illinois, related to the 800 MHz Digital Mobile Radio System Replacement project. The addendum provides technical specifications and engineering documentation for a 190-foot self-supporting vertical (SSV) tower installation at the primary Edwardsville, Illinois site. The attachments include an electrical site plan scaled at 1" = 30'-0" prepared by Kirk M. Meyer (Illinois Professional Engineer License 062-056289, valid through November 30, 2017), a tower analysis program output, and anchor bolt specifications for the foundation system.

The tower analysis was conducted using the TSTower v5.6.0 analysis program in accordance with ANSI/TIA-222-G-2005 design standards for Structure Class II in Exposure Category C. The design specification accounts for a basic wind speed of 90 mph without ice load and 40 mph with a 0.50-inch ice thickness. Maximum base reactions are documented as 219.6 kips download, 188.8 kips uplift, 21.6 kips shear, and 3,760.8 foot-kips overturning moment. The foundation requires six 1-inch diameter by 70-inch long anchor bolts (18 total). These technical specifications establish the structural requirements for integrating Motorola DMR trunked radio equipment at the tower site as part of the system replacement initiative.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum #1 Attachment #1

E.001

ELECTRICAL SITE PLAN

SCALE: 1" = 30'-0"

G R

A N

IT

E

C

IT

Y ,I

LL

IN

O

IS

KIRK M.

MEYER

062-056289

SIGNED: 1-29-2016

EXPIRES: 11-30-2017

Attachment #2

TSTower - v 5.6.0 Tower Analysis Program

(c) 1997-2015 TowerSoft www.TSTower.com

File : W:\Jobs\2016\219639\219639.out Contract: 219639 Project: 190 FT SSV TOWER Date and Time: 10/10/2016 10:01:14 AM

DESIGN SPECIFICATION

Design Standard: ANSI/TIA-222-G-2005 Add2 Basic Wind Speed (No Ice}= 90.0 {mph} V' Basic Wind Speed (With Ice} = 40.0 (mph} / Design Ice Thickness= 0.50 (in} Structure Class= II ,,- Exposure Category= C Topographic Category= 1

Set Length To) W. BotWtdth

(ft) (in (in)

1 20.00 226.18 250.32 2 20.00 20122 226.18 3 20.00 17724 201.22 4 20.00 152.17 17724 5 20.00 128.15 152.17 6 20.00 103.19 128.15 7 20.00 79.69 103.19 & 20.00 55.20 79.69 9 20.00 54.72 5520 10 10.00 54.72 54.72

MAXIMUM BASE REACTIONS

Download (Kips) Uplift (Kips) Shear (Kips) O.T.M. (Ft-Kips)

219.6 188.8 21 .6

3,760.8

Licensed to: ROHN Products LLC Peoria, IL

Revision : O Site: MADISON COUNTY ILLINOIS Engineer: AS~~

10.00

20.00

20.00

20.00

20.00

20.00

20.00

20.00

20.00

(6) 1" DIA. X 70" LONG ANCHOR BOLTS

(18 TOTAL)

Attachment #3

Attachment #4