Electrical Plans Summary

This is a set of electrical construction plans prepared by Pennoni Associates Inc. for the Perkasie Regional Authority (PRA) Well #7 Treatment Center project located in East Rockhill Township, Bucks County, Pennsylvania. The plans include comprehensive electrical design for a new treatment facility building, encompassing demolition of existing electrical systems and installation of new power distribution, lighting, control systems, and related infrastructure. The project scope involves a 480Y/277V three-phase service entrance with automatic transfer switch (ATS) rated at 200 amperes, a 30 kilovolt-ampere transformer stepping down to 208Y/120V for lighting and control panels, new panelboards (HP and LC), single-line diagrams, grounding systems, and conduit routing for both power and control circuits. The plans specify trenched PVC Schedule 40 conduit for underground utility connections from the existing generator to the new building, with three-inch conduits for primary power and two-inch conduits for auxiliary power and controls. The contract term is 180 consecutive calendar days from the Notice to Proceed, with temporary restoration required within 150 days and final restoration within 30 days thereafter. The bid deadline is August 31, 2026 at 1:00 PM EST, with a pre-bid meeting scheduled for August 12, 2026 at 10:00 AM. Bids remain binding for 60 days after closing.

The electrical plans comply with the 2020 National Electrical Code (NFPA 70), 2021 International Building Code, and 2021 Life Safety Code, and require all work to be performed by a licensed electrical contractor in strict accordance with manufacturer specifications and all applicable codes and standards. Feeder and branch circuit wiring shall be copper with 600-volt THHN insulation, with minimum conductor sizes of #12 AWG for branch circuits and #3/0 AWG for main service feeders as specified in the single-line diagrams and panel schedules. The project includes a concrete-encased grounding electrode system at the building foundation perimeter, bonding of structural steel columns, metal piping systems, and telecommunications room grounding bars, with all grounding connections sized per National Electrical Code Table 250.66 and 250.122. All dimensions and specifications shown on the drawings are subject to verification by the contractor and owner, with any discrepancies requiring notification prior to work commencement. The plans are diagrammatic in nature and indicate general system arrangement; the contractor is responsible for coordinating conduit routing with other trades, maintaining headroom, and allowing for overhead obstacles and variations in construction. Liquidated damages of $10,000 per calendar day apply for contract delays, and the contractor must submit performance bonds (100 percent of contract price), labor and materials bonds (100 percent), and maintenance bonds as required.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U:

\A cc ou nt s\P

ER

EA

\P

ER

EA

- W ell

T re at m en t C en te r (

PR

A2

5-

)\D

ES

IG

N\

_S

HE

ET

S\

E0

.d wg

PL

OT

TE

D:

/2 8/

:0

PM

, B Y:

H ale y Z ur its ky

ST

YL

E:

P en no ni

NC

S.

stb

E001

B Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF1 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATE; AND OWNER SHALL

INDEMNIFY AND HOLD HARMLESS PENNONI ASSOCIATES

FROM ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES

ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PREPARED FOR:

OWNER/DEVELOPER

PERKASIE REGIONAL AUTHORITY

150 RIDGE ROAD

SELLERSVILLE, PA 18960

WELL #7 PROPOSED ELECTRICAL PLANS

EAST ROCKHILL, BUCKS COUNTY, PA

LOCATION MAP

Scale: 1" = 800'

USGS MAP

Scale: 1" = 800'

SOILS MAP

Scale: 1" = 800'

N O

R

TH

N O

R

TH

N O

R

TH

CALL 1-800-242-1776

CALL BEFORE YOU DIG

BEFORE YOU DIG ANYWHERE IN PENNSYLVANIA

PA. ACT 287 OF 1974 REQUIRES THREE WORKING DAYS

NOTICE TO UTILITIES BEFORE YOU EXCAVATE, DRILL OR

BLAST PENNSYLVANIA ONE-CALL SYSTEM, INC.

SERIAL NUMBER(S): 20250482634

PREPARED BY:

PENNONI ASSOCIATES INC.

150 Ridge Road, Suite 2 Sellersville, PA 18960 T 215-257-5711 F 215-257-5766

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

F

-2

-5

W E

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

C O

V E

R S

H E

E T

SHEET LIST TABLE

SHEET PAGE SHEET TITLE ISSUED DATE REVISED DATE

E001 1 COVER SHEET 7/27/2026 -

E002 2 INDEX SHEET 7/27/2026 -

E100 3 ELECTRICAL DEMOLITION SITE PLAN 7/27/2026 -

E200 4 ELECTRICAL NEW WORK SITE PLAN 7/27/2026 -

E201 5 ELECTRICAL NEW WORK BUILDING PLAN 7/27/2026 -

E300 6 SINGLE-LINE DIAGRAM 7/27/2026 -

E301 7 PANEL SCHEDULES 7/27/2026 -

SITE

SITESITE

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text B

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text 1-800-242-1776

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text O

AutoCAD SHX Text Y

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text C.

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text

AutoCAD SHX Text L

AutoCAD SHX Text V

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text S

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text M cc ou nt s\P

ER

EA

\P

ER

EA

- W ell

T re at m en t C en te r (

PR

A2

5-

)\D

ES

IG

N\

_S

HE

ET

S\

E0

TE

D:

/2 8/

:0

PM

, B Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E002

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF2 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATE; AND OWNER SHALL

INDEMNIFY AND HOLD HARMLESS PENNONI ASSOCIATES

FROM ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES

ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

IN

D

E X

S H

E E

T

HOMERUN TO PANELBOARD "PANEL" CIRCUIT NUMBER #. REFER TO PANELBOARD SCHEDULES,

SWITCHGEAR SCHEDULES, AND/OR ONE-LINE DIAGRAMS FOR CIRCUIT BREAKER SIZE, SIZE AND

NUMBER OF CONDUCTORS AND SIZE AND NUMBER OF CONDUITS. THIS SYMBOL APPLIES TO ALL

HOMERUNS, SINGLE CIRCUIT OR MULTIPLE CIRCUITS.

CONDUIT INSTALLED IN AND BELOW FLOOR CONSTRUCTION, UNDERGROUND OR BELOW SLAB

CONDUIT INSTALLED IN AND ABOVE HUNG CEILING, OVERHEAD

NEW SURFACE MOUNTED PANEL

WALL MOUNTED JUNCTION AND/OR PULL BOX.

CEILING MOUNTED JUNCTION AND/OR PULL BOX.

DUPLEX RECEPTACLE, 20A SPECIFICATION GRADE, SIDE WIRE ONLY, ALMOND COLOR

ALL RECEPTACLES WITHIN 6' OF A WATER SOURCE SHALL BE GFI. WIRE ALL AS PIG-TAIL (NO

FEED-THRU WIRING). USE PAINTED STEEL COVER PLATE. MOUNTED AT 18" AFF TO TOP.

ELECTRICAL LEGEND

CONDUIT TURNING UP.

CONDUIT TURNING DOWN.

SWITCH, 20A RATED, 120/277V, BACK-WIRED. USE PAINTED STEEL COVER PLATE.

SUBSCRIPT DENOTES 3-WAY SWITCH

(NOT ALL ABBREVIATIONS USED)

A, AMP AMPHERE

AC ALTERNATING CURRENT, AIR CONDITIONER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AIC AMPERE INTERRUPTING CAPACITY

AWG AMERICAN WIRE GAUGE

C CONDUIT

CKT CIRCUIT

(D) EXISTING EQUIPMENT TO BE DEMOLISHED

(E), ETR EXISTING EQUIPMENT TO REMAIN

EC, E.C. ELECTRICAL CONTRACTOR

EPO EMERGENCY POWER OFF

F FUSE

G, GND GROUND OR GROUNDING

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

HOA HAND OFF AUTO SELECTION SWITCH

HZ HERTZ

J, JB JUNCTION BOX

K THOUSAND

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

(N) PROVIDE NEW EQUIPMENT AS SHOWN

N, NEUT NEUTRAL

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NTS NOT TO SCALE

P POLE, PUMP

PVC POLYVINYL CHLORIDE

RECPT RECEPTACLE

RF RETURN FAN

RMC RIGID METAL CONDUIT

SF SUPPLY FAN

T, XFMR TRANFORMER

TBD TO BE DETERMINED

TYP TYPICAL

U.O.N. UNLESS OTHERWISE NOTED

V, VOL VOLT

VFD VARIABLE FREQUENCY DRIVE

W WIRE, WATT, WELL

WP WEATHERPROOF (3R RATING, MINIMUM)

Ø PHASE

(D) DEMOLISH

(E) EXISTING

(ER) EXISTING TO BE RELOCATED

(RE) RELOCATED EXISTING

POINT OF CONNECTION

LIGHTING LEGEND

LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".

EXIT SIGN

J

ENCLOSED NON-FUSED DISCONNECT SWITCH - NUMBER INDICATES SWITCH RATING/NUMBER OF

POLES. SWITCHES SHOWN ON PLANS WITHOUT RATINGS ARE 600V/60A/3P. PROVIDE EQUIPMENT IN

NEMA 1 ENCLOSURES FOR INTERIOR INSTALLATIONS AND NEMA 3R ENCLOSURES FOR EXTERIOR

INSTALLATIONS.

30/3

SINGLE LINE SYMBOLS

POWER TRANSFORMER

VOLTAGES, WINDINGS AND SIZE AS INDICATED460V

500KVA

208/120V

GROUND CONNECTION

100/100 FUSED SWITCH

<SWITCH AMPS>/<TYPE 'FA' FUSE AMPS>

100/100

UNFUSED SWITCH

<SWITCH AMPS>

CIRCUIT BREAKER - MOLDED CASE TYPE

<FRAME AMPS>/<TRIP AMPS>

100/90

CIRCUIT BREAKER - DRAW-OUT TYPE

<FRAME AMPS>/<TRIP AMPS>

NETWORK PROTECTOR

<FRAME AMPS>/<TRIP AMPS>

2000/1600

M DIGITAL MULTIMETER

DESIGN AND PERFORMANCE OF COMPONENTS AND METHODS SPECIFIED HEREIN SHALL

COMPLY WITH THE LATEST ADOPTED VERSIONS OF THE STATE OF PENNSYLVANIA AND

LOCAL CODES, AND STANDARDS LISTED BELOW BUT NOT LIMITED TO:

· 2021 IBC INTERNATIONAL BUILDING CODE

· 2020 NEC, NFPA 70 NATIONAL ELECTRIC CODE

· 2021 NFPA 101 LIFE SAFETY CODE

CODE COMPLIANCE

INDEX SHEET GENERAL NOTES

1. SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES INDICATED ON THIS DRAWING ARE TYPICAL.

DRAWINGS MAY NOT INDICATE ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS DRAWING

2. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL DRAWINGS.

3. THESE DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDING THAT THE CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT OF

THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR

OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND

REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF

ANY DEPARTURES FROM THE DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH

DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FOR

APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ENGINEER AND

OWNER.

4. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S

WRITTEN INSTRUCTIONS.

INDEX SHEET ELECTRICAL NOTES

1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NFPA 70 (NEC) AND OTHER ADOPTED CODES

AND STANDARDS BY THE LOCAL JUSRISTICTION.

2. GROUNDING SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250.

3. ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTURANCES, DEVICES, AND MATERIALS OBVIOUSLY NECESSARY FOR A

SOUND, SECURE, AND COMPLETE INSTALLATION.

4. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. CONDUIT ROUTING IS SHOWN DIAGRAMMATICALLY AND DOES NOT SHOW ALL BENDS, OFFSETS, DROPS AND RISES OF RUNS. ALLOW IN PRICE FOR ROUTING OF CONDUIT TO AVOID OBSTRUCTIONS. COORDINATE WITH OTHER TRADES, AS REQUIRED. MAINTAIN HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. THE EXACT LOCATIONS OF DEVICES AND EQUIPMENT ARE SUBJECT TO THE APPROVAL OF THE OWNER, WHO RESERVES

THE RIGHT TO MAKE ANY REASONABLE CHANGES AT NO EXTRA COST.

5. UPON COMPLETION OF THE WORK, THE ENTIRE WIRING SYSTEM SHALL BE FREE FROM GROUNDS, SHORT

CIRCUITS, OPEN CIRCUITS, OVERLOADS AND IMPROPER VOLTAGES.

6. SECURE ALL SUPPORTS TO BUILDING STRUCTURE UTILIZING TOGGLE BOLTS (HOLLOW MASONRY), EXPANSION SHIELDS OR INSERTS (CONCRETE AND BRICK), MACHINE SCREWS (METAL), BEAM CLAMPS (FRAMEWORK), WOOD SCREWS (WOOD) OR PAN THRU STRAPS (METAL DECK). NAILS, RAWL PLUGS AND WOOD PLUGS ARE NOT PERMITTED. WHERE REQUIRED BY STRUCTURE, PROVIDE THRU BOLTS AND FISH PLATES. SUPPORT HORIZONTAL RUNS OF METALLIC RACEWAYS NOT MORE THAN 10' APART. SUPPORT RACEWAY RISERS AT EACH FLOOR LEVEL. RUN EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS. MC AND AC CABLES SHALL BE SECURED EVERY 6' AND WITHIN 12" FROM THE JUNCTION BOX.

SUPPORT PANEL, JUNCTION AND PULLBOXES INDEPENDENTLY TO BUILDING STRUCTURE WITH NO WEIGHT

BEARING ON RACEWAYS.

7. IN LOCATING BOXES AND OUTLETS TO AVOID INACCESSIBLITY, ALLOW FOR OVERHEAD PIPES, DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND PLASTERING, WINDOW AND DOOR TRIM, PANELING, HUNG CEILINGS AND THE LIKE. CORRECT ANY INACCURACY RESULTING FROM FAILURE TO DO SO

WITHOUT EXPENSE TO OWNER.

8. PASS RACEWAYS OVER WATER, STEAM OR OTHER PIPING WHEN PULL BOXES ARE NOT REQUIRED. NO RACEWAY WITHIN 3" OF STEAM OR HOT WATER PIPES OR APPLIANCES (EXCEPT PIPE CROSSINGS WHERE RACEWAY IS AT LEAST 1" FROM PIPE COVERS AND PARALLEL RUNS WHERE RACEWAY IS AT LEAST 18").

9. CUT CONDUIT ENDS SQUARE. REAM SMOOTH. PAINT MALE THREAD OF FIELD THREADED RACEWAYS WITH

GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAY COUPLING.

10. ALL INTERIOR WIRING SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING OR METAL CLAD CABLE AND CONCEALED IN WALLS OR IN HUNG CEILING SPACE. WHERE WIRING CANNOT BE CONCEALED IN FINISHED AREAS, IT SHALL BE RUN EXPOSED IN A NEAT MANNER VIA SURFACE RACEWAY. MINIMUM CONDUIT SIZE

SHALL BE 3/4".

11. LEAVE WIRES WITH SUFFICIENT SLACK TO PERMIT MAKING FINAL CONNECTIONS. RACEWAYS OVER 10' LONG IN WHICH WIRING IS NOT INSTALLED: FURNISH NYLON PULL STRING. FOR ANY RACEWAY OVER 25' PROVIDE PULL STRING WITH CONDUIT MEASURING TAPE AND INDICATE DESIGNATION OF THE RACEWAY ON EACH

END.

12. VERIFY LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS WITH ARCHITECTURAL DRAWINGS OF INTERIOR DETAILS AND FINISH. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS AT OR NEAR DOORS. COORDINATE WITH ARCHITECT AND INSTALL SWITCH ON LOCK/ LATCH SIDE OF DOOR. VERIFY FINAL HINGE LOCATIONS IN FIELD PRIOR TO SWITCH OUTLET INSTALLATION.

13. SET BOXES SQUARE AND TRUE WITH BUILDING FINISH. ERECT WALL AND SWITCH OUTLETS IN ADVANCE OF FURRING AND FIREPROOFING. SECURE TO BUILDING STRUCTURE BY ADJUSTABLE STRAP IRONS.

14. COVERS OF JUNCTION AND PULLBOXES SHALL BE ACCESSIBLE.

15. PROVIDE PULLBOXES WHERE INDICATED, REQUIRED BY CODE AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE. COORDINATE PULLBOX LOCATIONS WITH OTHER TRADES. BOXES SHALL BE ACCESSIBLE AND GENERALLY NOT EXPOSED IN FINISHED SPACES. WHERE NECESSARY, REROUTE RACEWAYS OR MAKE

OTHER ARRANGEMENTS FOR CONCEALMENT.

16. ALL ACCESS DOOR LOCATIONS SHALL BE REVIEWED BY ARCHITECT PRIOR TO INSTALLATION.

17. CONNECT CONDUIT TO MOTOR TERMINAL BOXES WITH FLEXIBLE CONDUIT OF MINIMUM 18", MAXIMUM 6' LENGTH. (PROVIDE SUFFICIENT WIRING SLACK AT EACH END OF TERMINATION). DO NOT TERMINATE IN OR

FASTEN RACEWAYS TO MOTOR FOUNDATION.

18. ALL CUTTING AND PATCHING REQUIRED FOR THE ELECTRICAL WORK SHALL BE THE RESPONSIBILITY OF THE

ELECTRICAL CONTRACTOR.

19. PULL NO THERMOPLASTIC WIRES AT AMBIENT TEMPERATURES LOWER THAN 32°F (0°C). PROVIDE CABLE

SUPPORTS FOR WIRE IN RISER CONDUITS AS REQUIRED BY CODE.

20. PROVIDE SEPARATE SYSTEMS AND ENCLOSURES FOR 208/120V AND 480/277V POWER AND CONTROL WIRING AND SEPARATE SYSTEMS FOR EMERGENCY AND NORMAL POWER. THE EMERGENCY AND NORMAL SYSTEMS SHALL NOT BE INSTALLED IN THE SAME RACEWAYS, ENCLOSURES, JUNCTION BOXES, PULLBOXES, TERMINATION CABINETS, EXCEPT IN EQUIPMENT ENCLOSURES DESIGNED TO ACCEPT BOTH SYSTEMS SUCH

AS AUTOMATIC TRANSFER SWITCH OR EMERGENCY LIGHTING.

21. FEEDER AND BRANCH CIRCUIT WIRING SHALL BE COPPER, 600 VOLT CONDUCTOR INSULATION TYPE THHN.

THE MINIMUM SIZE 600 VOLT CONDUCTOR SHALL BE #12 AWG FOR POWER AND LIGHTING BRANCH CIRCUIT WIRING. THE MINIMUM SIZE CONDUIT SHALL BE 3/4". ALL CIRCUIT WIRING SIZES #10 AWG OR LARGER SHALL BE STRANDED AND SMALLER CONDUCTORS SHALL BE SOLID. BRANCH CIRCUITS 100 TO 200 FEET IN LENGTH UTILIZING #12 AWG WIRE SHALL BE INCREASED TO #10 AWG TO THE CENTER OF THE CIRCUIT LOAD AND #12 WIRE TO THE REMAINING DEVICES BEYOND THE LOAD CENTER. ADJUST CABLING SIZES REQUIRED TO

MAINTAIN VOLTAGE DROP.

22. WHERE CONDUIT RUNS CROSS STRUCTURAL EXPANSION JOINTS, LIQUID-TIGHT FLEXIBLE METAL CONDUIT SHALL BE USED TO TRANSITION CONDUIT SYSTEM FROM ONE STRUCTURAL SECTION TO THE OTHER.

23. VERIFY THAT ANY ELECTRICAL DEVICE OR PRODUCT WHICH IS TO BE RELOCATED OR REUSED IS IN PROPER WORKING CONDITION IN ACCORDANCE WITH INSTRUCTIONS INCLUDED IN ITS LISTING OR LABELING. ANY

DEVICE OR PRODUCT FOUND TO BE DEFECTIVE OR DAMAGED SHALL BE REPLACED WITH NEW.

24. LABEL WITH PERMANENT MARKER ALL JUNCTION BOXES AND RECEPTACLE OUTLET BOXES WITH CIRCUIT NUMBER AND PANEL IDENTIFICATION. ALL FINISHED AREA OUTLET PLATES SHALL BE LABELED WITH LABEL

TAPE.

25. WIRE COLOR CODING: AS PER CODE.

26. REPORT INCONSISTENCIES TO THE ENGINEER IN FORM OF "RFI" REQUEST FOR INFORMATION BEFORE ANY

INACCURATE WORK IS EXECUTED.

27. EXISTING PANEL DIRECTORIES AFFECTED BY THE ALTERATION WORK SHALL BE MODIFIED TO REFLECT THE

BRANCH CIRCUIT WIRING CHANGES.

28. ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH

QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR.

MECHANICAL EQUIPMENT SYMBOLS

X MECHANICAL EQUIPMENT TAG

REFER TO E200 FOR MORE INFORMATION

S 3

ELECTRICAL ABBREVIATIONS

POINT OF DISCONNECTION

HANDHOLE

AutoCAD SHX Text J

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

HH

"A"

"B" "C"

EL

EC

. G

EN

THREE MILE RUN ROAD

ROCK PILE OUTLINE

ROCK PILE OUTLINE

WELL SITE

7 SIGN

"GAS" ANODE BED

WL#307

WL#306

WL#305

WL#304

WL#303

WL#302

WL#301

WL#300

WL#308

WL#309

WL#310

WL#311

WL#600

WL#601

WL#602

WL#105

WL#104

WL#103

WL#102

WL#101

WL#100 WL#200

WL#201

WL#202

WL#203

WL#204

WL#409 WL#408

WL#407

WL#503

WL#500

WL#502

WL#501

WL#406

WL#405

WL#404

WL#403

WL#402

WL#401

WL#400

WETLANDS LIMIT

WETLANDS LIMIT

EXISTING BOLLARD (TYP.)

"A"

"B" "C"

EL

EC

. G

EN

THREE MILE RUN ROAD

ROCK PILE OUTLINE

ROCK PILE OUTLINE

WELL SITE

7 SIGN

"GAS" ANODE BED

WL#307

WL#306

WL#305

WL#304

WL#303

WL#302

WL#301

WL#300

WL#308

WL#309

WL#310

WL#311

WL#600

WL#601

WL#602

WL#105

WL#104

WL#103

WL#102

WL#101

WL#100 WL#200

WL#201

WL#202

WL#203

WL#204

WL#409 WL#408

WL#407

WL#503

WL#500

WL#502

WL#501

WL#406

WL#405

WL#404

WL#403

WL#402

WL#401

WL#400

WETLANDS LIMIT

WETLANDS LIMIT

EXISTING BOLLARD (TYP.)

EL

EC

. G

EN

WL#307

WL#306

WL#305

WL#304

WL#303

WL#302

WL#301

WL#300

WL#308

WL#309

WL#310

WL#311

WL#600

WL#601

WL#602

WL#105

WL#104 WL#204

WL#409 WL#408

WL#407

WL#503

WL#500

WL#502

WL#501

WL#406

WL#405

WL#404

WL#403

WL#402

WL#401

WL#400

WETLANDS LIMIT

WETLANDS LIMIT

CENTERLINE OF THREE

MILE RUN STREAM

FLOODWAY BOUNDARY

FLOODWAY BOUNDARY

1% ANNUAL CHANCE

FLOODPLAIN BOUNDARY

RIPARIAN BUFFER ZONE 1

RIPARIAN BUFFER ZONE 2

RIPARIAN BUFFER ZONE 1

DISCONNECT AND REMOVE WIRE

AND CONDUIT FED FROM ELEC. GEN.

TO EXISTING WELL HOUSE ATS.

UNLESS OTHERWISE NOTED, REMOVE

ALL ELECTRICAL EQUIPMENT

LOCATED IN THE WELL HOUSE

POINT OF DISCONNECTION FOR

INCOMING ELECTRIC UTILITY

(E) ELECTRIC GENERATOR

(E) WELL PUMP

DISCONNECT AND REMOVE WIRE AND

CONDUIT FROM HP PANEL TO WELL

HOUSE PUMP

(D) PANEL HP

(D) SCADA PANEL

POINT OF DISCONNECTION FOR EXISTING ELECTRIC

GENERATOR POWER, AUXILIARY POWER, AND CONTROLS

TAKE NOTE OF EXISTING WIRE SIZE, MATERIAL,

MANUFACTURER, ETC. FOR REWIRING CONTROLS.

(ER) WELL PUMP VFD

U:

\A cc ou nt s\P

ER

EA

\p er ea

- w ell tr ea tm en t c en te r ( pr a2 5-

)\D

ES

IG

N\ _S

HE

ET

S\ E1

TE

D:

/2

8/

:0

PM

, B

Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E100

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

1" = 20'-0"

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF3 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATES; AND OWNER

SHALL INDEMNIFY AND HOLD HARMLESS PENNONI

ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND

EXPENSES ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

NORTH

00 20' 40'

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

E

LE

C

TR

IC

A

L D

E M

O

LI

TI

O

N S

IT

E

P

LA

N

GENERAL ELECTRICAL DEMOLITION NOTES:

1. TO ALLOW FOR CONTINUOUS OPERATION WHILE NEW BUILDING IS UNDER

CONSTRUCTION, PHASE DEMOLITION OF EXISTING BUILDING SO THAT ALL

ELECTRICAL AND EXISTING BUILDING DEMOLITION SHALL BE DONE AFTER

PROPOSED BUILDING AND ELECTRIC ARE INSTALLED. REFER TO SHEETS

E200 AND E201 FOR PROPOSED ELECTRICAL PLANS.

2. COORDINATE ELECTRIC SERVICE DISCONNECTION AND RECONNECTION

WITH PPL.

3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS

IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENATION ONLY.

4. CONTRACTOR IS RESPONSIBLE FOR VISITING THE PROJECT SITE AND

VERIFYING ALL QUANTITIES AND LOCATIONS OF ALL EQUIPMENT AND

DEVICES THAT ARE TO BE DEMOLISHED PRIOR TO BID.

5. DISCONNECT POWER PRIOR TO PERFORMING WORK IN ACCORDANCE

WITH NFPA 70E.

6. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.

7. SALVAGE, PROTECT, AND RETURN TO OWNER ALL ELECTRICAL

EQUIPMENT LOCATED IN THE WELL HOUSE TO BE DEMOED, INCLUDING

BUT NOT LIMITED TO SERVICE RATED 200A MAIN CIRCUIT BREAKER, 480V

PANEL, 240V PANEL, ALL ASSOCIATED CIRCUIT BREAKERS, 480-120/240V

TRANSFORMER, AND SCADA PANEL. COORDINATE WITH OWNER FOR ANY

OTHER ELECTRICAL EQUIPMENT TO BE SAVED.

AutoCAD SHX Text EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)

EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)

EX INLET-1 (INVERTS NOT ACCESIBLE)

GRATE 444.74

INV OUT 18"X36" RCP

ELEV 452.56

INV OUT 30 HDPE

ELEV: 453.52

"A"

"B" "C"

EXISTING 24" TR FLEX PLUG W/ONE

12" ECCENTRIC FLG BOSSED

EXISTING 12" DIA. FLANGE x PE 1'-6" LG

EXISTING 12" DIA. EXTRA FLEX COUPLING

EXISTING 1" POLYETHYLENE

U/G SAMPLE LINE

EXISTING 270LF 24" RJ D.I.P.

UNDERGROUND CHLORINE CONTACT TANK

EXISTING 1" POLYETHYLENE

BLOW-OFF

EXISTING BLOW-OFF

EXISTING IN-LINE VALVE

EXISTING WELL

6' HIGH, 10" DIA.

EL

EC

. G

EN

THREE MILE RUN ROAD

ROCK PILE OUTLINE

ROCK PILE OUTLINE

WELL SITE

7 SIGN

"GAS" ANODE BED

WL#307

WL#306

WL#305

WL#304

WL#303

WL#302

WL#301

WL#300

WL#308

WL#309

WL#310

WL#311

WL#600

WL#601

WL#602

WL#105

WL#104

WL#103

WL#102

WL#101

WL#100 WL#200

WL#201

WL#202

WL#203

WL#204

WL#409 WL#408

WL#407

WL#503

WL#500

WL#502

WL#501

WL#406

WL#405

WL#404

WL#403

WL#402

WL#401

WL#400

WETLANDS LIMIT

WETLANDS LIMIT

EXISTING BOLLARD (TYP.)

CENTERLINE OF THREE

MILE RUN STREAM

FLOODWAY BOUNDARY

FLOODWAY BOUNDARY

1% ANNUAL CHANCE

FLOODPLAIN BOUNDARY

Bo

CwB

SOILS BOUNDARY LINE

RIPARIAN BUFFER ZONE 1

RIPARIAN BUFFER ZONE 2

RIPARIAN BUFFER ZONE 1

PROPOSED 20,000 GAL.

UNDERGROUND

HOLDING TANK

PROPOSED

UNDERGROUND

GAS LINE

EX

IS

TI

NG

P

AV

ED

D

RI

VE

PROPOSED

ARBOR VITAE

TREE (TYP. 6)

PROPOSED 20,000 GAL.

UNDERGROUND

HOLDING TANK

EX

IS

TI

NG

P

AV

ED

D

RI

VE

PROPOSED POINT OF CONNECTION

FOR UNDERGROUND ELECTRIC

UTILITY. PROVIDE HANDHOLE PER

PPL REQUIREMENTS.

EXISTING ELECTRIC

GENERATOR TO REMAIN

(N) 200A ATS

(N) PPL METER

PROVIDE NEW POWER, AUXILIARY

POWER, AND CONTROL CONNECTION

FROM EXISTING ELECTRIC GENERATOR

TO NEW BUILDING.

PROVIDE (3) TRENCHED 2" SCHEDULE 40 PVC CONDUIT

FOR NEW POWER, AUXILIARY POWER, AND CONTROLS

TO NEW BUILDING. REFER TO SINGLE-LINE DIAGRAM

AND PANEL SCHEDULE FOR CONDUIT AND WIRE SIZES.

REFER TO MANUFACTURER'S RECOMMENDATION FOR

CONTROL WIRE SIZE.

PROVIDE 2" TRENCHED PVC

SCHEDULE 40 CONDUIT FOR

(E) WELL PUMP CIRCUIT.

PROVIDE (3) TRENCHED 3" SCHEDULE 40 PVC CONDUIT

FOR NEW POWER, AUXILIARY POWER, AND CONTROLS

TO NEW BUILDING. REFER TO SINGLE-LINE DIAGRAM

AND PANEL SCHEDULE FOR CONDUIT AND WIRE SIZES.

REFER TO MANUFACTURER'S RECOMMENDATION FOR

CONTROL WIRE SIZE.

PROVIDE SEPERATION BARRIER BETWEEN

POWER AND COMMUNICATIONS.

HH

HH

M

U:

\A cc ou nt s\P

ER

EA

\p er ea

- w ell tr ea tm en t c en te r ( pr a2 5-

)\D

ES

IG

N\ _S

HE

ET

S\ E2

TE

D:

/2

8/

:0

PM

, B

Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E200

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

1" = 20'-0"

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF4 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATES; AND OWNER

SHALL INDEMNIFY AND HOLD HARMLESS PENNONI

ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND

EXPENSES ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

NORTH

00 10' 20'

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

E

LE

C

TR

IC

A

L N

E W

W O

R K

S

IT

E P

LA

N

GENERAL ELECTRICAL NEW WORK NOTES:

1. PHASE CONSTRUCTION TO MAINTAIN FACILITY OPERATIONS.

2. COORDINATE ELECTRIC SERVICE RECONNECTION WITH PPL.

3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS

IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENTATION ONLY.

4. THE CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS,

SCOPE OF PHASING, AND PROJECT INTENT PRIOR TO BID SUBMISSION. NO

EXTRA WILL BE ALLOWED DUE TO THE LACK OF KNOWLEDGE OF EXISTING

CONDITIONS TO COORDINATE RELOCATION OF ELECTRICAL SYSTEMS AS

REQUIRED.

5. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.

6. UNLESS OTHERWISE SPECIFIED, REFER TO SINGLE LINE DIAGRAM AND

PANEL SCHEDULE FOR WIRE AND CONDUIT SIZES.

EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)

CARBON FILTER TANK 1 CARBON FILTER TANK 2 CARBON FILTER TANK 3

CHLORINE TANKS /

EQUIPMENT

(N) 200A SERVICE

RATED ATS

(N) PPL METER. COORDINATE AND INSTALL ALL

UTILITY SERVICE CABLE, CONDUIT, AND EQUIPMENT

PER PPL REQUIREMENTS.

(N) PANEL LP

(N) TX-1

(N) PANEL HP

(N) CT CABINET

(N) SERVICE RATED

CIRCUIT BREAKER

PROVIDE 2"C

ALONG WALL

FOR (RE) WELL

PUMP CIRCUIT

PROVIDE 3" TRENCHED CONDUIT FOR

(E) WELL PUMP CIRCUIT. REFER TO

E300 FOR CONDUIT AND WIRE SIZE

AND TRENCHING DETAIL.

TRANSITION METAL

CONDUIT TO PVC

SCHEDULE 40 CONDUIT

(N) SCADA PANEL

(N) LC-9

(N) HP-2,4,6

(N) PFAS UNIT MAIN

CONTROL PANEL

(N) LC-7

(N) CHLORINE GENERATOR

VFD PUMP 2

(N) CHLORINE

GENERATOR VFD PUMP 1

(N) LC-2,4,6(N) LC-8,10,12

(N) CHLORINE

ANALYZER

(N) MCT-12 CONTROL

CABINET

(N) LC-5 (N) LC-1,3

(TYP) CLEARANCE

REQUIREMENT

(RE) WELL PUMP VFD

(N) HP-1,3,5

U:

\A cc ou nt s\P

ER

EA

\P

ER

EA

- W ell

T re at m en t C en te r (

PR

A2

5-

)\D

ES

IG

N\

_S

HE

ET

S\

E2

TE

D:

/2 8/

:0

PM

, B Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E201

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

1" = 2'-0"

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF5 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATES; AND OWNER

SHALL INDEMNIFY AND HOLD HARMLESS PENNONI

ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND

EXPENSES ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

00 2' 4'

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

E

LE

C

TR

IC

A

L

L

IG

H

TI

N G

N E

W W

O R

K B

U

IL

D

IN

G P

LA

N

GENERAL ELECTRICAL NEW WORK NOTES:

1. PHASE CONSTRUCTION TO MAINTAIN FACILITY OPERATIONS.

2. COORDINATE ELECTRIC SERVICE RECONNECTION WITH PPL.

3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS

IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENTATION ONLY.

4. THE CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS,

SCOPE OF PHASING, AND PROJECT INTENT PRIOR TO BID SUBMISSION. NO

EXTRA WILL BE ALLOWED DUE TO THE LACK OF KNOWLEDGE OF EXISTING

CONDITIONS TO COORDINATE RELOCATION OF ELECTRICAL SYSTEMS AS

REQUIRED.

5. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.

6. UNLESS OTHERWISE SPECIFIED, REFER TO SINGLE LINE DIAGRAM AND

PANEL SCHEDULE FOR WIRE AND CONDUIT SIZES.

7. REFER TO M&W PRECAST & CONSTRUCTION SUPPLY DRAWINGS FOR

MORE INFORMATION ON THE PROPOSED PREFABRICATED BUILDING

INCLUDING, BUT NOT LIMITED TO, PRE-INSTALLED LC PANEL, INTERIOR &

EXTERIOR LIGHTING FIXTURES & DEVICES, RECEPTACLES, AND HVAC

EQUIPMENT.

AutoCAD SHX Text

SINK

M cc ou nt s\P

ER

EA

\p er ea

- w ell tr ea tm en t c en te r ( pr a2 5-

)\D

ES

IG

N\ _S

HE

ET

S\ E3

TE

D:

/2

8/

:0

PM

, B

Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E300

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF6 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATES; AND OWNER

SHALL INDEMNIFY AND HOLD HARMLESS PENNONI

ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND

EXPENSES ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

E

LE

C

TR

IC

A

L D

IA

G

R A

M S

D

E

TA

IL

S

E300 N.A

2 NEW WORK ELECTRICAL SINGLE LINE DIAGRAM - NEW BUILDING

E300 N.A

1 DEMOLITION ELECTRICAL SINGLE LINE DIAGRAM - OLD BUILDING

(D) SERVICE ENTRANCE RATED ATS

480Y/277V

3PH

(D) WIRE AND CONDUIT

(E) WIRE AND CONDUIT

PPL INCOMING LINE

(D) TRANSFORMER

M (D) PPL METER &

CT CABINET

(E) GENERATOR

125KVA/100KW

480Y/277V 3P

(D) WIRE AND CONDUIT

(D) WIRE AND CONDUIT

(D) PANEL HP

480Y/277V 200A 3P

(D) WIRE AND CONDUIT

(D) WIRE AND CONDUIT

(D) PANEL LP

120/240V 150A 1P

(D) WIRE AND CONDUIT

(N) ATS

480Y/277V

200A 3PH

3P WITH SOLID NEUTRAL

(N) 3#3/0 + 1#6GND, 3"C

(E) WIRE AND CONDUIT

PPL INCOMING LINE

(N) TX-1

30KVA

PRI 480V, 3PH, 3W

SEC 208Y/120V, 3PH, 4W

M (N) PPL METER &

CT CABINET

(N) 3#3/0 + 1#6GND, 2"C

(N) 3#3/0 + 1#6GND, 3"C

(N) PANEL HP

480Y/277V

200A MCB

3P

(N) 3#3/0 + 1#6GND, 2"C

(N) 3#6 + 1#10GND, 1"C

(N) PANEL LC

208Y/120V

100A MCB

3PH, 4W

(N)4#1 + 1#8GND, 2"C

(E) WIRE AND CONDUIT

NG

1#2GND

DUCT BANK NOTES:

1. CONCRETE SHALL BE 2500 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

2. PROVIDE REINFORCING RODS ON TOP OF DUCTS WHEN

CROSSING OR PLACED IN ROADWAYS.

3. COVER TO TOP OF ENVELOPE SHALL BE 24" OR AS REQUIRED IN

COORDINATION WITH UTILITY.

4. NON-FERROUS TIE WIRES TO BE IMBEDDED IN DUCT BED

CONCRETE.

5. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC. ALL 90

DEGREE BENDS AND ABOVE GROUND CONDUIT SHALL BE IN

RIGID GALVANIZED STEEL CONDUIT.

GRADE

DUCT [SIZE AS

INDICATED ON DWGS.]

30" MIN. AS PER

UTILITY

NOTES:

1. REMOVE & HAUL OFF-SITE ALL EXCESS SOIL

2. RESTORE ALL SURFACES TO ORIGINAL CONDITION.

3. REFER TO ELECTRICAL SITE PLAN FOR CONDUIT SIZE.

4" SAND

" M

IN

REMOVE AND REPLACE EXISTING VEGETATION.

REPLANT W/ NEW MATERIAL IF NECESSARY.

INSTALL TO CONDITION PRIOR TO DISTURBANCE.

METALLIC WARNING TAPE BURIED 12" BELOW

FINAL GRADE AND DIRECTLY ABOVE CONDUIT

RUNS

PVC SCHEDULE 80 CONDUITS WITH

QUANTITIES AS SHOWN ON ELECTRICAL SITE

PLAN CS1702.

P=POWER

COMPACTED SUBBASE

BACKFILL WITH AASHTO SELECT GRANULAR

MATERIAL COMPACTED IN 4" LIFTS

P

E300 N.A

3 SECONDARY SERVICE DUCTBANK

3"

3"

3"

3"

(E) BREAKER

(E) GENERATOR

125KVA/100KW

480Y/277V 3P

(E) WIRE AND CONDUIT

(E) BREAKER

(D) MAIN SERVICE

CIRCUIT BREAKER

(N) 200AF/200AT

MAIN SERVICE RATED

CIRCUIT BREAKER

NG

1#2GND

BUILDING STRUCTURAL

STEEL

TELECOMMUNICATIONS ROOM

#3/0 W/ 60OV INSULATION

MAIN GROUNDING

ELECTRODE

GROUND BAR

GROUND NEUTRAL

NEUTRAL

GROUND

GROUND NEUTRAL

BUILDING

STRUCTURAL

STEEL

METAL WATER PIPE WITHIN

5 FT OF ENTRANCE

GAS PIPE AND OTHER

METAL PIPING SYSTEMS

IN AND ON THE STRUCTURE

INSTALL GROUNDED (NEUTRAL) CONDUCTOR SAME SIZE AS THE LARGEST PHASE

CONDUCTOR.

BARE OR GALVANIZED REBARS THAT ARE MADE ELECTRICALLY CONTINUOUS

USING COPPER JUMPERS NOT SMALLER THAN THE NEC REQUIRED

GROUNDING ELECTRODE CONDUCTOR AND NOT SMALLER THAN 4 AWG. USE

REINFORCING BARS NOT SMALLER THAN THE FOLLOWING BASED ON THE

TOTAL LENGTH OF THE INTERCONNECTED AND PARALLELED REBARS:

TOTAL LENGTH MINIMUM REBAR SIZE

112 FT 1 3/8" (#11 BAR)

150 FT 1" (#8 BAR)

192 FT 3/4" (#6 BAR)

223 FT 5/8" (#5 BAR)

268 FT 1/2" (#4 BAR)

COMPRESSION SPADE LUGS.

12 NOT USED.

BOND TO GAS PIPE ON THE BUILDING SIDE OF THE GAS METER.

BUILDING WITH STEEL STRUCTURE

GROUND

GROUND NEUTRAL

SEPARATELY DERIVED SYSTEM.

3 3 1

18 INSTALL BONDING JUMBER THAT IS SIZED BASED ON NEC TABLE 250.66 USING

THE LARGEST SERVICE OR SEPARATELY DERIVED SYSTEM PHASE CONDUCTOR.

PAD-MOUNTED

TRANSFORMER (DELTA-WYE

CONNECTION)

480Y/277 VOLT

SERVICE ENTRANCE

EQUIPMENT

480Y/277 VOLT

POWER PANELBOARD

208Y/120 VOLT

LIGHTING PANELBOARD

TRANSFORMER FOR

SEPARATELY DERIVED

SYSTEM (DELTA- WYE

CONNECTION)

480Y/277 VOLT

LIGHTING PANELBOARD

1. CONDUCTOR SIZES SHOWN ARE MINIMUM AND MAY BE LARGER THAN THE MINIMUM SIZES REQUIRED BY NEC.

2. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE

VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.

3. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT.

BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250.66 USING THE SERVICE

PHASE CONDUCTOR SIZE.

4. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250.122 USING THE FEEDER CIRCUIT OVERCURRENT DEVICE SIZE OR THE SEPARATELY DERIVED SYSTEM OVERCURRENT DEVICE SIZE.

5. BOND HOT AND COLD WATER PIPING SYSTEMS.

INSTALL GROUNDING ELECTRODE CONDUCTOR (#3/0), SIZED BASED

ON NEC TABLE 250.66 USING THE SERVICE PHASE CONDUCTOR SIZE.

INSTALL EQUIPMENT GROUNDING CONDUCTOR SIZED BASED ON NEC TABLE

250.122 USING THE FEEDER OVERCURRENT DEVICE SIZE.

REFER TO SLD DIAGRAM FOR EQUIPMENT GROUNDING CONDUCTOR WIRE SIZE.

INSTALL GROUNDING ELECTRODE CONDUCTOR THAT IS SIZED BASED ON

NEC TABLE 250.66 USING THE SEPARATELY DERIVED SYSTEM PHASE

CONDUCTOR SIZE.

BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE

CONCRETE-ENCASED MAIN GROUNDING ELECTRODE. USE

COMPRESSION CONNECTORS THAT MEET IEEE 837 REQUIREMENTS OR

USE EXOTHERMIC WELDS.

INSTALL A "MAIN GROUND ELECTRODE GROUND BAR" FOR SINGLE

POINT GROUNDING. LOCATE AT AN ACCESSIBLE AND VISIBLE POINT

NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE CONNECTIONS TO THE

GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET

IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION TO THE GROUND

BAR.

USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF

BUILDING STRUCTURAL STEEL IF THE FIRST OVERCURRENT DEVICE FOR

THE SEPARATELY DERIVED SYSTEM IS WITHIN 50 FEET OF THE "MAIN

GROUNDING ELECTRODE GROUND BAR".

INSTALL A COPPER GROUNDING BAR IN EACH TELECOMMUNICATIONS

ROOM. CONNECT TO THE "MAIN GROUNDING ELECTRODE GROUND

BAR" USING 600V INSULATED 3/0 AWG COPPER CABLE AND

INSTALL GROUNDED (NEUTRAL) CONDUCTOR THAT IS NOT LESS THAN THE

PHASE CONDUCTOR AMPACITY. REFER TO SHEET E-601 FOR WIRE SIZE.

INSTALL BONDING CONDUCTOR THAT IS SIZED BASED ON NEC

TABLE 250.66 USING THE SERVICE OR SEPARATELY-DERIVED SYSTEM

PHASE CONDUCTOR SIZE.

INSTALL IRREVERSIBLE COMPRESSION CONNECTOR WITH TAMPER-PROOF

HARDWARE.

BOND TO METAL PIPING SYSTEMS IN THE AREA SERVED BY THE

INSTALL A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE

BUILDING FOUNDATION AROUND THE ENTIRE PERIMETER OF THE

BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD OF THE

FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE

EITHER OF THE FOLLOWING MATERIALS FOR THE ELECTRODE:

BARE COPPER CABLE NOT SMALLER THAN THE GROUNDING ELECTRODE

CONDUCTOR REQUIRED BY THE NEC AND NOT SMALLER THAN 4 AWG.

E300 N.A

4 GROUNDING SYSTEM DETAIL

E300 N.A

3 FEEDER CONDUIT TRENCH DETAIL

METALLIC WARNING TAPE BURIED

12" BELOW FINAL GRADE AND

DIRECTLY ABOVE CONDUIT RUNS

NOTE: PANEL LC IS BEING PROVIDED AS PART

OF THE PRE-FABRICATED BUILDING

cc ou nt s\P

ER

EA

\p er ea

- w ell tr ea tm en t c en te r ( pr a2 5-

)\D

ES

IG

N\ _S

HE

ET

S\ E3

TE

D:

/2

8/

:0

PM

, B

Y:

H ale y Z ur

ST

YL

E:

P en no ni

NC

E301

Y

N O

D

A

TE

R E

V

IS

IO

N

S

PEREA25001

HSZ

07/27/2026

JPR

SHEET

APPROVED BY

OF7 7

DRAWN BY

DRAWING SCALE

DATE

PROJECT

ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES

ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE

PROJECT. THEY ARE NOT INTENDED OR REPRESENTED

TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON

THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER

PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION

OR ADAPTATION BY PENNONI ASSOCIATES FOR THE

SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS

SOLE RISK AND WITHOUT LIABILITY OR LEGAL

EXPOSURE TO PENNONI ASSOCIATES; AND OWNER

SHALL INDEMNIFY AND HOLD HARMLESS PENNONI

ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND

EXPENSES ARISING OUT OF OR RESULTING THEREFROM.

A

LL

D

IM

E N

S

IO

N S

M U

S T

B E

V E

R

IF

IE

D

B Y

C O

N

TR

A C

TO

R

A N

D O

W N

E R

M U

S T

B E

N O

TI

FI

E D

O F

A N

Y D

IS

C

R E

P A

N C

IE

S

B E

FO

R

E P

R O

C E

E D

IN

G

W

IT

H W

O R

K

PE

N

N O

N I A

SS

O

C

IA

TE

S

IN

C

R id ge

R oa d, S ui te

Se lle rs vi lle

, P A

T

-2

-5

-2

-5

LL

P

R O

P O

S E

D E

LE

C

TR

IC

A L

P

LA

N S

T H

R E

E M

IL

E

R U

N R

O A

D

P E

R K

A S

IE

, P

A

R

ID

G E

R O

A D

S E

LL

E

R S

V

IL

LE

, P

A

P E

R K

A S

IE

R

E G

IO

N

A L

A U

TH

O

R

IT

Y

E

LE

C

TR

IC

A

L S

C H

E D

U

LE

S

Notes:

Demand Current: 81 A Demand Load: 68 kVA

Connected Current: 81 A Connected Load: 68 kVA

Panel Totals Load Classification Connected Factor Demand

Connected Current: 81 A 81 A 81 A Connected Load: 23 kVA 23 kVA 23 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 18013 4537 6

3 18013 4537 4

(RE) WELL PUMP

VFD

3-#2, 1-#8 90 3

18013 4537

1 3 50 3-#6, 1-#10 (N) TX-1

Ckt Description Wire Size Trip (A) Poles FN/Note Phase A

Load (VA) Phase B

Load (VA) Phase C

Load (VA) FN/Note Poles Trip (A) Wire Size Description Ckt

Enclosure: NEMA 1 Mounting: Surface Features &

Modifications: -

Supply: Feed-Thru Lugs: No SCCR: 65 kA Location: Neutral: 100% Mains FN/Note: -

Bus Rating: 250 A Mains Rating: 200 A Panelboard: HP Voltage: 480 V, 3Ø, 4W Mains Type: MCB

PANEL IS INCLUDED IN PREFABRICATED BUILDING. CONTRACTOR TO NOT PURCHASE SEPARATELY. CIRCUITS ASSOCIATED WITH THE PRE-FABRICATED BUILDING ARE NOT SHOWN. PER BASE SCOPE DRAWINGS, THE SUM OF ALL LOADS ASSOCIATED WITH THE PREFABRICATED BUILDING, INCLUDING LIGHTING, RECEPTACLES, AND HVAC, ARE ESTIMATED TO BE NO MORE THAN 40A, OR 14.4KVA.

Notes:

Demand Current: 37 A Demand Load: 13 kVA

Connected Current: 37 A Connected Load: 13 kVA

Panel Totals Load Classification Connected Factor Demand

Connected Current: 58 A 34 A 23 A Connected Load: 7 kVA 4 kVA 3 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 (RE) GENERATOR

AUXILIARY POWER 1-#12, 1-#12, 1-#12 20 1 500 375 12

9 (N) SCADA PANEL 1-#12, 1-#12, 1-#12 20 1 0 375 10

7 (N) PFAS UNIT MAIN

CONTROL PANEL 1-#10, 1-#10, 1-#10 30 1 2916 375

3 15 3-#12, 1-#12 (N) CHLORINE

GENERATOR VFD PUMP 1

5 (N) CHLORINE ANALYZER 1-#12, 1-#12, 1-#12 20 1 1500 375 6

3 3120 375 4

(N) MCT-12 CONTROL

CABINET 2-#8, 1-#10 40 2

3120 375

3 15 3-#12, 1-#12 (N) CHLORINE

GENERATOR VFD PUMP 1

Ckt Description Wire Size Trip (A) Poles FN/Note Phase A

Load (VA) Phase B

Load (VA) Phase C

Load (VA) FN/Note Poles Trip (A) Wire Size Description Ckt

Enclosure: NEMA 1 Mounting: Surface Features &

Modifications: -

Supply: Feed-Thru Lugs: No SCCR: 22 kA Location: Neutral: 100% Mains FN/Note: -

Bus Rating: 100 A Mains Rating: 100 A Panelboard: LC Voltage: 208Y/120V, 3Ø, 4W Mains Type: MCB

1. AN ADDITIONAL 14.4KVA SPLIT BETWEEN EACH PHASE HAS BEEN INCLUDED IN THE TRANSFORMER LOAD TO TAKE INTO ACCOUNT THE ESTIMATED PREFABRICATED BUILDING LIGHTING, RECEPTACLE, AND HVAC LOADS.

3 20 3-#12, 1-#12 (N) SPD

Sheets and Views
E001-COVER SHEET
E001-INDEX SHEET
E100-ELECTRICAL DEMOLITION SITE PLAN
E200-ELECTRICAL NEW WORK SITE PLAN
E201-ELECTRICAL & LIGHTING NEW WORK BUILDING PLAN
E300-Diagrams & Details
E300-Schedules

File details come from the government source that posted it. Updated .