12-2026-07-27 PRA25-01 Electrical Plans.pdf
PDF 2 MB Posted
- Attached to
- PRA 25-01 WELL 7 TREATMENT CENTER
- Solicitation number
- Not on record
- Issued by
- Bucks County, Pennsylvania
About this file
Electrical Plans Summary
This is a set of electrical construction plans prepared by Pennoni Associates Inc. for the Perkasie Regional Authority (PRA) Well #7 Treatment Center project located in East Rockhill Township, Bucks County, Pennsylvania. The plans include comprehensive electrical design for a new treatment facility building, encompassing demolition of existing electrical systems and installation of new power distribution, lighting, control systems, and related infrastructure. The project scope involves a 480Y/277V three-phase service entrance with automatic transfer switch (ATS) rated at 200 amperes, a 30 kilovolt-ampere transformer stepping down to 208Y/120V for lighting and control panels, new panelboards (HP and LC), single-line diagrams, grounding systems, and conduit routing for both power and control circuits. The plans specify trenched PVC Schedule 40 conduit for underground utility connections from the existing generator to the new building, with three-inch conduits for primary power and two-inch conduits for auxiliary power and controls. The contract term is 180 consecutive calendar days from the Notice to Proceed, with temporary restoration required within 150 days and final restoration within 30 days thereafter. The bid deadline is August 31, 2026 at 1:00 PM EST, with a pre-bid meeting scheduled for August 12, 2026 at 10:00 AM. Bids remain binding for 60 days after closing.
The electrical plans comply with the 2020 National Electrical Code (NFPA 70), 2021 International Building Code, and 2021 Life Safety Code, and require all work to be performed by a licensed electrical contractor in strict accordance with manufacturer specifications and all applicable codes and standards. Feeder and branch circuit wiring shall be copper with 600-volt THHN insulation, with minimum conductor sizes of #12 AWG for branch circuits and #3/0 AWG for main service feeders as specified in the single-line diagrams and panel schedules. The project includes a concrete-encased grounding electrode system at the building foundation perimeter, bonding of structural steel columns, metal piping systems, and telecommunications room grounding bars, with all grounding connections sized per National Electrical Code Table 250.66 and 250.122. All dimensions and specifications shown on the drawings are subject to verification by the contractor and owner, with any discrepancies requiring notification prior to work commencement. The plans are diagrammatic in nature and indicate general system arrangement; the contractor is responsible for coordinating conduit routing with other trades, maintaining headroom, and allowing for overhead obstacles and variations in construction. Liquidated damages of $10,000 per calendar day apply for contract delays, and the contractor must submit performance bonds (100 percent of contract price), labor and materials bonds (100 percent), and maintenance bonds as required.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U:
\A cc ou nt s\P
ER
EA
\P
ER
EA
- W ell
T re at m en t C en te r (
PR
A2
5-
)\D
ES
IG
N\
_S
HE
ET
S\
E0
.d wg
PL
OT
TE
D:
/2 8/
:0
PM
, B Y:
H ale y Z ur its ky
ST
YL
E:
P en no ni
NC
S.
stb
E001
B Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF1 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATE; AND OWNER SHALL
INDEMNIFY AND HOLD HARMLESS PENNONI ASSOCIATES
FROM ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES
ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PREPARED FOR:
OWNER/DEVELOPER
PERKASIE REGIONAL AUTHORITY
150 RIDGE ROAD
SELLERSVILLE, PA 18960
WELL #7 PROPOSED ELECTRICAL PLANS
EAST ROCKHILL, BUCKS COUNTY, PA
LOCATION MAP
Scale: 1" = 800'
USGS MAP
Scale: 1" = 800'
SOILS MAP
Scale: 1" = 800'
N O
R
TH
N O
R
TH
N O
R
TH
CALL 1-800-242-1776
CALL BEFORE YOU DIG
BEFORE YOU DIG ANYWHERE IN PENNSYLVANIA
PA. ACT 287 OF 1974 REQUIRES THREE WORKING DAYS
NOTICE TO UTILITIES BEFORE YOU EXCAVATE, DRILL OR
BLAST PENNSYLVANIA ONE-CALL SYSTEM, INC.
SERIAL NUMBER(S): 20250482634
PREPARED BY:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960 T 215-257-5711 F 215-257-5766
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
F
-2
-5
W E
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
C O
V E
R S
H E
E T
SHEET LIST TABLE
SHEET PAGE SHEET TITLE ISSUED DATE REVISED DATE
E001 1 COVER SHEET 7/27/2026 -
E002 2 INDEX SHEET 7/27/2026 -
E100 3 ELECTRICAL DEMOLITION SITE PLAN 7/27/2026 -
E200 4 ELECTRICAL NEW WORK SITE PLAN 7/27/2026 -
E201 5 ELECTRICAL NEW WORK BUILDING PLAN 7/27/2026 -
E300 6 SINGLE-LINE DIAGRAM 7/27/2026 -
E301 7 PANEL SCHEDULES 7/27/2026 -
SITE
SITESITE
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text B
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text 1-800-242-1776
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text C.
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text V
AutoCAD SHX Text S
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text Y
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text M cc ou nt s\P
ER
EA
\P
ER
EA
- W ell
T re at m en t C en te r (
PR
A2
5-
)\D
ES
IG
N\
_S
HE
ET
S\
E0
TE
D:
/2 8/
:0
PM
, B Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E002
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF2 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATE; AND OWNER SHALL
INDEMNIFY AND HOLD HARMLESS PENNONI ASSOCIATES
FROM ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES
ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
IN
D
E X
S H
E E
T
HOMERUN TO PANELBOARD "PANEL" CIRCUIT NUMBER #. REFER TO PANELBOARD SCHEDULES,
SWITCHGEAR SCHEDULES, AND/OR ONE-LINE DIAGRAMS FOR CIRCUIT BREAKER SIZE, SIZE AND
NUMBER OF CONDUCTORS AND SIZE AND NUMBER OF CONDUITS. THIS SYMBOL APPLIES TO ALL
HOMERUNS, SINGLE CIRCUIT OR MULTIPLE CIRCUITS.
CONDUIT INSTALLED IN AND BELOW FLOOR CONSTRUCTION, UNDERGROUND OR BELOW SLAB
CONDUIT INSTALLED IN AND ABOVE HUNG CEILING, OVERHEAD
NEW SURFACE MOUNTED PANEL
WALL MOUNTED JUNCTION AND/OR PULL BOX.
CEILING MOUNTED JUNCTION AND/OR PULL BOX.
DUPLEX RECEPTACLE, 20A SPECIFICATION GRADE, SIDE WIRE ONLY, ALMOND COLOR
ALL RECEPTACLES WITHIN 6' OF A WATER SOURCE SHALL BE GFI. WIRE ALL AS PIG-TAIL (NO
FEED-THRU WIRING). USE PAINTED STEEL COVER PLATE. MOUNTED AT 18" AFF TO TOP.
ELECTRICAL LEGEND
CONDUIT TURNING UP.
CONDUIT TURNING DOWN.
SWITCH, 20A RATED, 120/277V, BACK-WIRED. USE PAINTED STEEL COVER PLATE.
SUBSCRIPT DENOTES 3-WAY SWITCH
(NOT ALL ABBREVIATIONS USED)
A, AMP AMPHERE
AC ALTERNATING CURRENT, AIR CONDITIONER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
AWG AMERICAN WIRE GAUGE
C CONDUIT
CKT CIRCUIT
(D) EXISTING EQUIPMENT TO BE DEMOLISHED
(E), ETR EXISTING EQUIPMENT TO REMAIN
EC, E.C. ELECTRICAL CONTRACTOR
EPO EMERGENCY POWER OFF
F FUSE
G, GND GROUND OR GROUNDING
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
HOA HAND OFF AUTO SELECTION SWITCH
HZ HERTZ
J, JB JUNCTION BOX
K THOUSAND
KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT-AMPERE
KW KILOWATT
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
(N) PROVIDE NEW EQUIPMENT AS SHOWN
N, NEUT NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NTS NOT TO SCALE
P POLE, PUMP
PVC POLYVINYL CHLORIDE
RECPT RECEPTACLE
RF RETURN FAN
RMC RIGID METAL CONDUIT
SF SUPPLY FAN
T, XFMR TRANFORMER
TBD TO BE DETERMINED
TYP TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
V, VOL VOLT
VFD VARIABLE FREQUENCY DRIVE
W WIRE, WATT, WELL
WP WEATHERPROOF (3R RATING, MINIMUM)
Ø PHASE
(D) DEMOLISH
(E) EXISTING
(ER) EXISTING TO BE RELOCATED
(RE) RELOCATED EXISTING
POINT OF CONNECTION
LIGHTING LEGEND
LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".
EXIT SIGN
J
ENCLOSED NON-FUSED DISCONNECT SWITCH - NUMBER INDICATES SWITCH RATING/NUMBER OF
POLES. SWITCHES SHOWN ON PLANS WITHOUT RATINGS ARE 600V/60A/3P. PROVIDE EQUIPMENT IN
NEMA 1 ENCLOSURES FOR INTERIOR INSTALLATIONS AND NEMA 3R ENCLOSURES FOR EXTERIOR
INSTALLATIONS.
30/3
SINGLE LINE SYMBOLS
POWER TRANSFORMER
VOLTAGES, WINDINGS AND SIZE AS INDICATED460V
500KVA
208/120V
GROUND CONNECTION
100/100 FUSED SWITCH
<SWITCH AMPS>/<TYPE 'FA' FUSE AMPS>
100/100
UNFUSED SWITCH
<SWITCH AMPS>
CIRCUIT BREAKER - MOLDED CASE TYPE
<FRAME AMPS>/<TRIP AMPS>
100/90
CIRCUIT BREAKER - DRAW-OUT TYPE
<FRAME AMPS>/<TRIP AMPS>
NETWORK PROTECTOR
<FRAME AMPS>/<TRIP AMPS>
2000/1600
M DIGITAL MULTIMETER
DESIGN AND PERFORMANCE OF COMPONENTS AND METHODS SPECIFIED HEREIN SHALL
COMPLY WITH THE LATEST ADOPTED VERSIONS OF THE STATE OF PENNSYLVANIA AND
LOCAL CODES, AND STANDARDS LISTED BELOW BUT NOT LIMITED TO:
· 2021 IBC INTERNATIONAL BUILDING CODE
· 2020 NEC, NFPA 70 NATIONAL ELECTRIC CODE
· 2021 NFPA 101 LIFE SAFETY CODE
CODE COMPLIANCE
INDEX SHEET GENERAL NOTES
1. SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES INDICATED ON THIS DRAWING ARE TYPICAL.
DRAWINGS MAY NOT INDICATE ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS DRAWING
2. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL DRAWINGS.
3. THESE DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDING THAT THE CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT OF
THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR
OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND
REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF
ANY DEPARTURES FROM THE DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH
DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FOR
APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ENGINEER AND
OWNER.
4. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S
WRITTEN INSTRUCTIONS.
INDEX SHEET ELECTRICAL NOTES
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NFPA 70 (NEC) AND OTHER ADOPTED CODES
AND STANDARDS BY THE LOCAL JUSRISTICTION.
2. GROUNDING SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250.
3. ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTURANCES, DEVICES, AND MATERIALS OBVIOUSLY NECESSARY FOR A
SOUND, SECURE, AND COMPLETE INSTALLATION.
4. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. CONDUIT ROUTING IS SHOWN DIAGRAMMATICALLY AND DOES NOT SHOW ALL BENDS, OFFSETS, DROPS AND RISES OF RUNS. ALLOW IN PRICE FOR ROUTING OF CONDUIT TO AVOID OBSTRUCTIONS. COORDINATE WITH OTHER TRADES, AS REQUIRED. MAINTAIN HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. THE EXACT LOCATIONS OF DEVICES AND EQUIPMENT ARE SUBJECT TO THE APPROVAL OF THE OWNER, WHO RESERVES
THE RIGHT TO MAKE ANY REASONABLE CHANGES AT NO EXTRA COST.
5. UPON COMPLETION OF THE WORK, THE ENTIRE WIRING SYSTEM SHALL BE FREE FROM GROUNDS, SHORT
CIRCUITS, OPEN CIRCUITS, OVERLOADS AND IMPROPER VOLTAGES.
6. SECURE ALL SUPPORTS TO BUILDING STRUCTURE UTILIZING TOGGLE BOLTS (HOLLOW MASONRY), EXPANSION SHIELDS OR INSERTS (CONCRETE AND BRICK), MACHINE SCREWS (METAL), BEAM CLAMPS (FRAMEWORK), WOOD SCREWS (WOOD) OR PAN THRU STRAPS (METAL DECK). NAILS, RAWL PLUGS AND WOOD PLUGS ARE NOT PERMITTED. WHERE REQUIRED BY STRUCTURE, PROVIDE THRU BOLTS AND FISH PLATES. SUPPORT HORIZONTAL RUNS OF METALLIC RACEWAYS NOT MORE THAN 10' APART. SUPPORT RACEWAY RISERS AT EACH FLOOR LEVEL. RUN EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS. MC AND AC CABLES SHALL BE SECURED EVERY 6' AND WITHIN 12" FROM THE JUNCTION BOX.
SUPPORT PANEL, JUNCTION AND PULLBOXES INDEPENDENTLY TO BUILDING STRUCTURE WITH NO WEIGHT
BEARING ON RACEWAYS.
7. IN LOCATING BOXES AND OUTLETS TO AVOID INACCESSIBLITY, ALLOW FOR OVERHEAD PIPES, DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND PLASTERING, WINDOW AND DOOR TRIM, PANELING, HUNG CEILINGS AND THE LIKE. CORRECT ANY INACCURACY RESULTING FROM FAILURE TO DO SO
WITHOUT EXPENSE TO OWNER.
8. PASS RACEWAYS OVER WATER, STEAM OR OTHER PIPING WHEN PULL BOXES ARE NOT REQUIRED. NO RACEWAY WITHIN 3" OF STEAM OR HOT WATER PIPES OR APPLIANCES (EXCEPT PIPE CROSSINGS WHERE RACEWAY IS AT LEAST 1" FROM PIPE COVERS AND PARALLEL RUNS WHERE RACEWAY IS AT LEAST 18").
9. CUT CONDUIT ENDS SQUARE. REAM SMOOTH. PAINT MALE THREAD OF FIELD THREADED RACEWAYS WITH
GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAY COUPLING.
10. ALL INTERIOR WIRING SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING OR METAL CLAD CABLE AND CONCEALED IN WALLS OR IN HUNG CEILING SPACE. WHERE WIRING CANNOT BE CONCEALED IN FINISHED AREAS, IT SHALL BE RUN EXPOSED IN A NEAT MANNER VIA SURFACE RACEWAY. MINIMUM CONDUIT SIZE
SHALL BE 3/4".
11. LEAVE WIRES WITH SUFFICIENT SLACK TO PERMIT MAKING FINAL CONNECTIONS. RACEWAYS OVER 10' LONG IN WHICH WIRING IS NOT INSTALLED: FURNISH NYLON PULL STRING. FOR ANY RACEWAY OVER 25' PROVIDE PULL STRING WITH CONDUIT MEASURING TAPE AND INDICATE DESIGNATION OF THE RACEWAY ON EACH
END.
12. VERIFY LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS WITH ARCHITECTURAL DRAWINGS OF INTERIOR DETAILS AND FINISH. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS AT OR NEAR DOORS. COORDINATE WITH ARCHITECT AND INSTALL SWITCH ON LOCK/ LATCH SIDE OF DOOR. VERIFY FINAL HINGE LOCATIONS IN FIELD PRIOR TO SWITCH OUTLET INSTALLATION.
13. SET BOXES SQUARE AND TRUE WITH BUILDING FINISH. ERECT WALL AND SWITCH OUTLETS IN ADVANCE OF FURRING AND FIREPROOFING. SECURE TO BUILDING STRUCTURE BY ADJUSTABLE STRAP IRONS.
14. COVERS OF JUNCTION AND PULLBOXES SHALL BE ACCESSIBLE.
15. PROVIDE PULLBOXES WHERE INDICATED, REQUIRED BY CODE AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE. COORDINATE PULLBOX LOCATIONS WITH OTHER TRADES. BOXES SHALL BE ACCESSIBLE AND GENERALLY NOT EXPOSED IN FINISHED SPACES. WHERE NECESSARY, REROUTE RACEWAYS OR MAKE
OTHER ARRANGEMENTS FOR CONCEALMENT.
16. ALL ACCESS DOOR LOCATIONS SHALL BE REVIEWED BY ARCHITECT PRIOR TO INSTALLATION.
17. CONNECT CONDUIT TO MOTOR TERMINAL BOXES WITH FLEXIBLE CONDUIT OF MINIMUM 18", MAXIMUM 6' LENGTH. (PROVIDE SUFFICIENT WIRING SLACK AT EACH END OF TERMINATION). DO NOT TERMINATE IN OR
FASTEN RACEWAYS TO MOTOR FOUNDATION.
18. ALL CUTTING AND PATCHING REQUIRED FOR THE ELECTRICAL WORK SHALL BE THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR.
19. PULL NO THERMOPLASTIC WIRES AT AMBIENT TEMPERATURES LOWER THAN 32°F (0°C). PROVIDE CABLE
SUPPORTS FOR WIRE IN RISER CONDUITS AS REQUIRED BY CODE.
20. PROVIDE SEPARATE SYSTEMS AND ENCLOSURES FOR 208/120V AND 480/277V POWER AND CONTROL WIRING AND SEPARATE SYSTEMS FOR EMERGENCY AND NORMAL POWER. THE EMERGENCY AND NORMAL SYSTEMS SHALL NOT BE INSTALLED IN THE SAME RACEWAYS, ENCLOSURES, JUNCTION BOXES, PULLBOXES, TERMINATION CABINETS, EXCEPT IN EQUIPMENT ENCLOSURES DESIGNED TO ACCEPT BOTH SYSTEMS SUCH
AS AUTOMATIC TRANSFER SWITCH OR EMERGENCY LIGHTING.
21. FEEDER AND BRANCH CIRCUIT WIRING SHALL BE COPPER, 600 VOLT CONDUCTOR INSULATION TYPE THHN.
THE MINIMUM SIZE 600 VOLT CONDUCTOR SHALL BE #12 AWG FOR POWER AND LIGHTING BRANCH CIRCUIT WIRING. THE MINIMUM SIZE CONDUIT SHALL BE 3/4". ALL CIRCUIT WIRING SIZES #10 AWG OR LARGER SHALL BE STRANDED AND SMALLER CONDUCTORS SHALL BE SOLID. BRANCH CIRCUITS 100 TO 200 FEET IN LENGTH UTILIZING #12 AWG WIRE SHALL BE INCREASED TO #10 AWG TO THE CENTER OF THE CIRCUIT LOAD AND #12 WIRE TO THE REMAINING DEVICES BEYOND THE LOAD CENTER. ADJUST CABLING SIZES REQUIRED TO
MAINTAIN VOLTAGE DROP.
22. WHERE CONDUIT RUNS CROSS STRUCTURAL EXPANSION JOINTS, LIQUID-TIGHT FLEXIBLE METAL CONDUIT SHALL BE USED TO TRANSITION CONDUIT SYSTEM FROM ONE STRUCTURAL SECTION TO THE OTHER.
23. VERIFY THAT ANY ELECTRICAL DEVICE OR PRODUCT WHICH IS TO BE RELOCATED OR REUSED IS IN PROPER WORKING CONDITION IN ACCORDANCE WITH INSTRUCTIONS INCLUDED IN ITS LISTING OR LABELING. ANY
DEVICE OR PRODUCT FOUND TO BE DEFECTIVE OR DAMAGED SHALL BE REPLACED WITH NEW.
24. LABEL WITH PERMANENT MARKER ALL JUNCTION BOXES AND RECEPTACLE OUTLET BOXES WITH CIRCUIT NUMBER AND PANEL IDENTIFICATION. ALL FINISHED AREA OUTLET PLATES SHALL BE LABELED WITH LABEL
TAPE.
25. WIRE COLOR CODING: AS PER CODE.
26. REPORT INCONSISTENCIES TO THE ENGINEER IN FORM OF "RFI" REQUEST FOR INFORMATION BEFORE ANY
INACCURATE WORK IS EXECUTED.
27. EXISTING PANEL DIRECTORIES AFFECTED BY THE ALTERATION WORK SHALL BE MODIFIED TO REFLECT THE
BRANCH CIRCUIT WIRING CHANGES.
28. ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH
QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR.
MECHANICAL EQUIPMENT SYMBOLS
X MECHANICAL EQUIPMENT TAG
REFER TO E200 FOR MORE INFORMATION
S 3
ELECTRICAL ABBREVIATIONS
POINT OF DISCONNECTION
HANDHOLE
AutoCAD SHX Text J
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
HH
"A"
"B" "C"
EL
EC
. G
EN
THREE MILE RUN ROAD
ROCK PILE OUTLINE
ROCK PILE OUTLINE
WELL SITE
7 SIGN
"GAS" ANODE BED
WL#307
WL#306
WL#305
WL#304
WL#303
WL#302
WL#301
WL#300
WL#308
WL#309
WL#310
WL#311
WL#600
WL#601
WL#602
WL#105
WL#104
WL#103
WL#102
WL#101
WL#100 WL#200
WL#201
WL#202
WL#203
WL#204
WL#409 WL#408
WL#407
WL#503
WL#500
WL#502
WL#501
WL#406
WL#405
WL#404
WL#403
WL#402
WL#401
WL#400
WETLANDS LIMIT
WETLANDS LIMIT
EXISTING BOLLARD (TYP.)
"A"
"B" "C"
EL
EC
. G
EN
THREE MILE RUN ROAD
ROCK PILE OUTLINE
ROCK PILE OUTLINE
WELL SITE
7 SIGN
"GAS" ANODE BED
WL#307
WL#306
WL#305
WL#304
WL#303
WL#302
WL#301
WL#300
WL#308
WL#309
WL#310
WL#311
WL#600
WL#601
WL#602
WL#105
WL#104
WL#103
WL#102
WL#101
WL#100 WL#200
WL#201
WL#202
WL#203
WL#204
WL#409 WL#408
WL#407
WL#503
WL#500
WL#502
WL#501
WL#406
WL#405
WL#404
WL#403
WL#402
WL#401
WL#400
WETLANDS LIMIT
WETLANDS LIMIT
EXISTING BOLLARD (TYP.)
EL
EC
. G
EN
WL#307
WL#306
WL#305
WL#304
WL#303
WL#302
WL#301
WL#300
WL#308
WL#309
WL#310
WL#311
WL#600
WL#601
WL#602
WL#105
WL#104 WL#204
WL#409 WL#408
WL#407
WL#503
WL#500
WL#502
WL#501
WL#406
WL#405
WL#404
WL#403
WL#402
WL#401
WL#400
WETLANDS LIMIT
WETLANDS LIMIT
CENTERLINE OF THREE
MILE RUN STREAM
FLOODWAY BOUNDARY
FLOODWAY BOUNDARY
1% ANNUAL CHANCE
FLOODPLAIN BOUNDARY
RIPARIAN BUFFER ZONE 1
RIPARIAN BUFFER ZONE 2
RIPARIAN BUFFER ZONE 1
DISCONNECT AND REMOVE WIRE
AND CONDUIT FED FROM ELEC. GEN.
TO EXISTING WELL HOUSE ATS.
UNLESS OTHERWISE NOTED, REMOVE
ALL ELECTRICAL EQUIPMENT
LOCATED IN THE WELL HOUSE
POINT OF DISCONNECTION FOR
INCOMING ELECTRIC UTILITY
(E) ELECTRIC GENERATOR
(E) WELL PUMP
DISCONNECT AND REMOVE WIRE AND
CONDUIT FROM HP PANEL TO WELL
HOUSE PUMP
(D) PANEL HP
(D) SCADA PANEL
POINT OF DISCONNECTION FOR EXISTING ELECTRIC
GENERATOR POWER, AUXILIARY POWER, AND CONTROLS
TAKE NOTE OF EXISTING WIRE SIZE, MATERIAL,
MANUFACTURER, ETC. FOR REWIRING CONTROLS.
(ER) WELL PUMP VFD
U:
\A cc ou nt s\P
ER
EA
\p er ea
- w ell tr ea tm en t c en te r ( pr a2 5-
)\D
ES
IG
N\ _S
HE
ET
S\ E1
TE
D:
/2
8/
:0
PM
, B
Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E100
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
1" = 20'-0"
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF3 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATES; AND OWNER
SHALL INDEMNIFY AND HOLD HARMLESS PENNONI
ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND
EXPENSES ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
NORTH
00 20' 40'
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
E
LE
C
TR
IC
A
L D
E M
O
LI
TI
O
N S
IT
E
P
LA
N
GENERAL ELECTRICAL DEMOLITION NOTES:
1. TO ALLOW FOR CONTINUOUS OPERATION WHILE NEW BUILDING IS UNDER
CONSTRUCTION, PHASE DEMOLITION OF EXISTING BUILDING SO THAT ALL
ELECTRICAL AND EXISTING BUILDING DEMOLITION SHALL BE DONE AFTER
PROPOSED BUILDING AND ELECTRIC ARE INSTALLED. REFER TO SHEETS
E200 AND E201 FOR PROPOSED ELECTRICAL PLANS.
2. COORDINATE ELECTRIC SERVICE DISCONNECTION AND RECONNECTION
WITH PPL.
3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS
IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENATION ONLY.
4. CONTRACTOR IS RESPONSIBLE FOR VISITING THE PROJECT SITE AND
VERIFYING ALL QUANTITIES AND LOCATIONS OF ALL EQUIPMENT AND
DEVICES THAT ARE TO BE DEMOLISHED PRIOR TO BID.
5. DISCONNECT POWER PRIOR TO PERFORMING WORK IN ACCORDANCE
WITH NFPA 70E.
6. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.
7. SALVAGE, PROTECT, AND RETURN TO OWNER ALL ELECTRICAL
EQUIPMENT LOCATED IN THE WELL HOUSE TO BE DEMOED, INCLUDING
BUT NOT LIMITED TO SERVICE RATED 200A MAIN CIRCUIT BREAKER, 480V
PANEL, 240V PANEL, ALL ASSOCIATED CIRCUIT BREAKERS, 480-120/240V
TRANSFORMER, AND SCADA PANEL. COORDINATE WITH OWNER FOR ANY
OTHER ELECTRICAL EQUIPMENT TO BE SAVED.
AutoCAD SHX Text EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)
EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)
EX INLET-1 (INVERTS NOT ACCESIBLE)
GRATE 444.74
INV OUT 18"X36" RCP
ELEV 452.56
INV OUT 30 HDPE
ELEV: 453.52
"A"
"B" "C"
EXISTING 24" TR FLEX PLUG W/ONE
12" ECCENTRIC FLG BOSSED
EXISTING 12" DIA. FLANGE x PE 1'-6" LG
EXISTING 12" DIA. EXTRA FLEX COUPLING
EXISTING 1" POLYETHYLENE
U/G SAMPLE LINE
EXISTING 270LF 24" RJ D.I.P.
UNDERGROUND CHLORINE CONTACT TANK
EXISTING 1" POLYETHYLENE
BLOW-OFF
EXISTING BLOW-OFF
EXISTING IN-LINE VALVE
EXISTING WELL
6' HIGH, 10" DIA.
EL
EC
. G
EN
THREE MILE RUN ROAD
ROCK PILE OUTLINE
ROCK PILE OUTLINE
WELL SITE
7 SIGN
"GAS" ANODE BED
WL#307
WL#306
WL#305
WL#304
WL#303
WL#302
WL#301
WL#300
WL#308
WL#309
WL#310
WL#311
WL#600
WL#601
WL#602
WL#105
WL#104
WL#103
WL#102
WL#101
WL#100 WL#200
WL#201
WL#202
WL#203
WL#204
WL#409 WL#408
WL#407
WL#503
WL#500
WL#502
WL#501
WL#406
WL#405
WL#404
WL#403
WL#402
WL#401
WL#400
WETLANDS LIMIT
WETLANDS LIMIT
EXISTING BOLLARD (TYP.)
CENTERLINE OF THREE
MILE RUN STREAM
FLOODWAY BOUNDARY
FLOODWAY BOUNDARY
1% ANNUAL CHANCE
FLOODPLAIN BOUNDARY
Bo
CwB
SOILS BOUNDARY LINE
RIPARIAN BUFFER ZONE 1
RIPARIAN BUFFER ZONE 2
RIPARIAN BUFFER ZONE 1
PROPOSED 20,000 GAL.
UNDERGROUND
HOLDING TANK
PROPOSED
UNDERGROUND
GAS LINE
EX
IS
TI
NG
P
AV
ED
D
RI
VE
PROPOSED
ARBOR VITAE
TREE (TYP. 6)
PROPOSED 20,000 GAL.
UNDERGROUND
HOLDING TANK
EX
IS
TI
NG
P
AV
ED
D
RI
VE
PROPOSED POINT OF CONNECTION
FOR UNDERGROUND ELECTRIC
UTILITY. PROVIDE HANDHOLE PER
PPL REQUIREMENTS.
EXISTING ELECTRIC
GENERATOR TO REMAIN
(N) 200A ATS
(N) PPL METER
PROVIDE NEW POWER, AUXILIARY
POWER, AND CONTROL CONNECTION
FROM EXISTING ELECTRIC GENERATOR
TO NEW BUILDING.
PROVIDE (3) TRENCHED 2" SCHEDULE 40 PVC CONDUIT
FOR NEW POWER, AUXILIARY POWER, AND CONTROLS
TO NEW BUILDING. REFER TO SINGLE-LINE DIAGRAM
AND PANEL SCHEDULE FOR CONDUIT AND WIRE SIZES.
REFER TO MANUFACTURER'S RECOMMENDATION FOR
CONTROL WIRE SIZE.
PROVIDE 2" TRENCHED PVC
SCHEDULE 40 CONDUIT FOR
(E) WELL PUMP CIRCUIT.
PROVIDE (3) TRENCHED 3" SCHEDULE 40 PVC CONDUIT
FOR NEW POWER, AUXILIARY POWER, AND CONTROLS
TO NEW BUILDING. REFER TO SINGLE-LINE DIAGRAM
AND PANEL SCHEDULE FOR CONDUIT AND WIRE SIZES.
REFER TO MANUFACTURER'S RECOMMENDATION FOR
CONTROL WIRE SIZE.
PROVIDE SEPERATION BARRIER BETWEEN
POWER AND COMMUNICATIONS.
HH
HH
M
U:
\A cc ou nt s\P
ER
EA
\p er ea
- w ell tr ea tm en t c en te r ( pr a2 5-
)\D
ES
IG
N\ _S
HE
ET
S\ E2
TE
D:
/2
8/
:0
PM
, B
Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E200
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
1" = 20'-0"
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF4 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATES; AND OWNER
SHALL INDEMNIFY AND HOLD HARMLESS PENNONI
ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND
EXPENSES ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
NORTH
00 10' 20'
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
E
LE
C
TR
IC
A
L N
E W
W O
R K
S
IT
E P
LA
N
GENERAL ELECTRICAL NEW WORK NOTES:
1. PHASE CONSTRUCTION TO MAINTAIN FACILITY OPERATIONS.
2. COORDINATE ELECTRIC SERVICE RECONNECTION WITH PPL.
3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS
IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENTATION ONLY.
4. THE CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS,
SCOPE OF PHASING, AND PROJECT INTENT PRIOR TO BID SUBMISSION. NO
EXTRA WILL BE ALLOWED DUE TO THE LACK OF KNOWLEDGE OF EXISTING
CONDITIONS TO COORDINATE RELOCATION OF ELECTRICAL SYSTEMS AS
REQUIRED.
5. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.
6. UNLESS OTHERWISE SPECIFIED, REFER TO SINGLE LINE DIAGRAM AND
PANEL SCHEDULE FOR WIRE AND CONDUIT SIZES.
EXISTING SAN. MH RIM=457.78 INV.(A)=446.96(IN) INV.(B)=446.96(IN) INV.(C)=446.85(OUT)
CARBON FILTER TANK 1 CARBON FILTER TANK 2 CARBON FILTER TANK 3
CHLORINE TANKS /
EQUIPMENT
(N) 200A SERVICE
RATED ATS
(N) PPL METER. COORDINATE AND INSTALL ALL
UTILITY SERVICE CABLE, CONDUIT, AND EQUIPMENT
PER PPL REQUIREMENTS.
(N) PANEL LP
(N) TX-1
(N) PANEL HP
(N) CT CABINET
(N) SERVICE RATED
CIRCUIT BREAKER
PROVIDE 2"C
ALONG WALL
FOR (RE) WELL
PUMP CIRCUIT
PROVIDE 3" TRENCHED CONDUIT FOR
(E) WELL PUMP CIRCUIT. REFER TO
E300 FOR CONDUIT AND WIRE SIZE
AND TRENCHING DETAIL.
TRANSITION METAL
CONDUIT TO PVC
SCHEDULE 40 CONDUIT
(N) SCADA PANEL
(N) LC-9
(N) HP-2,4,6
(N) PFAS UNIT MAIN
CONTROL PANEL
(N) LC-7
(N) CHLORINE GENERATOR
VFD PUMP 2
(N) CHLORINE
GENERATOR VFD PUMP 1
(N) LC-2,4,6(N) LC-8,10,12
(N) CHLORINE
ANALYZER
(N) MCT-12 CONTROL
CABINET
(N) LC-5 (N) LC-1,3
(TYP) CLEARANCE
REQUIREMENT
(RE) WELL PUMP VFD
(N) HP-1,3,5
U:
\A cc ou nt s\P
ER
EA
\P
ER
EA
- W ell
T re at m en t C en te r (
PR
A2
5-
)\D
ES
IG
N\
_S
HE
ET
S\
E2
TE
D:
/2 8/
:0
PM
, B Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E201
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
1" = 2'-0"
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF5 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATES; AND OWNER
SHALL INDEMNIFY AND HOLD HARMLESS PENNONI
ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND
EXPENSES ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
00 2' 4'
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
E
LE
C
TR
IC
A
L
L
IG
H
TI
N G
N E
W W
O R
K B
U
IL
D
IN
G P
LA
N
GENERAL ELECTRICAL NEW WORK NOTES:
1. PHASE CONSTRUCTION TO MAINTAIN FACILITY OPERATIONS.
2. COORDINATE ELECTRIC SERVICE RECONNECTION WITH PPL.
3. PHYSICAL SIZE AND LOCATION OF ALL EQUIPMENT SHOWN ON DRAWINGS
IS FOR SCHEMATIC PURPOSES TO SHOW GENERAL ORIENTATION ONLY.
4. THE CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS,
SCOPE OF PHASING, AND PROJECT INTENT PRIOR TO BID SUBMISSION. NO
EXTRA WILL BE ALLOWED DUE TO THE LACK OF KNOWLEDGE OF EXISTING
CONDITIONS TO COORDINATE RELOCATION OF ELECTRICAL SYSTEMS AS
REQUIRED.
5. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES.
6. UNLESS OTHERWISE SPECIFIED, REFER TO SINGLE LINE DIAGRAM AND
PANEL SCHEDULE FOR WIRE AND CONDUIT SIZES.
7. REFER TO M&W PRECAST & CONSTRUCTION SUPPLY DRAWINGS FOR
MORE INFORMATION ON THE PROPOSED PREFABRICATED BUILDING
INCLUDING, BUT NOT LIMITED TO, PRE-INSTALLED LC PANEL, INTERIOR &
EXTERIOR LIGHTING FIXTURES & DEVICES, RECEPTACLES, AND HVAC
EQUIPMENT.
AutoCAD SHX Text
SINK
M cc ou nt s\P
ER
EA
\p er ea
- w ell tr ea tm en t c en te r ( pr a2 5-
)\D
ES
IG
N\ _S
HE
ET
S\ E3
TE
D:
/2
8/
:0
PM
, B
Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E300
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF6 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATES; AND OWNER
SHALL INDEMNIFY AND HOLD HARMLESS PENNONI
ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND
EXPENSES ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
E
LE
C
TR
IC
A
L D
IA
G
R A
M S
D
E
TA
IL
S
E300 N.A
2 NEW WORK ELECTRICAL SINGLE LINE DIAGRAM - NEW BUILDING
E300 N.A
1 DEMOLITION ELECTRICAL SINGLE LINE DIAGRAM - OLD BUILDING
(D) SERVICE ENTRANCE RATED ATS
480Y/277V
3PH
(D) WIRE AND CONDUIT
(E) WIRE AND CONDUIT
PPL INCOMING LINE
(D) TRANSFORMER
M (D) PPL METER &
CT CABINET
(E) GENERATOR
125KVA/100KW
480Y/277V 3P
(D) WIRE AND CONDUIT
(D) WIRE AND CONDUIT
(D) PANEL HP
480Y/277V 200A 3P
(D) WIRE AND CONDUIT
(D) WIRE AND CONDUIT
(D) PANEL LP
120/240V 150A 1P
(D) WIRE AND CONDUIT
(N) ATS
480Y/277V
200A 3PH
3P WITH SOLID NEUTRAL
(N) 3#3/0 + 1#6GND, 3"C
(E) WIRE AND CONDUIT
PPL INCOMING LINE
(N) TX-1
30KVA
PRI 480V, 3PH, 3W
SEC 208Y/120V, 3PH, 4W
M (N) PPL METER &
CT CABINET
(N) 3#3/0 + 1#6GND, 2"C
(N) 3#3/0 + 1#6GND, 3"C
(N) PANEL HP
480Y/277V
200A MCB
3P
(N) 3#3/0 + 1#6GND, 2"C
(N) 3#6 + 1#10GND, 1"C
(N) PANEL LC
208Y/120V
100A MCB
3PH, 4W
(N)4#1 + 1#8GND, 2"C
(E) WIRE AND CONDUIT
NG
1#2GND
DUCT BANK NOTES:
1. CONCRETE SHALL BE 2500 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2. PROVIDE REINFORCING RODS ON TOP OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
3. COVER TO TOP OF ENVELOPE SHALL BE 24" OR AS REQUIRED IN
COORDINATION WITH UTILITY.
4. NON-FERROUS TIE WIRES TO BE IMBEDDED IN DUCT BED
CONCRETE.
5. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC. ALL 90
DEGREE BENDS AND ABOVE GROUND CONDUIT SHALL BE IN
RIGID GALVANIZED STEEL CONDUIT.
GRADE
DUCT [SIZE AS
INDICATED ON DWGS.]
30" MIN. AS PER
UTILITY
NOTES:
1. REMOVE & HAUL OFF-SITE ALL EXCESS SOIL
2. RESTORE ALL SURFACES TO ORIGINAL CONDITION.
3. REFER TO ELECTRICAL SITE PLAN FOR CONDUIT SIZE.
4" SAND
" M
IN
REMOVE AND REPLACE EXISTING VEGETATION.
REPLANT W/ NEW MATERIAL IF NECESSARY.
INSTALL TO CONDITION PRIOR TO DISTURBANCE.
METALLIC WARNING TAPE BURIED 12" BELOW
FINAL GRADE AND DIRECTLY ABOVE CONDUIT
RUNS
PVC SCHEDULE 80 CONDUITS WITH
QUANTITIES AS SHOWN ON ELECTRICAL SITE
PLAN CS1702.
P=POWER
COMPACTED SUBBASE
BACKFILL WITH AASHTO SELECT GRANULAR
MATERIAL COMPACTED IN 4" LIFTS
P
E300 N.A
3 SECONDARY SERVICE DUCTBANK
3"
3"
3"
3"
(E) BREAKER
(E) GENERATOR
125KVA/100KW
480Y/277V 3P
(E) WIRE AND CONDUIT
(E) BREAKER
(D) MAIN SERVICE
CIRCUIT BREAKER
(N) 200AF/200AT
MAIN SERVICE RATED
CIRCUIT BREAKER
NG
1#2GND
BUILDING STRUCTURAL
STEEL
TELECOMMUNICATIONS ROOM
#3/0 W/ 60OV INSULATION
MAIN GROUNDING
ELECTRODE
GROUND BAR
GROUND NEUTRAL
NEUTRAL
GROUND
GROUND NEUTRAL
BUILDING
STRUCTURAL
STEEL
METAL WATER PIPE WITHIN
5 FT OF ENTRANCE
GAS PIPE AND OTHER
METAL PIPING SYSTEMS
IN AND ON THE STRUCTURE
INSTALL GROUNDED (NEUTRAL) CONDUCTOR SAME SIZE AS THE LARGEST PHASE
CONDUCTOR.
BARE OR GALVANIZED REBARS THAT ARE MADE ELECTRICALLY CONTINUOUS
USING COPPER JUMPERS NOT SMALLER THAN THE NEC REQUIRED
GROUNDING ELECTRODE CONDUCTOR AND NOT SMALLER THAN 4 AWG. USE
REINFORCING BARS NOT SMALLER THAN THE FOLLOWING BASED ON THE
TOTAL LENGTH OF THE INTERCONNECTED AND PARALLELED REBARS:
TOTAL LENGTH MINIMUM REBAR SIZE
112 FT 1 3/8" (#11 BAR)
150 FT 1" (#8 BAR)
192 FT 3/4" (#6 BAR)
223 FT 5/8" (#5 BAR)
268 FT 1/2" (#4 BAR)
COMPRESSION SPADE LUGS.
12 NOT USED.
BOND TO GAS PIPE ON THE BUILDING SIDE OF THE GAS METER.
BUILDING WITH STEEL STRUCTURE
GROUND
GROUND NEUTRAL
SEPARATELY DERIVED SYSTEM.
3 3 1
18 INSTALL BONDING JUMBER THAT IS SIZED BASED ON NEC TABLE 250.66 USING
THE LARGEST SERVICE OR SEPARATELY DERIVED SYSTEM PHASE CONDUCTOR.
PAD-MOUNTED
TRANSFORMER (DELTA-WYE
CONNECTION)
480Y/277 VOLT
SERVICE ENTRANCE
EQUIPMENT
480Y/277 VOLT
POWER PANELBOARD
208Y/120 VOLT
LIGHTING PANELBOARD
TRANSFORMER FOR
SEPARATELY DERIVED
SYSTEM (DELTA- WYE
CONNECTION)
480Y/277 VOLT
LIGHTING PANELBOARD
1. CONDUCTOR SIZES SHOWN ARE MINIMUM AND MAY BE LARGER THAN THE MINIMUM SIZES REQUIRED BY NEC.
2. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE
VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.
3. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT.
BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250.66 USING THE SERVICE
PHASE CONDUCTOR SIZE.
4. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250.122 USING THE FEEDER CIRCUIT OVERCURRENT DEVICE SIZE OR THE SEPARATELY DERIVED SYSTEM OVERCURRENT DEVICE SIZE.
5. BOND HOT AND COLD WATER PIPING SYSTEMS.
INSTALL GROUNDING ELECTRODE CONDUCTOR (#3/0), SIZED BASED
ON NEC TABLE 250.66 USING THE SERVICE PHASE CONDUCTOR SIZE.
INSTALL EQUIPMENT GROUNDING CONDUCTOR SIZED BASED ON NEC TABLE
250.122 USING THE FEEDER OVERCURRENT DEVICE SIZE.
REFER TO SLD DIAGRAM FOR EQUIPMENT GROUNDING CONDUCTOR WIRE SIZE.
INSTALL GROUNDING ELECTRODE CONDUCTOR THAT IS SIZED BASED ON
NEC TABLE 250.66 USING THE SEPARATELY DERIVED SYSTEM PHASE
CONDUCTOR SIZE.
BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE
CONCRETE-ENCASED MAIN GROUNDING ELECTRODE. USE
COMPRESSION CONNECTORS THAT MEET IEEE 837 REQUIREMENTS OR
USE EXOTHERMIC WELDS.
INSTALL A "MAIN GROUND ELECTRODE GROUND BAR" FOR SINGLE
POINT GROUNDING. LOCATE AT AN ACCESSIBLE AND VISIBLE POINT
NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE CONNECTIONS TO THE
GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET
IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION TO THE GROUND
BAR.
USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF
BUILDING STRUCTURAL STEEL IF THE FIRST OVERCURRENT DEVICE FOR
THE SEPARATELY DERIVED SYSTEM IS WITHIN 50 FEET OF THE "MAIN
GROUNDING ELECTRODE GROUND BAR".
INSTALL A COPPER GROUNDING BAR IN EACH TELECOMMUNICATIONS
ROOM. CONNECT TO THE "MAIN GROUNDING ELECTRODE GROUND
BAR" USING 600V INSULATED 3/0 AWG COPPER CABLE AND
INSTALL GROUNDED (NEUTRAL) CONDUCTOR THAT IS NOT LESS THAN THE
PHASE CONDUCTOR AMPACITY. REFER TO SHEET E-601 FOR WIRE SIZE.
INSTALL BONDING CONDUCTOR THAT IS SIZED BASED ON NEC
TABLE 250.66 USING THE SERVICE OR SEPARATELY-DERIVED SYSTEM
PHASE CONDUCTOR SIZE.
INSTALL IRREVERSIBLE COMPRESSION CONNECTOR WITH TAMPER-PROOF
HARDWARE.
BOND TO METAL PIPING SYSTEMS IN THE AREA SERVED BY THE
INSTALL A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE
BUILDING FOUNDATION AROUND THE ENTIRE PERIMETER OF THE
BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD OF THE
FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE
EITHER OF THE FOLLOWING MATERIALS FOR THE ELECTRODE:
BARE COPPER CABLE NOT SMALLER THAN THE GROUNDING ELECTRODE
CONDUCTOR REQUIRED BY THE NEC AND NOT SMALLER THAN 4 AWG.
E300 N.A
4 GROUNDING SYSTEM DETAIL
E300 N.A
3 FEEDER CONDUIT TRENCH DETAIL
METALLIC WARNING TAPE BURIED
12" BELOW FINAL GRADE AND
DIRECTLY ABOVE CONDUIT RUNS
NOTE: PANEL LC IS BEING PROVIDED AS PART
OF THE PRE-FABRICATED BUILDING
cc ou nt s\P
ER
EA
\p er ea
- w ell tr ea tm en t c en te r ( pr a2 5-
)\D
ES
IG
N\ _S
HE
ET
S\ E3
TE
D:
/2
8/
:0
PM
, B
Y:
H ale y Z ur
ST
YL
E:
P en no ni
NC
E301
Y
N O
D
A
TE
R E
V
IS
IO
N
S
PEREA25001
HSZ
07/27/2026
JPR
SHEET
APPROVED BY
OF7 7
DRAWN BY
DRAWING SCALE
DATE
PROJECT
ALL DOCUMENTS PREPARED BY PENNONI ASSOCIATES
ARE INSTRUMENTS OF SERVICE IN RESPECT OF THE
PROJECT. THEY ARE NOT INTENDED OR REPRESENTED
TO BE SUITABLE FOR REUSE BY OWNER OR OTHERS ON
THE EXTENSIONS OF THE PROJECT OR ON ANY OTHER
PROJECT. ANY REUSE WITHOUT WRITTEN VERIFICATION
OR ADAPTATION BY PENNONI ASSOCIATES FOR THE
SPECIFIC PURPOSE INTENDED WILL BE AT OWNERS
SOLE RISK AND WITHOUT LIABILITY OR LEGAL
EXPOSURE TO PENNONI ASSOCIATES; AND OWNER
SHALL INDEMNIFY AND HOLD HARMLESS PENNONI
ASSOCIATES FROM ALL CLAIMS, DAMAGES, LOSSES AND
EXPENSES ARISING OUT OF OR RESULTING THEREFROM.
A
LL
D
IM
E N
S
IO
N S
M U
S T
B E
V E
R
IF
IE
D
B Y
C O
N
TR
A C
TO
R
A N
D O
W N
E R
M U
S T
B E
N O
TI
FI
E D
O F
A N
Y D
IS
C
R E
P A
N C
IE
S
B E
FO
R
E P
R O
C E
E D
IN
G
W
IT
H W
O R
K
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
-2
-5
LL
P
R O
P O
S E
D E
LE
C
TR
IC
A L
P
LA
N S
T H
R E
E M
IL
E
R U
N R
O A
D
P E
R K
A S
IE
, P
A
R
ID
G E
R O
A D
S E
LL
E
R S
V
IL
LE
, P
A
P E
R K
A S
IE
R
E G
IO
N
A L
A U
TH
O
R
IT
Y
E
LE
C
TR
IC
A
L S
C H
E D
U
LE
S
Notes:
Demand Current: 81 A Demand Load: 68 kVA
Connected Current: 81 A Connected Load: 68 kVA
Panel Totals Load Classification Connected Factor Demand
Connected Current: 81 A 81 A 81 A Connected Load: 23 kVA 23 kVA 23 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 18013 4537 6
3 18013 4537 4
(RE) WELL PUMP
VFD
3-#2, 1-#8 90 3
18013 4537
1 3 50 3-#6, 1-#10 (N) TX-1
Ckt Description Wire Size Trip (A) Poles FN/Note Phase A
Load (VA) Phase B
Load (VA) Phase C
Load (VA) FN/Note Poles Trip (A) Wire Size Description Ckt
Enclosure: NEMA 1 Mounting: Surface Features &
Modifications: -
Supply: Feed-Thru Lugs: No SCCR: 65 kA Location: Neutral: 100% Mains FN/Note: -
Bus Rating: 250 A Mains Rating: 200 A Panelboard: HP Voltage: 480 V, 3Ø, 4W Mains Type: MCB
PANEL IS INCLUDED IN PREFABRICATED BUILDING. CONTRACTOR TO NOT PURCHASE SEPARATELY. CIRCUITS ASSOCIATED WITH THE PRE-FABRICATED BUILDING ARE NOT SHOWN. PER BASE SCOPE DRAWINGS, THE SUM OF ALL LOADS ASSOCIATED WITH THE PREFABRICATED BUILDING, INCLUDING LIGHTING, RECEPTACLES, AND HVAC, ARE ESTIMATED TO BE NO MORE THAN 40A, OR 14.4KVA.
Notes:
Demand Current: 37 A Demand Load: 13 kVA
Connected Current: 37 A Connected Load: 13 kVA
Panel Totals Load Classification Connected Factor Demand
Connected Current: 58 A 34 A 23 A Connected Load: 7 kVA 4 kVA 3 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 (RE) GENERATOR
AUXILIARY POWER 1-#12, 1-#12, 1-#12 20 1 500 375 12
9 (N) SCADA PANEL 1-#12, 1-#12, 1-#12 20 1 0 375 10
7 (N) PFAS UNIT MAIN
CONTROL PANEL 1-#10, 1-#10, 1-#10 30 1 2916 375
3 15 3-#12, 1-#12 (N) CHLORINE
GENERATOR VFD PUMP 1
5 (N) CHLORINE ANALYZER 1-#12, 1-#12, 1-#12 20 1 1500 375 6
3 3120 375 4
(N) MCT-12 CONTROL
CABINET 2-#8, 1-#10 40 2
3120 375
3 15 3-#12, 1-#12 (N) CHLORINE
GENERATOR VFD PUMP 1
Ckt Description Wire Size Trip (A) Poles FN/Note Phase A
Load (VA) Phase B
Load (VA) Phase C
Load (VA) FN/Note Poles Trip (A) Wire Size Description Ckt
Enclosure: NEMA 1 Mounting: Surface Features &
Modifications: -
Supply: Feed-Thru Lugs: No SCCR: 22 kA Location: Neutral: 100% Mains FN/Note: -
Bus Rating: 100 A Mains Rating: 100 A Panelboard: LC Voltage: 208Y/120V, 3Ø, 4W Mains Type: MCB
1. AN ADDITIONAL 14.4KVA SPLIT BETWEEN EACH PHASE HAS BEEN INCLUDED IN THE TRANSFORMER LOAD TO TAKE INTO ACCOUNT THE ESTIMATED PREFABRICATED BUILDING LIGHTING, RECEPTACLE, AND HVAC LOADS.
3 20 3-#12, 1-#12 (N) SPD
| Sheets and Views |
| E001-COVER SHEET |
| E001-INDEX SHEET |
| E100-ELECTRICAL DEMOLITION SITE PLAN |
| E200-ELECTRICAL NEW WORK SITE PLAN |
| E201-ELECTRICAL & LIGHTING NEW WORK BUILDING PLAN |
| E300-Diagrams & Details |
| E300-Schedules |
File details come from the government source that posted it. Updated .