1-PRA Standard Water Details REV 2026-02-24.pdf
PDF 4 MB Posted
- Attached to
- PRA 25-01 WELL 7 TREATMENT CENTER
- Solicitation number
- Not on record
- Issued by
- Bucks County, Pennsylvania
About this file
This is a Standard Water Supply System Details document prepared by Pennoni Associates Inc. for the Perkasie Regional Authority in Bucks County, Pennsylvania, containing comprehensive technical specifications and design standards for water system infrastructure. The document provides detailed specifications and installation requirements for various water system components including fire hydrants, blow-off assemblies, yard hydrants, air release valve manholes, horizontal and vertical thrust blocking, tapping sleeves and valves, residential service line connections, meter setting requirements for both residential and non-residential applications, pressure testing schematics, residential service/sprinkler line connections, valve box alignment devices, and residential meter pit installations. All specifications reference AWWA standards, PENNDOT materials and methods, and specific equipment manufacturers and models approved for use within the PRA system. The document was originally prepared on April 8, 1996, with most recent revisions dated February 24, 2026, and includes detailed technical drawings with dimensions, material specifications, and installation procedures for each component type.
The specifications establish rigid technical requirements for all water infrastructure components, including concrete compressive strength minimums of 2,500 to 3,300 PSI, specific soil bearing capacity considerations ranging from 0.75 to 15 tons per square foot depending on soil composition, and thrust block design standards based on 100, 150, 200, and 250 PSI working pressures. Service line requirements mandate SDR-9 ASTM 2737 polytubing with minimum 3/4-inch diameter and no underground splices or sweat joints, with 4-foot minimum cover depth and 40-inch minimum cover for meter installations. The document specifies approved manufacturers for all components, including Kennedy Guardian and American Flow Control hydrants meeting AWWA Standard C502, Watts backflow preventers and pressure reducers, Ford curb stops and valves, and Mueller/McDonald corporation stops. Pressure reducing valves are required where service pressure exceeds 65 PSI for residential applications or 75 PSI for non-residential applications, and the Authority Engineer must review any service line exceeding 80 feet in length or where available service pressure falls below 45 PSI.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PERKASIE REGIONAL AUTHORITY
BUCKS COUNTY, PENNSYLVANIA
WATER SUPPLY
SYSTEM DETAILS
PREPARED BY:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960 T 215-257-5711 F 215-257-5766
REVISED 2/24/2026
2'-0", OR AS
DIRECTED BY THE
ENGINEER
WHERE THERE IS
NO CURB
SIDEWALK,
REQUIRED ADA,
STATE, AND
LOCAL WIDTH
8"
1' -9
M
IN
H E
IG
H
T
.5
.5
A A
T*
5' WIDE ZONE
OF
UNDISTURBED
EARTH, NO
UTILITIES, OR
AS REQUIRED
BY ENGINEER
FIRE HYDRANT
T*
3' -6
" M
IN
. L E
N G
TH
1' -9
1'
-9
UNDISTURBED
EARTH (TYP.)
5' TYPICAL MINIMUM
3" WITH -1"
TO +3"
ALLOWANCE
HYDRANT TEE
REQUIRED
6" MJ GATE VALVE
5-1/4" C.I. VALVE
BOX SLIP TYPE
WITH BOXLOK
DEVICE
CENTERLINE
WATER MAIN
A S
D E
TE
R
M
IN
E D
B Y
D E
P
TH
O F
M A
IN
REACTION
BACKING PER
DETAIL PRA-W05
GEOTEXTILE PLACED
ON TOP AND SIDES
5 C.F. 2B STONE
TIE RODS @ 3
AND 9 O'CLOCK
4"x8"x16" SOLID PRECAST BLOCK
8 MIL POLYETHYLENE FILM AND THRUST BLOCK
T* = GREATER OF THE
DISTANCE TO UNDISTURBED
EARTH OR 2.25 FEET
SECTION A-A
STANDARD FIRE HYDRANT DETAIL
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:1
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
FIRE HYDRANT
PERKASIE REGIONAL AUTHORITY PRA-W01 1 OF 2
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
DATE:
REVISED 5/13/2025
FIRE HYDRANT DESIGN, PURCHASE, AND INSTALLATION GENERAL NOTES:
1. DESIGN OF THE THRUST BLOCKS ARE BASED ON THE WATER TABLE BEING BELOW THE BLOCK. THE HORIZONTAL BEARING STRENGTH CHOSEN FOR DESIGN IS 2,000 PSF AND REPRESENTS A CONSERVATIVE VALUE FOR SANDY SILT SOILS. CONTACT THE AUTHORITY ENGINEER FOR A SPECIAL DESIGN IF THE WATER
TABLE IS HIGHER, OR THE SOILS ARE SILT, SOFT CLAY, OR MUCK.
2. THE SOIL (ZONE OF INFLUENCE) BEHIND THE HYDRANT THRUST BLOCK IS TO REMAIN UNDISTURBED AND
FREE OF OTHER UTILITIES. CONTACT PRA'S ENGINEER FOR GUIDANCE.
3. FOR PIPE BEDDING AND ENVELOPE DETAILS, REFER TO DETAIL PRA-S020. FOR TRENCH BACKFILL DETAILS, REFER TO DETAIL PRA-S021.
4. HYDRANTS SHALL MEET AWWA STANDARD C502 AND SHALL BE EITHER:
A. KENNEDY GUARDIAN MODEL K81D WITH STANDARD UPPER BARREL CONFIGURATION AND OPTIONAL 6"
MECHANICAL JOINT INLET CONNECTION.
B. AMERICAN FLOW CONTROL 5-1/4 AMERICAN-DARLING B-62-B-5 TRAFFIC MODEL HYDRANT, OPEN
DIRECTION IS LEFT (C.C.W.).
5. HYDRANTS SHALL BE ORDERED TO THE DEPTH OF BURY REQUIRED AT THE PROPOSED LOCATIONS BASED ON THE WATER MAIN DEPTH AND THE FINISHED GRADE ELEVATION. EXTENSIONS ARE NOT PERMITTED.
6. THE ABOVE GROUND FINISH EXTERIOR COATING SHALL BE YELLOW. CAP CHAINS ARE NOT REQUIRED.
7. THE PIPE TO THE HYDRANT SHALL BE 6" DIP WITH NO BENDS. THE HYDRANT SHALL BE INSTALLED IN THE
TRUE VERTICAL POSITION. THE PUMPER NOZZLE SHALL FACE THE STREET.
8. TIE RODS SHALL BE 3/4" ASTM A307 STEEL WITH DUCT LUGS, A563 HEX OR HEAVY HEX NUTS AND F844 WASHERS. COAT ALL COMPONENTS WITH TWO COATS (8 MILS EACH, DMT) OF RUST-OLEUM C9578 SYSTEM COAL TAR EPOXY. FOLLOW MANUFACTURER'S REQUIREMENTS, INCLUDING A RECOAT TIME OF 16-25 HOURS, AND A HANDLE TIME OF 18-36 HOURS. ASTM F2329 HOT DIPPED GALVANIZED RODS AND
COMPONENTS MAY BE USED IN PLACE OF COATED RODS AND COMPONENTS.
9. IF MORE THAN ONE SECTION OF PIPE IS INSTALLED BETWEEN THE HYDRANT VALVE AND THE HYDRANT, THEN ALL PIPE SLIP-ON JOINTS SHALL BE RESTRAINED WITH EBAA IRON SERIES 1700 RESTRAINT
HARNESSES. TIE RODS WILL NOT BE REQUIRED.
10. EIGHT MIL POLYETHYLENE FILM SHALL BE INSTALLED TO PROTECT COMPONENTS FROM THE CONCRETE
AND TO PROTECT THE DRAIN PORTS.
11. CONCRETE SHALL BE CLASS A, 3,300 PSI. GEOTEXTILE SHALL BE PENNDOT NON-WOVEN, CLASS 4, TYPE A.
STANDARD FIRE HYDRANT DETAIL
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:4
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
FIRE HYDRANT
PERKASIE REGIONAL AUTHORITY PRA-W01 2 OF 2
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
NOTE:
VALVE AND VALVE
BOXES TO BE SET
ON 4" 2A MODIFIED
AND BACKFILL AT
LEAST 4" ABOVE
TOP OF WATER MAIN
EXISTING GRADE
CURB BOX TOP AND COVER
7/16" DRAIN HOLE
2" GALV. PIPE
NUT AND 1 1/2" WASHER
UNDISTURBED EARTH
PROVIDE CONCRETE BACKING
ON UNDISTURBED EARTH
2" ORISEAL
VALVE
2" GALV.
ELBOW
DRILL AND TAP AT PIPE
INVERT TO ACCEPT 2" GALV.
NIPPLE
2"x12" GALV. PIPE
PROVIDE SOCKET CLAMP (ITT GRINNEL FIG. 595 OR
EQUAL) AND EXTEND ALL-THREAD TIE RODS INTO
CONCRETE BACKING. ALTERNATIVE TO SOCKET
CLAMP, PROVIDE ONE ALL-THREAD TIE ROD THROUGH
LUG HOLES ON BOTH SIDES OF RISER.
M.J. PIPE, D.I.
MAIN SIZE
VARIABLE
C.I. PLUG (M.J.) TO
MATCH MAIN SIZE &
TYPE OF JOINT USED
ALL THREAD TIE ROD: ON
BOTH SIDES OF RISER
CURB BOX (COMPLETE) W/
ENLARGED BASE
6"
3" MIN.
5'-6" ±
STANDARD BLOW-OFF DETAIL
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:0
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
STANDARD BLOW-OFF
PERKASIE REGIONAL AUTHORITY PRA-W02
SRT
4/04/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
" M
IN
4" PRECAST CONCRETE
SPLASH PAD
3/4" FREEZELESS YARD
HYDRANT IOWA MODEL
Y34 BY WOODFORD
MFG. CO., OR EQUAL
LINE SIDES AND BOTTOM OF
HOLE W/ GEOTEXTILE FABRIC
BEFORE PLACING
NO. 2B STONE
FITTING TO ADAPT TO YARD
HYDRANT
ADAPTER COUPLING AND 90°
ELBOW WITH COMPRESSION
FITTINGS
3/4" SDR-9 POLYTUBE
4' C
O
VE
R (T
YP
IC
AL
YARD HYDRANT DETAIL
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
3:
:5
PM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
YARD HYDRANT DETAIL
PERKASIE REGIONAL AUTHORITY PRA-W03
SRT
3/7/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
REVISED 7/30/2025
5" 5"
2' -0
4' -0
7 1/2"± CLEARANCE
WITH 4' PIPE COVER
18" 12"
" F
O R
2"
P
IP
E
" F
O R
" T
O
0" P
IP
E
3" MIN.
PIPE
O.D.3" MIN.
6" MAX.
7"
12"
AS REQUIRED FOR
DEPTH OF THE
PIPE AND 3"
CLEARANCE FROM
FLOOR
B
4'-0" MIN.
FI
N
IS
H
E D
G R
A D
E A
B
FI
E
LD
C
U T
W E
E P
H O
LE
S
IN
S
TA
LL
" P O
LY
U
R E
TH
A
N E
FO
A
M
K
S H
E
LF
S
LO
P E
S
LO
P E
C 5 3/
4" P
R O
JE
C
TI
O
N
MC
L
A D
D E
R R
U N
G S
S E
E S
E C
TI
O
N A
L K J
I
H G
F
E D
U N
D
IS
TU
R
B E
D E
A R
TH
6"
MIN.
P E
N N
D O
T 2A
S
TO
N E
S E
C
TI
O N
A S
E C
TI
O
N B
A
S
TA
N D
A R
D M
A N
H O
LE
F
R A
M E
A N
D C
O V
E R
(S E
E P
R A
D E
TA
IL
B
S
E A
LI
N
G S
Y S
TE
M
S , I
N C
. M A
N H
O
LE
IN
S
E R
T, " D E
E P
F O
R
IN
S U
LA
TI
O N
C
LA
D
D E
R R
U N
G , M
.A . I
N D
U S
TR
IE
S P
S 4-
B D
A
IR
R
E
LE
A S
E V
A
LV
E
C R
IS
P
IN
U
L2
W
IT
H P
R O
TE
C
TO
P
E
2" H
E X
N
IP
P
LE
" L
O N
G , 3
O
R
S
TA
IN
LE
S
S S
TE
E
L F
- 2 " B
A
LL
C O
R P
O R
A
TI
O N
S
TO
P M x F
M G
TA
P P
E D
(2
F
LA
N G
E
H
1/ 8"
G A
S K
E T
I - C
O M
P A
C T
M J x
FE
D U
C
TI
LE
IR
O N
T E
E J
- E B
A A
M E
G A
LU
G
(2
K
P O
LY
U
R E
TH
A
N E
F O
A M
IN
S
U
LA
TI
O
N (A
N N
U
LA
R O
P E
N
IN
G
M A
N H
O
LE
IN
S
E R
T) L
- 2 A
C O
A R
S E
A G
G R
E G
A
TE
M
4' -0
" D O
G H
O U
S E
M A
N H
O
LE
N
" I
.D . M
IN
IM
U M
G R
A D
E R
IN
G
IF
N
E E
D E
D
N
A
TY
P
IC
A
L A
IR
R
E
LE
A S
E V
A
LV
E A
N D
D O
G H
O U
S E
M A
N H
O
LE
O
FF
R
O A
D N
O T
TO
S
C A
LE
M:\AUTHORITIY CLIENTS\PERKASIE\WATER DETAILS\ALL PRA WATER DETAILS 2025.DWG
PLOTTED: 7/18/2025 9:42:05 AM, BY: TINA CARTER PLOTSTYLE: PENNONI NCS.STB, PROJECT STATUS: ----
P R
E P
A R
E D
F O
R
PE
N
N O
N I A
SS
O
C
IA
TE
S
IN
C
R id ge
R oa d, S ui te
Se lle rs vi lle
, P A
T
-2
-5
F
-2
-5
AI
R
R
EL
EA
SE
M
AN
H O
LE
PE
RK
AS
IE
RE
GI
ON
AL
AU
TH
OR
ITY
P
R A
-W
S R
T
3/ 8/
JA
R
D E
S
IG
N E
D B
Y
C H
E C
K E
D B
Y
D R
A W
IN
G
N O
D A
TE
R E
V
IS
E D
/1
3/
HORIZONTAL REACTION BACKING
NOT TO SCALE
C D
B E
A 2'-0"
F
UNDISTURBED
EARTH (TYP.)
PLAN 45° BEND
PLAN 22 1/2° BEND
PLAN 90° BEND
PLAN 11 1/4° BEND
PLAN TEE SECTION
NOTE: PROVIDE PLASTIC COVERING TO PROTECT
PIPE JOINTS FROM CONCRETE.
DESIGN
PRESSURE
PIPE
DIAMETER
REACTION BACKING DIMENSIONS
A B C D E F
150 PSI
16 5'-6" 7'-9" 4'-2" 2'-2" ------ 3'-4"
12 4'-2" 5'-11" 3'-3" 1'-8" ------ 2'-6"
8 3'-0" 4'-3" 2'-4" 1'-2" ------ 1'-8"
6 2'-2" 3'-4" 1'-10" 0'-11" ------ 1'-3"
200 PSI
16 7'-3" 10'-3" 5'-7" 2'-10" 1'-6" 3'-4"
12 5'-7" 7'-11" 4'-3" 2'-2" 1'-2" 2'-6"
8 4'-0" 5'-7" 3'-1" 1'-7" 0'-10" 1'-8"
6 3'-1" 4'-5" 2'-5" 1'-3" 0'-8" 1'-3"
250 PSI
16 9'-3" 13'-2" 7'-1" 3'-6" 2'-3" 3'-4"
12 6'-4" 8'-11" 5'-4" 3'-5" 1'-9" 2'-6"
8 5'-0" 6'-11" 3'-10" 1'-11" 1'-3" 1'-8"
6 3'-10" 5'-6" 3'-9" 1'-10" 1'-1" 1'-3"
CONCRETE BRACING
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:2
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
HORIZONTAL REACTION BACKING
PERKASIE REGIONAL AUTHORITY PRA-W05
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
NOTES:
1. ALL CONCRETE SHALL HAVE A MIN. COMPRESSIVE STRENGTH OF 2500 P.S.I.
2. ALL FITTINGS AND JOINTS SHALL BE COVERED WITH POLYETHYLENE FILM BEFORE PLACING CONCRETE.
3. PAINT ALL EXPOSED STEEL WITH TWO COATS OF VALDURA PAINT OR APPROVED EQUAL.
4. FOR THE REQUIRED BEARING SURFACE SEE STANDARD DETAIL.
BEND
MEGA-LUG RETAINER
GLAND (TYP.)
BEARING
SURFACE
BEARING SURFACE REQUIRED - SQ. FT.
HORIZONTAL THRUST BLOCKING AND VERTICAL THRUST DOWNWARD
100 P.S.I. WORKING PRESSURE
PIPE SIZE 6" & 8" 10" & 12" 16" 18" 20" 24"
TYPE OF BEARING MATERIAL AND
ALLOWABLE LOAD
DEGREE OF BEND OR DEFLECTION
22.5° 45° 90° D.E. 22.5° 45° 90° D.E. 22.5° 45° 90° D.E. 22.5° 45° 90° D.E.
SAND 0.75 TON/SQ. FT. 3.4 6.0 11.0 6.4 6.7 12.8 23.4 14.2 14.8 28.8 52.9 34.4 26.1 48.3 89.7 64.0
SOFT CLAY 1 TON/SQ. FT. 2.6 4.6 8.2 4.8 5.0 9.6 17.5 10.7 11.2 21.7 39.7 28.2 19.6 36.3 67.3 48.0
SAND & GRAVEL 2 TON/SQ. FT. 1.3 2.3 4.1 2.4 2.5 4.8 8.8 5.3 5.6 10.8 20.0 14.1 9.8 13.1 33.6 24.0
CLAY 4 TON/SQ. FT. 1.0 1.2 2.1 1.3 1.3 2.4 4.4 2.7 2.8 5.4 10.0 7.2 4.9 9.1 16.8 12.0
SOFT ROCK 5 TON/SQ. FT. 1.0 1.0 1.6 1.0 1.0 1.9 3.5 2.2 1.6 4.4 8.0 5.7 3.9 7.3 13.5 9.6
ROCK 15 TON/SQ. FT. - - 1.0 0.4 - 1.0 1.2 0.8 1.0 1.4 2.6 1.9 1.3 2.4 4.5 3.2
TYPICAL SECTION
VERTICAL THRUST DOWNWARD
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:4
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
DOWNWARD THRUST BLOCK
PERKASIE REGIONAL AUTHORITY PRA-W06
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
CONCRETE BLOCKING DIMENSIONS, VERTICAL THRUST
UPWARD - 100 P.S.I. WORKING PRESSURE
PIPE
SIZE
LENGTH WIDTH DEPTH
11.25° 22.5° 45° 11.25° 22.5° 45° 11.25° 22.5° 45°
6" & 8" 3' 4' 6' 3' 4' 6' 3' 4' 6'
10" & 12" 3.5' 4' 7' 3.5' 4' 7' 3.5' 4' 7'
14" & 16" 4' 6' 9' 4' 6' 9' 4' 6' 9'
18" & 20" 5' 6.5' 11.5' 5' 6.5' 11.5' 5' 6.5' 11.5'
24" 5' 9' 12.5' 5' 9' 12.5' 5' 9' 12.5'
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:0
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
UPWARD THRUST BLOCK
PERKASIE REGIONAL AUTHORITY PRA-W07
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
DATE:
REVISED 5/13/2025
MEGA-LUG
RETAINER
GLAND (TYP.)
BEND
A
A
2" MIN.2" MIN.
8"
4" MIN.
2.
0'
M
IN
1/4" x 3" WIDE PIPE STRAP
(ASPHALT COATED) - TYP. 2 PLACES
3/4" ANCHOR BOLT (TYP.)
FILL BETWEEN PIPE AND REACTION
BLOCK WITH A NON-SHRINK GROUT.
FLANGES AND BOLTS ARE TO
REMAIN FREE OF CONCRETE
SECTION A-A
LENGTH
WIDTH
NOTES:
1. ALL CONCRETE SHALL BE PENNDOT CLASS A.
2. ALL REINFORCING STEEL SHALL BE DEFORMED BARS U-SHAPED AROUND PIPE.
3. ALL FITTINGS AND JOINTS SHALL BE COVERED WITH POLYETHYLENE FILM BEFORE PLACING CONCRETE.
4. PAINT ALL EXPOSED STEEL WITH TWO COATS OF VALDURA PAINT OR APPROVED EQUAL.
NOT TO SCALE
TYPICAL SECTION
VERTICAL THRUST UPWARD
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:2
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
TAPPING SLEEVE & VALVE
PERKASIE REGIONAL AUTHORITY PRA-W08
SRT
4/04/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
DATE:
REVISED 5/13/2025
* SIZE IN FIELD, MIN. OF 4 SF. BEARING AREA
UNDISTURBED
EARTH (TYP.)
HIGH EARLY STRENGTH CONCRETE
POURED AROUND SLEEVE AFTER TAP IS
MADE AND INSPECTED FOR NO LEAKAGE
TAPPING VALVE
H.E.S.
CONCRETE
TAPPING VALVE
UNDISTURBED
EARTH
TAPPING SLEEVE & VALVE
45°
PENNDOT 2A IN R/W, APPROVED BACKFILL
MATERIAL OUTSIDE R/W
AASHTO #10
SERVICE LINE
6" 6"
NOTES :
1. WET TAPPING UNDER NORMAL LINE PRESSURE IS REQUIRED. THERE ARE TO BE NO SPLICES IN THE SERVICE LINE.
2. CORPORATION STOPS: MULLER B-25008, OR McDONALD 4701B-22, WITH INSERT-51-Q SOLID TUBULAR 304 SS INSERT STIFFENERS, OR APPROVED EQUAL.
3. CURB STOPS: MULLER B-25209, OR McDONALD 6100-22, WITH INSERT-51-Q SOLID TUBULAR 304 SS INSERT STIFFENERS, OR
APPROVED EQUAL.
4. CURB BOX: MUELLER H-10306, OR McDONALD 5604, OR FORD EA2-45-50, OR EQUAL.
5. LID WITH CENTER, REMOVABLE, PENTAGONAL PLUG: MUELLER 89375, OR McDONALD 5614L.
6. CORPORATION STOP AND CURB STOP TO HAVE COMPRESSION FITTINGS. FLARE FITTINGS NOT PERMITTED.
7. IF THE TOTAL LENGTH OF THE POLYTUBE SERVICE LINE FROM THE WATER MAIN TO JUST INSIDE THE RESIDENCE IS MORE THAN
80 FEET, OR THE PRA AVAILABLE SERVICE PRESSURE IS LESS THAN 45 PSI, THEN THE AUTHORITY ENGINEER MUST REVIEW.
NOTE:
PROVIDE 6" (AASHTO #10) SCREENINGS
ABOVE AND BELOW SERVICE LINE
VARIABLE
VA
R
IA
BL
E
4' M
IN
. C
O
VE
R
VA
R
IA
BL
E 4'
M
IN
. C O
VE
R
SERVICE LINE SDR-9 CTS ASTM
2737 POLYTUBE (MIN. 3/4")
CUSTOMER TO CONNECT AT THIS POINT
BRICK OR CONCRETE BLOCK
CURB STOP
CORPORATION
STOP
SERVICE LINE SDR-9 CTS ASTM
2737 POLYTUBE (MIN. 3/4")
WATER MAIN
PROVIDE SLACK SDR-9 CTS
ASTM 2737 POLYTUBE FOR
PROTECTION AGAINST PULLING
CORPORATION OUT OF MAIN
CURB BOX
COMPLETE W/
STATIONARY ROD
2'-0" LONG
CURB BOX LID TO BE CAST
IRON WITH THE WORD "WATER"
CAST INTEGRALLY ON TOP
ROADWAY
ONE CONTINUOUS PIECE
FROM CORPORATION STOP
TO CURB STOP REQUIRED
24" FROM CURB FACE
30" FROM EDGE OF PAVING
OR AS DIRECTED
BY ENGINEER
M
AI
N
TA
IN
'-0 " M
IN
TYPICAL RESIDENTIAL SERVICE LINE CONNECTION
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
8/ 7/
:4
3:
A M, B
Y:
TI
NA
C
AR
TE
R
PL
OT
ST
YL
E:
PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
TYPICAL RESIDENTIAL SERVICE LINE CONNECTION
PERKASIE REGIONAL AUTHORITY PRA-W09
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
3/ 4"
O R
" S
TO
P
W
AS
TE
V
AL
VE
#7 W
AT
TS
B
AC
KF
LO
W P
R
EV
EN
TE
R
W
AT
TS
U
B5 P
R
ES
SU
R
E R
ED
U
C
ER
HOUSESTREET
3/ 4"
O R
" F
EM
AL
E
AD
AP
TE
R
3/ 4"
O R
" F
EM
AL
E
AD
AP
TE
R
3/ 4"
O R
" B
AL
L
VA
LV
E
GRADE
W
AL
L
GRADE
FLOOR
GENERAL NOTES:
1. NOTIFY AUTHORITY AT 215-257-3654 WHEN WATER SERVICE IS
READY FOR INSPECTION AND TESTING. DO NOT BACKFILL ANY
PORTION OF TRENCH PRIOR TO APPROVAL. 24 HOURS NOTICE
REQUIRED.
2. WATER AUTHORITY WILL SUPPLY 5/8"x5/8" SR BRONZE REMOTE
TYPE METER AND REMOTE METER READING.
3. PRESSURE REDUCING VALVE IS REQUIRED WHERE PRESSURE
IS GREATER THAN 65 PSI. OWNER/DEVELOPER SHALL PROVIDE
THE PRESSURE REDUCING VALVE.
4. METER LOCATION MUST BE APPROVED BY THE AUTHORITY.
5. ALL SERVICE LINES ARE TO BE SDR-9 ASTM 2737 POLYTUBING
WITH NO SWEAT JOINTS OR COUPLINGS UNDERGROUND.
*6. WATTS NUMBER 007 (LEAD FREE) BACKFLOW PREVENTER
SHALL BE PROVIDED BY THE OWNER/ DEVELOPER WHEN
REQUIRED BY PRA.
**7. PRESSURE REDUCER VALVE TO BE WATTS UB5 - LEAD FREE
12" FACE
TO FACE
OR AS REQ'D
FOR METER
#6 MIN. GROUND
JUMPER
FRONT VIEW OF SETTING
FOR SERVICE LINES INSTALLED
IN SHEDS, THE 3/4" OR 1"
SERVICE SHALL BE INSTALLED
THROUGH A CORE-DRILLED AND
SEALED FLOOR OPENING
3/4" OR 1"
SERVICE
(TYPICAL)
SERVICE LINE INSTALLED
WITHIN PVC SLEEVE (I) PIPE
DIA. MAX. LARGER THAN
SERVICE LINE (SEALED)
3/4" OR 1"
BALL VALVE
MIN. 12" FROM
OUTSIDE WALL
3/4" OR 1"
BALL VALVE
MIN. BEFORE BALL
VALVE 6" (MAX. 12")
" M
IN
C O
VE
R
" M
IN
C O
VE
R
BASEMENT SERVICE THROUGH FLOOR SERVICE
3/4" OR 1"
SERVICE
(TYPICAL)
SERVICE LINE INSTALLED
WITHIN PVC SLEEVE (I) PIPE
DIA. MAX. LARGER THAN
SERVICE LINE (SEALED)
RESIDENTIAL METER SETTING REQUIREMENTS
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
8/ 7/
:4
7:
A M, B
Y:
TI
NA
C
AR
TE
R
PL
OT
ST
YL
E:
PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
RESIDENTIAL METER SETTING REQUIREMENTS
PERKASIE REGIONAL AUTHORITY PRA-W10
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
W
AL
L
GENERAL NOTES:
1. NOTIFY AUTHORITY AT 257-3654 WHEN WATER
SERVICE IS READY FOR INSPECTION AND TESTING.
DO NOT BACKFILL ANY PORTION OF TRENCH PRIOR
TO APPROVAL.
2. WATER AUTHORITY WILL SUPPLY METER AND REMOTE
METER READING PAD AND THE BACKFLOW
PREVENTER FOR ALL SIZES UP TO AND INCLUDING 1".
3. PRESSURE REDUCING VALVE IS REQUIRED WHERE
PRESSURE IS GREATER THAN 75 PSI.
4. METER LOCATION MUST BE APPROVED BY THE
AUTHORITY.
5. ALL SERVICE LINES ARE TO BE SDR-9 ASTM 2737
POLYTUBING WITH NO SWEAT JOINTS OR COUPLINGS
UNDERGROUND.
*6. WATTS BACKFLOW PREVENTER SHALL BE PROVIDED
ON ALL NON-RESIDENTIAL, MULTI-FAMILY, OR
MULTI-STORY SERVICES IF REQUIRED BY PRA. IF THE
METER SIZE IS OVER 1" THE OWNER, NOT THE
AUTHORITY, SHALL PROVIDE THE BACKFLOW
PREVENTER.
**7. PRESSURE REDUCER VALVE TO BE WATTS UB5 (IF
REQUIRED) - OR APPROPRIATE MODEL
CORRESPONDING TO METER SIZE.
8. SIZE OF SERVICE AND METER TO BE APPROVED BY
AUTHORITY.
9. SIZE OF VALVES, ADAPTERS, PRESSURE REDUCING
VALVES AND BACKFLOW PREVENTERS TO BE SAME
AS METER SIZE.
BA
LL
V
AL
VE
W
AT
TS
U
B5 P
R
ES
SU
R
E R
ED
U
C
ER
FE
M
AL
E
AD
AP
TE
R
FE
M
AL
E
AD
AP
TE
R
W
AT
TS
B
AC
KF
LO
W
P R
EV
EN
TE
R
ST
O
P
W
AS
TE
V
AL
VE
#6 MIN. GROUND
JUMPER
AS REQ'D
FOR METER
WATER
MAIN
FLOOR
MIN. 12" FROM
OUTSIDE WALL
WATER
SERVICE
SERVICE LINE INSTALLED
WITHIN PVC SLEEVE (I) PIPE
DIA. MAX. LARGER THAN
SERVICE LINE (SEALED)
SERVICE LINE INSTALLED
WITHIN PVC SLEEVE (I) PIPE
DIA. MAX. LARGER THAN
SERVICE LINE (SEALED)
WATER
SERVICE
BALL VALVE
MIN. BEFORE BALL
VALVE 6" (MAX. 12")
" M
IN
C O
VE
R
GRADE
REMOTE METER
READING PAD
REMOTE METER
READING PAD
" M
IN
C O
VE
R
GRADE
BALL VALVE
BASEMENT SERVICE
THROUGH FLOOR SERVICE
FRONT VIEW OF SETTING
NON-RESIDENTIAL METER SETTING REQUIREMENTS
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
3:
:1
PM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
NON-RESIDENTIAL METER SETTING REQUIREMENTS
PERKASIE REGIONAL AUTHORITY PRA-W11
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
H O2
PUMP
TEST FROM
HYDRANT OR
TAP
BL
EE
D
ER
V
AL
VE
PR
ES
SU
R
E G
AU
G
E
SH
U
T O
FF
V
AL
VE
C H
EC
K
VA
LV
E
M
ET
ER
SH
U
T O
FF
V
AL
VE
WATER MAIN
55 GAL. BARREL
OF H₂O OR
OTHER
CONTAINER
HOSE SDR-9 POLYTUBE
3/4" OR 1"
NOTES:
ALL TESTING EQUIPMENT AND FITTINGS MUST BE DISINFECTED IN ACCORDANCE WITH
PRA SPECIFICATIONS PRIOR TO TESTING.
HYDROSTATIC PRESSURE TEST CONFIGURATION
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
3:
:4
PM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
PRESSURE TEST SCHEMATIC
PERKASIE REGIONAL AUTHORITY PRA-W12
SRT
4/08/96
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
NOTE: IF THE PRA AVAILABLE SERVICE PRESSURE IS LESS THAN 45 PSI, AUTHORITY ENGINEER MUST REVIEW.
PRA WATER MAIN
1 1/2" CORPORATION
STOP AND SERVICE
SADDLE 1 1/2" CURB STOP W/BOX
1 1/2" SDR 9 CTS ASTM2737
POLYTUBE, OR APPROVED
EQUAL
RESIDENCE
EXTERIOR
RESIDENCE
INTERIOR
1 1/2" BALL VALVE
3/4" TYPE-K COPPER OR SDR-9 POLYTUBE,
OR APPROVED EQUAL
1 1/2"x3/4"x 1 1/2" TEE
TO DOMESTIC SERVICE (REFER
TO PRA RESIDENTIAL METER
DETAIL DWG. NO. PRA-W10)
1 1/2" DOUBLE CHECK VALVE ASSEMBLY
(INSTALL HORIZONTALLY)
1 1/2" BALL VALVE
1 1/2" TYPE-K COPPER OR
SDR-9 POLYTUBE, OR
APPROVED EQUAL
DRAIN AND TEST CONNECTION
(1 1/2" TYPE-K COPPER OR
SDR-9 POLYTUBE), OR APPROVED EQUAL
TO AUTOMATIC
SPRINKLER SYSTEMNOTES:
1. REFER TO THE PRA RESIDENTIAL SERVICE/SPRINKLER LINE DETAIL DWG. NO. PRA-W14.
2. REFER TO THE PRA RESIDENTIAL METER DETAIL DWG. NO. PRA-W10.
3. SERVICE SADDLE: ROMAC INDUSTRIES 202U OR APPROVED EQUAL.
4. BALL VALVE: 1 1/2" WATTS LFF BV-3C; OR APPROVED EQUAL, THREADED BOTH ENDS. FOR POLYTUBE CONNECTIONS, INSTALL 1 1/2" FORD QUICK JOINT COUPLING WITH INSERT-54-Q SOLID TUBULAR 304SS INSERT STIFFENER, OR APPROVED
EQUAL.
5. DOUBLE CHECK VALVE ASSEMBLY: 1 1/2" WATTS LFU007M2QT, OR APPROVED EQUAL, WITH UNIONS, TWO RESILIENT SEATED ISOLATION VALVES, AND FOUR TOP MOUNTED RESILIENT SEATED TEST COCKS. INSTALL ASSEMBLY
HORIZONTALLY.
6. SINGLE SPRINKLER OPERATION DESIGN FIRE SPRINKLER NOZZLES MUST HAVE A MINIMUM K FACTOR OF 7.4 (107) AND
MUST PROVIDE A MINIMUM FLOW OF 24 GPM AT A MAXIMUM HEAD OF 10.5 PSI.
7. DUAL SPRINKLER OPERATION DESIGN FIRE SPRINKLER NOZZLES MUST HAVE A MINIMUM K FACTOR OF 4.9 (71) AND MUST PROVIDE A MINIMUM FLOW OF 13 GPM EACH AT A MAXIMUM HEAD OF 7.0 PSI. (TOTAL MIN. FLOW FOR DUAL SPRINKLERS =
26 GPM)
8. METHODS AND MATERIALS ARE TO BE PER THE MUNICIPALITY PLUMBING CODE AND PRA REQUIREMENTS
IF GREATER
THAN 80 FEET,
AUTHORITY
ENGINEER MUST
REVIEW
WATER
MAIN ℄
THERE ARE TO BE NO
SPLICES IN THE
SERVICE LINE
1 1/2" TYPE-K COPPER OR
SDR-9 POLYTUBE, OR
APPROVED EQUAL
1 1/2" TEE
(NOTE: AN EXPANSION TANK MUST
BE INSTALLED ON THE DOMESTIC
SYSTEM DUE TO THE DOUBLE CHECK
VALVE ON THE SPRINKLER SYSTEM.)
SPACE AT 48" MIN.
REFER TO SPECIFICATIONS
FOR PIPE INFORMATION
1 1/2" RESIDENTIAL SERVICE/SPRINKLER LINE CONNECTION
NOT TO SCALE
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
8/ 7/
:5
2:
A M, B
Y:
TI
NA
C
AR
TE
R
PL
OT
ST
YL
E:
PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
RESIDENTIAL SERVICE/SPRINKLER LINE
PERKASIE REGIONAL AUTHORITY PRA-W13
SRT
5/11/15
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
AI
N
TA
IN
'-0 " M
IN
45°
NOTES:
1. WET TAPPING UNDER NORMAL LINE PRESSURE IS REQUIRED. THERE ARE TO BE NO SPLICES IN THE SERVICE LINE.
2. SERVICE SADDLE: ROMAC INDUSTRIES 202U OR APPROVED EQUAL.
3. CORPORATION STOPS: 1 1/2" FORD FB 1000-6-Q-NL WITH INSERT-54-Q SOLID TUBULAR 304 SS INSERT STIFFENERS, OR
APPROVED EQUAL.
4. CURB STOPS: 1 1/2" FORD B44-666-Q-NL WITH INSERT-54-Q SOLID TUBULAR 304 SS INSERT STIFFENERS, OR APPROVED EQUAL.
5. CURB BOX: FORD EA2-45-50 WITH A CURB BOX BASE FOR 1 1/2" CURB STOP AND 2'-0" LONG STATIONARY OPERATING ROD, OR
APPROVED EQUAL. THE CURB BOX LID IS TO BE CAST IRON WITH THE WORD "WATER" CAST INTEGRALLY ON TOP.
6. IF THE TOTAL LENGTH OF THE POLYTUBE SERVICE LINE FROM THE WATER MAIN TO JUST INSIDE THE RESIDENCE IS MORE
THAN 80 FEET, OR THE PRA AVAILABLE SERVICE PRESSURE IS LESS THAN 45 PSI, THEN THE AUTHORITY ENGINEER MUST
REVIEW.
7. IF USING NON-METALLIC PIPING UTILIZE LOCATING TAPE.
SERVICE SADDLE
REQUIRED FOR
ALL SERVICES 1"
OR LARGER
PENNDOT 2A IN R/W, APPROVED BACKFILL
MATERIAL OUTSIDE R/W
AASHTO #10
SERVICE LINE
6" 6"
VARIABLE
CUSTOMER TO CONNECT AT THIS POINT
SERVICE LINE SDR-9 CTS
ATMS 2737 POLYTUBE (1 1/2")
NOTE:
PROVIDE 6" (AASHTO #10) SCREENINGS
ABOVE AND BELOW SERVICE LINE
SERVICE LINE SDR-9 CTS
ASTM 2737 POLYTUBE (1 1/2")
CORPORATION
STOP (SPACE
AT 48" MIN.)
24" FROM CURB FACE
30" FROM EDGE OF PAVING OR
AS DIRECTED BY ENGINEER
4' M
IN
. C
O
VE
R
4' M
IN
. C
O
VE
R
CURB BOX
COMPLETE W/
STATIONARY ROD
2'-0" LONG
CURB STOP
PROVIDE SLACK FOR
PROTECTION AGAINST PULLING
CORPORATION OUT OF MAIN
WATER MAIN
VA
R
IA
BL
E
VA
R
IA
BL
E
CURB BOX LID TO BE CAST IRON WITH THE
WORD "WATER" CAST INTEGRALLY ON TOP
1 1/2" RESIDENTIAL SERVICE/SPRINKLER LINE CONNECTION
NOT TO SCALE
ROADWAY
ONE CONTINUOUS PIECE
FROM CORPORATION STOP
TO CURB STOP REQUIRED
M :\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
3:
:1
PM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
RESIDENTIAL SERVICE/SPRINKLER LINE
PERKASIE REGIONAL AUTHORITY PRA-W14
SRT
5/11/15
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
:\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
7/
/2
9:
:5
AM,
BY
: T
IN
A
CA
RT
ER
P
LO
TS
TY
LE
: PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
BOXLOK VALVE BOX ALIGNMENT DEVICE
PERKASIE REGIONAL AUTHORITY PRA-W15
SRT
1/24/19
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
DATE:
REVISED 5/13/2025
BOXLOK VALVE BOX ALIGNMENT DEVICE
GROUND LINE
INNER LID
C.I. FROSTPROOF LID
FORD MODEL W3-T
METRON WATER METER 5/8"x3/4" OR 3/4"
INSTALLED IN METERPIT
CARTRIDGE DUAL CHECK OUTLET;
FORD METERBOX HHCA31-323
(EXPANSION TANK INSIDE HOUSE
REQUIRED)
PVC SUPPORT BRACE
HDPE 20x48 FORD
METERBOX 20-48-NL, OR
ADS HDPE 21 INCH METER
PIT
3/4" K-COPPER RISER TUBE WITH
BULKHEAD FITTING (2) BY FORD
METERBOX PDVH-244-20-48-NL
SERVICE LINE ADAPTER BY
FORD METERBOX C14-33Q (2)
STONE FILL (TYP.)
ANGLE BALL
METER VALVE,
BA13-332W
4'
METAL COVER
NOTES:
1. METERPIT TO BE INSTALLED JUST
OUTSIDE OF THE RIGHT-OF-WAY, ON
THE PRIVATE PROPERTY.
2. AN EXT-2 EXTENSION RING SHALL BE
USED WHEN BACKFLOW PREVENTORS
ARE NECESSARY.RESIDENTIAL METERPIT
NOT TO SCALE
U:
\A
DM
IN
\S
EL
LE
RS
VI
LL
E\
CA
D
DE
SI
GN
\A
UT
HO
RI
TI
Y
CL
IE
NT
S\
PE
RK
AS
IE
\W
AT
ER
D
ET
AI
LS
\A
LL
P
RA
W
AT
ER
D
ET
AI
LS
5.
DW
G
PL
OT
TE
D:
2/
/2
:3
6:
A M, B
Y:
TI
NA
C
AR
TE
R
PL
OT
ST
YL
E:
PE
NN
ON
I N
CS
.S
TB,
PR
OJ
EC
T
ST
AT
US
PREPARED FOR:
PENNONI ASSOCIATES INC.
150 Ridge Road, Suite 2 Sellersville, PA 18960
T 215-257-5711 F 215-257-5766
RESIDENTIAL METERPIT
PERKASIE REGIONAL AUTHORITY PRA-W16
SRT
12/12/19
JARDESIGNED BY:
CHECKED BY:
DRAWING NO.
DATE:
REVISED 02/24/2026
4" THICK FOAM
INSULATION DISK
| Blank Page |
| W01-1.pdf |
| Sheets and Views |
| Model |
| W01-2.pdf |
| Sheets and Views |
| Model |
| W02.pdf |
| Sheets and Views |
| Model |
| W03.pdf |
| Sheets and Views |
| Model |
| W04.pdf |
| Sheets and Views |
| Model |
| W05.pdf |
| Sheets and Views |
| Model |
| W06.pdf |
| Sheets and Views |
| Model |
| W07.pdf |
| Sheets and Views |
| Model |
| W08.pdf |
| Sheets and Views |
| Model |
| W09.pdf |
| Sheets and Views |
| Model |
| W10.pdf |
| Sheets and Views |
| Model |
| W11.pdf |
| Sheets and Views |
| Model |
| W12.pdf |
| Sheets and Views |
| Model |
| W13.pdf |
| Sheets and Views |
| Model |
| W14.pdf |
| Sheets and Views |
| Model |
| W15.pdf |
| Sheets and Views |
| Model |
| W16.pdf |
| Sheets and Views |
| Model |
| Blank Page |
| Blank Page |
| Blank Page |
| S01.pdf |
| Sheets and Views |
| Model |
| S02.pdf |
| Sheets and Views |
| Model |
| S03.pdf |
| Sheets and Views |
| Model |
| S04.pdf |
| Sheets and Views |
| Model |
| S05.pdf |
| Sheets and Views |
| Model |
| S06.pdf |
| Sheets and Views |
| Model |
| S07.pdf |
| Sheets and Views |
| Model |
| S08.pdf |
| Sheets and Views |
| Model |
| S09.pdf |
| Sheets and Views |
| Model |
| S010.pdf |
| Sheets and Views |
| Model |
| S011.pdf |
| Sheets and Views |
| Model |
| S012.pdf |
| Sheets and Views |
| Model |
| S013.pdf |
| Sheets and Views |
| Model |
| S014.pdf |
| Sheets and Views |
| Model |
| S015.pdf |
| Sheets and Views |
| Model |
| S016.pdf |
| Sheets and Views |
| Model |
| S017.pdf |
| Sheets and Views |
| Model |
| S018.pdf |
| Sheets and Views |
| Model |
| S019.pdf |
| Sheets and Views |
| Model |
| S020.pdf |
| Sheets and Views |
| Model |
| S021.pdf |
| Sheets and Views |
| Model |
| S022A.pdf |
| Sheets and Views |
| Model |
| S022B.pdf |
| Sheets and Views |
| Model |
| S023.pdf |
| Sheets and Views |
| Model |
| S024.pdf |
| Sheets and Views |
| Model |
| S025.pdf |
| Sheets and Views |
| Model |
| S026.pdf |
| Sheets and Views |
| Model |
| Blank Page |
| Blank Page |
| PRA Standard Sewer Details REV 5-13-25.pdf |
| Blank Page |
| S01.pdf |
| Sheets and Views |
| Model |
| S02.pdf |
| Sheets and Views |
| Model |
| S03.pdf |
| Sheets and Views |
| Model |
| S04.pdf |
| Sheets and Views |
| Model |
| S05.pdf |
| Sheets and Views |
| Model |
| S06.pdf |
| Sheets and Views |
| Model |
| S07.pdf |
| Sheets and Views |
| Model |
| S08.pdf |
| Sheets and Views |
| Model |
| S09.pdf |
| Sheets and Views |
| Model |
| S010.pdf |
| Sheets and Views |
| Model |
| S011.pdf |
| Sheets and Views |
| Model |
| S012.pdf |
| Sheets and Views |
| Model |
| S013.pdf |
| Sheets and Views |
| Model |
| S014.pdf |
| Sheets and Views |
| Model |
| S015.pdf |
| Sheets and Views |
| Model |
| S016.pdf |
| Sheets and Views |
| Model |
| S017.pdf |
| Sheets and Views |
| Model |
| S018.pdf |
| Sheets and Views |
| Model |
| S019.pdf |
| Sheets and Views |
| Model |
| S020.pdf |
| Sheets and Views |
| Model |
| S021.pdf |
| Sheets and Views |
| Model |
| S022A.pdf |
| Sheets and Views |
| Model |
| S022B.pdf |
| Sheets and Views |
| Model |
| S023.pdf |
| Sheets and Views |
| Model |
| S024.pdf |
| Sheets and Views |
| Model |
| S025.pdf |
| Sheets and Views |
| Model |
| S026.pdf |
| Sheets and Views |
| Model |
| S01.pdf |
| Sheets and Views |
| Model |
| S02.pdf |
| Sheets and Views |
| Model |
| S03.pdf |
| Sheets and Views |
| Model |
| S04.pdf |
| Sheets and Views |
| Model |
| S05.pdf |
| Sheets and Views |
| Model |
| S06.pdf |
| Sheets and Views |
| Model |
| S07.pdf |
| Sheets and Views |
| Model |
| S08.pdf |
| Sheets and Views |
| Model |
| S09.pdf |
| Sheets and Views |
| Model |
| S010.pdf |
| Sheets and Views |
| Model |
| S011.pdf |
| Sheets and Views |
| Model |
| S012.pdf |
| Sheets and Views |
| Model |
| S013.pdf |
| Sheets and Views |
| Model |
| S014.pdf |
| Sheets and Views |
| Model |
| S015.pdf |
| Sheets and Views |
| Model |
| S016.pdf |
| Sheets and Views |
| Model |
| S017.pdf |
| Sheets and Views |
| Model |
| S018.pdf |
| Sheets and Views |
| Model |
| S019.pdf |
| Sheets and Views |
| Model |
| S020.pdf |
| Sheets and Views |
| Model |
| S021.pdf |
| Sheets and Views |
| Model |
| S022A.pdf |
| Sheets and Views |
| Model |
| S022B.pdf |
| Sheets and Views |
| Model |
| S023.pdf |
| Sheets and Views |
| Model |
| S024.pdf |
| Sheets and Views |
| Model |
| S025.pdf |
| Sheets and Views |
| Model |
| S026.pdf |
| Sheets and Views |
| Model |
File details come from the government source that posted it. Updated .