12-10- Plans- LIB133030 Magna Library Rooftop Equip Replacement.pdf
PDF 10 MB Posted
- Solicitation number
- SLCo LIB133030 Magna Library Rooftop Equip Replacement - CONST
- Issued by
- Utah
About this file
Construction Documents Summary: Magna Library Rooftop Equipment Replacement
This file contains detailed construction documents for the Magna Library Rooftop Equipment Replacement project in Magna, Utah, prepared by HHY Associates for Salt Lake County. The project involves the comprehensive replacement of rooftop mechanical, plumbing, and electrical systems at the Magna Library located at 2675 South 8950 West, Magna, UT 84044. The scope of work includes demolition and replacement of eight packaged rooftop units (RTU-1 through RTU-8), installation of two ductless split heat pump systems (HP-1 and HP-2), replacement of exhaust fans (EF-1, EF-2, EF-3), installation of new condensate drain piping, gas line connections, roof drain systems, and electrical infrastructure modifications. The project also incorporates a new photovoltaic (PV) solar panel array system as a bid alternate, with specifications indicating approximately 1,550 square feet of solar panels with a weight load limit not exceeding 15 pounds per square foot. Construction documents are dated August 3, 2026, with document expiration noted as March 31, 2027, and include comprehensive architectural, mechanical, plumbing, and electrical drawings across multiple sheets with demolition and new installation plans.
The construction documents contain detailed specifications and schedules for all mechanical equipment, electrical connections, and plumbing modifications required for project completion. Mechanical equipment includes rooftop units ranging from 3 to 20 tons with electrical requirements from 17.3 to 82.9 amperes at 208 volts, exhaust fans with varying wattages, and ductless heat pump systems. Electrical work requires connection to existing panelboards (BLM and BLC-II) with new circuit breakers and conduit runs throughout basement, main level, and roof areas. Plumbing work involves natural gas instantaneous water heaters to remain in place, new condensate drain connections, roof drain modifications, and gas pipe extensions ranging from 1/2 inch to 1-1/4 inches in diameter. The project specifies that all work shall comply with Utah's prevailing state mechanical, plumbing, and building codes, with a one-year warranty on all parts and labor from final inspection date. Contractors are required to visit the site prior to bidding, obtain necessary permits, and coordinate with multiple trades including fire protection, structural, and architectural divisions for complete project execution.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING INDEX
VICINITY MAPOWNER
CONSULTANTS
2675 SOUTH 8950 WEST
MAGNA, UT 84044
August 3, 2026
CONSTRUCTION DOCUMENTS
MAGNA LIBRARY
ROOF TOP EQUIPMENT
REPLACEMENT
BID INFORMATION
ABBREVIATIONS
SYMBOL LEGEND
FLUE
FH
VTR
EX
RTU
GA
VENT
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
BUFFALO GRASS
LEED BOUNDARY
FDC
IRRIGATION
BACKFLOW
W MAGNA MAIN STREET
S
W
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
S
T
A
I
R
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L
I B
R A
R Y
R O
O F
T
P
E
Q U
I P
M E
N T
R E
P L
A C
E M
E N
T
S
W
M
A G
N A
U
T
SITE PLAN,
CODE ANALYSIS &
GENERAL NOTES
A0.1
CODE ANALYSIS
118'
113'
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
V
A
L
L
E
Y
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
C
L
E
A
R
O
Y
P
N
B
L
O
W
ROOF HEIGHT
ROOF
HEIGHT
S
L
O
P
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
R
I
D
G
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
S L O
P E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S L O
P E
I
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
117'
ROOF HEIGHT
K
K
L
H
L
H
K
K
W x
K
K
K
K
W x
W x
W x
W x
W x
W x
W x
H
S
S x x
W x
L w x
H
W x
L w x
H
W x
K
K
K
W x
W x
W x
W x
W8x10 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
ROOF
DEMOLITION PLAN
A1.1D
118'
113'
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
V
A
L
L
E
Y
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
C
L
E
A
O
Y
P
B
L
O
W
ROOF HEIGHT
ROOF
HEIGHT
S
L
O
P
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
R
I
D
G
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
S
L
O
P
E
S L O
P E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L O
P
E
S
L
O
P
E
S
L
O
P
E
S
L
O
P
E
S L O
P E
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
S
L
O
P
E
D
S
T
R
U
C
T
U
R
E
117'
ROOF HEIGHT
G
G
G
G
G
G
G mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
ROOF PLAN
A1.1N
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
S
T
A
I
R
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
T T T
T
T
T
T
T
CO2
T
T
CO2
CO2
T T
T
T T
T
CO2 T
CO
T CO2
CO
CO2
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
MAIN LEVEL
FLOOR DEMO PLAN
A1.2D
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
S
T
A
I
R
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
S
S
S
S
S
S S
S
CO2
CO2
CO2
CO2 CO
CO2
CO
CO2
TT
T mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
MAIN LEVEL
FLOOR PLAN
A1.2N
TELECOM
ELECTRICAL
MECHANICAL
CONRETE SLAB FOR RAISED
ACCESS FLOORING
UNEXCAVATED
NO FLOOR
UNEXCAVATED
CONCRETE FLOOR
UNEXCAVATED
U
N
E
X
C
A
V
A
T
E
D
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
BASEMENT LEVEL
FLOOR PLAN
A1.3
C-4
C-3
9'-0"
C-3
9'-0"
C-3
9'-0"
C-3
9'-0"
C-4
C-3
9'-0"
C-4
C-3
9'-0"
C-4
C-4
C-3
10'-0"
C-3
10'-0"
C-2
13'-0"
C-3
17'-10"
C-4
C-4
C-4
C-4
C-4
C-4
C-3
10'-0"
C-3
9'-0"
C-2
13'-0"
C-2
13'-0"
C-3
12'-0"
C-1
10'-0"
C-1
10'-0"
C-1
10'-0"
C-2
13'-0"
C-2
13'-0"
C-2
13'-0"
C-2
13'-0"
C-1
18'-2"
C-1
10'-0"
C-1
10'-0"
C-1
10'-0"
C-1
9'-0"
C-3
10'-0"
C-2
13'-0"
C-2
9'-0"
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
T T T
T
T
T
T
T
T
T
T T
T
T T
T T
T mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
REFLECTED CEILING
DEMO PLAN
A1.4D
X 10'-0"
C-4
C-3
9'-0"
C-3
9'-0"
C-3
9'-0"
C-3
9'-0"
C-4
C-3
9'-0"
C-4
C-3
9'-0"
C-4
C-4
C-3
10'-0"
C-3
10'-0"
C-2
13'-0"
C-3
17'-10"
C-4
C-4
C-4
C-4
C-4
C-4
C-3
10'-0"
C-3
9'-0"
C-2
13'-0"
C-2
13'-0"
C-3
12'-0"
C-1
10'-0"
C-1
10'-0"
C-1
10'-0"
C-2
13'-0"
C-2
13'-0"
C-2
13'-0"
C-2
13'-0"
C-1
18'-2"
C-1
10'-0"
C-1
10'-0"
C-1
10'-0"
C-1
9'-0"
C-3
10'-0"
C-2
13'-0"
C-2
9'-0"
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
S
S
S
S
S
S S
S
TT
T mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L I B
R A
R Y
R O
U
I P
M E
N T
R E
P L A
C E
M E
N T
W
M
A G
N A
U
T
REFLECTED
CEILING PLAN
A1.4N
≤ 8 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L
I B
R A
R Y
R O
U
I P
M E
N T
R E
P L
A C
E M
E N
T
W
M
A G
N A
U
T
DETAILS
A2.1 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210
2180 South 1300 East
Phone: 801 466 3996
M A
G N
A
L
I B
R A
R Y
R O
U
I P
M E
N T
R E
P L
A C
E M
E N
T
W
M
A G
N A
U
T
DETAILS
A2.2
SCALE: N.T.S.
PLUMBING GENERAL NOTES
1. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS WHICH
ARE OBVIOUSLY AND REASONABLY NECESSARY TO COMPLETE THE
INSTALLATION.
2. THE CONTRACTOR SHALL TAKE OUT PERMITS, PROCURE
CERTIFICATES AND PAY FEES CONNECTED THEREWITH.
3. BIDDERS SHALL VISIT THE SITE AND BECOME FAMILIAR WITH
EXISTING CONDITIONS SURROUNDING THE PROJECT PRIOR TO
BIDDING.
4. THE CONTRACTOR IS REFERRED TO ARCHITECTURAL,
STRUCTURAL, ELECTRICAL PLANS AND SPECIFICATIONS. SUCH
PLANS AND SPECIFICATIONS ARE CONTRACT DOCUMENTS.
5. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW
APPROXIMATE LOCATIONS.
6. ALL PLUMBING WORK SHALL BE PERFORMED IN STRICT
ACCORDANCE WITH THE LATEST EDITION OF THE PREVAILING
STATE MECHANICAL/PLUMBING AND BUILDING CODES AS WELL AS
ALL REGULATIONS THAT MAY APPLY. IN CASE OF CONFLICT
BETWEEN THE CONTRACT DOCUMENTS AND A GOVERNING CODE
OR ORDINANCE THE MORE STRINGENT STANDARD SHALL APPLY.
7. NO PIPING SHALL RUN EXPOSED IN FINISHED AREAS UNLESS
NOTED OTHERWISE.
8. RUN-OUT SIZES TO INDIVIDUAL PLUMBING FIXTURES TO BE EQUAL
TO ROUGH-IN SIZE NOTED IN THE PLUMBING FIXTURE SCHEDULE.
9. PLUMBING/PIPING IS SHOWN SCHEMATICALLY FOR VIEWING
PURPOSES ONLY; DURING INSTALLATION FIELD MODIFICATIONS TO
ROUTING MAY BE REQUIRED.
10. INSTALL ALL REQUIRED CLEANOUTS TO CLEAR EQUIPMENT AND
FIXTURES.
11. ALL WORK SHALL BE PROPERLY TESTED, BALANCED AND CLEANED
AND DISINFECTED. PROVIDE A ONE YEAR WARRANTY FROM DATE
OF FINAL INSPECTION ON ALL PARTS AND LABOR.
12. TERMINATE PLUMBING VENTS AT A MINIMUM OF 10' FROM ALL AIR
HANDLING EQUIPMENT INTAKE VENTS.
13. CONTRACTOR SHALL VERIFY LOCAL CODE REQUIREMENTS FOR
INDIRECT CONNECTIONS FOR FOOD PREP AREAS. CONNECTIONS
SHALL BE PROVIDED WITH A MINIMUM 1" AIR GAP, UNLESS
OTHERWISE NOTED.
14. PRESSURIZED PIPING SHALL NOT BE RUN IN ANY AREA SUBJECT
TO FREEZING.
15. PRIOR TO INSTALLING ANY PIPING, VERIFY DEPTH OF CONNECTION
POINTS OF GRADE DEPENDENT PIPING AND CONFIRM IN WRITING
TO ENGINEER.
16. WHERE RATED ASSEMBLIES ARE PENETRATED BY DUCTS, PIPES
OR OTHER ITEMS, THE "F" AND "T" RATING SHALL BE MAINTAINED
WITH REQUIRED UL LISTED ASSEMBLIES OR SEALANT AS REQUIRED
BY THE APPLICABLE CODE OR AUTHORITY HAVING JURISDICTION.
PLUMBING ABBREVIATIONS
A COMPRESSED AIR EWC ELECTRIC WATER COOLER
INV INVERT
RPBP REDUCED PRESSURE
BACKFLOW PREVENTERAFF ABOVE FINISHED FLOOR EWT ENTERING WATER
TEMPERATURE KW KILOWATTALT ALTERNATE
F FIRE SUPPRESION LAV LAVATORY
S SINK
ASL ABOVE SEA LEVEL
FCO FLOOR CLEANOUT LB POUND
SCHED SCHEDULE
AV ACID VENT
FD FLOOR DRAIN MAX MAXIMUM
SCW SOFT COLD WATER
AW ACID WASTE
FLEX FLEXIBLE MBH THOUSAND BRITISH
THERMAL UNITS/HOUR
SH SHOWER
BFF BELOW FINISHED FLOOR
FLR FLOORBTU BRITISH THERMAL UNIT
FS FLOOR SINK MECH MECHANICAL
SL SEA LEVEL
CO CLEANOUT
FT FEET MECH RM MECHANICAL ROOM
SPEC SPECIFICATION
CO2 CARBON DIOXIDE
G NATURAL GAS MFR MANUFACTURER
SQ FT SQUARE FEET
CONTR CONTRACTOR
GA GAUGE MIN MINIMUM
SRD SECONDARY ROOF DRAIN
COTG CLEANOUT TO GRADE
GAL GALLON(S) MISC MISCELLANEOUS
SS SERVICE SINK
CW CLOTHES WASHER
GALV GALVANIZED N NITROGEN
STD STANDARD
CW COLD WATER
GPM GALLONS PER MINUTE NIC NOT IN CONTRACT
TWS TEMPERED WATER
DOMESTIC
D DRAIN PIPE
GW GREASE WASTE NO NITROUS OXIDE
TEMP TEMPERATURE
DEG F DEGREE FAHRENHEIT
HA HAMMER ARRESTOR NTS NOT TO SCALE
TYP TYPICAL
DEMO DEMOLITION
HB HOSE BIBB O OXYGEN
U URINAL
DET DETAIL
HD HEAD PH PHASE
V VOLT
DF DRINKING FOUNTAIN
HORIZ HORIZONTAL PPM PARTS PER MILLION
VAC VACUUM
DIA DIAMETER
HP HORSEPOWER PRV PRESSURE REDUCING VALVE
VTR VENT THRU ROOF
DIM DIMENSION
H HOUR PSI POUNDS PER SQUARE INCH
W/ WITH
DIV DIVISION
HW HOT WATER PW PROCESS WASTE
W/O WITHOUT
DMPR DAMPER
HWR HOT WATER RETURN QTY QUANTITY
WAG WASTE ANESTHETIC GAS
DN DOWN
HZ HERTZ RD ROOF DRAIN
WC WATER CLOSET
DRN DRAIN
ICW INDUSTRIAL COLD WATER REQD REQUIRED
WCO WALL CLEANOUT
DS DOWNSPOUT
IE INVERT ELEVATION REV REVISION
WH WATER HEATER
ES EMERGENCY SHOWER
IHW INDUSTRIAL HOT WATER RP RECIRCULATION PUMPEW EMERGENCY EYE WASH
IN INCH
WASTE PIPING (BELOW GRADE OR FLOOR)
WASTE PIPING (ABOVE GRADE OR FLOOR)
PLUMBING LEGEND
DOMESTIC HOT WATER PIPING
DOMESTIC COLD WATER PIPING
NATURAL GAS PIPING
DOMESTIC HOT WATER RECIRCULATION PIPING
VENT PIPING
G
ACID WASTE PIPING (ABOVE GRADE OR FLOOR) AW
COMPRESSED AIR PIPING
OXYGEN PIPING
VACUUM PIPING
A
O
VAC
DIWDEIONIZED WATER PIPING
INDUSTRIAL COLD WATER PIPING ICW
INDUSTRIAL HOT WATER PIPING IHW
ACID VENT PIPING AV
ACID WASTE PIPING (BELOW GRADE OR FLOOR) AW
GREASE WASTE PIPING (ABOVE GRADE OR FLOOR) GW
GREASE WASTE PIPING (BELOW GRADE OR FLOOR) GW
ROOF DRAIN PIPING (BELOW GRADE OR FLOOR)
SECONDARY ROOF DRAIN PIPING
ROOF DRAIN PIPING (ABOVE GRADE OR FLOOR) RD
RD
SRD
DOMESTIC TEMPERED WATER TWS
CARBON DIOXIDE PIPING C02
NNITROGEN PIPING
NONITROUS OXIDE PIPING
PLUMBING FIXTURE CALLOUT
DETAIL NUMBER
SHEET DETAIL APPEARS
LARGE SCALE NUMBER
SHEET LARGE SCALE APPEARS
KEYED NOTE
DESCRIPTION SYMBOL
X S#
S#
P-??
DESCRIPTION
PRESSURE REGULATOR
GAS COCK VALVE
WALL CLEAN OUT
CLEAN OUT TO GRADE
FLOOR CLEAN OUT
BALL VALVE
DROP
RISE
UNION
CLEAN OUT CO
COTG
FCO
WCO
GATE VALVE
STRAINER
AUTOMATIC TWO-WAY VALVE
AUTOMATIC THREE-WAY VALVE
TEMPERING VALVE TWS
CHECK VALVE
CIRCUIT SETTER
BUTTERFLY VALVE
CAPPED PIPE
PIPE REDUCER
SYMBOL
NOTE: NEW ITEMS SHOWN DARK, EXISTING ITEMS SHOWN LIGHT.
ALL ITEMS MAY NOT APPEAR ON DRAWINGS.
HAMMER ARRESTOR
RELIEF VALVE
R
BACKFLOW PREVENTOR
SOFT COLD WATER PIPING SCW
SOFT HOT WATER PIPING SHW
RELIEF VALVE
THERMOMETER
FLEXIBLE PIPING
INLINE PUMP
DIRECTION OF SLOPE
FLOW DIRECTION
ACCESS DOOR
FLOW METER
WATER METER
FM
MANUAL AIR VENT
W
DEVICE IN DROP
X-#EQUIPMENT CALLOUT
PROCESS WASTE PIPING (ABOVE GRADE OR FLOOR) PW
PROCESS WASTE PIPING (BELOW GRADE OR FLOOR) PW
WASTE ANESTHETIC GAS PIPING WAG
REVISION DELTA
ROOM NAME
ROOM NUMBER
SECTION LETTER
SHEET NUMBER
ROOM
NO
NEW CONNECTION
TOP
BOT
LIQUID PROPANE GAS LPG
FIRE SPRINKLER PIPING F
DPUMPED DRAIN PIPING
DDRAIN PIPING
NON-POTABLE WATER NPW
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
PLUMBING LEGEND
& GENERAL NOTES
P0.1
I:\
JO
B S
\2
\C
A D
\Z N
P
1.
dw g, /4 /2
3:
:3
P M
, t aa rg yl e
K K
C
A A
J
J
H
H
G
G
F
F
E
D
B
TELECOM
ELECTRICAL
MECHANICAL
CONRETE SLAB FOR RAISED
ACCESS FLOORING
UNEXCAVATED
NO FLOOR
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
D
D
3/4" mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
LOWER LEVEL
PLUMBING
DEMOLITION PLAN
PD1.0
KEYED NOTES FOR SHEET PD1.0
1 NATURAL GAS INSTANTANEOUS WATER HEATER TO
REMAIN (199 MBH EACH).
2 DISCONNECT EXISTING DRAIN PIPE FROM DUCTLESS
SPLIT UNIT.
3 GAS PIPE UP.
4 REMOVE EXISTING CONTROLS FROM DOMESTIC WATER
RECIRCULATION PUMP.
I:\
JO
B S
\2
\C
A D
\Z N
P D
0.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
STAIR
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
1 2
1-1/2"
1-1/2" mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MAIN LEVEL
PLUMBING
DEMOLITION PLAN
PD1.1
KEYED NOTES FOR SHEET PD1.1
1 NATURAL GAS METER.
2 ROOF DRAIN DOWNSPOUTS.
3 1" GAS PIPE UP THROUGH ROOF AND 3/4" GAS PIPE DROP
TO BASEMENT.
I:\
JO
B S
\2
\C
A D
\Z N
P D
1.
dw g, /4
/2
3:
:4
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
1/2"
1/2"
1/2"
G
G
G
G
G
G
3/4" 3/4"
1"
RTU-2
RTU-3
RTU-7
RTU-1
RTU-6
RTU-5
RTU-8
RTU-4
1-1/4"
2"V
3/4"
1"
1/2"
3"V
EF-1
3/4"
3/4"
1/2"
CU-2
CU-1
1 1 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
ROOF LEVEL
PLUMBING
DEMOLITION PLAN
PD1.2
KEYED NOTES FOR SHEET PD1.2
1 REMOVE ROOF DRAINS.
2 REMOVE NATURAL GAS PIPING ON ROOF.
I:\
JO
B S
\2
\C
A D
\Z N
P D
2.
dw g, /4
/2
3:
:4
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
TELECOM
ELECTRICAL
MECHANICAL
CONRETE SLAB FOR RAISED
ACCESS FLOORING
UNEXCAVATED
NO FLOOR
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
D
D
FC-2
FC-1
3/4" 3 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
LOWER LEVEL
PLUMBING REMODEL
PLAN
PL1.0
KEYED NOTES FOR SHEET PL1.0
1 NATURAL GAS INSTANTANEOUS WATER HEATER TO
REMAIN.
2 CONNECT NEW CONDENSATE DRAIN PIPE TO EXISTING
DRAIN.
3 CONNECT NEW DDC CONTROLS TO EXISTING DOMESTIC
WATER RECIRCULATION PUMP.
I:\
JO
B S
\2
\C
A D
\Z N
P L1
.d w g, /4
/2
3:
:4
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
STAIR
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
1 2
1-1/2"
1-1/2"
1-1/4"UP,
3/4"DN
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MAIN LEVEL
PLUMBING REMODEL
PLAN
PL1.1
KEYED NOTES FOR SHEET PL1.1
1 NATURAL GAS METER (2 PSIG).
2 ROOF DRAIN DOWNSPOUTS.
3 CONNECT NEW 1-1/4" DIA GAS PIPE FROM ROOF TO
EXISTING 1-1/2" PIPE. EXISTING 3/4" DIA GAS PIPE DOWN
TO LOWER LEVEL.
I:\
JO
B S
\2
\C
A D
\Z N
P L1
.d w g, /4
/2
3:
:4
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
2"V
3"V
G
G
G
G
G
RD-1
SRD-1 2
SR
D-
RD
-1
G
1-1/4" 3/4"
RTU-1
1/2"
SR
D-
RD
-1
1/2"
RTU-7
1/2"
RTU-2
SR
D-
RD
-1
SR
D-
RD
-1
RTU-3
1"
1/2"
RTU-6
1"
3/4"
SR
D-
RD
-1
RTU-5
SRD-1 RD-1
SR
D-
RD
-1
1"
3/4"
RTU-8
RTU-4
SR
D-
RD
-1
SRD-1 RD-1
SRD-1
RD-1
3/4"
3/4"
1/2"
G
1/2" mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
ROOF LEVEL
PLUMBING REMODEL
PLAN
PL1.2
KEYED NOTES FOR SHEET PL1.2
1 EXTEND PLUMBING VENT TO BE 2 FEET HIGHER THAN
NEW ROOF SURFACE.
2 CONNECT TO EXISTING ROOF DRAIN AND SECONDARY
ROOF DRAIN PIPING IN CEILING SPACE.
3 DROP GAS PIPE THROUGH ROOF AND CONNECT TO
EXISTING INSIDE BUILDING.
4 RISE UP AND OVER PARAPET WALL.
I:\
JO
B S
\2
\C
A D
\Z N
P L1
.d w g, /4
/2
3:
:3
P
M , t aa rg
DECK
METAL
PLASTIC ROOFING
CEMENT (CONT.
BOND TO DRAIN)
ROOF MEMBRANE
ADHESIVE (CONT.
BOND TO LEAD)
LEAD PAN
EXTEND LEAD 18"
PAN BY PLUMBING CONTRACTOR
OVERFLOW DRAIN
ROOF DRAIN
2" WATER DAM
CONT. FLASHING COLLAR
5'-0" X 3'-0"
RIGID
INSULATION
EXTEND LEAD 18"
SCALE:
ROOF DRAIN DETAIL
N.T.S.
6" V
E R
TI
C
A L
GAS FIRED EQUIPMENT
TEE FITTING WITH
PLUG
GROUND JOINT UNION
SEDIMENT TRAP SAME
SIZE AS DROP
MANUAL MAIN
SHUT-OFF VALVE
DROP FROM MAIN.
SEE PLAN FOR SIZE.
FLEXIBLE GAS
CONNECTOR 18" MAX.
UP TO 2 PSIG PRESSURESCALE:
GAS LINE CONNECTION W/REGULATOR DETAIL
N.T.S.
GAS REGULATOR
10 PIPE DIA.
SEE SPECIFICATION
FOR DRAIN PIPING.
PLUGGED TEES
H
(0.5) H 1
TOP UNIT
ROOF
2H
DRAIN
RUN TO
H =EQUAL TO OPERATING
H =EQUAL TO 1"
BREAK VACUUM PRESSURE
OPEN TO ATMOSPHERE TO
2"
1 STATIC PRESSURE ON
PAN
SCALE:
CONDENSATE DRAIN TRAP
DRAW- THROUGH UNIT
N.T.S.3
SCALE:
GAS PIPE STAND DETAIL
N.T.S.
OF ROOF UNDER
EXTRA LAYER
MIRO PIPESTAND
ROOF
PIPE
PIPESTAND
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
PLUMBING DETAILS
AND LEGEND
P5.1
I:\
JO
B S
\2
\C
A D
\Z N
P
1.
dw g, /4 /2
3:
:3
P M
, t aa rg
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
PLUMBING
SCHEDULE
P6.1
I:\
JO
B S
\2
\C
A D
\Z N
P
1.
dw g, /4 /2
3:
:3
P M
, t aa rg
HVAC GENERAL NOTES
1. CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS WHICH ARE
OBVIOUSLY AND REASONABLY NECESSARY TO COMPLETE THE
INSTALLATION.
2. THE CONTRACTOR SHALL TAKE OUT PERMITS, PROCURE
CERTIFICATES AND PAY FEES CONNECTED THEREWITH.
3. BIDDERS SHALL VISIT THE SITE AND BECOME FAMILIAR WITH
EXISTING CONDITIONS SURROUNDING THE PROJECT PRIOR TO
BIDDING.
4. THE CONTRACTOR IS REFERRED TO ARCHITECTURAL,
STRUCTURAL, ELECTRICAL PLANS AND SPECIFICATIONS. SUCH
PLANS AND SPECIFICATIONS ARE CONTRACT DOCUMENTS.
5. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW
APPROXIMATE LOCATIONS.
6. ALL MECHANICAL HVAC WORK SHALL BE PREFORMED IN STRICT
ACCORDANCE WITH THE LATEST EDITION OF THE PREVAILING
STATE MECHANICAL/PLUMBING AND BUILDING CODES AS WELL AS
ALL REGULATIONS THAT MAY APPLY. IN CASE OF CONFLICT
BETWEEN THE CONTRACT DOCUMENTS AND A GOVERNING CODE
OR ORDINANCE THE MORE STRINGENT SHALL APPLY.
7. DIFFUSER RUN OUTS SHALL BE THE SAME AS LISTED DIFFUSER
NECK SIZE, UNLESS OTHERWISE NOTED.
8. COORDINATE EXACT LOCATION OF AIR DISTRIBUTION DEVICES
WITH CEILING GRID AND LIGHT FIXTURE LAYOUT.
9. ALL RECTANGULAR SUPPLY DUCT ELBOWS SHALL HAVE TURNING
VANES.
10. RECTANGULAR DUCT SIZES SHOWN INDICATE REQUIRED AIRFLOW
SIZES. SHEETMETAL CONTRACTOR SHALL INCREASE SIZES TO
ALLOW FOR LINER.
11. NO DUCTWORK SHALL BE FABRICATED WITHOUT FIRST FIELD
VERIFYING THAT THE AVAILABLE SPACE UNDER ACTUAL JOB
CONDITIONS WILL PERMIT INSTALLATION OF THE DUCTWORK
WITHOUT STRUCTURAL OR OTHER CONFLICTS. DUCT SIZES THAT
REQUIRE ON THE JOB MODIFICATION DUE TO UNFORESEEN
OBSTRUCTIONS SHALL BE MADE WITHOUT ANY ADDITIONAL COST
TO THE OWNER.
12. MAINTAIN A 10'-0" BETWEEN OUTSIDE AIR INTAKES AND
PLUMBING/EXHAUST VENTS.
13. WHERE RATED ASSEMBLIES ARE PENETRATED BY DUCTS, PIPES
OR OTHER ITEMS, THE "F" AND "T" RATING SHALL BE MAINTAINED
WITH REQUIRED UL LISTED ASSEMBLIES OR SEALANTS AS
REQUIRED BY THE APPLICABLE CODE OR AUTHORITY HAVING
JURISDICTION.
BRANCH DUCT TAKE-OFF
DUCT FLEXIBLE CONNECTION
VOLUME DAMPER
SUPPLY AIR, RISE AND DROP
OUTSIDE AIR, RISE AND DROP
FIRE SMOKE DAMPER
FIRE DAMPER
RETURN AIR, RISE AND DROP
DUCT TRANSITION
AUTOMATIC DAMPER
TURNING VANES
DUCT TEE CONNECTION
DESCRIPTIONSYMBOL
SQUARE TO ROUND DUCT TRANSITION
X-#
X-#
X S#
KEYED NOTE
AIR DEVICE
CFM
AIR DEVICE
DUCT ACCESS DOOR
BACK-DRAFT DAMPER
T THERMOSTAT
EXHAUST AIR, RISE AND DROP
FSD
FD
SYMBOL DESCRIPTION
GLOBE VALVE
PIPE SUPPORT
SUCTION LINE
EXTERIOR PIPE SUPPORT
EXTERIOR PIPE SUPPORT
DIRECTION OF SLOPE DOWN
S
L LIQUID LINE
EXPANSION VALVE
REFRIGERANT SHUT-OFF VALVE
MOISTURE INDICATING SIGHT GLASS
FILTER DRIER
FLEXIBLE CONNECTION
F
ROUND DUCT, RISE AND DROP
FLAT OVAL DUCT, RISE AND DROP
AIR FLOW DIRECTION
INLINE PUMP
SYMBOL DESCRIPTION
REFRIGERANT PIPING - LIQUIDRL
REFRIGERANT PIPING - SUCTIONRS
S#
ROOM
NO
ROOM NAME
ROOM NUMBER
SECTION LETTER
SHEET NUMBER
LARGE SCALE NUMBER
SHEET LARGE SCALE APPEARS
MECHANICAL LEGEND NOTE: NEW ITEMS SHOWN DARK, EXISTING ITEMS SHOWN LIGHT.
ALL ITEMS MAY NOT APPEAR ON DRAWINGS.
WITH MANUAL DAMPER
BD
RELIEF AIR, RISE AND DROP
DETAIL NUMBER
SHEET DETAIL APPEARS
EQUIPMENT CALLOUTX-#
FM
J-BOXJ ACCESS DOOR
AUTOMATIC 2-WAY VALVE
AUTOMATIC 3-WAY VALVE
AUTOMATIC BALL FLOAT VENT
BALL VALVE
CAPPED END W/BALL VALVE
CHECK VALVE
COMBINATION BALANCING VALVE/ SHUTOFF
DEVICE IN DROP
DIRECTION OF SLOPE
FLANGED BUTTERFLY VALVE
FLANGED ECCENTRIC REDUCER
FLANGED UNION
FLEXIBLE CONNECTION
FLOW DIRECTION
FLOW METER
GATE VALVE
TRAP. ONE PIECE FACTORY FABRICATED
CHILLED WATER RETURN
CHILLED WATER SUPPLYCHWS
CHWR
HOT WATER HTG. SUPPLY
HOT WATER HTG. RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLYCWS
CWR
HWR
HWS
HIGH PRESSURE STEAM PIPING
LOW PRESSURE CONDENSATE PIPING
HPS
LPC
LOW PRESSURE STEAM PIPINGLPS
GLYCOL HEATING SUPPLY PIPINGGHS
GLYCOL HEATING RETURN PIPINGGHR
IMMERSION WELL
MANUAL VENT WITH BALL VALVE
UNION
VENTURI
WATER FLOW SWITCHWFS
TOP
BOT
FLAT OVAL DUCTFO
FLEXIBLE DUCT
SENSORS
CO2 SENSORCO2
NEW CONNECTION
COMBUSTION AIR, RISE AND DROP
PNEUMATIC 2-WAY VALVE
P & T PLUG IN IMMERSION WELL
PIPE DROP
PIPE INLINE DROP
PIPE INLINE RISE
PIPE RISER
PRESSURE GUAGE
PRESSURE GAGE W/BALL VALVE
R
RELIEF VALVE
SCREWED CONCENTRIC REDUCER
STEAM TRAP
STRAINER
THERMOMETER
THREADED HOSE CONNECTION REVISION DELTA#
CONDENSATE DRAIN PIPINGD
MECHANICAL ABBREVIATIONS
AD ACCESS DOOR
DEMO DEMOLITION
HTG HEATING
PRV PRESSURE REDUCING VALVE
AFF ABOVE FINISHED FLOOR
DET DETAIL
HVAC HEATING, VENTILATING & AIR
CONDITIONING
PSI POUNDS PER SQUARE INCH
AHU AIR HANDLING UNIT
DH DUCT HEATER
ALT ALTERNATE
DIA DIAMETER HW HOT WATER
RA RETURN AIR
AMB ANBIENT
DIM DIMENSION HWR HOT WATER HEATING
RETURN
RAD RADIATED
AMP AMPERE
DIV DIVISION
HWS HOT WATER HEATING
SUPPLY RCP RECIRCULATION PUMP
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE DMPR DAMPER
HZ HERTZ REF ROOFTOP EXHAUST FAN
IN INCHES REQD REQUIRED
APD AIR PRESSURE DROP DRN DRAIN
INWC INCHES OF WATER COLUMN REV REVISION
APPROX APPROXIMATE DS DOWNSPOUT
INWG INCHES OF WATER GAUGE RH RELATIVE HUMIDITY
ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
EA EXHAUST AIR
IU INDOOR UNIT RL REFRIGERANT LIQUID
KW KILOWATT
EF EXHAUST FAN
LAT LEAVING AIR TEMPERATURE
RPBP REDUCED PRESSURE
BACKFLOW PREVENTER
AVG AVERAGE
EFF EFFICENCY
LB POUND
B BOILER
EQ EQUAL
LPC LOW PRESSURE
CONDENSATE
RPM REVOLUTIONS PER MINUTE
EQUIP EQUIPMENT
LPS LOW PRESSURE STEAM
SA SUPPLY AIR
ERV ENERGY RECOVERY
VENTILATION
LWT LEAVING WATER
TEMPERATURE
SCHED SCHEDULE
BTU BRITISH THERMAL UNIT ESP EXTERNAL STATIC PRESSURE
MAU MAKEUP AIR UNIT
SEN SENSIBLE
BTU BTU PER HOUR ET EXPANSION TANK
MAX MAXIMUM
SL SEA LEVEL
C COMMON EWT ENTERING WATER
TEMPERATURE
MBH THOUSAND BRITISH
THERMAL UNITS/HOUR
SPEC SPECIFICATION
C CONVECTOR
EXH EXHAUST
MECH MECHANICAL
SSHP SPLIT SYSTEM HEAT PUMP
CA COMBUSTION AIR
EXT EXISTING
MECH RM MECHANICAL ROOM
STD STANDARD
CAP CAPACITY
F FAHRENHEIT
MFR MANUFACTURER
TEMP TEMPERATURE
CC COOLING COIL
F FURNACE
MIN MINIMUM
TSP TOTAL STATIC PRESSURE
CEF CEILING MTD EXHAUST FAN
FCU FAN COIL UNIT
MISC MISCELLANEOUS
TSTAT THERMOSTAT
CFM CUBIC FEET PER MINUTE
FLR FLOOR
MTD MOUNTED
TW TEMPERED WATER
CHWR CHILLED WATER RETURN
FLEX FLEXIBLE
NC NOISE CRITERIA
TYP TYPICAL
CHWS CHILLED WATER SUPPLY
FO FLAT OVAL
NC NORMALLY CLOSED
UH UNIT HEATER
CO2 CARBON DIOXIDE
FPM FEET PER MINUTE
NIC NOT IN CONTRACT
V
VOLT
COMB COMBUSTION
FPVAV FAN POWERED VAV
NOM NOMINAL
VAV VARIABLE AIR VOLUME
CONTR CONTRACTOR
FT FEET
NTS NOT TO SCALE
VD VOLUME DAMPER
CU CONDENSING UNIT
GALV GALVANIZED
OA OUTSIDE AIR
VERT VERTICAL
CU FT CUBIC FEET
GPM GALLONS PER MINUTE
OBD OPPOSED BLADE DAMPER
VFD VARIABLE FREQUENCY DRIVE
CU YD CUBIC YARDS
GHR GLYCOL HEATING RETURN
OU OUTDOOR UNIT
VOL VOLUME DAMPER
CUH CABINET UNIT HEATER
GHS GLYCOL HEATING SUPPLY
PUMP
W/ WITH
CV CONSTANT VOLUME
H FUME HOOD
POUNDS PER CUBIC FEET
W/O WITHOUT
CW COLD WATER
HORIZ HORIZANTAL
WB WET BULB
CWR CONDENSOR WATER RETURN
HP HIGH PRESSURE
WPD WATER PRESSURE DROP
CWS CONDENSOR WATER SUPPLY
HP HORSEPOWER
PH PHASE
DB DRY BULB
HP HEAT PUMP
PLUM PLUMBING
DD DUAL DUCT BOX
PPM PARTS PER MILLION
ASL ABOVE SEA LEVEL
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE RS REFRIGERANT SUCTION
P
PCF
PERF PERFORATE(D)
V
PD PRESSURE DROPHPS HIGH PRESSURE STEAM
HR HOUR
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DEG DEGREE FAHRENHEIT
AI ANALOG INPUT
AO ANALOG OUTPUT
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MECHANICAL
LEGEND & GENERAL
NOTES
M0.1
I:\
JO
B S
\2
\C
A D
\Z N
M
1.
dw g, /4 /2
3:
:3
P M
, t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
TELECOM
ELECTRICAL
MECHANICAL
CONRETE SLAB FOR RAISED
ACCESS FLOORING
UNEXCAVATED
NO FLOOR
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
T
T T
T mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
LOWER LEVEL
MECHANICAL
DEMOLITION PLAN
MD1.0
KEYED NOTES FOR SHEET MD1.0
1 REMOVE DUCTLESS SPLIT INDOOR UNIT, PIPING, AND
CONTROLS.
2 ELECTRIC UNIT HEATER TO REMAIN.
3 HVAC CONTROLS CONTROL PANEL (REMOVE ALERTON
BCM-ETH, ALERTON BCM-PWS, AND VYKON JACE-2).
4 DIRECT VENT WATER HEATER FLUE (5" OUTSIDE DIA.) TO
REMAIN.
5 REMOVE REFRIGERANT PIPING AND CONTROLS.
6 EXISTING DDC PANEL.
I:\
JO
B S
\2
\C
A D
\Z N
M D
0.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGE
STORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREA
OFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFFSTAIR
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
110 109
T T T
T
T
T
T
T
CO2
T
T
CO2
CO2
T T
T
T T
T
CO2 T
CO
T CO2
CO
CO2
7(TYP)
4 1
3 1 6
3 1
10"Ø (2)
12"X12"
12"Ø
10"Ø (3)
8"Ø (8)10"X10" 18"X18"
10"Ø
18"X18"
"Ø
10"Ø (3)
265(3)
20"Ø
20"X20"
20"X20"
18"X18"
10"Ø (3)
18"Ø
"Ø
16"X16"
36"X18"
24"X22"
10"Ø (4) 36"X18"
10"Ø
10"X10"
20"X20"
10"Ø
16"X12"
10"Ø
10"Ø 8"Ø
"X
"X
" 12"Ø(3)
12"X12"
8"Ø
26"X10"
26"X10"
26"X10"
14"X10"
12"X10"
8"X10"
8"X10"
8"X16" 8"Ø(2)
10"Ø
8"Ø
12"Ø
12"X12"
"X
"X
16"X12"8"Ø 6"Ø
18"X14"
18"X14"
"X
"Ø
(6 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MAIN LEVEL
MECHANICAL
DEMOLITION PLAN
MD1.1
KEYED NOTES FOR SHEET MD101
1 REMOVE ALERTON THERMOSTAT.
2 REMOVE DUCTLESS SPLIT UNIT REFRIGERANT PIPING
AND CONTROLS.
3 REMOVE CO2 SENSOR.
4 ELECTRIC RADIANT HEAT PANEL AND THERMOSTAT TO
REMAIN.
5 THERMOSTAT FOR DIFFUSER CONTROL DAMPER TO
REMAIN.
6 REMOVE CEILING EXHAUST FAN AND DUCT.
7 ROOFTOP UNIT ABOVE. SEE SHEET MD1.2.
8 DISCONNECT DUCT FROM EXHAUST FAN.
9 DISCONNECT DUCT FROM ROOFTOP UNIT.
10 REMOVE DIRECT VENT WATER HEATER FLUES AT ROOF.
I:\
JO
B S
\2
\C
A D
\Z N
M D
1.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
RTU-2
RTU-3
RTU-7
RTU-1
RTU-6
RTU-5
RTU-8
RTU-4
8"Ø
6"ØEF-1
CU-2
CU-1
1 1 mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
ROOF LEVEL
MECHANICAL
DEMOLITION PLAN
MD1.2
KEYED NOTES FOR SHEET MD1.2
1 REMOVE PACKAGED ROOFTOP UNIT, DUCT, CURB, AND
CONTROLS.
2 REMOVE EXHAUST FAN.
3 REMOVE EXHAUST VENTS.
4 REMOVE DUCTLESS SPLIT OUTDOOR UNIT, PIPING, AND
CONTROLS.
5 REMOVE 5" DIA OUTSIDE DIRECT WATER HEATER VENTS
AND SAVE FOR REUSE.
I:\
JO
B S
\2
\C
A D
\Z N
M D
2.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
TELECOM
ELECTRICAL
MECHANICAL
CONRETE SLAB FOR RAISED
ACCESS FLOORING
UNEXCAVATED
NO FLOOR
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
T
T
FC-2
FC-1
T T
4 1 1
S
5 S mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
LOWER LEVEL
REMODEL PLAN
MH1.0
KEYED NOTES FOR SHEET MH1.0
1 ELECTRIC UNIT HEATER TO REMAIN.
2 NEW REFRIGERANT PIPING AND CONTROLS.
3 EXISTING HVAC CONTROLS PANEL. MODIFY AS PER
CONTROLS PLANS.
4 EXISTING GAS FIRED WATER HEATER.
5 DDC SPACE TEMPERATURE SENSOR.
6 PROVIDE NEW ALERTON DDC HEAD END CONTROLS.
I:\
JO
B S
\2
\C
A D
\Z N
M H
0.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
WOMEN
MEN
RESTROOM
CUSTODIAL
STORAGE
STORAGESTORAGE
STORAGE
VESTIBULE
ROOM
COMMUNITY
STORY TIME
CHILDREN'S
USED BOOKS
HOLDS
WORK AREAOFFICE
MANAGER'S
HALLWAY
WORK AREA
STAFF
STAIR
LOBBY
LOCKERS
LIBRARY TOTAL
BOOK DROP
AREA
PRODUCTION
BREAK ROOM
STAFF
ROOM
CONFERENCE
LOUNGE
STAFF
111 113
124 126
T T
T
T
T T
T
S T T
S
S
S
S
T
T
T T
T
S S
S
CO2
CO2
CO2
CO2 CO
CO2
CO
CO2
EXT
350 (4)
D-1
D-1
EXT
EXT
10"Ø(4)
EXT
EXT
EXT
325 (2)
9 (TYP.)
EXT
363 (3)
EXT
225 (8)
EXT
363 (3)
EXT
290 (3)
EXT
(3)EXT
363 (3)
EXT
290 (3)
EXT
290 (2)
EXT
265 (3)
EXT
170 (3)
EXT
340 (3)
D-2
TT
D-2
EXT
150 (3)
EXT
105 (3)
EXT
110 (2)
EXT
110 (6)
EXT
125 (4)
EXT
EXT
EXT
350 (2)
EXT
175 (4)
T
D-2
EXT
290 (2)
EXT
500 (6)
10"Ø (2)
12"X12"
12"Ø
10"Ø (3)
8"Ø (8)10"X10" 18"X18"
10"Ø
18"X18"
10"Ø (3)
20"Ø
20"X20"
20"X20"
18"X18"
10"Ø (3)
26"X26"
34"X16" 18"Ø
"Ø
16"X16"
36"X18"
24"X22"
10"Ø (4)
34"X16 UP
26"X26 UP
36"X18"
10"Ø
10"X10"
20"X20"
16"X16"10"Ø
16"X18" UP
26"X10" UP
10"Ø
10"Ø
12"X12"
16"X18" UP
16"X16"
16"X16"
10"Ø
10"Ø
16"X12"
10"Ø
10"Ø
12"Ø
12"Ø
8"Ø
"X
"X
" 12"Ø(3)
12"X12"
8"Ø
26"X10"
26"X10" UP
26"X10"
16"X14"16"X18"UP
26"X10"UP
26"X10"8"Ø
14"X10"
12"X10"
8"X10"
8"X10"
8"X16" 8"Ø(2)
10"Ø
8"Ø
12"Ø
12"X12"
"X
"X
12"Ø
16"X12"8"Ø 6"Ø
18"X14"
18"X14"
"X
"Ø
(6
EF-2
EF-3
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MAIN LEVEL
MECHANICAL
REMODEL PLAN
MH1.1
KEYED NOTES FOR SHEET MH1.1
1 TRANSITION TO ROOFTOP UNIT.
2 EXISTING SOUND TRAP TO REMAIN.
3 EXISTING THERMOSTATICALLY CONTROLLED DIFFUSER
TO REMAIN.
4 NEW THERMOSTATICALLY CONTROLLED DIFFUSER AND
THERMOSTAT (DIV. 26 TO PROVIDE 120 VOLTS).
5 DIFFUSER NOT CONNECTED TO DUCT.
6 ELECTRIC CABINET UNIT HEATER TO REMAIN,
7 ELECTRIC CEILING RADIANT HEATER AND THERMOSTAT
TO REMAIN.
8 TRANSITION TO ROOFTOP EXHAUST FAN.
9 NEW ALERTON DDC TEMPERATURE SENSOR AND CO2
SENSOR.
10 NEW 5" DIA GAS VENTS FROM WATER HEATER.
11 TRANSITION TO 6" DIA DUCT AND RISE THROUGH ROOF.
12 NEW REFRIGERANT PIPING AND CONTROLS.
I:\
JO
B S
\2
\C
A D
\Z N
M H
1.
dw g, /4
/2
3:
:3
P
M , t aa rg
C
A A
J
J
H
H
G
G
F
F
E
D
B
RTU-2
RTU-3
RTU-7
RTU-1
RTU-6
RTU-5
RTU-8
RTU-4
HP-1
HP-2
6"Ø 6"Ø
1EF-1
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
ROOF LEVEL
MECHANICAL
REMODEL PLAN
MH1.2
KEYED NOTES FOR SHEET MH1.2
1 REFRIGERATION PIPES & CONTROLS DOWN THROUGH
ROOF.
2 EXHAUST DUCT AND ROOF CAP.
3 NEW WATER HEATER VENTS THROUGH ROOF.
RE-INSTALL WATER VENT CAPS.
I:\
JO
B S
\2
\C
A D
\Z N
M H
2.
dw g, /4
/2
3:
:3
P
M , t aa rg
ROOF MOUNTED DX COOLING
CONDENSING UNIT, SEE PLANS
NOTE: PROVIDE
WIND BAFFLE
#10 SCREWS, 8"O.C.
1-5/8" GALV. UNISTRUT
TO SUPPORT UNIT.
22 GA (MIN) G.I.
CURB CAP
SECURE UNIT TO UNISTRUT WITH
3/8" BOLTS INTO SPRING LOADED
NUTS IN UNISTRUT. (TYP)
2"X12" FIRE RESISTANT WOOD
FRAMING AT 12" O.C.
W/3/4" PLYWOOD DECK
ELECTRICAL DISCONNECT,
WIRING AND MECHANICAL
CHANNEL FRAME BY
ELECTRICAL CONTRACTOR
INSTALL SHEET METAL COVER
ON ALL REFRIGERANT PIPING
SEE DRAWING M101 FOR
CONTINUATION OF
MITER MECH CHANNEL, AND
BEND AROUND CURB CAP
3/8"Ø LAG BOLT (TYP)
DO NOT BOLT THRU TOP
OF CURB CAP
ROOFING, INSULATION
MEMBRANE AND BALLAST
BY OTHERS
16 GA. CLIP ANGLE-ATTACH
CURB SECURELY TO ROOF
HEAT PUMP UNIT DETAIL
SCALE N.T.S.
INSTALLED OUTDOORS
REFRIGERANT PIPING
ATTACH TO STRUCTURE
AGAINST CLAMP
BUTT INSULATION HANGER RODS
INSULATION ON
SUCTION LINES
THIS DETAIL TO BE USED
FOR 2 OR MORE PIPES
RUNNING PARALLEL
NOTE:
OR EQUAL
1-5/8" P-1000
"UNISTRUT" CHANNEL
ASSEMBLY
SCALE:
PIPE SUPPORT AT CEILING DETAIL
SUSPENDED REFRIGERANT
N.T.S.
SECURE PIPING TO
"CUSH-A-CLAMP" OR
SUPPORTS WITH
OR EQUAL
"HYDRA-ZORB".
BASE FLASHING
FIBER CANT STRIP-
SET IN BITUMEN
APPROX. 8" O.C.
INSULATE INSIDE OF
METALWORK IN COLD
CLIMATES W/ DUCT
GALVANIZED SHEET METAL HOOD
SHEET METAL OR FLEX-
AROUND AT HOOD
LINER AS SPECIFIED.
APPROX. 24" O.C.
TUBE COLLAR. CAULK ALL
2" NOMINAL
FASTENERS
FASTENERS
EXHAUST FAN
BIRD SCREEN
14" ROOF CURB
WITH 1-1/2" RIGID
INSULATION
ROOFING
ANCHOR FAN
TO CURB
SEAL
COUNTER FLASHING
UP UNDER FAN BASE
DUCT TRANSITION
FROM CEILING
GRILLE SIZE TO
DAMPER SIZE
BACKDRAFT DAMPER
SCALE:
ROOF EXHAUST FAN DETAIL
N.T.S.
ANCHOR TO ROOF
STRUCTURE
22 GA. BLADE
SPECIFICATIONS
45°TAP AND DAMPER ASSEMBLY
IS PRE MANUFACTURED - SEE
EACH END
3/8" SQUARE ROD
22 GA. RIGID SHEET METAL
WRAPPED WITH INSULATION.
NEOPRENE BUSHING
DETAIL G
DUCT
INSULATION
FLEX
NOTE: TAKE-OFFS SHOULD NOT BE INSTALLED CLOSER
THAN TWO WIDTHS TO ELBOWS OR INTERSECTIONS
LOCKING QUADRANT HANDLE
OR REMOTE CEILING
OPERATOR WHERE DAMPER
IS INACCESSIBLE
NYLON CLAMP OVER INSULATION
NYLON CLAMP OVER FLEX DUCT
RIGID ROUND
DUCT OR
DIFFUSER
COLLAR
FLOW
AIR
RIGID ELBOW
24 GA.
B
NOTE: AREA OF A X B
SHALL BE EQUAL TO
1.5 X AREA BRANCH DUCT
A
45°
CEILING
DIFFUSER
INSULATED
SEE DETAIL G
FLEX DUCT MAX
SEE DETAIL G
INSULATED FLEX DUCT.
MAX LENGTH 3'-0"
NO FLEXIBLE DUCT
AT 90° ELBOW
RIGID ELBOW
LENGTH 3'-0"
SCALE:
TAKE-OFF DETAIL
N.T.S.
SQUARE TO ROUND
EXTEND THROAT OF PLENUM
WHERE FLEX DUCT RUNS OVER
TOP OF RECESSED LIGHTING
CEILING TILE
"T"-BAR CEILING GRID
LINEAR DIFFUSER SEE PLANS
INLET COLLAR
CINCH BAND
INSULATED PLENUM
SCALE:
LINEAR DIFFUSER INSTALLATION DETAIL
N.T.S.7
ADHESIVE (MIRACLE PF 96)
LINER TO BE ADHERED
GALV.IRON DUCT
FROM EDGE OF LINER
NOT MORE THAN 2"
12"C.C. MAX
(TYP.)
BUTTED FIRMLY TOGETHER
ENDS OF LINER SHALL BE
(MIRACLE PF 96)
COATED W/ADHESIVE.
ALL ENDS OF LINER TO BE
SHALL OVERLAP
SECTION OF LINER
TOP AND BOTTOM
2"
THE SIDES
TO DUCT W/100%
"AUTOMATIC FASTENER EQUIP."
BY "GRIPNAIL AIR HAMMER" OR BY
GRIP NAILS SHALL BE INSTALLED
OMARK INSUL-PINS, DURO DYNE
METAL FASTENERS:
FASTENERS OR GRIP NAILS.
DUCT LINER
SCALE:
DUCT LINER DETAIL
N.T.S.8
SCALE:
#10 X 3/4" SELF-TAPPING
TIGHT AGAINST DUCT AND
SUPPORT MEMBERS. (TYP.)
CADMIUM PLATED SHEET METAL
SCREWS TO ANCHOR STRAPS TO
DUCT. ALL STRAPS ARE TO BE
DUCT STRAP HANGER DETAIL
NO POP RIVETS ALLOWED1"
HANGER STRAPS
ATTACH TO STRUCTURE
HANGER SIZES FOR RECTANGULAR
DUCT
MAX.
SIDE
HANGER HORIZANTAL
SUPPORT ANGLE
MAXIMUM
SPACING
30" 1"X18 GAGE STRAP NONE REQUIRED 8'-0"
38" 1
4" ROUND ROD 1-1/2"X1-1/2"X1/8" 8'-0"
48" 1
4" ROUND ROD 2"X2"X1/8" 8'-0"
60" 5
16" ROUND ROD 2"X2"X1/8" 8'-0"
84" 3
8" ROUND ROD 2"X2"X1/8" 8'-0"
N.T.S.9
OPPOSED BLADE DAMPER
AS PER SPECIFICATIONS
L = 1/4 W (4" MIN.)
AIR FLOW
CEILING DAMPER
REGULATOR
PROVIDE CONCEALED
45°
W
L
NOTE:
SCALE:
BRANCH DUCT TAKE-OFF & DAMPER DETAIL
N.T.S.10
SCALE:4 PIPING THRU ROOF DECK DETAIL
MULTIPLE REFRIGERANT
N.T.S.
SCALE:
ROOF TOP UNIT DETAIL
N.T.S.
STEEL ANGLE SEE
SEE SCHEDULE BELOW FOR
1/2"Ø A307 THROUGH BOLTS
QUANTITY AND LAYOUT
STRUCTURAL DRAWINGS
6" MIN. 48"O.C. MAX.
UN
IT
S
HO
RT
DI
ME
NS
IO
N
UNIT LONG DIMENSION
NO BOLTS REQUIRED
AT SHORT END
RTU BOLT SCHEDULE
SIZE TON WEIGHT
LBS
MIN. #
BOLTS*
3-6 900 (4) 12"Ø
7.5-12.5 1500 (4) 12"Ø
15 2880 (4) 12"Ø
17.5 2900 (4) 12"Ø
20-25 3610 (4) 12"Ø
*NOTE: PROVIDE ADDITIONAL BOLTS AS NEEDED TO MEET THE FOLLOWING LAYOUT
REQUIREMENTS:
- (1) BOLT MINIMUM REQUIRED WITHIN 6" OF EACH CORNER
- MAXIMUM SPACING BETWEEN BOLTS SHALL NOT EXCEED 48"
- NO BOLTS REQUIRED AT SHORT END OF UNIT
ROOF INSULATION
CANT STRIP (AS REQUIRED)
MECHANICAL CONTRACTOR)
AIR CONDITIONING UNIT
COUNTER FLASHING (BY
ROOF CURB
MECHANICAL CONTRACTOR)
RIGID INSULATION (BY
ANCHOR ROOF CURB
SECURELY TO ROOF
MANUFACTURER)
WOOD NAILER (BY UNIT
STRUCTURE.
NOTE:
ROOF DECK
ROOFING
ANCHOR VIBRATION ISOLATOR
SECURELY TO ROOF CURB
NEOPRENE GASKET
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MECHANICAL
DETAILS
M5.1
I:\
JO
B S
\2
\C
A D
\Z N
M
1.
dw g, /4 /2
3:
:3
P M
, t aa rg
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MECHANICAL
SCHEDULES
M6.1
I:\
JO
B S
\2
\C
A D
\Z N
M
1.
dw g, /4 /2
3:
:3
P M
, t aa rg
FAN MOTOR
STARTER
DI - STATUS
DO - START/STOP
MOTOR
SCALE:1 EF-1 EXHAUST FAN CONTROL SCHEMATIC
N.T.S.
DI STATUS
DO START/STOP
AI - SPACE TEMPERATURES
SCALE:2 EF-2&3 EXHAUST FAN CONTROL
N.T.S.
SCALE:
DUCTLESS SPLIT CONTROL
N.T.S.5
AI - SPACE TEMPERATURES
SCALE:
DOMESTIC RECIRCULATION PUMP CONTROL
N.T.S.3
DO - START/STOP
AI - PIPE SENSOR
RECIRCULATION PIPE
SA
AI
SPACE
ROOM
TEMP
SENSOR
SA
FAN
D X
FILTER
DI
OA
RA
N.C.
SPACE PRESSURE
SA TEMP
120 VAC
PREVIOUS CONTROLLER
E-BUS
NEXT CONTROLLER
N.O.
SCALE:4 ROOF TOP UNIT CONTROL SCHEMATIC
N.T.S.
1 S 1
CO2 5
CR
DP 4
CONTROLLER
SUPPLY FAN CURRENT RELAY 3
FILTER ALARM 4
SPACE CO2 SENSOR 5
AI
AI
DI
DI
AI
DO
AO
SPACE TEMPERATURE 6 AI
ENABLE/DISABLE RTU
CO2 SENSOR OUTPUT TO RTU
S 6
Ps 2SPACE
PRESSURE
3DO CALL FOR COOLING STAGE 1
4DO CALL FOR COOLING STAGE 2
5DO CALL FOR HEATING STAGE 1
6DO CALL FOR HEATING STAGE 2
7AO RELIEF AIR CONTROL
PACKAGED ROOFTOP
TO CONTROL ECONOMISER
FOR OUTSIDE AIR DAMPER
T
CONNECT TO EXISTING RECIRC. PUMP
AND PROVIDE ECONOMISER
FAULT DETECTION.
mail@hhyassoc.com
Salt Lake City, UT 84106
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M A
G N
A L
IB
R
A R
Y R
O O
F
TO
P E
Q U
IP
M
E N
T R
E P
LA
C
E M
E N
T
S
W
, M A
G N
A , U
T
EXP. 03/31/27
MECHANICAL
CONTROLS
ME5.1
I:\
JO
B S
\2
\C
A D
\Z N
M E
1.
dw g, /4
/2
3:
:3
P
M , t aa rg
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M
AG
N A
LI
BR
AR
Y
R O
O F
TO
P
EQ
U
IP
M
EN
T
R
EP
LA
C
EM
EN
T
S
W
, M
AG
N A, U T
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com 2026-161.00
SYMBOLS, SCHEDULES
AND NOTES
EG0.1
ELECTRICAL SYMBOL SCHEDULE GENERAL NOTES
1. MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED FLOOR TO CENTER OF OUTLET BOX.
2. WHERE OUTLETS, DEVICES, AND EQUIPMENT ARE NOTED BY SUBSCRIPTS, REFER TO ABBREVIATION SCHEDULE FOR DEFINED
REQUIREMENTS.
3. WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE COUNTER. IF COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND COORDINATE WITH CASEWORK
SUPPLIER.
4. NOT ALL ELECTRICAL SYMBOLS MAY BE USED.
MOUNTING REMARKSDESCRIPTIONSYMBOL
NAME
PANEL
NAME
PANEL ELECTRONIC SYSTEMS MAY INCLUDE BUT
ARE NOT SPECIFICALLY LIMITED TO,
TELEPHONE, DATA, TELEVISION, LIGHTING
CONTROL, CLOCKS, FIRE ALARM, ACCESS
CONTROL, SECURITY, CCTV, SOUND
SYSTEM, NURSE CALL, OR INTERCOM.
ELECTRONIC SYSTEM GENERAL SYMBOLS
ELECTRONIC SYSTEM PANELBOARD (SURFACE MOUNT) TOP AT 72"
ELECTRONIC SYSTEM PANELBOARD (FLUSH MOUNT) TOP AT 72"
TOP AT 72"ELECTRONIC SYSTEM TERMINAL BOARD
DESCRIPTIONSYMBOL MOUNTING REMARKS
TELEPHONE OUTLET
DATA OUTLET
COMBINATION TELEPHONE/DATA OUTLET
TELEPHONE TERMINAL BOARD
+18"
+18"
+18"
TOP AT 72"
TELEPHONE / DATA SYMBOLS
GENERAL PROJECT NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR READING AND APPLYING WHAT IS IN THE SPECIFICATIONS TO
THIS PROJECT. ANYTHING THAT IS NOT INCLUDED ON THE PROJECT THAT IS CALLED OUT IN THE
SPECIFICATION SHALL BE LISTED ON THE SUBSTANTIAL COMPLETION PUNCHLIST. THE
CONTRACTOR WILL BE REQUIRED TO REMEDY THESE DEFICIENCIES. THERE WILL BE NO
EXCEPTIONS.
2. THE CONTRACTOR MAY SCHEDULE A PRE-CONSTRUCTION MEETING AT THEIR DISCRETION, WITH
THE ELECTRICAL ENGINEER AND REVIEW THE DRAWINGS AND SPECIFICATIONS. THE MEETING
SHALL BE A MAXIMUM OF ONE HOUR AND SHALL TAKE PLACE AT THE ENGINEER'S OFFICE WHERE
POSSIBLE.
3. THE FOLLOWING ITEMS ARE SOME OF THE REQUIREMENTS THAT ARE LISTED IN THE
SPECIFICATIONS. THESE ITEMS DO NOT REPRESENT ALL ITEMS AND THE CONTRACTOR IS
RESPONSIBLE FOR MEETING ALL REQUIREMENTS OF THE SPECIFICATIONS:
A. INSULATED THROAT CONNECTORS OR PLASTIC BUSHINGS SHALL BE UTILIZED FOR ALL
CONDUIT SIZES USED ON THIS PROJECT.
B. A DEDICATED NEUTRAL CONDUCTOR WILL BE PROVIDED FOR ALL LIGHTING AND POWER
CIRCUITS.
C. THE CONTRACTOR SHALL LABEL ALL ELECTRICAL EQUIPMENT AS IT IS CALLED OUT IN THE
SPECIFICATIONS.
D. THE CONTRACTOR SHALL PROVIDE SEISMIC SUPPORT AND BRACING FOR ALL ELECTRICAL
EQUIPMENT AS REQUIRED BY LOCAL AND NATIONAL CODE.
4. THE CONTRACTOR SHALL FOLLOW THE PANELBOARD SCHEDULES AS INDICATED IN THE DRAWINGS.
EACH CIRCUIT BREAKER HAS BEEN ASSIGNED A SPECIFIC AREA OF THE BUILDING. NO DEVIATION
WILL BE ALLOWED WITHOUT THE APPROVAL FROM THE ELECTRICAL ENGINEER.
5. THE CONTRACTOR SHALL INSTALL THE WIRE SIZES AS CALLED OUT ON THE ONE-LINE DIAGRAM, EQUIPMENT SCHEDULES, VOLTAGE DROP TABLES, AND ELECTRICAL SPECIFICATIONS. HOWEVER, THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE WIRE IS LARGE ENOUGH FOR VOLTAGE DROP.
6. THE CONTRACTOR SHALL VERIFY ALL MECHANICAL OVERCURRENT DEVICES FOR THE ACTUAL
MECHANICAL EQUIPMENT SUPPLIED ON THE JOB, PRIOR TO RELEASE OF ANY ELECTRICAL
DISTRIBUTION EQUIPMENT. CONTACT THE ELECTRICAL ENGINEER WITH ANY DISCREPANCIES.
7. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF HIS WORK. NO EXTRA
PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF EXTRA WORK MADE
NECESSARY BY THEIR FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL
BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE AND THE ENGINEER FOR
CLARIFICATION.
8. THE CONTRACTOR SHALL MAKE SURE THAT ALL EXISTING BRANCH CIRCUITS THAT ARE AFFECTED BY THIS PROJECT ARE NOT OVERLOADED AS A RESULT OF WORK UNDER THIS CONTRACT. PROVIDE ADDITIONAL BRANCH CIRCUITS FROM ELECTRICAL PANELS AS NECESSARY TO COMPLY WITH THE
BRANCH CIRCUIT LOADING REQUIREMENTS. PROVIDE ALL MATERIAL AND LABOR AS NECESSARY
FOR A COMPLETE AND OPERATING SYSTEM.
9. PROVIDE UPDATED, TYPED PANELBOARD SCHEDULE(S) TO REFLECT ALL THE CHANGES MADE, INCLUDING EXISTING LOADS. THE EXISTING LOADS SHALL BE NAMED THE SAME AS LISTED ON THE
EXISTING PANELBOARD SCHEDULE.
ELECTRICAL SHEET INDEX
NOTE: NOT ALL ABBREVIATIONS MAY BE USED.
ABBREVIATION SCHEDULE
ABOVE COUNTER
AMP OR AMPS
ADJACENT
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
ALUMINUM
AUTOMATIC TRANSFER SWITCH
AUXILIARY
AMERICAN WIRE GAUGE
BUILDING AUTOMATION SYSTEM
BUILDING
CONDUIT
CIRCUIT BREAKER
CIRCUIT
CEILING
CONVENIENCE OUTLETS
COPPER
DISTRIBUTED ANTENNA SYSTEM
EXISTING
EACH
EQUIPMENT GROUND
EQUIPMENT GROUNDING CONDUCTOR
ELECTRICAL
EMERGENCY
ELECTRIC METALLIC TUBING
ELECTRIC NONMETALLIC TUBING
EQUIPMENT
ELECTRIC WATER COOLER
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
FIBER OPTIC
FREIGHT ON BOARD
FEED-THROUGH LUGS
GROUNDING ELECTRODE CONDUCTOR
GROUND CONDUCTOR
HAND-OFF-AUTO
HORSE POWER
INTERSYSTEM BONDING TERMINATION BAR
INTRUSION DETECTION
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INSULATED
ISOLATED
KILO CIRCULAR MIL
KILO VOLT AMPERES
KILOWATTS
LIQUID-TIGHT NONMETAL CONDUIT
LONG-TIME, SHORT-TIME
A A
ADJ
AFF
AHJ
AL
ATS
AUX
AWG
BAS
BLDG
C
CB
CKT
CLG
CO
CU
DAS
(E)
EA
EG
EGC
ELEC
EM
EMT
ENT
EQUIP
EWC
EXP
FA
FACP
FLA
FMC
FO
FOB
FTL
GEC
GND
HOA
HP
IBT
ID
IG
IMC
INS
ISO
KCMIL
KVA
KW
LFNC
LS
LONG-TIME, SHORT-TIME INSTANTANEOUS
LONG-TIME, SHORT-TIME INSTANTANEOUS GROUND FAULT
LIGHTING
MAIN BONDING JUMPER
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MAIN LUGS ONLY
MEDIUM VOLTAGE
MICROWAVE
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
ON CENTER(S)
OVER CURRENT PROTECTION
OVER CURRENT PROTECTION DEVICE
PUBLIC ADDRESS
PHASE
PHOTOVOLTAIC
POWER
QUANTITY
REMOVE
REFRIGERATOR
REQUIREMENTS
RIGID GALVANIZED CONDUIT
RIGID METAL CONDUIT
ROCKY MOUNTAIN POWER
RIGID NONMETALLIC CONDUIT
REMOVE AND RELOCATE
SYSTEM BONDING JUMPER
SECURITY CONTROL PANEL
SUB-FEED LUGS
SURGE PROTECTIVE DEVICE
SURGE SUPPRESSION
SUPPLY SIDE BONDING JUMPER
TELECOMMUNICATION GROUNDING BUS BAR
TELECOMMUNICATION MAIN GROUNDING BUS BAR
TAMPER RESISTANT
TELEPHONE TERMINAL BOARD
TYPICAL
UNDER FLOOR
UNDERGROUND
UNLESS NOTED OTHERWISE
UNIVERSAL SERIAL BUS
VIDEO SURVEILLANCE SYSTEM
WITH
WITHOUT
WEATHER PROOF
WEATHER RESISTANT
TRANSFORMER
LSI
LSIG
LTG
MBJ
MCA
MCB
MLO
MV
MW
NC
NEC
NIC
NL
NO
OC
OCP
OCPD
PA
PH
PV
PWR
QTY
R
REF
REQ
RGC
RMC
RMP
RNC
RR
SBJ
SCP
SFL
SPD
SS
SSBJ
TGB
TMGB
TR
TTB
TYP
UF
UG
UNO
USB
VSS
W/
WO/
WP
WR
XFMR
FIRE ALARM SYMBOLS
D
BDT
BDR
FSD
T
W
F
Z
I
R
D
WF
H
M
M
S
B
DESCRIPTIONSYMBOL MOUNTING REMARKS
EOL
4" BELOW
CEILING TO TOP
OF DETECTOR
MANUFACTURER
RECOMMENDED
AT VALVE
ON FIRE RISER
CEILING
CEILING
SIDE OF DUCT
+48"
AT DEVICE(S) TO
BE CONTROLLED
AT DEVICE(S) TO
MONITOR
AT FAN CONTROL
PANEL
COORDINATE
WITH DOOR
INSTALLER
FLOOR
80" MIN AND 96"
MAX; MEASURED
FROM LENS.
IF CEILING IS
LESS THAN 80",
MOUNT WITHIN
6" OF CEILING.
FURNISHED BY FIRE PROTECTION
CONTRACTOR AND INSTALLED AND
CONNECTED BY DIV. 26
COORDINATE WITH DOOR INSTALLER;
SUBSCRIPT 'F' INDICATES TO MOUNT
AT FLOOR LEVEL
FIRE PROTECTION SPRINKLER RISER BELL
FIRE ALARM AUDIO/VISUAL SPEAKER/STROBE
FIRE ALARM AUDIO SPEAKER
MINI AUDIO/VISUAL HORN/STROBE
FIRE ALARM AUDIO/VISUAL HORN/STROBE
FIRE ALARM VISUAL STROBE
MINI AUDIO HORN
AUDIO HORN
WATER FLOOD INDICATOR
MAGNETIC DOOR HOLDER
FAN SHUTDOWN RELAY
MONITOR MODULE
CONTROL MODULE
FIRE ALARM MANUAL STATION
DUCT SMOKE DETECTOR
SMOKE DETECTOR
HEAT DETECTOR
FIRE/SMOKE DAMPER
WATER FLOW INDICATOR
TAMPER SWITCH
END OF LINE DEVICE
BEAM DETECTOR - RECEIVER
BEAM DETECTOR - TRANSMITTER
+90"
4" BELOW
CEILING TO TOP
OF DETECTOR
SUBSCRIPT 'WP' INDICATES THAT A
WEATHER PROOF BACK BOX IS REQ.
SUBSCRIPT 'C' INDICATES CEILING
MOUNTING.
NUMERIC SUBSCRIPT INDICATES
CANDELLA RATING OF STROBE
(I.E. - 15, 75, 110)
GF
T
F
T
VFD
RVS
DESCRIPTIONSYMBOL MOUNTING REMARKS
GEAR AND CONTROL SYMBOLS
FLOOR OR WALL
AS SPECIFIED
TOP AT +72" IF
WALL MOUNTED
TOP AT +72" IF
WALL MOUNTED
14"W X 3"D
14"W X 3"D
20"W X 6"D
20"W X 6"D
THESE SYMBOLS ARE GENERAL IN
NATURE AND MAY VARY IN SIZE AND
SHAPE TO SUIT APPLICATION. CROSS
HATCHING INDICATES "MAIN
PANELBOARD OR SWITCHBOARD" NAME
IS INDICATED IN SEMI-QUOTES (I.E. 'L2A',
'MDP')
FURNISH SWITCH UNLESS FURNISHED
BY ANOTHER DIVISION. INSTALL AND
CONNECT COMPLETE. REFER TO
RELATED SPECIFICATION SECTIONS.
PROVIDED BY DIVISION 23
MANUAL STARTER WITH THERMAL OVERLOAD(S)
ELECTRIC MOTOR
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
CIRCUIT BREAKER AND ENCLOSURE
MAGNETIC STARTER
COMBINATION MAGNETIC STARTER / NON-FUSED DISCONNECT
COMBINATION MAGNETIC STARTER / FUSED DISCONNECT
COMB. MAGNETIC STARTER / MOTOR CIRCUIT PROTECTOR
(MCP)
COMB. VARIABLE FREQUENCY DRIVE / MOTOR CIRCUIT
PROTECTOR (MCP)
REDUCED VOLTAGE STARTER
LOAD CENTER (SURFACE-MOUNTED)
LOAD CENTER (FLUSH-MOUNTED)
LIGHTING AND APPLIANCE PANELBOARD (SURFACE-MOUNTED)
LIGHTING AND APPLIANCE PANELBOARD (FLUSH-MOUNTED)
POWER DISTRIBUTION PANELBOARD
SWITCHBOARD
METER BASE
OPEN - STOP - CLOSE SWITCH
HVAC THERMOSTAT
HAND - OFF - AUTO SWITCH
GROUND FAULT PROTECTION
+60"
+60"
+60"
TOP AT +72"
FLOOR
WALL
TOP AT +72"
TOP AT +72"
TOP AT +72"
TOP AT +48"-72"
AT EQUIPMENT
TOP AT +72"
FLOOR OR WALL
AS SPECIFIED
TOP AT +48"-72"
TOP AT +48"-72"
TOP AT +48"-72"
TOP AT +48"-72"
TOP AT +48"-72"
TOP AT +48"-72"
WIRING DEVICE SYMBOLS
(5-20R)
J a
K
P
DIM
TIM
LV
a
3PM
3PN
DESCRIPTIONSYMBOL MOUNTING REMARKS
SUBSCRIPT KEYS SWITCH TO FIXTURES
CONTROLLED.
RATE DIMMER SWITCH FOR MAXIMUM
POSSIBLE WATTAGE
DUAL LEVEL SWITCH OUTBOARD LAMPS
SEPARATELY FROM INBOARD LAMPS.
REFER TO DETAIL UP-ON;
CENTER-NEUTRAL; DOWN-OFF
CEILING MOUNTED WITH SUBSCRIPT 'C';
WALL-MOUNTED WITH SUBSCRIPT 'W'
UP-ON; CENTER-OFF; DOWN-ON
RANGE -- NEMA 14-50R
DRYER -- NEMA 14-30R
SUBSCRIPT IN PARENTHESIS INDICATES
NEMA CONFIGURATION IF SHOWN. REFER
TO DRAWINGS AND/OR EQUIPMENT
SCHEDULES. CONFIRM EXACT
CONFIGURATION WITH OWNER PRIOR TO
INSTALLATION.
REFER TO DETAIL
4" ABOVE
BACKSPLASH
SINGLE-POLE TOGGLE SWITCH
SINGLE-POLE TOGGLE SWITCH
DOUBLE-POLE TOGGLE SWITCH
THREE-WAY TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
KEY-OPERATED SINGLE-POLE TOGGLE SWITCH
SINGLE-POLE TOGGLE SWITCH WITH PILOT LIGHT
DIMMER SWITCH
TIMER SWITCH
(2) SINGLE-POLE TOGGLE SWITCH
LOW VOLTAGE MOMENTARY CONTACT SWITCH
3-POSITION MOMENTARY CONTACT SWITCH
3-POSITION MAINTAINED CONTACT SWITCH
OCCUPANCY SENSOR
SPLIT-WIRED DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
FOURPLEX RECEPTACLE
SIMPLEX RECEPTACLE
125/250V RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTER FOURPLEX
RECEPTACLE
EMERGENCY DUPLEX RECEPTACLE
EMERGENCY FOURPLEX RECEPTACLE
MULTI-OUTLET ASSEMBLY
POWER / TELEPHONE POLE
CORD DROP WITH DUPLEX RECEPTACLE
SPECIAL PURPOSE OUTLET
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
AS NOTED
+18"
+18"
+18"
+18"
+18"
+18"
+18"
+18"
+18"
FLOOR/CEILING
+18"
OS WALL MOUNTED OCCUPANCY SENSOR SWITCH
DUAL RELAY WALL MOUNTED OCCUPANCY SENSOR SWITCH
+48"
+48"OS
EG0.1 SYMBOLS, SCHEDULES & NOTES
EG5.1 ELECTRICAL DETAILS
ED1.0 BASEMENT ELECTRICAL DEMOLITION PLAN
ED1.1 MAIN LEVEL ELECTRICAL DEMOLITION PLAN
ED1.2 ROOF ELECTRICAL DEMOLITION PLAN
EE1.0 BASEMENT ELECTRICAL FLOOR PLAN
EE1.1 MAIN LEVEL ELECTRICAL FLOOR PLAN
EE1.2 ROOF ELECTRICAL FLOOR PLAN
EE6.1 ELECTRICAL SCHEDULES
EE7.1 ELECTRICAL ONE-LINE DIAGRAMS
V:\26\2026-161.00 - SLCO - Magna Library Rooftop Equipment Replacement\01_Dwgs\EG0.1.dwg, 8/5/2026 11:59:41 AM, _DWG To PDF.pc3
Fax: 801 466 6022
Suite 210 2180 South 1300 East
Phone: 801 466 3996
M
AG
N A
LI
BR
AR
Y
R O
O F
TO
P
EQ
U
IP
M
EN
T
R
EP
LA
C
EM
EN
T
S
W
, M
AG
N A, U T
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com 2026-161.00
ELECTRICAL
DETAILS
EG5.1
NOTES:
FIRE ALARM AND
GENERATOR ANNUNCIATOR
COUNTERTOP ONLY
COUNTERTOP WITH
BACKSPLASH
FIRE ALARM STROBE
AND HORN/STROBE DISCONNECT SWITCH (TYP)
ELECTRICAL PANELBOARD,
FACP PANEL AND SECURITY PANEL
48"-72"
TO TOP
80" BOTTOM MIN.
96" TOP MAX.
(MEASURED
FROM LENS)
18" MIN.
48" MAX.
ADA PUSH BUTTONS, LIGHTING
CONTROLS, FIRE ALARM PULL
STATIONS, AND CARD ACCESS
60" DATA, PHONE, AND
ELECTRICAL OUTLETS
4"
CASEWORK;
BY OTHERS
LAY-IN OR HARD LID CEILING
4"
4"
FIRE ALARM BEAM DETECTOR
SMOKE AND HEAT
DETECTORS
SURFACE MOUNT CONDUITS ON
STRUCTURE. DO NOT PENDANT
MOUNT CONDUITS
DECK STRUCTURAL
JOIST OR BEAM
72" MAX
TO TOP
30'-0" MAX
CEILING MOUNTED
FIRE ALARM STROBE
AND HORN/STROBE
6" MAX (IF CLG IS
LESS THAN 80")
1.
2.
MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED
OTHERWISE ON THE DRAWINGS. UNLESS NOTED OTHERWISE , HEIGHTS ARE GIVEN FROM
FINISHED FLOOR TO CENTER OF OUTLET BOX.
WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4"
ABOVE COUNTER. IF COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER
TO ARCHITECTURAL INTERIOR ELEVATIONS AND COORDINATE WITH CASEWORK SUPPLIER.
BEAM CLAMP, HANGER CLAMP
OR APPROVED SUPPORT, AS
REQUIRED BY WEIGHT
SUPPORTED
CONDUIT CLAMP - 3/4" TO 1"
STRUT 2 PIECE CHANNEL PIPE
STRAPS - 1/4" TO 6"
STRUT CHANNEL - SIZE AS
REQUIRED BY WEIGHT
SUPPORTED PLUS ADDTIONAL
FUTURE CAPACITY AS SPECIFIED
ALL THREAD ROD-
SIZE AS REQUIRED
RACEWAY 3/4" TO 6"
(TYPICAL)
STRUCTURAL UNIT-
(BEAM, JOIST, SLAB, ETC.)
NOTES:
1. PROVIDE SUPPORT EVERY 8' OF CONDUIT RUN.
RACEWAY, 3/4" THRU 6"
CONDUIT HANGER
STRUCTURAL UNIT
RACEWAY - 3/4" THRU 1"
STRUCTURAL UNIT
BEAM CLAMP OR HANGER
CLAMP AS REQUIRED BY
WEIGHT SUPPORTED
ALL THREAD-SIZE
AS REQUIRED
BEAM CLAMP OR HANGER
CLAMP AS REQUIRED BY
WEIGHT SUPPORTED
NOTES:
1. THE WIRE SHALL NOT BE USED AS A COMPONENT OF
ANY RACEWAY HANGER SYSTEM. PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE WITH NEC AND
SPECIFICATION SPACING
REQUIREMENTS FOR TYPE OF
RACEWAY REQUIRED
BOX SUPPORT
AS REQUIRED FOR TYPE
OF CONSTRUCTION
TYPICAL
OUTLET BOX
BAR
STRAPS
BAR STRAPSTYPICAL WALL OUTLET
BAR STRAPS
NOTES:
TYPICAL
OUTLET BOX
1.
2.
3.
4.
TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.
PLASTER RINGS NOT SHOWN.
LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.
OUTLETS ON OPPOSITE SIDES OF FIRE RATED WALLS OR PARTITIONS IN THE SAME STUD SPACE MUST BE SEPARATED BY A
MINIMUM OF 24" HORIZONTAL DISTANCE.
A1-40
A1-40/IG
PROVIDE 4-11/16"x4"-11/16"x2-1/8" DEEP JUNCTION BOX
WITH SINGLE GANG PLASTER RING AND
EXTEND 1" CONDUIT WITH NYLON PULL
ROPE TO ACCESSIBLE CEILING.
TERMINATE CONDUIT IN CEILING SPACE
WITH A NYLON BUSHING. CABLE TO BE
PROVIDED BY OWNER.
ISOLATED GROUND CIRCUIT.
DESIGNATION OF CIRCUIT. WIRE
COMPLETE.
CP 25WB CAULK ON
BOTH SIDES OF
WALL
DAMMING MATERIAL
(BACKER ROD, FIBER-GLASS OR
MINERAL WOOL).
METAL PIPE
OR
CONDUIT
FIRE RATED CONCRETE
WALL (SOLID OR
BLOCK)
METALLIC CONDUIT
1/4" MINIMUM
DIAMETER
BEAD OF 3M FIRE
BARRIER CP 25 CAULK
OR MP MOLDABLE
PUTTY
1/4" MINIMUM
DIAMETER BEAD OF
3M FIRE BARRIER CP
25 CAULK OR MP
MOLDABLE PUTTY
STEEL STUD
GYPSUM BOARD
SOUND ATTENUATION
INSULATION (STC WALLS)
NOTE:
1. TYPICAL DETAILS SHOWING
GENERAL FIRE STOPPING
PROCEDURE. ACTUAL PROCEDURE
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .