12-08-MP27007-25333790 UVU - Data Points List.pdf

PDF 316 KB Posted

Attached to
DFCM Construction - VBS Consultant Services - Programming & Design - Utah Valley University - Student Athletic Center - 25333790
Solicitation number
MP27007
Issued by
Utah

About this file

This is a Building Automation System (BAS) Data Points List for Utah Valley University's Student Athletic Center project, a $3,100,000 repair and remodel initiative undertaken by the State of Utah Division of Facilities Construction and Management (DFCM). The document serves as a comprehensive specification for monitoring and control points across multiple building systems. The data points list encompasses air handlers, exhaust air handlers, domestic and industrial hot water systems, building reheat systems, glycol hot water loops, boiler systems, chilled water systems, chillers, cooling towers, heat exchangers, fan coil units, variable frequency drives, VAV terminal units, fume hood labs, exhaust fans, power meters, compressors and vacuum pumps, water meters, gas meters, unit heaters, automatic transfer switches, and VRF systems. Each system category specifies required data points with corresponding capabilities including digital input/output, analog input/output, hardwire interlock, BAS communication, dynamic flow diagrams, start/stop display, status display, value adjustment, alarm functionality, local alarm, email alerts, and 15-minute trend logging.

The data points specification establishes the technical requirements for building system integration and performance monitoring throughout the facility. The list indicates varying levels of monitoring sophistication across different system components, with some points requiring simple status display while others demand complex calculated values such as kWh from current transducers, pressure differentials, and load percentages. The document does not specify pricing terms, set-asides, contract duration, response deadlines, or award dates. The comprehensive nature of the data points list suggests this is part of the design phase for the athletic center project, defining the scope of building automation and controls integration necessary for effective facility operations and energy management.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Description of Points

D ig it al

In p u t

D ig it al

O u tp u t

A n al o g In p u t

A n al o g O u tp u t

H ar d w ir e

In te rl o ck

B A

S C o m m u n ic at io n yn am ic

F lo w D ia gr am s

St ar t/ St o p is p la y St at u s

D is p la y V al u e

A d ju st

V al u e

A la rm L o ca l

A la rm E m ai l

Tr en d m in

Air Handlers

Supply Fan VFD (Points per VFD) Refer to VFD in the list

Supply Fan Start/Stop (if not on VFD) x x x x x x

Supply Fan Status (if not on VFD) x x x x x x x x

Supply Fan Run Time x x

Calculated kWH from CT from status x x

Calculated kW x x

Supply Air Static Pressure x x x x x

Low Temp Detector (Freeze Stat) x x x x x

Pressure Relief Doors x x x

Pre-Filter Differential Pressure x x x

Final Filter Differential Pressure x x x

High Static Pressure Switch x x x

Low Static Pressure Switch x x x

Outside Air Damper x x x x x x

Discharge Isolation Damper Status x x x Discharge Isolation Damper Command x x x Return Air Damper x x x x x

Supply Air Temperature x x x x x

Pre-Heat Coil Discharge Air Temperature x x x x

Heat Recovery Coil DAT x x x x

Cooling Coil Valve x x x x x

Indirect Cooling Coil Valve x x x x x

Pre-Heat Coil Valve x x x x x

Heat Recovery Coil Valve x x x x x

Heating Coil Valve x x x x x

Cooling Coil Discharge Air Temperature x x x x

Indirect Cooling Coil DAT x x x x x

Heating Coil Discharge Air Temperature x x x x

Evap Media Discharge Air Temperature x x x x

Evap Media Humidity Sensor x x x x

Evap Media Pump x x x x

Evap Media Status x x x x

Evap Sump Drain x x x x

Evao End Switch for Drain x x x

Input/Outputs Graphics Other

Evap Sump Fill x x x x

Evap Sump Flush x x x

Mixed Air Dampers x x x x x

OA Sensor at the AHU (not a general OA sensor) x x x x

Return Air Tep x x x

Return Ar Humidity x x x

Mixed Air Temp x x x x

CO2 Return x x x x

CO2 Outside Sensor x x x

OA DB x x

OA WB x x

OA Flow Meter x x x

Occupancy x x x

Cooling Load PID (showing stages of cooling) x x x

Heating Load PID 9showing stages of heating) x x x

DAT Setpoint x x

Duct Pressure Setpoint x x

Heat Recovery Enable Disable Temp x x

Exhuast Air Handlers

Ehaust Fan VFD (Points per VFD) Refer to VFD list

Fan Start/Stop x x x x x

Fan Status x x x x x x x

Fan Runtime x x

Fan Inlet High Static Pressure Switch x x x x

Ehaust Air Pre-filter Differential Pressure x x

Reclaim Coil Valve x x x x x

Reclaim Coil Discharge Air Temp x x x x

Ehaust Duct Static Pressure x x x x

Ehaust AirIsolation Damper x x x x x x

Ehaust Air Bypass Damper x x x x x

Stack Differential Pressure x x x x

Exhaust Air Temperature x x x x

Occupancy x x x

Duct Pressure Setpoint x x

Reclaim Enable/Disable Temp x x

Domestic/Industrial Hot Water Systems

Pump Enable x x x x

Pump Current Transducer x x x x

Pump Runtime x x

Calculated kWH from CT x x

DHW Heater enable x x x x x

DHW Heater Fault x x

DHW Heater Additional Point via Manufacturer x

DHW Tank Temperature x x x

IHW Heater enable x x x x x

IHW Heater Fault x x

IHW Heater Additional Point via Manufacturer x

IHW Tank Temperature x x x

Leaving Water Temperature from Tanks x x x

Leaving Water Temperature from MV x x x

Return Water Temperature x x x

Meter for Kitchen System x x x

Water Meter for Domestic Hot Water System x x x

IHW Tank Temp Setpoint x x

DHW Tank Temp Setpoint x x

Building Reheat System

Pump VFD (Points per VFD) Refer to VFD

Reheat Pumps Stop/Start x x x

Reheat Pumps Status x x x x x

Reheat Pump Runtime x

Reheat Pump Calculated kWH from CT x x

Hot Water Supply Pressure x x x x x

Hot Water Return Pressue x x x x x

Calcualted DP x x

Supply Water Temperature x x x x

Return Water Temperature x x x x

System DP Setpoint x x

Low Return Pressure x x

Low Return Pressure Setpoint x x

Glycol Hot Water Loop

Glycol Supply Temperature x x x x

Glycol Return Temperature x x x x

Control Valve x x x x

Pump Current Transducer x

Pump

Pump Stop/Start x x x x x x

Pump Calculated kWh from CT x x

Low Alarm Glycol x x x

Glycol Tank Pump Status x x x

Glycol Supply Pressure x x x x

Glycol Return Pressure x x x x

Calculated DP x x

Pressure not needed for small loops

System DP Setpoint x x

Low Return Pressure x x

Low Return Pressure Setpoint x x

Boiler Hot Water Loop

Boiler Enable x x x

Boiler Status x x x x x x

Boiler Alarm x x

Boiler Fail x x x

Supply Water Temperature (Each Boiler) x x x x

Return Water Temperature x x x x

Boiler Pump Enables x x x

Boiler Pump Current Transducer x x x

Pump Calculated kWh from CT x x

Emergency Shutdown Switch (each door) x x x x

Modulation Rate x x x x

Supply Temp Common x x x x

Runtime x x

Boiler LWT Setpoint x x x

Chilled Water System

Pump VFD (Points per VFD) Refer to VFD

CHW Pumps Enable x x x

CHW Pumps Status x x x x

CHW Supply Pressure x x x x

CHW Return Pressure x x x x

CHW Calculated DP x x

Chilled Water Supply Temp x x x x

Chilled Water Return Temp x x x x

Indirect CW Supply Temp x x x x

Indirect CW Return Temp x x x x

Indirect CW Pump Enable x x

Indirect CW Pump Current Transducer x x x x

Pump Calculated kWh from CT x x

CHW DP Setpoint x x

Chillers (Air/Water Cooled)

CH-1 Enable x

CH-1 Status x x

CH-1 Fault x x

CH-1 CHWS Supply Temp SP x x x

Condenser Pressure x x

Evap Pressure x x

Runtimes x x

VFD x x

% Load x x

Fault x

KW x x x

KWh x x x

KW/Ton x x

Cooling Towers

Indirect CW Pump Enable x x

Indirect CW Pump Current Transducer x x x x

Pump Calculated kWh from CT x x

Sump Temperature x x x

Sump High Level Alarm x x

Low Level Alarm (interlocked with pumps) x x x

Sump Heater CT x x

Sump Heater Calculated kWH from CT x x

Tower Discharge Temperature x x x x

Tower Fan Enable x x x

Tower Fan Status x x x x

Tower Fan VFD Speed Signal (Points per VFD) Refer to VFD

Make-up Water Meter x x x

Drain Water Meter x x x

ISS/Chemical Feed

Status ISS Pump x x

Pump Interlocked with CW Pump x

Interlock Blow Down Valve with Chemical x

Chemical Feed Interlocked with CW Pump x

Chemical Feed Micro-Ohms x x

Drain Water Meter x x x

Heat Exchangers

Source Entering Water Temp x x x x

Source Leaving Water Temp x x x x

Load Entering Water Temp x x x x

Load Leaving Water Temp x x x x

Load Valve x x x x

Source Valve x x x x

Fan Coil Units

Space temperature x x x x

Space Temperature SP x x x

UnOccupied Space Temperature Cooling x x

UnOccupied Space Temperature Heating x x

Standby Space Temperature Cooling x x

Standby Space Temperature Heating x x

Supply air temperature x x x x

Chilled Water Valve x x x

Hot Water Valve x x x

Fan Motor Current Sensor x x

Fan Motor Start/Stop x x x

Fan Calculated kWh from CT x x

Filter DP x

Water Sensor x x x

Occupancy x

Variable Frequency Drive

Start/Stop x x x x x

Status x x x

System Fault x x x

External Fault x x x

Speed x x x

Frequency Output x

Percent Output x x

Current x

Power (kW) x x

Drive Temperature x x

KWH x x

Runtime x

DC Bus Volts x

VAV Terminal Units

Space Temperature SP x x x

Space Temp x x x

Hot Water Valve x x x x

AHU DAT x x

Max CFM x x

Min CFM x x

Reheat CFM x x

Damper Postion x

Actual CFM x x x x

Discharge Air Temperature x x x

Occupancy x x x x

Per cent Load x

UnOccupied Space Temperature Cooling x x

UnOccupied Space Temperature Heating x x

Standby Space Temperature Cooling x x

Standby Space Temperature Heating x x

Venturi VAV Tracking Pairs Controls

Space Temperature Sensor Input x x x x x

Occupied Temperature SetPoint Input x x x x

Occupancy Override Input x x x x

Occupancy Sensor Input x x x x x

Application Mode Command Input x

Unoccupied Cooling Temperature Setpoint x x x

Unoccupied Heating Temperature Setpoint x x x

Discharge Air Temperature Input x x x x

Terminal Load Output x x

BMS HVAC Emergency Override Input x x x

Zone Total Supply Flow Output x x x

Zone Total Ehaust Flow Output x x x

Zone Volumetric Offset Feedback Output x x x

Supply Valve Flow Feedback Output x x x x

Ehaust Valve Flow Feedback Output x x x x

Reheat Valve x x x x

Calculated Positive Room Alarm x

Fume Hood Labs

Space Temperature Sensor Input x x x x x

Occupied Temperature SetPoint Input x x x x x

Unoccupied Cooling Temperature Setpoint x x

Unoccupied Heating Temperature Setpoint x x

Discharge Air Temperature Input x x x x

Terminal Load Output x x

BMS HVAC Emergency Override Input x x x

Zone Total Supply Flow Output x x x

Zone Total Ehaust Flow Output x x x

Supply Valve Flow Feedback Output x x x x

Ehaust Valve Flow Feedback Output x x x x

Reheat Valve x x x x x

Flow Alarm x x

Hood Override x

Sash Height Alarm x x x

Face Velocity x x

Sash Open Percent x x x

User Status State x x x

Bypass Time Remain x x

Effective Emergency Mode x

Emergency Mode Command x

Occupancy x x x x

BTU Metering

Gallons per Minute x x x

Entering Water Temperature x x x

Leaving Water Temperature x x x

Instantaneous BTU x x x

Cumalative BTU x x x

Exhuast Fans

Fan Start/Stop x x

Fan Current Transducer x x x

Calculated kWH from CT x x

Motorized Damper x x x

End Switch x x x

Power Meters (sub meters) kW x x x

PF x x x kWH x x x

Volt (per phase) x x x

Amperage (per phase) x x x

Power Meters (main meter) kW x x x

PF x x x kWH x x x

Volt x x x

Amperage x x x

Total Harmonic Distortion x x x

Compressor & Vacuum Pumps

Alarm x x x

Pump Status x x x

Pump Pressure x x x x

Water Meters

Building Water Meter x x x

Gas Meters

Building Meter x x x

Boiler Meter x x x

Water Heater Meters x x x

Unit Heaters/Cabinet Unit Heaters

Space Temperature

Space Temperature Setpoint

Fan Start/Stop

Fan Status by CT

Fan kWH calculated by CT

Automatic Transfer Switches

Switch Status x x x

Generator

Status x x x

Running Hours x x x

Low Fuel Level x x x

VRF Systems

Condensing Unit Status x x x

FCU Status x x x

Mode x x x x

Setpoint High x x x

Setpoint Low x x x

Mode x x x x

On/Off x x x

Setpoint Change x x x x

OA_Damper x x x x

Space Temperature x x x x