This package includes construction documents and drawings for the Biloxi Building 1 Renovation project located in Biloxi, Mississippi. The project involves selective demolition, exterior building envelope alterations, and interior renovation of areas within Building 1, including upgrades to HVAC, plumbing, electrical, telecommunication systems, chilled water systems, and modifications to fire protection systems. Limited structural, mechanical, and electrical work is also required on the underside of the 3rd floor within occupied areas of the 2nd floor. The awarded contractor will be responsible for monitoring the existing building foundation system throughout the project duration. Work will occur on unoccupied floors 3 through 5 and within crawl spaces and the attic. The solicitation number is QSE-36C10F24R50025 and is currently in the pre-solicitation stage.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDICAL GAS MOUNTING HEIGHT DETAIL
NOT TO SCALE
PIPE PENETRATION THROUGH WALL BELOW GRADE
NOT TO SCALE
(P-809) DIALYSIS BOX DETAIL
NOT TO SCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL501
DETAILS - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 161 238Revisions: Date:
PORTABLE
WATER
ANALYZER
AUTOMATIC SPRINKLER SYSTEM SECTIONAL
CONTROL VALVE AND INSPECTOR'S TEST
VALVE AND DRAIN ASSEMBLY DETAIL
FLOOR MOUNTED HANDICAPPED, WATER CLOSET DETAIL
WALL HUNG HANDICAPPED, WATER CLOSET DETAIL
MEDICAL GAS PIPING AT OUTLETS 4
5a
3 5WATER MONITORING SYSTEM DETAIL
NOT TO SCALE
5b
NOT TO SCALE
NOT TO SCALE NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL502
DETAILS - PLUMBING RENOVATE BUILDING 1
10/27/2023 SCOPRZ AARMEY 162 238Revisions: Date:
1ST FLOOR 0'-0"
2ND FLOOR 13'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
CS-2
CS-2
EXISTING FLOOR
DRAIN
EXISTING
4" VTR
EXISTING
4" VTR
EXISTING
4" VTR
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
4" VTR
4" VTR
4" VTR
CONNECT TO
EXISTING 4" VTR
EXISTING 4" VTR
CS-2
EXISTING VENT PIPING IN
ATTIC WHICH IS TO BE
REMOVED AS EXISTING
RISERS ARE REMOVED FROM
SERVICE. (TYPICAL)
REMOVE EXISTING
4" VTR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL505
OVERALL SANITARY RISER RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 163 238
KEYED NOTES:
1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE
CONNECTIONS FOR SINK LOCATED IN SIDE ACCESSORY
CONSOLE. COORDINATE ROUGH-IN REQUIREMENTS
WITH EQUIPMENT PROVIDER.
GENERAL SHEET NOTES:
1. REFER TO FLOOR PLANS FOR SIZES.
2. REFER TO PL601 FOR SYMBOLS AND NOTES.
3. REFER TO PL508, PL509, PL510, AND PL511 FOR
ENLARGED RISER DIAGRAMS.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38
ALTERNATE NO.2 FOR REQUIREMENTS OF
DEDUCT ALTERNATE OF THE DIALYSIS BOXES
INDICATED ON THIS SHEET.
Revisions: Date:
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
CS-2
CS-2
CS-2
CS-2
CS-2
CS-2
CS-2
CS-2
CS-2
CS-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
TP-2
CS-2
CS-2
CS-2
CS-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL506
OVERALL WATER RISER RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 164 238
KEYED NOTES:
1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE
CONNECTIONS FOR SINK LOCATED IN SIDE
ACCESSORY CONSOLE. COORDINATE ROUGH-
IN REQUIREMENTS WITH EQUIPMENT
PROVIDER.
2. PROVIDE P-710 HANDHELD EYEWASH STATION
WITH MIXING VALVE MOUNTED BELOW
COUNTER. COORDINATE PIPING, MOUNTING
BRACKET, UNIT LOCATION, AND MIXING VALVE
LOCATION WITH SINK AND EQUIPMENT.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO FLOOR PLANS FOR SIZES.
3. REFER TO PL508, PL509, PL510, AND PL511 FOR
ENLARGED RISER DIAGRAMS.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38
ALTERNATE NO.2 FOR REQUIREMENTS OF
DEDUCT ALTERNATE OF THE DIALYSIS BOXES
INDICATED ON THIS SHEET.
ATTIC 66'-0"
5TH FLOOR 52'-0"
4TH FLOOR 39'-0"
3RD FLOOR 26'-0"
2ND FLOOR 13'-0"
1ST FLOOR 0'-0"
EXISTING
EXISTING
EXISTING
EXISTING
VA PROVIDED,
CONTRACTOR INSTALLED
SEPARATOR TANK
EXISTING
VA PROVIDED,
CONTRACTOR INSTALLED
VACUUM PUMP
MEDICAL GAS
AREA ALARM
MEDICAL GAS
AREA ALARM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL507
OVERALL MED GAS RISER RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 165 238
GENERAL NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO FLOOR PLANS FOR SIZES NOT SHOWN.
3. REFER TO FLOOR PLANS PL301, PL302, AND PL307 FOR SYSTEM CONNECTIONS.
4. PROVIDE MEDICAL GAS RISER DIAGRAM IN SHOP DRAWING SUBMITTAL FOR REVIEW. VERIFY ROUTING IN FIELD PRIOR TO SUBMITTING DRAWINGS.
WCO
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
TO EXISTING VTR
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
TP-2
TP-2
CS-2
WCO
WCO
WCO
WCO
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
FD-M
FD-M
2" VTR
TP-2
TP-2
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR
39'-0"
5TH FLOOR 52'-0"
TP-2
TP-2
TP-2
TP-2
WCO
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3/4" HW DRAIN LINES WITH
SOLENOID VALVE THEN MANUAL
SHUT-OFF VALVE EXTENDED TO
FLOOR SINK (OR MOP SINK) TO
"HEAT AND FLUSH" DOMESTIC HOT
WATER LINE.
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3/4" HW DRAIN LINES WITH
SOLENOID VALVE THEN MANUAL
SHUT-OFF VALVE EXTENDED TO
FLOOR SINK (OR MOP SINK) TO
"HEAT AND FLUSH" DOMESTIC
HOT WATER LINE.
TP-2
TP-2
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
BFP
BFP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL508
PLUMBING RISERS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 166 238
SIMILAR RISERS:
P/3, P/4, P/7, P/8, P/9
SIMILAR RISERS:
P/3, P/4, P/7, P/8, P/9
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38 ALTERNATE
NO.2 FOR REQUIREMENTS OF DEDUCT ALTERNATE
OF THE DIALYSIS BOXES INDICATED ON THIS SHEET.
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
WCO
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3/4" HW DRAIN LINES WITH SOLENOID
VALVE THEN MANUAL SHUT-OFF VALVE
EXTENDED TO FLOOR SINK (OR MOP
SINK) TO "HEAT AND FLUSH" DOMESTIC
HOT WATER LINE.
WCO
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL509
PLUMBING RISERS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 167 238
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38 ALTERNATE
NO.2 FOR REQUIREMENTS OF DEDUCT ALTERNATE
OF THE DIALYSIS BOXES INDICATED ON THIS SHEET.
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
FLOOR 3 26'-0"
FLOOR 4 39'-0"
FLOOR 5 52'-0"
WCO
2ND FLOOR 13'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
2ND FLOOR 13'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL510
PLUMBING RISERS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 168 238
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
CS-2
TP-2
TP-2
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
6TH FLOOR 66'-0"
3/4" HW DRAIN LINES WITH SOLENOID
VALVE THEN MANUAL SHUT-OFF VALVE
EXTENDED TO FLOOR SINK (OR MOP
SINK) TO "HEAT AND FLUSH" DOMESTIC
HOT WATER LINE.
CS-2
TP-2
TP-2
FILTER
BFP
2ND FLOOR 13'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
CS-2
CS-2
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
CS-2
CS-2
3RD FLOOR 26'-0"
PATIENT ROOMS
3&4, 5&6, 8&9 10&11
ARE SIMILAR
3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
CS-2
CS-2
CS-2
CS-2
PATIENT ROOMS
3&4, 5&6, 8&9, 10 &11
ARE SIMILAR 3RD FLOOR 26'-0"
4TH FLOOR 39'-0"
5TH FLOOR 52'-0"
CS-2
CS-2
CS-2
CS-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL511
PLUMBING RISERS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 169 238
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS SPECIFICATION
SECTION 01 00 00.1.38 ALTERNATE NO.2 FOR
REQUIREMENTS OF DEDUCT ALTERNATE OF THE
DIALYSIS BOXES INDICATED ON THIS SHEET.
PACKAGE BOOSTER PUMP SCHEDULE
MARK LOCATION AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
TYPE
CIRCULATING FLUID
PRESSURE
TRANSMITTER
SETPOINT
OUTLET BUFFER
TANK ACCEPTANCE
VOLUME
(MINIMUM)
ELECTRICAL MOTOR
FLUID NO
PUMPS
FLOW EA. PUMP HEAD EA. PUMP MIN
NPSH
AVAIL
TEMPERATURE
SP GR % EFF
NOMINAL POWER,
EA. PHASE VOLT MAX RPM SPEED
CONTROL REMARKS
GPM [L/s] FT [M] °F [°C] PSIG [kPa] GAL [L] HP [kW]
1-BP1
BLDG 1
BASEMENT
MECH ROOM BC
HOSPITAL
PRESSURE
FLOORS 3, 4,
AND 5
DOMESTIC
BOOSTER PUMP
VERTICAL
MULTISTAGE
DOMESTIC COLD
WATER 3 75 [ 5 ] 173.3 [ 52 ] N/A 50 [ 10 ] 1 68 75 [ 520 ] 30 [ 110 ] 3.0 [ 2 ] 3 208 3600 VARIABLE -----
NOTES:
1. UNIT INCOMING PRESSURE 50PSI, OUTLET PRESSURE TO BE 75 PSI. REFER TO SPECIFICATIONS FOR OPERATION.
2. PROVIDE UNIT WITH CAPABILITY TO INTERFACE WITH BAS. REFER TO DRAWINGS AND SPECIFICATIONS FOR MORE INFORMATION.
3. SYSTEM CONTROLLER SHALL ALTERNATE PUMPS TO EQUAL RUNTIME ON THE PUMPS. REFER TO SPECIFICATIONS FOR MORE INFORMATION.
4. PROVIDE SEPARATE PRESSURE SWITCHES FOR THE HIGH PRESSURE CUT OFF AND NOT FLOW CUT OFF SAFETIES. EACH DEVICE SHALL BE WIRED SEPARATELY TO THE BOOSTER PUMP CONTROL. THE USE OF A SINGLE DEVICE FOR VFD/SYSTEM PRESSURE CONTROL
AND MULTIPLE SAFETIES IS NOT ACCEPTABLE.
5. BASIS OF DESIGN UNIT ARMSTRONG DESIGN ENVELOPE 6800 BOOSTER SYSTEM MODEL N290102-3. CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES REQUIRED DUE TO DIFFERENCES FROM BASIS OF DESIGN MODEL INCLUDING COORDINATION WITH ELECTRICAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL601
SCHEDULES - PLUMBING RENOVATE BUILDING 1
10/27/2023 SCOPRZ AARMEY 170 238Revisions: Date:
PROVIDE TWO 6" LOW PRESSURE DROP RPZ STYLE BACK FLOW
PREVENTORS ARRANGED IN PARALLEL CONFIGURATION ON 8" WATER LINE
SERVING BUILDING 1. UNITS SHALL BE INSTALLED ABOVE GRADE WITH
PIPING CONNECTION TO EXISTING MAINS LOCATED BELOW GRADE.
CONTRACTOR SHALL FIELD VERIFY EXISTING PIPING LOCATIONS PRIOR TO
EXCAVATING. CONTRACTOR SHALL COORDINATE TIE IN LOCATIONS AND
NEW BACKFLOW PREVENTOR LOCATION WITH THE RESIDENT ENGINEER.
CONNECT TO EXISTING 4" CW MAIN. ROUTE NEW 4" CW LINE THROUGH
BASEMENT WINDOW BOX AT BUILDING 53. CONTRACTOR SHALL VERIFY
EXISTING PIPE MATERIAL AT TIE-IN LOCATIONS. CONTRACTOR SHALL FIELD
VERIFY EXISTING PIPING LOCATIONS PRIOR TO EXCAVATING.
CONTRACTOR SHALL COORDINATE TIE IN LOCATION WITH THE RESIDENT
ENGINEER.
8" CW
8" CW
PRIMARY PUMP LOCATION
IN ROOM BC 109
ALTERNATE PUMP
LOCATION IN ROOM BC 109
APPROXIMATE LOCATION
OF ROOM BC 109
PROVIDE DOMESTIC WATER
BOOSTER PUMP SYSTEM IN
BASEMENT ROOM BC 109.
UNIT SHALL BE NO LARGER
THAN 72"W X 88" H X 60"D.
4" CW
CONTRACTOR TO TIE INTO VA FURNISHED 4"
COPPER PIPING WITH BACKFLOW PREVENTOR
IN MECHANICAL SPACE BELOW BUILDING 53.
REFER TO PL101 FOR MORE INFORMATION.
EXISTING 4" WATER
MAIN FOR BUILDING 53
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PS101
SITE PLAN - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 136 238
KEYED NOTES:
1. CONNECT TO EXISTING LIFT STATION.
2. REFER TO PL101 FOR CONTINUATION.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTORS SHALL REVIEW ROUTING OF PIPING
PRIOR TO BID. ROUTING SHOWN IS ONE POTENTIAL ROUTE
WITH FINAL ROUTE UP TO INSTALLING CONTRACTOR TO
DETERMINE.
3. CONTRACTORS SHALL COORDINATE ROUTING OF PIPING
WITH EXISTING CONDITIONS.
File details come from the government source that posted it. Updated .