This pre-solicitation notice and draft solicitation are for the Biloxi Building 1 Renovation project in Biloxi, Mississippi. The contractor will provide all labor, materials, equipment, supervision, and transportation necessary to complete selective demolition, exterior building envelope alterations, and interior renovations of areas within Building 1. Work includes upgrades to HVAC, plumbing, electrical, telecommunications, chilled water systems, and modifications to fire protection. Limited structural, mechanical, and electrical work will occur on occupied areas of the second floor. The contractor will also monitor the existing building foundation system throughout the project duration using a qualified consultant. The solicitation number is QSE--36C10F24R50025 and the project name is Biloxi Building 1 Renovation - Biloxi, MS -- Y1DA. The agency is the Department of Veterans Affairs Office of Construction and Facilities Management.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
EXISTING 1-1/4"
OXYGEN RISER UP
WITH SHUT-OFF
VALVE IN RISER.
EXISTING 1/2" OXYGEN UP
TO ZONE VALVE ABOVE.
NEW 1-1/4" O, RISER UP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL301
EXISTING CRAWL SPACE -MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 150 238
KEYED NOTES:
1. CONNECT TO EXISTING 2" OXYGEN PIPING.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTORS SHALL REVIEW ROUTING OF PIPING
PRIOR TO BID. ROUTING SHOWN IS ONE POTENTIAL
ROUTE WITH FINAL ROUTE UP TO INSTALLING
CONTRACTOR TO DETERMINE.
3. CONTRACTORS SHALL COORDINATE ROUTING OF PIPING
WITH EXISTING CONDITIONS.
4. REMOVE ALL EXISTING DENTAL VACUUM PIPING
SERVING THE FIRST FLOOR AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED.
Revisions: Date:
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
EXISTING 1 1/4"O UP & DN
EXISTING 1 1/4" MA & 1 1/2" MV
UP
PROVIDE SHUT-OFF
VALVES.
UPUP & DN
UP
2" MV CAPPED
FOR FUTURE USE
EXISTING O, MA, MV UP
TO 2ND FLOOR
BIOMEDICAL DEPT.
EXISTING SHUT-OFF VALVES
FOR SERVICES TO 2ND FLOOR
BIOMEDICAL DEPT. EXISTING 0, MA, & MV SERVICES
TO EAST WING
1" O, 1" MA
REMOVE EXISTING DENTAL AIR RISER FROM THE
FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL302
EXISTING 1ST FLOOR - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 151 238
KEYED NOTES:
1. CONNECT TO EXISTING 3/4" O & 3/4" MA
PIPING DOWNSTREAM OF EXISTING SHUT-OFF
VALVES. CAP EXISTING O & MA AT SHUT-OFF VALVES.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO PL501 AND PL502 FOR DETAILS.
3. REFER TO PL507 FOR RISER DIAGRAMS.
4. REMOVE ALL EXISTING DENTAL AIR AND DENTAL
VACUUM PIPING ON THE FIRST FLOOR AFTER THE
NEW DENTAL LAB HAS BEEN COMPLETED.
5. REFER TO DRAWING AE102 FOR INFORMATION
REGARDING PHASING OF WORK ON THE SECOND
FLOOR.
1 2 3 4 5 6 7 8 9
11 12
14 15 16 17 18 19 20 21 22
G
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
PROVIDE SHUT-OFF
VALVES AND CAP
FOR FUTURE USE.
TURN UP/DN..
1"O, 1" MA, 2" MV
CAPPED.
REMOVE EXISTING DENTAL AIR RISER FROM
THE FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL303
EXISTING 2ND FLOOR - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 152 238
KEYED NOTES:
1. EXISTING 1 1/4" OXYGEN PIPING SHALL CONTINUE TO SERVE
THE 1ST & 2ND FLOORS. CAP RISER BELOW 3RD FLOOR & PROVIDE
WITH A SHUT-OFF VALVE.
2. CONNECT TO EXISTING 1 1/2" MA & 1 1/2" MV.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO PL501 AND PL502 FOR DETAILS.
3. REFER TO PL507 FOR RISER DIAGRAMS.
4. REFER TO DRAWING AE102 FOR INFORMATION REGARDING
PHASING OF WORK ON THE SECOND FLOOR.
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
FEC
FEC FEC
ZONE VALVE
MEDICAL GAS
AREA ALARM
PROVIDE
SHUT-OFF VALVES.
ZONE
VALVE
TURN UP/DN..
NEW MA & MV
UP/DN..
SHUT-OFF
VALVES
SHUT-OFF
VALVES
SHUT-OFF
VALVES
1 1/4" O, 1 1/2" MA,
2" MV
REMOVE EXISTING DENTAL AIR RISER FROM
THE FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL304
3RD FLOOR - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 153 238
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO PL501 AND PL502 FOR DETAILS.
3. REFER TO PL507 FOR RISER DIAGRAMS.
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
ZONE VALVE
ZONE
VALVE
1 1/2" LA & 1 1/2" DA
UP TO 5TH FLOOR
PROVIDE
SHUT-OFF VALVES.
DENTAL AIR
TURN UP/DN..
NEW MA & MV
UP/DN..
LA
SHUT-OFF VALVE IN
VERTICAL. ( TYP.)
SHUT-OFF
VALVES
1 1/4"O, 1 1/2"
MA, 2"MV
UP TO
WCO
UP TO
WCO
1 1/2" DV UP TO WCO
1 1/2" DV UP TO WCO
2" DV UP
REMOVE EXISTING DENTAL AIR RISER FROM
THE FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
2" DV FROM
DENTAL INTO TANK
2" DV FROM
PUMP INTO TANK
MEDICAL GAS
AREA ALARM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL305
4TH FLOOR - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 154 238
KEYED NOTES:
1. 1/2" DA UP TO DENTAL CHAIR FLOOR BOX.
2. 1/2" LA UP TO DENTAL LAB. COORDINATE
EXACT LOCATION WITH DENTAL LAB
EQUIPMENT LAYOUT, STRUCTURE, AND
RESIDENT ENGINEER.
3. 1-1/2" DV UP TO DENTAL CHAIR FLOOR BOX.
4. 1/2" DA UP TO SIDE ACCESSORY CONSOLE.
5. 1" LA PIPING UP TO DENTAL LAB.
COORDINATE EXACT LOCATION WITH DENTAL
LAB EQUIPMENT LAYOUT, STRUCTURE, AND
RESIDENT ENGINEER.
6. CONTRACTOR TO INSTALL VA PROVIDED
SEPARATOR TANK. CONTRACTOR SHALL
PROVIDE ALL NECESSARY COMPONENTS FOR
COMPLETE INSTALLATION. COORDINATE
REQUIREMENTS WITH VA.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND
NOTES.
2. REFER TO PL501 AND PL502 FOR DETAILS.
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
ZONE VALVE
1 1/2" LA & 1 1/2" DA
DOWN TO 4TH FLOOR
PROVIDE SHUT-OFF
VALVES.
NEW MA & MV
DN..
NEW MA & MV
UP.
LA
1 1/4" O DN, 1 1/2"MA, 2"
MV UP/DN
UP
UP
UP & DN
WCO
WCO
WCO
WCO
REMOVE EXISTING DENTAL AIR RISER FROM
THE FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
LOCATE Y-SPLIT OUTLET
AT THESE STATIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL306
5TH FLOOR - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 155 238
KEYED NOTES:
1. CAP 2" MV & 1 1/2" MA FOR FUTURE USE.
2. 1/2" LA PIPING DOWN TO 4TH FLOOR.
COORDINATE EXACT FLOOR PENETRATION
LOCATION, PIPING TERMINATION, AND OUTLET
TYPE, LOCATION, AND ELEVATION WITH DENTAL
LAB EQUIPMENT/FURNITURE, STRUCTURE, AND
RESIDENT ENGINEER.
3. 1" LA PIPING DOWN TO 4TH FLOOR.
COORDINATE EXACT ROUTE OF LA PIPING WITH
VACUUM TUBING SYSTEM LOCATED WITHIN
ISLAND CABINETRY.COORDINATE EXACT FLOOR
PENETRATION LOCATION, PIPING TERMINATION,
AND OUTLET TYPE, LOCATION, AND ELEVATION
WITH DENTAL LAB EQUIPMENT/FURNITURE AND
VENDOR (LOC), STRUCTURE, AND RESIDENT
ENGINEER.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. REFER TO PL501 AND PL502 FOR DETAILS.
F
E
D
C
B
A
7.4
F.8
F.3
B.4
B.7
D.8
D.2
B.8
B.2
10.8 12.2
5.1
EXISTING 1-1/2" MEDICAL AIR
EXISTING 2" MEDICAL VACUUM
NEW 1-1/2" DENTAL AIR
NEW 1 1/2"MA, 2"MV, 1 1/2" LA,
& 1 1/2" DA DOWN TO 5TH FLOOR
NEW MA & MV
DN..
NEW 1-1/2" LABORATORY AIR
DN
2" DV EXHAUST TO OUTSIDE WEATHER
CAP. COORDINATE INSTALLATION WITH
MECHANICAL CONTRACTOR. EXHAUST
OUTLET TO BE 25 FEET MINIMUM FROM
HVAC INTAKES.
INSTALL VA PROVIDED PUMP. CONTRACTOR
SHALL PROVIDE ALL NECESSARY
COMPONENTS FOR COMPLETE INSTALLATION.
COORDINATE REQUIREMENTS WITH VA AND
ELECTRICAL.
REMOVE EXISTING DENTAL AIR RISER FROM
THE FIRST FLOOR BACK TO THE DENTAL AIR
COMPRESSORS AFTER THE NEW DENTAL LAB
HAS BEEN COMPLETED AND IS OPERATIONAL.
VERIFY WITH VA PRIOR TO REMOVAL.
REVISE EXISTING PIPING ROUTE FOR NEW
MECHANICAL AND DUCT INSTALLATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL307
ATTIC - MED GAS RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 156 238
KEYED NOTES:
1. 1 1/2" LA CONNECTION TO EXISTING DENTAL
AIR COMPRESSOR. PROVIDE PRESSURE REDUCING VALVE
SET AT 50 PSI.
2. 1 1/2" DA CONNECTION TO EXISTING DENTAL AIR
COMPRESSOR. PROVIDE PRESSURE REDUCING VALVE SET
AT 140 PSI.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
12 13
B
A
B.4
B.2
12.2
UP & DN
4" SAN UP
& DN
4"
VENT
UP
2" CW UP
1 1/2" CW
UP
UP
UP
UP
UP
UP & DN
16 17
D
D.2
4" SAN
UP & DN
3" VENT
UP
UP
UP
UP
UP
UP
UP
UP
12 13
B.4
B.2
12.2
4" SAN
DN
UP1" CW,
1/2" HW,
1/2" HWR
DN
UP
3 4
D
C
D.2
WCO
4" SV UP
4" SS DN
F
E
D.8
1 1/2" CW DN
1" HW DN
1" CW DN
1/2" HWR DN
DN
4" SV
UP
UP & DN
19 20 21 22
C
B
B.4
B.7
B.8
B.2
4" SAN
DN
2" SAN
DN
2" SS DN
WCO
4" SAN
DN
2" CW DN
1 1/2"HW DN
UP
UP
1 1/2"HWR DN
MULTIPLE
TRAP PRIMER
DN
4" SV UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL401
ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 157 238
KEYED NOTE
1. 1/2" CW BELOW SLAB TO TRAP.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
10 11 12 13
F
F.8
F.3
10.8 12.2
DN
UP
DN
3" SS
3" SS DN
2" SV UP
WCO
2" SV
4" SS
DN
2" CW DN
1 1/2" HW DN
1 1/2" HWR DN
1" CW UP TO
HOSE BIBBS IN
ATTIC.
UP
MULTIPLE
TRAP PRIMER
UP
3" SS UP TO EXISTING
FLOOR DRAIN
2 3 4
C
B
B.4
B.7
B.8
B.2
4" VENT
UP
UP & DN
WCO
UP
UP
UP
UP
UP
SERVICES TO
PATIENT
ROOM SINK
CS-2
UP
UP
TP-2
UP
UP
G
F
E
F.8
F.3
D.8
4" SAN
UP & DN
4" VENT
UPUP
UP
UPUP
UP
UP
UP
UP & DN
TP-2
TP-2
BFP
1/2" HWR UP
1/2" HW UP
1/2" CW UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL402
ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 158 238
KEYED NOTE
1. 1/2" CW BELOW SLAB TO TRAP
2. PROVIDE 3/4" DRAIN WITH SOLENOID VALVE THEN
MANUAL SHUT-OFF VALVE EXTENDED TO FLOOR SINK (OR
MOP SINK) TO "HEAT AND FLUSH" DOMESTIC HOT WATER
LINE. SOLENOID VALVE TO BE WIRED TO BAS FOR REMOTE
OPERATION AND MONITORING. COORDINATE VALVE
SELECTION AND LOCATION WITH OWNER AND
TEMPERATURE CONTROL CONTRACTOR.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38
ALTERNATE NO.2 FOR REQUIREMENTS OF
DEDUCT ALTERNATE OF THE DIALYSIS
BOXES INDICATED ON THIS SHEET.
1 2 3 4 5 6
F
E
F.8
F.3
D.8
4" SV UP
4" SAN
UP & DN
4" SV UP
4" SAN
UP & DN
4" SAN
UP &
DN
4" SAN
UP & DN
1/2" HWR
UP
WC
UP
UP UP
UP
WCO
UP
UP UP & DN
UP
UP
DN
UPUP
UP
UP & DN
CS-2
CS-2
CS-2
CS-2
UPUP
UP
TP-2
TP-2
TP-2
DNTP-2
1/2" HW
UP
1/2" CW
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL403
ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 159 238
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38
ALTERNATE NO.2 FOR REQUIREMENTS OF
DEDUCT ALTERNATE OF THE DIALYSIS
BOXES INDICATED ON THIS SHEET.
19 20 21
C
B
B.4
B.7
B.8
B.2
UP
DN
UP & DN
DN
UP
DN
UP
UP
CS-2
TP-2
UP
UP
UP
UP
UP
UP
UP
1 2 3 4
C
B
B.4
B.7
B.8
B.2
DN
BAL V
4" SS DN
4 5
F
F.8
F.3
WCO
87.4
F.8
F.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
BID DOCUMENTS
520-317X
Dwg. of
PL404
ENLARGED PLANS - PLUMBING RENOVATE BUILDING 1
BILOXI, MISSISSIPPI
10/27/2023 SCOPRZ AARMEY 160 238
KEYED NOTES:
1. PROVIDE 1/2" CW, 1/2" HW, AND 1 1/2" WASTE
CONNECTIONS FOR SINK LOCATED IN SIDE ACCESSORY
CONSOLE. COORDINATE ROUGH-IN REQUIREMENTS
WITH EQUIPMENT PROVIDER.
2. PROVIDE P-710 HANDHELD EYEWASH STATION WITH
MIXING VALVE MOUNTED BELOW COUNTER.
COORDINATE PIPING, MOUNTING BRACKET, UNIT
LOCATION, AND MIXING VALVE LOCATION WITH SINK
AND EQUIPMENT.
GENERAL SHEET NOTES:
1. REFER TO PL601 FOR SYMBOLS AND NOTES.
2. CONTRACTOR SHALL SET ALL BALANCE VALVES TO
0.5GPM UNLESS NOTED OTHERWISE.
DEDUCT ALTERNATE:
1. REFER TO GENERAL REQUIREMENTS
SPECIFICATION SECTION 01 00 00.1.38
ALTERNATE NO.2 FOR REQUIREMENTS OF
DEDUCT ALTERNATE OF THE DIALYSIS BOXES
INDICATED ON THIS SHEET.