This solicitation seeks proposals for construction of a new parking structure at the Wilkes-Barre VA Medical Center campus in Pennsylvania. The project includes providing all labor, materials, tools, equipment, permits, testing and reports to construct a new parking garage to accommodate approximately 435 vehicles according to the drawings and specifications provided. The magnitude of the project is estimated between $10 million to $20 million. This procurement is set aside for Service-Disabled Veteran-Owned Small Businesses and will use a tiered evaluation process including large businesses. Offerors shall price proposals in whole U.S. dollars and the Government reserves the right to cancel the solicitation before award. The selected contractor will be responsible for correct worker classification and wage compliance.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania
078410 - 1
SECTION 078410 THROUGH-PENETRATION FIRESTOP SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes through-penetration firestop systems for penetrations of duct, cable, cable tray, conduit, piping, electrical busways and raceways through the following fire-resistance-rated assemblies, including both empty openings and openings containing penetrating items:
1. Floors.
2. Roofs.
3. Walls and partitions.
4. Openings between structurally separate sections of wall or floors.
5. Gaps between the top of walls and ceilings or roof assemblies.
6. Expansion joints in walls and floors.
7. Openings and penetrations in fire-rated partitions or walls containing fire doors.
8. Openings around structural members which penetrate floors or walls.
B. Related Sections include the following:
1. Division 3 Section "Cast-in-Place Concrete" for construction of openings in concrete slabs and walls.
2. Division 14 Section “Hydraulic Elevator”
3. Division 25 Sections specifying duct and piping penetrations.
4. Division 26 Sections specifying cable and conduit penetrations.
1.3 DEFINITIONS
A. Firestopping: Material or combination of materials used to retain integrity of fire-rated construction by maintaining an effective barrier against the spread of flame, smoke, water and hot gases through penetrations in fire rated wall and floor assemblies.
1.4 PERFORMANCE REQUIREMENTS
A. General: For the following constructions, provide through-penetration firestop systems that are produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of assembly penetrated.
078410 - 2
1. Fire-resistance-rated non-load-bearing walls, including partitions, with fire-protection-rated openings.
2. Fire-resistance-rated floor assemblies.
B. F-Rated Systems: Provide through-penetration firestop systems with F-ratings indicated, as determined per ASTM E 814, but not less than that equaling or exceeding fire-resistance rating of constructions penetrated.
C. For through-penetration firestop systems exposed to view, traffic, moisture, and physical damage, provide products that after curing do not deteriorate when exposed to these conditions both during and after construction.
1. For piping penetrations for plumbing, provide moisture-resistant through-penetration firestop systems.
2. For floor penetrations with annular spaces exceeding 4 inches (100 mm) in width and exposed to possible loading and traffic, provide firestop systems capable of supporting floor loads involved either by installing floor plates or by other means.
3. For penetrations involving insulated piping, provide through-penetration firestop systems not requiring removal of insulation.
D. For through-penetration firestop systems exposed to view, provide products with flame-spread ratings of less than 25 and smoke-developed ratings of less than 450, as determined per ASTM E 84.
1.5 SUBMITTALS
A. Product Data: Manufacturer’s specifications and technical data fro each material including the composition and limitations, documentation of UL firestop systems to be used and manufacturer’s installation instructions to comply with Division 1 Section “Submittals”.
B. Shop Drawings: For each through-penetration firestop system, show each kind of construction condition penetrated, relationships to adjoining construction, and kind of penetrating item. Include firestop design designation of testing and inspecting agency acceptable to authorities having jurisdiction that evidences compliance with requirements for each condition indicated.
1. Submit documentation, including illustrations, from a qualified testing and inspecting agency that is applicable to each through-penetration firestop system configuration for construction and penetrating items.
C. Qualification Data: For firms and persons specified in "Quality Assurance" Article to demonstrate their capabilities and experience. Include lists of completed projects with project names and addresses, names and addresses of architects and owners, and other information specified.
D. Product Certificates: Signed by manufacturers of through-penetration firestop system products certifying that products furnished comply with requirements.
078410 - 3
E. Product Test Reports: From a qualified testing agency indicating through-penetration firestop system complies with requirements, based on comprehensive testing of current products.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: An experienced installer who has completed through-penetration firestop systems similar in material, design, and extent to that indicated for this Project and whose work has resulted in construction with a record of successful in-service performance.
1. A manufacturer’s representative shall be on-site during initial installation of firestop systems to train appropriate contractor personnel in proper selection and installation procedures. Training shall be performed to comply with manufacturer’s published recommendations.
B. Source Limitations: Obtain through-penetration firestop systems, for each kind of penetration and construction condition indicated, from a single manufacturer.
C. Fire-Test-Response Characteristics: Provide through-penetration firestop systems that comply with the following requirements and those specified in "Performance Requirements" Article:
1. Firestopping tests are performed by a qualified testing and inspecting agency.
A qualified testing and inspecting agency is UL, or another agency performing testing and follow-up inspection services for firestop systems acceptable to authorities having jurisdiction.
2. Through-penetration firestop systems are identical to those tested per ASTM E 814. Provide rated systems complying with the following requirements:
a. Through-penetration firestop system products bear classification marking of qualified testing and inspecting agency.
b. Through-penetration firestop systems correspond to those indicated by reference to through-penetration firestop system designations listed by the following:
1) UL in "Fire Resistance Directory."
D. Preinstallation Conference: Conduct conference at Project site to comply with requirements in Division 1 Section "Project Meetings."
1.7 DELIVERY, STORAGE, AND HANDLING
A. Deliver through-penetration firestop system products to Project site in original, unopened containers or packages with intact and legible manufacturers' labels identifying product and manufacturer; date of manufacture; lot number; shelf life, if applicable; qualified testing and inspecting agency's classification marking applicable to Project; curing time; and mixing instructions for multicomponent materials.
078410 - 4
B. Store and handle materials for through-penetration firestop systems to prevent their deterioration or damage due to moisture, temperature changes, contaminants, or other causes.
1.8 PROJECT CONDITIONS
A. Environmental Limitations: Do not install through-penetration firestop systems when ambient or substrate temperatures are outside limits permitted by through-penetration firestop system manufacturers or when substrates are wet due to rain, frost, condensation, or other causes.
B. Ventilate through-penetration firestop systems per manufacturer's written instructions by natural means or, where this is inadequate, forced-air circulation.
PART 2 - PRODUCTS
2.1 PRODUCTS AND MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering through-penetration fire stop systems that may be included in the work include, but are not limited to the following:
1. Specified Technologies, Inc., Somerville, NJ.
2. 3M Fire Protection Products, St. Paul, MN.
3. Tremco Sealants & Coatings, Beechwood, OH.
4. Nelson Firestop Products, Tulsa, OK.
B. Available Products: Subject to compliance with requirements, through-penetration firestop systems that may be incorporated into the Work include, but are not limited to, those systems indicated in the Through-Penetration Firestop System Schedule at the end of Part 3.
C. Use only firestop products that have been tested in accordance with ASTM E 814 (UL 1479), ASTM E-119 (UL 263), ASTM E 84 (UL 723), and UL 2079.
2.2 FIRESTOPPING, GENERAL
A. Compatibility: Provide through-penetration firestop systems that are compatible with one another, with the substrates forming openings, and with the items, if any, penetrating through-penetration firestop systems, under conditions of service and application, as demonstrated by through-penetration firestop system manufacturer based on testing and field experience.
B. Accessories: Provide components for each through-penetration firestop system that are needed to install fill materials and to comply with "Performance Requirements" Article. Use only components specified by through-penetration firestop system manufacturer and approved by the qualified testing and inspecting agency for firestop systems indicated. Accessories include, but are not limited to, the following items:
1. Permanent forming/damming/backing materials, including the following:
078410 - 5
a. Slag-/rock-wool-fiber or fiberglass insulation.
b. Sealants used in combination with other forming/damming/backing materials to prevent leakage of fill materials in liquid state.
c. Fillers for sealants.
2. Temporary forming materials.
3. Substrate primers.
2.3 FILL MATERIALS
A. General: Provide through-penetration firestop systems containing the types of fill materials indicated in the Through-Penetration Firestop System Schedule at the end of Part 3 by reference to the types of materials described in this Article. Fill materials are those referred to in directories of the referenced testing and inspecting agencies as fill, void, or cavity materials.
B. Latex Sealants: Single-component latex formulations that after cure do not re-emulsify during exposure to moisture.
C. Intumescent Putties: Nonhardening dielectric, water-resistant putties containing no solvents, inorganic fibers, or silicone compounds.
D. Intumescent Wrap Strips: Single-component intumescent elastomeric sheets with aluminum foil on one side.
E. Mortars: Prepackaged, dry mixes consisting of a blend of inorganic binders, hydraulic cement, fillers, and lightweight aggregate formulated for mixing with water at Project site to form a nonshrinking, homogeneous mortar.
F. Pillows/Bags: Reusable, heat-expanding pillows/bags consisting of glass-fiber cloth cases filled with a combination of mineral-fiber, water-insoluble expansion agents and fire-retardant additives.
G. Silicone Foams: Multicomponent, silicone-based liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam.
H. Silicone Sealants: Moisture-curing, single-component, silicone-based, neutral-curing elastomeric sealants of grade indicated below:
1. Grade: Pourable (self-leveling) formulation for openings in floors and other horizontal surfaces and nonsag formulation for openings in vertical and other surfaces requiring a nonslumping, gunnable sealant, unless indicated firestop system limits use to nonsag grade for both opening conditions.
2.4 MIXING
A. For those products requiring mixing before application, comply with through-penetration firestop system manufacturer's written instructions for accurate proportioning of materials, water (if required), type of mixing equipment, selection of mixer speeds, mixing containers, mixing time, and other items or procedures needed
078410 - 6 to produce products of uniform quality with optimum performance characteristics for application indicated.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with requirements for opening configurations, penetrating items, substrates, and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Verification of Conditions: Verify penetrations are properly sized and in suitable condition for application of materials.
B. Surface Cleaning: Clean out openings immediately before installing through-penetration firestop systems to comply with written recommendations of firestop system manufacturer and the following requirements:
1. Remove from surfaces of opening substrates and from penetrating items foreign materials that could interfere with adhesion of through-penetration firestop systems.
2. Clean opening substrates and penetrating items to produce clean, sound surfaces capable of developing optimum bond with through-penetration firestop systems. Remove loose particles remaining from cleaning operation.
C. Priming: Prime substrates where recommended in writing by through-penetration firestop system manufacturer using that manufacturer's recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces.
D. Masking Tape: Use masking tape to prevent through-penetration firestop systems from contacting adjoining surfaces that will remain exposed on completion of Work and that would otherwise be permanently stained or damaged by such contact or by cleaning methods used to remove smears from firestop system materials. Remove tape as soon as possible without disturbing firestop system's seal with substrates.
3.3 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLATION
A. General: Install through-penetration firestop systems to comply with "Performance Requirements" Article and firestop system manufacturer's written installation instructions and published drawings for products and applications indicated.
B. Install forming/damming/backing materials and other accessories of types required to support fill materials during their application and in the position needed to produce cross-sectional shapes and depths required to achieve fire ratings indicated.
078410 - 7
1. After installing fill materials, remove combustible forming materials and other accessories not indicated as permanent components of firestop systems.
C. Install fill materials for firestop systems by proven techniques to produce the following results:
1. Fill voids and cavities formed by openings, forming materials, accessories, and penetrating items as required to achieve fire-resistance ratings indicated.
2. Apply materials so they contact and adhere to substrates formed by openings and penetrating items.
3. For fill materials that will remain exposed after completing Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes.
3.4 IDENTIFICATION
A. Identify through-penetration firestop systems with pressure-sensitive, self-adhesive, preprinted vinyl labels. Attach labels permanently to surfaces of penetrated construction on both sides of each firestop system installation where labels will be visible to anyone seeking to remove penetrating items or firestop systems. Include the following information on labels:
1. The words: "Warning--Through-Penetration Firestop System--Do Not Disturb.
Notify Building Management of Any Damage."
2. Contractor's name, address, and phone number.
3. Through-penetration firestop system designation of applicable testing and inspecting agency.
4. Date of installation.
5. Through-penetration firestop system manufacturer's name.
6. Installer's name.
3.5 CLEANING AND PROTECTION
A. Clean off excess fill materials adjacent to openings as Work progresses by methods and with cleaning materials that are approved in writing by through-penetration firestop system manufacturers and that do not damage materials in which openings occur.
B. Provide final protection and maintain conditions during and after installation that ensure through-penetration firestop systems are without damage or deterioration at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated through-penetration firestop systems immediately and install new materials to produce through-penetration firestop systems complying with specified requirements.
3.6 THROUGH-PENETRATION FIRESTOP SYSTEM SCHEDULE
A. Where UL-classified systems are indicated, they refer to the alpha-alpha-numeric designations listed in UL's "Fire Resistance Directory" under product Category XHEZ.
B. Firestop Systems with No Penetrating Items FS-1: Comply with the following:
078410 - 8
1. Available UL-Classified Systems: W-J-0003
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Silicone sealant.
c. Intumescent putty.
d. Mortar.
C. Firestop Systems for Metallic Pipes, Conduit, or Tubing FS-2: Comply with the following:
1. Available UL-Classified Systems: W-J1025.
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Silicone sealant.
c. Intumescent putty.
d. Mortar.
D. Firestop Systems for Nonmetallic Pipe, Conduit, or Tubing FS-3: Comply with the following:
1. Available UL-Classified Systems: W-J2013.
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Silicone sealant.
c. Intumescent putty.
d. Intumescent wrap strips.
e. Firestop device.
E. Firestop Systems for Electrical Cables FS-4: Comply with the following:
1. Available UL-Classified Systems: W-J-3017.
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Silicone sealant.
c. Intumescent putty.
d. Silicone foam.
F. Firestop Systems for Insulated Pipes FS-5: Comply with the following:
1. Available UL-Classified Systems: W-J5007.
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Intumescent putty.
c. Silicone foam.
d. Intumescent wrap strips.
078410 - 9
G. Firestop Systems for Miscellaneous Mechanical Penetrations FS-6: Comply with the following:
1. Available UL-Classified Systems: W-J-7001.
2. Type of Fill Materials: One or both of the following:
a. Latex sealant.
b. Mortar.
H. Firestop Systems for Groupings of Penetrations FS-7: Comply with the following:
1. Available UL-Classified Systems: C-AJ-8015.
2. Type of Fill Materials: One or more of the following:
a. Latex sealant.
b. Mortar.
c. Intumescent wrap strips.
d. Firestop device.
e. Intumescent composite sheet.
END OF SECTION 078410