This document contains a solicitation for construction services and specifications for sheet metal flashing and trim. The solicitation is for Project 693-222 to construct a new parking garage at the Wilkes-Barre VA Medical Center campus in Pennsylvania with a magnitude between $10 million and $20 million. The work includes providing all labor, materials, tools, equipment, permits, testing and reports to construct the garage according to the drawings, specifications, and applicable federal, state and local codes and VA rules. The solicitation is set aside for verified service-disabled veteran-owned small businesses and will use a tiered evaluation process including large businesses. Pricing must be in whole dollars. Sheet metal flashing and trim specifications require aluminum, galvanized steel, copper and other materials in various thicknesses for items like roof drains, fascia, base flashing, scuppers and counterflashing, equipment supports, and expansion joints.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania
076200 - 1
SECTION 076200 SHEET METAL FLASHING AND TRIM
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes sheet metal flashing and trim in the following categories:
1. Roof drain flashing.
2. Exposed trim and fasciae.
3. Metal flashing.
4. Reglets.
5. Roof expansion joint covers.
B. Related Sections: The following Sections contain requirements that relate to this Section:
1. Division 4 Section “Unit Masonry” for through-wall flashing and other integral masonry flashings specified as part of masonry work.
2. Division 5 Section "Expansion Joint Cover Assemblies" for metal expansion-joint covers.
3. Division 7 Section "Joint Sealants" for elastomeric sealants.
4. Division 7 Section EPDM Single Ply Membrane Roofing for flashing and roofing accessories installed integral with roofing membrane as part of roofing-system work.
1.3 PERFORMANCE REQUIREMENTS
A. General: Install sheet metal flashing and trim to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failing.
B. Fabricate and install flashings at roof edges to comply with recommendations of FM Loss Prevention Data Sheet 1-49 for the following wind zone:
1. Wind Zone 2: Wind pressures of 31 to 45 psf.
1.4 SUBMITTALS
A. General: Submit each item in this Article according to the Conditions of the Contract and Division 1 Specification Sections.
B. Product Data including manufacturer's material and finish data, installation instructions, and general recommendations for each specified flashing material and fabricated product.
076200 - 2
C. Shop Drawings of each item specified showing layout, profiles, methods of joining, and anchorage details.
D. Samples of sheet metal flashing, trim, and accessory items, in the specified finish.
Where finish involves normal color and texture variations, include Sample sets composed of 2 or more units showing the full range of variations expected.
1. 8-inch- square Samples of specified sheet materials to be exposed as finished surfaces.
2. 12-inch- long Samples of factory-fabricated products exposed as finished Work.
Provide complete with specified factory finish.
E. Qualification data for firms and persons specified in the "Quality Assurance" Article to demonstrate their capabilities and experience.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Engage an experience Installer who has completed sheet metal flashing and trim work similar in material, design, and extent to that indicated for this Project and with a record of successful in-service performance.
1.6 PROJECT CONDITIONS
A. Coordinate Work of this Section with interfacing and adjoining Work for proper sequencing of each installation. Ensure best possible weather resistance, durability of Work, and protection of materials and finishes.
PART 2 - PRODUCTS
2.1 METALS
A. Aluminum: Alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated and with not less than the strength and durability of alloy and temper designated below:
1. Anodized Finish: Apply the following coil-anodized finish:
a. Class I, Clear Anodic Finish: AA-M12C22A41 (Mechanical Finish:
nonspecular as fabricated; Chemical Finish: etched, medium matte;
Anodic Coating: Architectural Class I, clear coating 0.018 mm or thicker) complying with AAMA 611.
B. Galvanized Steel Sheet (for work not exposed to view): ASTM A 526, G 90, commercial quality, or ASTM A 527, G 90, lock-forming quality, hot-dip galvanized steel sheet with 0.20 percent copper, mill phosphatized where indicated for painting;
not less than 0.0396 inch thick, unless otherwise indicated.
C. Aluminum-Zinc Alloy-Coated Steel Sheet (for work not exposed to view):
ASTM A 792, Class AZ-50 coating, Grade 40 or to suit project conditions, with 55 percent aluminum, not less than 0.0396 inch thick, unless otherwise indicated.
076200 - 3
2.2 REGLETS
A. General: Units of type, material, and profile indicated, formed to provide secure interlocking of separate reglet and counterflashing pieces and compatible with flashing indicated.
B. Masonry Type: Provide with offset top flange for embedment in masonry mortar joint.
C. Surface-mounted Type: Provide with slotted holes for fastening to substrate, with neoprene or other suitable weatherproofing washers, with channel for sealant at top edge.
D. Flexible Flashing Retainer: Provide resilient plastic or rubber accessory to secure flexible flashing in reglet where clearance does not permit use of standard metal counterflashing or where Drawings show reglet without metal counterflashing.
E. Counterflashing Wind-Restraint Clips: Provide clips to be installed before counterflashing to prevent wind uplift of the counterflashing lower edge.
1. Material: Aluminum, 0.024 inch thick.
F. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following:
1. Fry Reglet Corporation.
2. Hickman: W.P. Hickman Co.
3. Keystone Flashing Company.
2.3 MISCELLANEOUS MATERIALS AND ACCESSORIES
A. Solder: ASTM B 32, Grade Sn50, used with rosin flux.
B. Fasteners: Same metal as sheet metal flashing or other noncorrosive metal as recommended by sheet metal manufacturer. Match finish of exposed heads with material being fastened.
C. Asphalt Mastic: SSPC-Paint 12, solvent-type asphalt mastic, nominally free of sulfur and containing no asbestos fibers, compounded for 15-mil dry film thickness per coat.
D. Mastic Sealant: Polyisobutylene; nonhardening, nonskinning, nondrying, nonmigrating sealant.
E. Elastomeric Sealant: Generic type recommended by sheet metal manufacturer and fabricator of components being sealed and complying with requirements for joint sealants as specified in Division 7 Section "Joint Sealants."
F. Epoxy Seam Sealer: 2-part, noncorrosive, aluminum seam-cementing compound, recommended by aluminum manufacturer for exterior and interior nonmoving joints, including riveted joints.
076200 - 4
G. Adhesives: Type recommended by flashing sheet metal manufacturer for waterproof and weather-resistant seaming and adhesive application of flashing sheet metal.
H. Paper Slip Sheet: 5-lb/square red rosin, sized building paper conforming to FS UU-B- 790, Type I, Style 1b.
I. Polyethylene Underlayment: ASTM D 4397, minimum 6-mil- thick black polyethylene film, resistant to decay when tested according to ASTM E 154.
J. Metal Accessories: Provide sheet metal clips, straps, anchoring devices, and similar accessory units as required for installation of Work, matching or compatible with material being installed; noncorrosive; size and thickness required for performance.
K. Roofing Cement: ASTM D 4586, Type I, asbestos free, asphalt based.
2.4 FABRICATION, GENERAL
A. Sheet Metal Fabrication Standard: Fabricate sheet metal flashing and trim to comply with recommendations of SMACNA's "Architectural Sheet Metal Manual" that apply to the design, dimensions, metal, and other characteristics of the item indicated.
B. Comply with details shown to fabricate sheet metal flashing and trim that fit substrates and result in waterproof and weather-resistant performance once installed.
Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal.
C. Form exposed sheet metal Work that is without excessive oil canning, buckling, and tool marks and that is true to line and levels indicated, with exposed edges folded back to form hems.
D. Seams: Fabricate nonmoving seams in aluminum with flat-lock seams. Form seams and seal with epoxy seam sealer. Rivet joints for additional strength.
E. Expansion Provisions: Space movement joints at maximum of 10 feet with no joints allowed within 24 inches of corner or intersection. Where lapped or bayonet-type expansion provisions in Work cannot be used or would not be sufficiently weatherproof and waterproof, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant (concealed within joints).
F. Sealed Joints: Form nonexpansion, but movable, joints in metal to accommodate elastomeric sealant to comply with SMACNA standards.
G. Separate metal from noncompatible metal or corrosive substrates by coating concealed surfaces at locations of contact with asphalt mastic or other permanent separation as recommended by manufacturer.
H. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of sheet metal exposed to public view.
076200 - 5
I. Fabricate cleats and attachment devices from same material as sheet metal component being anchored or from compatible, noncorrosive metal recommended by sheet metal manufacturer.
1. Size: As recommended by SMACNA manual or sheet metal manufacturer for application but never less than thickness of metal being secured.
2.5 SHEET METAL FABRICATIONS
A. General: Fabricate sheet metal items in thickness or weight needed to comply with performance requirements but not less than that listed below for each application and metal.
B. Roof Drain Flashing: Fabricate from the following material:
1. Lead-coated Copper: 12 oz./sq. ft.
C. Exposed Trim and Fasciae: Fabricate from the following material:
1. Aluminum: 0.050 inch thick.
D. Base Flashing: Fabricate from the following material:
1. Aluminum: 0.040 inch thick.
E. Scuppers & Counterflashing: Fabricate from the following material:
1. Aluminum: 0.0320 inch thick.
F. Flashing Receivers: Fabricate from the following material:
G. Drip Edges: Fabricate from the following material:
H. Eave Flashing: Fabricate from the following material:
I. Equipment Support Flashing: Fabricate from the following material:
1. Lead-coated Copper: 16 oz./sq. ft.
J. Overhead-Piping Safety Pans: Fabricate from the following material:
1. Galvanized Steel: 0.0396 inch thick.
K. Roof Penetration Flashing: Fabricate from the following material:
1. Lead-coated Copper: 16 oz./sq. ft.
076200 - 6
L. Roof Expansion Joint Cover: Fabricate from the following material:
1. Aluminum: 0.040 inch thick.
M. Roof-to-Wall Expansion Joint Cover: Fabricate from the following material:
PART 3 - EXECUTION
5.1 EXAMINATION
A. Examine substrates and conditions under which sheet metal flashing and trim are to be installed and verify that Work may properly commence. Do not proceed with installation until unsatisfactory conditions have been corrected.
5.2 INSTALLATION
A. General: Unless otherwise indicated, install sheet metal flashing and trim to comply with performance requirements, manufacturer's installation instructions, and SMACNA's "Architectural Sheet Metal Manual." Anchor units of Work securely in place by methods indicated, providing for thermal expansion of metal units; conceal fasteners where possible, and set units true to line and level as indicated. Install Work with laps, joints, and seams that will be permanently watertight and weatherproof.
B. Install exposed sheet metal Work that is without excessive oil canning, buckling, and tool marks and that is true to line and levels indicated, with exposed edges folded back to form hems. Install sheet metal flashing and trim to fit substrates and to result in waterproof and weather-resistant performance. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal.
C. Roof-Edge Flashings: Secure metal flashings at roof edges according to FM Loss Prevention Data Sheet 1-49 for specified wind zone.
D. Expansion Provisions: Provide for thermal expansion of exposed sheet metal Work.
Space movement joints at maximum of 10 feet with no joints allowed within 24 inches of corner or intersection. Where lapped or bayonet-type expansion provisions in Work cannot be used or would not be sufficiently weatherproof and waterproof, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant (concealed within joints).
E. Soldered Joints: Clean surfaces to be soldered, removing oils and foreign matter.
Pretin edges of sheets to be soldered to a width of 1-1/2 inches, except where pretinned surface would show in finished Work.
1. Do not solder the following metals:
a. Aluminum.
b. Coil-coated galvanized steel sheet.
076200 - 7
2. Do not use torches for soldering. Heat surfaces to receive solder and flow solder into joint. Fill joint completely. Completely remove flux and spatter from exposed surfaces.
F. Sealed Joints: Form nonexpansion, but movable, joints in metal to accommodate elastomeric sealant to comply with SMACNA standards. Fill joint with sealant and form metal to completely conceal sealant.
1. Use joint adhesive for nonmoving joints specified not to be soldered.
G. Seams: Fabricate nonmoving seams in aluminum with flat-lock seams. Form seams and seal with epoxy seam sealer. Rivet joints for additional strength.
H. Separations: Separate metal from noncompatible metal or corrosive substrates by coating concealed surfaces, at locations of contact, with asphalt mastic or other permanent separation as recommended by manufacturer.
1. Underlayment: Where installing stainless steel or aluminum directly on cementitious or wood substrates, install a slip sheet of red-rosin paper and a course of polyethylene underlayment.
2. Bed flanges of Work in a thick coat of roofing cement where required for waterproof performance.
I. Install reglets to receive counterflashing according to the following requirements:
1. Where reglets are shown in masonry, furnish reglets for installation under Division 4 Section "Unit Masonry."
J. Counterflashings: Coordinate installation of counterflashings with installation of assemblies to be protected by counterflashing. Install counterflashings in reglets or receivers. Secure in a waterproof manner by means of snap-in installation and sealant, lead wedges and sealant, interlocking folded seam, or blind rivets and sealant. Lap counterflashing joints a minimum of 2 inches and bed with sealant.
K. Roof Drainage System: Install drainage items fabricated from sheet metal, with straps, adhesives and anchors recommended by SMACNA’s Manual or the manufacturer, to drain roof in the most efficient manner. Coordinate roof drain flashing installation with roof drainage system installation. Coordinate flashing and sheet metal items for steep-sloped roofs with roofing installation.
L. Overhead-Piping Safety Pans: Suspend pans from pipe and install drain line to plumbing waste or drain line.
M. Equipment Support Flashing: Coordinate equipment support flashing installation with roofing and equipment installation. Weld or seal flashing to equipment support member.
N. Roof Penetration Flashing: Coordinate roof penetration flashing installation with roofing and installation of items penetrating roof.
1. Turn lead flashing down inside vent piping, being careful not to block vent piping with flashing.
076200 - 8
2. Seal and clamp flashing to pipes penetrating roof, other than lead flashing on vent piping.
5.3 CLEANING AND PROTECTION
A. Clean exposed metal surfaces, removing substances that might cause corrosion of metal or deterioration of finishes.
B. Provide final protection and maintain conditions that ensure sheet metal flashing and trim Work during construction is without damage or deterioration other than natural weathering at the time of Substantial Completion.
END OF SECTION 076200