238200.pdf
PDF 42 KB Posted
- Attached to
- Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 Federal contract opportunity
- Solicitation number
- 36C24420R0075
About this file
This document includes a federal construction contract specification and related federal contract opportunity. The specification outlines requirements for convection heating and cooling units, cabinet unit heaters, wall-mounted unit heaters, and their installation for the Parking Garage Project Number 693-222 at the Department of Veterans Affairs Wilkes-Barre campus in Pennsylvania. The specification addresses product descriptions, materials, controls, testing procedures, and demonstration and training requirements.
The related federal contract opportunity is a solicitation to construct the parking garage outlined in the specification. Offerors are to provide all labor, materials, tools, permits, testing and reports to build the approximately 435-space parking structure according to the provided drawings, specifications, and Statement of Work while adhering to federal, state and local codes and VA rules. The magnitude of the project value is between $10-20 million. The solicitation is set aside for verified service-disabled veteran-owned small businesses and utilizes tiered evaluation procedures.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania
238200 - 1
SECTION 23 82 00 - CONVECTION HEATING AND COOLING UNITS
PART 1 - GENERAL
1.1 DESCRIPTION
Unit heaters and cabinet unit heaters.
1.2 RELATED WORK
A. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General mechanical requirements and items, which are common to more than one section of Division 23.
B. Section 23 31 00, HVAC DUCTS and CASINGS: Ducts and flexible connectors.
C. Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC: Flow rates adjusting and balancing.
1.3 QUALITY ASSURANCE
Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK
RESULTS FOR HVAC.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Manufacturer's Literature and Data:
1. Unit heaters.
2. Cabinet unit heaters.
C. Certificates:
1. Compliance with paragraph, QUALITY ASSURANCE.
2. Compliance with specified standards.
D. Operation and Maintenance Manuals: Submit in accordance with paragraph, INSTRUCTIONS, in Section 01 00 00, GENERAL REQUIREMENTS.
E. Completed System Readiness Checklists provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 23 08 00 COMMISSIONING
OF HVAC SYSTEMS.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced.
The publications are referenced in the text by the basic designation only.
Wilkes-Barre, Pennsylvania
238200 - 2
B. American National Standards Institute / Air Conditioning, Heating and Refrigeration
Institute (ANSI/AHRI):
440-08 ...................................Performance Rating of Room Fan Coils
National Fire Protection Association (NFPA):
90A-09 ...................................Standard for the Installation of Air Conditioning and
Ventilating Systems
70-11 .....................................National Electrical Code
C. Underwriters Laboratories, Inc. (UL):
181-08 ...................................Standard for Factory-Made Air Ducts and Air Connectors
1995-05 .................................Heating and Cooling Equipment
1.6 GUARANTY
In accordance with FAR clause 52.246-21
PART 2 - PRODUCTS
2.1 UNIT HEATERS
A. General: Horizontal or vertical discharge type for steam, hot water or electric heating medium, as indicated.
B. Casing: Steel sheet, phosphatized to resist rust and finished in baked enamel. Provide hanger supports.
C. Fan: Propeller type, direct driven by manufacturer's standard electric motor. Provide resilient mounting. Provide fan guard for horizontal discharge units.
D. Discharge Air Control:
1. Horizontal discharge: Horizontal, adjustable louvers.
2. Vertical discharge: Radial louver diffuser.
E. Electric Units: UL listed, factory wired to terminal strips for field connection of power and control wiring.
1. Heating elements: Nickel chromium alloy resistance wire embedded in a magnesium oxide insulating refractory and sealed in corrosion resisting metallic sheath with fins.
Three phase heaters shall have balanced phases.
2. Thermal cutout: Manual reset type, which disconnects elements, and motor in the event normal operating temperatures are exceeded.
3. Magnetic contactor: Factory installed with low voltage relay for remote pilot duty thermostat operation.
Wilkes-Barre, Pennsylvania
238200 - 3
F. Controls: Provide factory installed unit mounted line voltage electric space thermostats to control the unit fan and heater.
2.2 CABINET UNIT HEATERS
A. General: Vertical or horizontal type for steam, hot water or electric heating medium, as indicated.
B. Cabinet: Not less than 1.3 mm (l8 gage) steel with front panel for vertical units and hinged front panel for horizontal units. Finish on exposed cabinet shall be factory-baked enamel in manufacturer's standard color as selected by the Architect. Provide 76 mm
(3-inch) high sub-base for vertical floor mounted units.
C. Fan: Centrifugal blower, direct driven by a single phase, two-speed, electric motor with inherent overload protection. Provide resilient motor/fan mount.
D. Filter: Manufacturer's standard, one inch thick, throwaway type MERV 7 filters.
E. Electric Coil: Spiral sheath or finned-tube construction with Cal-rod resistance elements in aluminum tubes. Units shall be UL listed and factory wired with unit mounted heat switch, magnetic contactors, high temperature cutout safety control, and fan override thermostat.
F. Controls: Provide factory installed unit mounted line voltage electric space thermostats to control the unit fan and heater.
2.5 WALL-MOUNTED UNIT HEATER
A. General: Electric heat, fan driven, thermostatic control, UL listed.
B. Enclosure:
1. Wall box: Not less than 1.3 mm (l8 gage) steel, recessed type.
2. Ribbed 1.6 mm (l6 gage) steel front cover.
3. Closely spaced discharge louvers.
4. Concealed screws for locking trim frame to front cover.
5. Finished in baked enamel of manufacturer’s standard color with satin finish anodized aluminum trim frame.
C. Heating Elements: Steel sheath enclosed finned-tube type.
D. Integral Controls:
l. Two-pole terminal block.
2. Built-in fan delay switch.
3. Automatic reset line voltage internal thermal overheats protection.
Wilkes-Barre, Pennsylvania
238200 - 4
4. Built-in thermostat comfort control with adjustment range between -1 to 32 degree C
(30-90 degrees F), and manually set "No Heat" position; tamper resistant adjustment by inserting screwdriver through front cover louvers.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Work shall be installed as shown and according to the manufacturer’s diagrams and recommendations.
B. Handle and install units in accordance with manufacturer's written instructions.
C. Support units rigidly so they remain stationary at all times. Cross-bracing or other means of stiffening shall be provided as necessary. Method of support shall be such that distortion and malfunction of units cannot occur.
D. Install fiberglass blanket insulation with a minimum R value of 8 above hydronic radiant panels.
3.2 OPERATIONAL TEST
Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
3.5 DEMONSTRATION AND TRAINING
A. Provide services of manufacturer’s technical representative for two hours to instruct VA personnel in operation and maintenance of units.
- - - E N D - - -
| PART 1 � GENERAL |
| 1.1 DESCRIPTION |
| 1.2 RELATED WORK |
| 1.3 QUALITY ASSURANCE |
| 1.4 SUBMITTALS |
| 1.5 APPLICABLE PUBLICATIONS |
| 1.6 GUARANTY |
| PART 2 � PRODUCTS |
| 2.1 UNIT HEATERS |
| 2.2 CABINET UNIT HEATERS |
| 2.5 WALL�MOUNTED UNIT HEATER |
| PART 3 � EXECUTION |
| 3.1 INSTALLATION |
| 3.2 OPERATIONAL TEST |
| 3.5 demonstration and training |