PROJECT:
DRAWING No:
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 1 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
COVER
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
DEVELOPED BY:
DATA CENTER AND INFRASTRUCTURE ENGINEERING
COMMUNITY BASED OUTPATIENT CLINIC (CBOC)
INSIDE PLANT
INFORMATION TRANSPORT SYSTEMS SPECIFICATIONS
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 2 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
LEGEND
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
LEGEND
ELECTRICAL
NOTES
TYP
DETAIL NUMBER
TYPICAL THROUGHOUT THIS
SHEET
ELECTRICAL
BONDING BUSBAR
ARCHITECTURAL
TELECOMMUNICATIONS TELECOMMUNICATIONS
ARCHITECTURAL
DETAIL NUMBER#
TYP
DETAIL NUMBER
DETAIL NUMBER
TYPICAL THROUGHOUT THIS SHEET
40" TELECOMMUNICATIONS CABINET WITH HORIZONTAL CABLE
CUTOUTS AND APPROPRIATE CABLE MANAGEMENT
ACCESSORIES, SUPPORTING 5KW REDUNDANT
DEMO WALL
NEW WALL
MECHANICAL MECHANICAL
CHANGES TO DESIGN WILL REQUIRE A NEW COMPUTATIONAL FLUID
DYNAMICS (CFD) ANALYSIS TO BE PERFORMED
FLOORPLANS ARE NOT TO SCALE
DOCUMENTS ARE NOT TO BE USED FOR CONSTRUCTION
COLD AISLE CONTAINMENT (PVC CURTAIN)
1 SERVICE PROVIDER ENTRANCE POINT
SERVICE BACKBONE (ENTRANCE ROOM-MAIN COMPUTER
ROOM)
MAIN CROSS CONNECT (CAMPUS/BUILDING DISTRIBUTOR) –
BACKBONE CABLING (MCR-TELECOMMUNCIATIONS ROOMS)
ENTRANCE ROOM (TR) INTERCONNECT
HORIZONTAL DISTRIBUTION TO WORK AREA OUTLETS (WAO)
ADDITIONAL CABINETS OR TELECOMMUNICATIONS RACKS TO
MEET REQUIREMENTS.
7 HORIZONTAL DISTRIBUTION AREA – SIDE A
8 HORIZONTAL DISTRIBUTION AREA – SIDE B
9 MAIN DISTRIBUTION AREA – SIDE A
10 MAIN DISTRIBUTION AREA – SIDE B
STANDARD DENSITY CABINET SUPPORTING 5KW
REDUNDANT
12 HIGH DENSITY CABINET SUPPORTING 10KW REDUNDANT
WIRE MESH CABLE TRAY MINIMUM OF 6"X 12" WITH SECOND
LEVEL OF FIBER CHANNEL PATHWAY (4" X 4")
BLUE CABLE TRAY PATH FOR CABLES TO THE A-SIDE MDA/
HDA
YELLOW CABLE TRAY PATH FOR CABLES TO THE B-SIDE MDA/
HDA
17 TELECOMMUNICATIONS CHANNEL RACK
SECONDARY BONDING BUSBAR PLACEMENT DETERMINED BY
OTHERS
PRIMARY BONDING BUSBAR PLACEMENT DETERMINED BY
OTHERS
MINIMUM TWO 110V 20A CONVENIENCE BUILDING POWER
OUTLETS PER WALL; PLACEMENT DETERMINED BY OTHERS. 1
30 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE
(L21-30R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE
INSTALLATION LOCATION WITH TELECOMMUNICATIONS
CONTRACTOR
20 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE (L21-
20R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE INSTALLATION
LOCATION WITH TELECOMMUNICATIONS CONTRACTOR
SERVICE PANEL FOR RACK POWER. IT LOAD ONLY. SHALL BE
EQUIPPED WITH POWER METER; MONITORED SOLUTION
PREFERRED. PLACEMENT PER OTHERS
SERVICE PANEL FOR DEDICATED ROOM AIR CONDITIONING. NON-IT
LOAD ONLY. SHALL BE EQUIPPED WITH POWER METER;
MONITORED SOLUTION PREFERRED. PLACEMENT PER OTHERS
1. LED LIGHTING PLACED IN AISLES DIRECTLY IN FRONT OF
AND BEHIND CABINET ROWS
2. LIGHTING OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION
3. 500 LUX IN THE HORIZONTAL PLANE AND 200 LUX IN THE
VERTICAL PLANE REQUIRED MEASURED AT 3 FT AFF IN
FRONT OF AND BEHIND EQUIPMENT CABINETS
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM A SIDE SOURCE
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM B SIDE SOURCE
WIRE MESH CABLE TRAY SIZE COMMENSURATE
WITH REQUIREMENTS
SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
CONDUIT WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND
INNERDUCT FOR FIBER
TELECOMMUNICATIONS CHANNEL RACK, 19" RAILS, #12-24
TAPPED EIA HOLE PATTERN, 30" DEEP CHANNEL MINIMUM, 7'
HIGH, 45RU, WHITE
VERTICAL CABLE MANAGER WITH DOOR, 6" WIDE MINIMUM
SERVER CABINET, 45U, 24"X48" (NOMINAL), SQUARE
PUNCHED RAIL, SINGLE PERFORATED FRONT DOOR, SOLID
REAR DOOR (VERTICAL EXHAUST DUCT IMPLEMENTATION),
DOUBLE PERFORATED REAR DOOR (NO VED), TWO-POINT
KEYED LOCKS, WHITE,SOLID SIDE PANELS
OR
TELECOMMUNICATIONS CABINET, 7' HIGH, 45U, 40"X48"
(NOMINAL), SQUARE PUNCHED RAIL, SINGLE
PERFORATED FRONT DOOR, SOLID REAR DOOR
(VERTICAL EXHAUST DUCT IMPLEMENTATION), TWO-
POINT KEYED LOCKS, WHITE,SOLID SIDE PANELS
OR WIRE MESH CABLE TRAY SIZE COMMENSURATE WITH
REQUIREMENTS
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT FIVE [5] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM A SIDE SOURCE
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT FIVE [5] 208V, 20 AMP, L21-20R BUSWAY TAPS) FED
FROM B SIDE SOURCE
BLUE CABLE PATH FOR A-SIDE UPS12
YELLOW CABLE PATH FOR B-SIDE UPS13
LIGHTING:
RETURN AIR DUCT
COMPUTER ROOM AIR CONDITIONER (SEE COMPUTATIONAL
FLUID DYNAMICS REPORT FOR SIZING)
REQUIRED CLEARANCE AROUND CRACS
ELECTRICAL SERVICE PANEL
OVERHEAD POWER DROP CORD WITH L21-20 RECEPTACLE
POWER BUSWAY TAP WITH SINGLE BREAKER 3' DROP
CORD WITH L21-20R FOR STANDARD-DENSITY CABINETS
POWER BUSWAY TAP WITH DUAL BREAKER AND TWO 3'
DROP CORDS WITH L21-20R FOR HIGH DENSITY CABINETS
TYPICAL UNSWITCHED 110 VOLT, 20 AMP DUPLEX
CONVENIENCE OUTLET
AC
SPLIT PACKAGE AIR CONDITIONER OR EQUIVALENT 24/7
SUPPLY AIR TO REJECT 5KW (17,000 BTU PER
TELECOMMUNICATIONS RACK)
AC
ADDITIONAL SPLIT PACKAGE AIR CONDITIONER OR LARGER
UNIT TO REJECT HEAT FROM ADDITIONAL RACKS (17,000
BTU PER TELECOMMUNICATIONS RACK)
4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT FOR SERVICE PROVIDER / SECURITY /
VIDEO / ET CETERA
3 FT WIDE, 8 FT HIGH DOOR, FIRE RESISTANT TO ¾ HOUR OR
MORE PER AHJ
6 FT WIDE, 8 FT HIGH DOOR, NO CENTER MULLION, FIRE
RESISTANT TO ¾ HOUR OR MORE PER AHJ
STANDARD 25% OPEN PERFORATED FLOOR TILE
C R
A C
MODULAR UPS CABINET (POWER MODULES, BATTERIES,
POWER PANELS)
LED LIGHTING
POWER BUSWAY WITH METERED HEADEND FOR B SIDE
POWER DISTRIBUTION
POWER BUSWAY WITH METERED HEADEND FOR A SIDE
POWER DISTRIBUTION
C FIXED CAMERA, PAN/TILT/ZOOM, PASSIVE INFRARED
CAMERA - DUAL TECHNOLOGY”
PIV ENABLED TWO-FACTOR AUTHENTICATION KEYPAD
M
CEILING MOUNTED MOTION SENSOR (LOCATIONS AS
REQUIRED FOR FULL ROOM COVERAGE)
MOTION SENSOR LIGHT SWITCH
J
OVERHEAD POWER DROP CORD WITH L21-30 RECEPTACLE
POWER JUNCTION BOX FOR 60A CONNECTION
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 3 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SPECIFICATIONS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
GENERIC TELECOMMUNICATIONS MEDIA AND INTERFACE SPECIFICATIONS FOR TELECOMMUNICATION SPACES
SPECIFICATIONPRIMARY ATTRIBUTEID SECONDARY ATTRIBUTE
1 COPPER PATCH PANELS
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)
POSITION COUNT 48
FORM FACTOR ANGLED
SIZE ONE RACK UNIT
JACK COLOR CODING A-SIDE BLUE / B-SIDE YELLOW
CASSETTE CAPACITY 12 CASSETTES OR 6 DOUBLE CASSETTES
CASSETTE USER INTERFACES LC DUPLEX CONNECTORS
FIBER DISTRIBUTION PANELS CASSETTE BACKBONE INTERFACES MPO-12
PERFORMANCE CHARACTERISTICS OM4 LASER ENHANCED 40 GBE 50/125 MULTIMODE / OS1 9/125 SINGLE MODE
FORM FACTOR ONE (1) RU
3 UTP (HORIZONTAL AND FIRST LEVEL BACKBONE)
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)
PERFORMANCE SPECIFICATIONS MEETS OR EXCEEDS TIA-EIA-568-C.2-10, TSB-155.
JACKET COLOR BLUE (HORIZONTAL), WHITE (1ST LEVEL BACKBONE)
PERFORMANCE CATEGORY OM4 LASER ENHANCED TO 40 GIGABIT ETHERNET (GBE) / OS1 / OS2
PERFORMANCE SPECIFICATIONS
LASER OPTIMIZED 50/125 MM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /
OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)
FIBER (HORIZONTAL AND FIRST LEVEL BACKBONE)
MODE MULTIMODE/SINGLE MODE (DISTRIBUTION TO TRS ONLY)
JACKET COLOR AQUA (OM4) / YELLOW (OS1/2)
MEDIA CONNECTOR PRE-TERMINATED WITH MPO, TYPE A
STRAND COUNT 12 OR 24
BUNDLING LOOSE TUBE
5 UTP PATCH CORDS
PERFORMANCE CATEGORY CATEGORY 6A, 26-GAUGE, STRANDED
PERFORMANCE SPECIFICATIONS CENTER TUNED TO HORIZONTAL MEDIA
JACKET COLOR BLUE
6 FIBER PATCH CORDS MODE MULTIMODE/SINGLE MODE (PATCH CORD TO TRS ONLY)
MEDIA CONNECTOR PRE-TERMINATED WITH DUPLEX LC
JACKET COLOR AQUA (OM4) / YELLOW (OS1/2)
PERFORMANCE SPECIFICATIONS
LASER OPTIMIZED 50/125 ΜM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /
OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)
PERFORMANCE CATEGORY OM4 / OS1 / OS2
TERMINATION METHOD FACTORY PRE-TERMINATED
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 4 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
GENERIC HEALTH CARE FACILITY
EQUIPMENT ROOM
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY EQUIPMENT ROOM 1
AC
SERVICE PANEL FOR
DEDICATED ROOM AIR
CONDITIONING. NON-IT
LOAD ONLY. SHALL BE
EQUIPPED WITH
SCHNEIDER EM3500
SERIES DIN RAIL METER
OR EQUIVALENT
SERVICE PANEL FOR RACK
POWER IN
TELECOMMUNICATION ROOM.
IT LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL
METER OR EQUIVALENT
TWO (2) CONDUITS
INTERCONNECTING NETWORK
SUPPORT CENTER WITH
ENTRANCE FACILITY. TRADE SIZE
CONDUIT OR SLEEVES WITH BUSHING AND
FIRESTOP OR OTHER AHJ-APPROVED
PENETRATION FOR HORIZONTAL
DISTRIBUTION FROM WORK AREA OUTLETS
AND TELECOMMUNICATION ROOMS
L21-30R
PRIMARY OR
SECONDARY BONDING
BUSBAR (PBB/SBB)
WIRE MESH CABLE TRAY SIZE
COMMENSURATE WITH
REQUIREMENTS
VERTICAL CABLE MANAGER WITH
DOOR, 6" WIDE
TYPICAL UNSWITCHED DUPLEX
CONVENIENCE OUTLETS
SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU/H)
AC
L21-30R
ADDITIONAL SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU) WHEN
NECESSARY
T
AIR CONDITIONER THERMOSTAT
TELECOMMUNICATIONS CHANNEL
RACK, 19" RAILS, #12-24 TAPPED
EIA HOLE PATTERN, MINIMUM 30"
DEEP, 7' HIGH, 45RU, WHITE
SERVER CABINET, 45U, 24"X48"
(NOMINAL), SQUARE PUNCHED
RAIL, SINGLE PERFORATED FRONT
DOOR, SOLID REAR DOOR, TWO-
POINT KEYED LOCKS, WHITE,SOLID
SIDE PANELS
3'-0"
RK-1 RK-2 RK-3 RK-4
NOTE:
THERE SHALL BE A MINIMUM OF ONE
TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
THE EQUIPMENT ROOM CAN SERVE AS A TR.
ADDITIONAL ROOMS SHOULD BE PROVIDED WHEN:
A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2
(10 000 FT2);
OR
B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE
WORK AREA EXCEEDS 90 M (295 FT).
NO RAISED FLOOR.
C
PIV/
KEYPAD
• MINIMUM 170 FT2
• STATIC DISSIPATING FLOOR
• NO DROP CEILING
• SLAB TO DECK ABOVE 12 FT
MINIMUM (16 FT PREFERRED)
• WALLS FULL HEIGHT TO DECK
ABOVE
4'X 8' AC GRADE ¾” TRADE
SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE
WITH TWO COATS OF FIRE
RESISTANT PAINT FOR
SERVICE PROVIDER
EQUIPMENT
4'X 8' AC GRADE ¾” TRADE
SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE
WITH TWO COATS OF FIRE
RESISTANT PAINT FOR
SECURITY EQUIPMENT
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 5 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
GENERIC HEALTH CARE FACILITY
TELECOMMUNICATIONS ROOM
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS
AC
SERVICE PANEL FOR
DEDICATED ROOM AIR
CONDITIONING. NON-IT
LOAD ONLY. SHALL BE
EQUIPPED WITH
SCHNEIDER EM3500
SERIES DIN RAIL METER
OR EQUIVALENT
SERVICE PANEL FOR RACK
POWER IN
TELECOMMUNICATION ROOM.
IT LOAD ONLY. SHALL BE
EQUIPPED WITH SCHNEIDER
EM3500 SERIES DIN RAIL
METER OR EQUIVALENT
CONDUITS INTERCONNECTING
NETWORK SUPPORT CENTER
WITH ENTRANCE FACILITY
CONDUIT OR SLEEVES WITH BUSHING AND
FIRESTOP OR OTHER AHJ-APPROVED
PENETRATION FOR HORIZONTAL DISTRIBUTION
FROM WORK AREA OUTLETS AND
TELECOMMUNICATION ROOMS
L21-30R
WIRE MESH CABLE TRAY SIZE
COMMENSURATE WITH
REQUIREMENTS
• MAXIMUM 170 FT2
• STATIC DISSIPATING
FLOOR
• NO DROP CEILING
• SLAB TO DECK 12 FT
MINIMUM (16 FT
PREFERRED)
• WALLS FULL HEIGHT TO
DECK
VERTICAL CABLE MANAGER WITH
DOOR, 6" WIDE
TYPICAL UNSWITCHED DUPLEX
CONVENIENCE OUTLETS
PRIMARY OR
SECONDARY BONDING
BUSBAR (PBB/SBB)
SPLIT PACKAGE AIR
CONDITIONER
AC
L21-30R
ADDITIONAL SPLIT PACKAGE AIR
CONDITIONER WHEN NECESSARY
T
AIR CONDITIONER THERMOSTAT
TELECOMMUNICATIONS RACK, 19" RAILS, #12-
24 TAPPED EIA HOLE PATTERN, 30" DEEP
CHANNEL, 7' HIGH, 45RU, WHITE
3'-0"
NOTE:
THERE SHALL BE A MINIMUM OF ONE
TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
THE EQUIPMENT ROOM CAN SERVE AS A TR. ADDITIONAL
ROOMS SHOULD BE PROVIDED WHEN:
A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10
000 FT2);
OR
B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK
AREA EXCEEDS 90 M (295 FT).
NO RAISED FLOOR.
RK-1 RK-2 RK-3 RK-4
C
PIV/
KEYPAD
4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD
BACKBOARD PAINTED HIGH-GLOSS WHITE
WITH TWO COATS OF FIRE RESISTANT
PAINT FOR SERVICE PROVIDER EQUIPMENT
4'X 8' AC GRADE ¾” TRADE SIZE
PLYWOOD BACKBOARD PAINTED HIGH-
GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT FOR SECURITY
EQUIPMENT
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 6 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS ROOMS
IN ADMINISTRATIVE AREAS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
AC AC
3 45
TY
P
T
AC
P
TY
P
T
AC
P
TY
P
T
NOTE:
THERE SHALL BE A MINIMUM OF ONE TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
ADDITIONAL ROOMS SHOULD BE PROVIDED WHEN:
A) THE FLOOR AREA TO BE SERVED EXCEEDS 1000 M2 (10,000 FT2);
OR
B) THE HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK AREA EXCEEDS 90 M (295 FT).
FLOOR SPACE REQUIREMENT:
1. MINIMUM OF 80 SQ FT FOR A ONE RACK TR
2. ADD AN ADDITIONAL 20 SQ FT PER ADDITIONAL RACK
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS 2
GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (TWO RACK REQUIREMENT)
(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA
OUTLETS)3
GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (ONE RACK REQUIREMENT)
(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA
OUTLETS )
TELECOMMUNICATION ROOM NOTES1
M
C
M
C
J J
TY
P
'-0
'-0
'-0
15'-5 7/16"
8'-0"10'-0"
C
M
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 7 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL BACKBOARD
RESERVATIONS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
AC AC T
RESERVED
VIDEO DISTRIBUTION
WAN/DEMARC
SECURITY POWER METERING
FIRE ALARM/
ANNOUNCIATOR
3'-0"
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 8 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK ELEVATION
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
M ODE CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
M ODE CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C 38 50 -NM-4 -10 G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
RK-1
MAXIMUM OF 12 ANGLED CATEGORY 6A, 24 PORT
PATCH PANELS PER RACK. IF MORE THAN TWELVE (12)
PATCH PANELS ARE REQUIRED, INSTALL NEXT SET IN
RK-3.
1 RU BLANKING PANELS BETWEEN LOWEST
PATCH PANEL AND RU32
1 RU CABLE MANAGER. SIX POSITION
SPACING WITH DOOR AT RU31
3850 POE LAN SWITCH WITH 1100 WATT POWER
SUPPLIES. MAX OF SIX (6) PER RACK.
2 RU CABLE MANAGER. SIX POSITION
SPACING WITH DOOR.
1 RU CABLE MANAGER. SIX
POSITION SPACING WITH DOOR.
ZONE PDU
UPS
RK-2 RK-3
RK-4
TYPICAL RACK ELEVATION FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
1 2 3 4 5 6
7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 24
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G3 G4
NETWORK MODULE
TE3 TE4TE1 TE2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
M ODE
CONSOLE
37X
Catalys t 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G 2 G3 G 4
NET WO RK MO DULE
T E3 T E4TE1 T E2
SPACE
RESERVED
FOR WAN
ROUTERS, IP
PBX,
SECURITY
EQUIPMENT,
ETC.
SPACE
RESERVED
FOR
SERVERS.
SERVICE PROVIDER MAIN CROSS CONNECT
FIRST LEVEL BACKBONE (FIBER)
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 9 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK DETAIL
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
6" WIDE VERTICAL CABLE MANAGEMENT
P/N: OR-MM20VMD706 (OR EQUIVALENT)
MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH
DOOR, 6" X 8.61" X 7' , BLACK
CAPACITY: 350 CATEGORY 6 PATCH CORDS OR 245
CATEGORY 6A PATCH CORDS
6 in
TYPICAL RACK DIMENSIONS AND SPECIFICATIONS
NTS
P/N: OR-MM2073038-W (OR EQUIVALENT)
MIGHTY MO 20 CABLE MANAGEMENT RACK
30" CHANNEL DEPTH, 7' HIGH, WHITE FINISH OR EQUIVALENT
DIMENSIONS:
USABLE HEIGHT: 45RU
DEPTH (US): 30
HEIGHT (US): 7'
WIDTH (US): 23.75"
STATIC LOAD CAPACITY: 2000 LBS
SQUARE HOLE
FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-
MM20724PDHD-W)1
SECURITY DOOR FRONT
MOUNTING HARDWARE (OR-
MM2024DMFHD-W) OR
EQUIVALENT4
SECURITY DOOR REAR
MOUNTING HARDWARE (OR-
MM2024DMRHD-W) OR
EQUIVALENT5
PDU MOUNTING BRACKET KIT
(TWO KITS PER RACK)
P/N: OR-MM20PDUMB1D2W-W
OR EQUIVALENT6
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 10 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL CABINET DETAIL
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
TYPICAL ENCLOSURE SPECIFICATION
NTS
TYPICAL ENCLOSURE FRONT
NTS
TYPICAL ENCLOSURE SIDE VIEW
NTS
CP3210245 F-Series TeraFrame Gen 3 Cabinet System with accessories installed Configuration includes the following components:
Item Number Description (Qty) FF1N-113C-E42-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30"
(1100mm) D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing Handle Lock, Double Perforated Metal Rear Door, Two Point, Keyed Swing Handle Latch, Server Top Panel, 2 Solid Side
Panel, Glacier White, 6-Slide Frame
024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier White (1)
024-739060-E03 Door, TeraFrame, Front, Asssembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)
024-739050-E03 Double Door Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739054-703 Lock Kit, 2-Point Latching, Keyed, Perforated Door, 45 RMU (1)
024-739140-E12 Top Panel, 2-Piece, Brush, 23.6'' (600 mm) W x 43.3'' (1100 mm) D, Glacier White
024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)
024-739200-002 Kit,Common Parts Parts,Teraframe,UL,White (1)
024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)
024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41 mm) H
39085-E03 Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
39137-703 Baying Seal Kit, 45U (2)
39132-E00 Bottom Panel, With Brush, 23.6'' (600 mm) W x 39.4" - 47.2" (1000 - 1200 mm) D, Glacier White (1)
31920-E03 Finger Cable Manager no Cover (2)
UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard.
UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.
(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)
TYPICAL ENCLOSURE TOP VIEW WITH FOUR (4)
BRUSHED GROMMET CABLE OPENINGS
NTS
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
.6
23.6"43.3"
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 11 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL WORK AREA OUTLETS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
TYPICAL WORK FLOOR MOUNT OUTLET4TYPICAL WALL MOUNT PHONE VOIP OUTLET3
ONE CATEGORY 6A
8P8C OUTLET ACTIVE
FOR TELEPHONY
TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY 6A
COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45). EACH
CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A HORIZONTAL
CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS ROOM AS SPECIFIED
ELSEWHERE IN THIS DESIGN PACKAGE.
ALL HORIZONTAL UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.
TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.
FACEPLATE MATERIAL AND COLOR DETERMINED BY OTHERS.
THIS SHEET DETAILS A GENERIC FACEPLATE SPECIFICATION.
NOTES:
ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING ON WHITE
FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON ADMINISTRATION MAY BE
SPECIFIED IN OTHER SECTIONS OF THIS DESIGN PACKAGE.
TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA
OUTLET CONFIGURATION2
STANDARD DENSITY WALL MOUNTED WORK AREA OUTLET
CONFIGURATION1
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS.
SINGLE GANG
WORKBOX WITH ONE
CONNECTOR CHASSIS.
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
TWO CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE MOUNTED
ON SINGLE GANG WORKBOX.
FACEPLATE COLOR SPECIFIED BY
OTHERS.
MINIMUM OF FOUR
CATEGORY 6A 8P8C
OUTLETS FOR DATA OR
TELEPHONY
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 12 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK POWER
DISTRIBUTION
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
NOTIONAL POWER SCHEMATIC FOR INFORMATION ONLY – NOT FOR CONSTRUCTION
TYPICAL ZONE PDU UNIT WITH REAR DETAIL AND ADAPTORS REQUIRED FOR VERTICAL PDU5
APC AP7900 RACK PDU, SWITCHED, 1U, 15A, 100/120V, (8)5-15 APC
SWITCHED RACK PDU , INPUT: 120V (OR EQUIVALENT)
30 Amp 3-Phase PDU BASE UNIT – FRONT
(ZONIT ZON-C-ZPDU1)
REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS
WITH L21-30R RECEPTACLES
(OR EQUIVALENT)
30 Amp 3-Phase PDU BASE UNIT – REAR
FOUR (4) L21-20R
SIX (6) NEMA 5-15/20 T-SLOT
(OR EQUIVALENT)
110 Volt PDU FOR PLACEMENT AS NEEDED4
PDU INPUTS REQUIRE
TWO L21-30Rs
POWER SCHEMATIC FOR POWER RACK- LEVEL REDUNDANCY1
THE CORRECT SPECIFICATION FOR THE PDU IS TO FEED IT WITH A TWO POWER SOURCES. POWER INPUTS SHOULD ORIGINATE FROM TWO INDEPENDENT POWER SOURCES. EACH INPUT WILL USE IDENTICAL SPECS:
WYE (5-WIRE) CONFIGURED, 208V, 30A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.
NOTE:
ONE ZONE PDU FOR TWO
SERVER CABINETS/
NETWORK RACKS
NOTE:
THIS DESIGN PROVIDES DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT BY SPLITTING THE
SOURCE POWER ACROSS TWO INPUTS ON THE ZONE PDU. EACH INPUT WILL SUPPORT TWO
EQUIPMENT-FACING PDUs. EACH SERVER CABINET WILL CONTAIN A MINIMUM OF TWO EQUIPMENT- FACING PDUs – EACH WILL BE ENERGIZED BY SEPARATE ZONE PDU INPUTS.
208 VOLT PDU FOR EQUIPMENT POWER – TO BE ENERGIZED BY ZONE
PDU3
REQUIRES ONE (1) L21-
20R
20A 120/ 208V
Y
DUAL 3-PHASE 480 VOLT INPUTS
(WITH 480 – 208
TRANSFORMER)
BUS OR FEEDER
3-PHASE 208-VOLT 30-AMP PDU
PDU PDU
COMPUTER
ZONE PDU
“ZERO U” VERTICAL PDU
DUAL POWER SUPPLY
DUAL INPUT UPS 250-500 kVA
UPS RACK MOUNT UPS
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
APC AP8861 RPDU OR EQUIVALENT; RACK PDU 2G, METERED; L21-20 PLUG;
THREE PHASE; 120/208V INPUT; 20A; ZERO U,
5.7 KW, 208V, (36) C13 & (6) C19 & (2) 5-20 OUTLETS; FOR USE IN
TELECOMMUNCIATION ROOMS AND LOCATIONS WITH LEGACY 110V ONLY
EQUIPMENT
RACK/ENCLOSURE
ZONE PDU
RACK/ENCLOSURE
PDU
B
PDU
A
BUS A BUS B
RACKED
EQUIPMENT
PS1 PS2
RACKED
EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACK-MOUNT
UPS
RACK-MOUNT
UPS
LEG2LEG1
Rack
PDU
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 13 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
POWER DISTRIBUTION
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
POWER SCHEMATIC RACKS – REAR VIEW1
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
RACK/ENCLOSURE
ZONE PDU
RACK/ENCLOSURE
L21-30P SIDE A
REQUIRES A 208V, 30A, THREE-PHASE CIRCUIT,
TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE.
L21-30P SIDE B
REQUIRES A 208V, 30A, THREE-PHASE CIRCUIT, TERMINATING
IN A NEMA L21-30R LOCKING RECEPTACLE.
PDU
B
PDU
A
BUS A BUS B
RACKED EQUIPMENT
PS1 PS2
RACKED EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACK-MOUNT UPS RACK-MOUNT UPS
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B L EG 1
L EG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B L EG 1
L EG 2
ZONE PDU
30A 3-PHASE ZONE PDU BASE UNIT – REQUIRES
TWO 30A 3-PHASE (WYE) CIRCUITS WITH L21-30R
RECEPTACLES
LEG2LEG1
RACK-MOUNTED 5 KW, 208V UNINTERRUPTIBLE POWER
SUPPLY (UPS) WITH NEMA 20A L21-20P INPUT AND L21-
20R OUTPUT
ZONE PDU
30A 3-PHASE ZONE PDU BASE UNIT – REQUIRES
TWO 30A 3-PHASE (WYE) CIRCUITS WITH L21-30R
RECEPTACLES
R ac k P
D U
R ac k P
D U
R ac k P
D U
R ac k P
D U
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 14 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
BONDING
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
12"
4"
ANSI/EIA/TIA COMPLIANT BUSBAR
CHATSWORTH P/N: 40158-012 OR
EQUIVALENT
ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND
IN COMPLIANCE WITH LOCAL CODES.
ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.
3 TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB)
NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR OR OPERATE
THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND CONDUCTOR. THESE DEVICES WILL BE BONDED TO THE RACK BONDING BUSBAR (RBB) IN THE SAME RACK. EACH DEVICE WILL
HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT BE SHARED.
RACK BONDING CONDUCTOR
(RBC) - 6 AWG
TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR (TEBC) – 6 AWG
INDIVIDUAL EQUIPMENT BONDING
CONDUCTORS FROM EACH PIECE OF
EQUIPMENT AND RACK TO THE RACK
BONDING CONDUCTOR
RACK BONDING CONDUCTOR (RBC)
EXTENDED TO BOTTOM OF RACK TO
ACCOMMODATE FUTURE GROWTH
RACK ISOLATION PADS (IF
APPLICABLE)
SERVER
CABINET
NETWORK
RACK
TO PBB/
SBB
TO PBB/SBB
PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS
EARTHING EXAMPLE (CISCO 6509/9606)
Ref: CISCO PRODUCT INSTALLATION GUIDE
NOTES:
O I
O I
Catalyst 9600 Series
RFID
C9606R
C9606-FAN
RFID
O I
O I
C9600-SUP-1
SS
SS
Catalyst 9600 Series Supervisor Module
C9600-SUP-1
SS
SS
Catalyst 9600 Series Supervisor Module
C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
C9600-LC-24CCatalyst 9600 Series Ethernet Switching Module
17 18 19 20 21 22 23 249 10 11 12 13 14 15 161 2 3 4 5 6 7 8
C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
C9600-LC-48YLCatalyst 9600 Series Ethernet Switching Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
TWO-HOLE
COMPRESSI
ON LUG
UBC
SYSTEM
GROUND
LOCATION
CISCO 9606CISCO 6509
SYSTEM GROUND
LOCATION
TWO-HOLE
COMPRESSION LUG
GROUNDING PAD
UBC
SCREWS
(M4)
TWO-HOLE COMPRESSION LUGS (RACKS
SHALL NOT BE MODIFIED IF ONLY ONE-
HOLE IS PROVIDED; USE ONE-HOLE
COMPRESSION LUGS IN THIS CASE)
TOP-MOUNTED RACK BONDING BUSBAR
(RBB)
UNIT BONDING CONDUCTOR
(UBC) - 6 AWG
GROUNDING TERMINAL
(TYPICAL EACH PIECE OF
EQUIPMENT)
IRREVERSIBLE CRIMP CONNECTOR
TELECOMMUNICATIONS EQUIPMENT
BONDING CONDUCTOR (TEBC) – 6 AWG
RACK BONDING CONDUCTOR
(RBC) - 6 AWG
IRREVERSIBLE CRIMP CONNECTOR
IRREVERSIBLE CRIMP
CONNECTOR
CABLE TRAY BONDING
CONDUCTOR. TYPICAL AT
EACH SECTION CONNECTION
POINT
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) –
6 AWG
SCREWS
(M4)
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 15 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
CBOC ITS NAMING STANDARDS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
• RACK = RK1 THROUGH RK4. LABELED LEFT TO RIGHT WHEN LOOKING AT THE FRONT OF THE RACK. APPLIES TO RACKS AND CABINETS.
• UTP PATCH PANEL = CPL-RACK NAME-01 THROUGH 45. EXAMPLE: CPL-RK1-01 FOR THE PANEL LOCATED IN RACK UNIT #1 IN RACK #1.
• UTP PATCH PANEL POSITION = PANEL ID.01 THROUGH 24. EXAMPLE CPL-RK1-01.01
• FIBER DISTRIBUTION PANEL = FDP-RACK NAME-01 THROUGH 45. EXAMPLE: FDP-RK1-01 FOR THE PANEL IN RACK UNIT #1 RACK #1.
• FIBER DISTRIBUTION CASSETTE = FDC-RACK NAME-01 THROUGH 45.1 THROUGH 3. EXAMPLE: FDC-RK1-01.1 FOR THE CASSETTE IN POSITION #1 IN
PANEL LOCATED IN RACK UNIT #1 IN RACK #1.
• UTP PATCH CORDS = CCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE CCA[CPL-RK1-01.01]/[CPL-RK2-02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE COPPER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.
• FIBER PATCH CORDS = FCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE FCA[FDP-RK1-01.01.01]/[FDP-RK2-02.02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE FIBER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.
• FACEPLATE = TR ROOM NUMBER-PATCH PANEL ID.PORT. EXAMPLE. 1A-CPL-RK1-01.1 FOR TELECOMMUNICATIONS ROOM 1, UTP PANEL IN RACK #1, RACK UNIT #1, PORT POSITION #1.
EXAMPLE INSIDE PLANT ADMINISTRATION1
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 16 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (TOP VIEW)
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
RBB
TYPICAL TOP-DOWN VIEW
NTS
CONDUIT OR SLEEVES WITH BUSHING AND
FIRESTOP FOR HORIZONTAL DISTRIBUTION
AS NEEDED
TYPICAL WALL-
MOUNTED CABINET
W
T
A/C GRADE ¾ TRADE SIZE PLYWOOD BACKBOARD.
PAINTED WITH TWO COATS OF FIRE RESISTANT BRIGHT
HIGH-GLOSS WHITE PAINT.
MULTIPLE DEDICATED 20-A, 120 VAC SINGLE
PHASE CIRCUIT DUPLEX OUTLET TO
NEAREST AVAILABLE POWER PANEL
PBB
ELECTRONIC EQUIPMENT BONDED TO RBB; RBB
BONDED TO TEBC; TEBC BONDED TO PBB ALL
USING A MINIMUM OF 6 AWG
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 17 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (ELEVATION VIEW)
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
PRESS
T O
RESET
PRESS
T O
RESET
Smart-UPS 3000
Esc
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
MODE CONSOLE
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
ST AT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G 3 G 4
NETWORK MO DULE
TE3 TE4TE1 TE2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
LINK
LINK
LINK
LINK CLASS 1
LASER
ASR 1001
AUXCONMGMT
LINKUSB
BF
MAJ
MIN
CRIT
STAT
PWR
STA
TU
S
S P
A -5
X 1G
E -V
A/L
A/L
A/L
A/L
A/L
RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15
OUTPUT. 1 RU. TWO PER ENCLOSURE. ONE
ENERGIZED BY UPS. ONE ENERGIZED BY WALL
OUTLET.
RESERVED FOR SERVICE
PROVIDER, DVRs, AND
OTHER
TELECOMMUNICATIONS
EQUIPMENT.
LOCKING 110 VOLT 20 AMP OUTLETS. ONE OUTLET ASSIGNED
TO PDU. ONE OUTLET ASSIGNED TO UPS. EACH ENERGIZED BY
SEPARATE ONE-POLE 20 AMP BREAKERS.
VA ROUTER
PATCH PANELS TO WORK
AREAS
ANALOG TELEPHONY
PATCH PANEL (IF
REQUIRED)
FIBER PATCH PANEL FOR
INCOMING CIRCUITS
1 RU CABLE MANAGER
VA LAN SWITCH
SHELF FOR NON-RACKMOUNT EQUIPMENT
1 RU CABLE MANAGER
HOOK AND LOOP STRAPS
EVERY 12 INCHES.
CABLE TO WORKSTATIONS
CABLE FROM SP AND
CABLE TO OTHER CAMPUS
BUILDINGS
QUAD OUTLET (5-20) FOR
BACKBOARD MOUNTED
EQUIPMENT
QUAD OUTLET (5-20) FOR
BACKBOARD MOUNTED
EQUIPMENT
4 FOOT BY 8 FOOT ¾ INCH PLYWOOD BACKBOARD.
A/C GRADE. PAINTED WHITE WITH FIRE RESISTANT
PAINT IF PERMITTED BY AHJ
ELEVATION FOR TELECOMMUNICATIONS ENCLOSURE
CUBE-iT Wall-Mount Cabinet;
Gen 3; 48"H x 24"W x 30"D (1220 mm x 610 mm x 760 mm); 26U; #12-24 Tapped Rails; Tempered Glass Door;
Glacier White or Equivalent
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
MODE CONSOLE
37X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
ST AT
SYST
SPEED
XPS
STACK
S-PWR
C3850-NM-4-10G
G1 G2 G 3 G 4
NETWORK MO DULE
TE3 TE4TE1 TE2
VA LAN SWITCH
PATCH PANELS TO WORK
AREAS (MAX 96
POSITIONS)
TELECOMMUNICATIONS
BONDING BUSBAR
RACK MOUNT UPS. L5-20
INPUT. L5-20 OUTPUT.
CAPACITY NTE 1920 VA. 2
RU. METERED
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 18 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (ELEVATION)
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
TELECOMMUNICATIONS
BONDING BUSBAR (PBB)
BONDING CONDUCTOR TO
PANEL BOARD GROUND
LUG
RACK BONDING BUSBAR
(RBB)
BOND RBB TO CABINET BONDING LUG. AWG #6
BOND RBB TO PBB.
AWG #6
S-PW R 1
XPS
S-PW R 2
RESET
CONSOLE SERIAL MGMT
AC OK PS OK PWR-C1 -1100WAC AC OK PS OK PWR-C1-1100 WAC
BOND RBB TO EACH SWITCH AND ROUTER
CHASSIS
USE TWO-HOLE LUGS FOR
BONDING CONNECTOR
1 BONDING TOPOLOGY FOR TELECOMMUNICATIONS ENCLOSURES
Department of Veterans Affairs
IT Operations and Services Solution Delivery
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v1_1.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: Jul 8, 2021
ISSUE DATE: Jul 8, 2021
SHEET: 19 OF 19
1.1
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE SPECIFICATIONS
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
REAR HINGE AND PANEL2
10 SPECIFICATIONS
VERTICAL CABLE MANAGEMENT. TWO KITS FOR PRIMARY. ONE KIT FOR
SECONDARY.
FAN FILTER KIT AND LIGHT KIT (ONE PER
CABINET).
5 BRUSH KIT (ONE PER CABINET)
8 FAN KIT QTY 1 PER CABINET
9 FRONT AND REAR RAIL KIT
SPECIFICATIONS
DESCRIPTION:
Wall-mount enclosure with lockable front door and swing-out rear access to equipment. Tempered glass front door.
PRIMARY:
CUBE-iT Wall-Mount Cabinet; Gen 3; 48"H x 24"W x 30"D (1220 mm x 610 mm x 760 mm); 26U; #12-24 Tapped Rails; Tempered Glass Door; Glacier White. 12419- E48 CUBE-It or Equivalent
SECONDARY:
CUBE-iT Wall-Mount Cabinet; Gen 3; 24"H x 24"W x 30"D (610 mm x 610 mm x 760 mm); 12U; #12-24 Tapped Rails; Tempered Glass Door; Black. 12419-724 or Equivalent.
USE:
For indoor use only, in environmentally controlled areas; may not be used outdoors, in harsh environments, or in air-handling spaces
SIZE:
• Height: 48" (1220 mm)
• Width: 24" (610 mm); 19" EIA rack-mount
• Depth: 30" (760 mm)
INTERIOR:
• Height: 26U
• Width: 19" EIA rack-mount
• Threaded #12-24 equipment mounting holes
• 19"W, EIA-310-D compliant
• Fan assemblies with filter kits
• For use with small equipment such as modems, routers and fiber modules in 19” EIA racks
• 1U; Includes multiples tie-down points
• Supports up to 20 lb (9.1 kg) of equipment
SHELF (TWO PER CABINET)
REQUIRED GROUND JUMPERS1
6 POWER STRIP (TWO PER CABINET)