RDM Org
| ROOM DATA MATRIX | INTERIOR CONSTRUCTION | DOORS AND HARDWARE | MECHANICAL | ELECTRICAL | |||||||||||||||||||||||||||||||||||||||||||||
| ROOM IDENTIFICATION | ALTERNATE ROOM CODES | FLOOR | WALLS | CEILING | NOTES | Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. | POWER | ||||||||||||||||||||||||||||||||||||||||||
| RDM ROW NO. | DEPARTMENT | PRIMARY ROOM CODE | ROOM NAMES (VA) | ALTERNATE ROOM CODES (VA) | ALT ROOM CODE - 01 | ALT ROOM CODE - 02 | ALT ROOM CODE - 03 | ALT ROOM CODE - 04 | ALT ROOM CODE - 05 | ALT ROOM CODE - 06 | ALT ROOM CODE - 07 | ALT ROOM CODE - 08 | ALT ROOM CODE - 09 | ALT ROOM CODE - 10 | ALT ROOM CODE - 11 | ALT ROOM CODE - 12 | ALT ROOM CODE - 13 | ALT ROOM CODE - 14 | ROOM NAME | FGI EQUIVALENT FOR ASHRAE 170 | FGI EQUIVALENT FOR TABLE 1.2-6 | Floor Finish | Base | Wall Finish | Wainscot Material | Wainscot Height | STC | Ceiling Finish | Height | Notes | Size (Width) | Type | Material | Glazing | Rating | Hardware Group | Hardware Notes | Indoor Temperature | |||||||||||
| Cooling F | Indoor Temperature | ||||||||||||||||||||||||||||||||||||||||||||||||
| Heating F | Indoor Relative Humidity | ||||||||||||||||||||||||||||||||||||||||||||||||
| % RH Max | Indoor Relative Humidity | ||||||||||||||||||||||||||||||||||||||||||||||||
| % RH Min | Minimum Total ACH | Minimum OA ACH | Room Air Return | ||||||||||||||||||||||||||||||||||||||||||||||
| Gen. Exh G Spec Exh S | Maximum Noise | ||||||||||||||||||||||||||||||||||||||||||||||||
| Level NC | Room Air Balance | HVAC Notes | # Duplex Receptacles | # Quad Receptacles | # GFCI Receptacles | # USB Receptacles | Normal Power | Emergency Power | Power - Special Requirements (Radiology Equipment, Lift, etc.) | Power - Notes | Fixture Type | Controls | Normal Power3 | Emergency Power4 | Lighting - Special Requirements | Lighting - Notes | # Data Outlets | # Phone Outlets | # Wall Phone Outlets | IT - | |||||||||||||||||||||||||||||
| Special Requirements | Duress Alarm | Nurse Call | Video Teleconferencing | Motion Intrusion Detection | Electronic Access and Door Control | Security Surveillance TV | Audio/Visual Device Ceiling, Center of Tile | ||||||||||||||||||||||||||||||||||||||||||
| 1 | Audiology and SLP | AUD01 | Audiology Rehabilitation / Counseling Room | EXOS1 | EXOS1 | AUDIOLOGY REHABILITATION / COUNSELING ROOM | CONSULTATION | CPT, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 15 S | _ | 75 | 70 | 60 | - | 4 | 2 | Return | 40 | NR | 5 | ||||||||||||||||
| dimming/occupancy | Y | N | N/A | N/A | 3 | 1 | Y | Staff emergency station where required | Y | Y | |||||||||||||||||||||||||||||||||||||||
| 2 | Audiology and SLP | HATL1 | Hearing Aid Testing Lab/ Shop | AUDIOLOGY HEARING AID TESTING | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-0" | Flush | Wood | _ | _ | 15 S | _ | 75 | 70 | 60 | - | Exh. (G) | (-) | 6 | 0 | ||||||||||||||||||||
| 3 | Audiology and SLP | AUD03 | Audiology Programming / Fitting, Hearing Aid Fitting Room | HAFR1 | HAFR1 | AUDIOLOGY HEARING AID FITTING | EXAM | EXAMINATION | CPT | RB | P | -- | -- | 60 | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 5 | ||||||||||||||||||||||||
| 4 | Audiology and SLP | AUDE1 | Audiometric Exam Suite, Exam - Audiometric Booth, Aud: Suite - Audiometric Exam, Hearing/Diagnostics, Booth, 1-Person | PEHS3, PEHS4, EXAU1 | PEHS3 | PEHS4 | EXAU1 | PEHS1 | AUDIOMETRIC EXAM BOOTH | EXAM | EXAMINATION | Pre-Fab | Pre-Fab | Pre-Fab | -- | -- | SEE EQUIP LIST | Pre-Fab | 8'-0" | -- | 3'-0" |
| 3'-6" | Pre-Fab | Pre-Fab | _ | _ | 1 | 2,3,4 | 9 | Y | N | N/A | P1 | 2 X 2 recessed lensed or self-contained indirect | Typically pre-packaged unit including lighting and switching | Y | N | N/A | L1 | 5 | 1 | Y | Staff emergency station where required | Yes control side | Y | ||||||||||||||||||||||||||
| 5 | Audiology and SLP | AUDP1 | Electrophysiology | OPAE1, OPAE2 | ELECTROPHYSIOLOGY | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 15 S | _ | 5 | 1 | Y | N | N/A | P2 | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | ||||||||||||||||
| 6 | Audiology and SLP | AUDP3 | Vestibulography | EXVE1 | VESTIBULOGRAPHY | TREATMENT | TREATMENT | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 15 S | _ | 8 | 1 | Y | N | Floor duplex for table | P3 | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | ||||||||||||||||
| 7 | General | CFR01 | Conference Room, Group Room, Conference Room (VTEL and TELEHEALTH Ready), Training - Educational - Conference Room, Conference Room/Placement and Examination Room | CRA01, CRA02, CRA03, CFR03, CLR08, CFR02 | CRA01 | CRA02 | CRA03 | CFR02 | CFR03 | CFR08 | CONFERENCE ROOM | __ | CPT | RB | P | RWC | 4'-0" | 40 | AT | 9'-0" | 17 | 3'-6" | Flush | Wood | _ | _ | 15 S | _ | M2 | 8 | 2 | Y | N | Floor duplex for table | 2 X 2 recessed lensed or self-contained indirect/downlights/pendant/accent | Multilevel switching/dimming/occupancy | Y | N | |||||||||||
| 8 | Primary Care, Specialty Care, PACT | EXPA1 | Exam PACT, Exam Room - Multi-Specialty, Exam / Treatment, Exam - Consult, Consult Room - PACT, Exam/Consult Room (Mental Health/Social Work), Exam Room EMG/EEG, Exam Room-Cardiology, Exam/Consult, Nurse Practitioner | EXBH1, EXEB1, EXPA1, EXRG0, EXRG3, EXRG4, EXP01, EXRG1, EXR10, EXRE2, EXRC1, EXR10 | EXBH1 | EXEB1 | EXPA1 | EXRG0 | EXRG3 | EXRG4 | EXP01 | EXRG1 | EXR10 | EXRE2 | EXRC1 | EXRC10 | EXAM ROOM | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 10 | 3'-0" |
| 3'-6" | Flush | Wood | _ | _ | 12 S | 3 | 7 | 1 | 1 | Y | N | Overhead lift | 2 X 4 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Multi-level switching or manual dimming | N/A | 3 | 1 | Y | Staff emergency station where required | Y | ||
| 9 | Primary Care, Specialty Care, PACT | EXW01 | Exam, Womens Health | EXAM, WOMENS HEALTH | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 10 | 3'-0" |
| 3'-6" | Flush | Wood | _ | _ | 12 S | 3 | 2 | 1 | 1 | Y | N | Overhead lift | 2 X 4 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Multi-level switching or manual dimming | N/A | 1 | 1 | Y | Staff emergency station where required | Y | ||||||||||||||||||||||||||
| 10 | Pathology and Laboratory Medicine | LBGM1 | Lab, General OP Clinic | LAB, GENERAL OP CLINIC | LABORATORY WORK AREA, GENERAL | __ | WSF | WSF | EP | -- | -- | 40 | AT-SP | 9'-0" | 3 | 3'-0" | Flush | Wood | _ | _ | 15 AG | 4 | 5 | 1 | Y | Y Refrigerator receptacles | N/A | P4 | |||||||||||||||||||||
| 11 | Primary Care, Specialty Care, PACT | LBVP1 | Blood Specimen Collection, Alcove - Specimen Collection Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory-Venipuncture | RCA07, LBBD1, RCA97, LBSP1, LBBD2 | RCA07 | LBBD1 | RCA97 | LBSP1 | LBBD2 | SPECIMEN COLLECTION | TREATMENT | __ | WSF | WSF | EP | -- | -- | 40 | AT/GWB-PT | 9'-0" | 3 | -- | _ | _ | _ | _ | _ | 6 | 4 | Y | Y Refrigerator receptacles | N/A | |||||||||||||||||
| 12 | General Rooms/Spaces | OFDC1 | Consult, Consultation Room, Consultation Room - Homeless Outreach, Consultation Room - Pharmacy, Consult - Mental Health | CLCEX, OFDC2, CMP01 | CLCEX | OFDC2 | CMP01 | CONSULT | CONSULTATION | CPT, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 75 | 70 | 60 | - | 4 | 2 | Return | 40 | NR | 5 | 1 | Y | N | N/A | ||||||||||
| 13 | Optometry | OPET2 | Exam/Treatment Optometry | EYOT2 | EYOT2 | EXAM/TREATMENT OPTOMETRY | TREATMENT | TREATMENT | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 5 | Y | N | N/A | |||||||||||||||||||||
| 14 | Optometry | OPFD1 | Fitting & Dispensing, Eyeglasses | EYFD1 | EYFD1 | FITTING & DISPENSING, EYEGLASSES | -- | CPT, RSF or RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | -- | -- | -- | -- | -- | -- | 6 | 75 | 70 | 60 | - | 4 | 2 | Return | 40 | NR | 1 | 1 | Y | N | N/A | ||||||||||||
| 15 | Optometry | OPLV2 | Low Vision Exam/ Therapy/ Training | EYOT4 | EYOT4 | LOW VISION EXAM/ THERAPY/ TRAINING | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 5 | 1 | Y | N | N/A | ||||||||||||||||||||
| 16 | Optometry | OPPT2 | Pre-Testing/ Intake | PRE-TESTING/ INTAKE | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 5 | 1 | 1 | Y | N | N/A | |||||||||||||||||||||
| 17 | Optometry | OPVF2 | Visual Fields Room, Visual Fields Room (OCT, VF Machine) | EYVF1 | EYVF1 | VISUAL FIELDS ROOM | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 6 | 1 | Y | N | N/A | ||||||||||||||||||||
| 18 | Primary Care, Specialty Care, PACT | WRTM1 | PACT Team Work Space, Team Work Area- Home Based Primary Care | WKTM3, NSTA1, WRCH1 | WKTM3 | NSTA1 | WRCH1 | PACT TEAM WORK SPACE | -- | CPT, RSF or RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | -- | _ | _ | _ | _ | _ | _ | 6 | M3 | 9 | 9 | Y | N | |||||||||||||||||||
| 19 | Primary Care, Specialty Care, PACT | PEHW2 | Scale Alcove - Accessible | SCALE ALCOVE | PATIENT CORRIDOR | -- | RF, RFT, or RSF | RF or RB | P | RWC | 4'-0" | -- | AT | 9'-0" | 6 | _ | _ | _ | _ | _ | _ | 6 | 1 | Y | N | N/A | |||||||||||||||||||||||
| 20 | Pharmacy Service | PHOD5 | Pharmacy, Pharmacy, PACT 3 (Controlled Substance) (w/3 AutoDispensing) | PHOD6 | PHOD6 | PHARMACY | PHARMACY | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | -- | 6'-0" | Flush | Metal | - | - | 200 AS | 7 | 14 | 1 | Y | Y Refrigerator receptacles | N/A | P5 | |||||||||||||||||||
| 21 | Pharmacy Service | PHOW1 | Dispense/Consult Window, Workroom, Pharmacist | PHOW2 | PHOW2 | PHARMACY DISPENSING WINDOW | PHARMACY | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | -- | - | - | - | - | - | - | OPEN | 11 | 1 | Y | N | N/A | ||||||||||||||||||||
| 22 | Primary Care, Specialty Care, PACT | RCA06 | Medication Alcove, Medication Room | MEDICATION ALCOVE | MEDICATION ROOM | -- | RFT or RSF | RB | P | RWC | 5'-0" | -- | AT | 9'-0" | _ | _ | _ | _ | _ | _ | -- | 6 | 2 | 1 | Y | Y Refrigerator receptacles | N/A | ||||||||||||||||||||||
| 23 | General Rooms/Spaces | RCP01 | Reception, Information Desk, Travel Window, Reception - Accessible | RECP5, RECP3, RECP1, RCP03, RCP02 | RECP5 | RECP3 | RECP1 | RCP03 | RCP02 | RECEPTION | -- | CPT, RSF or RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" |
| 3'-0" | Flush w/ narrow vision | Wood | _ | _ | 12 CG | 3 | M4 | 11 | 4 | Y | N | Power feeds to systems furniture | Downlights, pendants, decorative, and accent | Multilevel switching/dimming/occupancy/daylighting control | Y | Y - minimal | N/A | N/A | 10 | 5 | Data/phone feeds to systems furniture | Y | Y | ||||||||||||||||||||||||||
| 24 | General Rooms/Spaces | RPR01 | Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room | RPR03, MRWK1, SACS1, SACP1 | RPR03 | MRWK1 | SACS1 | SACP1 | COPY ALCOVE | PATIENT CORRIDOR | -- | CPT, RSF or RFT | RB | P | -- | -- | -- | AT | 9'-0" | 6 | _ | _ | _ | _ | _ | _ | 6 | 3 | Y | N | N/A | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy/daylighting control | Y | N | N/A | |||||||||||||
| 25 | Audiology and SLP | SPL01 | Office/ Treatment Speech-Language Pathology | OFFICE/ TREATMENT SPEECH-LANGUAGE PATHOLOGY | EXAM | EXAMINATION | CPT, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | 4 | 4 | 1 | Y | N | N/A | P5 | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | ||||||||||||||||
| 26 | General Rooms/Spaces | TLTU1 | General Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family Assist | TNPG1, TLTF2, TLTF3, TLTM2, TLTF1, TNPM2, TLTB1, TPG01, TNPFM, TPB01, TNPM3, TNPF3, TLTM1 | TNPG1 | TLTF2 | TLTF3 | TLTM2 | TLTF1 | TNPM2 | TLTB1 | TPG01 | TNPFM | TPB01 | TNPM3 | TNPF3 | TLTM1 | TOILET | TOILET ROOM | TOILET ROOM | PT | PT | P | CT | 7'-0" | SEE FGI | AT | 9'-0" | 1,2 | 3'-6" | Flush | Wood | _ | _ | 11 | _ | 1 | Y | N | N/A | Downlights/Mirror or vanity | Vacancy sensor | Y | N | N/A | ||||
| 27 | Pathology and Laboratory Medicine | TPSP1 | Toilet, Specimen | TOILET, SPECIMEN | TOILET ROOM | TOILET ROOM | PT | PT | P | CT | 7'-0" | SEE FGI | AT | 9'-0" | 1,2 | 3'-6" | Flush | Wood | -- | -- | 11 | _ | 1 | Y | N | Water valve shut-off switch on lab side of pass-thru wall | Downlights/Mirror or vanity | Vacancy sensor | Y | N | N/A | ||||||||||||||||||
| 28 | General Rooms/Spaces | TRPR1 | Procedure, General | PROCEDURE, GENERAL | TREATMENT | TREATMENT | WSF | WSF | EP | RWC | 4'-0" | SEE FGI | AT | 9'-0" | 3 | 3'-0" |
| 3'-6" | Flush | Wood | -- | -- | 12 S | 3 | 5 | 2 | Y | N | Overhead lift | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Wall mounted exam light | N/A | 2 | 1 | Y | Staff emergency station where required | Y | |||||||||||||||||||||||||||
| 29 | General Rooms/Spaces | UCCL1 | Clean Utility | CSUC1, LCCL3, LCCL1, CSUC4, CLHS1 | CSUC1 | LCCL3 | LCCL1 | CSUC4 | CLHS1 | CLEAN UTILITY | CLEAN LINEN STORAGE | -- | RFT | RB | P | RWC | 4'-0" | 40 | AT | 8'-0" | -- | 3'-0" | Flush | Wood | -- | 45 MIN | 121 AG | _ | 1 | Y | N | ||||||||||||||||||
| 30 | General Rooms/Spaces | USCL1 | Soiled Holding | SPSU1, BSTC1, LCSL1 | SPSU1 | BSTC1 | LCSL1 | SOILED HOLDING | SOILED HOLDING | -- | WSF | WSF | P | RWC | 4'-0" | 40 | AT | 8'-0" | 3 | 3'-0" | Flush | Wood | -- | 45 MIN | 121 AG | _ | 2 | 1 | Y | N | |||||||||||||||||||
| 31 | Primary Care, Specialty Care, PACT | WRTM2 | Tele-Health, Exam-Telehealth | EXTH1 | EXTH1 | TELE-HEALTH | EXAM | EXAMINATION | CPT, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 G | _ | 5 | 1 | 1 | Y | N | ||||||||||||||||||||
| 32 | Optometry | WRTM3 | Tele-Retinal | TELE-RETINAL | EXAM | EXAMINATION | CPT, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 17 AG | -- | 5 | 1 | 1 | Y | N | ||||||||||||||||||||||
| 33 | Imaging Services | XDR01 | Radiology, ES: General Purpose Radiology Room | RADIOLOGY | X-RAY (D&T) | TREATMENT | WSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 4'-0" | Flush | Wood | -- | LEAD LINED | 15 LS | 8 | 5 | Y | N | ||||||||||||||||||||||||
| 34 | Imaging Services | XDUS1 | Ultrasound | ULTRASOUND | EXAM | EXAMINATION | WSF, RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 15 S | -- | 5 | 1 | Y | N | |||||||||||||||||||||||
| 35 | General Rooms/Spaces | JANC1 | Housekeeping Aides Closet (HAC) | BSHC1, BGSH1, JANC2 | BSHC1 | BGSH1 | JANC2 | JANITOR'S CLOSET | JANITOR'S CLOSET | -- | CS | RB | P | FRP | 4'-0" | -- | AT | 8'-0" | 3'-0" | Flush | Wood | -- | -- | 14 | _ | -- | -- | 1 | -- | Y | N | ||||||||||||||||||
| 36 | General Rooms/Spaces | USCL1 | Utility Room, Soiled, Utility Room - Recycled Material | CSUS2, CSUS1, UTC01 | CSUS2 | CSUS1 | UTC01 | SOILED UTILITY | SOILED WORK | -- | WSF | WSF | P | RWC | 4'-0" | 40 | AT | 8'-0" | 3 | 3'-0" | Flush | Wood | -- | 45 MIN | 121 AG | _ | -- | -- | 2 | -- | Y | N | |||||||||||||||||
| 37 | General Rooms/Spaces | DOCK1 | Receiving/ Shipping Dock | LOADING DOCK | -- | CS | RB | EP | -- | -- | -- | EXP. | -- | 8 | 6'-0" | Flush | Wood | -- | -- | 44 APW | 7 | - | 60 | - | - | Exh. (G) | (+) | M5 | -- | -- | 2 | -- | Y | N | |||||||||||||||
| 38 | General Rooms/Spaces | FSCD1 | Social Activities Space/ Kitchen | IPK01, FSNP1 | IPK01 | FSNP1 | KITCHENETTE | NOURISHMENT | -- | WSF or RSF | RB | P | -- | -- | -- | AT | 9'-0" | 17 | 3'-0" | Flush | Wood | -- | -- | 15 A | _ | 2 | -- | 2 | -- | Y | N | ||||||||||||||||||
| 39 | Logistics, Engineering | PMWS8 | General Mech. Shop, Workbench and Worktable | GEN. MECHANICAL SHOP | -- | CS | RB | P | -- | -- | -- | EXP. | -- | 4'-0" | Flush | Wood | -- | -- | 14 KS | _ | Exh. (G) | (-) | 8 | -- | 2 | -- | Y | N | |||||||||||||||||||||
| 40 | General Rooms/Spaces | RCA01 | Alcove, AED, Alcove - Resuscitation Cart | AED | PATIENT CORRIDOR | -- | RFT, RSF or WSF | RB or WSF | P | RWC | 4'-0" | -- | AT | 8'-0" | 3 | -- | -- | -- | -- | -- | - | 6 | 1 | -- | -- | -- | Y | N | |||||||||||||||||||||
| 41 | General Rooms/Spaces | RCA02 | Alcove, Portable Patient Lift | EQUIPMENT ALCOVE | PATIENT CORRIDOR | -- | RFT, RSF or WSF | RB or WSF | P | RWC | 4'-0" | -- | AT | 8'-0" | 3,6 | -- | -- | -- | -- | -- | - | 6 | 1 | -- | -- | -- | Y | N | |||||||||||||||||||||
| 42 | General Rooms/Spaces | SL001 | Staff Lounge | SSLG1, SSLG2, SSLG3 | SSLG1 | SSLG2 | SSLG3 | STAFF LOUNGE | -- | RSF/CPT or RSF | RB | P | -- | -- | 40 | AT | 9'-0" | 4 | 3'-0" | Flush | Wood | -- | -- | 200 | _ | Exh. (G) | (-) | 6 | -- | 2 | 4 | Y | N | ||||||||||||||||
| 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | 2 | 1 | -- | Y | Y | Y | ||||||||||||||||||||||||||||||||||||||
| 43 | Logistics, Engineering | SRR02 | Storage, Refrigerated | REF. STORAGE | -- | QT | QT | EP | -- | -- | -- | GWB:SC | 8'-0" | 14 | 3'-0" | Flush | Wood | -- | -- | 33 ABG | M6 | -- | -- | 1 | -- | Y | N | ||||||||||||||||||||||
| 44 | Logistics, Engineering | SRS04 | Storage Room, Sterile, Storage-Sterile Processing Supplies, Storage-Sterile Durables (Sterile Instruments) | SRSP1, SRS05 | SRSP1 | SRS05 | STERILE STORAGE | STERILE STORAGE | -- | WSF | WSF | P | RWC | 4'-0" | -- | AT-SP | 9'-0" | 3 | 3'-0" | Flush | Wood | -- | -- | 121 AG | 1 | -- | -- | -- | Y | N | |||||||||||||||||||
| 45 | Logistics, Engineering | UTLC1 | Utility, Trash and Linen Collection | LCSL2 | LCSL2 | TRASH/ LINEN COLLECTION | LINEN AND TRASH CHUTE ROOM | -- | WSF | WSF | P | RWC | 4'-0" | -- | AT-SP | 9'-0" | 3 | 3'-6" | Flush | Wood | -- | 45 MIN | 121 AG | -- | -- | 1 | -- | Y | N | ||||||||||||||||||||
| 46 | Police Service | POH01 | Holding Room | POLICE HOLDING ROOM | EXAM | -- | WSF | WSF | P | -- | -- | -- | GWB-PT | 9'-0" | 3,15 | 3'-6" | Flush | Hollow Metal | Half Glass w/ Laminated Glass | 18 P | -- | -- | -- | -- | NA | NA | |||||||||||||||||||||||
| 47 | Logistics, Engineering | BMER1 | Repair Shop, Biomedical Eng. | BIOMED. REPAIR SHOP | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 35 AG | Exh. (G) | (-) | M7 | 8 | -- | 2 | -- | Y | N | |||||||||||||||||||||
| 48 | General Rooms/Spaces | MEDP1 | Medication Room | CLHMD | CLHMD | MEDICATION ROOM | MEDICATION ROOM | -- | RFT or RSF | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 200 AS | 5 | -- | 1 | -- | Y | N | |||||||||||||||||||||
| 49 | OI&T | CMP02 | Telecommunications Room/ Closet, IT Telecommunications Room | TETR1, TEDR1 | TETR1 | TEDR1 | TELECOMM. | -- | RFT | RB | P | -- | -- | -- | EXP. | -- | 3'-0" | Flush | Wood | -- | -- | 200 AS | 75 | 70 | - | - | - | - | - | - | NR | 6 | -- | -- | -- | Y | N | ||||||||||||
| 50 | OI&T | COMC1 | Central Server Room | CMP03 | CMP03 | SERVER ROOM | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 200 S | M8 | 10 | -- | -- | -- | Y | Y | |||||||||||||||||||||
| 51 | Sterile Processing Service | CSSS2 | Central Sterile, Clean SPS Carts | DENTAL, STERILE CARTS | STERILE STORAGE | -- | WSF | WSF | P | RWC | 4'-0" | -- | AT-SP | 9'-0" | 3 | 3'-6" | Flush | Wood | -- | -- | 15 AS | 1 | -- | -- | -- | Y | N | ||||||||||||||||||||||
| 52 | Optometry | OPPH1 | Photography Room | EYVS1 | EYVS1 | PHOTO ROOM, EYE CLINIC | TREATMENT | RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | __ | __ | 12 CVS | Exh. (G) | (-) | 4 | -- | -- | -- | Y | N | ||||||||||||||||||||
| 53 | General Rooms/Spaces | FSCD5 | Canteen, Retail/ Dining/ Coffee Bar | CANTEEN | -- | CPT/RFT or RSF | RB | P | -- | -- | -- | AT | 9'-0" | 10,12,17 | 3'-0" | Flush | Wood | __ | __ | 96.01 S | (+) | M9 | 6 | -- | 2 | 4 | Y | N | |||||||||||||||||||||
| 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | -- | 4 | -- | Voice outlets for card swipes on Vending machines | Y | |||||||||||||||||||||||||||||||||||||||
| 54 | Food and Nutrition | FSTD1 | Food Preparation and Production | PRODUCTION KITCHEN | FOOD PREPARATION CENTER | -- | QT | QT | CT | -- | -- | -- | AT:SP | 9'-0" | 14,18 | 3'-0" | Flush | Wood | -- | -- | 13 AS |
Exh. (S)
| (-) | PER APPLIANCE plus convenience receptacles | -- | ALL | ||||||||||||||||||||||||||||||||||||||||||||||
| -- | Y | N | Device NEMA configuration to coordinate with equipment | P7 | |||||||||||||||||||||||||||||||||||||||||||||
| 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Sealed fixture, flat lens surface on exterior | N/A | 2 | 1 | -- | Y | ||||||||||||||||||||||||||||||||||||||||
| 55 | OI&T | ITWR1 | IT Workroom, Equip. Configuration/ Repair | I.T. WORKROOM | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 35 AG | 8 | -- | ||||||||||||||||||||||||||||
| Surface or chain mounted 1' x 4' | Occupancy/vacancy | Y | N | N/A | N/A | 8 | 4 | -- | Y | Y | |||||||||||||||||||||||||||||||||||||||
| 56 | General Rooms/Spaces | LAC01 | Employee Wellness, Lactation Room, Quiet Room | LACTATION ROOM | -- | RFT | RB | P | -- | -- | 50 | AT | 9'-0" | 10 | 3'-0" | Flush | Wood | -- | -- | 12 CS | 4 | -- | |||||||||||||||||||||||||||
| 57 | General Rooms/Spaces | LR001 | Locker Room, Locker Room (Male/ Female) Locker - Staff Personal Property, Locker Room - Staff | LR002, LR004, SSLK1 | LR002 | LR004 | SSLK1 | LOCKER ROOM | -- | CPT, RSF or RFT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 200 | Exh. (G) | (-) | 2 | -- | ||||||||||||||||||||||
| 58 | Dental Service | MECH1 | Dental Equipment Mech. Room, Mechanical Rooms - Electrical | SPECIALTY EQUIPMENT MECHANICAL ROOM | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 6'-0" | Flush | Wood | -- | -- | 44 S | Exh. (G) | (-) | -- | -- | ||||||||||||||||||||||||||
| 59 | Logistics, Engineering | MRRS1 | Support: Mail Room and Dist. Center, Mailing Room - Prosthetic Appliances | MRMB1, MRPA1 | MRMB1 | MRPA1 | MAIL ROOM | -- | RF | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 G | 4 | -- | |||||||||||||||||||||||||
| 60 | General Rooms/Spaces | OFA01 | Office, Behavioral Health - Testing, Office - Voluntary Service, Veteran Service Organization, Office - Radiology, Office-AFGE | AFA04, OPMH2, OFDR1, OFA09, OFA04, OFD01, OFC01, OFD02, OFA11 | AFA04 | OPMH2 | OFDR1 | OFA09 | OFA04 | OFD01 | OFC01 | OFD02 | OFA11 | OFFICE | CONSULTATION | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 CSV | 5 | -- | ||||||||||||||||||
| 61 | General Rooms/Spaces | OFA03 | Cubicle - Administrative, Data Processing, Workstation - Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical | WKTM4, OFA07, CLSC2, LBSS1, OFA08, SEC01, LR003, OFA10, PHWP1, OFA06, PHCC1 | WKTM4 | OFA07 | CLSC2 | LBSS1 | OFA08 | SEC01 | LR003 | OFA10 | PHWP1 | OFA06 | PHCC1 | OFFICE, CUBICLE | -- | CPT | RB | P | -- | -- | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 13 C | 4 | -- | ||||||||||||||||
| 62 | General Rooms/Spaces | OFA05 | Office - Shared - 2-Person | OFA02 | OFA02 | OFFICE, SHARED | -- | CPT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 12 CG | 6 | -- | ||||||||||||||||||||||||||
| 63 | Primary Care, Specialty Care, PACT | OPMH1 | Group Therapy Room - Mental Health | GROUP THERAPY ROOM | OCCUPATIONAL THERAPY | TREATMENT | RFT or CPT | RB | P | -- | -- | SEE FGI | GWB:P | 9'-0" | 10 | 3'-6" | Flush | Wood | -- | -- | 15 S | 8 | -- | ||||||||||||||||||||||||||
| 64 | Specialty Care Services | OPPF2 | Pulmonary Function - Analysis | PULMONARY FUNCTION ROOM | EXAM | TREATMENT | WSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 15 G | 5 | -- | |||||||||||||||||||||||||||
| 65 | Specialty Care Services | OPTM1 | Treadmill Room | OPPF5, OPPF1 | OPPF5 | OPPF1 | TREADMILL ROOM | PHYSICAL THERAPY | TREATMENT | RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 35 MS | 5 | -- | ||||||||||||||||||||||||
| 66 | Primary Care, Specialty Care, PACT | PEHW1 | Alcove - Height / Weight Station | EXR11 | EXR11 | ALCOVE, PHYSICAL EVALUATION | PATIENT CORRIDOR | -- | RFT, RSF or WSF | RB or WSF | P | RWC | 4'-0" | -- | AT | 8'-0" | 3,6 | -- | -- | -- | -- | -- | - | 6 | 1 | -- | |||||||||||||||||||||||
| 67 | Pharmacy Service | PHC01 | Pharmacy - Clean Room - Chemotherapy Compounding | CLEAN ROOM, COMPOUNDING | -- | RF | RF | P | -- | -- | -- | GWB:P | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | 68 | 68 | 60 | 20 | 30 | 2 | Exh. (S) | 55 | (-) | M12 | 12 | -- | |||||||||||||||||
| 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Sealed fixture, flat lens surface on exterior | N/A | 5 | 2 | -- | Y | Y | Y | Y | |||||||||||||||||||||||||||||||||||||
| 68 | Pharmacy Service | PHIV1 | Pharmacy - IV Admixture - Low Volume | LBSM1 | LBSM1 | IV ADMIXTURE | -- | RF | RF | P | -- | -- | -- | GWB:P | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | 68 | 68 | 60 | 20 | 30 | 2 | Return | 55 | (++) | M12 | 12 | -- | |||||||||||||||
| 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Sealed fixture, flat lens surface on exterior | N/A | 5 | 2 | -- | Y | Y | Y | Y | |||||||||||||||||||||||||||||||||||||
| 69 | Pharmacy Service | PHOD2 | Prescription Dispensing Area - OmniCell Station | PRESCRIPTION DISPENSING AREA | PHARMACY | -- | RF | RF | P | -- | -- | -- | AT | 9'-0" | 3 | -- | -- | -- | -- | -- | - | 6 | 6 | -- | |||||||||||||||||||||||||
| 70 | Specialty Care Services | PTEA1 | Treatment Exercise Area (includes workstations therapists) | PHYSICAL THERAPY GYM | PHYSICAL THERAPY | TREATMENT | RF | RB | P | -- | -- | SEE FGI | AT | 9'-0" MIN. | 3'-6" | Flush | Wood | -- | -- | 15 S | 12 | -- | |||||||||||||||||||||||||||
| 71 | Other | RAMR1 | Quiet Room for Patients | QUIET ROOM | EXAM | TREATMENT | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 35 S | 4 | -- | |||||||||||||||||||||||||||
| 72 | Food and Nutrition | RER01 | Storage - Refrigerated and Frozen Food | KITCHEN, REFRIGERATED AND FROZEN FOOD | DIETARY STORAGE | -- | QT | QT | P | -- | -- | -- | AT:SP | 9'-0" | 14 | 3'-0" | Flush | Wood | -- | -- | 15 GK | -- | -- | ||||||||||||||||||||||||||
| 73 | Recreation Therapy | RTCA2 | Creative Arts - Group Therapy Room - Music | GROUP THERAPY ROOM, MUSIC | OCCUPATIONAL THERAPY | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 CG | 8 | -- | |||||||||||||||||||||||||||
| 74 | Recreation Therapy | RTCA3 | Creative Arts - Group Therapy Room - Large | GROUP THERAPY ROOM, ART | OCCUPATIONAL THERAPY | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 CG | 8 | -- | |||||||||||||||||||||||||||
| 75 | Recreation Therapy | RTEW1 | Recreation Therapy Exercise / Weight Room - Small | WEIGHT ROOM, SMALL | PHYSICAL THERAPY | TREATMENT | RF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 34 AG | 10 | -- | |||||||||||||||||||||||||||
| 76 | Logistics, Engineering | SRGC2 | Storage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior | SRGC1 | SRGC1 | GAS CYLINDER STORAGE | -- | WSF | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | 45 MIN | 34 G | Exh. (S) | |||||||||||||||||||||||||||
| (-) | 1 | -- | -- | -- | Y | N | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | -- | -- | -- | ||||||||||||||||||||||||||||||||||
| 77 | Logistics, Engineering | SRHM1 | Storage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous Waste | BIO-HAZARD STORAGE | HAZARDOUS MATERIAL STORAGE | -- | WSF | WSF | EP | RWC | 4'-0" | -- | GWB:SP | 9'-0" | 3 | 3'-6" | Flush | Hollow Metal | -- | -- | 34 G | -- | -- | ||||||||||||||||||||||||||
| 78 | Logistics, Engineering | SRLG3 | Storage Area - Logistics | SRPS1 | SRPS1 | LOGISTICS STORAGE AREA | CLEAN STORAGE | -- | RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 34 G | 1 | -- | |||||||||||||||||||||||||
| 79 | Pharmacy Service | SSV01 | Secure Storage, Vault | SSV, PHMP2 | SSV | PHMP2 | SECURE STORAGE VAULT | CLEAN STORAGE | -- | RFT | RB | P | RWC | 4'-0" | -- | GWB:P | 9'-0" | 3'-0" | Flush | Hollow Metal | -- | -- | 1 | 1 | -- | ||||||||||||||||||||||||
| 80 | General Rooms/Spaces | WRC01 | Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-Zone 2 | WRC03, WTG03, WRL01, WTG02, PHVS1, WTG04, WTMRI | WRC03 | WTG03 | WRL01 | WTG02 | PHVS1 | WTG04 | WTMRI | SUB-WAITING | -- | CPT, RSF or RFT | RB | P | -- | -- | -- | AT | 9'-0" | 10, 17 | -- | -- | -- | -- | -- | - | 6 | M4 | 4 | -- | |||||||||||||||||
| 81 | Specialty Care Services | TROB2 | Procedure Room - Urology, Procedure Room - Gynecology | TROB1 | TROB1 | PROCEDURE ROOM, UROLOGY or GYNECOLOGY | PROCEDURE | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT:SP | 9'-0" | 3 | 3'-6" | Flush | Wood | -- | -- | 12 S | 8 | -- | ||||||||||||||||||||||||
| 82 | Domiciliary | LAUN1 | Laundry Room, In-Patient | LAUNDRY ROOM, RESIDENT | GENERAL LAUNDRY | -- | WSF | WSF | P | -- | -- | -- | AT | 9'-0" | 8 | 3'-0" | Flush | Wood | -- | -- | 15 AG | 8 | -- | ||||||||||||||||||||||||||
| 83 | Specialty Care Services | OPMH3 | Biofeedback Treatment Room | BIOFEEDBACK TREATMENT ROOM | TREATMENT | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 15 S | 4 | -- | |||||||||||||||||||||||||||
| 84 | Pharmacy Service | PHAR1 | Anteroom, Compound Sterile Preparation | ANTEROOM | -- | WSF | WSF | EP | -- | -- | -- | GWB:SP | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | 68 | 68 | 60 | 20 | 30 | 2 | Return | 55 | (+) | M12 | 1 | -- | |||||||||||||||||
| 85 | Specialty Care Services | APFR1 | Appliance, Fitting Room | APPLIANCE FITTING ROOM | EXAM | TREATMENT | RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 15 S | 6 | -- | |||||||||||||||||||||||||||
| 86 | Domiciliary | BRPT1 | Bedroom - 1 Bedroom, Bedroom - 1 Bedroom - DOM | DOMICILIARY BEDROOM | RESIDENT ROOM | PATIENT ROOM | CPT | RB | P | -- | -- | SEE FGI | GWB:P | 9'-0" | 4'-0" | Flush | Wood | -- | -- | 10 G | |||||||||||||||||||||||||||||
| 75 | 70 | NR | NR | 4 | 2 | Return | 40 | NR | 4 | -- | -- | 1 | Y | N | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | 1 | 1 | -- | Y | |||||||||||||||||||||||||
| 87 | Dental Service | DNPL1 | Laboratory, Dental Prosthetics | DENTAL PROSTHETICS LABORATORY | -- | WSF | WSF | P | -- | -- | -- | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 AG | 75 | 70 | 60 | 20 | 6 | 2 | Return |
Exh. (G)
| 45 | (-) | M13 | 6 | -- | 1 | -- | Y | N | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | 5 | 2 | -- | Y | Y | ||||||||||||||||||||||||||||||
| 88 | Dental Service | DNTG1 | Dental Treatment Room (DTR), Multi-Functional (4/Hygiene) | DENTAL TREATMENT ROOM | TREATMENT | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 CS | (+) | 6 | |||||||||||||||||||||||||||
| 89 | Dental Service | DNTG5 | Dental Treatment Room, Special Needs Patient | SPECIAL NEEDS DENTAL TREATMENT ROOM | TREATMENT | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 CKS | (+) | 6 | |||||||||||||||||||||||||||
| 90 | Dental Service | DNXS1 | X-Ray Room, Panoramic / Cephalometric (Cone Beam) | DENTAL X-RAY ROOM | X-RAY (D&T) | TREATMENT | RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 17 AGL | 6 | |||||||||||||||||||||||||||
| 91 | Primary Care, Specialty Care, PACT | EXRG6 | Exam, Isolation, Negative Pressure | EXAM ROOM, AIRBORNE INFECTION ISOLATION | ALL | EXAMINATION | WSF | WSF | P | -- | -- | SEE FGI | GWB:P | 9'-0" | 3,7 | 3'-6" | Flush | Wood | -- | -- | 12 S | 5 | |||||||||||||||||||||||||||
| 92 | Food and Nutrition | FSDW1 | Dishwashing | KITCHEN, DISHWASHING | WAREWASHING | -- | QT | QT | FRP | -- | -- | -- | AT:SP | 9'-0" | 14 | 3'-0" | Flush | Hollow Metal | -- | -- | 43 AJS | Exh. (S) | |||||||||||||||||||||||||||
| (-) | -- | -- | 2 | -- | Y | N | Dishwasher and hood fan | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | Sealed fixture, flat lens surface on exterior | N/A | -- | -- | -- | Y | ||||||||||||||||||||||||||||||||
| 93 | Pathology and Laboratory Medicine | LMCH1 | Laboratory - Clinical Chemistry, Chemistry - Minimal and Blood Gas | LABORATORY, CHEMISTRY | LABORATORY WORK AREA, BIOCHEMISTRY | -- | WSF | WSF | P | -- | -- | -- | AT:SP | 9'-0" | 3'-0" | Flush w/ Narrow Vision | Wood | -- | -- | 15 AG | 6 | ||||||||||||||||||||||||||||
| 94 | Pathology and Laboratory Medicine | LMHI1 | Laboratory - Hematology - Minimal | LABORATORY, HEMATOLOGY | LABORATORY WORK AREA, SEROLOGY | -- | WSF | WSF | P | -- | -- | -- | AT:SP | 9'-0" | 3'-0" | Flush w/ Narrow Vision | Wood | -- | -- | 15 AG | 6 | ||||||||||||||||||||||||||||
| 95 | Pathology and Laboratory Medicine | LMS01 | Laboratory - Serology - Small | LABORATORY, SEROLOGY | LABORATORY WORK AREA, SEROLOGY | -- | WSF | WSF | P | -- | -- | -- | AT:SP | 9'-0" | 3'-0" | Flush w/ Narrow Vision | Wood | -- | -- | 15 AG | 6 | ||||||||||||||||||||||||||||
| 96 | Pathology and Laboratory Medicine | LMU02 | Laboratory - Urinalysis - Small | LABORATORY, URINALYSIS | LABORATORY WORK AREA, PATHOLOGY | -- | WSF | WSF | P | -- | -- | -- | AT:SP | 9'-0" | 3'-0" | Flush w/ Narrow Vision | Wood | -- | -- | 15 AG | 6 | ||||||||||||||||||||||||||||
| 97 | Specialty Care Services | PTTC1 | Treatment Room, Treatment Room - Private Therapy with 2 Walls | PHYSICAL THERAPY, TREATMENT ROOM | TREATMENT | TREATMENT | RF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 S | 4 | ||||||||||||||||||||||||||||
| 98 | Specialty Care Services | TROB2 | Procedure Room | PROCEDURE ROOM | PROCEDURE | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT:SP | 9'-0" | 3 | 3'-6" | Flush | Wood | -- | -- | 12 S | 8 | |||||||||||||||||||||||||||
| 99 | Imaging Services | XCTC1 | CT Control Area, X-Ray - Computed Tomography - Control | C.T. CONTROL ROOM | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-0" | Flush | Wood | -- | LEAD LINED | 12 LS | 45 | M14 | 6 | ||||||||||||||||||||||||||
| 100 | Imaging Services | XCTI1 | CT Equipment Room, X-Ray - Computed Tomography - Indep View Console | XMRE1 | XMRE1 | C.T. EQUIPMENT ROOM | -- | WSF | WSF | P | -- | -- | -- | AT | 9'-0" | 5 | 6'-0" | Flush | Wood | -- | -- | 45 AG | 7 | 50 | M14 | 6 | |||||||||||||||||||||||
| 101 | Imaging Services | XCTS1 | CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography - Scanner | C.T. SCAN ROOM | X-RAY (D&T) | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 4'-0" | Flush | Wood | -- | LEAD LINED | 15 ALG | 6 | |||||||||||||||||||||||||||
| 102 | Imaging Services | XDM01 | Mammo - X-ray, Mammography Room | MAMMOGRAPHY SCAN ROOM | X-RAY (D&T) | TREATMENT | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 12 LS | 6 | |||||||||||||||||||||||||||
| 103 | Imaging Services | XDRF1 | Radiographic / Fluoroscopic (R/F) Room | RADIOGRAPHIC / FLOURO SCAN ROOM | X-RAY (D&T) | TREATMENT | WSF | WSF | P | - | - | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 17 AGL | 6 | |||||||||||||||||||||||||||
| 104 | Imaging Services | XDUS1 | Ultrasound Room | ULTRASOUND SCAN ROOM | TREATMENT | TREATMENT | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 12 S | |||||||||||||||||||||||||||||
| 6 | -- | 1 | -- | Y | N | Dedicated receptacle for Ultrasound - verify NEMA configuration | 2 X 2 recessed lensed or self-contained indirect, and downlights | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | 1 | 1 | -- | Y | Staff emergency station where required | Y | |||||||||||||||||||||||||||||||
| 105 | Imaging Services | XFDS1 | X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System (PACS) | XVC01 | XVC01 | PACS SERVER ROOM | -- | RFT | RB | P | - | - | - | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 GK | 50 | 4 | ||||||||||||||||||||||||||
| 106 | Imaging Services | XMRC1 | MRI Control Room, X-Ray - Magnetic Resonance - Control, MRI Zone 3 | MRI CONTROL ROOM | MRI ROOM | RFT or RSF | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 G | 45 | M14 | 6 | |||||||||||||||||||||||||||
| 107 | Imaging Services | XMRC2 | MRI System Component Room, X-Ray - Magnetic Resonance - System Component | XMRE1 | XMRE1 | MRI EQUIPMENT ROOM | RFT or RSF | RB | P | RWC | 4'-0" | AT | 9'-0" | 11 | 4'-0" | Flush | Wood | -- | -- | 35 AG | 40 | 50 | M14 | 6 | |||||||||||||||||||||||||
| 108 | Imaging Services | XMRF1 | X-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI Zone 2, MRI Viewing Room | MRI FERROMAGNETIC DETECTION | MRI ROOM | WSF, RFT or RSF | RB | P | -- | -- | AT | 9'-0" | 11, 16 | 4'-0" | Flush | Wood | -- | -- | 15 G | 75 | 70 | 60 | 40 | 12 | 2 | Return | 40 | NR | 1 | ||||||||||||||||||||
| 109 | Imaging Services | XMRS1 | MRI Scanning, X-Ray - Magnetic Resonance - Scanner, | MRI SCAN ROOM | MRI SCANNER ROOM | WSF, RFT or RSF | RB | P | -- | -- | SEE FGI | AT | VARIES | 11,13,16 | 4'-0" | Flush | Wood | -- | R/F Shielded | 1 | 75 | 70 | 60 | 40 | 12 | 2 | Return | ||||||||||||||||||||||
| Exh. (S) | 50 | NR | M17 | 2 | -- | -- | -- | Y | N | MRI rated devices | 2 X 2 recessed lensed or self-contained indirect, and downlights | Multilevel switching/dimming/occupancy | Y | N | MRI rated fixtures | N/A | 1 | -- | -- | ||||||||||||||||||||||||||||||
| 110 | Imaging Services | XMRV1 | MRI Viewing Room, X-Ray - Magnetic Resonance - Viewing | READING ROOM | -- | CPT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 G | 40 | 6 | ||||||||||||||||||||||||||||
| 111 | Medical Center | XXYYC | Operations Room - MH Clinic and Domiciliary Psychosocial Rehabilitation and Recovery Center | DOMICILIARY OPERATIONS ROOM | -- | CPT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-0" | Flush | Wood | -- | -- | 15 GK | 4 | |||||||||||||||||||||||||||||
| 112 | General Rooms/Spaces | LOB02 | VESTIBULE | VESTIBULE | WM | RB or PT | P | -- | -- | -- | GWB/P | 9'-0" | 20 | 6'-0" | Full Glass | Alum/Glass | Full | -- | 710 | 7 | M4 | 1 | |||||||||||||||||||||||||||
| 113 | General Rooms/Spaces | NCWD4 | ALCOVE - VOLUNTEER, ALOVE - WHEELCHAIR, Kiosk - My Healthy Vet, Kiosk - Patient Check-In | SRLW1, CLSC1, RCHK2, RECP4, RCHK2, CSWH1, RCHK1 | SRLW1 | CLSC1 | RCHK2 | RECP4 | RCHK2 | CSWH1 | RCHK1 | ALCOVE | PATIENT CORRIDOR | SEE NOTE | SEE NOTE | P | RWC | 4'-0" | -- | AT | 8'-0" | 6 | -- | -- | -- | -- | -- | - | 6 | 1 | |||||||||||||||||||
| 114 | General Rooms/Spaces | WR01 | Waiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6 People, Waiting-General | WRF01, WRC06, WTG20, WTG10, WTF03, WTPC3, WRC05, WTG06, LOB06, WTF01, WTG21, WTG07, WTG28, WTG27 | WRF01 | WRC06 | WTG20 | WTG10 | WTF03 | WTPC3 | WRC05 | WTG06 | LOB06 | WTF01 | WTG21 | WTG07 | WTG28 | WTG27 | WAITING | PUBLIC SPACE | CPT, RSF, or RFT | RB | P | -- | -- | -- | AT | 9'-0" | 10, 17 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | M4 | -- | ||||||||||||
| 115 | Primary Care/ Mental Health | CLSC4 | Shared Medical Appointment Room | MEDICAL APPOINTMENT | CONSULTATION | CPT | RB | PT | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 12 CG | M3 | -- | ||||||||||||||||||||||||||||
| 116 | Logistics, Engineering | SRE01 | Storage - Medical Equipment, Storage - Shared Medical Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage - Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area | SRS01, SRS02, SRSE1, CLHS4, STSP4, CLCS1, SRCS1, FILE1, CLHS3, SRPB1, PRC03, CLHS2, FSCS1 | SRS01 | SRS02 | SRSE1 | CLHS4 | STSP4 | CLCS1 | SRCS1 | FILE1 | CLHS3 | SRPB1 | PRC03 | CLHS2 | FSCS1 | STORAGE | CLEAN STORAGE | RFT | RB | P | -- | -- | -- | AT | 8'-0" | 3'-0" | Flush | Wood | -- | -- | 35 AG | At least 1 per wall, not to exceed 12' spacing | |||||||||||||||
| 117 | General Rooms/Spaces | WKTM1 | Classroom | CLASSROOM | CPT or RFT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 35 S | M4 | 8 | |||||||||||||||||||||||||||||
| 118 | Imaging Services | DR001 | Dressing room | CHANGING ROOM | CPT, RSF, or RFT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 11 K | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | 1 | |||||||||||||||||||||
| 119 | Imaging Services | XDBD1 | Bone Densitometer | BONE DENSITOMETRY | EXAM | TREATMENT | RSF or RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 35 S | 6 | ||||||||||||||||||||||||||||
| 120 | Logistics, Engineering | SRLG1 | Break Down | CLNRB, MMRP1 | CLNRB | MMRP1 | BREAK DOWN | CLEAN WORKROOM | RPT | RB | EP | -- | -- | -- | AT | 8'-0" | 8 | 4'-0" | Flush | Wood | -- | -- | 34 AG | 1 | |||||||||||||||||||||||||
| 121 | Other | CROP1 | Operations Room | OPERATIONS ROOM | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-6" | Flush | Hollow Metal | -- | -- | 200 APS | M15 | -- | |||||||||||||||||||||||||||||
| 122 | Police Service | SSS01 | Small Arms Armory, Storage - Secure | SECURE STORAGE | RFT | RB | P | -- | -- | -- | AT | 8'-0" | 3'-0" | Flush | Hollow Metal | -- | -- | 200 P | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | 1 | |||||||||||||||||||||
| 123 | General Rooms/Spaces | BX002 | Vending Machine Area | VENDING | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | -- | -- | -- | -- | -- | 6 | M4 | -- | ||||||||||||||||||||||||||||
| 124 | Other | CSPL3 | Alcove - Auto Refractor, Alcove-PPE | CSPE1 | CSPE1 | ALCOVE, EQUIPMENT | PATIENT CORRIDOR | RFT or RSF | RB | P | -- | -- | -- | AT | 8'-0" | -- | -- | -- | -- | -- | - | 6 | 1 | ||||||||||||||||||||||||||
| 125 | Logistics, Engineering | BLND1 | Special Needs Vendor Area | BX001 | BX001 | VENDOR AREA - SPECIAL NEEDS | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 15 AG | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | 4 | |||||||||||||||||||
| 126 | General Rooms/Spaces | TLTS1 | Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff | TLTS4, TLTS2, TSSF1, TSSM1, TSSU1 | TLTS4 | TLTS2 | TSSF1 | TSSM1 | TSSU1 | TOILET/SHOWER ROOM | TOILET ROOM | TOILET ROOM | PT | PT | CT | -- | -- | SEE FGI | GWB/P | 9'-0" | 2, 19 | 3'-6" | Flush | Wood | -- | -- | 11 G | -- | |||||||||||||||||||||
| 127 | Domiciliary | DAYR1 | Dayroom - Patient Lounge | DAYROOM | CPT, RFT | RB | P | -- | -- | 40 | AT | 9'-0" | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 S | M4 | 4 | |||||||||||||||||||||||||||||
| 128 | Domiciliary | NCWD1 | Nourishment Center | NOURISHMENT | NOURISHMENT | PT | RB | P | -- | -- | -- | AT | 9'-0" | 3'-6" | Flush | Wood | -- | -- | 121 AG | 4 | |||||||||||||||||||||||||||||
| 129 | Domiciliary | ZK100 | Recreation Space - Outdoor | RECREATION SPACE - OUTDOOR | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | - | 6 | N/A | -- | ||||||||||||||||||||||||||||
| 130 | Food and Nutrition | FSSL1 | Canteen Serving Area | FOOD SERVICE | FOOD PREPARATION | PT | PT or CT | CT | -- | -- | -- | AT - SP | 9'-0" | 2, 21 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | M9 | 6 | |||||||||||||||||||||||||||
| 131 | NOT USED | NOT USED | NOT USED | ||||||||||||||||||||||||||||||||||||||||||||||
| 132 | Specialty Care Services | OPPS1 | Outpatient Pulmonary Function Screening | PULMONARY FUNCTION SCREENING | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0 | 3'-6" | Flush | Wood | -- | -- | 15 S | One per wall | ||||||||||||||||||||||||||||
| 133 | Cardiology | OPEC1 | EKG Testing Room | EKG TESTING ROOM | EXAM | EXAMINATION | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0 | 3'-6" | Flush | Wood | -- | -- | 12 S | One per wall | ||||||||||||||||||||||||||||
| 134 | PHYSICAL THERAPY | OTEV1 | Exam Room, Physical Therapy | PHYSICAL THERAPY EXAM ROOM | EXAM | EXAMINATION | RFT or RSF | RB | P | SEE FGI | AT | 9'-0 | 3'-6" | Flush | Wood | -- | -- | 12 S | One per wall | ||||||||||||||||||||||||||||||
| 135 | PHYSICAL THERAPY | OTDL1 | ADL Evaluation and Training Center | ADL EVALUATION/TRAINING CENTER | PHYSICAL | ||||||||||||||||||||||||||||||||||||||||||||
| THERAPY | TREATMENT | RFT or RSF | RB | P | -- | -- | SEE FGI | AT | 9'-0 | 3'-6" | Flush | Wood | -- | -- | 15 S | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | Y | |||||||||||||||||||||
| 136 | Primary Care, Specialty Care, PACT | ORPP3 | Procedure Room, Pain | PAIN PROCEDURE ROOM | TREATMENT | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT - SP | 9'-0 | 3 | 3'-6" | Flush | Wood | -- | -- | 16 AG | -- | |||||||||||||||||||||||||||
| 137 | SINK1 | SINK1 | Sink, Staff Handwashing | STAFF HANDWASHING SINK - ALCOVE | PATIENT CORRIDOR | -- | RF or WSF | RF or WSF | P | S | 5'-0" | -- | AT | 9'-0 | 3, 6 | -- | -- | -- | -- | -- | -- | OPEN | -- | ||||||||||||||||||||||||||
| 138 | Prosthetics | BMCW1 | Workspace, Wheelchair Repair | WHEELCHAIR REPAIR WORKROOM | -- | RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0 | 3'-6" | Flush w/ Narrow Vision | Wood | Yes | -- | 35 S | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | -- | ||||||||||||||||||||
| 139 | Logistics, Engineering | BMWS1 | Workroom, Biomedical Engineer | BIOMEDICAL ENGINEER WORKROOM | CLEAN WORKROOM | -- | RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0 | 6'-0" | Flush w/ Narrow Vision | Wood | Yes | -- | 45 G | 7 | -- | |||||||||||||||||||||||||||
| 140 | Business Office | CASH1 | Secure Money Handling Room | SECURE CASH ROOM | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0 | 3'-0" | Flush w/ 1-Way Viewer | Steel | -- | -- | 200 GV | One per wall | |||||||||||||||||||||||||||||
| 141 | VCS | BX000 | Retail Area | RETAIL AREA | PUBLIC SPACE | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0 | 17 | 6'-0" | Flush w/ Full Vision | Wood | Full Vision | 47 KM | 7, 9 | M4 | One per wall, 6' spacing maximum. | |||||||||||||||||||||||||||
| 142 | OI&T | ITAE1 | OIT IT Active Equipment | OIT EQUIPMENT SPACE | -- | SD | RB | P | -- | -- | -- | EXP | -- | 11, 22, 23 | 3'-0" | Flush | Wood | -- | -- | 200 AGZ | 9 | -- | |||||||||||||||||||||||||||
| 143 | OI&T | TEIP1 | VoIP Active Equipment | VOIP EQUIPMENT SPACE | -- | SD | RB | P | -- | -- | -- | EXP | -- | 11, 22, 23 | 3'-0" | Flush | Wood | -- | -- | 200 AGZ | 9 | -- | |||||||||||||||||||||||||||
| 144 | OI&T | SAWK1 | Workroom, PIV Staff | PIV STAFF WORKROOM | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0 | 3'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 200 S | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | One per wall | ||||||||||||||||||||
| 145 | Logistics, Engineering | UTR01 | Utility, Waste Recycling | UTILITY ROOM, RECYCLING | JANITOR'S | ||||||||||||||||||||||||||||||||||||||||||||
| CLOSET | -- | RSF | RB | P | RWC | 4'-0" | -- | AT | 9'-0 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 121 AG | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed or self-contained indirect | Multilevel switching/dimming/occupancy | Y | N | N/A | N/A | ||||||||||||||||||||||
| 146 | SPS | CSCR1 | Anteroom, Soiled Transition/Drop-Off | ANTEROOM, SOILED TRANSITION | DECONTAM | ||||||||||||||||||||||||||||||||||||||||||||
| ROOM | -- | RES or WSF | RES or WSF | EP | -- | -- | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 19 AG | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Gyp ceiling - lights to be sealed type/flange mounted | N/A | |||||||||||||||||||||
| 147 | SPS | USCL2 | Decontamination Room, Scope | DECONTAMINATION ROOM, SCOPE | DECONTAM | ||||||||||||||||||||||||||||||||||||||||||||
| ROOM | -- | RES or WSF | RES or WSF | EP | S | 5'-0" | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Gyp ceiling - lights to be sealed type/flange mounted | N/A | |||||||||||||||||||||
| 148 | SPS | USCL3 | Reprocessing Room, Scope | REPROCESSING ROOM, SCOPE | ENDOSCOPE | ||||||||||||||||||||||||||||||||||||||||||||
| CLEANING | -- | RES or WSF | RES or WSF | EP | S | 5'-0" | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 1 | ||||||||||||||||||||
| 149 | SPS | USCL4 | Storage, Clean Scope | STORAGE, CLEAN SCOPE | STERILE |
STORAGE
| ROOM | -- | RES or WSF | RES or WSF | EP | RWC | 4'-0" | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | One per wall | -- | -- | -- | Y | N | 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Gyp ceiling - lights to be sealed type/flange mounted | N/A | Y | ||||||||||||||||||||
| 150 | Pathology and Laboratory Medicine | LBBD2 | Specimen Accessioning, Processing & Distribution Room | SPECIMEN ACCESSIONING, PROCESSING & DISTRIBUTION ROOM | LABORATORY WORK AREA, PATHOLOGY | -- | RES or WSF | RES or WSF | EP | -- | -- | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | One per wall | One at each workstation | One adjacent sink | -- | Y | N | 2 X 2 recessed lensed | Multilevel switching/dimming/occupancy | Y | N | Gyp ceiling - lights to be sealed type/flange mounted |
Instructions
| Sorting, Printing & Security Instructions | |||||||||||||
| March 25, 2021 | |||||||||||||
| Sorting | PRINT AREAS - WITHOUT NOTES BELOW MATRIX | ||||||||||||
| 1 | To quick sort in ascending order, click (Sort A to Z), or Smallest to Largest or | ||||||||||||
| (Sort Z to A), or Largest to Smallest | Range: | INTERIOR CONSTRUCTION | DOORS AND HARDWARE | MECHANICAL | ELECTRICAL | LIGHTING | IT | SYSTEMS | FIRE ALARM | ||||
| 2 | However you sort the matrix, it might be helpful to Sort by Row Number before you close the file to make it easier to orient yourself to the file on the next open. | Top | W3 | AF3 | AM3 | AW3 | BE3 | BK3 | BO3 | BU3 | |||
| Bottom of Data | AE156 | AL156 | AV156 | BD156 | BJ156 | BN156 | BT156 | BU156 |
| Printing | PRINT AREAS - WITH NOTES BELOW MATRIX | |||||||||
| E-Sized | The spreadsheet's default's page size is E-sized (36" x 48" Landscape) | Range: | INTERIOR CONSTRUCTION | DOORS AND HARDWARE | MECHANICAL | ELECTRICAL | LIGHTING | IT | SYSTEMS | FIRE ALARM |
| Best for on-screen viewing of all columns on one sheet. | Top | W3 | AF3 | AM3 | AW3 | BE3 | BK3 | BO3 | BU3 | |
| Bottom of Notes | AE222 | AL176 | AV179 | BD173 | BJ167 | BN156 | BT156 | BU156 | ||
| To print All Columns: | ||||||||||
| Select Cells: | A1 through BU155 | |||||||||
| Sheet Size: | E-sized | |||||||||
| Page Orientation: | Landscape | |||||||||
| Result: | Legible/ scaled for printed views: 2 sheet wide x 3 sheets high, about 56 rows per sheet, headings on each sheet | NOTES: | ||||||||
| In Print Window: | With your cursor, hold and select the cells in print range above. In print window, choose "Print Selection". Custom Scaling - Custom Scaling Options: Scaling: Fit to 2 pages wide by 3 tall | 1 | Matrix data in rows 1-130 are from the August 14, 2019 version of the RDM; Data in rows 131-150 are from the Nov. 6, 2020 update. All data in red text is from the Nov. 6, 2020 update. | |||||||
| 2 | When printing, choose "Print Selection" to print a specific set of data | |||||||||
| Print and save your PDF. | 3 | Notes for certain divisions are referenced below the data cells. See matrix above for print areas to select to include or exclude these notes for printing. | ||||||||
| 4 | Before printing a specific discipline, begin by Sorting by the notes column of the group you are printing, then select the group and print. | |||||||||
| To print Only Interior Construction + Doors & Hardware Columns: | 5 | Certain cells within the spreadsheet have been protected to minimize inadvertent changes to data. See "Password Protection" instuctions in A82 this sheet. | ||||||||
| Select Cells: | A1 through A155 | 6 | Due to cell protection, dragging to select cells is disabled. To select cells to print, click and hold the first cell, and shift-click to select the last cell from the tables above for the specific range you wish to print. | |||||||
| Sheet Size: | E-sized | |||||||||
| Page Orientation: | Landscape | |||||||||
| Result: | 1 sheet wide x 2 sheets high, about 50 rows per sheet, headings on each sheet, legible but text is very small. | Password Protection Options: | ||||||||
| In Print Window: | Select the cells in print range above. In print window under "Settings", choose "Print Selection", Collated, Landscape Orientation, ARCH_E size, Normal Margins, and Fit All Columns on One Page | To prevent editing of this document, this sheet has been protected. Each tab can be protected or unprotected individually. | ||||||||
| To unprotect the spreadsheet, on the Review Menu, select 'Unprotect sheet'. Enter the password in the pop-up window. | ||||||||||
| Password to Unprotect this file: gsa | ||||||||||
| Print and save your PDF. | ||||||||||
| To protect the sheet, on the Review Menu, select 'Protect sheet'. Enter a password in the pop-up window. Confirm password in second window. | ||||||||||
| To print Only Mechanical, Electrical, IT, Systems, and Fire Alarm Columns: | ||||||||||
| Select Cells: | AM1 through BU155 | |||||||||
| Sheet Size: | E-sized | |||||||||
| Page Orientation: | Landscape | |||||||||
| Result: | 1 sheet wide x 3 sheets high, about 60 rows per sheet, headings on each sheet, legible but text is very small. | |||||||||
| In Print Window: | Select the cells in print range above. In print window under "Settings", choose "Print Selection", Collated, Landscape Orientation, ARCH_E size, Normal Margins, and Fit All Columns on One Page |
D-Sized Change your sheet size to D-sized (24" x 36" Landscape)
| To print All Columns: | |
| Select Cells: | A1 through BU155 |
| Sheet Size: | D-sized |
| Page Orientation: | Landscape |
| Result: | 1 sheet wide x 2 sheets high, about 110 rows per sheet, headings on each sheet |
| In Print Window: | With your cursor, hold and select the cells in print range above. In print window, Select "Fit All Columns on One Page" |
Print and save your PDF.
| To print All Columns (enlarged): | |
| Select Cells: | A1 through BU155 |
| Sheet Size: | D-sized |
| Page Orientation: | Landscape |
| Result: | Legible/ scaled for printed views: 2 sheet wide x 3 sheets high, about 51 rows per sheet, headings on each sheet |
| In Print Window: | With your cursor, hold and select the cells in print range above. In print window, choose "Print Selection". Custom Scaling - Custom Scaling Options: Scaling: Fit to 2 pages wide by 3 tall |
Print and save your PDF.
| To print Only Interior Construction + Doors & Hardware Columns: | |
| Select Cells: | A1 through A155 |
| Sheet Size: | D-sized |
| Page Orientation: | Landscape |
| Result: | 1 sheet wide x 2 sheets high, about 96 rows per sheet, headings on each sheet |
| In Print Window: | With your cursor, hold and select the cells in print range above. In print window, choose "Print Selection". |
| Select "Fit All Columns on One Page" | |
| Print and save your PDF. |
| To print Only Mechanical, Electrical, IT, Systems, and Fire Alarm Columns: | |
| Select Cells: | AM1 through BU155 |
| Sheet Size: | D-sized |
| Page Orientation: | Landscape |
| Result: | 1 sheet wide x 2 sheets high, about 110 rows per sheet, headings on each sheet |
| In Print Window: | With your cursor, hold and select the cells in print range above. In print window, choose "Print Selection". |
| Select "Fit All Columns on One Page" | |
| Print and save your PDF. |
Interior Finishes Notes Interior Finishes Notes
| General Notes | |
| A. | Hollow metal frames and doors to be painted. |
| B. | Window sills to be solid surface fabrication. |
| C. | Resilient base to be 4", unless otherwise noted. |
| D. | Provide painted finishes only on inside of exterior walls (no wall covering). |
| E. | Floor material transitions to occur at centerline of door, unless otherwise noted. |
| F. | Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color. |
| G. | Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety. |
| H. | Coordinate height of wall protection with wall-mounted devices. |
| I. | Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and |
| lobby/waiting areas. | |
| J. | Soffit above upper cabinets to be gypsum board. |
| K. | Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials. |
| L. | Solid surface countertops to have sides and backsplash at walls. |
| Schedule Notes | |
| 1. | CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling. |
| 2. | Tile base to be coved. |
| 3. | Integral coved base 6" high tightly sealed to walls. |
| 4. | If sink is present, use hard suface flooring as noted. |
| 5. | Lead lined walls and control area view window. |
| 6. | Flooring and base to match adjacent area flooring material and base. |
| 7. | Use gasketed, clip down ACT/grid system |
| 8. | Use slip-retardant finish on floor material |
| 9. | Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety. |
| 10. | Note that if wall saver designed chairs are used, no wall protection is required. |
| 11. | Extend all room partitions to structural deck. |
| 12. | CT above countertop on wall. |
| 13. | Ceiling height as required to acommodate equipment. |
| 14. | Cove QT base, 6" high. |
| 15. | No separate trim at top of base, use alternate method to seal to wall. |