05Drawings Architectural.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25521R0027
About this file
This solicitation is for a construction project to create an elevator tower and stairwell within Building 23 at the Jefferson Barracks VA Medical Center in St. Louis, Missouri. The project cost is estimated between $2 million to $5 million, with an anticipated completion period of 383 calendar days after notice to proceed. The North American Industry Classification System code for this procurement is 238220 for commercial and institutional building construction. The award will be made using the best value lowest price technically acceptable source selection process. The successful prime contractor must self-perform at least 15% of the general construction labor. Registration in the System for Award Management and VetBiz databases is required. The solicitation and drawings will be posted on January 22, 2021 to beta.SAM.gov. Attendance at the pre-solicitation site visit is encouraged for all responsible sources to submit an offer. Questions must be submitted by email with the subject line referencing the project number. Pursuant to law, this project is a competitive total set-aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING CORRIDOR
EXISTING
BUILDING 23
NEW ELEVATOR
TOWER & STAIR
DN
G R
A V
E S
S T
R E
E T
1 2
3DN DN DN
DN
DN
DN
T E
M P
O R
A R
Y C
O R
R
ID
O R
TEMPORARY CONNECTING CORRIDOR, REF SHEET AE-413
NEW ENTRY PLAZA W/ SEATING AREA
NEW CONCRETE RAMP, REF SHEET AE-101 & AE-111
NEW CONCRETE STAIR, REF SHEET AE-101 & AE-111
SPLASH BLOCK @ DOWNSPOUT
EXISTING SIGNAGE TO BE GIVEN RIGHT OF FIRST REFUSAL
DURING DEMOLITION
BUILDING PROTECTION / SEATING
EXISTING UTILITY VAULT TO REMAIN
NEW RETAINING WALL, REF CIVIL
PROPOSED RELOCATION OF EXISTING DUMPSTER / DISPOSAL
UNIT, REF SHEET AE-413
EXISTING INFILTRATION TRENCH
SITE PLAN KEYNOTE LEGEND
FIRE ACCESS ROUTE
SITE PLAN LEGEND
ARCHITECTURAL SCOPE BOUNDARY
EXISTING BUILDING
NEW BUILDING
EXISTING LIGHT POLE
FIRE ACCESS ROUTE
25'-0" SECURITY SETBACK
EXISTING HYDRANT
PROPOSED CONSTRUCTION STAGING AREA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:4
A
M
23-AS-101
ARCHITECTURAL SITE PLAN
BHR
33 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/16" = 1'-0"
ARCHITECTURAL SITE PLAN
jet Image
DN
FD
DESCRIPTION
LIFE SAFETY LEGEND
SYMBOL
PATH OF EGRESS IDENTIFIER
1/2-HOUR RATED FIRE BARRIER
1-HOUR RATED FIRE BARRIER
2-HOUR RATED FIRE BARRIER
1-HOUR RATED FIRE/SMOKE BARRIER
2-HOUR RATED FIRE/SMOKE BARRIER
A
FEC
ADA
OCCUPANT LOAD PER SPACE
CUMULATIVE OCCUPANT LOAD
AREA OUTSIDE LIMITS OF WORK
ADA PUSH BUTTON FOR POWER-ASSISTED DOOR OPERATOR
FIRE EXTINGUISHER CABINET
D
ACTUAL CLEAR WIDTH
REQUIRED CLEAR WIDTH
ACTUAL EGRESS
MAXIMUM EGRESS CAPACITY
EGRESS COMPONENT
(D)DOOR (S)STAIRWAY
EGRESS CAPACITY TAG
OCCUPANCY USE LEGEND
HATCH DESCRIPTION
INDUSTRIAL
100 SF/PERSON, GROSS
USE
I
BUSINESS
150 SF/PERSON, GROSS
B
STORAGE
500 SF/PERSON, GROSS
S
NFPA 101-2018 EDITION
BUILDING HEIGHT: 2 STORIES, 29'-0" HEIGHT
BUILDING AREA LIMITATION: 46,500 S.F. PER FLOOR
(2018 IBC TABLE 503)
• FLOOR 00 1,425 SF NEW
10,370 SF EXISTING
11,795 SF TOTAL
• FLOOR 01 446 SF NEW
10,540 SF EXISTING
10,986 SF TOTAL
TOTAL AREA 22,781 SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER
SYSTEM THROUGHOUT - TO MEET NFPA 13 REQUIREMENTS
CONSTRUCTION TYPE PER TABLE A.8.2.1.2: TYPE II (000) ASSUMED
[2018 IBC TABLE 6A - TYPE II (B) ASSUMED]
FIRE RESISTANCE RATINGS (NFPA 220 TABLE 4.1.1):
• COLUMN: 0 HR
• BEAMS, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 1 HR (>10' FROM ADJ. BLDG.)
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS,
ROOF DECK, EXTERIOR NON-BEARING WALLS, INTERIOR NON-
BEARING WALLS (U.N.O. AT EXTERIOR)
CHAPTER 39: EXISTING BUSINESS OCCUPANCIES
CHAPTER 40: INDUSTRIAL OCCUPANCIES
OCCUPANT LOADS (TABLE 7.3.1.2):
• BUSINESS USE = 150 SF/PERSON
• BUSINESS USE (CONCENTRATED) = 50 SF/PERSON
• COLLABORATION ROOMS <450 SF = 30 SF/PERSON
• COLLABORATION ROOMS >450 SF = 15 SF/PERSON
• INDUSTRIAL USE, GENERAL & HIGH HAZARD = 100 SF/PERSON
• STORAGE USE - 500 SF/PERSON
FLOOR 00
EXISTING INDUSTRIAL OCCUPANCY 10,540 SF/100 SF = 106 OCC.
EXISTINTING BUSINESS OCCUPANCY 3,074 SF/150 SF = 20 OCC.
TOTAL OCCUPANT LOAD 126 OCCUPANTS
FLOOR 01
EXISTING WORKROOM 199 851 SF/50 SF = 18 OCC.
EXISTING RECEPTION AREA 98 139 SF/50 SF = 3 OCC.
EXISTING CONFERENCE ROOM 125 221 SF/30 SF = 8 OCC.
EXISTING BUSINESS OCCUPANCY 6,789 SF/150 SF = 46 OCC.
EXISTING INDUSTRIAL OCCUPANCY 2,370 SF/100 SF = 24 OCC.
TOTAL OCCUPANT LOAD 99 OCCUPANTS
SHAFTS (3 STORIES OR LESS) - MINIMUM 1-HOUR RATING [8.6.5 (2)]
SHAFTS (4 STORIES OR MORE) - MINIMUM 2-HOUR RATING [8.6.5 (2)]
DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (39.2.5.2/40.2.5.1)
MAXIMUM COMMON PATH OF TRAVEL: 100' (39.2.5.3.1/40.2.5.1)
MAXIMUM TRAVEL DISTANCE: 250' (40.2.6.1)
CORRIDOR MINIMUM FIRE RATING: 0 HR (39.3.6/40.3.6)
ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR
EXIT WIDTH .
• 0.15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT
LOAD PER DOOR MAX.
PROTECTED AREAS:
• STORAGE ROOMS/CLEAN/SOILED - REQUIRED BY VA FIRE
PROTECTION DESIGN MANUAL 3.1.A & PER NFPA 101: 20.3.2.1. &
8.7.1.1, SMOKE PARTITIONS WITH SPRINKLER PROTECTION,
PROVIDED.
• MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION
DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION:
• NOT REQUIRED / NOT PROVIDED PER NFPA 39.3.7
FIRE ALARM SYSTEM:
• REQUIRED/PROVIDED
1040 SF
LOBBY
95 SF
EQUIPMENT
ELEVATOR
BUILDING 23
(EXISTING BUSINESS/INDUSTRIAL
OCCUPANCIES, NFPA 101 CH. 39/40)
169' TRAVEL DISTANCE
' T
R A
V E
L D
IS
T
A N
C E
C
O M
M O
N P
A T
H O
F T
R A
V E
L
205 SF
UTILITY
193 SF
ELEVATOR
LOBBY
DN
DN
D
D
BREAK RM. /
STORAGE
G23
CARPENTER
SHOP
G26
CARPENTER
SHOP OFFICE/
KEY PICK-UP
G25
LOCKER, MALE
G15
TOILET / SHOWER
G16
STORAGE
G14
STAIRWELL NO. 1
CORRIDOR
H001
TOILET, MEN
G12
STORAGE
G13
LOCKER, MALE
G11 CARPENTER
STORAGE
G10
CHARGING
STATION
G07
STORAGE
G08
LOCK SHOP
G09
KEY SHOP
G09A
BREAK RM.
G04
STORAGE
G05
OFFICE
G01A
ELEC RM.
G01
MECH. RM.
G02
ELEC RM.
G03
CORRIDOR
H002
CORRIDOR
H003
BATTERY
STORAGE
G13C
TRASH RM.
G13B
WASH RM.
G13A
STAIRWELL NO. 2
S2
MECH. RM.
G17
CORRIDOR
H000
CLOSET
H002A
FEC
ICRA BARRIER, 1-HOUR WALL TO
REMAIN THROUGHOUT CONSTRUCTION
ICRA PASSAGE / CONSTRUCTION
ACCESS, 1-HOUR WALL & 45 MIN DOOR
UP
DNDND
N
DN
CLEAR
8'-0"
EXISTING
UTILITIES
VAULT
LOADING
DOCK
ICRA BARRIER, 1-HOUR WALL TO
REMAIN THROUGHOUT REMEDIATION
STAIR (001)
9"
9" 3/4"
9"
1/ 2"
3/ 4"
3/ 8" 3/
4" 3/
4"
5/8" 3/4"
LEVEL 1
Keep Door Closed
NOTE: SIGN COPY IS FOR EXAMPLE ONLY.
FINAL COPY TO BE COORDINATED BY VA.
1. THE ICRA DESIGNATION FOR THIS PROJECT IS CONSTRUCTION TYPE 'D' &
LEVEL 'III' CLASS OF PRECAUTION OF INFECTION CONTROL ACTIVITIES. HARD
SURFACE BARRIERS SHALL BE USED.
2. WITH REGARD FOR REMEDIATION REQUIREMENTS, AN ENTRY VESTIBULE FOR
CLOTHING CHANGES TO TYVEK SUITS SHALL BE PROVIDED ADJACENT TO THE
HARD SURFACE BARRIER OR ENTRY VESTIBULE. UPON COMPLETION OF THE
CONSTRUCTION PHASE, DUST BARRIERS SHALL BE REMOVED CAREFULLY TO
MINIMIZE SPREADING OF DUST AND THE CONTRACTOR SHALL TEMPORARY
DUST PROTECTION IN PLACE BEFORE REMOVAL OF THE HARD SURFACE
BARRIERS. A DWYER GAUGE SHALL BE USED AT THE CONSTRUCTION ENTRY
TO VALIDATE NEGATIVE AIR FLOWS. AFTER EACH PHASE, PERFORM TASKS
STATED IN NOTE 11.
3. TRAFFIC CONTROL: CONTRACTOR SHALL PROVIDE STICKY MATS AT PLASTIC
BARRIER ENTRANCES OR CONSTRUCTION ENTRY VESTIBULE AND CHANGE
DAILY OR MORE OFTEN AS NEEDED TO PREVENT THE SPREAD OF DUST AND
DEBRIS INTO ADJACENT CLEAN SPACE. ANY DUST TRACKED OUTSIDE OF THE
CONSTRUCTION ENTRY SHALL BE IMMEDIATELY CLEANED. EGRESS PATHS
SHALL BE FREE OF DEBRIS AND COR SHALL DESIGNATE ELEVATORS FOR USE
DURING APPROVED WORKING HOURS. ONLY AUTHORIZED PERSONNEL SHALL
BE ALLOWED TO ENTER THE CONSTRUCTION AREA. SIGNAGE SHALL DIRECT
PEDESTRIAN TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND
MATERIALS. REFER SECURITY INFORMATION FOR ALTERNATE ACCESS
REQUIREMENTS.
4. MATERIAL TRANSPORT: CONTRACTOR SHALL USE ISOLATION CARTS TO
TRANSFER CONSTRUCTION MATERIAL IN AND OUT OF THE CONSTRUCTION
AREA. A CLEAN CART SHALL BE USED FOR TRANSPORTING MATERIAL TO THE
CONSTRUCTION AREA. CARTS ARE TO BE CLEANED AND COVERED BEFORE
LEAVING THE CONSTRUCTION AREA.
5. DEMOLITION DEBRIS: DEBRIS SHALL BE REMOVED IN CARTS WITH TIGHTLY
FITTED COVERS. DEBRIS TRANSPORT TRAFFIC ROUTES SHALL BE
ESTABLISHED TO MINIMIZE USE OF ELEVATORS. TRANSPORT OF DEBRIS WILL
OCCUR DURING THE LOWEST PERIOD OF ACTIVITY IN THE ADJACENT UNIT.
DEBRIS SHALL BE REMOVED DAILY AND AT TIMES SPECIFIED BY THE COR.
6. AIR SYSTEM FLOW: THE COR SHALL VERIFY AND NOTIFY THE CONTRACTOR
WHETHER THE CONSTRUCTION AREA USES FRESH/OUTSIDE OR RE-
CIRCULATED AIR. FILTERS SHALL BE ADDED OR RETURN VENTS COVERED
WITH FILTER MATERIAL OR PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY
AREAS.
7. NEGATIVE AIR PRESSURE: THE AIRE WITHIN THE CONSTRUCTION AREA SHALL
BE NEGATIVE WITH RESPECT TO SURROUNDING AREAS AND WITH NO
DISRUPTION TO AIR SYSTEMS OF ADJACENT AREAS. USE OF THE NEGATIVE
AIR PRESSURE SYSTEM WITHIN THE ENCLOSURE TO REMOVE DUST SHALL
PASS AIR THROUGH AN INDUSTRIAL GRADE PORTABLE HEPA FILTER CAPABLE
OF FILTRATION RATES OF 300-800 CUBIC FEET PER MINUTE. FOR
CONSTRUCTION AREA AIR RETURNED TO THE HVAC SYSTEM, A PRE-FILTER
AND HEPA FILTER SHALL BE USED BEFORE EXHAUST TO PREVENT
CONTAMINATION OF HVAC SYSTEM DUCTING.
8. ADJACENT AREAS: THE STATUS OF SEALED PENETRATIONS AND INTACT
CEILING SHALL BE VERIFIED DAILY.
9. AIR EXCHANGE RATES AND PRESSURE RELATIONSHIPS: VAMC AND
CONTRACTOR SHALL VERIFY AND MAINTAIN PROPER AIR EXCHANGE RATES IN
CRITICAL AREAS NEAR CONSTRUCTION ACTIVITY. CONTRACTOR TO ENSURE
AIR IS RE-CIRCULATED WITH FILTRATION FROM ALL CONSTRUCTION AREAS.
PROVIDE AIR PRESSURE TESTING THROUGHOUT THE PROJECT IN
ACCORDANCE WITH COR PROVIDED REQUIREMENTS.
10. WORKSITE CLOTHING: CONTRACTOR PERSONNEL CLOTHING SHALL BE FREE
OF LOOSE SOIL AND DEBRIS BEFORE LEAVING THE CONSTRUCTION AREA. IF
PROTECTIVE APPAREL IS NOT WORN (EXAMPLES: COVERALLS, FOOTGEAR,
AND HEADGEAR) A HEPA-FILTERED VACUUM SHALL BE USED TO REMOVE
DUST FROM CLOTHING BEFORE LEAVING THE BARRICADE. IF PROTECTIVE
APPAREL IS UTILIZED, THE CONTRACTOR SHALL CONSTRUCT A SPACE OR
ANTEROOM FOR CHANGING OF CLOTHING.
11. POST CONSTRUCTION: DO NOT REMOVE BARRIERS AND KEEP ALL HVAC
ISOLATION IN PLACE UNTIL CONTRACTOR HAS CLEANED THE CONSTRUCTION
SITE, VA EMS STAFF HAS PERFORMED A TERMINAL CLEANING, AND VA
INFECTIOUS DISEASE CONTROL HAS INSPECTED AND APPROVED THE
CLEANING.
12. FIRE ALARMS AND OTHER LIFE SAFETY FIXTURES WITHIN THE ICRA BARRIERS
OF THE CONSTRUCION AREA SHALL BE TEMPORARILY RELOCATED TO THE
OUTSIDE OF BARRIERS.
13. REFER TO SPECIFICATION SECTION 01 01 10 FOR EC-51 SAFETY AND HEALTH
POLICY AND PROCEDURES DURING CONSTRUCTION ACTIVITIES.
ICRA GENERAL NOTES
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING, REF RCP
METAL RUNNER
FASTENED @ 24" OC
WALL FINISH, REF FINISH
SCHEDULE
5/8" "TYPE X" GYPSUM
BOARD, EACH SIDE
METAL RUNNER,
FASTENED @ 24" OC
FINISH FLOOR, REF
FINISH SCHEDULE
BASE AS SCHEDULED
METAL STUD FRAMING
@ 16" OC
FIRE RATED SEALANT
AROUND PERIMETER
FIRE RATED SEALANT
AROUND PERIMETER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:3
A
M
23-AL-101
LIFE SAFETY PLAN - FLOOR 00
BHR
34 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/8" = 1'-0"
LIFE SAFETY PLAN - FLOOR 00
STAIR IDENTIFICATION SIGN
1-HOUR RATED FIRE/SMOKE BARRIER
TEMPORARY ICRA BARRIER
DESCRIPTION
LIFE SAFETY LEGEND
SYMBOL
PATH OF EGRESS IDENTIFIER
1/2-HOUR RATED FIRE BARRIER
1-HOUR RATED FIRE BARRIER
2-HOUR RATED FIRE BARRIER
1-HOUR RATED FIRE/SMOKE BARRIER
2-HOUR RATED FIRE/SMOKE BARRIER
A
FEC
ADA
OCCUPANT LOAD PER SPACE
CUMULATIVE OCCUPANT LOAD
AREA OUTSIDE LIMITS OF WORK
ADA PUSH BUTTON FOR POWER-ASSISTED DOOR OPERATOR
FIRE EXTINGUISHER CABINET
D
ACTUAL CLEAR WIDTH
REQUIRED CLEAR WIDTH
ACTUAL EGRESS
MAXIMUM EGRESS CAPACITY
EGRESS COMPONENT
(D)DOOR (S)STAIRWAY
EGRESS CAPACITY TAG
OCCUPANCY USE LEGEND
HATCH DESCRIPTION
INDUSTRIAL
100 SF/PERSON, GROSS
USE
I
BUSINESS
150 SF/PERSON, GROSS
B
STORAGE
500 SF/PERSON, GROSS
S
NFPA 101-2018 EDITION
BUILDING HEIGHT: 2 STORIES, 29'-0" HEIGHT
BUILDING AREA LIMITATION: 46,500 S.F. PER FLOOR
(2018 IBC TABLE 503)
• FLOOR 00 1,425 SF NEW
10,370 SF EXISTING
11,795 SF TOTAL
• FLOOR 01 446 SF NEW
10,540 SF EXISTING
10,986 SF TOTAL
TOTAL AREA 22,781 SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER
SYSTEM THROUGHOUT - TO MEET NFPA 13 REQUIREMENTS
CONSTRUCTION TYPE PER TABLE A.8.2.1.2: TYPE II (000) ASSUMED
[2018 IBC TABLE 6A - TYPE II (B) ASSUMED]
FIRE RESISTANCE RATINGS (NFPA 220 TABLE 4.1.1):
• COLUMN: 0 HR
• BEAMS, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 1 HR (>10' FROM ADJ. BLDG.)
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS,
ROOF DECK, EXTERIOR NON-BEARING WALLS, INTERIOR NON-
BEARING WALLS (U.N.O. AT EXTERIOR)
CHAPTER 39: EXISTING BUSINESS OCCUPANCIES
CHAPTER 40: INDUSTRIAL OCCUPANCIES
OCCUPANT LOADS (TABLE 7.3.1.2):
• BUSINESS USE = 150 SF/PERSON
• BUSINESS USE (CONCENTRATED) = 50 SF/PERSON
• COLLABORATION ROOMS <450 SF = 30 SF/PERSON
• COLLABORATION ROOMS >450 SF = 15 SF/PERSON
• INDUSTRIAL USE, GENERAL & HIGH HAZARD = 100 SF/PERSON
• STORAGE USE - 500 SF/PERSON
FLOOR 00
EXISTING INDUSTRIAL OCCUPANCY 10,540 SF/100 SF = 106 OCC.
EXISTINTING BUSINESS OCCUPANCY 3,074 SF/150 SF = 20 OCC.
TOTAL OCCUPANT LOAD 126 OCCUPANTS
FLOOR 01
EXISTING WORKROOM 199 851 SF/50 SF = 18 OCC.
EXISTING RECEPTION AREA 98 139 SF/50 SF = 3 OCC.
EXISTING CONFERENCE ROOM 125 221 SF/30 SF = 8 OCC.
EXISTING BUSINESS OCCUPANCY 6,789 SF/150 SF = 46 OCC.
EXISTING INDUSTRIAL OCCUPANCY 2,370 SF/100 SF = 24 OCC.
TOTAL OCCUPANT LOAD 99 OCCUPANTS
SHAFTS (3 STORIES OR LESS) - MINIMUM 1-HOUR RATING [8.6.5 (2)]
SHAFTS (4 STORIES OR MORE) - MINIMUM 2-HOUR RATING [8.6.5 (2)]
DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (39.2.5.2/40.2.5.1)
MAXIMUM COMMON PATH OF TRAVEL: 100' (39.2.5.3.1/40.2.5.1)
MAXIMUM TRAVEL DISTANCE: 250' (40.2.6.1)
CORRIDOR MINIMUM FIRE RATING: 0 HR (39.3.6/40.3.6)
ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR
EXIT WIDTH .
• 0.15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT
LOAD PER DOOR MAX.
PROTECTED AREAS:
• STORAGE ROOMS/CLEAN/SOILED - REQUIRED BY VA FIRE
PROTECTION DESIGN MANUAL 3.1.A & PER NFPA 101: 20.3.2.1. &
8.7.1.1, SMOKE PARTITIONS WITH SPRINKLER PROTECTION,
PROVIDED.
• MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION
DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION:
• NOT REQUIRED / NOT PROVIDED PER NFPA 39.3.7
FIRE ALARM SYSTEM:
• REQUIRED/PROVIDED
253 SF
MEZZANINE
95 SF
ELECTRICAL
ELEVATOR
89' TRAVEL DISTANCE
' T
R A
V E
L D
IS
T
A N
C E
' T
R A
V E
L D
IS
T
A N
C E
' T
R A
V E
L D
IS
T
A N
C E
OPEN TO BELOW
UTILITY ROOM ROOF
DN
D
D
D
CONFERENCE
RM.
PROSTHETICS
RESTORATION
PROSTHETICS
RESTORATION
OFFICE
PROSTHETICS
RESTORATION
LAB
LAB DUSTER
115A
OI&T
115B
CORRIDOR
C119
STAFF LOUNGE
HAC
TOILET
CORRIDOR
C128
ORTH LAB
SUPPLIES
ORTH LAB
SUPPLIES
AMPUTEE CLINIC
WHEELCHAIR
ASSEMBLY
WHEELCHAIR
REPAIR
OFFICE
EXAM 1
CORRIDOR
C118
CORRIDOR
C102
EXAM 2
FIT 2
FIT 1
OFFICE
CLEAN SUPPLY
109ORTH
LAB/OFFICE
SEWING
STORAGE
TOILET, STAFF
CAD CAM
CAST RM.
LAB WORK
CORRIDOR
C110
LAB
FUME/STORAGE
OVEN
114A
ALCOVE
122A
DME SUPPLY /
DISTRIBUTION
PROSTHETICS
SERVICE
CHECK-IN
TOILET
RECEPTION
PURCHASING
AGENTS
PROGRAM
SUPPORT
ASSISTANT
OFFICE
OFFICE
CORRIDOR
CORRIDOR
C102A
STAIRWELL NO. 1
S1
CORRIDOR
C102B
ELEVATOR
E-1
WORK
129A
WORK
129B
OFFICE
97D
OFFICE
97A
HALLWAY
96A
OFFICE
97B
OFFICE
97E
OFFICE
97C
OFFICE
97F
OFFICE
114B
194 SF
ELEVATOR
LOBBY
FEC
E101
NEW INFILL WALL
DN
DN
DNDN
BUILDING 23
(EXISTING BUSINESS/INDUSTRIAL
OCCUPANCIES, NFPA 101 CH. 39/40)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:4
A
M
23-AL-111
LIFE SAFETY PLAN - FLOOR 01
BHR
35 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/8" = 1'-0"
LIFE SAFETY PLAN - FLOOR 01
1213 13
CARPENTER
STORAGE
G10
CHARGING
STATION
G07
STORAGE
G08
LOCK SHOP
G09
KEY SHOP
G09A
BREAK RM.
G04
STORAGE
G05
CORRIDOR
H003
GENERAL ARCHITECTURAL DEMOLITION NOTES
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENT SET. CONTRACTOR
SHALL CONFIRM ALL ITEMS REQUIRED TO BE DEMOLISHED & EXTENT OF
DEMOLITION BASED UPON THE OVERALL INTENT OF THE ENTIRE DOCUMENT
SET.
2. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY DEMOLITION
WORK TO CONFIRM ACCURACY IN THE DRAWINGS. REPORT ANY
DISCREPANCIES TO CONTRACTING OFFICER. DO NOT SCALE THE DRAWINGS.
FIELD VERIFY ALL DIMENSIONS & EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT
SHALL BE KEPT CLEAN & FREE OF OBSTRUCTIONS AT ALL TIMES. ERECT
BARRICADES & WARNING SIGNS TO DIVERT & WARN PASSERS-BY OF THE
CONSTRUCTION WORK. PROVIDE ENCLOSURES TO SEPARATE WORK AREAS
FROM THE EXISTING FACILITIES THAT MEET NFPA 241.
4. DURING DEMOLITION, PROVIDE PROTECTION FOR ALL EXISTING SURFACES
& CONDITIONS TO REMAIN IN PLACE DURING THE RENOVATION WORK.
SHOULD ANY DAMAGE OCCUR, PATCH & REPAIR ANY DAMAGE TO ADJACENT
FINISHES TO MATCH EXISTING.
5. CONTRACTOR NOT TO BEGIN DEMOLITION WITHOUT AN APPROVED, BY THE
COR, SHORING AND PROTECTION PLAN FOR EXISTING FIBER-OPTIC CABLES.
6. CONTRACTOR TO FIELD VERIFY ON-SITE FIBER-OPTIC CABLE LOCATIONS,
ELEVATIONS, RUNS, AND TERMINATION, AND PULL-BOX LOCATIONS BEFORE
DEMOLITION BEGINS.
7. CONTRACTOR TO COORDINATE WITH VA IT SPECIALIST TO DEVELOP AND
PROVIDE FIBER-OPTIC SERVICE-INTERRUPTION AND CONTINGENCY PLAN.
8. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE
REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO
ADDITIONAL COST TO THE OWNER.
9. EXTENT OF DEMOLTION OF CONNECTING CORRIDOR.
10. CAUTION: ASBESTOS & LEAD ARE PRESENT IN CERTAIN BUILDING
MATERIALS. ALL WORKERS INVOLVED IN DISTURBING EXISTING BUILDING
MATERIALS SHALL HAVE CURRENT 2-HOUR ASBESTOS AWARENESS
TRAINING AS A MINIMUM & SHALL BE INSTRUCTED TO STOP WORK & NOTIFY
COR SHOULD ANY SUSPECT MATERIALS BE ENCOUNTERED. REFER TO
ATTACHED HAZARDOUS MATERIAL REPORTS & SPECIFICATIONS 02-82-11 FOR
ADDITIONAL INFORMATION & REQUIREMENTS.
EXISTING WALL CONSTRUCTION TO
BE DEMOLISHED IN ITS ENTIRETY
EXISTING DOOR & FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
EXISTING WALLS TO REMAIN
DEMOLITION PLAN LEGEND
EXISTING CONCRETE WALL
CONSTRUCTION TO BE DEMOLISHED
EXISTING WINDOW & FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
ARCHITECTURAL DEMOLITION BOUNDARY
DEMOLITION PLAN KEYNOTES
EXISTING CONCRETE RETAINING WALL TO BE REMOVED & REPLACED,
PROVIDE TEMPORARY BRACING & SUPPORT AS REQUIRED.
DEMOLISH EXISTING CONCRETE SIDEWALK & PAD.
EXISTING WINDOW ASSEMBLY TO BE REMOVED IN ITS ENTIRETY.
REMOVE EXISTING DOOR & FRAME ASSEMBLY IN ITS ENTIRETY
EXISTING EXTERIOR WALL ASSEMBLY TO BE DEMOLISHED IN ITS
ENTIRETY.
EXISTING FLOOR FINISHES TO BE REMOVED IN THEIR ENTIRETY.
EXISTING CEILING SYSTEMS TO BE REMOVED IN THEIR ENTIRETY.
EXISTING STAIR TOWER TO BE DEMOLISHED IN ITS ENTIRETY.
PROVIDE TEMPORARY WEATHERPROOF BARRIER AT OPENING.
EXISTING CURTAIN WALL ASSEMBLY TO BE DEMOLISHED IN ITS ENTIRETY.
DEMOLISH EXISTING CONCRETE RAMP/GUARDRAILS IN THEIR ENTIRETY.
DEMOLISH EXISTING CONCRETE STEPS/GUARDRAILS IN THEIR ENTIRETY.
DEMOLISH EXISTING CONCRETE PAD/GUARDRAILS IN THEIR ENTIRETY.
REMOVE EXISTING BUILDING SIGN, DEMOLISH EXISTING CONCRETE BASE
IN ITS ENTIRETY. STLVA TO BE GIVEN RIGHT OF FIRST REFUSAL DURING
DEMOLITION.
SALVAGE EXISTING SITE LIGHTING POLE/HEAD & RETURN TO OWNER,
DEMOLISH EXISTING CONCRETE BASE IN ITS ENTIRETY. TERMINATE
ELECTRICAL WIRING PER CODE.
REMOVE EXISTING DOOR & FRAME ASSEMBLY IN ITS ENTIRETY. REPLACE
WITH NEW WALL INFILL PER ARCHITECTURAL DRAWINGS.
ICRA PASSAGE / CONSTRUCTION ACCESS, 1-HOUR WALL & 45 MIN DOOR
EXISTING UTILITIES VAULT TO REMAIN.
DUST COLLECTOR TO BE RELOCATED PRIOR TO START OF
CONSTRUCTION TO LOCATION COORDINATED WITH COR.
PATCH & REPAIR FACE OF EXISTING CORRIDOR AFTER REMOVAL OF
RAMP/WALL MOUNTED HANDRAILS.
EXISTING CEILING MOUNTED UTILITIES TO REMAIN-IN-PLACE
THROUGHOUT CONSTRUCTION, REF ALL DISCIPLINES FOR ADDITIONAL
INFORMATION.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AD-101
DEMOLITION PLAN - FLOOR 00
BHR
36 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/4" = 1'-0"
DEMOLITION PLAN - FLOOR 00
-A
D -1
DEMO CURB & PAVING TO ACCOMMODATE
NEW ENTRY PLAZA, REF CIVIL FOR EXTENT
PROVIDE BARRIER BETWEEN AREA OF
CONTSTRUCTION & PARKING AREA WHERE
NOT PART OF APPROVED STAGING AREAS,
CONSTRUCTION SHALL NOT INFRINGE ON
ACCESSIBLE PARKING REQUIREMENTS
OVEN
114A
LAB DUSTER
115A
OFFICE
114B
LAB
FUME/STORAGE
CORRIDOR
C102B
DME SUPPLY /
DISTRIBUTION
GENERAL ARCHITECTURAL DEMOLITION NOTES
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENT SET. CONTRACTOR
SHALL CONFIRM ALL ITEMS REQUIRED TO BE DEMOLISHED & EXTENT OF
DEMOLITION BASED UPON THE OVERALL INTENT OF THE ENTIRE DOCUMENT
SET.
2. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY DEMOLITION
WORK TO CONFIRM ACCURACY IN THE DRAWINGS. REPORT ANY
DISCREPANCIES TO CONTRACTING OFFICER. DO NOT SCALE THE DRAWINGS.
FIELD VERIFY ALL DIMENSIONS & EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT
SHALL BE KEPT CLEAN & FREE OF OBSTRUCTIONS AT ALL TIMES. ERECT
BARRICADES & WARNING SIGNS TO DIVERT & WARN PASSERS-BY OF THE
CONSTRUCTION WORK. PROVIDE ENCLOSURES TO SEPARATE WORK AREAS
FROM THE EXISTING FACILITIES THAT MEET NFPA 241.
4. DURING DEMOLITION, PROVIDE PROTECTION FOR ALL EXISTING SURFACES
& CONDITIONS TO REMAIN IN PLACE DURING THE RENOVATION WORK.
SHOULD ANY DAMAGE OCCUR, PATCH & REPAIR ANY DAMAGE TO ADJACENT
FINISHES TO MATCH EXISTING.
5. CONTRACTOR NOT TO BEGIN DEMOLITION WITHOUT AN APPROVED, BY THE
COR, SHORING AND PROTECTION PLAN FOR EXISTING FIBER-OPTIC CABLES.
6. CONTRACTOR TO FIELD VERIFY ON-SITE FIBER-OPTIC CABLE LOCATIONS,
ELEVATIONS, RUNS, AND TERMINATION, AND PULL-BOX LOCATIONS BEFORE
DEMOLITION BEGINS.
7. CONTRACTOR TO COORDINATE WITH VA IT SPECIALIST TO DEVELOP AND
PROVIDE FIBER-OPTIC SERVICE-INTERRUPTION AND CONTINGENCY PLAN.
8. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE
REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO
ADDITIONAL COST TO THE OWNER.
9. EXTENT OF DEMOLTION OF CONNECTING CORRIDOR.
10. CAUTION: ASBESTOS & LEAD ARE PRESENT IN CERTAIN BUILDING
MATERIALS. ALL WORKERS INVOLVED IN DISTURBING EXISTING BUILDING
MATERIALS SHALL HAVE CURRENT 2-HOUR ASBESTOS AWARENESS
TRAINING AS A MINIMUM & SHALL BE INSTRUCTED TO STOP WORK & NOTIFY
COR SHOULD ANY SUSPECT MATERIALS BE ENCOUNTERED. REFER TO
ATTACHED HAZARDOUS MATERIAL REPORTS & SPECIFICATIONS 02-82-11 FOR
ADDITIONAL INFORMATION & REQUIREMENTS.
EXISTING WALL CONSTRUCTION TO
BE DEMOLISHED IN ITS ENTIRETY
EXISTING DOOR & FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
EXISTING WALLS TO REMAIN
DEMOLITION PLAN LEGEND
EXISTING CONCRETE WALL
CONSTRUCTION TO BE DEMOLISHED
EXISTING WINDOW & FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
ARCHITECTURAL DEMOLITION BOUNDARY
DEMOLITION PLAN KEYNOTES
EXISTING CONCRETE RETAINING WALL TO BE REMOVED & REPLACED,
PROVIDE TEMPORARY BRACING & SUPPORT AS REQUIRED.
DEMOLISH EXISTING CONCRETE SIDEWALK & PAD.
EXISTING WINDOW ASSEMBLY TO BE REMOVED IN ITS ENTIRETY.
REMOVE EXISTING DOOR & FRAME ASSEMBLY IN ITS ENTIRETY
EXISTING EXTERIOR WALL ASSEMBLY TO BE DEMOLISHED IN ITS
ENTIRETY.
EXISTING FLOOR FINISHES TO BE REMOVED IN THEIR ENTIRETY.
EXISTING CEILING SYSTEMS TO BE REMOVED IN THEIR ENTIRETY.
EXISTING STAIR TOWER TO BE DEMOLISHED IN ITS ENTIRETY.
PROVIDE TEMPORARY WEATHERPROOF BARRIER AT OPENING.
EXISTING CURTAIN WALL ASSEMBLY TO BE DEMOLISHED IN ITS ENTIRETY.
DEMOLISH EXISTING CONCRETE RAMP/GUARDRAILS IN THEIR ENTIRETY.
DEMOLISH EXISTING CONCRETE STEPS/GUARDRAILS IN THEIR ENTIRETY.
DEMOLISH EXISTING CONCRETE PAD/GUARDRAILS IN THEIR ENTIRETY.
REMOVE EXISTING BUILDING SIGN, DEMOLISH EXISTING CONCRETE BASE
IN ITS ENTIRETY. STLVA TO BE GIVEN RIGHT OF FIRST REFUSAL DURING
DEMOLITION.
SALVAGE EXISTING SITE LIGHTING POLE/HEAD & RETURN TO OWNER,
DEMOLISH EXISTING CONCRETE BASE IN ITS ENTIRETY. TERMINATE
ELECTRICAL WIRING PER CODE.
REMOVE EXISTING DOOR & FRAME ASSEMBLY IN ITS ENTIRETY. REPLACE
WITH NEW WALL INFILL PER ARCHITECTURAL DRAWINGS.
ICRA PASSAGE / CONSTRUCTION ACCESS, 1-HOUR WALL & 45 MIN DOOR
EXISTING UTILITIES VAULT TO REMAIN.
DUST COLLECTOR TO BE RELOCATED PRIOR TO START OF
CONSTRUCTION TO LOCATION COORDINATED WITH COR.
PATCH & REPAIR FACE OF EXISTING CORRIDOR AFTER REMOVAL OF
RAMP/WALL MOUNTED HANDRAILS.
EXISTING CEILING MOUNTED UTILITIES TO REMAIN-IN-PLACE
THROUGHOUT CONSTRUCTION, REF ALL DISCIPLINES FOR ADDITIONAL
INFORMATION.
INFILL TO MATCH EXISTING
ADJACENT FINISHES,
INTERIOR & EXTERIOR
TEMPORARILY BRACE WINDOW
DURING DEMOLITION &
CONSTRUCTION
TRANSOM WINDOW TO REMAIN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AD-111
DEMOLITION PLAN - FLOOR 01
BHR
37 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/4" = 1'-0"
DEMOLITION PLAN - FLOOR 01
1/4" = 1'-0"
DEMO ELEVATION - EAST ENTRY DOOR
GENERAL PARTITION NOTES
1. NOT ALL PARTITION TYPES SHOWN HERE MAY BE USED. REFER TO PLANS FOR LOCATION & TYPES OF EACH
PARTITION.
2. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES OF ALL FIRE & SMOKE WALLS
DESIGNATING THE PARTITION RATING INDICATED ON THE LIFE SAFETY PLAN.
3. REFER TO FINISH SCHEDULE & INTERIOR ELEVATIONS FOR LOCATIONS OF ALL WALL TILE. PROVIDE & INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GWB AT ALL SCHEDULED TILE LOCATIONS. UNLESS NOTED OTHERWISE, TILE SHALL BE INSTALLED PER TILE COUNCIL OF AMERICA'S LATEST STANDARDS FOR EACH TYPE OF
BACKING MATERIAL REPRESENTED IN WALL/PARTITION.
4. ALL SUSPENDED WALLS & PARTITIONS SHALL HAVE GWB WHICH EXTENDS A MINIMUM OF 6" ABOVE THE
SUSPENDED CEILING UNLESS SHOWN &/OR NOTED OTHERWISE BY THE ARCHITECT.
5. REFER TO STRUCTURAL DRAWINGS FOR ALL LOAD BEARING WALL CONDITIONS IN REGARDS TO STRUCTURAL
REQUIREMENTS.
6. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, E.G. WALLS, JAMBS, ETC. SHALL ALIGN ACROSS
VOIDS & JOINTS.
7. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS NOTED OTHERWISE) WHERE DRYWALL CONTINUES ABOVE CEILING & ABOVE THE CEILING LEVEL UP TO THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL HAVE CORNER BEADS MINIMUM FLOOR TO CEILING. ALL PENETRATIONS IN DRYWALL CONSTRUCTION ABOVE FINISHED CEILING SHALL BE EFFECTIVELY SEALED TO PREVENT SOUND
LEAKAGE & FIRE STOPPING TAPE/CAULK AT ALL RATED PARTITIONS.
8. ALL MECHANICAL CHASES & OTHER NOTED CHASES ARE TO EXTEND UP TO THE UNDERSIDE OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS OTHERWISE NOTED, SHALL EXTEND ABOVE THE HIGHEST
ADJOINING CEILING & BE BRACED TO STRUCTURE.
9. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL BE SUPPORTED BY TOP
CHORD OF STRUCTURAL JOISTS & NOT FROM THE METAL DECK.
10.COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF BLOCKING IN WALLS/PARTITIONS. ALL WOOD
BLOCKING IS TO BE FIRE RETARDANT TREATED.
11.IMPACT RESISTANT GWB, WHERE NOTED, IS OPTIONAL ABOVE 8' AFF & BEHIND LOCKERS.
12.SEAL THE TOP & BOTTOM OF WALL AS WELL AS ALL PENETRATIONS WHERE SMOKE PARTITIONS ARE
DESIGNATED ON THE LIFE SAFETY PLAN TO ELIMINATE THE PASSAGE OF SMOKE.
13.ALL PARTITIONS THAT HOST PLUMBING FIXTURES SHALL RECEIVE MOLD / MOISTURE RESISTANT GWB IN LIEU OF
REGULAR GWB.
DETAILSMARK
1A
1B
UNDERSIDE OF
EXISTING
STRUCTURE
CEILING MATERIAL AS
SCHEDULED
WALL FINISH AS
SCHEDULED
5/8" GYP. BD. ONE
SIDE OF 3 5/8" METAL
STUDS AT 16" OC
BASE & FLOORING
AS SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 3 5/8" METAL STUDS
AT 16" OC EXTEND TO UNDERSIDE OF EXISTING
STRUCTURE. SEAL TO EXISTING STRUCTURE WITH
ACOUSTIC SEALANT. ALL JOINTS TAPED.
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 6" METAL STUDS AT 16"
OC EXTEND TO UNDERSIDE OF EXISTING STRUCTURE. SEAL
TO EXISTING STRUCTURE WITH ACOUSTIC SEALANT. ALL
JOINTS TAPED.
TYPE 1
(NON RATED)
F
LO
O R
T O
U N
D E
R S
ID
E
O F
S T
R U
C T
U R
E A
B O
V E
TYPE 2
(NON RATED)
DETAILSMARK
2A
C E
IL
IN
G H
E
IG
H T
R E
: R C
P C
E
IL
IN
G
H E
IG
H
T R
E : R
C P
C E
IL
IN
G H
E
IG
H T
R E
: R C
P 6"
R E
F . A
A
S -6
C .T
. W A
IN
S
C O
T H
E
IG
H T
TILE BACKER
BOARD AS
REQUIRED
1 LAYER 5/8" GYP. BD. ON EACH SIDE OF 3 5/8" METAL
STUDS AT 16" OC EXTEND TO UNDERSIDE OF EXISTING
STRUCTURE. SEAL TO EXISTING STRUCTURE WITH
ACOUSTIC SEALANT. ALL JOINTS TAPED.
UNDERSIDE OF
EXISTING
STRUCTURE
CEILING MATERIAL AS
SCHEDULED
WALL FINISH AS
SCHEDULED
5/8" GYP. BD. ONE
SIDE OF 3 5/8" METAL
STUDS AT 16" OC
BASE & FLOORING
AS SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
F
LO
O R
T O
U N
D E
R S
ID
E
O F
S T
R U
C T
U R
E A
B O
V E
C E
IL
IN
G H
E
IG
H T
R E
: R C
P C
E
IL
IN
G
H E
IG
H
T R
E : R
C P
C E
IL
IN
G H
E
IG
H T
R E
: R C
P 6"
R E
F . A
A
S -6
C .T
. W A
IN
S
C O
T H
E
IG
H T
TILE BACKER
BOARD AS
REQUIRED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AE-001
PARTITION TYPES
BHR
38 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
1 / 23-AE-201
1040 SF
LOBBY
95 SF
EQUIPMENT
ELEVATOR
E
B
A
23-AE-301
205 SF
UTILITY
E004
23-AE-401
23-AE-301
23-AE-301
C
A
23-AE-301
U
Y
V
6 7
8 9 10 11
6.3 7.8 9.7 9.8
W
X
9.3
23-AE-401
Z
6.1
23-AE-501
9.9
2 / 23-AE-202
1 / 23-AE-202
-A
E -2
49'-11"
7'-0" 10'-0" 7'-0" 10'-0" 10'-0" 10'-0"
5'-8" 24'-0" 5'-1" 12'-10 1/2" 10'-6" 2'-3 1/4"
60'-4 3/4"
1'-4" 30'-4"
18'-3"
193 SF
ELEVATOR
LOBBY
515'-1"
DN
UP
1A
1A
1A
1B
1A
1A 1A
M A
T C
H C
O R
R
ID
O R
W
ID
T H
24'-0" CMU 30'-0" CMU
1A
1A
GUARD RAIL
HAND RAIL
GUARD
RAIL
ALIGN
PARTITION ATTACHED TO
BOTTOM OF STRINGER
6 / 23-AE-601
-A
E -6
-A
E -6
-A
E -6
CHASE
2A
POSSIBLE FUTURE
RECEPTION DESK
AREA
CHARGING
STATION
G07
STORAGE
G08
LOCK SHOP
G09
KEY SHOP
G09A
BREAK RM.
G04
STORAGE
G05
PROPOSED SEATING,
VA PROVIDED
LANDING
6'-6" CLEAR 8'-2" STAIR 24'-0" LANDING 25'-0" 1:20 RAMP 5'-0" LANDING 12'-6" 1:20 RAMP
LANDING
5'-8 1/4" CLEAR
6'-10"
6'-2 1/2" C
LE
A R
C
LE
A R
4'-0" 3'-0"
DN DN DN
23-AE-501
EXISTING
UTILITIES
VAULT
7 TREADS @ 14"
4' -4
/2
C
LE
A
R
23-AE-411
4 4
8.5
1A
1A
1A
1A
9.5
515'-8"
515'-1"
6'-0"
12'-0"
DN
513'-2 1/2"513'-10"511'-1"
23-AE-501
515'-1"
CORRIDOR
H003
RADIATOR, REF
MECHANICAL
ROOF
DRAINS
EXISTING INFILTRATION TRENCH, REF CIVIL
2A
EXISTING FIBER LINES ABOVE TO
REMAIN-IN-PLACE THROUGHOUT
CONSTRUCTION
18'-0"
23-AE-501
OPP
23-AE-501
GENERAL NOTES
1. ALL DOOR FRAMES TO BE LOCATED 3" FROM OUTSIDE EDGE OF FRAME TO
FINISH FACE OF ADJACENT WALL UNLESS NOTED OTHERWISE.
2. ALL PARTITIONS TO BE TYPE 5A UNLESS NOTED OTHERWISE, REFERENCE
SHEET GI010 FOR ADDITIONAL INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO OUTSIDE FACE OF STUD FRAMING
WHERE APPLICABLE UNLESS NOTED OTHERWISE.
4. THROUGH-SLAB PENETRATIONS FOR MECHANICAL DUCTWORK SHALL BE
OVERSIZED 2" TO ALLOW FOR DUCT PASSAGE TOLERANCE & APPLICABLE
FIRE SAFING, REFERENCE MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
5. ALIGN FINISH FACE OF NEW CORRIDOR WALLS WITH FINISH FACE OF
EXISTING CORRIDOR WALLS, TYPICAL
6. FURR-OUT AROUND ALL EXPOSED COLUMN PROTRUSIONS, TYPICAL.
7. EXTERIOR SPOT ELEVATIONS INDICATE GENERAL CHANGE IN ELEVATION,
REFER CIVIL & STRUCTURAL FOR ACCURACY.
KEYNOTES
1 48" HIGH CORNER GUARD WITH 3" WINGS, REFERENCE SPEC. SECTION
10 26 00 FOR ADDITIONAL INFORMATION.
SEMI-RECESSED FIRE EXTINGUISHER CABINET, REFERENCE SPEC.
SECTION 10 44 13 FOR ADDITIONAL INFORMATION.
EXPANSION JOINT WITH ABAAS COMPLIANT COVER, REFERENCE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
EXISTING SIDEWALK
MODIFY EXISTING ASSEMBLY TO PROVIDE & MAINTAIN 1-HOUR FIRE
SEPARATION RATING AS REQUIRED.
CONTINUOUS METAL DOWNSPOUT, PRE-FINISHED TO MATCH EXISTING.
THROUGH-WALL SCUPPER & DOWNSPOUT
EXPANSION JOINT & WATERPROOFING @ BUILDING JOIN
LEGEND
PROEJCT SCOPE BOUNDARY
EXISTING WALL TO REMAIN
WINDOW TAG; REF. SHEET AP601
DOOR TAG; REF. AS500
WALL TAG; REF. GI010
FLOOR DRAIN; REF. PLUMBINGFD
A
1i th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AE-101
FLOOR PLAN - FLOOR 00
BHR
39 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/4" = 1'-0"
FLOOR PLAN - FLOOR 00
-A
E -2
1 / 23-AE-201
253 SF
MEZZANINE
95 SF
ELECTRICAL
ELEVATOR
B
A
E101
23-AE-301
23-AE-401
23-AE-301
23-AE-301
EXHAUST FAN, REF.
MECHANICAL
OPEN TO BELOW
B
A
A
A
23-AE-301
-A
D -1
U
23-AE-501
Y
V
6 7
8 9 10 11
6.3 7.8 9.7 9.8
W
X
9.3
23-AE-401
Z
6.1
23-AC-101
9.9
2 / 23-AE-202
1 / 23-AE-202
-A
E -2
194 SF
ELEVATOR
LOBBY
49'-11"
5'-8" 24'-0" 5'-1" 12'-10 1/2" 10'-6" 2'-3 1/4"
60'-4 3/4"
31'-8" 18'-3"
DN
1A
1A
1B
1A
10'-0" 2'-4"
CANOPY ROOF
BELOW
2' -4
'-0
7'-0" 10'-0" 7'-0" 10'-0" 10'-0" 10'-0"
1A
1A
6 / 23-AE-601
-A
E -6
-A
E -6
CHASE
-A
E -6
/4
INFILL @ DEMOLISHED DOOR
PROSTHETICS
RESTORATION
LAB
LAB DUSTER
115A
LAB
FUME/STORAGE
OVEN
114A
DME SUPPLY /
DISTRIBUTION
CORRIDOR
C102B
OFFICE
114B
8 / 23-AE-601
16'-0" LANDING
(6) TREADS @ 14"
7'-0" STAIR
23-AE-501
18'-0" 1:20 RAMP
LANDING
5'-0" CLEAR
30'-8" 1:20 RAMP
5'-0" LANDING
UTILITY ROOM ROOF
'-1
'-1
1"
18'-0" 1:20 RAMP
EXTERIOR SEATING /
SAFETY BARRIER4'
-2
C
LE
A R
4' -2
C
LE
A
R
DN
DN
DNDN
23-AE-412
4' -2
/2
C
LE
A
R
'-1
1" C
LE
A
R
4' -0
2' -0
4' -0
2' -0
4' -0
2' -0
3' -0
3'-0" 2'-0"
8.5
12'-0"
9.5
23-AE-412
528'-0"
528'-0"
528'-0"
526'-2 3/8"
527'-1 3/16"
5' -0
5' -0
C J
CJ
C J
CJ
C J
EXISTING FIBER LINES BELOW TO
REMAIN-IN-PLACE THROUGHOUT
CONSTRUCTION
EXISTING CORRIDOR ROOF
1'-4"
18'-0"
EXPANSION JOINT
AT BUILDING JOIN
GENERAL NOTES
1. ALL DOOR FRAMES TO BE LOCATED 3" FROM OUTSIDE EDGE OF FRAME TO
FINISH FACE OF ADJACENT WALL UNLESS NOTED OTHERWISE.
2. ALL PARTITIONS TO BE TYPE 5A UNLESS NOTED OTHERWISE, REFERENCE
SHEET GI010 FOR ADDITIONAL INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO OUTSIDE FACE OF STUD FRAMING
WHERE APPLICABLE UNLESS NOTED OTHERWISE.
4. THROUGH-SLAB PENETRATIONS FOR MECHANICAL DUCTWORK SHALL BE
OVERSIZED 2" TO ALLOW FOR DUCT PASSAGE TOLERANCE & APPLICABLE
FIRE SAFING, REFERENCE MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
5. ALIGN FINISH FACE OF NEW CORRIDOR WALLS WITH FINISH FACE OF
EXISTING CORRIDOR WALLS, TYPICAL
6. FURR-OUT AROUND ALL EXPOSED COLUMN PROTRUSIONS, TYPICAL.
7. EXTERIOR SPOT ELEVATIONS INDICATE GENERAL CHANGE IN ELEVATION,
REFER CIVIL & STRUCTURAL FOR ACCURACY.
LEGEND
PROEJCT SCOPE BOUNDARY
EXISTING WALL TO REMAIN
WINDOW TAG; REF. SHEET AP601
DOOR TAG; REF. AS500
WALL TAG; REF. GI010
FLOOR DRAIN; REF. PLUMBINGFD
A
1i
KEYNOTES
1 48" HIGH CORNER GUARD WITH 3" WINGS, REFERENCE SPEC. SECTION
10 26 00 FOR ADDITIONAL INFORMATION.
SEMI-RECESSED FIRE EXTINGUISHER CABINET, REFERENCE SPEC.
SECTION 10 44 13 FOR ADDITIONAL INFORMATION.
EXPANSION JOINT WITH ABAAS COMPLIANT COVER, REFERENCE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
EXISTING SIDEWALK
MODIFY EXISTING ASSEMBLY TO PROVIDE & MAINTAIN 1-HOUR FIRE
SEPARATION RATING AS REQUIRED.
CONTINUOUS METAL DOWNSPOUT, PRE-FINISHED TO MATCH EXISTING.
THROUGH-WALL SCUPPER & DOWNSPOUT
EXPANSION JOINT & WATERPROOFING @ BUILDING JOIN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AE-111
FLOOR PLAN - FLOOR 01
BHR
40 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/4" = 1'-0"
FLOOR PLAN - FLOOR 01
ROOF PLAN KEYNOTES
PROVIDE ROOFING CRICKETS WITH MINIMUM 1/4" PER 12" SLOPE WHERE
REQUIRED TO MAINTAIN PROPER DRAINAGE.
SINGLE-PLY FULLY ADHERED TPO ROOFING SYSTEM ON TAPERED
INSULATION WITH 1:48 MINIMUM SLOPE, REFERENCE SPEC. SECTION
07 54 23 FOR ADDITIONAL INFORMATION. DEDUCT ALTERNATE OPTION TO
UTILIZE MODIFIED BITUMEN SYSTEM IN LIEU OF TPO.
INSTALL CONTINUOUS 30" WIDE WALK PAD TO ALL SERVICABLE SIDES OF
ALL ROOF MOUNTED EQUIPMENT, TYPICAL.
PROVIDE LIGHTNING PROTECTION AS REQUIRED, REF. ELECTRICAL
DRAWINGS & SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PREFINISHED METAL THROUGH-WALL SCUPPER & DOWNSPOUT W/
SPLASH-BLOCK
PREFINISHED METAL PARAPET CAP, MATCH PARAPET CAP FINISH @
EXISTING ADJACENT BUILDINGS
THROUGH-WALL OVERFLOW SCUPPER
UPBLAST EXHAUST FAN, REF. MECHANICAL
WALK AREA, ADDITIONAL LAYER ROOFING MATERIAL
CONDENSING UNITS ON PLATFORMS, REF. MECHANICAL
ROOF HOOD, REF. MECHANICAL
ROOFTOP CROSSOVER LADDER
EXPANSION JOINT & WATERPROOFING @ BUILDING JOIN
B
A
U
EXISTING CORRIDOR ROOF
EXISTING BUILDING 23 ROOF
Y
V
6 7
8 9 10
6.3 7.8 9.7 9.8
W
X
9.3
Z
6.1 9.9
NORTH CANOPY
E A
S T
C A
N O
P Y
/4
/4
M
IN
1/4" / 12" MIN 1/4" / 12" MIN
/4
M
IN
/4
M
IN
1/4" / 12" MIN 1/4" / 12" MIN
/4
M
IN
23-AE-121
23-AE-121
23-AE-121
23-AE-121
23-AE-121
23-AE-121
8.5 9.5
1/4" / 12"
SIM
SIM 3
23-AE-121
/4
23-AE-121
SIM
T.O. MASONRY 2
546'-8"
U
METAL COPING SLOPED TO ROOF,
FINISH TO MATCH ANNODIZED
STOREFRONT SYSTEM
COMPRESSION CLIP SYSTEM
ATTACHED TO CMU
COPING ANCHOR
CLIP SYSTEM
CONTINUOUS DRIP EDGE
ROOFING MEMBRANE,
LAPPED OVER BLOCKING &
FASTENED TO FACE OF 2X
ROOFING MEMBRANE
ADHERED TO WALL
SLOPE
BONDING ADHESIVE
FLOOR 01
528'-0"
EXTERIOR INSULATION
FINISH SYSTEM
Z
ROOFING MEMBRANE,
LAPPED OVER FACE
OF EIFS1" RIGID INSULATION
COVER BOARD
2" RIGID INSULATION
4" RIGID INSULATION
ON METAL DECK
CANT STRIP SLOPE
MOISTURE BARRIER
5/8" EXTERIOR SHEATHING
6" METAL STUD FRAMING
METAL PARAPET CAP,
MATCH ENTRY CANOPY
METAL PANEL FINISH
SLOPE
EIFS COATING
ON SHEATHING
5/8" EXTERIOR SHEATHING
STEEL FRAMING,
REF STRUCTURAL
FASCIA PANEL, FINISH TO
MATCH CAMPUS BUILDINGS
W/ SIM DETAIL
RIVET TO FACE OF METAL PANEL
2"x4"x1/8" ALUM ANGLE, PAINTED TO MATCH
METAL PANEL
3 5/8" METAL STUD FRAMING
TAPERED RIGID
INSULATION BLOCKINGCOPING CLEAT
ROOFING
MEMBRANE LAPPED
OVER PARAPET
MEMBRANE
BONDING ADHESIVE
TAPERED RIGID
INSULATION FOR
POSITIVE DRAINAGE
TO SCUPPER
MOISTURE BARRIER
HOT AIR WELD
TPO MEMBRANE FLASHING
BONDING ADHESIVE
1/2" to 3/4"
1/2" to 1"
2 1/256"
8" M
IN
BONDING ADHESIVE
CONT. BEAD OF SEALANT
STAINLESS STEEL
CLAMPING RING
TPO MEMBRANE
FASTENER
NOTE:
GENERAL CONTRACTOR TO
COORDINATE WITH TPO ROOFING
MANUFACTURER'S INSTALLATION
REQUIREMENTS.
VENT STACK PER MEP DWGS.
A
FLASHING WITH SLIP-JOINT
TAPERED RIGID
INSULATION
CANT STRIP
8" REINFORCED
CONCRETE MASONRY
UNITS, REFERENCE
STRUCTURAL DRAWINGS
GFRC SUBFRAMING SYSTEM
GLASS FIBER REINFORCED
CONCRETE PANEL
2" RIGID
INSULATION BOARD
STEEL DECK ON
STEEL JOIST, REF
STRUCTURAL
7 5/8" 4 3/8"
6" RIGID
INSULATION
EXPANSION JOINT
W
4"X8"X1/8" ALUM TUBE,
PAINTED TO MATCH
METAL PANEL
TPO LAPPED THRU
SCUPPER
TPO W/ BONDING
ADHESIVE LAPPING
TOP OF FRAMING
CONTINUOUS SEALANT @
PENETRATION, ALL SIDES
SHEATHING ON 3-5/8"
METAL STUD FRAMING
SLOPE TUBE TO ACHIEVE
POSITIVE DRAINAGE
TAPERED
RIGID INSULATION
TPO W/ BONDING
ADHESIVE ATTACHED
TO RIGID INSULATION
4"
1'-6" @ EAST CANOPY
8" TYPICAL
CORRUGATED METAL PANEL,
MATCH EXISTING CAMPUS PROFILE
SLOPE BRAKE-METAL COPING
RIVETED TO METAL PANEL,
MATCH METAL PANEL FINISH
TAPERED RIGID
INSULATION BLOCKING
COPING CLIP FASTENED
TO FRAMING
RTU CURB
RTU, REF
MECHANICAL
TAPERED RIGID
INSULATION ON
METAL DECK
STEEL TRUSS,
REF. STRUCTURAL
CURB SUPPORTING
STEEL CHANNEL, REF
STRUCTURAL
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2
:0
A
M
23-AE-121
ROOF PLAN
BHR
41 101
AM/JP
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
1/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
N
1/4" = 1'-0"
ROOF PLAN
1 1/2" = 1'-0"
PARAPET CAP @ MASONRY WALL
1 1/2" = 1'-0"
PARAPET CAP @ METAL FRAMING
3" = 1'-0"
SECTION DETAIL @ EAST CANOPY
3" = 1'-0"
PIPING PENETRATION DETAIL
1 1/2" = 1'-0"
ROOF JOIN @ BLDG 23
3" = 1'-0"
SECTION DETAIL @ CANOPY SCUPPER
1" = 1'-0"
SECTION DETAIL @ RTU CURB
FLOOR 00
516'-0"
FLOOR 01
528'-0"
T.O. MASONRY 2
546'-8"
C
23-AE-301
AA
A
6.37.89.8 6.1
T.O. MASONRY 1
544'-8"
12'-0" 16'-8"
2'-0"
EQEQEQEQ
28'-8"
10'-0" 3'-4"
8'-8" 3'-4"
6'-8"
2'-6" 2'-6"
C. CORRIDOR
515'-1"
30'-8"
5'-0" 10'-0" 5'-0"
EQEQ
E001
FLOOR 00
516'-0"
FLOOR 01
528'-0"
T.O. MASONRY 2
546'-8"
B A
B
23-AE-301
A
23-AE-301 UV
T.O. MASONRY 1
544'-8"
8'-8" 3'-4"
8'-8" 3'-4"
5'-0" 3'-6"
2'-0" 16'-8"
12'-0"
6'-8"
10" 1'-4"4
30'-8"
E101
ELEVATION LEGEND
WINDOW TAG; REF. AP601
PATTERN - A
DESIGN OPTION 1: GFRC PANEL SYSTEM W/ CAST REVEALS
DESIGN OPTION 2: EIFS SYSTEM WITH ROUTED REVEALS
A
PATTERN - B
DESIGN OPTION 1: GFRC PANEL SYSTEM W/ CAST REVEALS
DESIGN OPTION 2: EIFS SYSTEM W/ ROUTED REVEALS
ALUMINUM STOREFRONT SYSTEM, CLEAR ANODIZED FINISH,
REF SHEET: AP-601
EMERGENCY OVERFLOW SCUPPER
GLASS FIBER REINFORCED CONCRETE PANELS ON 8"
REINFORCED CMU WALL
PREFINISHED METAL PARAPET CAP, MATCH PARAPET CAP
FINISH @ EXISTING ADJACENT BUILDINGS
PREFINISHED METAL THROUGH-WALL SCUPPER & DOWNSPOUT
W/ SPLASH-BLOCK
ENTRY CANOPY, METAL PANEL FASCIA ON METAL FRAMING,
ROOF SYSTEM SIMILAR TO MAIN-BUILDING ASSEMBLY
EXISTING BUILDING
GFRC PANEL MAJOR BREAK/REVEAL
CONCRETE RETAINING WALL & CONTROL JOINT LAYOUT AS
SHOWN, HAND-RUBBED FINISH
BUILDIN…