This federal contract opportunity notice is for the construction project to create an elevator tower and stairwell within Building 23 at Jefferson Barracks VAMC. The project cost range is between $2,000,000 to $5,000,000. It has a NAICS code of 238220 and small business size standard of $39.5 million. The duration is estimated at 383 calendar days from notice to proceed.
The project is a competitive total set-aside for Service-Disabled Veteran-Owned Small Businesses. The prime contractor must perform at least 15% of general construction labor. Proposals are due as specified in the solicitation to be posted on January 22, 2021. The agency will award without discussions using lowest price technically acceptable procedures. Registration in SAM and VetBiz is required. Only one pre-solicitation site visit will be held and attendance is encouraged.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER, NOR THE PRESENCE OF THE
ENGINEER OR THEIR EMPLOYEES AND SUBCONSULTANTS AT THE CONSTRUCTION SITE,
SHALL RELIEVE THE CONTRACTOR AND ANY OTHER ENTITY OF THEIR OBLIGATIONS,
DUTIES AND RESPONSIBILITIES INCLUDING BUT NOT LIMITED TO, CONSTRUCTION MEANS,
METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES NECESSARY FOR PERFORMING,
SUPERINTENDING OR COORDINATING ALL PORTIONS OF THE CONSTRUCTION WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ANY HEALTH OR SAFETY
PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES. THE ENGINEER AND THEIR
PERSONNEL HAVE NO AUTHORITY TO EXERCISE ANY CONTROL OVER ANY
CONSTRUCTION CONTRACTOR OR OTHER ENTITY OR THEIR EMPLOYEES IN CONNECTION
WITH THEIR WORK OR ANY HEALTH OR SAFETY PRECAUTIONS. THE CONTRACTOR IS
SOLELY RESPONSIBLE FOR THE JOBSITE SAFETY. THE ENGINEER AND THE ENGINEER’S
CONSULTANTS SHALL BE MADE ADDITIONAL INSUREDS UNDER THE CONTRACTOR’S
GENERAL LIABILITY INSURANCE POLICY.
2. ALL DRAWINGS AND SPECIFICATIONS ARE CONSIDERED TO BE A PART OF THE CONTRACT
DOCUMENTS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND
COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF
CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
COR PRIOR TO THE START OF CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY
WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE
REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE
AND AT NO EXPENSE TO THE VA OR ARCHITECT.
3. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE COR SHALL BE NOTIFIED FOR CLARIFICATION.
4. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT
OF NEW WORK.
5. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
6. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH COR.
8. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9. THE CONTRACT DOCUMENTS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE
CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE
AND SAFETY OF WORKMEN DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE,
BUT NOT BE LIMITED TO, BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL
ENGINEER SHALL NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND
DOES NOT IN ANY WAY RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE
ABOVE.
10. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
11. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
12. NO HOLES, NOTCHES, BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
13. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH BIDDER SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS,
TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE
BID SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING
CONDITIONS.
14. SHOP DRAWINGS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
COR. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW BY THE
CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE COR OR
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
15. SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DO NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS AND
SPECIFICATIONS.
GENERAL
DEMOLITION
1. ALL DEMOLITION SHALL BE CARRIED OUT IN SUCH A WAY AS TO NOT DAMAGE
EXISTING ELEMENTS WHICH ARE TO REMAIN.
2. ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING
DEMOLITION WORK SHALL BE REPLACED AT NO ADDED COST. EXISTING
ELEMENTS ARE TO BE PROTECTED TO THE FULLEST EXTENT POSSIBLE TO
REDUCE SUCH DAMAGE TO A MINIMUM.
3. REFER TO ARCHITECTUAL DRAWINGS FOR EXTENTS OF EXISTING BUILDING
DEMOLITION.
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2018
ASCE/SEI 7-16
ACI 318-14
ACI 530-16
AISC 360-16
AISC 341-16, INCLUDING SUPPLEMENTS
VA H-18-8 SEISMIC DESIGN REQUIREMENTS, NOV 1, 2019
2. OCCUPANCY CATEGORY II
3. SEISMIC:
SEISMIC DESIGN CATEGORY D
IMPORTANCE FACTOR 1.0
SOIL CLASSIFICATION PER
GEOTECHNICAL REPORT D
SS 0.47 g S1 0.18 g Sds 0.49 g Sd1 0.25 g
SEISMIC FORCE RESISTING SYSTEM BEARING WALL SYSTEM WITH SPECIAL
REINFORCED MASONRY SHEAR WALLS
R 5 Cd 2.5
ΩO 3.5
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE PROCEDURE
BASE SHEAR, STRENGTH LEVEL V = CS x W = 0.09 x 260 = 23.4 KIPS, EAST-WEST
V = CS x W = 0.09 x 260 = 23.4 KIPS, NORTH-SOUTH
4. WIND:
BASIC WIND SPEED 107 MPH
IMPORTANCE FACTOR 1.0
EXPOSURE CLASS C
MWFRS DESIGN PRESSURE 25 PSF
NET ROOF UPLIFT PRESSURE 15 PSF [LC: 0.9DL + 1.0WL]
C&C DESIGN PRESSURE PER APPLICABLE BUILDING CODE
5. LIVE LOADS:
TYPICAL ROOF 20 PSF (REDUCIBLE)
TYPICAL FLOOR 100 PSF (REDUCIBLE)
CORRIDORS, STAIR & PUBLIC AREAS 100 PSF (UNREDUCIBLE)
HANDRAILS MAX SIMULTANEOUS VERT AND HORIZ THRUST
50 PLF APPLIED AT THE TOP OF THE RAILING OR
200 LBS IN ANY DIRECTION
6. SNOW:
GROUND SNOW 20 PSF
SNOW EXPOSURE FACTOR 1.0
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.0
FLAT-ROOF SNOW 16 PSF
DESIGN SNOW 25 PSF
RAIN-ON-SNOW SURCHARGE 5 PSF
DRIFTING SNOW REFER TO SG-002
7. ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE COMPLETED
STRUCTURE IS PROVIDED BY SPECIAL REINFORCED MASONRY SHEAR WALLS IN EACH
ORTHOGONAL DIRECTION. REFER TO PLANS FOR LOCATIONS. THE ROOF AND FLOOR
DECK SERVE AS HORIZONTAL DIAPHRAGMS DISTRIBUTING THE LATERAL WIND AND
SEISMIC FORCES TO THE VERTICAL LATERAL ELEMENTS WHICH IN TURN CARRY THE
LOAD TO THE BUILDING FOUNDATIONS.
DESIGN CRITERIA AND LOADS
1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT FOR VAMC
BUILDING 23 - ELEVATOR TOWER / STAIRWELL, BY SCI ENGINEERING (SCI No.
2019-0252.10, DATED DECEMBER 2019). REPORT IS ON FILE WITH THE ARCHITECT.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
CONTINUOUS FOOTINGS 2000 PSF
ISOLATED COLUMN FOOTINGS 2400 PSF
FROST DEPTH 2.5 FT
3. EQUIVALENT FLUID PRESSURE FOR RESTRAINED WALLS ARE BASED ON
GRANULAR BACKFILL (1-INCH MINUS)
AT-REST EARTH PRESSURES 60 PSF/FT, DRAINED
ACTIVE PRESSURE 40 PSF/FT, DRAINED
4. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. DO NOT PLACE
BACKFILL BEHIND RETAINING/BASEMENT WALLS BEFORE CONCRETE HAS
ATTAINED SPECIFIED COMPRESSIVE STRENGTH. CONTRACTOR SHALL BRACE OR
PROTECT ALL WALLS BELOW GRADE FROM LATERAL LOADS UNTIL SUPPORTING
FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED AT LEAST 75% OF THE
SPECIFIED 7-DAY STRENGTH MINIMUM. BACKFILLING IS NOT PERMITTED FOR
FOUNDATION WALLS UNTIL SUPPORTED SLAB TOP AND BOTTOM IS IN PLACE OR
THE WALL IS ADEQUATELY BRACED TO RESIST LATERAL LOADS. CONTRACTOR
SHALL PROVIDE FOR DESIGN, PERMITS, AND INSTALLATION OR SHORING AND/OR
SHEETING.
5. EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT
TO EXISTING STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE
FOUNDATIONS, WALLS, SLABS, UTILITIES, ETC.
6. THE MOISTURE CONTENT OF ONSITE CLAYEY SOILS AT THE TIME OF COMPACTION
SHALL BE BETWEEN 2-3% ABOVE OPTIMUM MOISTURE CONTENT.
7. ANY IMPORT FILL SOIL REQUIRED SHALL HAVE A LOW POTENTIAL FOR EXPANSION
AND SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER OF RECORD PRIOR
TO IMPORTING.
8. ALL SITE WORK SHALL BE PERFORMED UNDER THE INSPECTION OF THE SPECIAL
INSPECTION AGENCY. VARIATIONS IN SITE CONDITIONS AND THE GEOTECHNICAL
REPORT SHALL BE REPORTED TO THE COR FOR CLARIFICATIONS PRIOR TO
PROCEEDING.
9. ADEQUATE DRAINAGE SHALL BE PROVIDED BY MEANS OF EITHER WEEP HOLES
WITH PERMEABLE MATERIAL INSTALLED BEHIND THE WALL OR BY MEANS OF A
SYSTEM OF SUBDRAINS. FOR THE SUBDRAIN SYSTEM, THE TOP OF THE
PERFORATED PIPE SHOULD BE BELOW THE BOTTOM OF THE ADJACENT SLAB OR
GRADE AT THE TOE OF THE WALL. DRAINS SHOULD CONSIST OF A DRAIN ROCK
LAYER AT LEAST 12 INCHES THICK THAT EXTENDS TO WITHIN 2 FEET OF THE
GROUND SURFACE. FOUR-INCH-DIAMETER PERFORATED PLASTIC PIPE SHOULD BE
INSTALLED, WITH PERFORATIONS DOWN, ALONG THE BASE OF THE WALL ON A 2-
INCH-THICK BED OF DRAIN ROCK. THE PIPE SHOULD BE SLOPED TO DRAIN BY
GRAVITY TO A SUITABLE DRAINAGE FACILITY. DRAIN ROCK SHOULD CONFORM TO
CALTRANS SPECIFICATIONS FOR CLASS 2 PERMEABLE MATERIAL. A MORE OPEN-
GRADED MATERIAL, SUCH AS 3/4” CRUSHED ROCK, COULD BE USED PROVIDED THE
ROCK IS WRAPPED IN A GEOTEXTILE FILTER FABRIC (MIRAFI 140 N OR EQUIVALENT)
TO REDUCE THE MIGRATION OF FINE-GRADED SOILS INTO THE DRAIN ROCK.
PAVING OR A TWO-FOOT-THICK CAP OF CLAYEY SOIL SHOULD BE PLACED OVER
THE DRAIN ROCK TO INHIBIT SURFACE WATER INFILTRATION. DRAINPIPES SHOULD
OUTLET TO AN APPROPRIATE DRAINAGE FACILITY. ALTERNATIVELY, WALL BACK-
DRAINAGE CAN BE PROVIDED BY PERFORATED DRAINAGE MATERIAL, SUCH AS
MIRADRAIN 6000 OR AN APPROVED EQUIVALENT. THE DRAINAGE MATERIAL CAN BE
INSTALLED ON THE SOIL FACE OF THE BASEMENT WALL AND SHOULD TERMINATE
AT A 4-INCH-DIAMETER PERFORATED PLASTIC PIPE SURROUNDED BY AT LEAST 6
INCHES OF DRAIN ROCK AS DEFINED ABOVE.
10. EXPANSIVE "FAT" CLAYS WERE DISCOVERED ON SITE DURING THE INITIAL
GEOTECHNICAL INVESTIGATIONS. IF PRESENT AT FLOOR SLABS OR AT THE
BEARING ELEVATION OF FOOTINGS AND FOUNDATIONS, THEY MUST BE
OVEREXCAVATED AND REMOVED TO A DEPTH OF 2'-0". REPLACE WITH
COMPACTED GRANULAR FILL OR UNREINFORCED LEAN CONCRETE.
EARTHWORK
1. NEW FOUNDATIONS THAT ARE CONSTRUCTED ADJACENT TO EXISTING
FOUNDATIONS SHALL BE PLACED AT THE SAME ELEVATION. CONTRACTOR SHALL
INVESTIGATE EXISTING CONDITIONS TO ENSURE THAT NEW CONSTRUCTION WILL
NOT UNDERMINE OR COMPROMISE EXISTING FOOTINGS. IF CONDITIONS ARE SUCH
THAT NEW CONSTRUCTION WILL DISTURB THE SOIL BENEATH EXISTING
FOUNDATIONS, THE CONTRACTOR SHALL CONTACT THE AOR AND SEOR FOR
FURTHER INSTRUCTIONS.
2. IF UNDERPINNING OF EXISTING CONSTRUCTION IS REQUIRED, THE CONTRACTOR
SHALL SUBMIT A SCHEDULE OF UNDERPINNING OPERATIONS FOR REVIEW BY THE
AOR AND SEOR.
3. CONTRACTOR SHALL SURVEY EXISTING FOOTING AND WALL ELEVATIONS PRIOR
TO, DURING AND AFTER CONSTRUCTION TO MONITOR POTENTIAL MOVEMENTS.
UNDERPINNING
REINFORCING STEEL
1. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR60 Fy = 60 KSI WELDED WIRE REINFORCING ASTM A1064 Fy = 65 KSI STEEL WIRE ASTM A1064 Fy = 60 KSI
2. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE
OUTERMOST REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3"
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2"
#5 BARS OR SMALLER 1 1/2"
NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
SLABS AND WALLS WITH #11 BARS OR SMALLER 3/4"
3. BAR SPLICES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. ALL
SPLICES SHALL BE CLASS 'B' AS DEFINED IN ACI 318. IF SPLICE LENGTH IS NOT
GIVEN ON THE DRAWINGS, PROVIDE LAP LENGTH (IN INCHES) AS FOLLOWS:
LAP LENGTHS ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS, AND
A MINIMUM COVER OF 1 BAR DIAMETER. FOR DEVELOPMENT LENGTHS, DIVIDE BY
1.3. TOP BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 1'-0" OF
FRESH CONCRETE BELOW.
CAST-IN-PLACE CONCRETE
1. CONCRETE STRENGTHS SHALL CONFORM TO:
2. DRYPACK SHALL BE 1:3-1/2 PORTLAND CEMENT TO SAND WITH A MINIMUM 28-DAY
STRENGTH OF 7000 PSI.
3. LOCATE SAW CUT CONTROL JOINTS IN SLABS-ON-GRADE PER PLAN DETAIL
2/SG-002.
4. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ASSURE
PROPER DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS,
NOTCHES, EDGES OF WALLS/GRADE BEAMS AND PIERS.
5. UNO, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS OR COLUMNS.
6. DO NOT PLACE PIPES, DUCTS, REGLETS OR CHASES IN STRUCTURAL CONCRETE
WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE COR.
7. NOTIFY THE COR 48 HOURS MINIMUM PRIOR TO ALL POURS.
MASONRY
1. MINIMUM 28-DAY COMPRESSIVE STRENGTHS FOR MASONRY CONSTRUCTION
SHALL BE:
DESIGN ASSEMBLY STRENGTH, f'm 2000 PSI
INDIVIDUAL CONCRETE MASONRY UNITS 2800 PSI
MORTAR 1800 PSI
GROUT 2000 PSI
2. MASONRY MATERIALS SHALL CONFORM TO THE FOLLOWING STANDARDS:
CONCRETE MASONRY UNITS (CMU) ASTM C90, GRADE N-1
MORTAR ASTM C270, TYPE S
GROUT ASTM C476
REINFORCING STEEL ASTM A615, GR 60
PLATE AND BENT BAR ANCHORS ASTM A36
SHEET METAL ANCHORS AND TIES ASTM A1008
WIRE MESH TIES ASTM A1064
WIRE TIES AND ANCHORS ASTM A951
ANCHOR BOLTS ASTM A307, GRADE A
3. BAR SPLICES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. IF
SPLICE LENGTH IS NOT GIVEN ON THE DRAWINGS, PROVIDE LAP LENGTHS (IN
INCHES) AS FOLLOWS EXCEPT BARS LARGER THAN #9 SHALL BE MECHANICALLY
SPLICED:
4. GROUT SOLID ALL JAMBS FULL HEIGHT IN LOAD BEARING MASONRY WALLS TO
UNDERSIDE OF LINTEL. EXTEND GROUTED JAMB FROM FACE OF MASONRY
OPENING AT LEAST EQUAL TO THE BEARING LENGTH OF THE LINTEL BEYOND THE
OPENING PLUS 8 INCHES.
5. PROVIDE A MINIMUM OF 1 INCH GROUT BETWEEN MAIN REINFORCING AND/OR
BOLTS AND MASONRY UNIT FACE. VERTICAL REINFORCEMENT SHALL BE
CENTERED IN WALL, UNO.
6. COORDINATE ANY UNIDENTIFIED PIPE OR DUCT PASSING THROUGH STRUCTURAL
MASONRY WALLS, UNLESS NOTED OR DETAILED SPECIFICALLY.
LINTELS
1. PROVIDE LINTELS OVER ALL OPENINGS AND RECESSES IN MASONRY
CONSTRUCTION.
2. PENETRATIONS NOT IDENTIFIED ON THE DOCUMENTS ARE TO BE TREATED IN A
MANNER SIMILAR TO THE IDENTIFIED LOCATIONS. LINTELS OCCURRING IN
EXISTING BEARING WALLS ARE TO BE SIZED ACCORDING TO SIMILAR CONDITIONS
AND SPANS IN THE NEW CONSTRUCTION. LINTELS ARE NOT REQUIRED OVER
OPENINGS 12” WIDE OR LESS AND AT LEAST 1 COURSE BELOW THE TOP OF WALL.
3. UNLESS NOTED OTHERWISE ON PLAN, LINTELS IN NON-BEARING MASONRY CAN BE
SIZED PER THE FOLLOWING:
* ALL ANGLES THAT ARE BACK-TO-BACK SHALL BE WELDED TOP AND BOTTOM 3"
AT 12" OC MINIMUM.
4. BOTTOM PLATE SIZE SHALL BE A MINIMUM OF 3/8” THICK AND A WIDTH OF 3/4” LESS
THAN THE FIELD VERIFIED WALL THICKNESS, UNO. THE PLATE SHALL BE THE FULL
LENGTH OF THE LINTEL MEMBER.
5. ALL LINTELS SHALL HAVE A MINIMUM OF 8” END BEARING AND DO NOT REQUIRE
BEARING PLATES, UNO.
6. ALL LINTELS IN EXTERIOR WALL CONSTRUCTION SHALL BE HOT-DIP GALVANIZED,
UNO.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY
AND CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY
AND CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH
MANUFACTURER’S WRITTEN INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR
TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
EXPANSION ANCHORS
THREADED SCREW ANCHORS
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR
ASTM A193 GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO
COMPONENT STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW
MASONRY, A SCREEN TUBE SHALL BE PROVIDED.
SPAN
0'-0" TO 2'-0"
STEEL OPTION
(FOR EACH 4" OF
MASONRY WIDTH)*
5/16" PLATE
MASONRY
BOND BEAM
8" BLOCK
8" DEEP WITH
(1) #4
2'-0" TO 4'-0" L3 1/2x3 1/2x1/4
8" DEEP WITH
(1) #4
4'-0" TO 6'-0" L4x3 1/2x5/16 (LLV)
12" DEEP WITH
(1) #5
6'-0" TO 8'-0" L5x3 1/2x5/16 (LLV)
12" DEEP WITH
(2) #5
8'-0" TO 10'-0" L6x3 1/2x3/8 (LLV)
16" DEEP WITH
(2) #5
MINIMUM LAP SPLICE LENGTH
BAR SIZE
#3
#4
#5
#6
BAR
SIZE
#3
OTHER
TOP
3000 PSI CONCRETE
OTHER
TOP
4000 PSI CONCRETE
#4 29 38 25 33
#5 36 47 31 41
#6 43 56 37 49
ANCHORED
INTO
GROUTED
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI KWIK BOLT 3 [ESR-1385]
DEWALT POWER STUD+ SD1 [ESR-2966]
SIMPSON WEDGE-ALL [ESR-1396]
UNCRACKED
CONCRETE
HILTI KWIK BOLT 3 [ESR-2302]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
ANCHORED
INTO
GROUTED
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI KWIK HUS-EZ [ESR-3056]
DEWALT WEDGE-BOLT+ [ESR-1678]
SIMPSON TITEN HD [ESR-1056]
UNCRACKED
CONCRETE
HILTI KWIK HUS-EZ [ESR-3027]
DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
ANCHORED
INTO
HOLLOW
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI HIT-HY 270 [ESR-4143]
DEWALT AC 100+ GOLD [ESR-3200]
SIMPSON SET-XP [ESR-0265]
GROUTED
MASONRY
DEWALT AC 100+ GOLD [ESR-3200]
RED HEAD A7 ACRYLIC [ESR-3951]
SIMPSON SET-XP [ESR-0265]
CONCRETE
DEWALT AC 200+ [ESR-4027]
SIMPSON SET-3G [ESR-4057]
HILTI HIT-HY 270 [ESR-4143]
HILTI HIT-HY 200 [ESR-3187]
INTENDED USE
28-DAY
STRENGTH (PSI)
MAX W/C
RATIO
A/E SLUMP
FOOTINGS
FOUNDATIONS
SLAB-ON-GRADE
UNLESS NOTED OTHERWISE
0.45
0.5
0.45
0.45
N/A
5-8%
N/A
5-8%
1"-4"
4"-6"
1"-4"
1"-4"
8" CMU
10" CMU
12" CMU
f'm = 2000 PSI
16. ELEVATIONS ARE BASED ON THE FIRST FLOOR CIVIL ELEVATION OF ( +516'-0" ) WHERE IT
MEETS THE EXISTING BUILDING.
17. EXISTING CONDITIONS:
A. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
DRAWINGS FOR JEFFERSON BARRACKS DINING HALL BUILDING NO. 23, PROJECT
NUMBER 1154, DATED MARCH 12, 1937, AND BY LIMITED FIELD TAKE-OFF BY IMEG AS
PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
B. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE COR SO PROPER CLARIFICATION MAY BE MADE. MODIFICATION OF
CONSTRUCTION DETAILS SHALL NOT BE MADE WITHOUT WRITTEN APPROVAL OF THE
COR.
STEEL
1. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
WIDE FLANGE SHAPES ASTM A992 Fy = 50 KSI OTHER ROLLED SHAPES ASTM A36 Fy = 36 KSI HSS SECTIONS, SQ/RECT ASTM A500, GR B Fy = 46 KSI BASE AND CONNECTION PLATES ASTM A36 Fy = 36 KSI ANCHOR RODS ASTM F1554, GR 36 Fy = 36 KSI HIGH STRENGTH BOLTS ASTM F3125, GR A325 Fv = 120 KSI HIGH STRENGTH TWIST-OFF BOLTS ASTM F3125, GR F1852 Fv = 120 KSI
HEAVY HEX NUTS ASTM A563
WASHERS ASTM F436
HEADED STUDS ASTM A108, TYPE B
ELECTRODES FOR ARC WELDING AWS 5.1, E70XX
2. HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH AISC
“SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS”.
REFER TO DETAILS FOR BOLT SIZE AND MATERIAL ASTM DESIGNATION.
3. USE TENSION-CONTROL, “TWIST-OFF”, BOLTS FOR ALL HIGH STRENGTH BOLTS
REQUIRING FULL TENSION AS INDICATED ON THE DRAWINGS.
4. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM F3125, GRADE A325N, UNO.
5. STANDARD BOLT HOLES IN STEEL SHALL BE 1/16 INCH LARGER IN DIAMETER THAN
NOMINAL SIZE OF BOLT USED, UNO.
6. BOLTS IN SLOTTED HOLES SHALL BE LOCATED IN THE CENTER OF THE HOLE
AFTER FIELD ASSEMBLY IS COMPLETE, UNLESS DETAILED OTHERWISE.
7. WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE,
USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360, SECTION J2.4.
8. FIELD CONNECTIONS SHALL BE WELDED OR BOLTED. SHOP CONNECTIONS SHALL
BE WELDED, UNO. WELDS INDICATED WITH A SHOP WELD SYMBOL MAY BE MADE
IN THE FIELD WITH THE APPROVAL OF THE STRUCTURAL ENGINEER. LOCATIONS
OF ALL FIELD WELDS SHALL BE CLEARLY SHOWN ON THE SHOP DRAWINGS.
WELDS SHALL BE DESIGNED TO BE FULLY EQUIVALENT IN STRENGTH TO BOLTED
CONNECTIONS DETAILED TO MINIMIZE BENDING IN THE CONNECTION.
9. HEADED STUDS:
A. STUDS SHALL BE AUTOMATICALLY END WELDED IN ACCORDANCE WITH THE
MANUFACTURER’S RECOMMENDATIONS IN SUCH A MANNER AS TO PROVIDE
COMPLETE FUSION BETWEEN THE END OF THE STUD AND THE PLATE. THERE
SHOULD BE NO POROSITY OR EVIDENCE OF LACK OF FUSION BETWEEN THE
WELDED END OF THE STUD AND THE PLATE. THE STUD SHALL DECREASE IN
LENGTH DURING WELDING APPROXIMATELY 1/8” FOR 5/8”ø AND SMALLER AND 3/16” FOR LARGER THAN 5/8”ø. WELDING SHALL BE DONE ONLY BY QUALIFIED
WELDERS APPROVED BY THE INSPECTION AGENCY.
10. REFER TO DRAWINGS FOR DETAIL OF DECK OPENINGS. REFER TO
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, ETC. FOR EXACT
SIZE, LOCATION, AND COUNT OF REQUIRED OPENINGS.
11. CUTS, HOLES, OPENINGS, ETC., REQUIRED IN STRUCTURAL STEEL MEMBERS FOR
THE WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS.
BURNING OF HOLES AND CUTS IN THE FIELD SHALL NOT BE ALLOWED, EXCEPT BY
WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. NO HOLES SHALL
BE CUT IN STRUCTURAL STEEL BY OTHER TRADES UNLESS SHOWN ON
STRUCTURAL DRAWINGS OR APPROVED IN WRITING BY THE STRUCTURAL
ENGINEER.
12. STRUCTURAL STEEL STAIR FRAMING CONFIGURATION AND CONNECTIONS ARE TO
BE DESIGNED AND DETAILED BY THE CONTRACTOR.
STEEL JOISTS
1. ATTACH STEEL JOIST TO SUPPORT AS FOLLOWS:
WHERE WELDS OR BOLTS ARE INDICATED, WELD/BOLT TO BE INSTALLED ON BOTH SIDES OF JOIST SEAT.
2. DESIGN JOIST SEAT FOR 1650 LB ROLLOVER LOAD FOR K-SERIES JOIST ONLY.
3. JOISTS SHALL BE DESIGNED FOR A MAXIMUM LIVE LOAD DEFLECTION OF L/360, UNO.
4. PROVIDE BRIDGING PER SJI SPECIFICATIONS. DESIGN AND PROVIDE UPLIFT BRIDGING TO WITHSTAND A NET UPLIFT PRESSURE AS INDICATED WITHIN THE DESIGN CRITERIA AND LOADS NOTES. WHERE BRIDGING INTERFERES WITH MECHANICAL OR OTHER TRADE INSTALLATIONS, THE FABRICATOR SHALL REMOVE THE BRIDGING AFTER THE STEEL DECK IS IN PLACE AND REPLACE AS DIRECTED BY THE JOIST MANUFACTURER.
5. ERECTOR SHALL FOLLOW MANUFACTURER’S AND STEEL JOIST INSTITUTE’S GUIDELINES FOR ERECTION
STABILITY AND HANDLING.
6. WHERE STEEL COLUMNS ARE NOT FRAMED IN AT LEAST TWO DIRECTIONS WITH STRUCTURAL STEEL
MEMBERS, JOISTS AT COLUMN LINES SHALL BE FIELD BOLTED.
7. DO NOT APPLY CONCENTRATED LOADS TO THE JOISTS WITHOUT WRITTEN APPROVAL FROM THE JOIST
MANUFACTURER. ALTERNATELY, JOISTS MAY BE REINFORCED IN THE FIELD FOR SUPPORT OF
CONCENTRATED LOADS PER DETAIL 4/SF-503.
STEEL DECK
1. DECK SIZE AND GAUGE INDICATED ON THE DRAWINGS ARE BASED ON THE FOLLOWING:
A. VULCRAFT 2018 CATALOG FOR GRAVITY DESIGN LOADS AND UNSHORED CONSTRUCTION SPANS.
B. STEEL DECK INSTITUTE (SDI) DIAPHRAGM DESIGN MANUAL 3RD EDITION FOR DIAPHRAGM LOADS.
2. STEEL DECK GALVANIZING SHALL CONFORM TO ASTM A653 WITH A MINIMUM COATING OF G60.
3. ALL DECK SHALL MEET THE MINIMUM TYPE AND GAUGE INDICATED ON THE DRAWINGS, AND AS FOLLOWS:
4. PROVIDE 16 GAUGE WELD WASHERS AT PUDDLE WELD CONNECTIONS TO 24 GAUGE AND LIGHTER STEEL
DECKS.
5. USE SUMP PANS AT ALL ROOF DRAINS. MINIMUM THICKNESS FOR SUMP PANS SHALL BE 14 GAUGE.
6. DO NOT PLACE PIPES, DUCTS, REGLETS OR CHASES IN COMPOSITE FLOOR SYSTEMS WITHOUT APPROVAL
OF THE STRUCTURAL ENGINEER.
7. DO NOT EXCEED 25 LBS PER HANGER AND A MINIMUM SPACING OF 2’-0” ON CENTER WHEN ATTACHING TO STEEL ROOF DECK. THIS 25 LBS LOAD AND 2’-0” SPACING INCLUDES ADJACENT MECHANICAL, ELECTRICAL, AND ARCHITECTURAL ITEMS HANGING FROM THE DECK. IF THE HANGER RESTRICTIONS CANNOT BE ACHIEVED, SUPPLEMENTAL FRAMING SUPPORTED OFF STEEL FRAMING WILL NEED TO BE ADDED. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING LOCATION AND WEIGHT OF ALL THE
ELEMENTS BEING HUNG.
8. CORRUGATED FORM DECK GAUGES SHOWN ON THE DRAWINGS ARE INTENDED TO SUPPORT THE WEIGHT OF THE WET CONCRETE PLUS A CONSTRUCTION LIVE LOAD OF 20 PSF WITHOUT INTERMEDIATE SHORING BASED ON A THREE SPAN CONTINUOUS CONDITION. DECK MANUFACTURER SHALL EVALUATE OTHER SPAN CONDITIONS FOR DEFLECTION WHICH SHALL NOT EXCEED L/180 NOR 1/8 INCH UNDER THE UNIFORMLY DISTRIBUTED CONCRETE DEAD LOAD AND NOTE AREAS WHICH WILL REQUIRE SHORING TO CONTROL
DEFLECTION AND/OR MEET ALLOWABLE STRESSES.
JOIST
TYPE/SERIES
K
FILLET
WELD SIZE
WELD
LENGTH (IN)
BOLT DIAMETER
(IN)
BOLT
MATERIAL STEEL MASONRY
DETAILS WITH WELD
INFORMATION
DETAILS WITH BOLT
INFORMATION
MINIMUM END
BEARING (IN)
1/8 2 1/2 A307 2 1/2 4
TYPE
1.5" B (ROOF)
GAUGE lx Sx Fy
20 0.201 0.234 33
STRUCTURAL TESTS AND INSPECTION
1. UNLESS NOTED, MATERIALS SHALL CONFORM AND TESTS AND INSPECTIONS SHALL BE PERFORMED BY
THE INSPECTION AGENCY WHO IS APPROVED THE ARCHITECT AND THE STRUCTURAL ENGINEER.
CONTINUOUS AND PERIODIC TESTING AND INSPECTION SHALL CONFORM TO IBC CHAPTER 17, AND AS
FOLLOWS:
A. CONCRETE CONSTRUCTION 1705.3
B. MASONRY CONSTRUCTION 1705.4
C. STEEL CONSTRUCTION 1705.2 AND CHAPTER N OF AISC 360
D. SOILS 1705.6
E. WIND RESISTANCE 1705.11
F. SEISMIC RESISTANCE 1705.12 AND 1705.13
2. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
A. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE
STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL AT LEAST TWO WEEKS PRIOR TO
COMMENCEMENT OF WORK.
B. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION
PROGRAM.
C. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT,
STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED
AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
D. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH
THE APPROVED PLANS AND SPECIFICATIONS.
4. CONTINUOUS INSPECTION REQUIRED FOR: MASONRY BLOCK LAYING AND GROUTING, ALL FIELD AND SHOP WELDING EXCEPT MINOR OR TACK WELDING, COMPLETE PENETRATION GROOVE WELDS, HIGH
STRENGTH BOLT INSTALLATIONS, AND STEEL DECK WELDING.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
F U
L L
Y S
P R
IN
K
L E
R E
D
-J a n
-2
:0
:2
P M
23-SG-001
STRUCTURAL GENERAL NOTES
WHL
MLA
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
01/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE, ST. LOUIS, MO 63125
STRUCTURAL ABBREVIATION KEY
EOS
WWR
WT
WP
VERT
UNO
TYP
tf
TEMP
T.O.
STIFF
SQ
SL
SIM
SCHED
RTU
REQD
REINF
R
PSI
PSF
P.H.
PCF
PC
OH
OC
NTS
NIC
(N) N
MTL
MIN
MECH
MAX
LO
LLV
LLH
LL
LB
K, KIP
JT
INT
IN
HORIZ
GB
GALV
FT
FRMG
F.O.W.
F.O.S.
FLR
FIN
FDN
f'c
EXT
EXP
(E)
EW
EQUIP
EQ
ELEC
EL
EF
EA
DET
DL
CONT
CONC
CMU
CLR
CFSF
BP
BM
B.O.
ARCH
EOD
AHU
VIF
VWA
DWG
EDGE OF SLAB
WELDED WIRE REINFORCING
WEIGHT
WORK POINT
VERTICAL
UNLESS NOTED OTHERWISE
TYPICAL
BEAM FLANGE THICKNESS
TEMPERATURE
TOP OF
STIFFENER
SQUARE
SNOW LOAD
SIMILAR
SCHEDULE
ROOF-TOP UNIT
REQUIRED
REINFORCING, -MENT, -ED
RADIUS
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
PENTHOUSE
POUNDS PER CUBIC FOOT
PIECE
OPPOSITE HAND
ON CENTER
NOT TO SCALE
NOT IN CONTRACT
NEW
NORTH
METAL
MINIMUM
MECHANICAL
MAXIMUM
LOW
LONG LEG VERTICAL
LONG LEG HORIZONTAL
LIVE LOAD
POUND
KILOPOUND (1,000 POUNDS)
JOINT
INTERIOR
INCH
HORIZONTAL
GRADE BEAM
GALVANIZED
FOOT
FRAMING
FACE OF WALL
FACE OF STUD
FLOOR
FINISH, -ED
FOUNDATION
CONCRETE COMPRESSIVE STRENGTH
EXTERIOR
EXPANSION
EXISTING
EACH WAY
EQUIPMENT
EQUAL
ELECTRICAL
ELEVATION
EACH FACE
EACH
DETAIL
DEAD LOAD
CONTINUOUS
CONCRETE
CONCRETE MASONRY UNIT
CLEAR
COLD FORM STEEL FRAMING
BASE PLATE
BEAM
BOTTOM OF
ARCHITECT, -URE, -URAL
DIAMETER
AT
NUMBER OR POUNDS
EDGE OF DECK
AIR-HANDLING UNIT
DEGREE
VERIFY IN FIELD
VERIFY WITH ARCHITECTURAL DRAWINGS
DRAWING
SC TC WITH CLASS A FAYING SURFACE
TC PRE-TENSIONED BOLT
bf BEAM FLANGE WIDTH
TRANS TRANSVERSE
LSV
LSH
LONG SIDE VERTICAL
LONG SIDE HORIZONTAL
SLRS SEISMIC LOAD RESISTING SYSTEM
Ø
ABBR: DESCRIPTION:
SLAB DEPRESSION-3"
ANCHOR BOLTA.B.
BF BRACE FRAME
B.O.F. BOTTOM OF FOOTING
BOTT BOTTOM
BTWN BETWEEN
CL CENTERLINE
COL COLUMN
DIA DIAMETER
DIM DIMENSION
DWL DOWEL
ELEV ELEVATOR
FTG FOOTING
Fy YIELD STRESS
GA GAGE OR GAUGE
HI HIGH
HSB HIGH STRENGTH BOLT
KSP KIPS PER SQUARE FOOT
LONG LONGITUDINAL
LT WT LIGHTWEIGHT
M.B. MACHINE BOLT
MANUF MANUFACTURER
OPNG OPENING
PL PLATE
PLF POUNDS PER LINEAR FOOT
SCBF SPECIAL CONCENTRIC BRACE FRAME
SEP'N SEPARATION
SOG SLAB ON GRADE
SP SPACE(S)
SPEC SPECIFICATION(S)
STL STEEL
SUPPT SUPPORT
SYM SYMMETRICAL
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
THK THICK
W/ WITH
BLKG BLOCKING
B.N. BOUNDARY NAILING
E.N. EDGE NAILING
F.N. FIELD NAILING
PLYWD PLYWOOD
PTDF PRESSURE TREATED DOUGLAS FIR
SHTG SHEATHING
T&B TOP AND BOTTOM
EJ EXPANSION JOINT (1/2", UNO)
AOR ARCHITECT OF RECORD
SEOR STRUCTURAL ENGINEER OF RECORD
COR CONTRACTOR OFFICER'S REPRESENTATIVE
STRUCTURAL SYMBOL LIST
SYMBOL: DESCRIPTION:
FLOOR OPENING
SLAB DEPRESSION
REVISION TRIANGLE - NUMBER
INDICATES REVISION NUMBER
DRAIN/OVERFLOW
HEADED STUD ANCHORS ON BEAMS
TOP OF STEEL FRAMING ELEVATION
ABOVE ELEVATION +0' - 0"
WELD SIZE, LENGTH & SPACING, ETC.
WHERE SHOWN ONE SIDE OF SYMBOL
REFERENCE LINE, IT IS TYPICAL TO
OPPOSITE SIDE IF SYMBOL OCCURS
OPPOSITE SIDE, UNO
STEP IN FOOTING
CANTILEVER MOMENT CONNECTION
NEW GRIDLINE
EXISTING GRIDLINE
(+16' - 3")
-1"
S
5/16 1-18
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
S300
SIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE KEY:
NEW WORK
(DARK SOLID LINE)
NEW WORK UNDERGROUND OR UNDER OTHER FRAMING AND EXISTING TO BE
REMOVED
(DARK DASHED LINE)
EXISTING TO REMAIN
(LIGHT SOLID LINE)
GRID OR CENTERLINE
MATERIAL LEGEND:
CONCRETE - CAST-IN-PLACE
CONCRETE - EXISTING
EARTH
GRAVEL OR GRANULAR FILL
GROUT OR DRYPACK OR SAND
MASONRY
METAL / COLD-FORM STUD
STEEL
COLUMN DESIGNATION
BASE PLATE MARK
SF# ( +X' - X" )
FOOTING MARK (TOP ELEVATION)
x#
BP #
N O R
HT
25 PSF
ADDITIONAL
16 PSF
ADDITIONAL
15 PSF
ADDITIONAL
16 PSF
ADDITIONAL
0 PSF
ADDITIONAL
0 PSF
ADDITIONAL
25 PSF
ADDITIONAL
25 PSF
ADDITIONAL
NOTES:
1. SNOW DRIFT LOADS ARE IN ADDITION TO THE SG-001 FLAT-ROOF
SNOW LOAD. REFER TO DESIGN CRITERIA ON SHEET SI-001.
2. ROOF DEAD LOAD = 20 PSF.
4' - 6"
0 PSF
ADDITIONAL
7' - 0"
5' - 0"
4' - 0"
0 PSF
ADDITIONAL
25 PSF
ADDITIONAL
16 PSF
ADDITIONAL
0 PSF
ADDITIONAL
N E
W E
X
IS
T
IN
G
SEE CIVIL FOR EXTERIOR
RAMP CONSTRUCTION
N E
W E
X
IS
T
IN
G
(3) EQ SP
RAMP DOWN
R A
M P
D O
W N
NOTES:
1. REFER TO FOUNDATION / FLOOR 00 PLAN, SHEET SB-101, FOR DIMENSIONS
OF SLABS, RAMP, AND FOUNDATIONS.
2. SEE DETAILS 1, 2, AND 3/SB-501 FOR ADDITIONAL INFORMATION.
3. MINIMUM CONTROL JOINT SPACING SHALL BE AS FOLLOWS:
THICKNESS
(IN)
MAX JOINT
SPACING (FT)
4 12 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
F U
L L
Y S
P R
IN
K
L E
R E
D
-J a n
-2
:0
:2
P M
23-SG-002
SNOW DRIFT PLAN, SYMBOLS AND
ABBREVIATIONS
WHL
MLA
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
01/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE, ST. LOUIS, MO 63125
N O R
HT
1/8" = 1'-0"1
SNOW DRIFT LOAD PLAN
3D
VIEW – FOR REFERENCE ONLY
N O R
HT
1/8" = 1'-0"2
CONTROL JOINT SPACING PLAN
NOTE:
1. 3D VIEW IS FOR REFERENCE ONLY - NOT FOR CONSTRUCTION. REFER
TO PLANS, DETAILS AND SPECIFICATIONS FOR ACTUAL CONSTRUCTION
REQUIREMENTS.
PERIMETER OF
NEW BUILDING
4 4 4
SD-102
SD-102
EXISTING CONDUITS TO
REMAIN, COORD WITH
ARCH AND MEP
NEW SHORING - SEE
PLAN AND KEYNOTES
REMOVE WALL BRACKETS AND
PROVIDE NEW HANGERS OR
BRACKETS TO TEMPORARILY
SUPPORT CONDUITS WHICH ARE
TO REMAIN FROM EXISTING ROOF
OR NEW SHORING WALL
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
BUILDING 23
AREA OF
WORK
N
F U
L L
Y S
P R
IN
K
L E
R E
D
-J a n
-2
:0
:1
P M
23-SD-101
STRUCTURAL DEMOLITION AND
PHASING PLAN
WHL
MLA
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
01/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE, ST. LOUIS, MO 63125
N O R
HT
1/4" = 1'-0"1
STRUCTURAL PLAN FOR TEMPORARY
SUPPORT OF EXISTING CONDUIT
NO SCALE2
TEMPORARY SHORING
ADDITIONAL INFORMATION.
THAN 10'-0" ON CENTER. REFER TO SECTIONS FOR
BETWEEN WINDOWS AT A SPACING THAT IS NOT MORE
4. NEW TEMPORARY CFSF SHEAR WALL. LOCATE WALLS
CORRIDOR UNTIL THE NEW WALL IS COMPLETE.
BARRIER TO PROTECT THE INTERIOR OF THE EXISTING
THE CONTRACTOR SHALL PROVIDE A WEATHER-PROOF
FOOTINGS, BEARING WALL, AND STEEL SUPERSTRUCTURE.
THIS WALL CAN BE REMOVED AS REQUIRED FOR NEW
IN-PLACE AND CONDUITS AREA ADEQUATELY SUPPORTED,
3. = AFTER THE TEMPORARY SHORING IS
REFER ALSO TO PHOTO 2/SD-101.
STEEL. THE USE OF WOOD SHORING IS NOT PERMITTED.
COLD-FORM STEEL FRAMING STUDS OR STRUCTURAL
DESIGNED AND INSTALLED BY CONTRACTOR USING
2. = TEMPORARY SHORING WALL, TO BE
ENTIRETY.
SECOND FLOOR LEVEL SHALL BE REMOVED IN THEIR
FLOOR SHALL REMAIN. ALL WALLS AND ROOF ABOVE THE
BUILDING SHELL IS COMPLETE. THE EXISTING SECOND
AND ENCLOSE EXISTING CONDUITS UNTIL NEW
REMAIN DURING CONSTRUCTION TO PROTECT, SUPPORT,
1. = EXISTING FIRST FLOOR CORRIDOR TO
KEYNOTES:
REFER TO SHEET SG-001 FOR LOAD CRITERIA.
AND BRACE IT AGAINST LATERAL SEISMIC MOVEMENT.
REQUIRED TO SUPPORT THE WEIGHT OF THE CONDUITS
SPECIFIED, AND LOCATED BY THE CONTRACTOR AS
STRUCTURE. THE HANGERS SHALL BE DESIGNED,
TO INSTALL NEW CONDUIT HANGERS FROM THE NEW
DEMOLISH THE EXISTING CORRIDOR ROOF AS REQUIRED
ENCLOSES THE EXISTING CORRIDOR, SELECTIVELY
4. ONCE THE NEW BUILDING IS CONSTRUCTED AND FULLY
ELEMENTS AT ALL TIMES.
ACTIVITY, NEW CONSTRUCTION, AND EXPOSURE TO THE
SHALL BE PROTECTED FROM DAMAGE BY DEMOLITION
3. THE SUSPENDED CONDUITS IDENTIFIED ON THIS PLAN
IDENTIFICATION, SIZE, PURPOSE, ROUTING, AND FUNCTION.
CONCERNING THE CONDUITS, WHICH INCLUDES
BY OTHER DISCIPLINES FOR ADDITIONAL INFORMATION
OF THE SUSPENDED CONDUITS. REFER TO DOCUMENTS
TO THE GRAVITY SUPPORT AND LATERAL STABILITY
2. THE INFORMATION ON THIS PLAN IS LIMITED EXCLUSIVELY
THE CONTRACTOR.
ITEMS TO REMAIN IS THE SOLE RESPONSIBILITY OF
OPERABILITY, AND FUNCTIONALITY OF THE EXISTING
MEANS AND METHODS. THE SAFETY, PROTECTION,
PERIOD. IMEG HAS NO CONTROL OVER THE CONTRACTOR'S
AND IN OPERATION THROUGHOUT THE CONSTRUCTION
EXISTING CORRIDOR WHICH MUST REMAIN PROTECTED
CONDUITS, PIPES, AND OTHER UTILITIES WITHIN THE
CONTINUITY AND SUPPORT OF EXISTING SUSPENDED
INFORMATION AND CONVENIENCE IN MAINTAINING
1. THIS PLAN IS PROVIDED FOR THE CONTRACTOR'S
NOTES:
SD-101
10121
FLOOR
EL (515' - 1")
FLOOR 01
EL (528' - 0")
ROOF
EL (542' - 2 3/4")
FLOOR 00
EL (516' - 0")
SEE NOTES 1-3
CONCRETE SLAB ON METAL
DECK - SEE PLAN
METAL ROOF DECK AND
FRAMING - SEE PLAN
(E) FIRST FLOOR CORRIDOR WALLS
TO REMAIN UNTIL BUILDING SHELL
IS COMPLETE.
CONSTRUCT TEMPORARY CFSF
SHEAR WALL AT LOCATIONS
SHOWN ON PLAN, TO CONSIST OF
600S162-68 STUDS @ 24" OC, WITH
DOUBLE STUDS AT EACH END;
CONSTRUCT WALL AS TALL AS
POSSIBLE WITH IMPACTING
CONDUITS WHICH ARE TO REMAIN
ANCHOR END STUDS TO (E) WALL
WITH 3/4" EPOXY ANCHORS @ 24"
OC, 6" MIN EMBED (4 ANCHORS
PER SIDE, MINIMUM)
ANCHOR BASE TRACK TO (E)
CONCRETE SLAB WITH 5/8"
EXPANSION ANCHORS @ 24" OC, 3"
MIN EMBEDMENT (4 ANCHORS MIN)
NOTES:
1. CONTRACTOR TO IDENTIFY AND PROTECT EXISTING CONDUITS
THAT ARE TO REMAIN IN OPERATION THROUGH THE
CONSTRUCTION PERIOD.
2. AFTER THE BUILDING SHELL IS COMPLETE, PROVIDE NEW
CONNECTIONS, HANGERS, ETC., FROM THE NEW STRUCTURE TO
SUPPORT (E) CONDUITS.
3. THE (E) CORRIDOR SHALL BE REMOVED IN ITS ENTIRETY AFTER
THE CONDUITS ARE SECURED.
4. CONSTRUCT NEW MASONRY WALL AND FOOTING AS REQUIRED
PER PLANS AND DETAILS.
5. IF (E) FOOTING AND (E) CORRIDOR INTERFERES WITH PLACEMENT
OF NEW FOUNDATIONS, REFER TO 3/SD-102..
68 GA x 6" THICK STRAP CROSS
BRACING, EACH SIDE; ANCHOR
ENDS OF STRAP TO DOUBLE STUD
WITH (6) #12 SCREWS, AND
ANCHOR TO EACH CROSSING
STUD WITH (1) #12 SCREW
TEMPORARY CFSF SHORING
WALL, BY CONTRACTOR
(E) FIRST FLOOR CORRIDOR ROOF
TO REMAIN UNTIL BUILDING SHELL
IS COMPLETE.
(E) FOOTING AND
FOUNDATION WALL
NEW MASONRY WALL - SEE
PLANS AND DETAILS
SEE NOTES 4 - 5
1' - 6"
REMOVE (E) CORRIDOR
STRUCTURE ABOVE
FIRST FLOOR
FLOOR
EL (515' - 1")
FLOOR 01
EL (528' - 0")
ROOF
EL (542' - 2 3/4")
FLOOR 00
EL (516' - 0")
SEE NOTES 1-3
(E) FIRST FLOOR CORRIDOR
ROOF TO REMAIN UNTIL
BUILDING SHELL IS COMPLETE.
METAL ROOF DECK AND
FRAMING - SEE PLAN
(E) FIRST FLOOR CORRIDOR WALLS
TO REMAIN UNTIL BUILDING SHELL
IS COMPLETE.
CONSTRUCT TEMPORARY CFSF
SHEAR WALL AT LOCATIONS
SHOWN ON PLAN, TO CONSIST OF
600S162-68 STUDS @ 24" OC, WITH
DOUBLE STUDS AT EACH END;
CONSTRUCT WALL AS TALL AS
POSSIBLE WITH IMPACTING
CONDUITS WHICH ARE TO REMAIN
ANCHOR END STUDS TO (E) WALL
WITH 3/4" EPOXY ANCHORS @ 24"
OC, 6" MIN EMBED (4 ANCHORS
PER SIDE, MINIMUM)
ANCHOR BASE TRACK TO (E)
CONCRETE SLAB WITH 5/8"
EXPANSION ANCHORS @ 24" OC, 3"
MIN EMBEDMENT (4 ANCHORS MIN)
NOTES:
1. CONTRACTOR TO IDENTIFY AND PROTECT EXISTING CONDUITS
THAT ARE TO REMAIN IN OPERATION THROUGH THE
CONSTRUCTION PERIOD.
2. AFTER THE BUILDING SHELL IS COMPLETE, PROVIDE NEW
CONNECTIONS, HANGERS, ETC., FROM THE NEW STRUCTURE TO
SUPPORT (E) CONDUITS.
3. THE (E) CORRIDOR SHALL BE REMOVED IN ITS ENTIRETY AFTER
THE CONDUITS ARE SECURED.
68 GA x 6" THICK STRAP CROSS
BRACING, EACH SIDE; ANCHOR
ENDS OF STRAP TO DOUBLE STUD
WITH (6) #12 SCREWS, AND
ANCHOR TO EACH CROSSING
STUD WITH (1) #12 SCREW
(E) FIRST FLOOR CORRIDOR
WALLS TO REMAIN UNTIL
BUILDING SHELL IS COMPLETE.
DOWELS - SIZE AND SPACING
TO MATCH VERTICAL CMU
WALL REINFORCING. CENTER
DOWEL IN CMU
CONCRETE SLAB-ON-
GRADE - SEE
FOUNDATION PLAN
#5 @ 12" OC, DRILL
AND EPOXY INTO (E)
CONCRETE, 8" EMBED
M
IN
EL (SEE PLAN)
T.O. SLAB
EL (SEE PLAN)
T.O. FOOTING
APPROXIMATE GRADE
CMU WALL - SEE PLAN
NOTES:
1. IF THE EXISTING FOOTING INTERFERES WITH PLACEMENT OF THE NEW
FOOTING, THE CONTRACTOR MAY USE THIS DETAIL AS AN ALTERNATE
TO THE TYPICAL FOOTING SECTIONS.
G E
N E
R A
L N
O T
E S
L A
P S
P L
IC
E P
E R
SEE PLAN
THICKNESS
8" HOOK
EXTERIOR FINISH -
SEE ARCH
EL (SEE PLAN)
T.O. FDN WALL
(E) FOOTING
REMOVE (E)
FOUNDATION WALL
AS REQUIRED FOR
NEW CONSTRUCTION
IF BAR IS OVER EXISTING
FOOTING, DOWEL AND EPOXY
WITH 6" EMBEDMENT
IF BAR IS OVER NEW
CONCRETE, PROVIDE 8" HOOK
1' - 0" MIN
E X
IS
T
IN
G
M A
T C
H
C L
(2) #5 BARS
FOUNDATION WALL
PER 7/SB-501
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
F U
L L
Y S
P R
IN
K
L E
R E
D
-J a n
-2
:0
:1
P M
23-SD-102
BUILDING SECTION
Author
Checker
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
01/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE, ST. LOUIS, MO 63125
3/8" = 1'-0"1
BUILDING SECTION
3/8" = 1'-0"2
BUILDING SECTION
3/4" = 1'-0"3
FOOTING SECTION
10122
N E
W E
X
IS
T
IN
G
A
CF3.0
C F
.0
C F
.0
CF2.5
C F
.5
C F
.5
CF2.33
MW1
M W
MW1
M W
M W
MW3
M W
SB-501
SB-501
SB-502
SB-501
T.O. SLAB
EL ( +516' - 0" )
CF2.0
C F
.5
STOOP
C F
.0
SB-501
SB-501
SB-501
SB-503
/8
/2
12' - 6 7/8" 7 5/8" 10' - 6" 1' - 0" 1' - 6"
(V
IF
(V
IF
/4
(V
IF
/8
(E) CORRIDOR
AND SLAB, TO
REMAIN
EL ( +515' - 1" )
T.O. SLAB
SB-502
_____ 1
SB-502
SB-502
SB-502
EL ( +515' - 1" )
T.O. SLAB
EL ( +515' - 0 5/8" )
T.O. SLAB
S
S L O
P E
SB-501
CF3.0
S
S
S
EL ( +513' - 0" )
T.O. FOOTING
EL ( +513' - 0" )
S
S
EL ( +516' - 0" )
( +511' - 4" )
( +512' - 8" )
( +511' - 4" )
( +512' - 8" )
( +514' - 8" )
EL ( +516' - 0" )
T.O. FDN WALL
( +513' - 0" )
C F
.5
( +515' - 4" )
( +512' - 0" )
T.O. FDN WALL
1' - 0" 34' - 7 3/8"
SB-501
( +516' - 0" )
T.O. FDN WALL
S
S
EL ( +528' - 0" )
T.O. FDN WALL
SB-502
6.3 7.8 9.3 9.7 9.8 9.9
U
V
W
Y
Z
6.1
X
SF3.0
T.O. SLAB
SIDEWALK LANDING - SEE CIVIL
M W
T.O. FDN WALL
( +514' - 8" )( +512' - 0" ) ( +512' - 0" )
( +514' - 8" )
C F
.0
EL ( +515' - 8" )
WITH STAIR MANUF)
5' - 3" (COORD
SB-502
SIM
5' - 8" 24' - 0" 5' - 1" 12' - 10 1/2" 10' - 6" 2' - 3 1/4"
60' - 4 3/4"
1' - 0"
3' - 9 1/4" 4' - 2 3/4"
1' - 0"
15°
8" 10' - 6" 1' - 0" 1' - 4 1/2"
1' - 0"
EJ
8" 6' - 0" 11' - 4" 5' - 4" 8"
1' - 0"
H SS12x4x3/8
BP2
H SS12x4x3/8
BP2
SF3.0 SF3.0
RAMP DOWN RAMP DOWN
SB-502
8' - 6"
8' - 10" 2' - 8 1/2"
/2
/8
/4
:2
EL ( +515' - 1" )
T.O. SLAB
RAMP DOWN
1:20
11' - 8"
2' - 6 5/8"
(SEE CIVIL FOR SLOPE)
(SEE CIVIL FOR SLOPE)
1' - 0" 5' - 2"
S
( +511' - 4" )
( +509' - 4" )
S
( +509' - 4" )
( +511' - 4" )
( +513' - 0" )
( +512' - 0" )
T.O. PIT SLAB
C F
.3
C F
.3
SB-502
_____ 3
SB-502
SB-502
SB-502
S
EL ( +516' - 0" )
T.O. FDN WALL
EL ( +517' - 4" )
T.O. FDN WALL
SIDEWALK LANDING - SEE CIVIL
SLOPE TOP OF WALL
EL ( +511' - 4" )
T.O. FOOTING
EL ( +517' - 4" )
T.O. RETAINING WALL
T.O. RETAINING WALL
SLOPE TOP OF WALL
EL ( +515' - 8" )
T.O. RETAINING WALL
EL ( +515' - 3" )
S
E J
SB-503
H SS6x
6x 3/
BP1
SF3.0
SB-501
8.5 9.5
H SS6x
6x 3/
BP1
SF2.0
R A
M P
D O
W N
1' - 0"
( +514' - 5" )
( +515' - 0" )
SB-501
6' - 0"
11' - 0"
TYP
MW1
12 13
SEE SF-101 FOR
CONTINUATION
OF FOOTING
SEE SF-101 FOR
CONTINUATION
OF FOOTING
(E) BUILDING
COLUMN
(E) BUILDING
COLUMN
(E) BUILDING
COLUMN
EL ( +528' - 0" )
T.O. FDN WALL
8' - 0"
SB-503
/1
/8
/1
75°
(E) BUILDING
COLUMN
(E) BUILDING
COLUMN
SB-502
18' - 0" 18' - 0" 25' - 10 1/2"
FACE OF (E)
BUILDING
FACE OF EXISTING
BUILDING BEYOND
SB-503
( +514' - 8" )
/2
0' - 7 5/8"
( +514' - 8" )
105°
1' - 0"
C F
.5
BUILDING 23
AREA OF
WORK
TEMPORARY CORRIDOR -
REFER TO ARCHITECT
FOR DETAILS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
VA Health Care System Approval:
Brad Petrovic, Project Manager Gary Drikow, Chief of Design and Construction Kevin Knight, Contracting Officer
Revision: Date:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2020
MO ENGR REG. NO. 2014031351, EXP. 12/31/2020
STRUCTURAL /
CIVIL ENGINEER
IMEG CORP.
15 SUNNEN DR., SUITE 104
ST. LOUIS, MO 63143
(314) 645-1132
MECHANICAL / ELECTRICAL /
PLUMBING / TECHNICAL ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
ELEVATOR CONSULTANT
KENNETH H. LEMP ELEVATOR
CONSULTANT, INC.
211 3RD STREET
VALLEY PARK, MO 63088
(636) 861-2722
ENVIRONMENTAL
ENGINEER
RIVER FRONT SAFETY & HEALTH, LC
1139 OLIVE STREET, SUITE 300
ST. LOUIS, MO 63101
(314) 436-9192
F U
L L
Y S
P R
IN
K
L E
R E
D
-J a n
-2
:0
:1
P M
23-SB-101
FOUNDATION PLAN - FLOOR 00
WHL
MLA
BID DOCUMENTS
CREATE ELEVATOR TOWER &
STAIRWELL, BUILDING 23
01/22/2021
657-19-128JB
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE, ST. LOUIS, MO 63125
N O R
HT
1/4" = 1'-0"1
FOUNDATION / FLOOR 00 PLAN
FIELD VERIFY DEPTH AND EXTENTS.
PLAN DIMENSIONS ARE 3'-11" x 3'-11". CONTRACTOR TO
13. PER ORIGINAL DRAWINGS, (E) FOOTING EL ( +514' - 10" ).
FIELD VERIFY DEPTH AND EXTENTS.
PLAN DIMENSIONS ARE 6'-1" x 3'-10". CONTRACTOR TO
12. PER ORIGINAL DRAWINGS, (E) FOOTING EL ( +512' - 9" ).
11. CFSF WALL HOLDOWN LOCATION. REFER TO 7/SB-503.
2'-6" BELOW GRADE.
10. TURN- DOWN SLAB TO EXTEND TO A MINIMUM OF
9. STEP TOP OF FOUNDATION WALL.
DEPRESSION.
AND VERTICAL REINFORCING INTERRUPTED AT THE
THE SLAB ELEVATION AT DOORS. STOP HORIZONTAL
8. DEPRESS TOP OF FOUNDATION WALL 0'-8" LOWER THAN
ELEVATION.
7. SLOPE TOP OF SLAB AS REQUIRED TO MATCH EXISTING
THE EXISTING CONCRETE.
MAY BE INFILLED AND PLACED OVER THE TOP OF
OVERLAPS THE EXISTING FOOTING, THE NEW CONCRETE
SPLICE REQUIREMENTS. IF THE NEW FOOTING
REINFORCEMENT. REFER TO GENERAL NOTES FOR
DOWELS TO MATCH SIZE AND SPACING OF VERTICAL
VERTICAL DOWELS INTO EXISTING CONCRETE.
CUT BLOCKS TO MATCH COURSING AND EPOXY
6. IF NEW MASONRY WALL BEARS ON EXISTING FOOTING,
8" MINIMUM.
REINFORCEMENT INTO EXISTING CONCRETE,
TO MATCH. DOWEL AND EPOXY HORIZONTAL
PROVIDE ADDITIONAL FOOTING STEPS AS REQUIRED
FOOTINGS, MATCH EXISTING BOTTOM ELEVATION (VIF).
5. WHERE NEW FOOTINGS ARE ADJACENT TO EXISTING
PLANS.
AND COORDINATE WITH CIVIL AND ARCHITECTURAL
TOP OF SLAB ELEVATION VARIES. REFER TO PLAN
4. 4" CONCRETE SIDEWALK WITH 6x6 - W2.1xW2.1 WWR.
FOR DETAILS.
WITH ELEVATOR MANUFACTURER. REFER TO 10/SB-501
3. SUMP PIT. COORDINATE LOCATION, SIZE, AND DEPTH
REINFORCEMENT.
MANUFACTURER. REFER TO SECTIONS FOR SLAB
ELEVATION AND COORDINATE WITH ELEVATOR
2. 12" THICK ELEVATOR PIT SLAB. REFER TO PLAN FOR SLAB
EACH WAY, CENTERED IN SLAB.
SUBSTITUTED WITH A MAT OF #3 BARS @ 16" OC,
AT CONTRACTOR'S OPTION, THE WWR MAY BE
WWR. TOP OF SLAB ELEVATION VARIES - SEE PLAN.
1. 4" CONCRETE SLAB ON GRADE WITH 6x6 - W2.1xW2.1
KEYNOTES:
AND UTILITY LOCATIONS.
AND MEP DRAWINGS FOR ADDITIONAL INFORMATION
FOUNDATIONS, REFER TO 6/SB-503. REFER TO CIVIL
12. WHERE SITE UTILITIES CROSS THROUGH EXTERIOR
AND ELEVATIONS.
SIDEWALK CONSTRUCTION, SIDEWALK SLOPES,
ARCHITECTURAL SITE PLANS FOR SITE ELEVATIONS,
11. EXCEPT WHERE NOTED, REFER TO CIVIL AND
DETAIL ON SF-502.
10. BP# INDICATES STEEL BASE PLATE. REFER TO
9. REFER TO 2/SG-002 FOR CONTROL JOINT SPACING PLAN.
CONSTRUCTION DETAILS.
8. REFER TO 1 AND 3/SF-501 FOR TYPICAL MASONRY WALL
FOR SCHEDULE.
7. MW# INDICATES MASONRY WALL. REFER TO 2/SF-501
BARS.
6. REFER TO 4/SB-501 FOR TYPICAL FOOTING CORNER
DETAIL.
5. REFER TO 5/SB-501 FOR TYPICAL FOOTING STEP
4. REFER TO SB-501 FOR TYPICAL FOUNDATION DETAILS.
GRADE DETAILS.
3. REFER TO 1, 2 AND 3/SB-501 FOR TYPICAL SLAB ON
SCHEDULE THIS SHEET.
INDICATES CONTINUOUS FOOTING. REFER TO
2. SF#.# INDICATES SPREAD FOOTING. CF#.#
CONTRACTOR TO VERIFY.
1. (E) FINISHED FLOOR ELEVATION ( +516' - 0" ),
NOTES:
SPREAD FOOTING SCHEDULE
MARK LENGTH WIDTH THICKNESS
REINFORCING
LONG DIRECTION SHORT DIRECTION
SF2.0 2' - 0" 2' - 0" 1' - 4" (3) #4 (3) #4
SF3.0 3' - 0" 3' - 0" 1' - 4" (3) #5 (3) #5
CONTINUOUS FOOTING SCHEDULE
MARK WIDTH THICKNESS
REINFORCING
LONG DIRECTION SHORT DIRECTION
CF2.0 2' - 0" 1' - 4" (2) #5 WALL DOWELS
CF2.33 2' - 4" 1' - 0" (3) #5 WALL DOWELS
CF2.5 2' - 6" 1' - 4" (3) #5 #5 @ 16" OC
CF3.0 3' - 0" 1' - 4" (3) #5 #5 @ 12" OC
10123
W E
X
IS