This solicitation seeks a firm fixed-price contract for non-personal services to provide all plant, labor, transportation, materials, tools, equipment, appliances and supervision necessary for the construction of the MILCON project "Base-wide Fire Alarm Repair and Upgrade" at Camp Murray, WA. The project will modernize the fire alarm system with addressable Monaco brand panels that have the ability to integrate with the existing Mass notification and Warning System. An option is included to integrate the fire alarm system into the existing American Signal Corp brand Compulert Nexgen system. The magnitude is estimated between $1,000,000 and $5,000,000. Interested offerors must be registered in the System for Award Management. All inquiries must be submitted in writing to 194.wg.fal.msc.contracting@us.af.mil. The solicitation is issued by the Department of the Army National Guard.
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Detect Manage
Record
227-95x-xx, 227-96x-xx Rev C 6/18/15
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
Description MAAP-X is the premier addressable integrated fire and mass notification system (MNS) control panel from Monaco Enterprises, Inc. The MAAP-X comprises a single touch screen enclosure incorporating fire monitoring, addressable point reporting, live voice, and pre-recorded MNS functions which are compatible with the D-21 system.
Key Features Fully integrated panel combines transceiver, addressable fire panel and mass notification Addressable point reporting Touch-screen graphical interface with capability to extend to local operating console/remote display units (LOC/RDU)
Live and pre-recorded MNS functions and fire voice evacuation
Up to 100W of audio amplification without booster circuits
Built-in synchronized NAC, up to eight Class B or four Class A
Compatible with the D-21 Central Receiving System Single, seamless upgrade from previous M-series
Monaco panels Flexible configuration achieved with addition of speaker amplifier and addressable cards
Upgrading existing Monaco 28 in. or larger M-series fire-only panels to MAAP-X fire-and-MNS panels is easy using the MAAP-X upgrade kit. The kit provides a cost-effective method to meet current building fire MNS requirements while reusing the existing enclosure, conduits, wiring, and addressable devices.
MAAP-X Base Panel The base MAAP-X includes:
A master control unit (MCU) with a color touch screen for fire and MNS operation.
An MNS message card with nine standard pre-recorded messages An Analog Addressable Controller II (AAC II) backplane One Addressable Driver Card (ADC) One Speaker Output Card (SOC)
On-board circuits:
Eight Class B or four Class A non-loop-powered
Initiating Device Circuits (IDCs) Eight Class B or four Class A regulated or synchronized programmable Notification Appliance Circuits (NACs)
Four Form C programmable relays Autosensing power supply, 120/240 VAC 50/60 Hz Dual-rate 4A 24 VDC battery charger that meets the requirements of NFPA 72 and UL 864 24 VDC auxiliary power FSK interface for communication to D-21 through the standard integrated transceiver, or optional network or fiber module
FM
APPROVED
Made in USA
MAAP-X Addressable Fire Alarm MNS Voice Evacuation Panel 227-95x-xx, 227-96x-xx
Addressable Fire Alarm Control Panels with MNS
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Main Panel and LOC/RDU Touch-Screen Features
Fire and MNS operation for first responders Simple English messages identify alarm, trouble, and supervisory conditions Displays zone input or addressable device pro-grammable descriptions User-defined device and zone descriptions Panel reset, alarm/trouble silence LED status indicators for primary/secondary power, radio communication, general alarm, and trouble Panel maintenance functions, such as:
– Zone and sensor device enable/disable
– Walktest
– Radio key-up test
– Enhanced diagnostic information—identifying panel troubles and loop faults Panel history Built-in microphone or optional push-to-talk microphone for live voice
Message Card Standard card has eight default pre-recorded MNS messages and one fire evacuation message for a total of nine pre-recorded messages.
User-defined messages available with a customer-option message card with eight user-defined pre-recorded MNS messages and one user-defined pre-recorded fire evacuation message.
AAC II Backplane
The AAC II supports a combination of up to eight cards.
The cards can be either ADCs (up to seven, one included) or SOCs (up to four, one included).
ADC (for addressable devices) Each ADC supports one Class A/X or two Class B Signaling Line Circuits (SLCs) for addressable device pathways. Each card supports 99 smoke or heat detectors and 99 monitor or control modules.
Options such as sounder or relay bases and fault isola-tor modules reduce the number of addressable devices (198 device equivalents maximum).
SOC (for speakers)
Each SOC supports one Class A or two Class B speaker circuits for speaker audio pathways. Each card provides 25 VRMS, 32W of speaker audio power.
LOC/RDU Touch Screen LOC/RDUs are a critical part of every installation, placed at strategic locations throughout the building. With an advanced approach to technology, Monaco’s LOC/RDU touch screen combines the pre-recorded and live-voice message functions of an MNS LOC with the functions of a typically separate Fire Alarm Panel Remote Control Annunciator into one combination LOC/RDU.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Features LOC/RDU provides the same functions as the main panel, at key locations within the protected building
Built-in live-voice microphone or optional push-to-talk microphone
Three user programmable modes of operation based on LOC/RDU location needs—Fire and MNS, Fire only, and MNS only.
Each LOC/RDU touch screen provides a visual indication for active pre-recorded or live-voice MNS.
Touch screen displays an explanation message if a lower priority MNS request is denied
Additional MAAP-X Features Legacy zone-only fire reporting, or point reporting for each addressable device Pre-tone and post-tone options for MNS messages Messages settable for time-outs of 1–60 minutes MNS display screen can be customized by user MNS prioritized by LOC/RDU locations and message numbers, with live-voice override
Text display notification using 2010 NFPA 72 compliant textual visual boards for emergency notification programmed to match MAAP-X MNS pre-recorded messages
Local speaker for MNS messages and audible alert for alarm, trouble, and supervisory notification
Additional battery backup expansion options available for increased operation times during AC power failures
Transfer between AC primary power and battery secondary power is automatic
Sensor Grouping
With point reporting enabled, MAAP-X supports the Monaco sensor-group feature:
Smoke detectors function together to control local sounder bases and reduce nuisance alarms Beneficial in dormitory environments, reducing costly response runs and building evacuations for isolated incidents
MAAP-X Configuration Programming Software MAAP-X Planner Kit allows the user to program the panel. Planner functions include:
Uploading/downloading the MAAP-X program file to/from the panel Creates a MAAP-X configuration file that can be imported into the D-21 Central; manual information entry to D-21 not needed
Central reporting modes:
– Point reporting (addressable device addresses with zone reporting to D-21 and MNS operation)
– Legacy (zone reporting to D-21 and MNS operation)
– Stand-alone (in-building fire and MNS operation only) Setting D-21 Central communication modes—radio or hard-wire (Ethernet, fiber), single comm or dual comm
Configuring fire and MNS device circuits
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Configuring MAAP-X and LOC/RDUs for fire and MNS operation
Provides the ability to keep panel configuration files for backup
Windows® (XP, 7.0, 8.0) compatible Monaco MAAP-X Planner software
Define zone and device descriptions
MAAP-X D-21 Configuration Options
Panel Configuration
A configuration-file copy is stored at the D-21 that can be used as a backup.
Mass Notification In-building, pre-recorded, and live-voice MNS from the main panel, LOC/RDUs, and from D-21 Central systems configured for base-wide MNS
Preconfigured MNS message files streamed from D-21 Central systems configured for broadcast MNS
Fire Zone Reporting MAAP-X can be configured for legacy fire non-point-reporting, compatible with D-21 Central systems configured with an FSK interface
MAAP-X displays the address of the individual device in alarm on its touch screen and reports up to 64 fire zones to the D-21
Fire Point Reporting
MAAP-X:
Supports Monaco’s advanced fire point reporting and is compatible with D-21 Central systems con-figured for point reporting
Individually reports alarm and trouble status of addressable sensors and monitor modules in real-time to the D-21 Central
D-21 Connectivity MAAP-X supports radio (site-specific narrowband frequency) and hard-wire communication User selects central communication mode— primary only or primary with fallback to secondary Only one antenna system needed for radio communication; hard-wire options include Ethernet and fiber-optic.
Panel Clock Synchronization D-21 can be configured to synchronize the MAAP-X internal clock and calendar Synchronizing eliminates the need to adjust each panel for daylight-saving time
Software Version
MAAP-X requires D-21 software with MAAP-X support.
An RFM-X is required for point reporting and MNS.
Hardware Specifications
Electrical IDC (Zone Inputs) Capacity: 4 Class A or 8 Class B
Non-loop-power: 4 VDC with EOL, 12 VDC at 25 mA max.
EOL: 3.9 kΩ 1/2W, Class B only Max. loop resistance: 50Ω per leg
NAC (Notification Appliance Circuit
Outputs)
Capacity: 4 Class A or 8 Class B, polarity reversing EOL: 3.9 kΩ 1/2W, Class B only NACs programmed as “regulated”:
Power: 24 VDC 1A Max. loop resistance: 1.5Ω per leg NACs programmed as “special application” (synchronized strobes):
Power: 24 VDC 2A Max. loop resistance: 0.75Ω per leg Wiring: Standard fire-alarm-rated cable
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Environmental
Ordering Information
Panels Integrated Radio, Surface- and Flush-mount
SLC (Addressable) Per ADC:
2 Class B or 1 Class A/X SLC input(s) 99 smoke or heat sensors 99 monitor or control modules Power: 0–29 VDC polling protocol Supervision: open, short, ground fault Max. loop resistance: 40Ω per leg Wiring: Unshielded twisted pair
Speaker Circuits Per SOC: 2 Class B or 1 Class A output(s) Power: 25 VAC RMS, 32W max. each, 100W total Supervision: open, short, ground fault EOL: 3.9 kΩ 1/2W, Class B only Max. loop resistance: 1.5Ω per leg Wiring: Standard fire-alarm-rated cable
AUX PWR Power: 24 VDC 2A Supervision: none Max. loop resistance: 1Ω per leg Wiring: Standard fire-alarm-rated cable
Relays, K1–K4 Contact rating: 30 VDC at 2A max.
Supervision: none
Radio Output Power 4W minimum (2W, some frequencies)
Battery Backup Standard: 2 rechargeable 12V/18 Ah Integrated charger: supervised dual-rate, meets NFPA 72 and UL 864 requirements,
27.6 VDC 4A
Low battery alert: 20.4 VDC Low battery disconnect: 18.5 VDC
AC Power 3-wire autosensing, 120/240 VAC 50/60 Hz 2.2/1.2A
Radio Narrowband radio meets requirements of the National Telecommunications and Information Administration Manual of Regulations and Procedures for Federal Frequency Management. FCC certified.
Operating Temperature 32 to 120°F (0 to 49°C)
Relative Humidity 0–90% noncondensing
Part Number Description
227-955-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-956-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-957-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
60" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-965-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-966-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Hard-wire Only (Ethernet), Surface- and Flush-mount
Europe, Surface- and Flush-mount
227-968-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 4X surface-mount red enclosure
24" H x 24" W x 8" D Two 12V/18 Ah batteries
227-969-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 3R surface-mount red enclosure
24" H x 24" W x 8" D Two 12V/18 Ah batteries
*Specify frequency (-xx) when ordering.
Part Number Description
227-955-EN MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries Does not support D-21 Central live voice; for options contact Monaco.
227-956-EN MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries Does not support D-21 Central live voice; for options contact Monaco.
Part Number Description
227-965-EN MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries Does not support D-21 Central live voice; for options contact Monaco.
227-966-EN MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries Does not support D-21 Central live voice; for options contact Monaco.
227-955-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-956-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-957-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
60" H x 18" W x 3.6" D Two 12V/18 Ah batteries
Part Number Description
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Associated Parts
MNS Message Card Kit
227-965-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
28" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-966-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43" H x 18" W x 3.6" D Two 12V/18 Ah batteries
227-968-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 4X surface-mount red enclosure
24" H x 24" W x 8" D Two 12V/18 Ah batteries
227-969-CE* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm, Europe:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 3R surface-mount red enclosure
24" H x 24" W x 8" D Two 12V/18 Ah batteries
*Specify frequency (-xx, -CE) when ordering.
Part Number Description
176-194-00 Addressable Driver Card (ADC), supports up to 198 addressable devices on an SLC—1 Class A or 2 Class B SLCs
176-272-00 Speaker Output Card (SOC), 25 VAC RMS, 32W, 1 Class A or 2 Class B speaker circuits
710-072-01 LOC/RDU with touch screen, fire/MNS, 19" H, surface-mount, 115/230 VAC, 50/60 Hz, 72-hour battery backup
710-072-02 LOC/RDU with touch screen, fire/MNS, 19" H, flush-mount, 115/230 VAC, 50/60 Hz, 72-hour battery backup
176-268-02 Isolated multiplexer PCB for LOC/RDU touch screen connection; one PCB for up to 8 LOC/RDUs (must be ordered separately for systems with LOC/RDUs)
122-012-00 Handheld Push to Talk Microphone and holder for use on LOC/ RDUs, includes 2 foot cable for connection to LOC/RDU
122-012-05 Handheld Push to Talk Microphone in Red Enclosure 6"x 8"x 3" with window, includes 15 foot cable for connection to MAAP-X
227-912-xx* MAAP-X upgrade kit for existing 28" or larger M-series fire panels (M-1, M-2, MAAP(+)) or spare Electronics Package for MAAP-X installs
205-032-00 MAAP Printer Kit, includes power cable, ink cartridge, optoisolator with power cable, RJ-45 to DB-25 female adapter, and RJ-45 cable
400-712-00 Battery, gel type, rechargeable, 12V/18 Ah, two required
081-156-00 Battery enclosure, red, 18" H x 12" W x 6" D, two each 12V/26 Ah gel-type batteries (P/N 400-701-00)
207-625-00 MAAP-X Addressable Planner kit for Windows®, CD, programming cable, 9-pin serial adaptor
*Specify frequency (-xx) when ordering.
Part Number Description
326-M00-01 MAAP-X standard message card—8 MNS, 1 fire, for 9 total pre-recorded messages. These are summaries, not the full-message text; voice gender is female for all messages:
Message 1 Emergency, evacuate to designated area Message 2 Bomb threat, evacuate at nearest exit Message 3 Severe weather warning Message 4 Intruder, follow designated pre-plan Message 5 Shelter in-place Message 6 Emergency, use alternate exit Message 7 Emergency has ended Message 8 Test of Monaco Mass Notification System Message 9 Fire emergency, leave by nearest exit
326-M01-01 MAAP-X customer option message card—8 MNS, 1 fire, for 9 total pre-recorded messages:
Contact Monaco for the forms needed to order this message set and have it installed on the card before MAAP-X panel ships. Message information must be provided at time of ordering.
326-M10-01 MAAP-X customer option message card field upgrade kit—8 MNS, 1 fire, for 9 total pre-recorded messages:
Contact Monaco for the forms needed to order this upgrade to replace existing messages at your site.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Wiring Diagrams
Addressable Circuits
J1
TB8TB7TB6TB5TB4TB3TB2TB1
J17J15J13J12J11
AUDIO J14 AUDIO J16
J21
LED TEST
A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B-
AUDIO J18
INOUT OUT IN OUT INRS422
R S
-232-A R
S -232-B
DC
RESET
AUDIO INPUTS
RS485
PORT A PORT B
J19
J9
SW2
J3 J10 J2
J6
4(-) (+) 3 (+)(-)
GND
GLB
TXD
RXD
KEY
RST
J8
J7
J5
J22
2(+)(-)
AUDIO
STAT
+24VDC IN
AUDIO J20
CAN
Lo
CAN
Hi
SLOT 6SLOT 5SLOT 4SLOT 3SLOT 2SLOT 1 SLOT 7 SLOT 8INOUT
CD
M
NC
MM
IM
R
R
(No more than 25 devices between isolators)
47k
EOL
Core II PCB P/N 176-271-00
All Circuits Power Limited
Class A (Style 6)
Class B (Style 4)
Class X (Style 7)
3.9k
EOL
Form C Contacts #2Contacts #1
Form C
24 VDC
Aux Pwr
S S
S
Class B
Class A S S
3.9k
EOL
3.9k
EOL
S
3.9k
EOL
Note: To reset the loop-powered (2-wire) conventional detectors connected through the interface module, that shall interrupt power.
or by a relay module configured as "smoke power" auxiliary power must be an interruptible versionRelay P/N 790-013-01
Power Supervisory
A A A
A A A
A AA
A A
A A A
Speaker Output Cards (SOCs) P/N 176-272-xx
24 VDC Input Non-power Limited
Addressable Driver Cards (ADCs) P/N 176-194-xx
Analog Adressable Controller II
(AAC II) P/N 176-273-00
NC
M
MM
IM
Isolator Module
NAC Control Module
Monitor Module
Mini Module
Interface Module
Addressable Initiating Devices:
Smoke Detector
Heat Detector A
A
Notification Appliance
Speaker ApplianceS
S Speaker/MNS Strobe Combo
NAC Devices:
All NACs Supervised
Speaker Configuration:
Up to 8 Class B or 4 Class A
Unused Speaker Circuits A+ A- B+ B- A+ A- B+ B-
Class A
Class B 3.9k 3.9k
Only TB5 TB8 terminals can be used for speaker circuits; requires SOCs
Terminals TB1 TB8 can be addressable circuits (SLC) if ADCs placed in all 8 slots.
R
Conventional Initiating Devices:
Pull Station
Heat Detector
Relay Module
LEGEND
SD Cardu
To NAC defined for MNS strobes
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
Conventional Circuits
D C
IN
A
U X
A U
XP
W
R
P
W R
D C
IN
1-
1-
1-
1-
2-
2-
2-
2-
3-
3-
3-
3-
4-
4-
4-
4-
1-
1-
1-
1-
2-
2-
2-
2-
3-
3-
3-
3-
4-
4-
4-
4-
N O
C O
M N
C
N O
C O
M N
C
N O
C O
M N
C
N O
C O
M N
C
NACZONE INPUTS K1 K2 K3 K4
1-
1-
1-
1-
NACZONE INPUTS
1-
1-
1-
1-
1-
1-
1-
1-
NACZONE INPUTS
1-
1-
1-
1-
Auxiliary Power Out;
Power Limited
4 Form C relays, 30 VDC, 2A, non-power limited
3.9k
EOL
Typical Class B
(Style B)
Typical Class A
(Style D)
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
P/N 790-013-01
DC In; Non-power Limited
P/N 790-013-01
3.9k
Typical Class B (Style Y)
Typical Class A (Style Z)
Unused Class A
(Style D) (Style Z)
(Style B) (Style Y)
Unused Class B
3.9k 3.9k 3.9k
8 Class B or 4 Class A.
All IDCs supervised.
IDC Configuration:
Contact devices;
non-loop power.
8 Class B or 4 Class A.
All NACs supervised.
NAC Configuration:
Power Limited
Power Limited Combined max. current for NACs 1 and 2 is regulated 1A or special application 2A.
Same specification applies to NACs 3 and 4.
Initiating Devices:
Pull Station
Smoke Detector
Heat Detector
Notification Appliance
Strobe
Waterflow Device
LEGEND
NAC Devices:
Notification/Strobe Appliance
Note Class B resistor values in this diagram are
3.9 kΩ, 1/2W (5%), end-of-line (EOL)
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx Rev C 6/18/15
MAAP-X to LOC/RDU Wiring
MAAP-X LOC/RDU
SUPV TBL COM R
Gnd Neut Hot
RCV XMT MIC
J2
C A
N L
C A
N H
C D
K ey
R X
D
TX
D R es et
G N
D
A ud io 2(
A ud io
2(
A ud io 1(
A ud io
1(
TB1
RS-422 Mux Cable P/N 630-025-02
In In
Out Out
Pwr Gnd
In
Gnd
In
J1
(-) (+)INOUT OUT IN OUT INRS422
RS485 J3 J10
J2
INOUT
A ud io
A ud io pair with drain Audio twisted shielded
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 7 Slot 8
A ud io
A ud io
In /O ut In
/O ut
G nd
NC In/Out In/Out (+) (-) NC
RS-485 Audio maximum distance 2000 ft 22 AWG 3-conductor cable, Wht/Blue Wht/Vio
Blk
Wht/Grn Wht/Yel
Orn
MAAP-X Unit
MAAP-X AAC II
(Two 12 VDC 18 Ah batteries) 24 VDC to batteries
Ratings:
120 VAC (102-132 VAC)
240 VAC (204-264 VAC)
45-65 Hz, 15A Max.
100 VAC (85-110 VAC)
O ut
O utInIn
G nd
Vi n
+ 1( +) 1(
A U
X
IN
G N
D
2( +) 2(
N C
C O
M N O
N C
C O
M N O
S P
K R
S P
K R
M
IC
IN
T(
IN
T(
P
TT
N .O
P
TT
C
O M
M
IC
X
FM
R 1(
X
FM
R
1(
O ut
O ut
In In G nd Vi n
X
FM
R 2(
X
FM
R 2(
To 8 devices using RS-485
Wht/Blue Wht/Vio
Blk
Wht/Grn Wht/Yel
Orn
MUX
P/N 176-268-02
AC BAT ALM
service@monaco.com
AC BAT ALM SUPV TBL COM RCV XMT RMIC
TB6
D C
IN
A U
X
A U
X
TB9
C A
N L
C A
N H
P W
R
TB
P W
R
TB7
D C
IN
TB10TB8
K4
K3
K2
K1
J17J15J13J12J11 J21
DC
AUDIO INPUTSPORT A PORT B
J19
J6
GND
GLB
TXD
RXD
RST
J8 24VDC In
Slot 6
CD
Out
In
Out
In Gnd Vcc
TB6
Out
In
Out
In Gnd Vcc
TB5
Out
In
Out
In Gnd Vcc
TB4
TB3
TB2
Out(+) Gnd
In(+)
TB1
Gnd
Out
In
Out
In Gnd Vcc
Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
F ire
A la rm C o n tro l P a n e l A cce sso rie s: M
-2 F ire A larm C on trol P an el Fire Alarm Control Panel Accessories
M-2 Fire Alarm Control Panel Expansion Cards
Expansion Backplane
Features
■ Used to add conventional zones, auxiliary outputs, and alarm-initiating input capabilities to the conventional and addressable M-2 Integrated Radio Transceiver and Fire Alarm Control Panels
■ Accepts up to seven Zone Expansion Cards, Auxiliary Output Cards, or Universal Input Cards
■ Seven sets of terminals available for making connections to the circuits associated with the cards
■ Each expansion backplane is separately addressed by a switch
Zone Expansion Card
Features
■ Two Class A or four Class B zones for M-2s; a slide switch selects the class
■ Plugs easily into the M-2 Expansion Backplane
Auxiliary Output Card
Features
■ Eight programmable circuits
■ Programmable for general alarm or trouble, or alarm or trouble on one or more zones
■ Used to drive annunciator LEDs, relays, or similar devices
Universal Input Card
Features
■ Four pairs of current limited 2-wire Class B zone inputs
■ Each terminal pair can be programmed to accept several types of alarm-initiating inputs, including polarity reversal and presence or absence of voltage
■ DIP switch settings define the operation of each input pair
Ordering Information Part Number Description
176-185-00 Expansion Backplane - accepts Zone Expansion Cards, Auxiliary Output Cards, and Universal Input Cards
176-186-00 Zone Expansion Card
176-187-00 Auxiliary Output Card
176-197-00 Universal Input Card Fire Managment Systems Catalog Rev N 4/12
Record
122-012-06 Rev A 2/02/17
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
Description This push-to-talk paging microphone is ideal for the MAAP-X addressable Fire Alarm Control Panel (FACP) with Mass Notification System (MNS).
The handheld push-to-talk paging microphone in enclosure (P/N 122-012-06) comes in a separate red enclosure to connect to the MAAP-X.
Features Wiring harness to connect directly back to the
MAAP-X
Easy-to-Use, push-to-talk, dynamic handheld MIC
5-foot extended length MIC cord Handheld push-to-talk Paging MIC with enclosure
(P/N 122-012-06) includes a red enclosure with an easy-access turn latch
Specifications
Ordering Information
Handheld Push-to-Talk Paging MIC in Enclosure P/N 122-012-06 Handheld Push-to-Talk Paging Microphone in Enclosure
(P/N 122-012-06)
For use With MAAP-X Addressable FACP with MNS
Enclosure Color Red
Enclosure Size 8" H x 6" W x 3" D
Connector Cable Length 15-feet
Microphone (For 122-012-06)
Impedance 400 ohm at 1,000 Hz
Frequency Response 200 to 5,000 Hz
Type Dynamic
Polar Pattern Omnidirectional
Output Level -33 dB ±3.0 dB
Relative Humidity 0-95% (non-condensing)
Operating Temperature -40° to 165° F (-40° to 74° C)
MIC Cable Length 5-foot extended length
MIC Cable Material 4-conductor (2 shielded) vinyl-jacketed coil-cable
MIC Cable Color Black
Part Number Description
122-012-06 Handheld Non-Emergency Push-to-Talk Paging Microphone in red Enclosure, 8"H x 6"W x 3"D.
15-foot single cable for connecting to MAAP-X, LOC/RDU Touch Screen or LOC Keypad. Dual cable also included if connecting MNS and Paging microphone to the MAAP-X or LOC /RDU Touch Screen.
MAAP-X Push-to-Talk Paging Microphone 122-012-06
Addressable Fire Alarm Control Panels with MNS
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
122-012-06 Rev A 2/02/17
Assembly Drawings
Handheld Push-to-Talk Paging MIC (P/N 122-012-06) to LOC Touch Screen or MAAP-X Touch Screen
AC BAT ALM SUPV TBL COM RCV XMT RMIC
J2
J7
P
TT
N .O
M
IC
P
TT
C O
M
M
IC
IN
T(
IN
T(
B lk
B rn
R ed
G rn
B lu e
W ht
Terminal Block Wiring Detail
J16
J15
Spokane Washington, USA Monaco Enterprises Inc.
www.monaco.com R
PA Non-Emergency Microphone
Paging Mic with Enclosure Kit P/N 122-012-06
MAAP-X Touch Screen / LOC Touch Screen
Cable must be in a conduit o Plug 15 foot cable assembly P/N 625-227-01 into LOC J15 o Run cable conduit to MIC enclosure plate terminal block o Cut cable to desired length, strip ends and connect as shown in "Terminal Block Wiring Detail"
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149
Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco.com Web www.monaco.com
Addressable Fire Alarm Control Panels with MNS
122-012-06 Rev A 2/02/17
Handheld Push-to-Talk MNS (P/N 122-012-05) and Paging Mic (P/N 122-012-06) to LOC Touch Screen or MAAP-X Touch Screen
Cables must be in a conduit
AC BAT ALM SUPV TBL COM RCV XMT RMIC
J7
Gnd Neut Line
Ba t(+
G nd
O ut
O ut
O ut
G nd
G nd
G nd
PT
T
N .O
M
IC
PT
T
C O
M
M
IC
IN
T(
IN
T(
PT
T
N .O
M
IC
PT
T
C O
M
M
IC
IN
T(
IN
T(
Bl k
Br n
R ed
G rn
Bl ue
W ht
Terminal Block Wiring Detail
Bl k
Br n
R ed
G rn
Bl ue
W ht
Terminal Block Wiring Detail
Bl ue
G rnW ht
47.5K
Spokane Washington, USA Monaco Enterprises Inc.
www.monaco.com R
J16
J15
Spokane Washington, USA Monaco Enterprises Inc.
www.monaco.com R
TB4 TB3
Existing cable
MAAP-X Touch Screen / LOC Touch Screen
MNS MIC with Enclosure Kit P/N 122-012-05
Paging Mic with Enclosure Kit P/N 122-012-06
Mass Notification Microphone PA Non-Emergency
Microphone
P/N 470-270-00 o Run cable conduit to PA MIC enclosure plate terminal block o Cut cable to desired length, strip ends and connect as shown in "Terminal Block Wiring Detail" o Plug 15 foot cable assembly P/N 625-277-02 into
MAAP-X J15, TB3 &TB4
o Run cable conduit to MNS MIC enclosure plate terminal block o Cut cable to desired length, strip ends and connect as shown in "Terminal Block Wiring Detail"
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
F ire
A la rm C o n tro l P a n e l A cce sso rie s: N otification A p p lian ce C ircu it Notification Appliance Circuit (NAC) Distributed Power Extender 8A
Features
■ UL Listed (UL864 and UL1481)
■ 24Vdc rated @ 8 amps maximum
■ Delivers four Class A, or four Class B outputs
■ Two (2) Class A, Style Z or two (2) Class B, Style Y
FACP inputs
■ Two Normally Closed (NC) dry contact trigger inputs
■ Four Class A or four Class B NACs
■ One (1) Aux. Power Output @ 1 amp supply current
(w/battery back up)
■ Compatible with 24 Vdc or 12 Vdc fire panels
■ Ground fault detection
■ Input 120 Vac
■ AC fail supervision (form “C” contact, 1 amp/28 Vdc)
■ Low battery supervision (form “C” contacts, 1 amp/28 Vdc)
■ Battery presence supervision (form “C” contacts, 1 amp/28 Vdc)
■ Power supply, logic board, red enclosure, cam lock, transformer & battery leads
■ Input to Output Follower Mode (maintains synchronization of notification appliance circuits)
■ Horn/Strobe sync protocols include:
• Wheelock®
• System Sensor®
Description The NAC Distributed Power Extender is a compact, easy-to-install, 8 A unit complete with a battery charger.
It is equipped with horn/strobe synchronization modes that support several styles of horn/strobe appliances allowing horns to be silenced while strobes continue to operate without additional sync modules. It may be connected to any Monaco FACP (including the M-2 Integrated Radio Transceiver and Fire Alarm Control Panel, the Vulcan I Fire Alarm Control Panel) or it may also standalone.
Primary applications include notification appliance (horn or strobe) circuit expansion (supports ADA requirements). The Distributed Power Extender contains a battery charger capable of charging sealed lead acid or gel type batteries.
NOTE: Due to the size of the enclosure, the use of batteries (for ac failure back-up) may interfere with the use of the bottom of the enclosure for conduit entry.
Ordering Information Part Number Description
404-126-00 Type I and Type II NAC Distributed Power Extender
400-704-00 Gel-type Battery, 12 V/7.7 Ah (two required)
400-713-00 Gel-type Battery, 12 V/12 Ah (two required)
UL®
F ire
A la rm C o n tro l P a n e l A cce sso rie s: N otification A p p lian ce C ircu it
Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129 Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
Specifications Standby Battery Specifications
Wiring Diagrams The NAC Distributed Power Extender must be properly connected to the FACP to ensure the proper functioning of the synchronization feature of both the Type I and Type II panels. The FACP requires two NAC inputs at the Power Extender panel: input one silences upon reset and input two silences upon silence.
Class A: 2-wire Sync Mode with Audible Silence ac Power 120 Vac @ 60 Hz, 5 A
Output 12 – 24 Vdc, 2.5 A per output, but not to exceed 8 A total output
Stand-by/Alarm Current
90 mA/175 mA
Battery Two 12 V/12 Ah batteries or two 12 V/7 Ah batteries connected in series
Wire Size #14 AWG minimum with 600 V insulation
Weight 20 lbs
Size 18" H × 14.5" W × 4.625" D
Stand-by Batteries
Stand-by Time Total
Amp/Minutes
Alarm Output Current Aux 2 Output
24 Vdc/7 Ah 24 Hours 8 amp/5 minutes
24 Vdc/12 Ah (use two (2)
12 Vdc batteries in series)
24 Hours 8 amp/5 minutes
50mA
24 Vdc/36 Ah 24 Hours 8 amp/5 minutes
1 amp 63Fire Managment Systems Catalog Rev N 4/12
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
A n te n n a
N e tw o rk A cce sso rie s: Stan d ard
V H
F A n ten n as Antenna Network Accessories
Standard VHF Antennas VHF antennas provide transmission and reception of VHF RF signals between a transceiver and the Radio Frequency Modem connected to the Radio Central Receiving System. Monaco offers omnidirectional and directional antennas:
■ Omnidirectional antennas transmit and receive RF signals in any horizontal direction and are the primary antenna used with BTs, M-Panels, M Addressable Panels, and RFMs that operate in the VHF frequency range
■ Directional antennas transmit and receive RF signals in one direction and are used to transmit VHF signals longer distances or in areas where significant interference exists
Specifications Ordering Information
BSA-1, Omnidirectional 5/8" Ground Plane, P/N 190-400-00
BSA-2, 6-Element Directional Yagi, P/N 190-401-xx*
*xx: This portion of the part number varies depending on frequency.
Material P/N 190-400-00 and 190-407-00:
Stainless Steel P/N 190-401-10 through 190-401-14:
Aluminum
Connector Type P/N 190-400-00: SO-259 UHF female P/N 190-407-00: BNC male
Polarization Vertical
Gain P/N 190-400-00 and 190-407-00:
5.2 dBi, 5/8 wave ground plane P/N 190-401-10 through 190-401-14:
7.1 dBd
RF Impedance 50 nominal
VSWR at Resonance P/N 190-400-00 and 190-407-00:
1.5 to 1 maximum P/N 190-401-10 through 190-401-14:
1.5:1 typical
Wind Load Resistance P/N 190-400-00: 100 mph P/N 190-401-10 through 190-401-14:
125 mph
Horizontal Beam Width
P/N 190-401-10 through 190-401-14:
74°
Vertical Beam Width P/N 190-401-10 through 190-401-14:
53°
Part Number Description
190-400-00 BSA-1 VHF 136 – 174 Mhz Omnidirectional Antenna with mounting hardware, ground clamp, and coaxial cable sealant. Needs to be cut to system frequency by customer.
199-001-00 Spare 54 inch Antenna Whip for use with P/N 190-400-00. Needs to be cut to system frequency by customer.
199-002-00 Spare VHF Coil for use with P/N 190-400-00
190-407-00 BSA-6 VHF 136 – 174 MHz Omnidirectional Antenna, magnetic-mount, portable. Needs to be cut to system frequency by customer.
190-401-10 BSA-2, VHF 6-element Yagi Directional Antenna, 134 – 142 MHz
190-401-11 BSA-2, VHF 6-element Yagi Directional Antenna, 142 – 150 MHz
190-401-12 BSA-2, VHF 6-element Yagi Directional Antenna, 150 – 158 MHz
190-401-13 BSA-2, VHF 6-element Yagi Directional Antenna, 158 – 166 MHz
190-401-14 BSA-2, VHF 6-element Yagi Directional Antenna, 166 – 174 MHz
A n te n n a
N e tw o rk A cce sso rie s: Stan d ard
U H
F A n ten n as
Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129 Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
Standard UHF Antennas UHF antennas provide transmission and reception of UHF RF signals between a transceiver and the Radio Frequency Modem connected to the Radio Central Receiving System. Monaco offers omnidirectional and directional antennas:
■ Omnidirectional antennas transmit and receive RF signals in any horizontal direction and are the primary antenna used with BTs, M-Panels, M Addressable Panels, and RFMs that operate in the UHF frequency range
■ Directional antennas transmit and receive RF signals in one direction and are used to transmit UHF signals longer distances or in areas where significant interference exists NOTE: UHF antennas require the use of low-loss cabling and N type connectors to work properly with Monaco Enterprises’s transceivers.
Specifications Ordering Information
BSA-9 5-Element Yagi, P/N 190-410-xx BSA-3 & BSA-8 UHF Omnidirectional, P/N 190-403-xx & 190-409-xx
Material P/N 190-403-xx* and 190-409-xx:* Stainless Steel P/N 190-410-01,190-410-02 and 190-410-03:Aluminum
Connector Type P/N 190-403-xx and P/N 190-410-xx: UHF female P/N 190-409-xx: BNC male
Polarization Vertical
Gain P/N 190-403-xx* and 190-409-xx*:
3 dBd, 5/8 wave ground plane P/N 190-410-01 and 190-410-02: 9 dBd P/N 190-410-03: 9.2 dBd
RF Impedance 50 nominal
VSWR at Resonance
P/N 190-403-xx: 1.5 to 1 maximum P/N 190-409-xx*, 190-410-01, and 190-410-02: 1.5 to 1 maximum
Wind Load Resistance
P/N 190-403-xx: 100 mph P/N 190-410-02: 100 mph
Horizontal Beam Width
P/N 190-410-01: 54° P/N 190-410-02: 53° P/N 190-410-02: 56°
Vertical Beam Width
P/N 190-410-01: 47° P/N 190-410-02: 46° P/N 190-410-02: 48°
* - xx: This portion of the part number varies depending on frequency.
Part Number Description
190-403-01 BSA-3 UHF Omnidirectional Antenna, 406 – 420 Mhz, mounting hardware, coaxial cable sealant, and ground clamp. Needs to be cut to system frequency by customer.
190-403-02 BSA-3 UHF Omnidirectional Antenna, 420 – 440 Mhz, mounting hardware, coaxial cable sealant, and ground clamp. Needs to be cut to system frequency by customer.
190-403-04 BSA-3 UHF Omnidirectional Antenna, 450 – 470 Mhz, mounting hardware, coaxial cable sealant, and ground clamp. Needs to be cut to system frequency by customer.
190-414-00 Spare BSA-3 UHF Omnidirectional Antenna whip and nose cone. Only for use replacing P/N 190-403-01 antenna whips. Upgrades antenna whips revisions A-C to Revision D.
Needs to be cut to system frequency by customer.
190-409-01 BSA-8 UHF Omnidirectional Antenna, 406 – 420 Mhz, magnetic-mount, portable.
Needs to be cut to system frequency by customer.
190-409-02 BSA-8 UHF Omnidirectional Antenna, 420 – 430 Mhz, magnetic-mount, portable.
Needs to be cut to system frequency by customer.
121Fire Managment Systems Catalog Rev N 4/12
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
A n te n n a
N e tw o rk A cce sso rie s: Stan d ard
U H
F A n ten n as NOTE: UHF antennas require the use of low-loss cabling and N type connectors to work properly with Monaco Enterprises’s transceivers.
190-409-04 BSA-8 UHF Omnidirectional Antenna, 450 – 470 Mhz, magnetic-mount, portable.
Needs to be cut to system frequency by customer.
190-410-01 BSA-9 UHF 5-element Yagi Directional Antenna, 406 – 430 Mhz
190-410-02 BSA-9 UHF 5-element Yagi Directional Antenna, 450 – 470 Mhz
190-410-03 BSA-9 UHF 5-element Yagi Directional Antenna, 420 – 440 Mhz te n n a
N e tw o rk A cce sso rie s: H igh G ain V
H F
O m n id irection al F iberglass Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129 Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
High Gain VHF Omnidirectional Fiberglass Broadband Antennas
Features
■ Omnidirectional
■ Heavy-duty fiberglass
■ Brass and copper internal components
■ 7 Mhz bandwidth
■ 6 dBd gain
■ Withstands 125 mph winds with ½ inch of radial ice
■ Withstands 150 mph winds without ice
Description The broadband, high-gain, omnidirectional colinear antennas are constructed of heavy-duty fiberglass that works under the most adverse conditions. Enclosed in cool blue fiberglass radome, these antennas are built to withstand ice, snow, high winds and the most adverse weather conditions. Its fiberglass radome will not corrode, even in the presence of saltwater, oil or most common chemical fumes. Internal grounding maintains the antenna at dc ground potential.
The heavy duty 2 ¾ inch support pipe with a recessed type N female connector is permanently bonded to the fiberglass radome and provides years of trouble-free operation. The antennas are suitable for mounting to the top of, or on the side of a tower.
Use a Lightning Surge Protector (P/N 198-003-00) for additional surge protection.
Specifications Ordering Information
Power Rating 500 W
Gain 6 dBd
Bandwidth 7 MHz
VSWR 1.5:1
Impedance 50
Vertical Beam 20°
Lighting Protection dc ground
Termination Recessed Type N female
Dimensions P/N 190-211-01 & P/N 190-211-02:
256 inches × 2 3/4 inches Other antennas: 244 inches × 2 3/4 inches
Net Weight P/N 190-211-01 & P/N 190-211-02: 43 lbs.
Other antennas: 41 lbs.
Wind Velocity ■ 125 mph winds with 1/2 inch radial ice
■ 150 mph winds without ice
Part Number Description
190-211-01 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 138 – 144 Mhz
190-211-02 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 144 – 151 Mhz
190-211-03 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 150 – 157 Mhz
190-211-04 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 156 – 164 Mhz
190-211-05 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 158 – 166 Mhz
190-211-06 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 161 – 168 Mhz
190-211-07 VHF Omnidirectional Broadband Antenna, 6 dBd gain, 167 – 174 Mhz
198-003-00 Lightning Surge Protector 123Fire Managment Systems Catalog Rev N 4/12
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
A n te n n a
N e tw o rk A cce sso rie s: H igh G ain V
H F
O m n id irection al F iberglass VSWR vs. Frequency Typical Radiation Pattern
Vertical Radiation Pattern for Vertical Polarization te n n a
N e tw o rk A cce sso rie s: L igh tw eigh t V
H F
O m n id irection al F iberglass Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129 Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
Lightweight VHF Omnidirectional Fiberglass Broadband Antenna
Features
■ Omnidirectional
■ Unity gain
■ UV coated to stand up to sun exposure
■ High-density fiberglass radome
■ Precision copper-clad elements
■ Heavy wall gold anodized 1.25 inch mounting sleeve
Description The fiberglass broadband antenna is rugged and small.
The colinear design is enclosed in high-density fiberglass and covered with a protective coating that inhibits UV damage. The mounting sleeve is tuned to eliminate RF currents from the transmission line, which allows for greater freedom in mounting.
This antenna is suitable for a corrosive environment (for example, near salt water) where no gain is required.
Because of its wide bandwidth, this antenna is ideal as an emergency backup antenna. Its small size and mounting fixture allows easy storage and quick installation.
Specifications Ordering Information
Gain Unity
Frequency Range 136 to 174
Connector type Recessed N female
Wind Survival 125 mph
VSWR 1.5:1
Maximum Power Input
150 W
Vertical Beam width 75°
Polarization Vertical
Overall Length 68 inches (172.72 cm)
Weight 6 lbs (2.72 kg)
Part Number Description
190-412-xx Lightweight VHF Omnidirectional Broadband Antenna, with bracket and UHF Female to N Male adaptor. Specify frequency when ordering.
125Fire Managment Systems Catalog Rev N 4/12
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
A n te n n a
N e tw o rk A cce sso rie s: H igh G ain U
H F
O m n id irection al F iberglass High Gain UHF Omnidirectional Fiberglass Broadband Antennas
Features
■ Omnidirectional
■ Heavy-duty fiberglass
■ Brass and copper internal components
■ 8 Mhz bandwidth
■ 6 dBd gain
Description The broadband, medium-gain, omnidirectional colinear antennas are constructed of heavy-duty fiberglass that works under the most adverse conditions. Enclosed in cool blue fiberglass radome, these antennas are built to withstand ice, snow, high winds and the most adverse weather conditions. Its fiberglass radome will not corrode, even in the presence of saltwater, oil or most common chemical fumes. Internal grounding maintains the antenna at dc ground potential.
The heavy duty 2 ¾ inch support pipe, with recessed type N female connector, is permanently bonded to the fiberglass radome and provides years of trouble-free operation. A 24 inch N male to N female jumper is included. The antennas are suitable for mounting to the top or on the side of a tower.
Ordering Information
NOTE: UHF antennas require the use of low-loss cabling and N type connectors to work properly with Monaco Enterprises’s transceivers.
Part Number Description
190-216-01 UHF Omnidirectional Broadband Antenna, 6 dBd gain, 405 – 440 Mhz*
190-216-02 UHF Omnidirectional Broadband Antenna, 6 dBd gain, 445 – 480 Mhz*
NOTE: Each antenna is provided with a dual clamp set (for mounting to a 1.5 – 3.5 inch outside diameter support pipe), and a 24 inch removable RG-213 N-Male jumper.
te n n a
N e tw o rk A cce sso rie s: H igh G ain U
H F
O m n id irection al F iberglass Monaco Enterprises, Inc.
14820 East Sprague Avenue, P.O. Box 14129, Spokane, Washington 99214-0129 Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
Specifications
VSWR vs. Frequency: Typical Radiation Pattern
Vertical Radiation Pattern for Vertical Polarization
Power Rating 500 W
Gain 6 dBd
VSWR 1.5:1 or less
Impedance 50
Vertical Beamwidth 18°
Lighting Protection dc ground
Termination Recessed Type N female at the base
Dimensions ■ P/N 190-216-01: 101 inches × 2 3/4 inches (256.54 cm × 6.98 cm)
■ P/N 190-216-02: 94 inches × 2 3/8 inches (238.80 cm × 6.03 cm)
Tower Weight
(antenna + clamps)
■ P/N 190-216-01: 22 lbs
■ P/N 190-216-02: 21 lbs
Wind Velocity ■ P/N 190-216-01: 155 mph winds with 1/2 inch radial ice; 185 mph winds without ice
■ P/N 190-216-02: 125 mph winds with 1/2 inch radial ice; 150 mph winds without ice
190-216-01 190-216-02
190-216-01 190-216-02 127Fire Managment Systems Catalog Rev N 4/12
Telephone: (509) 926-6277 Facsimile: (509) 924-4980 E-mail:service@monaco.com Web: www.monaco.com
A n te n n a
N e tw o rk A cce sso rie s: L ow P rofile M arin e R ated
U H
F /V
H F
A n ten n a
Low Profile Marine Rated UHF/VHF Antenna
Features
■ Weather and vibration resistant
■ Larger diameter whip decreases resistive losses and provides an increased radiating surface
■ Propagation pattern and low angle of radiation minimize clipping and fading
Description The Low Profile Marine Rated UHF/VHF Antenna is built from a painted aluminum tube with a high tensile strength stainless steel tip; and the whip is built using a larger diameter stainless steel rod to decrease…
This is the start of the file's text. The full file is on GovTribe.