05 Norcross Downtown Parking Retaining Walls_.pdf
PDF 1 MB Posted
- Attached to
- Downtown Norcross Parking Improvements
- Solicitation number
- PE-66780-NONST-2027-000000047
- Issued by
- Gwinnett County, Georgia
About this file
This is a structural design specifications and foundation detail document prepared by NV5 Engineers and Consultants, Inc. for the City of Norcross Downtown Parking Improvements project located at 65 Lawrenceville Street and 345 Lively Avenue in Norcross, Georgia. The document establishes comprehensive structural requirements for retaining walls and foundation systems supporting parking and pedestrian facilities. The project includes multiple retaining wall configurations (RW1 through RW5) with varying heights ranging from 3 feet to 13 feet, concrete footings, drainage systems, and reinforcement specifications. The specifications are designed per the 2024 Georgia State Building Code and 2024 International Building Code, with design loads including a 250 PSF retaining wall surcharge, ultimate wind speed of 105 MPH, and seismic design category C. Construction must be completed within 315 calendar days following Notice to Proceed. The sealed bid deadline is 11:00 a.m. on September 28, 2026, with submission to the City of Norcross Public Works Department. A non-mandatory pre-bid meeting and optional site visit are scheduled for August 26, 2026, at 11:00 a.m. at 345 Lively Avenue. Questions must be submitted by email to Charlene Marsh (procurement@norcrossga.net) no later than 5:00 p.m. on September 7, 2026.
The specifications require normal weight concrete with minimum 28-day compressive strength of 3,000 PSI for footings and 4,500 PSI for retaining walls, Grade 60 deformed reinforcing steel per ASTM A615, and compliance with ACI 318-19 and ACI 301 standards. Foundation design assumes net allowable soil bearing pressure of 2,000 PSF for walls and 3,000 PSF for stormwater pond structures based on a geotechnical report to be verified by the contractor. The contractor is responsible for engaging a licensed professional engineer to design delegated items including site retaining walls, temporary shoring, and stone veneer connections. Special inspections are required for concrete construction, reinforcing steel, formwork, soil conditions, and retaining wall systems per IBC 1705 standards. The document establishes a Statement of Special Inspections coordinator responsibility for maintaining daily observation reports and monthly interim reports to the building official and structural engineer. All work must comply with concrete cover requirements, lap splice specifications, reinforcement development lengths, and construction joint and control joint placement standards detailed in the specifications and foundation plans.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THESE DRAWINGS ARE THE PROPERTY OF NV5 ENGINEERS AND CONSULTANTS, INC. FOR USE SOLELY
FOR THIS PROJECT AND SHALL NOT BE REPRODUCED, COPIED OR USED FOR OTHER PURPOSES
WITHOUT WRITTEN PERMISSION OF NV5 ENGINEERS AND CONSULTANTS, INC.
2. THE DESIGN PROFESSIONAL WHOSE SEAL APPEARS ON THESE DRAWINGS IS THE STRUCTURAL ENGINEER OF RECORD (SER) FOR THIS PROJECT. THE SER BEARS THE RESPONSIBILITY OF THE PRIMARY STRUCTURAL SYSTEM AND THE PERFORMANCE OF THIS STRUCTURE. NO OTHER PARTY MAY REVISE, ALTER, OR DELETE THESE CONSTRUCTION DOCUMENTS WITHOUT WRITTEN PERMISSION OF THE SER. FOR THE PURPOSES OF THESE CONSTRUCTION DOCUMENTS THE SER AND NV5 ENGINEERS
AND CONSULTANTS, INC SHALL BE CONSIDERED THE SAME ENTITY.
3. THIS STRUCTURE IS ONLY STABLE IN ITS COMPLETED FORM. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED TEMPORARY BRACING DURING CONSTRUCTION TO STABILIZE THE STRUCTURE. TEMPORARY SHORING AND BRACING METHODS ARE NOT THE RESPONSIBILITY OF THE SER AND ARE BEYOND THE
SCOPE OF THESE DRAWINGS.
4. THE STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR CONSTRUCTION SEQUENCES, METHODS, OR TECHNIQUES IN CONNECTION WITH THE CONSTRUCTION OF THIS STRUCTURE. THE SER
WILL NOT BE HELD RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO CONFORM TO THE
CONSTRUCTION DOCUMENTS, SHOULD ANY NON-CONFORMITIES OCCUR.
5. ANY STRUCTURAL ELEMENTS OR DETAILS NOT FULLY DEVELOPED ON THE CONSTRUCTION DRAWINGS SHALL BE COMPLETED UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER. THESE SHOP DRAWINGS SHALL BE SUBMITTED TO THE SER FOR REVIEW BEFORE ANY CONSTRUCTION BEGINS. SEE
THE "SUBMITTALS" SECTION OF THESE SPECIFICATIONS.
6. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH AND COORDINATED WITH THE ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND CIVIL DRAWINGS. THIS COORDINATION IS
NOT THE RESPONSIBILITY OF THE SER. SHOULD ANY DISCREPANCIES BECOME APPARENT THE
CONTRACTOR SHALL NOTIFY THE SER BEFORE ANY CONSTRUCTION BEGINS.
7. VERIFICATION OF ASSUMED FIELD CONDITIONS IS NOT THE RESPONSIBILITY OF THE STRUCTURAL ENGINEER OF RECORD. THE CONTRACTOR SHALL VERIFY THE FIELD CONDITIONS FOR ACCURACY AND
REPORT ANY DISCREPANCIES TO THE SER BEFORE CONSTRUCTION BEGINS.
8. THE STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR ANY SECONDARY STRUCTURAL ELEMENTS OR NON-STRUCTURAL ELEMENTS, EXCEPT FOR THE ELEMENTS SPECIFICALLY NOTED ON
THE STRUCTURAL DRAWINGS.
9. THIS STRUCTURE AND ALL CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE SECTIONS OF THE
GEORGIA STATE BUILDING CODE AND ANY LOCAL LAWS WHERE THE STRUCTURE IS TO BE
CONSTRUCTED.
10. RECORD DRAWINGS OF THE EXISTING BUILDING WERE NOT AVAILABLE AT THE TIME OF DESIGN. NEW CONSTRUCTION SHALL NOT BEGIN UNTIL THE CONTRACTOR HAS REVIEWED EXISTING CONSTRUCTION
AND VERIFIED THESE AND ALL OTHER ITEMS WHICH MAY AFFECT NEW CONSTRUCTION. ANY
DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND THOSE ASSUMED ON DRAWINGS ARE TO BE
BROUGHT TO THE ATTENTION OF THE SER BEFORE WORK PROCEEDS.
GENERAL CONSTRUCTION SPECIFICATIONS
1. BUILDING CODES
A. GEORGIA STATE BUILDING CODE 2024 EDITION
B. 2024 INTERNATIONAL BUILDING CODE
C. MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES, ASCE 7-22
2. RISK CATEGORY II
3. LIVE LOAD:
A. RETAINING WALL SURCHARGE 250 PSF
4. WIND LOADS / DATA
A. ULTIMATE WIND SPEED (3 SECOND GUST), VULT 105 MPH
B. NOMINAL WIND SPEED, VASD 81 MPH
C. EXPOSURE B
D. INTERNAL PRESSURE COEFFICIENT, GCpi ± 0.18 E. TOPOGRAPHY FACTOR, Kzt 1.00 F. APPLIED DIRECTIONALITY FACTOR, Kd 0.85
5. SEISMIC LOADS / DATA
A. ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
B. SITE CLASS D
C. SEISMIC IMPORTANCE FACTOR, Ie 1.00 D. MAPPED SPECTRAL RESPONSE ACCELERATION (0.2 sec.), Ss 0.26 E. MAPPED SPECTRAL RESPONSE ACCELERATION (1.0 sec.), S1 0.095 F. SPECTRAL RESPONSE COEFFICIENT, Sds 0.21 G. SPECTRAL RESPONSE COEFFICIENT, Sd1 0.13
H. SEISMIC DESIGN CATEGORY C
I. BASIC STRUCTURAL SYSTEM BEARING WALL SYSTEM
J. RESPONSE MODIFICATION FACTOR, R 3.0
K. SYSTEM OVER-STRENGTH FACTOR, 8 3.0
L. DEFLECTION AMPLIFICATION FACTOR, Cd 3.0 M. SEISMIC RESPONSE COEFFICIENT, Cs 0.xx
N. SEISMIC RESISTING SYSTEM ORDINARY REINF CONC SHEAR WALLS
6. A PROGRAM OF SPECIAL INSPECTIONS IS PROVIDED IN ACCORDANCE WITH THE 2024 GEORGIA
STATE BUILDING CODE CHAPTER 17. THE SCOPE OF THE PROGRAM OF SPECIAL INSPECTIONS
AND/OR QUALITY ASSURANCE PLANS WILL INCLUDE THE PRIMARY STRUCTURAL SYSTEM AND
OTHER SECONDARY STRUCTURAL ELEMENTS WHICH ARE SPECIFICALLY DESIGNED BY THE SER.
THE PROGRAM PROVIDED BY THE SER WILL SPECIFICALLY EXCLUDE ALL NON-STRUCTURAL
ELEMENTS INCLUDING BUT NOT LIMITED TO SMOKE CONTROL AND SMOKE EXHAUST SYSTEMS,
SPRAYED FIRE-RESISTANT MATERIALS, MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS AND THEIR ATTACHMENTS. THE PLANS OF SPECIAL INSPECTIONS FOR THESE EXCLUDED ITEMS MUST BE PREPARED BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF EACH DESIGNATED SYSTEM THAT IS SUBJECT TO SPECIAL INSPECTIONS, WHETHER IT IS ARCHITECTURAL, ELECTRICAL, MECHANICAL OR STRUCTURAL IN NATURE.
DESIGN LOADS
SUBMITTALS
1. SHOP DRAWINGS AND SUBMITTALS SHALL BE SUBMITTED TO THE SER FOR REVIEW BEFORE ANY CONSTRUCTION BEGINS. THESE SUBMITTALS WILL BE REVIEWED FOR OVERALL COMPLIANCE AS IT RELATES TO THE STRUCTURAL DESIGN OF THIS PROJECT. VERIFICATION OF THE SHOP DRAWINGS FOR DIMENSIONS, OR FOR ACTUAL FIELD CONDITIONS IS NOT THE RESPONSIBILITY OF THE SER.
REFER TO THE PROGRAM OF SPECIAL INSPECTIONS FOR SUBMITTAL REQUIREMENTS FOR ITEMS
RECEIVING SPECIAL INSPECTIONS.
2. ALLOW ENOUGH TIME FOR SUBMITTAL REVIEW, INCLUDING TIME FOR RESUBMITTALS. TIME FOR REVIEW SHALL COMMENCE ON THE SER'S RECEIPT OF SUBMITTAL. ALLOW 15 DAYS FOR INITIAL
REVIEW OF EACH SUBMITTAL AND 15 DAYS FOR REVIEW OF EACH RESUBMITTAL.
3. HIGHLIGHT, ENCIRCLE, OR OTHERWISE SPECIFICALLY IDENTIFY DEVIATIONS FROM THE CONTRACT
DOCUMENTS ON SUBMITTALS.
4. REVIEW EACH SUBMITTAL AND CHECK FOR COORDINATION WITH OTHER WORK OF THE CONTRACT
AND FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS. NOTE CORRECTIONS AND FIELD
DIMENSIONS. MARK WITH APPROVAL STAMP BEFORE SUBMITTING TO THE SER. STAMP SHALL
INCLUDE NAME OF REVIEWER, DATE OF CONTRACTOR'S APPROVAL, AND STATEMENT CERTIFYING
THAT SUBMITTAL HAS BEEN REVIEWED, CHECKED, AND APPROVED FOR COMPLIANCE WITH THE
CONTRACT DOCUMENTS.
5. SHOULD CHANGES MADE BY THE SER IN THE SHOP DRAWING REVIEW PROCESS OR RESPONSES TO REQUESTS FOR INFORMATION (RFI'S) RESULT IN A CHANGE IN THE CONTRACT PRICE, DO NOT
PROCEED UNTIL A CHANGE ORDER IS SUBMITTED AND APPROVED
6. WHERE PROFESSIONAL DESIGN SERVICES OR CERTIFICATIONS BY A DESIGN PROFESSIONAL ARE
SPECIFICALLY REQUIRED OF CONTRACTOR BY THE CONTRACT DOCUMENTS, PROVIDE PRODUCTS
AND SYSTEMS COMPLYING WITH SPECIFIC PERFORMANCE AND DESIGN CRITERIA INDICATED. IN ADDITION, SUBMIT COPIES OF A STATEMENT, SIGNED AND SEALED BY THE RESPONSIBLE DESIGN
PROFESSIONAL, FOR EACH PRODUCT AND SYSTEM SPECIFICALLY ASSIGNED TO CONTRACTOR TO
BE DESIGNED OR CERTIFIED BY A DESIGN PROFESSIONAL. INDICATE THE LOCATIONS, MAGNITUDES, DIRECTIONS AND CONNECTION TYPES OF LOADS IMPOSED ON THE SUPPORTING STRUCTURE AND
INDICATE THE LOADS AND LOAD COMBINATIONS USED IN THE DESIGN.
7. SHOP DRAWINGS, STATEMENTS, AND CALCULATIONS REQUIRING A PROFESSIONAL DESIGN
SERVICES OR CERTIFICATIONS BY A DESIGN PROFESSIONAL THAT ARE SUBMITTED UNSEALED WILL
BE RETURNED NOT REVIEWED BY THE SER FOR RESUBMITTAL BY THE CONTRACTOR.
8. LIMITED CONSTRUCTION ADMINISTRATION SERVICES ARE INCLUDED IN THE SCOPE OF SERVICES PROVIDED BY THE SER HOWEVER, IT IS POSSIBLE THAT SOME SUBMITTALS MAY BE RECOMMENDED BUT ARE NOT INCLUDED IN THE SCOPE OF SERVICES PROVIDED BY THE SER. THE ARCHITECT, OWNER, OR CONTRACTOR MAY ARRANGE FOR THESE SERVICES TO BE PROVIDED BY THE SER. OR A 3rd PARTY MAY PROVIDE THESE SERVICES WITH PRIOR APPROVAL FROM THE SER. THE
FOLLOWING SUBMITTALS ARE RECOMMENDED FOR THIS PROJECT:
9. CAST-IN-PLACE CONCRETE
A. IN ADDITION TO THE FOLLOWING, COMPLY WITH SUBMITTAL REQUIREMENTS IN ACI 301
B. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED
C. DESIGN MIXTURES: FOR EACH CONCRETE MIXTURE.
D. REBAR SHOP DRAWINGS
E. SHOP DRAWINGS FOR THE DESIGN, ERECTION AND REMOVAL OF FORMWORK, SHORES AND
RESHORES PREPARED BY OR UNDER THE SUPERVISION OF A QUALIFIED PROFESSIONAL
ENGINEER. SHOP DRAWINGS, INCLUDE STRUCTURAL ANALYSIS DATA SIGNED AND SEALED BY
THE QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR THEIR PREPARATION. COMPLY
WITH REQUIREMENTS IN "ACI MANUAL OF CONCRETE PRACTICE".
FOUNDATIONS
1. THE SCOPE OF SERVICES FOR THIS PROJECT PROVIDED BY THE SER BEGINS FROM THE BOTTOM OF THE FOUNDATION ELEMENTS. SUBSURFACE INVESTIGATIONS ARE BEYOND THE SCOPE OF THE
STRUCTURAL SERVICES PROVIDED. THE FOUNDATION SYSTEM SHOWN ON THESE DRAWINGS ARE
BASED UPON THE ASSUMED SOIL PROPERTIES LISTED BELOW. IT IS THE SOLE RESPONSIBILITY OF
THE CONTRACTOR, OWNER OR OWNER'S AGENT TO CONTACT THE SER IF ANY ADVERSE SOIL
CONDITIONS ARE ENCOUNTERED DURING CONSTRUCTION. VERIFICATION OF THIS ASSUMED VALUE
IS ALSO THE RESPONSIBILITY OF THE CONTRACTOR, OWNER OR OWNER'S AGENT.
A. NET ALLOWABLE SOIL BEARING PRESSURE:
a. ALL WALLS UNO 2000 PSF (ASSUMED, GEOTECH REPORT REQUIRED)
b. STORMWATER POND 3000PSF (ASSUMED, GEOTECH REPORT REQUIRED)
B. SUBGRADE MODULUS (k) 150 PCI (ASSUMED, GEOTECH REPORT REQUIRED)
C. ULTIMATE FRICTION COEFFICIENT 0.35 (ASSUMED, GEOTECH REPORT REQUIRED)
BETWEEN CONCRETE FOUNDATIONS AND SOIL
D. UNIT WEIGHT OF SOIL 120 PCF (ASSUMED, GEOTECH REPORT REQUIRED)
E. ACTIVE LATERAL EARTH PRESSURE, Ka
a. SOIL BACKFILL, ALL WALLS UNO 45 PSF/FT (ASSUMED, GEOTECH REPORT REQUIRED)
b. STONE BACKFILL, POND WALLS 27 PSF/FT (ASSUMED, GEOTECH REPORT REQUIRED)
F. AT-REST LATERAL EARTH PRESSURE, K0 60 PSF/FT (ASSUMED, GEOTECH REPORT REQUIRED) G. PASSIVE LATERAL EARTH PRESSURE, Kp 270 PSF/FT (ASSUMED, GEOTECH REPORT REQUIRED)
H. MINIMUM INTERNAL ANGLE OF FRICTION 25° (ASSUMED, GEOTECH REPORT REQUIRED)
I. THE RETAINING WALL DESIGN PRESSURES SPECIFIED ABOVE ARE FOR THE DRAINED
CONDITION WITH NO BUILDUP OF WATER PRESSURE ACTING BEHIND THE WALLS
2. THE BOTTOM OF ALL FOOTINGS SHALL EXTEND BELOW THE FROST LINE FOR THE REGION IN WHICH THE STRUCTURE IS TO BE CONSTRUCTED. HOWEVER, THE TOP OF FOOTING SHALL BE A MINIMUM
OF 12" BELOW GRADE.
3. EXCAVATE TO INDICATED ELEVATIONS AND DIMENSIONS WITHIN A TOLERANCE OF PLUS OR MINUS 1 INCH. IF APPLICABLE, EXTEND EXCAVATIONS A SUFFICIENT DISTANCE FROM STRUCTURES FOR
PLACING AND REMOVING CONCRETE FORMWORK, FOR INSTALLING SERVICES AND OTHER
CONSTRUCTION, AND FOR INSPECTIONS. DO NOT DISTURB BOTTOM OF EXCAVATION. EXCAVATE BY
HAND TO FINAL GRADE JUST BEFORE PLACING CONCRETE REINFORCEMENT. TRIM BOTTOMS TO
REQUIRED LINES AND GRADES TO LEAVE SOLID BASE TO RECEIVE OTHER WORK.
4. ANY FILL SHALL BE PLACED UNDER THE DIRECTION OR RECOMMENDATION OF A LICENSED
PROFESSIONAL ENGINEER USING SUITABLE SOILS OR ENGINEERED FILL. PLOW, SCARIFY, BENCH, OR BREAK UP SLOPED SURFACES STEEPER THAN 1 VERTICAL TO 4 HORIZONTAL SO FILL MATERIAL WILL BOND WITH EXISTING MATERIAL. PLACE BACKFILL AND FILL SOIL MATERIALS IN LAYERS NOT MORE THAN 8" IN LOOSE DEPTH FOR MATERIAL COMPACTED BY HEAVY COMPACTION EQUIPMENT, AND NOT MORE THAN 4" IN LOOSE DEPTH FOR MATERIAL COMPACTED BY HAND-OPERATED
TAMPERS. COMPACT SOIL MATERIALS TO NOT LESS THAN 95% OF MAXIMUM DRY UNIT WEIGHT
ACCORDING TO ASTM D 698, UNLESS A HIGHER PERCENTAGE IS RECOMMENDED BY THE
GEOTECHNICAL ENGINEER. UNDER SLABS ON GRADE AND STEPS, SCARIFY AND RECOMPACT TOP
12" OF EXISTING SUBGRADE AND EACH LAYER OF BACKFILL OR FILL SOIL MATERIAL AT 98%.
5. INSPECT AND TEST SUBGRADES AND EACH FILL OR BACKFILL LAYER AND AT FOOTING SUBGRADES.
PERFORM TESTING TO VERIFY DESIGN BEARING CAPACITIES IN ACCORDANCE WITH THE PROGRAM
OF SPECIAL INSPECTIONS.
6. EXCAVATION FOR FOOTINGS SHALL BE LINED TEMPORARILY WITH A 6 MIL POLYETHYLENE IF
PLACEMENT OF CONCRETE DOES NOT OCCUR WITHIN 24 HOURS OF EXCAVATION.
7. NO CONCRETE SHALL BE POURED AGAINST ANY SUBGRADE CONTAINING WATER, ICE, FROST, OR
LOOSE MATERIAL.
8. DO NOT BACKFILL AGAINST CANTILEVERED RETAINING WALL UNTIL THE CONCRETE HAS ATTAINED 100 PERCENT OF ITS DESIGN STRENGTH. REFER TO THE PLANS FOR ADDITIONAL REQUIREMENTS.
9. PROVIDE BRACING AND SHORING FOR ALL BASEMENT FOUNDATION WALLS AND WALLS INDICATED AS RESTRAINED PRIOR TO BACKFILLING. THE BRACING AND SHORING SHALL REMAIN IN PLACE UNTIL ALL SLABS ON GRADE, ELEVATED SLABS AND BEAMS FRAMING INTO THE WALL, ABOVE AND BELOW, HAVE BEEN PLACED, HAVE CURED FOR AT LEAST 7 DAYS AND HAVE ATTAINED 100 PERCENT
OF THEIR DESIGN STRENGTH.
10. BACKFILL PLACED IMMEDIATELY BEHIND WALLS SHALL BE COMPACTED WITH HAND OPERATED
EQUIPMENT.
11. CONSULT THE GEOTECHNICAL REPORT FOR FURTHER RECOMMENDATIONS AND REQUIREMENTS
CONCRETE
1. CONCRETE SHALL BE PROPORTIONED, MIXED, PLACED, AND TESTED IN ACCORDANCE WITH THE ACI MANUAL OF CONCRETE PRACTICE INCLUDING BUT NOT LIMITED TO ACI 318-19 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" AND ACI 301-10 "SPECIFICATION FOR STRUCTURAL
CONCRETE". COMPLY WITH ACI 117-10 "SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIALS," ACI 305.1-06 "SPECIFICATION FOR HOT WEATHER CONCRETING"
AND ACI 306.1-10 "STANDARD SPECIFICATIONS FOR COLD WEATHER CONCRETING."
2. STEEL REINFORCEMENT SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS:
A. REINFORCING BARS: ASTM A615, GRADE 60, DEFORMED
B. REINFORCING BARS, WELDABLE: ASTM A706, GRADE 60, DEFORMED
C. PLAIN-STEEL WIRE: ASTM A1064, AS DRAWN
D. PLAIN-STEEL WELDED: ASTM A1064, FABRICATED WIRE REINFORCEMENT FROM AS-DRAWN
STEEL WIRE INTO FLAT SHEETS
E. JOINT DOWEL BARS: ASTM A615, GRADE 60, PLAIN, FREE OF BURRS
3. NORMAL WEIGHT CONCRETE (NWC) SHALL HAVE A UNIT WEIGHT OF 145 PCF (+/- 3 PCF), UNLESS NOTED OTHERWISE. CONCRETE MATERIALS SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS:
A. PORTLAND CEMENT: ASTM C150, TYPE I OR TYPE II
B. FLY ASH: ASTM C618, CLASS F
C. BLENDED HYDRAULIC CEMENT: ASTM C595, TYPE I (PM) POZZOLAN-MODIFIED PORTLAND
D. NORMAL-WEIGHT AGGREGATE: ASTM C33, GRADED
E. LIGHTWEIGHT AGGREGATE: ASTM C330, GRADED
F. WATER: ASTM C1602, POTABLE
G. AIR-ENTRAINING ADMIXTURE: ASTM C260
4. NO ADMIXTURES SHALL BE ADDED TO ANY STRUCTURAL CONCRETE WITHOUT WRITTEN
PERMISSION OF THE SER. ALL PROPOSED ADMIXTURES SHALL BE SUBMITTED TO THE SER WITH
THE PROPOSED MIX DESIGNS AND SHALL INCLUDE CERTIFICATION FROM THE MANUFACTURER
THAT THE ADMIXTURE IS COMPATIBLE WITH OTHER ADMIXTURES AND NOT CONTRIBUTE WATER-
SOLUBLE CHLORIDE IONS EXCEEDING THOSE PERMITTED IN HARDENED CONCRETE. DO NOT USE
CALCIUM CHLORIDE OR ANY ADMIXTURE CONTAINING CALCIUM CHLORIDE.
5. SLUMP LIMIT: 8 INCHES PLUS OR MINUS 1 INCH AT THE POINT OF DELIVERY FOR CONCRETE WITH VERIFIED SLUMP OF 2 TO 4 INCHES BEFORE ADDING HIGH-RANGE WATER-REDUCING ADMIXTURE OR PLASTICIZING ADMIXTURE. OTHERWISE, PROVIDE SLUMP LIMIT OF 4 INCHES, PLUS OR MINUS 1 INCH
AT THE POINT OF DELIVERY.
6. IT IS RECOMMENDED THAT INTERIOR SLABS TO BE GIVEN A SMOOTH, DENSE, HARD-TROWELED FINISH NOT CONTAIN ENTRAINED AIR SINCE BLISTERING OR DELAMINATION MAY OCCUR. IF SLAB
WILL BE EXPOSED TO DEICING OR OTHER AGGRESSIVE CHEMICALS CONTACT THE SER FOR
PROPER AIR ENTRAINMENT REQUIREMENTS.
7. COMPLY WITH CRSI'S "MANUAL OF STANDARD PRACTICE" FOR FABRICATING, PLACING AND
SUPPORTING REINFORCEMENT.
8. COMPLY WITH THE MINIMUM CONCRETE COVER FOR REINFORCEMENT LISTED IN THE TABLES
BELOW.
9. SPLICE REINFORCEMENT AS DETAILED OR AUTHORIZED BY THE SER. MAKE BARS CONTINUOUS
AROUND CORNER. SPLICES SHALL BE MADE BY CONTACT TENSION LAP SPLICES, UNLESS
OTHERWISE NOTED.
10. PLACING SLEEVES THROUGH CONCRETE ELEMENTS IS NOT PERMITTED UNLESS SHOWN ON THE
DRAWINGS, ON APPROVED SLEEVING SHOP DRAWINGS, OR AS AUTHORIZED BY THE SER IN
WRITING.
11. WELDING OF REINFORCING IS NOT PERMITTED UNLESS SPECIFICALLY CALLED FOR OR APPROVED
BY THE STRUCTURAL ENGINEER OF RECORD.
12. FIELD BENDING OF REINFORCING PARTIALLY EMBEDDED IN THE CONCRETE IS NOT PERMITTED
UNLESS OTHERWISE SHOWN OR APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
13. LOCATING JOINTS IN HORIZONTAL PLANE OF FOUNDATIONS, PILE CAPS, DRILLED PIERS, SLABS, BEAMS, GIRDERS AND JOISTS IS NOT PERMITTED UNLESS OTHERWISE NOTED OR APPROVED BY
THE STRUCTURAL ENGINEER OF RECORD.
14. CHAMFER EXPOSED CONCRETE CORNERS 3/4" x 3/4" MINIMUM, UNLESS OTHERWISE NOTED ON THE
ARCHITECTURAL DRAWINGS.
15. COMPLY WITH ACI 301 FOR MEASURING, BATCHING, MIXING, TRANSPORTING, AND PLACING
CONCRETE. BEFORE TEST SAMPLING AND PLACING CONCRETE, WATER MAY BE ADDED AT THE
PROJECT SITE, SUBJECT TO LIMITATIONS OF ACI 301.
16. SEE ARCHITECTURAL DRAWINGS FOR FINISHING REQUIREMENTS OF FORMED CONCRETE
SURFACES. FOR UNFORMED SURFACES COMPLY WITH ACI 302.1R FOR SCREEDING,
RESTRAIGHTENING, AND FINISHING OPERATIONS UNLESS OTHERWISE NOTED ON THE
ARCHITECTURAL DRAWINGS.
17. CURE FORMED AND UNFORMED CONCRETE FOR AT LEAST SEVEN DAYS BY ONE OF THE FOLLOWING METHODS; MOISTURE CURING, MOISTURE-RETAINING-COVER CURING, APPLICATION OF A CURING
COMPOUND, OR BY APPLICATION OF A CURING AND SEALING COMPOUND.
18. SAMPLE MATERIALS, PERFORM TESTS, AND SUBMIT REPORTS DURING CONCRETE PLACEMENT
ACCORDING TO ACI 301 AND CHAPTER 19 OF THE INTERNATIONAL BUILDING CODE AND IN
ACCORDANCE WITH THE PROGRAM OF SPECIAL INSPECTIONS.
PROJECT
CLASS
ELEMENT 28 DAY f'c
(MIN)
CONCRETE
TYPE
ACI
EXPOSURE
CLASS
A
B
FOOTINGS
RETAINING WALLS
3000 PSI
4500 PSI
NWC
NWC
NON-POST TENSIONED CONCRETE
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH
CONCRETE EXPOSED TO EARTH OR WEATHER:
CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH GROUND:
No.6 BAR THROUGH No.18 BARS
No.5 BAR AND SMALLER
SLABS, WALL AND JOISTS: No.14 AND No.18 BARS
3"
2"
1 1/2"
1 1/2"
3/4"
1 1/2"
MINIMUM
COVER
SLABS, WALL AND JOISTS: No.11 BARS AND SMALLER
BEAMS, COLUMNS: PRIMARY REINFORCEMENT, TIES,
STIRRUPS, SPIRALS
F0, C1
F2, C1
NOTES:
1. ALL MIXES ARE EXPOSURE CLASS S0 AND P0 ACCORDING TO ACI 318 UNLESS NOTED OTHERWISE
2. WATER CEMENT RATIO: PROPORTION MIXES TO COMPLY WITH THE MAXIMUM WATER CEMENT
RATIO REQUIREMENTS SHOWN IN ACI 318-19 TABLE 19.3.2.1 MAXIMUM WATER CEMENT RATIOS DO
NOT APPLY TO LIGHTWEIGHT (LWC) CONCRETE.
3. AIR ENTRAINMENT: PROPORTION MIXES TO COMPLY WITH THE MAXIMUM AIR CONTENT
REQUIREMENTS SHOWN IN ACI 318-19 TABLE 19.3.3.1. FOR LIGHTWEIGHT (LWC) CONCRETE
EXPOSURE CLASS F0, PROVIDE 5.5% +/-1.5% AIR ENTRAINMENT.
4. MAXIMUM PERCENT OF TOTAL CEMENTITIOUS MATERIALS BY WEIGHT: COMPLY WITH THE
REQUIREMENTS OF ACI 318-19 TABLE 26.4.2.2(b). FOR EXPOSURE CLASS F3
5. CHLORIDE ION CONTENT: PROPORTION MIXES TO COMPLY WITH THE MAXIMUM WATER SOLUBLE
CHLORIDE ION CONTENT REQUIREMENTS SHOWN IN ACI 318-19 TABLE 19.3.2.1
MAX
AGGREGATE
SIZE
1"
1"
CONCRETE MIX DESIGN REQUIREMENTS
DELEGATED DESIGN
1. THE CONTRACTOR SHALL ENGAGE A QUALIFIED, LICENSED ENGINEER(S) IN THE STATE IN WHICH
THE PROJECT IS CONSTRUCTED TO DESIGN, DETAIL AND SUBMIT FOR REVIEW SEALED
CALCULATIONS AND SHOP DRAWINGS FOR THE DELEGATED DESIGN SHOWN IN THE CONTRACT
DOCUMENTS. ADDITIONAL DELEGATED DESIGN SYSTEMS MAY BE FOUND IN THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, PROCESS, LANDSCAPE AND CIVIL DRAWINGS NOT
CONTAINED, HEREIN.
2. REFER TO THE SUBMITTALS SECTION FOR ADDITIONAL REQUIREMENTS.
3. DELEGATED DESIGN ITEMS SHALL INCLUDE BUT ARE NOT LIMITED TO:
A. SITE RETAINING WALLS INCLUDING SEGMENTAL BLOCK AND MECHANICALLY STABILIZED EARTH
RETAINING WALLS
B. TEMPORARY SHORING
C. STONE VENEER AND CONNECTIONS
CONCRETE COVER REQUIREMENTS
UNIT MASONRY ASSEMBLIES
1. CONCRETE MASONRY UNITS (CMU) SHALL BE ERECTED AS LOAD BEARING CONCRETE MASONRY.
COMPLY WITH ACI 530.1 "SPECIFICATION FOR MASONRY STRUCTURES" FOR MATERIALS, METHODS, AND WORKMANSHIP AND ERECTION TOLERANCES.
2. PROVIDE CONCRETE MASONRY UNIT ASSEMBLIES (CMUS) AS INDICATED ON THE DRAWINGS THAT DEVELOPS A MINIMUM NET-AREA COMPRESSIVE STRENGTH (F'M) OF 2000 PSI AT 28 DAYS AND AS
FOLLOWS:
A. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 WITH A MINIMUM AVERAGE NET-
AREA COMPRESSIVE STRENGTH OF 2000 PSI.
B. MAXIMUM WEIGHT CLASSIFICATION: NORMAL WEIGHT, UNLESS OTHERWISE NOTED.
C. SIZE: MANUFACTURED TO DIMENSIONS 3/8" LESS THAN NOMINAL DIMENSIONS
3. PROVIDE MORTAR AND GROUT MATERIALS AS INDICATED ON THE DRAWINGS AND CONFORMING TO
THE REQUIREMENTS LISTED BELOW. ALL CELLS CONTAINING REINFORCEMENT, CELLS BELOW
GRADE, AND ANY LOCATIONS NOTED ON THE DRAWINGS SHALL BE GROUTED SOLID. DO NOT USE
ADMIXTURES, INCLUDING AIR-ENTRAINING AGENTS, ACCELERATORS, RETARDERS, WATER-
REPELLENT AGENT, ANTIFREEZE COMPOUNDS, OR OTHER ADMIXTURES UNLESS OTHERWISE
NOTED. DO NOT USE CALCIUM CHLORIDE IN MORTAR OR GROUT.
A. MORTAR FOR MASONRY ASSEMBLIES SHALL BE TYPE S, CONFORMING TO ASTM C270
B. GROUT FOR UNIT MASONRY SHALL BE FINE GROUT CONFORMING TO ASTM C476 AND HAVE A
MINIMUM 28 DAY COMPRESSIVE STRENGTH ( FM ) OF 2500 PSI. GROUT SHALL HAVE A SLUMP OF 8 TO 11 INCHES AS MEASURED ACCORDING TO ASTM C143. COMPLY WITH TABLE 1.15.1 IN ACI
530.1 FOR DIMENSIONS OF GROUT SPACES AND POUR HEIGHT.
4. LAY SOLID MASONRY UNITS WITH COMPLETELY FILLED BED AND HEAD JOINTS; BUTTER ENDS WITH SUFFICIENT MORTAR TO FILL HEAD JOINTS AND SHOVE INTO PLACE. DO NOT DEEPLY FURROW BED
JOINTS OR SLUSH HEAD JOINTS.
5. DO NOT USE FROZEN MATERIALS OR MATERIALS MIXED OR COATED WITH ICE OR FROST. DO NOT
BUILD ON FROZEN SUBSTRATES. REMOVE AND REPLACE UNIT MASONRY DAMAGED BY FROST OR
BY FREEZING CONDITIONS. COMPLY WITH COLD-WEATHER CONSTRUCTION REQUIREMENTS
CONTAINED IN ACI 530.1.
6. COMPLY WITH HOT-WEATHER CONSTRUCTION REQUIREMENTS CONTAINED IN ACI 530.1.
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
E T
N
O R
C R
O S
S
G A
L
IV
E
L Y
A V
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S0.1
SPECIFICATIONS
AND INDEX
DRAWING INDEX
S0.1 SPECIFICATIONS AND INDEX
S0.2 SPECIAL INSPECTION
S0.3 ABBREVIATIONS, SYMBOLS & LAP LENGTH SCHEDULES
S1.1 FOUNDATION PLAN
S1.2 FOUNDATION PLAN - STORMWATER POND
S2.1 TYPICAL FOUNDATION DETAILS
S2.2 TYPICAL FOUNDATION DETAILS
TOTAL: 7
REVISIONS DATE
Docusign Envelope ID: CFDD52A8-E61D-8D4D-81B1-3C8EBE9D0629
STATEMENT OF SPECIAL INSPECTIONS BASED UPON THE 2024 IBC
SPECIAL INSPECTIONS SHALL BE PROVIDED FOR THIS PROJECT IN ACCORDANCE WITH THE FOLLOWING SCHEDULE. THE PROGRAM PROVIDED HEREIN SPECIFICALLY EXCLUDES ALL ELEMENTS NOT DESIGNED BY THE SER AND NON-STRUCTURAL ELEMENTS INCLUDING BUT NOT LIMITED: TO SMOKE CONTROL AND SMOKE EXHAUST SYSTEMS, SPRAYED FIRE-RESISTANT MATERIALS, MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS AND THEIR ATTACHMENTS EVEN THOUGH THEY MAY BE REQUIRED. THE PLAN OF SPECIAL INSPECTIONS FOR THESE EXCLUDED ITEMS MUST BE PREPARED BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF EACH DESIGNATED SYSTEM THAT IS SUBJECT TO SPECIAL INSPECTIONS, WHETHER IT IS ARCHITECTURAL, ELECTRICAL, MECHANICAL OR STRUCTURAL IN NATURE.
THE SPECIAL INSPECTION COORDINATOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION.
INTERIM REPORTS SHALL BE SUBMITTED MONTHLY TO THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THESE REPORTS SHALL INCLUDE THE DAILY OBSERVATION REPORTS AND A SUMMARY OF THE ACTIVITIES COMPLETED AND/OR IN PROGRESS THAT ARE RECEIVING SPECIAL INSPECTIONS. DAILY REPORTS SHOULD NOT BE PROVIDED TO THE SER FOR REVIEW UNLESS THERE IS AN UNCORRECTED DISCREPANCY. UNCORRECTED DISCREPANCIES
SHALL BE REPORTED TO THE SER WITHOUT DELAY.
THE SPECIAL INSPECTION PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES. JOB SITE SAFETY AND MEANS AND METHODS OF CONSTRUCTION ARE SOLELY THE RESPONSIBILITY OF THE CONTRACTOR.
THIS STATEMENT OF SPECIAL INSPECTIONS INCLUDES THE FOLLOWING BUILDING SYSTEMS:
FABRICATORS (1.0)
STEEL CONSTRUCTION (2.0)
CONCRETE CONSTRUCTION (3.0)
MASONRY CONSTRUCTION (4.0)
WOOD CONSTRUCTION (5.0)
SOILS CONSTRUCTION (6.0)
DRIVEN DEEP FOUNDATIONS (7.0)
CAST-IN-PLACE DEEP FOUNDATIONS (8.0)
HELICAL PILE FOUNDATIONS (9.0)
COLD-FORMED STEEL CONSTRUCTION (10.0)
RETAINING SYSTEMS PROVIDING VERTICAL RELIEF GREATER THAN
5FT IN HEIGHT WITH HORIZONTAL SEPARATION DISTANCE OF 50 FT
OR LESS (11.0)
THIS STRUCTURE HAS A RISK CATEGORY II, IS LESS THAN 75 FT AND THE BASIC WIND SPEED Vasd IS LESS THAN 110 MPH AND IS THEREFORE EXEMPT FROM STRUCTURAL OBSERVATIONS FOR WIND REQUIREMENTS (IBC 1704.6.1).
THIS STRUCTURE HAS A SEISMIC DESIGN CATEGORY OF C AND IS THEREFORE EXEMPT FROM SPECIAL OBSERVATIONS FOR
SEISMIC RESISTANCE (IBC 1704.6.1).
3.0 CONCRETE CONSTRUCTION (IBC 1705.3)
ITEM CONTINUOUS PERIODIC DETAILED INSTRUCTIONS
3.1 VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS
OF SPECIFIED TYPE, GRADE AND SIZE; THAT IT IS FREE OF
OIL, DIRT AND RUST; THAT IT IS LOCATED AND SPACED
PROPERLY; THAT HOOKS, BENDS, TIES, STIRRUPS AND
SUPPLEMENTAL REINFORCEMENT ARE PLACED CORRECTLY;
THAT LAP LENGTHS, STAGGER AND OFFSETS ARE PROVIDED;
AND THAT ALL MECHANICAL CONNECTIONS ARE INSTALLED
PER THE MANUFACTURER’S INSTRUCTIONS AND/OR
EVALUATION REPORT.
REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS
3.2 VISUALLY INSPECT ALL WELDS AND ALSO VERIFY
WELDABILITY OF REINFORCING STEEL BASED UPON CARBON
EQUIVALENT AND IN ACCORDANCE WITH AWS D1.4.
WELDING OF REINFORCING STEEL
3.3 INSPECTION OF ANCHORS OR EMBEDS CAST IN CONCRETE IS
REQUIRED WHEN ALLOWABLE LOADS HAVE BEEN INCREASED
OR WHERE STRENGTH DESIGN IS USED.
CAST-IN BOLTS & EMBEDS
3.4 ALL POST-INSTALLED ANCHORS/DOWELS SHALL BE SPECIALLY
INSPECTED AS REQUIRED BY THE APPROVED ICC-ES REPORT.
HORIZONTALLY OR UPWARDLY INCLINED ANCHORS THAT
RESIST SUSTAINED TENSION LOADS REQUIRE CONTINUOUS
INSPECTION AND APPROVED INSTALLERS.
POST-INSTALLED ANCHORS OR
DOWELS
3.5 VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318: CH. 19, 26.4.3, 26.4.4;
AND IBC 1904.1, 1904.2, 1908.2, 1908.3.
USE OF REQUIRED MIX DESIGN
3.6 CONCRETE SAMPLING FOR
STRENGTH TESTS, SLUMP, AIR
CONTENT, AND TEMPERATURE
3.7 CONCRETE & SHOTCRETE
PLACEMENT
3.8 CURING TEMPERATURE AND
TECHNIQUES
VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS
KEPT AT > 50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT.
HIGHEARLY-STRENGTH CONCRETE SHALL BE KEPT AT > 50°F
FOR AT LEAST 3 DAYS. ACCELERATED CURING METHODS MAY
BE USED (SEE ACI 318: 26.4.7-26.4.9). THE AMBIENT
TEMPERATURE FOR SHOTCRETE SHALL BE > 40°F FOR THE
SAME PERIOD OF TIME AS NOTED FOR CONCRETE.
SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST FOR AT
LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS, FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO
AVOID PLASTIC SHRINKAGE CRACKING AND THAT THE
SPECIFIED WATER/CEMENT RATIO IS NOT EXCEEDED.
3.6 PRE-STRESSED CONCRETE
3.7 VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED,
ASSEMBLED AND BRACED IN ACCORDANCE WITH THE
APPROVED CONSTRUCTION DOCUMENTS.
ERECTION OF PRECAST CONCRETE
3.8 VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED
PRIOR TO THE REMOVAL OF SHORES AND FORMS OR THE
STRESSING OF POST-TENSIONED TENDONS.
STRENGTH VERIFICATION
3.9 VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM
TO THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS
AS REQUIRED BY THE APPROVED CONSTRUCTION
DOCUMENTS.
FORMWORK
11.0 RETAINING SYSTEMS PROVIDING VERTICAL RELIEF
GREATER THAN 5FT IN HEIGHT WITH HORIZONTAL SEPARATION
DISTANCE OF 50 FT OR LESS(IBC 1807.2)
ITEM
11.1
CONTINUOUS PERIODIC DETAILED INSTRUCTIONS
FOUNDATION SUPPORT SYSTEM VERIFY FOUNDATION SUPPORT SYSTEM IS ADEQUATE FOR THE
INTENDED SITE CONDITIONS
11.2 QUALITY OF CONSTRUCTION
MATERIALS
VERIFY WITH MEASUREMENTS THE QUALITY OF THE
CONSTRUCTION MATERIALS FOR CONFORMANCE WITH THE
SPECIFICATIONS
11.3 ANTICIPATED DESIGN
CONDITIONS
VERIFY THE SIMILARITY OF ACTUAL SOIL CONDITIONS TO
THOSE ANTICIPATED IN DESIGN
11.4 BACKFILL MATERIALS AND
DRAINAGE SYSTEMS
VERIFY AND EXAMINE BACKFILL MATERIALS AND DRAINAGE
SYSTEMS FOR COMPLIANCE WITH PLANS AND SPECIFICATIONS
6.0 SOILS CONSTRUCTION (IBC 1705.6)
ITEM
6.1
CONTINUOUS PERIODIC DETAILED INSTRUCTIONS
VERIFY SUBGRADE IS ADEQUATE
TO ACHIEVE DESIGN BEARING
CAPACITY.
PRIOR TO PLACEMENT OF CONCRETE.
6.2 VERIFY SUBGRADE IS ADEQUATE
TO ACHIEVE DESIGN BEARING
CAPACITY.
PRIOR TO PLACEMENT OF COMPACTED FILL OR CONCRETE.
6.3 VERIFY THAT SUBGRADE HAS BEEN
APPROPRIATELY PREPARED PRIOR
TO PLACING COMPACTED FILL
PRIOR TO PLACEMENT OF COMPACTED FILL.
6.4 PERFORM CLASSIFICATION AND
TESTING OF COMPACTED FILL
MATERIALS
ALL MATERIALS SHALL BE CHECKED AT EACH LIFT FOR
PROPER CLASSIFICATIONS AND GRADATIONS NOT LESS THAN
ONCE FOR EACH 10,000FT² OF SURFACE AREA.
6.5 VERIFY PROPER MATERIALS,
DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND
COMPACTION.
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
R
C R
O S
S
G A
L
IV
E
L Y
A
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S0.2
SPECIAL
INSPECTION
HOOK DEVELOPMENT LENGTH "Ldh" (INCHES)
BAR SIZE
#5
#6
#7
#8
#9
#10
#11 f'c=3000 PSI f'c=4000 PSI f'c=5000 PSI f'c=6000 PSI f'c=7000 PSI
#4
#3
NORMAL WEIGHT CONCRETE, GR.60 REINFORCEMENT, UNCOATED
NOTE: DO NOT USE THIS TABLE FOR SPLICING REINFORCEMENT. REFER TO LAP LENGTH TABLES THIS
DRAWING
f'c=8000 PSI
FOOTING REINFORCEMENT LAP LENGTH (INCHES)
BAR SIZE
#5
#6
#7
#8
#9
#10
#11 f'c=3000 PSI f'c=4000 PSI f'c=5000 PSI f'c=6000 PSI f'c=7000 PSI
OTHER
BARS
TOP
BAR
#4
#3
OTHER
BARS
TOP
BAR
OTHER
BARS
TOP
BAR
OTHER
BARS
TOP
BAR
OTHER
BARS
TOP
BAR
NORMAL WEIGHT CONCRETE, GR.60 REINFORCEMENT, UNCOATED
MIN. BAR
SPACING
1 1/8"
1 1/2"
1 7/8"
2 1/4"
2 5/8"
3"
3 1/2"
3 7/8"
4 1/4" f'c=8000 PSI
OTHER
BARS
TOP
BAR
NOTE: REFER TO NOTE 8 FOR BAR SPACINGS THAT
DO NOT MEET MIN BAR SPACINGS NOTED
VERTICAL WALL REINFORCEMENT LAP LENGTH (INCHES)
BAR SIZE
#5
#6
#7
#8
#9
#10
#11 f'c=3000 PSI f'c=4000 PSI f'c=5000 PSI f'c=6000 PSI f'c=7000 PSI
#4
#3
NORMAL WEIGHT CONCRETE, GR.60 REINFORCEMENT, UNCOATED
MIN. BAR
SPACING
1 1/8"
1 1/2"
1 7/8"
2 1/4"
2 5/8"
3"
3 1/2"
3 7/8"
4 1/4" f'c=8000 PSI
NOTE: REFER TO NOTE 8 FOR BAR SPACINGS THAT
DO NOT MEET MIN BAR SPACINGS NOTED
HORIZONTAL WALL REINFORCEMENT LAP LENGTH (INCHES)
BAR SIZE
#5
#6
#7
#8
#9
#10
#11 f'c=3000 PSI f'c=4000 PSI f'c=5000 PSI f'c=6000 PSI f'c=7000 PSI
#4
#3
NORMAL WEIGHT CONCRETE, GR.60 REINFORCEMENT, UNCOATED
MIN. BAR
SPACING
1 1/8"
1 1/2"
1 7/8"
2 1/4"
2 5/8"
3"
3 1/2"
3 7/8"
4 1/4" f'c=8000 PSI
NOTE: REFER TO NOTE 8 FOR BAR SPACINGS THAT DO NOT
MEET MIN BAR SPACINGS NOTED
BAR DEVELOPMENT LENGTH "Ld" (INCHES)
BAR SIZE
#5
#6
#7
#8
#9
#10
#11 f'c=3000 PSI f'c=4000 PSI f'c=5000 PSI f'c=6000 PSI f'c=7000 PSI
#4
#3
NORMAL WEIGHT CONCRETE, GR.60 REINFORCEMENT, UNCOATED
NOTE: DO NOT USE THIS TABLE FOR SPLICING REINFORCEMENT. REFER TO LAP LENGTH TABLES THIS
DRAWING
f'c=8000 PSI
TYPICAL MARK TO DENOTE SLAB STEP
TYPICAL MARK TO DENOTE STEP IN FOOTING LOCATION AND CHANGE IN
ELEVATION VALUE. REFER TO TYPICAL FOOTING STEP DETAIL.
WALL FOOTING MARK, REFER TO SCHEDULE
TYPICAL FOUNDATION PLAN SYMBOLS
16"
WF2.5
1/2"
T/F
TG
0'- 0"
TOP OF FOOTING ELEVATION CALLOUT
@ AT
AB ANCHOR BOLT
ADDL ADDITIONAL
ACI AMERICAN CONCRETE INSTITUTE
ASCE AMERICAN SOCIETY OF CIVIL
ENGINEERS
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
APA AMERICAN PLYWOOD ASSOCIATION
ARCH ARCHITECTURAL
ASL ABOVE SEA LEVEL
ASTM AMERICAN SOCIETY FOR TESTING
AND MATERIALS
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
BM BEAM
BOT BOTTOM
BRG BEARING
BTWN BETWEEN
B/W BETWEEN
C CAMBER OR COMPRESSION
CC CENTER TO CENTER
CANT CANTILEVER
CFS COLD FORMED STEEL
CIP CAST-IN-PLACE
CJ CONTRACTION (CONTROL) JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CONSTR JT CONSTRUCTION JOINT
D DEPTH
db BAR DIAMETER
DBA DEFORMED BAR ANCHOR
DBE DECK BEARING ELEVATION
DBL DOUBLE
DEG DEGREES
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DJ DOUBLE JOIST
DL DEAD LOAD
DN DOWN
DO DITTO
DWG DRAWING
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATION OR ELEVATOR
EMBED EMBEDMENT
ENGR ENGINEER
EOS EDGE OF SLAB, EDGE OF
STRUCTURE
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EW EACH WAY
EX EXISTING
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
f'c 28 DAY COMPRESSION
STRENGTH
FD FLOOR DRAIN
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FLR FLOOR
FL FULL LENGTH
FNDN FOUNDATION
FS FAR SIDE
FT FOOT OR FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
Fy YIELD STRENGTH
GA GAGE
GALV GALVANIZE(D)
GB GRADE BEAM
GEN GENERAL
GR GRADE
GYP GYPSUM
HDG HOT DIPPED GALVANIZED
HI HIGH
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
ID INSIDE DIAMETER
IF INSIDE FACE
INT INTERIOR
JBE JOIST BEARING ELEVATION
JT JOINT
K 1000 POUNDS, KIP
KIP 1000 POUNDS
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LBS POUNDS
Ld DEVELOPMENT LENGTH Ldh HOOK DEVELOPMENT LENGTH
LE LEFT END
LF LATERAL FRAME
LFRS LATERAL FORCE RESISTING SYSTEM
LG LONG
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LSH LONG SIDE HORIZONTAL
LSL LONG SLOTTED HOLE (AISC)
LSV LONG SIDE VERTICAL
LVL LEVEL
LW LIGHTWEIGHT
LWC LIGHTWEIGHT CONCRETE
LRFD LOAD RESISTANCE FACTOR DESIGN
M MOMENT
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MC MOMENT CONNECTION
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
& FIRE PROTECTION
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MLS MASONRY LAP SPLICE LENGTH
MTL METAL
NDS NATIONAL DESIGN SPECIFICATION
FOR WOOD CONSTRUCTION
NIC NOT IN CONTRACT
NIS NOT IN SUBMISSION
NLGA NATIONAL LUMBER GRADES
AUTHORITY
No. NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OD OUTSIDE DIAMETER
OC ON CENTER
OF OUTSIDE FACE
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OVS OVERSIZED HOLE (AISC)
P AXIAL FORCE
PAF POWDER ACTUATED FASTENER
PCF POUNDS PER CUBIC FOOT
PCI POUNDS PER SQUARE INCH PER INCH
PERP PERPENDICULAR
PEN PANEL EDGE NAILING
PEN PENETRATION
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTS POINTS
PT POST TENSIONED (CONCRETE)
PT PRESSURE TREATED (TIMBER)
QTY QUANTITY
R RADIUS OR REACTION
RAD RADIUS
RE RIGHT END
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
REQ(S) REQUIREMENT(S)
REV REVISION
RTU ROOF TOP UNIT
RXN REACTION
SC SLIP CRITICAL
SCHED SCHEDULE
SECT SECTION
SER STRUCTURAL ENGINEER OF RECORD
SEOR STRUCTURAL ENGINEER OF RECORD
SF SQUARE FOOT
SHT SHEET
SI SPECIAL INSPECTIONS, SPECIAL
INSPECTOR
SIM SIMILAR
SLBB SHORT LEG BACK TO BACK
SOG SLAB ON GRADE
SOMD SLAB ON METAL DECK
SPA SPACING
SPEC SPECIFICATIONS
SPIB SOUTHERN PINE INSTITUTES BUREAU
SPF SPRUCE PINE FIR
SR STUD RAIL
SQ SQUARE
SS STAINLESS STEEL
SSL SHORT SLOTTED HOLE (AISC)
SST SIMPSON STRONG TIE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL OR STRUCTURE
SYMM SYMMETRICAL, SYMMETRIC
SYP SOUTHERN YELLOW PINE
T THICKNESS OR TENSION
Tu TRANSFER FORCE, ULTIMATE
T&B TOP AND BOTTOM
T/ TOP OF
TEMP TEMPERATURE OR TEMPORARY
TJ TRIPLE JOIST
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOM TOP OF MASONRY
TOS TOP OF SLAB OR TOP OF STEEL
TOW TOP OF WALL
TPI TRUSS PLATE INSTITUTE
TRPL TRIPLE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V SHEAR FORCE
VERT VERTICAL
W WIDTH
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WT WEIGHT OR WT SECTION PER AISC
WWR WELDED WIRE REINFORCEMENT
WWF WELDED WIRE FABRIC, SEE WWR
XJ EXTRA JOIST
XS EXTRA STRONG
XXS DOUBLE EXTRA STRONG
COMMON ABBREVIATIONS & DEFINITIONS
DETAIL REFERENCE
NUMBER OR LETTER
SHEET WHERE
DETAIL IS DRAWN
DETAIL REFERENCE
NUMBER OR LETTER
SHEET WHERE DETAIL IS CUT OR
CALLED OUT, IF SHEET NUMBER IS
OMITTED, ITEM IS A TYPICAL DETAIL,
SCHEDULE OR LEGEND
SX
X
SIM
INDICATES 'SIMILAR'
CONDITION
DETAIL REFERENCE
NUMBER OR LETTER
AREA
CONTAINED
IN DETAIL
S5.1
SHEET WHERE
ELEVATION IS SHOWN
ELEVATION
REFERENCE NUMBER
DETAIL REFERENCES
INDICATES 'SIMILAR'
CONDITION
SECTIONS
DETAILS
VIEW TITLES
ELEVATIONS
SX
X
SIM
INDICATES 'SIMILAR'
CONDITION
X
SX
SIM
DEVELOPMENT AND LAP LENGTH SCHEDULE NOTES:
1. ALL SPLICE LENGTHS ARE IN INCHES.
2. TABULATED LAP SPLICE VALUES ARE BASED UPON ACI 318-19 CLASS B SPLICE LENGTHS.
3. THESE TABLES APPLY TO NORMAL WEIGHT CONCRETE ONLY, EXCEPT WHERE INDICATED.
4. WHEN SPECIFIED COMPRESSIVE STRENGTH (f'c) IS BETWEEN TABULATED STRENGTHS, USE LOWER f'c TO DETERMINE SPLICE
LENGTHS
5. FOR EPOXY-COATED BARS, MULTIPLY SPLICE LENGTH VALUES BY 1.5.
6. FOR BARS OF DIFFERENT SIZES, USE THE LARGER OF THE DEVELOPMENT LENGTH OF THE LARGER BAR AND THE LAP
LENGTH OF THE SMALLER BAR.
7. ACI DEFINES 'TOP BARS' AS HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF FRESH CONCRETE
IS CAST BELOW THE DEVELOPMENT LENGTH OR SPLICE. "OTHER BARS" ARE DEFINED AS ALL OTHER CONDITIONS.
8. WHERE BAR SPACINGS ARE LESS THAN THE MINIMUM BAR SPACINGS TABULATED, SUBMIT LAP SPLICE LENGTHS TO NV5 FOR
APPROVAL.
9. SUBMIT SPLICE LENGTHS FOR APPROVAL WHERE CONDITIONS DIFFER FROM THE COMPRESSIVE STRENGTHS, BAR SIZES, MINIMUM SPACINGS, AND CONCRETE WEIGHT CLASSES LISTED.
10. DO NOT LAP SPLICE #14 AND #18 BARS, INCLUDING #14 AND #18 BARS WITH SMALLER BARS. PROVIDE MECHANICAL
COUPLERS CAPABLE OF DEVELOPING, IN TENSION OR COMPRESSION, 1.25 fy OF THE BAR OR WELD IN ACCORDANCE WITH ACI
318. STAGGER SPLICES FOR MEMBERS DESIGNATED AS TENSION TIE MEMBERS AT LEAST 30 INCHES IN ACCORDANCE WITH
ACI 318
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
R
C R
O S
S
G A
L
IV
E
L Y
A
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S0.3
ABBREVIATIONS,
SYMBOLS & LAP
LENGTH
SCHEDULES
1. REFER TO GENERAL NOTES AND SPECIFICATIONS FOR ADDITIONAL STRUCTURAL INFORMATION.
2. REFER TO TYPICAL DETAIL SHEETS S2.1 AND S2.2 FOR ADDITIONAL REQUIREMENTS NOT SHOWN.
3. ALL FOOTING ELEVATIONS ARE MEASURED FROM MEAN SEA LEVEL ELEVATION (0'-0"). REFER TO
PLAN FOR FOOTING ELEVATIONS.
4. REFER TO CIVIL DRAWINGS FOR DIMENSIONS AND ADDITIONAL REQUIREMENTS NOT SHOWN.
5. THE SER HAS NOT PERFORMED A SITE VISIT TO VERIFY STRUCTURAL CONDITIONS. ALL ASSUMED
INFORMATION SHOWN ON THESE DRAWINGS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO
CONSTRUCTION. CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO THE SER BEFORE
PROCEEDING.
6. REFER TO CIVIL FOR RETAINING WALL LOCATIONS.
FOUNDATION PLAN NOTES
RW2
T/W
ALL
EL
.35
T/F
TG
EL
1, 6.
T/W
ALL
EL
.90T/W
ALL
EL
.10
TYP
1'-0" T/W
ALL
EL
.40 T/F
TG
EL
1, 0.
RW1
T/F
TG
EL
1, 0.
T/W
ALL
EL
.00
T/F
TG
EL
1, 8.
T/W
ALL
EL
.50
T/F
TG
EL
1, 6.
T/W
ALL
EL
.75
24''
16''
R W
4-
PROPERTY LINE
EXIST BUILDING
FFE: 1035.42' (FV)
S2.2
R W
4-
R W
4-
R W
4-
T/W
ALL
EL
.12
T/W
ALL
EL
.88T/W
ALL
EL
.12
T/W
ALL
EL
.90
T/W
ALL
EL
.27
T/W
ALL
EL 1041.27
RW3-1 RW3-2
RW3-3T/W
ALL
EL
.50
T/W
ALL
EL
.90T/W
ALL
EL
.02
T/W
ALL
EL 1,040.54
T/W
ALL
EL
.71
T/W
ALL
EL
.21
T/W
ALL
EL 1,037.67
RW3-1
R W
3-
T/W
ALL
EL
.00
NOTE: RECORD DRAWINGS OF THE EXISTING BUILDING
WERE NOT AVAILABLE AT THE TIME OF DESIGN. GC
FIELD VERIFY THAT THE BOTTOM OF THE WALL
FOOTING MATCHES THE BOTTOM OF THE EXISTING
FOOTING SO AS NOT TO UNDERMINE EACH OTHER.
NOTIFY THE SER OF ANY DISCREPANCIES PRIOR TO
CONSTRUCTION.
ASSUMED COLUMN
FOOTING, GC FV, TYP
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
R
C R
O S
S
G A
L
IV
E
L Y
A
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S1.1
FOUNDATION
PLAN
N
SCALE: 1" = 10'-0"1
FOUNDATION PLAN
1. REFER TO GENERAL NOTES AND SPECIFICATIONS FOR ADDITIONAL STRUCTURAL INFORMATION.
2. REFER TO TYPICAL DETAIL SHEETS S2.1 AND S2.2 FOR ADDITIONAL REQUIREMENTS NOT SHOWN.
3. ALL FOOTING ELEVATIONS ARE MEASURED FROM MEAN SEA LEVEL ELEVATION (0'-0"). REFER TO
PLAN FOR FOOTING ELEVATIONS.
4. REFER TO CIVIL DRAWINGS FOR DIMENSIONS AND ADDITIONAL REQUIREMENTS NOT SHOWN.
5. THE SER HAS NOT PERFORMED A SITE VISIT TO VERIFY STRUCTURAL CONDITIONS. ALL ASSUMED
INFORMATION SHOWN ON THESE DRAWINGS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO
CONSTRUCTION. CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO THE SER BEFORE
PROCEEDING.
6. REFER TO CIVIL FOR RETAINING WALL LOCATIONS.
FOUNDATION PLAN NOTES
16''
RW5-1
R W
5-
R W
5-
T/F
TG
EL
1, 2.
T/W
ALL
EL
.50
T/F
TG
EL
1, 4.
WEIR OPENING PER CIVIL
R W
5-
T/W
ALL
EL 1
2.0
R W
5-
R W
5-
16''
T/F
TG
EL
1, 4.
T/W
ALL
EL
.00
T/W
ALL
EL
.50
T/W
ALL
EL
.50
T/W
ALL
EL
.00
T/W
ALL
EL
.50
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
R
C R
O S
S
G A
L
IV
E
L Y
A
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S1.2
FOUNDATION
PLAN -
STORMWATER
POND
N
SCALE: 1" = 10'-0"1
FOUNDATION PLAN - STORMWATER POND
ISOMETRIC2
3D - STORMWATER POND
NOTE: ISOMETRIC VIEW IS FOR
REFERENCE ONLY AND DOES NOT
ILLUSTRATE ALL ELEMENTS OF
CONSTRUCTION.
EL PER PLAN
T/WALL
"M" HORIZ BARS
ROUGHEN SURFACE
EL VARIES
T/GRADE
EL PER PLAN
T/FTG
1' -4
M
IN
C
LR3"
"F" DOWELS
REFER TO CIVIL DWGS FOR
DRAINAGE REQS
LA
P
G
"A"
C
LR2"
T H
IC
K
N E
S S
"B
F T
G M
A X
R E
T A
IN
E
D H
E
IG
H T
H
W
"L"
WALL
THICKNESS
"N" VERT BARS
CENTERED IN WALL
"D" BARS
"E" BARS
TYP
3" CLR
CANTILEVERED CONCRETE RETAINING WALL SCHEDULE
(SINGLE LAYER REINFORCEMENT)
MAXIMUM
RETAINED HEIGHT
"HW" A
FOOTING REQUIREMENTS
3'-0"
3'-7"
5'-0"
B
1'-0"
1'-0"
1'-3"
C
1'-2"
1'-2"
1'-6"
"D" BARS
#5 @14''
"E" BARS "F" DOWELS G
31"
31"
37"
#5 @ 14''
#6 @ 12''
#5 @ 14"
#5 @ 14"
#6 @ 12"
#5 @ 14"
#5 @ 14"
#6 @ 12"
"M" BARS
#4 @ 12"
#4 @ 12"
#4 @ 12"
L
8"
8"
8"
"N" BARS
#5 @ 14"
#5 @ 14"
#6 @ 12"
4'-0"
5'-0"
7'-0"
WALL REQUIREMENTS
NOTES:
1. LAP "D" AND "M" BARS PER LAP SCHEDULE.
2. PROVIDE CONTROL JOINT @ 20'-0" MAXIMUM; COORDINATE WITH
ARCHITECTURAL DRAWINGS, PER TYPICAL DETAIL.
3. PROVIDE CONSTRUCTION JOINT @ 60' O.C. MAXIMUM, PER TYPICAL DETAIL.
4. REFER TO CIVIL AND PLUMBING DRAWINGS FOR DRAINAGE REQUIREMENTS
AND CONNECTION DETAILS.
5. RETAINING WALL HAS BEEN DESIGNED FOR DRAINED CONDITION BEHIND
WALL.
6. RETAINING WALL HAS BEEN DESIGNED FOR LEVEL BACKFILL BEHIND WALL.
NOTIFY THE SER IF GRADE SLOPES UP BEHIND WALL
GEOCOMPOSITE
DRAINAGE MAT
REFER TO CIVIL DWGS
FOR WATERPROOFING AS
REQ'D
REFER TO SPECS/ GENERAL
NOTES FOR BACKFILL REQS.
SPECIFIED BACKFILL SOIL
PROPERTIES MAY VARY FROM ON
SITE SOIL PROPERTIES
"D" BARS
"E" BARS
"C"
TOE SIDE HEEL SIDE
STANDARD HOOK
EXTEND DOWEL
TO TOE
WEEPHOLES @ 10'-0" MAX
WALL CALLOUT
RW1
RW2
RW3-1
ASHLAR STONE VENEER AT
RW1,RW2 AND RW4 PER CIVIL
DECORATIVE STEEL FENCE PER CIVIL
SOLID 4'' CMU BELOW GRADE
4'-6" 1'-0" 1'-6" 31"#5 @ 14'' #5 @ 14" #5 @ 14" #4 @ 12"8" #5 @ 14"5'-0"RW3-2
3'-0" 1'-0" 1'-2" 31"#5 @ 14'' #5 @ 14" #5 @ 14" #4 @ 12"8" #5 @ 14"4'-0"RW3-3
5'-4" 1'-0" 1'-4" 31"#5 @ 14'' #5 @ 14" #5 @ 14" #4 @ 12"8" #5 @ 14"5'-0"RW4-1
5'-7" 1'-5" 1'-7" 37"#6 @ 14'' #6 @ 14" #6 @ 14" #4 @ 12"8" #6 @ 14"5'-9"RW4-2
3'-0" 1'-0" 1'-4" 31"#5 @ 14'' #5 @ 14" #5 @ 14" #4 @ 12"8" #5 @ 14"4'-0"RW4-3
BACKFILL PER
FOUNDATION GENERAL
NOTES. UNO
COARSE AGGREGATE
DRAINAGE FILL
MATERIAL
FILTER FABRIC
EXTERIOR PAVING OR
GRADE PER CIVIL
SLOPE PER GEOTECH
REPORT & OSHA REQS
GEOCOMPOSITE
DRAINAGE MAT, CONNECT
TO DRAIN PIPE
RETAINING WALL
PER PLAN
FOUNDATION PER PLAN
SLOTTED AND SLOPED DRAIN PIPE.
DISCHARGE TO DAYLIGHT OR
STORM SEWER PER CIVIL. REFER
TO CIVIL / PLUMBING DWGS AND
SPECS FOR REQS
UNDISTURBED SITE SOIL
NOTES
1. RETAINING WALLS HAVE BEEN DESIGNED FOR
DRAINED CONDITION, FREE OF HYDROSTATIC
PRESSURE.
2. WHERE STABLE SLOPES CANNOT BE ACHIEVED
DUE TO SITE RESTRICTIONS, PROVIDE
TEMPORARY SHORING DESIGNED BY A QUALIFIED
PROFESSIONAL ENGINEER.
3. REFER TO CIVIL DRAWINGS FOR LOCATIONS OF
DRAIN PIPES, INVERTS, CONNECTION DETAILS,
AND DRAINAGE MAT TIE-IN DETAILS.
4. PROVIDE DRAIN PIPE CLEANOUTS TO PERMIT
PERIODIC MAINTENANCE. REFER TO CIVIL FOR
REQUIREMENTS.
ELEV PER PLAN
T/FTGM
IN6"
NOTE: DO NOT
DISCHARGE STORM
WATER BEHIND
RETAINING WALL
REFER TO FOUNDATION
GENERAL NOTES FOR NET
ALLOWABLE SOIL BEARING
PRESSURES
1'-6"
1'-0" IMPERVIOUS
MATERIAL TO LIMIT WATER
RETENTION
SEPARATION FABRIC
"O" VERT BARS
EL PER PLAN
T/WALL
"M" HORIZ BARS
ROUGHEN SURFACE
EL VARIES
T/GRADE
EL PER PLAN
T/FTG
1' -4
M
IN
C
LR3"
"F" DOWELS
REFER TO CIVIL DWGS FOR
DRAINAGE REQS
LA
P
G
"A"
C
LR2"
T H
IC
K
N E
S S
"B
F T
G M
A X
R E
T A
IN
E
D H
E
IG
H T
H
W
"L"
WALL
THICKNESS
"N" VERT BARS
"D" BARS
"E" BARS
TYP
2" CLR
CANTILEVERED CONCRETE RETAINING WALL SCHEDULE
(TOW LAYERS REINFORCEMENT)
MAXIMUM
RETAINED HEIGHT
"HW" A
FOOTING REQUIREMENTS
9'-0"
13'-0"
10'-0"
B
1'-8"
2'-4"
2'-0"
C
2'-0"
3'-0"
2'-6"
"D" BARS
#7 @ 12''
"E" BARS "F" DOWELS G
54"
62"
54"
#8 @ 9''
#7 @ 12''
#7 @ 12"
#8 @ 9"
#7 @ 12"
#7 @ 12"
#8 @ 9"
#7 @ 12"
"M" BARS
#4 @ 12"
#4 @ 12"
#4 @ 12"
L
12"
12"
12"
"N" BARS
#7 @ 12"
#8 @ 9"
#8 @ 12"
"O" BARS
#5 @ 18"
#5 @ 18"
#5 @ 18"
9'-4''
11'-4"
10'-0''
WALL REQUIREMENTS
NOTES:
1. LAP "D" AND "M" BARS PER LAP SCHEDULE.
2. PROVIDE CONTROL JOINT @ 20'-0" MAXIMUM; COORDINATE WITH
ARCHITECTURAL DRAWINGS, PER TYPICAL DETAIL.
3. PROVIDE CONSTRUCTION JOINT @ 60' O.C. MAXIMUM, PER TYPICAL DETAIL.
4. REFER TO CIVIL AND PLUMBING DRAWINGS FOR DRAINAGE REQUIREMENTS
AND CONNECTION DETAILS.
5. RETAINING WALL HAS BEEN DESIGNED FOR DRAINED CONDITION BEHIND
WALL.
6. RETAINING WALL HAS BEEN DESIGNED FOR LEVEL BACKFILL BEHIND WALL.
NOTIFY THE SER IF GRADE SLOPES UP BEHIND WALL
GEOCOMPOSITE
DRAINAGE MAT
REFER TO CIVIL DWGS
FOR WATERPROOFING AS
REQ'D
FREE DRAINING STONE BACKFILL
WASHED NO. 57, MAX 2% PASSING
NO. 200 SIEVE. NO ABC OR
CRUSHER RUN.
"D" BARS
"E" BARS
"C"
TOE SIDE DOWELS W/
STD HK TO MATCH "O"
BAR SIZE AND SPACING
LA
P
TOE SIDE HEEL SIDE
STANDARD HOOK
EXTEND DOWEL
TO TOE
4'' ⌀ @ 10'-0" MAX, REFER TO
CIVIL FOR INVERT
DECORATIVE STEEL FENCE PER CIVIL
WALL CALLOUT
RW5-3
RW5-4
RW5-5
7'-6" 1'-5" 2'-0" 37"#6 @ 12'' #6 @ 12" #6 @ 12" #4 @ 12"12" #6 @ 12"7'-10"RW5-1
6'-0" 1'-5" 1'-6" 37"#6 @ 12'' #6 @ 12" #6 @ 12" #4 @ 12"12" #6 @ 12"6'-6"RW5-2
"P
''Q''
KEY REQUIREMENTS
P Q ''R'' STIRRUP
''R'' STIRRUP
#5 @ 18"
#5 @ 18" 2'-0" 2'-0" #7 @ 12''
2'-0" 2'-0" #7 @ 12''
2'-0" 2'-0" #7 @ 12''
2'-0" 2'-0" #7 @12
3'-0" 3'-0" #8 @ 9''
2-#7 CONT BARS AT 2'-0''x2'-0'' KEY 4-#7 CONT BARS AT 3'-0''x3'-0'' KEY
R
G
EO AI
G
E EI
N G N E E R E
D
R
KCAJ
A B
N
I NG
N
S
R
EG
E T
DE
RE
PROFESSIONAL
No. 027967
NV5 ENGINEERS AND CONSULTANTS, INC.
1101 Haynes Street, Suite 207
Raleigh, NC 27604
T. 919-821-7146 | www.NV5.com
DRAWING TITLE
D O
W N
T O
W N
N O
R C
R O
S S
P A
R K
IN
G
I M
P R
O V
E M
E N
T S
C
IT
Y O
F N
O R
C R
O S
S
L A
W R
E N
C E
V
IL
L E
S T
R E
R
C R
O S
S
G A
L
IV
E
L Y
A
R C
R O
S S
G
A
C L
IE
N T
P R
O J E
C T
PROJECT NO.
DATE
DRAWN BY DRAWING NO.
DRAWING FILE:
SEAL DATE:
GA COA #: PEF003715
FOR BIDDING PURPOSES ONLY - NOT
RELEASED FOR CONSTRUCTION
AUG 14,2026
/1
/2
:3 :0
P
M
NKF
AUG 14, 2026
6170050.01 S2.1
TYPICAL
FOUNDATION
DETAILS
DETAIL3
TYPICAL SITE RETAINING WALL
BACKFILL & DRAINAGE
REQUIREMENTS
SCALE: 3/8" = 1'-0"
SCHEDULE1
CANTILEVERED CONCRETE
RETAINING WALL SCHEDULE
SCHEDULE2
CANTILEVERED CONCRETE
RETAINING WALL SCHEDULE
CONC FTG, SEE
SCHED FOR SIZE
AND REINF REQS
COMPACTED SOIL, SEE
FOUNDATION SPECS
REINF TO MATCH BOT OF
WALL FTG REINF, TYP
MAX
Ld
M A
X
2' -0
T MIN
CLR
3"
T
Ld2T MIN
T MIN
T
TOP LAYER FTG REINF AS
REQ'D PER SCHED,
TERMINATE WITH STD HK
CLR
2"
T
Ld
NOTE:
1. REFER TO FOOTING SCHEDULE FOR
FOOTING THICKNESS, 'T'
2. REFER TO DEVELOPMENT LENGTH
SCHEDULE FOR DEVELOPMENT LENGTH
'Ld'
EL PER PLAN
T/FTG
EL PER PLAN
T/FTG
C
LR2"
CUT OR BUTT 50% OF HORIZ REINF
BAR 2" CLEAR OF JOINT, EA FACE
CONTROL JOINT, CAULK WITH
ELASTOMERIC SEALANT AT
EXPOSED FACE
NOTE:
PROVIDE CONTROL JOINTS IN ALL
WALLS AT 20'-0" MAX AND 10'-0"
FROM WALL CORNERS AND
INTERSECTIONS.
t t/8 3/4"
TYP
2" CLR
NOTE:
PROVIDE CONSTRUCTION JOINTS IN ALL WALLS
AND SLABS AS REQUIRED FOR CONSTRUCTION
AND AT 60'-0" MAX.
CUT OR BUTT 50% OF HORIZ REINF
BAR 2" CLEAR OF JOINT, EA FACE
CONTROL JOINT, CAULK WITH
ELASTOMERIC SEALANT AT
EXPOSED FACE
t t/8
3/4"
CONT KEYWAY
WATERSTOP
PER SPECS
TYP
2" CLR
t/3 t/3 t/3
AT CORNERS T INTERSECTION
STANDARD HOOK
(12" MIN), TYP, UNO
NOTES:
1. VERTICAL REINFORCING NOT SHOWN FOR CLARITY.
2. HOOKED, CORNER, AND "U" BARS SHALL MATCH SIZE OF
HORIZONTAL WALL REINFORCING, TYP. UON.
STANDARD HOOK
(12" MIN), TYP, UNO
IF CONSTRUCTION JOINT EXISTS
AT CORNERS
STANDARD HOOK
(12" MIN), TYP, UNO
STANDARD HOOK
WATERSTOP PER
SPECS (WHERE REQ'D)
P E
R S
C H
E D
, T Y
P
LA
P
S P
LI
C
E
P E
R S
C H
E D
, T Y
P
LA
P
S P
LI
C
E
HORIZ BARS
WATERSTOP PER
SPECS (WHERE REQ'D)
P E
R S
C H
E D
, T Y
P
LA
P
S P
LI
C
E
AT OPENINGS AND
DISCONTINUOUS ENDS
"U" BARS
PER SCHED, TYP
LAP SPLICE
MATCH VERT REINF
MATCH VERT REINF
MATCH VERT
REINF, TYP
MATCH VERT
REINF, TYP
ANGLED CORNERS
HORIZ BARS
SCHED, TYP
Ld PER
PER S
CHED, T
YP
LA
P S
PLIC
E
PER S
CHED, T
YP
LA
P S
PLIC
E
AT CORNERS T INTERSECTION
NOTES:
1. VERTICAL REINFORCING NOT SHOWN FOR CLARITY.
2. HOOKED, CORNER, AND "U" BARS SHALL MATCH SIZE OF
HORIZONTAL WALL REINFORCING, TYP. UON.
STANDARD HOOK (12"
MIN), TYP, UNO
IF CONSTRUCTION JOINT EXISTS
AT CORNERS
WATERSTOP PER
SPECS (WHERE REQ'D)
S P
LI
C
E , T
Y P
C
LA
S S
B L
A P
HORIZ BARS
WATERSTOP PER
SPECS (WHERE REQ'D)
S P
LI
C
E , T
Y P
C
LA
S S
B L
A P
S P
LI
C
E , T
Y P
C
LA
S S
B L
A P
HORIZ BARS
ALTERNATE HOOK
ORIENTATION
HORIZ BARS
MATCH VERT REINF
NOTE:
PROVIDE CONSTRUCTION JOINTS IN ALL WALLS
AND SLABS AS REQUIRED FOR CONSTRUCTION
AND AT 60'-0" MAX.
CUT OR BUTT 50%
OF HORIZ REINF
BAR 2" CLEAR OF
JOINT, EA FACE
CONTROL JOINT, CAULK WITH
ELASTOMERIC SEALANT AT
EXPOSED FACE
t
3/4"
CONT KEYWAY
WATERSTOP
PER SPECS
TYP
2" CLR
t/8
EXIST SLAB ON GRADE,
ASSUMED
EXIST COLUMN FOOTING,
ASSUMED
MATCH BOTTOM OF EXIST FOOTING.
NOTIFY SER OF DISCREPANCIES
WALL REINF PER SCHED
CONC WALL. THICKNESS
PER SCHED
EL PER PLAN
T/WALL
EL PER CIVIL
T/GRADE
EL PER PLAN
T/FTG
DECORATIVE STEEL
FENCE PER CIVIL
WALL FOOTING PER SCHED NOTE:
1. REFER TO SCHEDULE X/SXX FOR ADDITIONAL REQUIREMENTS
NOT SHOWN.
2. GC FIELD VERIFY THAT THE BOTTOM OF THE NEW WALL
FOOTING ALIGNS WITH THE BOTTOM OF THE EXISTING FOOTING.
DO NOT UNDERMINE THE EXISTING FOOTING. NOTIFY THE SER
OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION.
EXIST WALL ASSEMBLY
1' -4
M
IN
M A
X R
E T
A
IN
IN
G
H E
IG
H
T P
E R
S C
H E
D
1/ S2.1
GRID
SEE NOTE 1,
TYP
4 ADDITIONAL #5 EA SIDE
OF OPNG (2 EA FACE)
PIPE OR OPNG THROUGH
WALL OR SLAB
LENGTH, TYP
BAR DEVELOPMENT
SEE N
OTE
2'- 0"
, T
YP
PIPE OR OPNG THROUGH
WALL OR SLAB
NOTES:
1. PROVIDE ADDITIONAL HORIZONTAL AND VERTICAL BARS EQUAL TO THE NUMBER OF BARS TERMINATED AT OPENING, HALF EACH SIDE.
SPACE ADDITIONAL BARS AT 4" OC.
2. TERMINATE REINFORCING…