04 Norcross Parking Lighting Plan_20260804.pdf

PDF 9 MB Posted

Attached to
Downtown Norcross Parking Improvements
Solicitation number
PE-66780-NONST-2027-000000047
Issued by
Gwinnett County, Georgia

About this file

This file is a lighting plan document prepared by NV5 for the City of Norcross, Georgia for the Downtown Norcross Parking Improvements project located at 65 Lawrenceville Street. The project encompasses the design and installation of a comprehensive electrical lighting system for parking and pedestrian facilities surrounding Norcross City Hall. The lighting plan includes multiple fixture types: Type A and A3 streetlights (50-watt LED acorn-style luminaires on 10-foot decorative poles with 12-foot mounting height), Type P3 and P4 lights (138-watt LED fixtures on existing and new utility poles), Type B bollards, Type G tree grid-mounted lights, and Type U and U1 uplights for trees. The design incorporates a 150-amp main electrical service panel (Panel P1) with a 300-VA low-voltage transformer for secondary lighting circuits, photocell and contactor controls, and comprehensive grounding systems. The lighting system is designed to meet City of Norcross development standards and IESNA RP8-18 requirements, maintaining 0.5 footcandle average illumination with 15:1 maximum-to-minimum ratios in parking areas and 0.5 footcandle average with 4:1 ratios for sidewalks. All work must comply with the National Electrical Code (NFPA 70), Georgia Building Code, and local utility company standards. The plan was submitted as a 08/03/2026 submittal with electronic signature certification dated 08/04/2026.

The electrical specifications detail contractor responsibilities including furnishing all labor, materials, equipment, and permits for a complete operating system. Wiring systems utilize underground Schedule 40 PVC conduit, EMT where permitted, and rigid galvanized steel as required by code, with copper THHN/THWN-2 secondary conductors and UV-resistant, waterproof cable for direct burial installations. All electrical equipment and devices must be new, UL-approved, and listed, with complete testing and adjustment for proper operation prior to project completion. The plan establishes specific requirements for pole installation (minimum 3 feet from paving or 1 foot back from sidewalk), lighting control via photocell and contactor systems, and comprehensive grounding with copper ground rods achieving maximum 15-ohm resistance. Buried wire enclosures are specified as high-density polyethylene (Pen-Cell PE-10HDH) with 10-inch diameter tops and 19-inch depth, and all outdoor electrical equipment must be weatherproof. Material cut sheets require submittal to the electric department for approval prior to ordering.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P4

P4 P4

P4

A A

A A

A

A

AA3AAA

A EXISTING

A3

B

B

B

B

B

B

B

B

B

ABB

BBBB

A

P3

P3

P3

P3

A

GGGGGGGG

GGGG

U U

U

U

U

UGFI WP

P1-7 (1.8% VD)

LT P1-5

GFI WP

P1-7

GFI WP P1-7

GFI WP

P1-3

LT P1-1

GFI WP

P1-3

LT P1-1

GFI WP

P1-4

3.6% VD

LT P1-2

.8% VD

GFI WP P1-4

LT P1-2

GFI WP P1-4

LT P1-2

GFI WP P1-3 (VD 2.8%)

LT P1-1

GFI WP P1-3

LT P1-1

P1-1

P1-1

P1-1

P1-1

P1-1 (3.27%)

P1-1

P1-1

GFI WP P1-4

LT P1-2

P1-5

(.6% VD)

P1-5 P1-5

LV 1

LV 1

LV 4

LV 2

LV 3

PANEL P1

& METER

LV TRANSFORMER

LT P1-2

GFI WP P1-10 (1.12% VD)

LT P1-8 (.4% VD)

GFI WP P1-10

LT P1-8

LT P1-8

P1-1,3

P1-2,4

P1-1,3

P1-1,3

LV 4

150 A

SERVICE

CONSTRUCTION NOTES:

1. PROVIDE 150A SERVICE FROM P1 TO UTILITY POLE

BASE. RUN SEPARATE FEEDER FOR PRIVATE LIGHTS

TO BE INSTALLED AT 25' MOUNTING HEIGHT. FUSE

LIGHTS IN BURIED WIRE ENCLOSURE

2. INSTALL FEED UP UTILITY POLE TO FEED PRIVATE

LIGHTS. FUSE LIGHTS IN BURIED WIRE ENCLOSURE

NOTE: ALL "A" AND "A3" POLES HAVE 2 RECEPTACLES

EACH. THESE POLES HAVE 20A 2-POLE BREAKERS; ONE

POLE FOR LIGHTS (120V) AND THE OTHER FOR

RECEPTACLES (120V).

BWE

P1-8,10

BWE

LT P1-5

LT P1-5

GFI WP P1-10

LT P1-8

P1-5,7

P1-5,7

#6

#8

#8

#8

#6

#6

#8

#8

#6 #6

#12

#12

#12

#12

#12

#12 #12

#8

U1 (14 TOTAL, TYP, LV 5)

LV 5

BOLBOLBOL BOLBOLBOLBOL BOL

BOL

#12

A

B

C

D

IF

N

O T

O N

E

IN

C H

O N

B A

R I S

O N

E

IN

C H

O N

V

ER

IF

Y S

C A

LE

O R

IG

IN

A

L D

R A

W

IN

G

T H

IS

S

H

EE

T

A D

JU

ST

SC

A

LE

S

A C

C O

R D

IN

G

LY

Q U

A

LI

T Y C

O N

T R O

L:

T

EC

H N

IC

IA

N

D

ES

IG

N

ER

PR

O

JE

C

T

SH

EE

T T

IT

LE

C

LI

EN

T

42 3

PR

O

JE

C

T N

U M

B

ER

SHEET NO.:

SU

B M

IT

T

A

LS

C

O N

ST

R

U C

T

IO

N /B

ID

R

EV

IS

IO

N

S:

SC

A

LE

N O

R C

R O

SS

P

A R

K

IN

G I M

PR

O

V

EM

EN

T

S

/2

/2

C O

N C

EP

T

U A

L

/2

/2

S

U B M

IT

T

A L

/0

/2

S U

B M

IT

T

A L

R es ea rc h D riv e

Al ac hu a, F lo rid a

(3

)3

-1 w w w .n v5 .c om

E1

L

IG

T H

IN

G

P L A

N

N 20 40100

This item has been electronically signed and sealed by Robert J. Walpole, PE on

08.04.2026 using a digital signature.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

P4

P4 P4

P4

A A

A A

A

A

AA3AAA

A EXISTING

A3

B

B

B

B

B

B

B

B

B

0.2 0.2

0.2 0.1

0.1 0.1

0.1 0.1

0.1 0.2

0.2 0.4

0.7 0.9

0.9

0.7

0.7

1.0

1.1

1.1 1.0

0.8 0.8

0.3 0.1

0.1 0.0

0.0 0.0

0.0 0.0

0.0 0.0

0.5 0.6

1.0 1.3

0.7 0.8 0.9 0.9 0.9 0.9 1.0 1.1 1.2 1.2 0.7

1.0 1.0 1.1 1.0 1.0 1.0 1.1 1.2 1.2 1.1 0.6

1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.2 1.2 1.3 1.3 0.7

0.6 1.3 1.4 1.4 1.2 1.1 1.1 1.1 1.2 1.4 1.5 1.3 0.7

0.7 1.3 1.7 1.6 1.3 1.1 1.1 1.1 1.4 1.6 1.7 1.3

0.9 1.3 1.9 1.7 1.4 1.1 1.1 1.2 1.4 1.7 1.9 1.3

1.0 1.3 1.8 1.6 1.3 1.1 1.1 1.2 1.4 1.7 1.8 1.3

1.1 1.3 1.5 1.4 1.2 1.1 1.1 1.1 1.3 1.5 1.6 1.4

1.1 1.3 1.3 1.3 1.2 1.1 1.1 1.1 1.2 1.3 1.4 1.4

0.9 1.1 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.3 1.3

0.8 1.1 1.2 1.3 1.3 1.2 1.1 1.0 0.7 0.5

0.8 1.0 1.1 1.1 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.2

1.0 1.2 1.3 1.4 1.4 1.4 1.3 1.2 1.0 0.8 0.6 0.6 0.8

0.9 1.0 1.0 1.0 0.9 1.0 0.9 0.9 0.9 0.9 1.1 1.4

1.1 1.2 1.4 1.6 1.8 1.7 1.4 1.2 1.0 0.8 0.6 0.6 0.7 0.8 0.8

1.4 1.4 1.1 0.9 0.9 0.9 0.9 0.8 0.8 0.8 1.1 1.6

1.0 1.1 1.2 1.4 1.4 1.4 1.2 1.1 0.9 0.8 0.7 0.6 0.6 0.8 0.9

1.6 1.6 1.5

0.9 1.7 1.4 1.1 1.0 0.9 0.8 0.8 0.8 0.8 1.0 1.6 1.7 1.0 0.7 0.8 1.1 1.3 1.3 1.1 1.0 1.0 1.0 1.1 1.0 1.0 0.9 0.8 0.8 0.6 0.6 0.6 1.0 0.8

1.9 2.0 1.8 1.6 1.5 1.7 1.9 2.0 1.7 1.5 1.5 1.8 2.1 2.0 1.6 1.3 1.1 1.0 0.9 0.9 0.8 0.8 0.9 1.1 0.9 0.7 1.0 1.8 0.6 2.0 1.3 0.9 0.8 0.8 0.8 0.8 0.7 0.7 0.7 0.7 0.6 0.6 0.6 0.9 0.7

2.3 2.2 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.9 2.1 2.3 2.2 1.9 1.7 1.5 1.3 1.1 1.0 0.9 0.8 0.8 0.8 0.7 0.7 0.7 0.9 1.4 1.6 1.6 1.1 0.8 0.7 0.7 0.7 0.7 0.6 0.6 0.6 0.6 0.6 0.5 0.6 0.7 0.9

2.7 2.4 2.1 1.9 1.8 1.8 1.9 2.0 2.2 2.5 2.7 2.6 2.4 2.1 1.8 1.5 1.3 1.1 0.9 0.8 0.7 0.7 0.6 0.6 0.6 0.6 0.8 0.9 0.9 0.8 0.7 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.5

1.9 2.1 2.4 2.9 3.3 3.2 2.9 2.6 2.2 1.8 1.4 1.2 1.0 0.9 0.8 0.7 0.6 0.5 0.5 0.5 0.5 0.6 0.7 0.7 0.7 0.6 0.6 0.5 0.6 0.6 0.6 0.7 0.6 0.6 0.5 0.5 0.5

0.9 0.8 0.8 0.6 0.6 0.5 0.6 0.7 0.9 1.0 0.8 0.6 0.6 0.6 0.8 0.9 1.0 0.8 0.6 0.6 0.6

1.4 1.5 1.6 1.1 0.8 0.8 1.0

1.3 1.0 1.1

1.1 0.8 1.0

0.7 0.6

0.5

1.5 1.6 1.6 1.5 1.4 1.4 1.5 1.5 1.6

2.2 2.3 2.1 1.9 1.7 1.7 1.6 1.7 1.9 2.2

2.5 2.9 2.9 2.5 2.1 1.8 1.7 1.7 1.8 1.9 2.3 3.0 3.8 4.2 3.7

2.7 3.3 3.2 2.5 2.1 1.9 1.8 1.8 1.8 2.0 2.3 2.8 3.5 3.1

2.9 2.4 2.1 1.9 1.9 1.9 2.1 2.4 3.9 3.3

3.2 3.4 3.1

6.6 1.9

6.6 2.0

6.8 2.2

0.8 1.5

1.4 1.1

1.3

3.4

1.2

3.2

1.1

3.3

1.4

3.8

1.1

3.8

1.5

3.2

2.0

2.6

1.2

1.8

1.7

1.4

1.9 1.3

2.1 1.3

2.1 1.4

2.0 1.3

3.4

0.9

0.9

1.1 0.9

2.4 2.4 1.8 1.5 1.5 1.7

3.2 3.0 2.4 1.9 1.6 1.6 1.8

2.9 2.8 2.3 2.0 1.7 1.6 2.0

3.3 2.7 2.8 2.3 2.0 1.7 1.5 2.4

2.7 2.2 2.7 2.3 2.1 1.7 1.4 1.7

1.5 2.4 2.2 2.1 1.7 1.3 2.0

1.0 2.0 2.1 2.1 1.6 1.2 1.4

1.7 2.0 2.0 1.5 1.1 1.7

1.6 1.7 1.7 1.4 1.0

1.8 1.5 1.5 1.2

1.9 1.5 1.3 1.0

1.4 1.3 1.1 0.9

ABB

BBBB

A

P3

P3

P3

P3

A

GGGGGGGG

GGGG

U U

U

U

U

U

U1 (14 TOTAL, TYP, LV 5)

BOLBOLBOL BOLBOLBOLBOL BOL

BOL

A

B

C

D

IF

N

O T

O N

E

IN

C H

O N

B A

R I S

O N

E

IN

C H

O

V

ER

IF

Y S

C A

LE

O R

IG

IN

A

L D

R A

W

IN

G

T H

IS

S

H

EE

T

A D

JU

ST

SC

A

LE

S

A C

C O

R D

IN

G

LY

Q U

A

LI

T Y C

O N

T R O

L:

T

EC

H N

IC

IA

N

D

ES

IG

N

ER

PR

O

JE

C

T

SH

EE

T T

IT

LE

C

LI

EN

T

42 3

PR

O

JE

C

T N

U M

B

ER

SHEET NO.:

SU

B M

IT

T

A

LS

C

O N

ST

R

U C

T

IO

N /B

ID

R

EV

IS

IO

N

S:

SC

A

LE

N O

R C

R O

SS

P

A R

K

IN

G I M

PR

O

V

EM

EN

T

S

/2

/2

C O

N C

EP

T

U A

L

/2

/2

S

U B M

IT

T

A L

/0

/2

S U

B M

IT

T

R es ea rc h D riv e

Al ac hu a, F lo rid a

(3

)3

-1 w w w .n v5 .c om

E2

P H

O T

O M

E T

R

IC

P L A

N

20 40100

N

This item has been electronically signed and sealed by Robert J. Walpole, PE on

08.04.2026 using a digital signature.

Printed copies of this document are not considered signed and sealed and the signature must

B

C

D

IF

N

O T

O N

E

IN

C H

O N

B A

R I S

O N

E

IN

C H

O

V

ER

IF

Y S

C A

LE

O R

IG

IN

A

L D

R A

W

IN

G

T H

IS

S

H

EE

T

A D

JU

ST

SC

A

LE

S

A C

C O

R D

IN

G

LY

Q U

A

LI

T Y C

O N

T R O

L:

T

EC

H N

IC

IA

N

D

ES

IG

N

ER

PR

O

JE

C

T

SH

EE

T T

IT

LE

C

LI

EN

T

42 3

PR

O

JE

C

T N

U M

B

ER

SHEET NO.:

SU

B M

IT

T

A

LS

C

O N

ST

R

U C

T

IO

N /B

ID

R

EV

IS

IO

N

S:

SC

A

LE

N O

R C

R O

SS

P

A R

K

IN

G I M

PR

O

V

EM

EN

T

S

/2

/2

C O

N C

EP

T

U A

L

/2

/2

S

U B M

IT

T

A L

/0

/2

S U

B M

IT

T

R es ea rc h D riv e

Al ac hu a, F lo rid a

(3

)3

-1 w w w .n v5 .c om

E3

S T

A T

S A

N D

C U

T S H

E E T

S

TYPE A

TYPE B TYPE P4

POLE FOR P4

POLE FOR A

LIGHTING NOTES:

A. THIS PLAN MEETS THE CITY OF NORCROSS, (CON), DEVELOPMENT STANDARDS AND RECOMMENDED MAINTAINED HORIZONTAL FOOTCANDLE RECOMMENDATIONS OF THE ILLUMINATING ENGINEER SOCIETY OF NORTH AMERICA (IESNA) FOUND IN IESNA RP8-18 FOR PARKING LOT LIGHTING (.5 FC AVERAGE AND 15:1 MAX/MIN). SIDEWALKS MEET IESNA RP 8-18 REQUIREMENTS FOR SIDEWALKS IN MEDIUM PEDESTRIAN AREAS (.5 FC AVERAGE

AND 4:1 AVERAGE/MIN).

B. ALL LUMINAIRES ARE CUT-OFF AS PER COA DEVELOPMENT STANDARDS 6.4.4 (F)(1) .

C. LIGHTING UNIFORMITY RATIOS DO NOT EXCEED 6:1 AS PER CON 406.4

D. MAXIMUM HORIZONTAL ILLUMINATION DOES NOT EXCEED 4.5 FOOTCANDLES AVERAGE AS PER CON 406.3(1)b IN PARKING LOT. ALSO, MINIMUM LIGHT

IN PARKING AREA IS NO LESS THAN .5 FC AND MAXIMUM IS NO MORE THAN 5 FC AS PER CON 406.5.

E. THE MAXIMUM LIGHT SPILL IS LESS THAN 1 FOOTCANDLE (FC) ON ADJACENT PROPERTIES. ROADWAY VALUES NOT INCLUDED.

F. THE MAXIMUM MOUNTING HEIGHT OF THE POLE MOUNTED FIXTURES IS 12' ABOVE FINISH GRADE. AREA POLES ARE 30' IN HEIGHT.

G. LIGHT POLES ARE BLACK METAL (AL OR STEEL). MOUNTING HEIGHTS INCLUDING ABOVE GRADE FOUNDATION ARE INCLUDED IN SCHEDULE.

CONTRACTOR RESPONSIBILITY TO VERIFY POLE CAPACITY AND FOUNDATIONS MEET GEORGIA BUILDING CODE WIND LOAD REQUIREMENTS. POLE LENGTH MUST TAKE INTO ACCOUNT THE HEIGHT OF THE CONCRETE FOUNDATION AND MAXIMUM MOUNTING HEIGHT ABOVE GRADE.

H. POLES ARE INSTALLED 3' MIN. FROM PAVING TO FACE OF POLE OR 1' BACK OF SIDEWALK.

I. LIGHTS ARE CONTROLLED BY A PHOTOCELL AND CONTACTOR. .

J. FOOTCANDLE LEVELS SHOWN ARE INITIAL VALUES.

Statistics

Description Avg Max Min Max/Min Avg/Min

PARKING LOT (MAIN)

Applicable Code

1.1 fc 3.3 fc 0.5 fc 6.6:1 2.3:1 NOTES C AND D, IESNA RP 8-18

SIDEWALK AROUND BUILDING 6.8 fc 0.8 fc2.5 fc 8.5:1 3.1:1 MEETS IESNA RP 8-18

TRESPASS AT PROPERTY LINES 1.1 fc N/AN/A N/A N/A

PARKING LOT W OF SKIN ALLEY PLAZA 2.3 fc 4.2 fc 1.4 fc 3.0:1 1.7:1 NOTES C AND D, IESNA RP 8-18

SIDEWALK TO WINGO STREET 3.4 fc 0.9 fc1.6 fc 7.8:1 1.76:1 MEETS IESNA RP 8-18

This item has been electronically signed and sealed by Robert J. Walpole, PE on

08.04.2026 using a digital signature.

Printed copies of this document are not considered signed and sealed and the signature must

B

C

D

IF

N

O T

O N

E

IN

C H

O N

B A

R I S

O N

E

IN

C H

O

V

ER

IF

Y S

C A

LE

O R

IG

IN

A

L D

R A

W

IN

G

T H

IS

S

H

EE

T

A D

JU

ST

SC

A

LE

S

A C

C O

R D

IN

G

LY

Q U

A

LI

T Y C

O N

T R O

L:

T

EC

H N

IC

IA

N

D

ES

IG

N

ER

PR

O

JE

C

T

SH

EE

T T

IT

LE

C

LI

EN

T

42 3

PR

O

JE

C

T N

U M

B

ER

SHEET NO.:

SU

B M

IT

T

A

LS

C

O N

ST

R

U C

T

IO

N /B

ID

R

EV

IS

IO

N

S:

SC

A

LE

N O

R C

R O

SS

P

A R

K

IN

G I M

PR

O

V

EM

EN

T

S

/2

/2

C O

N C

EP

T

U A

L

/2

/2

S

U B M

IT

T

A L

/0

/2

S U

B M

IT

T

R es ea rc h D riv e

Al ac hu a, F lo rid a

(3

)3

-1 w w w .n v5 .c om

E4

S T

A T

S A

N D

C U

T S H

E E T

S

SERVICE ENTRANCE PANELBOARD SCHEDULE PANEL P1

FOR 240/120 VOLT, SINGLE PHASE, 3-WIRE SERVICE. PROVIDE ALL SPARE BREAKERS AND GROUND BAR.

SERVING

WIRE

HOT NEUT GRD

BREAKER

AMP POLES

CONNECTED

LOAD VA

CIR

NO

WIRE

HOTNEUTGRD

SERVINGCIR

NO

BREAKER

POLES AMP

1 2 3 4 5 6 7 8 9 10 11 12

50LIGHT - PARKING/DRIVE - N

150 AMP. MAIN BREAKER, 22,000 AIR SYMMETRICAL FULLY RATED ALL BREAKERS. 100% NEUTRAL.

LIGHTING (2695 VA)*1.25

TOTAL

= 3369 VA

= 9609 VA (40 AMP.)

P1 -1

P1 -2

P1 -5

N

TO

LIG

H

TS

CONTACTOR (SQ D CLASS 8903 6 POLE)

CONTACTOR WIRING DIAGRAM

NOT TO SCALE - VERIFY SCHEMATIC

HINGED DOOR CABINET WITH

FLUSH CATCH AND LOCK - WP

ELECTRICAL DISTRIBUTION ONE LINE DIAGRAM

#4 CU TO GROUND ROD.

3/4" X 20'-0" MINIMUM COPPER

CLAD GROUND ROD, 15 OHMS

MAXIMUM RESISTANCE.

NOTE

ALL 120/240v CONDUCTORS SHALL BE

COPPER TYPE THWN-2 IN CONDUIT.

NOT TO SCALE

TO BASE OF UTILITY POLE

PA

N

EL

-P

0A

M

AI

N

,0

A

IR

SPACE

CONTACTOR CAB.

WP

WP

RECEP 30@180 VA = 5400 VA

MOUNT ON CONCRETE

POSTS AND UNISTRUT

PHOTOCELL TO TURN ON

LIGHTING FIXTURES.

CONTACTOR CAB. & RECEP

13 14 15 16 17 18 19 20

SPARE

SPACE

26 66

SPACE

SPACE

SURGE ARRESTER

CONTACTOR = 360 VA

ELECTRICAL SPECIFICATIONS - LIGHTING SYSTEM

A. GENERAL

1. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND NECESSARY ITEMS FOR A COMPLETE AND OPERATING PARKING AND LOW VOLTAGE (LV) LIGHTING SYSTEM. OBTAIN AND PAY ALL FEES AND PERMITS

REQUIRED TO INSTALL A COMPLETE ELECTRICAL SYSTEM.

2. IT IS THE INTENT OF THESE DRAWINGS TO PROVIDE A COMPLETE ELECTRICAL SYSTEM, REGARDLESS

OF WHETHER EACH INDIVIDUAL COMPONENT IS MENTIONED OR NOT.

3. THE WORK SHALL COMPLY WITH ALL LEGALLY REQUIRED CODES AND STANDARDS, INCLUDING:

NFPA 70, NATIONAL ELECTRICAL CODE, LATEST ADOPTED EDITION.

NECA STANDARD OF INSTALLATION.

CITY OF NORCROSS UTILITY COMPANY STANDARDS AND POLICIES.

UNDERWRITER'S LABORATORY STANDARDS (UL).

OTHER APPLICABLE CODES AND STANDARDS THAT APPLY TO THIS TYPE OF CONSTRUCTION.

B. MATERIALS AND WORKMANSHIP

1. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE TIMELY PLACEMENT OF ALL

CONDUITS AND OTHER WIRING DEVICES AS THE CONSTRUCTION PROGRESSES.

2. LIGHTING SYSTEM SHALL BE CONTROLLED BY PHOTO CELL AND CONTACTORS AT PANEL.

3. WIRING SYSTEMS SHALL BE AS FOLLOWS:

UNDERGROUND SCHEDULE 40 PVC.

EMT WHERE PERMITTED BY CODE.

RIGID GALVANIZED STEEL WHERE REQUIRED BY CODE.

FLEXIBLE STEEL CONDUIT WHERE REQUIRED, LIQUID TIGHT WHERE REQUIRED.

4. SECONDARY CONDUCTORS SHALL BE COPPER TYPE THHN/THWN-2; LV SHALL BE TYPE SPT.

5. PARKING LOT LIGHT HOME RUNS SHALL BE CONNECTED TO PANEL AS INDICATED ON DRAWINGS.

6. ALL METAL BOXES, CABINETS, CONDUIT, EQUIPMENT, ETC. SHALL BE GROUNDED

AS REQUIRED BY CODE. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR ALL CIRCUITS.

7. ELECTRICAL CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO ITEMS AND EQUIPMENT

SHOWN AS PART OF THE GENERAL CONTRACT WHICH REQUIRE ELECTRICITY, INCLUDING

CONTROL WIRING AND WIRING TO CONNECT EXISTING EQUIPMENT.

8. ALL MATERIAL SHALL BE NEW AND UL APPROVED, LISTED, OR LABELED.

9. ALL ELECTRICAL EQUIPMENT AND SYSTEMS SHALL BE TESTED AND ADJUSTED FOR PROPER

OPERATION. COMPLETE WIRING SYSTEM SHALL BE FREE OF SHORT CIRCUITS.

10. CONTRACTOR SHALL MAKE COMPLETE CONNECTIONS TO ALL EQUIPMENT. COORDINATE WITH

EQUIPMENT SUPPLIER FOR EXACT LOCATIONS AND REQUIREMENTS.

GEORGIA BUILDING CODE LATEST REVISIONS.

NFPA 101

ADA

NATIONAL ELECTRICAL SAFETY CODE.

11. ALL ELECTRICAL EQUIPMENT, DEVICES, ETC. LOCATED OUTDOORS SHALL BE WEATHERPROOF.

13. EXISTING UTILITIES AND OTHER UNDERGROUND OR CONCEALED ITEMS ARE SHOWN FOR REFERENCE ONLY.

ADDITIONAL ITEMS NOT SHOWN MAY BE PRESENT AND LOCATIONS MAY DIFFER FROM THAT SHOWN. CONTRACTOR SHALL EXCAVATE AND CONDUCT DEMOLITION SO AS TO AVOID DAMAGE TO EXISTING ITEMS, SHALL NOTIFY OWNER AND ENGINEER AT ONCE OF ALL DAMAGE AND SHALL REPAIR DAMAGE TO ORIGINAL CONDITION TO THE

SATISFACTION OF OWNER AND ENGINEER AT NO CHANGE IN CONTRACT AMOUNT.

14. CAREFUL COORDINATION WITH OTHER DIVISIONS DURING INSTALLATION OF ARCHITECTURAL AND STRUCTURAL ELEMENTS IS NECESSARY TO INSTALL CONCEALED CONDUIT IN MANY AREAS. CONDUIT SHALL BE CONCEALED AS MUCH AS POSSIBLE - COORDINATE WITH STRUCTURAL DRAWINGS AND OTHER DIVISIONS WHEN INSTALLING CONDUIT. WHERE EXPOSED CONDUIT IS NECESSARY IT SHALL BE INSTALLED IN THE LEAST CONSPICUOUS

MANNER.

12. PROVIDE AN INSULATED GROUNDING CONDUCTOR IN ALL FEEDER AND BRANCH CIRCUITS.

12 1212 20

6 66502834

PROVIDE 3-1/0 CU THWN-2 IN 2" C. SERVICE

15. PROVIDE TYPE "A" AND "A3" POLE AND LIGHT FIXTURES MEETING CITY OF NORCROSS APPROVED MATERIAL.:

TO P1-7

120V 20A DIGITAL TIMER

SWITCH FOR TEMPORARY

LIGHTING CONTACTOR IS

ELECTRICALLY HELD, 120V COIL, 60A

N

SPARE

SPACE

LV TRANSFORMER RECEP GFI

* - INDICATES FEED FOR POLE LIGHTS CONTROLLED VIA PHOTOCELL AND LIGHTING CONTACTOR.

3-1/0 CU IN 2"C.

CONDUCTORS, AND 10" DIAM. SECONDARY ENCLOSURES AS SHOWN ON THE DRAWINGS.

CONTRACTOR SHALL FURNISH AND INSTALL ALL POLE MOUNTED LIGHT FIXTURES,

Plastic Type PE-10HDH with lid and stainless steel bolts.

Finished grade

10" Diameter BURIED WIRE ENCLOSURE (BWE) Pen-Cell

3"

24" Radius Elbow for

1.25" PVC

Warning tape 18

NOTE:

" m in

NOT TO SCALE

HANDHOLE WITH PLATE. PROVIDE TERMINATIONS AND

FUSES AS REQUIRED BY NATIONAL ELECTRICAL CODE. GROUND

3-#8 IN 1 1/4 C. (VERIFY W/ DRAWINGS)

LUG MOUNTED IN POLE OPPOSITE THE PLATE.

6' V

ER

IF

Y

DECISION ON HOW TO PRECEED.

COST TO THE CONTRACT. IN CASE OF DISPUTE, THE ENGINEER WILL RENDER A

HAVING JURISDICTION, WILL BE MADE BY THE CONTRACTOR AT NO ADDITIONAL

TO FIELD CONDITIONS, TO FIT WORK OF OTHER TRADES, OR TO RULES OF BODIES

CHANGES FROM THE DRAWINGS THAT ARE NECESSARY TO MAKE WORK CONFORM

BY ADDENDUM WHEN NECESSARY. INTERPRETATION OF THE DRAWINGS WILL BE BY

ENGINEER PRIOR TO SUBMITTING A BID. THE ENGINEER WILL ISSUE INSTRUCTIONS

DISCREPANCIES DISCOVERED DURING THE BID PROCESS SHALL BE REFERRED TO THE

CONTRACTOR AS DIRECTED BY THE ENGINEER AND AS REQUIRED BY FIELD CONDITIONS.

CONDUIT SYSTEM AND WORK OF OTHER TRADES SHALL BE COORDINATED BY THE

AS PRACTICAL IN PERFORMING THE WORK. DISCREPANCIES BETWEEN THE ELECTRICAL

INTERFERENCE WITH SURROUNDS. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY

EXAMINE ALL DRAWINGS FOR COORDINATION AND ALLOCATION OF SPACE AND AVOID

FURNISHED AND INSTALLED BY THE CONTRACTOR.

BUT IT IS INTENDED THAT ALL ACCESSORIES REQUIRED FOR A COMPLETE SYSTEM BE

AND ALL ACCESSORIES REQUIRED AT EACH LOCATION FOR THE EXECUTION OF THE WORK,

PADS OR BASES, AND THE LIKE. IT IS NOT INTENDED TO SHOW IN MINUTE DETAIL EVERY

OF THE WORK, INDICATE THE GENERAL LOCATION AND ARRANGEMENT OF CONDUIT AND

THE DRAWINGS ARE IN PART DIAGRAMMATIC AND ARE INTENDED TO CONVEY THE SCOPE

THE ENGINEER.

GENERAL NOTES:

LUMINAIRES - SEE LIGHTING SCHEDULE. LOCATE POLES AND BOLLARDS 1'

BACK OF SIDEWALK OR 3' FROM PAVEMENT.A

ELECTRICAL UTILITIES LEGEND

CU SECONDARY CONDUCTORS AT 36" MIN. CONDUCTOR SIZE AND QUANTITY

BURIED WIRE ENCLOSURE, APPROXIMATELY10" X 19" DEEP. (TYPICALLY

AS MARKED. FOR PRIVATE LIGHTING SYSTEM REFER TO PANEL SCHEDULES

FOR STREETLIGHTING FEEDS - INSTALLED 2' FROM POLES) PROVIDE AT ALL

SEE PANEL SCHEDULES FOR SIZE AND QUANTITY.)

CIRCUIT TO PANELBOARD. "P1" INDICATES THE PANELBOARD NUMBER (LV INDICATES

LOW VOLTAGE CIRCUIT). "3" INDICATES THE BRANCH CIRCUIT NUMBERS.

P1-3

PANEL P1 SERVICE CONDUCTORS TO TRANSFORMER

ELECTRIC UTILITY METER SOCKET(IF REQUIRED. LIGHTING CONTACTOR AND

ELECTRICAL PANEL- PROVIDE, SEE PANEL SCHEDULE FOR DETAILS. PROVIDE

BWE

# 8

FOR QUANTITY AND SIZE OF CONDUCTORS. CONDUIT FOR 3/0 IS 2 1/2", #2 IS 2",

AND #8 IS 1 1/4".

50 WATT LED. SEE SCHEDULE FOR TYPE DISTRIBUTION, ACORN STYLE LUMINAIRE ON 10' (12' M.H.) DECORATIVE POLE ON CONCRETE BASE. 2-POLE GFI BREAKER IN BASE OF POLE. ONE NON-GFI RECEPTACLE 2' FROM TOP OF POLE AND ONE GFI RECEPTACLE MIDPOINT OF POLE (SEE DRAWING FOR DETAILS OF LIGHT AND POLE ASSEMBLY.

SEE SCHEDULE FOR CATALOG NUMBERS. PROVIDE CONCRETE BASE AS REQUIRED TO MEET LOCAL CODES.

BOUND POLE TO GROUND. NOTE: ONE OF BREAKER IS FOR LIGHT, SECOND IS FOR RECEPS.

16. PROVIDE TYPE "P4" POLE AND LIGHT AND TYPE "P3" LIGHT ON EXISTING UTILITY POLE. 138 WATT LED. SEE SCHEDULE FOR DISTRIBUTION TYPE AND CATALOG NUMBERS. PROVIDE CONCRETE BASES FOR P4 LUMINAIRES. ADD FUSE TO POLE FOR P4 LIGHT. PLACE FUSE IN BURIED WIRE ENCLOSURE FOR P3.

17. PROVIDE TYPE "B" BOLLARDS AND SUITABLE CONCRETE BASES. LOCATE 1' FROM SIDEWALK.

SEE SCHEDULE FOR CATALOG NUMBERS.

19. BURIED WIRE ENCLOSURE (BWE), SECONDARY JUNCTION BOX SHALL BE MADE OF HIGH DENSITY POLYETHYLENE AND TOP. APPROXIMATE DIMENSTIONS 10" TOP DIAMETER, 19: DEPTH. BASIS OF DESIGN PENCELL PLASTICS

PE-10HDH WITH ELECTRIC ID.

20. LINE VOLTAGE SECONDARY CONNECTIONS MADE WITHIN ENCLOSURES SHALL BE DIRECT BURIAL, BOLTED TYPE. APPROVED

MANUFACTURERS ARE UTILCO, CMC, AND ESP.

21. PROVIDE SERVICE ENTRANCE RATED PANEL BOARD WITH 150 AMP MAIN, 22 kAIR, WEATHER PROOF, SINGLE PHASE

120/240V RATED. SHALL BE SQUARE D, QO LOAD CENTER.

22. MATERIALS AND EQUIPMENT SHALL BE NEW AND SUITABLE FOR THE PURPOSE INTENDED. MATERIAL CUT SHEETS

SHALL BE SUBMITTED TO THE ELECTRIC DEPARTMENT PRIOR TO ORDERING FOR APPROVAL.

23. ALL SPECIFICATIONS AND PLANS SHALL BE APPROVED BY THE ENGINEER PRIOR TO BIDDING.

24. "PROVIDE" SHALL MEAN FURNISH, INSTALL, CONNECT, ADJUST, AND TEST EXCEPT WHERE NOTED.

120 V/ 15 V, 300 VA LIGHTING TRANSFORMER (LV), FOR LOW VOLTAGE LIGHTINGLV

EX INDICATES EXISTING TO REMAIN

POLES, AND 10" DIAM. SECONDARY ENCLOSURES AS SHOWN ON THE DRAWINGS.

CONTRACTOR SHALL FURNISH AND INSTALL ALL POLE MOUNTED LIGHT FIXTURES,

Plastic Type PE-10HDH with lid and stainless steel bolts.

Finished grade

10" Diameter BURIED WIRE ENCLOSURE (BWE) Pen-Cell

TYPE "A" AND "A3' STREETLIGHT DETAIL (TYP.)

3"

24" Radius Elbow for

1.25" PVC

Warning tape 18

NOTE:

" m in

NOT TO SCALE

HANDHOLE WITH PLATE. PROVIDE 2 -POLE 20A BREAKER.

TO FEED LIGHT AND BREAKER FROM LOAD SIDE. GROUND

3#8 CU IN 1 1/4" C. (VERIFY W/ DRAWINGS)

LUG MOUNTED IN POLE OPPOSITE THE PLATE.

12/2 CU UF WITH GROUND

P4 STREETLIGHT DETAIL

12'

2"

TWO RUNS OF 12/2 CU WITH GROUND UF CABLE FROM

LOAD SIDE OF BREAKER. ONE FOR LIGHT SWITCHED FROM CONTACTOR OTHER FOR RECEP.

POLE BASE

POLE RECEPTACLES 14406**

120 V CONTACTS, 6-POLES, NEMA 3R

SQ D CLASS 8903 OR EQUAL

NOTE: ADD SURGE ARRESTOR TO PANEL.

* - INDICATES FEED FOR POLE RECEPTACLES. EACH POLE HAS CIRCUIT BREAKER IN POLE BASE.

50LIGHT - PARKING/DRIVE - W 93328 88*

LIGHT - PARKING/DRIVE - E *

POLE RECEPTACLES **61800

STAINLESS STEEL

P1 -6

P1 -9

SP

AR

E

TO

LIG

H

TS

TO

LIG

H

TS

R

EC

EPTAC

LE

OVERIDE (2 HR MAX)

SURGE ARRESTER

WITH NORCROSS POWER

COORDINATE CONNECTION

WP

200 A METER SOCKET

TO 120V LIGHTS

WP

LIGHTS

TO LOW VOLTAGE

LOW VOLTAGE TRANSFORMER

300 VA, 15V SECONDARY

STAINLESS STEEL CABINET

KICHLER 15PC300SS OR EQUAL

LV

WP

GFI

WP

GFI

P1-6

P1-7

LV 1 - 66 VA CONNECTED

LV 2 - 15 VA CONNECTED

LV 3 - 33 VA CONNECTED

LV 4 - 30 VA CONNECTED

LOW V TRANSFORMER CIRCUITS

TOTAL - 180 VA CONNECTED

X 1.25 = 225 VA - PROVIDE 300 VA

NOTE

ALL LOW VOLTAGE (15V) CABLES SHALL BE

COPPER #12 AWG SPT IN CONDUIT.

SUITABLE FOR DIRECT BURIAL.

ONE UNSWITCHED FOR POLE RECEPTACLES

15 A DUPLEX RECEPTACLE, WP

FEED FROM LOADSIDE OF 20A GFI RECEP

20 A DUPLEX GFI RECEPTACLE, WP

FEEDS 15A GFI, UNSWITCHED CIRCUIT

TO

LV TR

FM

ER

WITH NORCROSS POWER

COORDINATE SOCKET

12 1212

NOTE: MOUNT 2 A4 FIXTURES AT 25'

RECEPS ARE PROTECTED BY POLE-BASE

MOUNTED 20A BREAKERS.

18. PROVIDE COMPLETE LV LIGHTING SYSTEM INCLUDING 300 KA TRANSFORMER, TYPE "G" TREE GRID MOUNTED LIGHTS AND TYPE "U" UPLIGHTS FOR TREES. USE UV-RESISTANT, WATERPROOF CABLE SUITABLE FOR DIRECT BURIAL, #12 AWG CONDUCTOR. CABLE TO BE INSTALLED IN CONDUIT WHEN EXPOSED, UNDER PAVING AND UNDER CONCRETE. CONNECTIONS MUST BE WATERPROOFAND PREFILLED WITH GEL. SEE SCHEDULE FOR CATALOG

NUMBERS FOR FIXTURES.

POLE BASE

PROVIDE

PROVIDE

WP WEATHERPROOF

GFI GROUND FAULT INTERUPTER

PROVIDE INDICATES FURNISH AND INSTALL

DUPLEX RECEPTACLE

CIRCUIT BREAKER

POLES AND BOLLARDS.

POLE RECEPTACLES 8**

8 88502316 LIGHT - PARKING/DRIVE - S

POLE RECEPTACLES 81080

50 2

LV TRASFORMER = 480 VA

TO

LIG

H

TS

CONDUCTORS, AND 10" DIAM. SECONDARY ENCLOSURES AS SHOWN ON THE DRAWINGS.

CONTRACTOR SHALL FURNISH AND INSTALL ALL POLE MOUNTED LIGHT FIXTURES,

Plastic Type PE-10HDH with lid and stainless steel bolts.

Finished grade

10" Diameter BURIED WIRE ENCLOSURE (BWE) Pen-Cell

3"

24" Radius Elbow for

1.25" PVC

Warning tape 18

NOTE:

" m in

NOT TO SCALE

HANDHOLE WITH PLATE. PROVIDE TERMINATIONS AND

FUSES AS REQUIRED BY NATIONAL ELECTRICAL CODE. GROUND

3-#8 IN 1 1/4 C. (VERIFY W/ DRAWINGS)

LUG MOUNTED IN BOLLARD OPPOSITE THE PLATE.

2.

5'

V

ER

IF

Y

12/2 CU UF WITH GROUND

BOLLARD DETAIL

NOTE: MOUNT 2 A4 FIXTURES AT 25'

BOLLARD BASE

PROVIDE

VD INDICATES WORST CASE VOLTAGE DROP%

LV 5 - 36 VA CONNECTED

This item has been electronically signed and sealed by Robert J. Walpole, PE on

08.04.2026 using a digital signature.

Printed copies of this document are not considered signed and sealed and the signature must

B

C

D

IF

N

O T

O N

E

IN

C H

O N

B A

R I S

O N

E

IN

C H

O

V

ER

IF

Y S

C A

LE

O R

IG

IN

A

L D

R A

W

IN

G

T H

IS

S

H

EE

T

A D

JU

ST

SC

A

LE

S

A C

C O

R D

IN

G

LY

Q U

A

LI

T Y C

O N

T R O

L:

T

EC

H N

IC

IA

N

D

ES

IG

N

ER

PR

O

JE

C

T

SH

EE

T T

IT

LE

C

LI

EN

T

42 3

PR

O

JE

C

T N

U M

B

ER

SHEET NO.:

SU

B M

IT

T

A

LS

C

O N

ST

R

U C

T

IO

N /B

ID

R

EV

IS

IO

N

S:

SC

A

LE

N O

R C

R O

SS

P

A R

K

IN

G I M

PR

O

V

EM

EN

T

S

/2

/2

C O

N C

EP

T

U A

L

/2

/2

S

U B M

IT

T

A L

/0

/2

S U

B M

IT

T

R es ea rc h D riv e

Al ac hu a, F lo rid a

(3

)3

-1 w w w .n v5 .c om

E5

C U

T S H

E E T

S F

O R

L O

W V

O L T

A G

E

V

TYPE G TYPE U & U1 TRANSFORMER FOR LV LIGHTING

This item has been electronically signed and sealed by Robert J. Walpole, PE on

08.04.2026 using a digital signature.

Printed copies of this document are not considered signed and sealed and the signature must

Sheets and Views
Norcross Parking Lighting Plan-E1
Norcross Parking Lighting Plan-E2
Norcross Parking Lighting Plan-E3
Norcross Parking Lighting Plan-E4
Norcross Parking Lighting Plan-E5
2026-08-04T12:22:13-0400
Robert Justin Walpole
2026-08-04T12:22:14-0400
Robert Justin Walpole
2026-08-04T12:22:16-0400
Robert Justin Walpole
2026-08-04T12:22:17-0400
Robert Justin Walpole
2026-08-04T12:22:18-0400
Robert Justin Walpole

File details come from the government source that posted it. Updated .