04-552-20-101 Drawing-1.pdf
PDF 19 MB Posted
- Solicitation number
- 36C25026B0023_1
About this file
This is a design and construction drawing set for a renovation project at the VA medical facility in Dayton, Ohio. The project, numbered 552-20-101, involves renovating approximately 16,028 square feet on the sixth floor south wing to create an inpatient mental health facility. The facility will accommodate approximately 98 occupants across inpatient treatment and sleeping departments, with specific occupant load factors of 240 square feet per occupant for treatment areas and 120 square feet per occupant for sleeping areas.
The design incorporates comprehensive fire and life safety requirements per NFPA 101 (2018), including full sprinkler protection with smoke detection, Type I-332 construction with specified fire resistance ratings ranging from 0 to 3 hours depending on assembly type, and multiple smoke compartments with maximum areas of 22,500 square feet. Key design features include travel distance limitations (30-foot dead-end limit, 100-foot common path maximum, 200-foot suite remote point to exit maximum), 1 to 2-hour fire-rated exit enclosures, 1-hour smoke barrier separations with 20-minute minimum fire-rated doors, and detailed penetration firestopping specifications. The drawings encompass architectural, mechanical, electrical, plumbing, and fire protection systems with extensive schedules, details, and specifications referencing applicable codes including NFPA 10, 70, 99, and relevant VA design standards. The project is being submitted for bid and construction by CBLH Design Inc., with mechanical consultation from Scheeser Buckley Mayfield, dated September 20, 2021.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 101 (2018)
PROJECT AREA:
SIXTH FLOOR-SOUTH PROJECT AREA: 16,028 SF
SMOKE COMPARTMENT AREA: 15,728 SF
OCCUPANCY (6.1.5):
EXISTING HOSPITAL: HEALTH CARE OCCUPANCY
OCCUPANT LOAD FACTOR (HEALTH CARE USE, TABLE 7.3.1.2):
INPATIENT TREATMENT DEPARTMENT: 240 SF PER OCCUPANT
SLEEPING DEPARTMENT: 120 SF PER OCCUPANT
PROJECT AREA:
INPATIENT TREATMENT DEPARTMENT: 7,845 SF / 240 = 32.69 OCCUPANTS
SIXTH FLOOR - SOUTH: 7,883 SF / 120 = 65.69 OCCUPANTS
TOTAL OCCUPANTS: = 98.38 OCCUPANTS
FIRE SUPPRESSION:
FULLY SPRINKLERED WITH SMOKE DETECTION
TRAVEL DISTANCE:
DEAD-END LIMIT (18.2.5.2 AND TABLE A.7.6): 30 FEET MAX
COMMON PATH OF TRAVEL (18.2.5.3 AND TABLE A.7.6): 100 FEET MAX
SUITE REMOTE POINT TO EXIT (18.2.5.7.2.4): 200 FEET MAX
TYPE OF CONSTRUCTION:
TYPE I-332
FIRE RESISTANCE RATING (TABLE A.8.2.1.2 AND NFPA 220 TABLE 4.1.4)
EXTERIOR BEARING WALLS: 3 HR
INTERIOR BEARING WALLS: 3 HR - 2 HR FOR SINGLE FLOOR OR ROOF SUPPORT ONLY
STRUCTURAL COLUMNS: 3 HR - 2 HR FOR SINGLE FLOOR OR ROOF SUPPORT ONLY
FLOOR-CEILING ASSEMBLIES: 2 HR
ROOF-CEILING ASSEMBLIES: 1 1/2 HR
INTERIOR NONBEARING WALLS: 0 HR
EXTERIOR NONBEARING WALLS: 0 HR
EXIT ENCLOSURES: (7.1.3.2.1)
EXISTING: 1 HR MIN.
NEW: 2 HR
SHAFT ENCLOSURES: (8.6.5)
CONNECTING 4 STORIES OR MORE: 2 HR
CONNECTING LESS THAN 4 STORIES: 1 HR
SUITE SUBDIVISION: (18.2.5.7.1.4)
SUITE SUBDIVISION PARTITIONS: 0 HR
PROTECTION FROM HAZARDS: (18.3.2)
CENTRAL / BULK LAUNDRIES > 100SF: 1 HR (18.3.2.1.2 - 2)
ROOMS WITH SOILED LINEN > 64 GAL: 1 HR (18.3.2.1.2 - 5)
STORAGE ROOMS > 100SF WITH COMBUSTIBLE MATERIAL: 1 HR (18.3.2.1.2 - 7)
INTERIOR FINISH: (18.3.3 AND TABLE A.10.2.2)
CLASS A
CORRIDOR SEPARATION: (18.3.6)
DAY ROOM: (18.3.6.1)
DAY ROOM SPACE SHALL BE PERMITTED TO BE UNLIMITED IN AREA AND OPEN TO THE
CORRIDOR PER EXCEPTION 1:
(a) SPACE IS NOT USED FOR SLEEPING ROOMS, TREATMENT ROOMS, HAZARDOUS AREAS
(b) SPACE OPENS TO CORRIDOR IN THE SAME SMOKE COMPRATMENT PROTECTED BY
ELECTRICALLY SUPERVISED AUTOMATIC SMOKE DETECTION SYSTEM
(c) OPEN SPACE IS PROTECTED BY ELECTRICALLY SUPERVISED AUTOMATIC SMOKE
DETECTION SYSTEM OR ENTIRE SPACE IS ARRANGED AND LOCATED TO ALLOW
DIRECT SUPERVISION BY THE FACILITY STAFF FROM NURSES' STATION
(d) SPACE DOES NOT OBSTRUCT ACCESS TO REQUIRED EXITS
NURSE STATION: (18.3.6.1 AND A.18.3.6.1(3))
18.3.6.1: CORRIDOR SEPARATION DOES NOT APPLY TO NURSE STATION PER EXCEPTION 3
A.18.3.6.1 (3): TYPICAL NURSE STATION CONTAINS THE FOLLOWING
(1) CHARTING AREA
(2) CLERICAL AREA
(3) NOURISHMENT STATION
(4) MEDICATIONS, MEDICAL EQUIPMENT AND SUPPLIES, CLERICAL SUPPLIES, LINENS
(5) PATIENT MONITORING AND COMMUNICATIONS EQUIPMENT
CONSTRUCTION OF CORRIDOR WALLS (18.3.6.2.3): LIMIT THE TRANSFER OF SMOKE
CORRIDOR DOORS (18.3.6.3.5): SELF-LATCHING WITH POSITIVE LATCHING HARDWARE
PORTABLE FIRE EXTINGUISHERS (9.9):
NFPA 10 (TABLE 6.2.1.1):
TRAVEL DISTANCE : 75 FEET MAX
TYPE: 2-A
MAXIMUM FLOOR AREA: 11,250 SF
SUBDIVISION OF BUILDING SPACE: (18.3.7)
MAX. SMOKE COMPARTMENT AREA (18.3.7.4 (3) (a)): 22,500 SF
MAX. TRAVEL DISTANCE (18.3.7.1 (5)): 200 FEET
SMOKE BARRIER SEPARATION (18.3.7.3): 1 HR FIRE RATED
DOOR IN SMOKE BARRIER (18.3.7.6): *20 MINUTE MIN.
*OR DOOR OF SUBSTANTIAL CONSTRUCTION
BUILDING CODES / PROJECT MANUALS
NFPA 10 PORTABLE FIRE EXTINGUISHERS 2018
NFPA 70 NATIONAL ELECTRICAL CODE 2020
NFPA 99 HEALTH CARE FACILITIES CODE 2018
NFPA 101 LIFE SAFETY CODE 2018
PG-18-3 DESIGN AND CONSTRUCTION PROCEDURES JULY 2004
PG-18-5 EQUIPMENT GUIDE LIST FEBRUARY 2018
PG-18-12 DESIGN GUIDE (MENTAL HEALTH FACILITIES) DECEMBER 2017
PG-18-13 VA BARRIER FREE DESIGN STANDARD JANUARY 2017
PG-18-14 PROGRAM GUIDE (ROOM FINISHES, DOOR, & HARDWARE SCHEDULE) APRIL 2017
PG-18-15 MINIMUM REQUIREMENTS FOR A/E SUBMISSIONS MAY 2006
HVAC DESIGN MANUAL MAY 2019
PLUMBING DESIGN MANUAL MAY 2018
FIRE PROTECTION DESIGN MANUAL DECEMBER 2015
PHYSICAL SECURITY DESIGN MANUAL JANUARY 2015
PROJECT NUMBER:
SUBMITTAL FOR:
DRAWING INDEX: CODE DATA:LOCATION MAP:
VA DAYTON RENOVATE MENTAL HEALTH
6TH FLOOR
552-20-101
BID AND CONSTRUCTION
4100 WEST THIRD STREET,
DAYTON, OHIO 45428
P R
ELI
M
IN
AR
Y
N O
T F O
R
C O
N S
TR
U C
TIO
N
C B
LH
D E
SIG
N
IN
C
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building 330
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
/6 /2
:1
:3
P
M C
R e v it L o c a l\
M e n ta l H e a lt h F lo o r
C e n tr a l_
R
C e n tr a l_ rb o u k z a m
.r v t
GI-100
552-20-101
MS CE
VA DAYTON RENOVATE MENTAL
HEALTH 6TH FLOOR
09/20/2021
4100 WEST THIRD STREET, DAYTON, OHIO 45428
COVER SHEET
GENERAL
GI-100 COVER SHEET
GI-101 NOTES AND SYMBOLS
GI-102 SIXTH FLOOR LIFE SAFETY PLAN
GI-103 PENETRATION FIRE STOPPING DETAILS
GI-104 PENETRATION FIRE STOPPING DETAILS
GI-105 PENETRATION FIRE STOPPING DETAILS
GI-106 PENETRATION FIRE STOPPING DETAILS
ARCHITECTURAL
AD-200 SIXTH FLOOR DEMOLITION PLANS
AE-300 SIXTH FLOOR DIMENSION PLAN
AE-301 SIXTH FLOOR EQUIPMENT PLAN
AE-302 SIXTH FLOOR PATTERN PLAN
AE-303 SIXTH FLOOR SIGNAGE PLAN
AE-500 BUILDING SECTIONS
AE-510 INTERIOR DETAILS
AE-511 INTERIOR DETAILS
AE-600 ENLARGED PLANS AND ELEVATIONS (FURNITURE SHOWN FOR REFERENCE)
AE-601 ENLARGED PLANS AND ELEVATIONS
AE-602 ENLARGED PLANS AND ELEVATIONS
AE-603 ENLARGED PLANS AND ELEVATIONS
AE-604 ENLARGED PLANS AND ELEVATIONS
AE-700 ROOM FINISH SCHEDULE AND DETAILS
AE-710 MILLWORK DETAILS
AE-711 MILLWORK DETAILS - NURSE STATION
AE-800 INTERIOR ELEVATIONS
AE-801 INTERIOR ELEVATIONS
AE-810 INTERIOR PERSPECTIVES
AE-900 SIXTH FLOOR REFLECTED CEILING PLANS
AE-910 SIXTH FLOOR REFLECTED CEILING PLAN - ALTERNATE
AE-1000 DOOR SCHEDULE AND DETAILS
AE-1001 INTERIOR SIGN SCHEDULE
AE-1010 PARTITION TYPES
FIRE PROTECTION
FJ-100 FIRE SUPPRESSION GENERAL NOTES, SYMBOL LEGEND, AND DETAILS
FX-100 NEW WORK - SIXTH FLOOR PLAN - FIRE SUPPRESSION
PLUMBING
PD-100 DEMOLITION - FIFTH FLOOR PLAN - PLUMBING (SANITARY)
PD-101 DEMOLITION - SIXTH FLOOR PLAN - PLUMBING (SANITARY)
PD-102 DEMOLITION - SIXTH FLOOR PLAN - PLUMBING (WATER AND MEDICAL GAS)
PL-100 NEW WORK - FIFTH FLOOR PLAN - PLUMBING (SANITARY)
PL-101 NEW WORK - SIXTH FLOOR PLAN - PLUMBING (SANITARY)
PL-102 NEW WORK - SIXTH FLOOR PLAN - PLUMBING (WATER)
PJ-100 PLUMBING GENERAL NOTES, SYMBOL LEGEND, AND SCHEDULES
PJ-101 DETAILS - PLUMBING
MECHANICAL
MD-100 DEMOLITION - SIXTH FLOOR PLAN - HVAC (DUCTWORK)
MD-101 DEMOLITION - SIXTH FLOOR PLAN - HVAC (PIPING)
MH-100 NEW WORK - SIXTH FLOOR PLAN - HVAC (DUCTWORK)
MI-100 MECHANICAL TEMPERATURE CONTROLS
MP-100 NEW WORK - SIXTH FLOOR PLAN - HVAC (PIPING)
MJ-100 MECHANICAL GENERAL NOTES AND SYMBOL LEGEND
MJ-101 MECHANICAL DETAILS
MJ-102 MECHANICAL SCHEDULES
Revisions Date
BID AND CONSTRUCTION 10/06/2025
ELECTRICAL
ED-100 DEMOLITION - SIXTH FLOOR PLAN - ELECTRICAL
EL-100 LIGHTING - SIXTH FLOOR PLAN - ELECTRICAL
EL-101 LIGHTING - SIXTH FLOOR PLAN ALTERNATE - ELECTRICAL
EP-100 POWER - SIXTH FLOOR PLAN - ELECTRICAL
ET-100 TELECOM - SIXTH FLOOR PLAN - ELECTRICAL
EY-100 SYSTEMS - SIXTH FLOOR PLAN - ELECTRICAL
EJ-100 ELECTRICAL SYMBOL LEGEND AND GENERAL NOTES
EJ-101 LIGHTING SCHEDULE AND DETAILS
EJ-102 ELECTRICAL DETAILS
EJ-103 RISER DIAGRAM AND SCHEDULES
EJ-104 PANELBOARD SCHEDULES
EJ-105 PANELBOARD SCHEDULES
EK-100 TELECOMMUNICATIONS DETAILS
EK-101 TELECOM ROOM DETAILS
EK-102 TELECOMMUNICATIONS GROUNDING AND PATHWAY DETAILS
EK-103 ELECTRICAL SYSTEMS DETAILS
EK-104 ELECTRICAL SYSTEMS DETAILS
AIR CONDITIONED
ACOUSTICAL CEILING TILE
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ALTERNATE
AUDIO VISUAL
ARCHITECTURAL WOODWORK
AC
A.C.T.
A.C.U.
A.F.F.
ALT
A.V.
A.W.
BD
BLDG
BLK
BLKG
BOT
BR
BRG
BSMT
CONC
CAB
CBB
C.C.T.
C.G.
C.J.
CL.
CLG
C.M.U.
COL
COMM
CONF
CONN
CONST
CONT
CONTR
COORD
CORR
C.R.
C.W.
CYL
D. ALT.
DBL
DEMO
DET
D.F.
DIA
DIAG
DIM
DISP
DN
DR
D.S.
D.W.
DWG(S)
EXIST
E
EA EACH
EAST
EXISTING
DRAWING(S)
DUMBWAITER
DOWNSPOUT
DOOR
DOWN
DISPENSER
DIMENSION
DIAGONAL
DIAMETER
DRINKING FOUNTAIN
DETAIL
DEMOLITION
DOUBLE
DEDUCT ALTERNATE
CYLINDER
COLD WATER
CRASH RAIL
CORRIDOR
COORDINATE
CONTRACTOR
CONTINUOUS
CONSTRUCTION
CONNECTION
CONFERENCE
COMMUNICATION
COLUMN
CONCRETE MASONRY UNIT
CEILING
CLOSET
CONTROL JOINT
CORNER GUARD
CUBICAL CURTAIN TRACK
CEMENTITIOUS BACKER BOARD
CABINET
CONCRETE
BASEMENT
BEARING
BRICK
BOTTOM
BLOCKING
BLOCK
BUILDING
BOARD
POUND OR NUMBER #
DIAMETER OR ROUND
CENTERLINE
AT
ANGLE
AND
EXPANSION JOINT
ELECTRICAL
E.I.F.S.
E.J.
ELECT
EL
ELEV
EMER
ENCL
EQ
EQUIP
E.T.R.
EVAC
E.W.C.
EXT
F.B.
F.C.
F.C.U.
F.D.
F.D.V.C.
F.E.
F.E.C.
F.H.C.
FIN
FIXT
FLR
FLEX
FLUOR
F.R.T.
FT
FTG
FURN
FUT
G
GA
GALV
G.C.
G.F.M.U.
GL
GR
GRND
GWB
H.B.
HD
HDWD
H.M.
HOSP
H.P.
HR
H.R.
HORIZ
HT
HTG
HTR
H.V.A.C.
H.W.
HW
HYD
I.D.
ILLUM
INCIN
INCAND
INCL
INFO
INSUL
INT
I.P.S.
ISOL
IV
JT
KITCH
K.O.
K.P.
K.S. KNEE SPACE
KICK PLATE
KNOCK OUT
KITCHEN
JOINT
INTRAVENOUS
ISOLATION
INSIDE PIPE SIZE
INTERIOR
INSULATION
INFORMATION
INCLUDE
INCINERATOR
INCANDESCENT
ILLUMINATION
INSIDE DIAMETER (DIM)
HYDRANT
HARDWARE
HOT WATER
HEATING, VENTILATION, AIR CONDITIONING
HEATER
HEATING
HEIGHT
HORIZONTAL
HANDRAIL
HOUR
HIGH POINT
HOSPITAL
HOLLOW METAL
HEAD
HOSE BIBB
GYPSUM WALL BOARD
GROUND
GRADE
GLASS
GROUND FACE MASONRY UNITS
GENERAL CONTRACTOR
GALVANIZED
GAGE
GAS
FUTURE
FURNITURE
FOOTING
FOOT OR FEET
FIRE RESISTANT TREATED
FLUORESCENT
FLEXIBLE
FLOOR
FIXTURE
FINISH
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE DEPARTMENT VALVE CABINET
FLOOR DRAIN
FAN COIL UNIT
FOOT CONTROL
FACE BRICK
EXTERIOR
ELECTRIC WATER COOLER
EVACUATION
EXISTING TO REMAIN
EQUIPMENT
EQUAL
ENCLOSURE
EMERGENCY
ELEVATOR
ELEVATION
L
LAB
LAM
LIB
LIN
LOC
L.P.
LT.WT.
LTG
MACH
MAS
MATL
MAX
MECH
MED
MED.CAB.
MEMB
MEZZ
MFR
MH
MIN
MISC
MKR.BD.
MLDG
M.O.
MOD
M.R.G.B.
MTD
MTL
N
N.C.
NEG
N.I.C.
NO
N.T.S.
O
O.C.
O.D.
OFF.
OPNG
OPP
O.F.C.I.
PART.BD.
P.C.
P.C.D.
PERIM
PERP
PLWD
PORT
PR
PREFAB
PREFIN
PROJ
PROP
P.T.
PTD
R
R.A.
REC
RECEP
RECT
REF REFRIGERATOR
RECTANGULAR
RECEPTACLE
RECESSED
RETURN AIR
RADIUS
PAINTED
PNEUMATIC TUBE
PROPERTY
PROJECT
PREFINISHED
PREFABRICATED
PAIR
PORTABLE
PLYWOOD
PERPENDICULAR
PERIMETER
PAPER CUP DISPENSER
PRECAST CONCRETE
PARTICLEBOARD
OWNER FURNISHED, CONTRACTOR INSTALLED
OPPOSITE
OPENING
OFFICE
OUTSIDE DIAMETER(DIM)
ON CENTER
OXYGEN
NOT TO SCALE
NOMINAL
NUMBER
NOT IN CONTRACT
NEGATIVE
NURSE CALL
NITROGEN/NORTH
METAL
MOUNTED
MOISTURE RESISTANT GYPSUM BOARD
MODIFIED, MODULAR
MASONRY OPENING
MOULDING
MARKERBOARD
MISCELLANEOUS
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MEMBRANE
MEDICINE CABINET
MEDICINE/MEDICAL
MECHANICAL
MAXIMUM
MATERIAL
MASONRY
MACHINE
LIGHTING
LIGHTWEIGHT
LOW POINT
LOCATION/LOCATE
LINEAR
LIBRARY
LAMINATE
LABORATORY
LOCK
REFL REFLECTED
REINF REINFORCED
REM REMOVABLE
REQ'D REQUIRED
REV REVISION
R.F. RADIO FREQUENCY
RM
RND
R.O.
R.S.T. RUBBER STAIR TREADS
ROUGH OPENING
ROUND
S
S.S.
S.A.
SAN
SCHED
S.C.R.
S.D.
SECT
SGL
SH
SHR
SHT
SIM
S.O.G.
SPEC (S)
S&R
S.P.T.
SQ
S.F.
S.I.
S.Y.
S.T.C.
STD
STL
STOR
STRUCT
SURF
SUSP
T
T&B
T&G
TAN
TEL
TEMP
THRESH
THRU
TK.BD.
TLT
T.O.P.
TV
TYP
U.C.
UNFIN
U.N.O.
UTIL
V, VAC
VENT
VERT
VEST
VIT
W
W/
W/O
W.C.
W/C
WD
W.P.
YD YARD
WORKPOINT
WOOD
WHEEL CHAIR
WATER CLOSET
WITHOUT
WITH
WEST/WATER
VITREOUS
VESTIBULE
VERTICAL
VENTILATION
VACUUM
UTILITY
UNLESS NOTED OTHERWISE
UNFINISHED
UNDER COUNTER
TYPICAL
TELEVISION
TOP OF PAVEMENT
TOILET
TACKBOARD
THROUGH
THRESHOLD
TEMPERATURE
TELEPHONE
TANGENT
TONGUE AND GROOVE
TOP AND BOTTOM
THERMOSTAT
SUSPENDED
SURFACE
STRUCTURAL
STORAGE
STEEL
STANDARD
SOUND TRANSMISSION CLASS / COEFFICIENT
SQUARE YARD
SQUARE INCH
SQUARE FOOT
SQUARE
SPECIMEN PASS-THRU
SHELF & ROD
SPECIFICATION(S)
SLAB ON GRADE
SIMILAR
SHEET
SHOWER
SHELVING, SHELF
SINGLE
SECTION
SUPPLY DIFFUSER
SHOWER CURTAIN ROD
SCHEDULE
SANITARY
SUPPLY AIR
STAINLESS STEEL
SOUTH
LT LIGHT
LAV LAVATORY
W.W.F. WELDED WIRE FABRIC
EXTERIOR INSULATION FINISH SYSTEM
HARDWOOD
NOM
ROOM
V.I.F. VERIFY IN FIELD
ALUMINUMAL
F.P. FIRE PROTECTION
F.P.G. FIRE PROTECTED GLAZING
CL
O.F.O.I. OWNER FURNISHED, OWNER INSTALLED SSM SOLID SURFACE MATERIAL
BRK BREAK
CLR CLEAR
DEPT DEPARTMENT
GB GYPSUM BOARD
GYP GYPSUM
MGR. MANAGER
S.W. SOCIAL WORKER
T.R. TOILET ROOM
W/D WASHER / DRYER
NOTE: ALL ITEMS/MATERIALS MAY NOT OCCUR IN THIS PROJECT. LIST
PROVIDED FOR REFERENCE ONLY.
UNDISTURBED EEARTH OR
UNDISTURBED SUBGRADE
COMPACTED EARTH OR
COMPACTED SUBGRADE
ROCK
POROUS FILL OR SUBBASE
IMPERVIOUS FILL
DRAINAGE FILL
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE
TOPSOIL
CEMENTITIOUS DECKS AND
TOPPINGS
GROUT
BRICK
GLAZED BRICK
STRUCTURAL CLAY TILE
UNIT MASONRY
GLAZED STRUCTURAL CLAY TILE
UNIT MASONRY
CONCRETE UNIT MASONRY
GLAZED CONCRETE UNIT MASONRY
GLAZED UNIT MASONRY
CUT STONE
FIREBRICK
CAST STONE
STEEL
ALUMINUM
ORNAMENTAL
METAL/STAINLESS STEEL
CONTINUOUS WOOD FRAMING
WOOD BLOCKING
PLYWOOD
PARTICLE BOARD
FINISHED LUMBER FOR
ARCHITECTURAL WORK
BATT INSULATION
RIGID INSULATION
LOOSE FILL INSULATION
EXTERIOR INSULATION AND
FINISH SYSTEM
FIBROUS FIRE SAFING
GLASS
CARPET
LATH AND PLASTER
GYPSUM BOARD
PLASTIC GLAZING
TERRAZZO
ACOUSTICAL CEILING
RESILIENT TILE
CERAMIC TILE
FINISHED CONTOURS
EXISTING CONTOURS
CONTRACT LIMIT LINE
PROPERTY LINE
ELEVATION INDICATORS
FINISH ELEVATION
EXISTING ELEVATION
FENCE
STRUCTURAL GRID COLUMN TAG (NEW)
STRUCTURAL GRID COLUMN TAG (EXISTING)
CENTERLINE
REVISION INDICATOR
DRAWING BREAK LINE
MATCH LINE INDICATOR
HIDDEN LINE
1. ITEMS ABOVE OR BEYOND
2. ITEMS NOT IN CONTRACT (N.I.C.)
3. ITEMS BEING DEMOLISHED
ELEVATION DATUM
WINDOW & LOUVER SYMBOL
(SEE WINDOW SCHEDULE)
DOOR SYMBOL
(SEE DOOR SCHEDULE)
EQUIPMENT SYMBOL
(SEE EQUIPMENT SCHEDULE)
WALL TYPE SYMBOL
(SEE PARTITION TYPES)
PARTITION NUMBER
WORK POINT
ROOM NUMBER SYMBOL
ELEVATION VIEW INDICATOR
DETAIL INDICATOR
SECTION INDICATOR
DRAWING TITLE
1 View Name
SCALE:1/8" = 1'-0"A101
DETAIL NO.
DRAWING NO.
1'-0"
1'-0"
INTERIOR 01
INTERIOR 02
ELEVATION NO.
DRAWING NO. A101
ELEVATION NO.
A
A
NEW
EXISTING
SECTION NO.
DRAWING NO.
X
B
Room name
X
/1 A101
/1 A101
A101
A101
NEW PARTITION
PATCH TO MATCH EXISTING PARTITION
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED
NEW DOOR AND FRAME
POCKET DOOR
CASED OPENING
BIFOLD DOOR
SLIDING DOOR
Room name
Room name
P R
ELI
M
IN
AR
Y
N O
T F O
R
C O
N S
TR
U C
TIO
N
C B
LH
D E
SIG
N
IN
C
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building 330
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
/6 /2
:1
:3
P
M C
R e v it L o c a l\
M e n ta l H e a lt h F lo o r
C e n tr a l_
R
C e n tr a l_ rb o u k z a m
.r v t
GI-101
552-20-101
MS CE
VA DAYTON RENOVATE MENTAL
HEALTH 6TH FLOOR
09/20/2021
4100 WEST THIRD STREET, DAYTON, OHIO 45428
NOTES AND SYMBOLS
STANDARD ABBREVIATIONS
MATERIALS LEGEND LEGEND_GRAPHIC SYMBOLS
FLOOR PLAN LEGEND
Revisions Date
BID AND CONSTRUCTION 10/06/2025
F
1 1
1.2
F1
F6 G
G
B3
B3
B6
B6
C5
C5 D3
E1
E6
G6 H
H
H9
H9
J
J
K
K
J8
J8
K8
K8
L
L
L3
L3
L7 N
N
1.5
1.7 1.7
2.2
3.2
4.1
5 5
5.3
6 6
7 7
8 8
11 11
11.2
12 12
K7J7D8
5.6
6.6
7.4
8.9
9.8
D2
D2
B7
10.7
11.8
11.5
C2
C2
G9
K6
K6
10.6
2.3
L6
L6
E11
E11
H8G8
TRAVEL DISTANCE
176'-11" TO EXIT
TRAVEL DISTANCE
143'-1" TO EXIT
36'-9" COMMON
PATH OF TRAVEL
O
VERALL DIAG
O
NAL D
ISTANCE
210' - 11"
EXIT SEPARATION DISTANCE
157' - 5"
EXTENT OF SMOKE
COMPARTMENT
15,728 SF
F.E.C.
F.E.C.
F.E.C.
E7
E7
BELONGINGS
UTILITY ROOM
6D-101
OFF
6D-104
CONFERENCE
6D-102
RES. OFF.
6D-103
CHECK IN
6D-100
INTERVIEW
6D-133
EXAM
6D-134
EQUIPMENT
6D-111
TRASH
6D-152
ELECTRICAL CL.
6D-153
COMM CL.
6D-154
CONFERENCE
ROOM
6D-116
STUDENT OFF.
6D-115
BRK
6D-114
T.R.
6D-112
S.W.
6D-150 S.W.
6D-149
SOILED UTIL &
LINEN
6D-151
NURSE MGR.
6D-109
ALCOVE
6D-107
TELECOM
6D-106
EXERCISE
6D-143
C L E
A N
L
IN
E N
D
-1
M E
D
IC
A T
IO
N
D
-1
SERVERY
6D-105
VISITOR/CONSULT
6D-132
MULTI-PURPOSE
6D-142
JC
6D-110
T.R.
6D-113
CORRIDOR
6C-5
DAY ROOM
6D-141
CORRIDOR
6C-6
N O
U R
IS
H
M E
N T
D
-1
OFF
6D-108
SALLY PORT
6C-3
BARIATRIC
PATIENT ROOM
6D-131
PATIENT ROOM 2
6D-130
PATIENT ROOM 3
6D-129
PATIENT ROOM 4
6D-128
PATIENT ROOM 5
6D-127
PATIENT ROOM 6
6D-126
PATIENT ROOM 7
6D-125
PATIENT ROOM 8
6D-124
T.R.
6D-131A
T.R.
6D-130A
T.R.
6D-129A
T.R.
6D-128A
T.R.
6D-127A
T.R.
6D-126A
T.R.
6D-124A
WOMEN'S
LOUNGE
6D-138
W/D
6D-137
PATIENT ROOM 9
6D-123
PATIENT ROOM 10
6D-122
PATIENT ROOM 11
6D-121
PATIENT ROOM 12
6D-120
PATIENT ROOM 13
6D-119
T.R.
6D-123A T.R.
6D-122A
T.R.
6D-121A T.R.
6D-120A
T.R.
6D-119A
STORAGE
6D-135
CORRIDOR
6C-8
QUIET
6D-136
T.R.
6D-125A
J.C.
6D-130B
NURSE STATION
6D-144
CORRIDOR
6C-4
SITTING
6D-140
CORRIDOR
6C-7
F.E.C.
F.E.C.
CONSTRUCTION LIMIT LINE
CONSTRUCTION
LIMIT LINE
F9
F9
FLEX ROOM
6D-118
RESTRAINT
6D-117
UTIL RM
6D-117B
FLEX T.R.
6D-118A
F.E.C.
SOUND CLOSET
6D-126B
1 HR FIRE
SEPARATION
1 HR FIRE
SEPARATION
1 HR FIRE
SEPARATION
2 HR FIRE
SEPARATION
C L E
A N
U T
IL
IT
Y
D
-1
STORAGE
6D-155
CORRIDOR
C6-4
TRAVEL DISTANCE
96'-0" TO EXIT
TRAVEL DISTANCE
124'-6" TO EXIT
TEMPORARY 1 HOUR
RATED CONSTRUCTION
PARTITION AND DOOR T1
2 HR FIRE
SEPARATION
NON-RATED SMOKE PARTITION
1 HR FIRE SEPARATION
2 HR FIRE SEPARATION
TRAVEL DISTANCE
EXIT SIGN
FIRE EXTINGUISHER CABINETF.E.C.
TEMPORARY 1-HOUR RATED
PARTITION TO BE REMOVED BY
CONTRACTOR AT PROJECT
COMPLETION. SEE PARTITION
TYPE 'T1' ON SHEET AE-1010.
P R
ELI
M
IN
AR
Y
N O
T F O
R
C O
N S
TR
U C
TIO
N
C B
LH
D E
SIG
N
IN
C
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building 330
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
/6 /2
:1
:4
P
M C
R e v it L o c a l\
M e n ta l H e a lt h F lo o r
C e n tr a l_
R
C e n tr a l_ rb o u k z a m
.r v t
GI-102
552-20-101
MS CE
VA DAYTON RENOVATE MENTAL
HEALTH 6TH FLOOR
09/20/2021
4100 WEST THIRD STREET, DAYTON, OHIO 45428
SIXTH FLOOR LIFE SAFETY PLAN
SCALE: 1/16" = 1'-0"GI-102
1 SIXTH FLOOR LIFE SAFETY PLAN
LIFE SAFETY LEGEND
++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN.
DIAM PIPE IN 2" DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.
4. FIRESTOP DEVICE* — (NOT SHOWN) -TOP SEAL PLUG FOR USE WITH CP 680-75/2.5"N DEVICES AND NOM PIPE OR CONDUIT SIZES 3/4 IN. (19 MM) TO 2 IN. (51 MM), INSTALLED IN ACCORDANCE WITH THE MANUFACTURER\'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38 MM). W RATING APPLIES ONLY WHEN THE CPS OR IPS TOP SEAL PLUGS ARE
USED.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - APPLIES TO NOM 2", 3" AND 4" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3" AND CP 680-P 4" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN
WATER BARRIER MODULE IS USED.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
1. FLOOR ASSEMBLY — MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF
OR 1600-2400 KG/M3) CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL
D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. CONCRETE — MIN 2-1/2 IN (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF
OR 1600-2400 KG/M3) CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL
FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE 3, 4 AND 6 IN. DEVICES MAY EXTEND A MAX 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE. THE MAX EXTENSION ABOVE THE SLAB FOR THE 2 AND 2.5 IN. DEVICES IS NOT RESTRICTED.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES
AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR
VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR
SDR13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT
INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
NOM PIPE DIAMETER FIRESTOP DEVICE
CP 680-75/2.5"N
CP 680 -P 2"
CP 680-P 3"
CP 680-1 10/4"N
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
1/2 IN. TO 2 IN. (19 MM TO 51 MM)
3 IN.(76 MM)
3 IN. TO 4 IN. (76 MM TO 102 MM)
6 IN. (152 MM)
2 3
A
A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2053
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2054
F RATING - 3 HR
T RATING - 0 AND 3 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
1. FLOOR ASSEMBLY — MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400
KG/M3) CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL
FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. CONCRETE — MIN 4-1/2 IN (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400
KG/M3) CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL FLUTED
UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE DEVICES MAY
EXTEND A MAX 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY
BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — PIPE-NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR SDR13.5
CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
+3 HR T RATING APPLIES WHEN CP 680-P 3" AND CP 680-P 4" DEVICES ARE USED. 3 HR T RATING ALSO APPLIED WHEN CP 680-110/4"N DEVICE IS USED PROVIDED THAT MIN 4 IN. (102 MM) THICKNESS OF NOM 4 PCF (64 KG.M3) MINERAL WOOL BATT INSULATION TIGHTLY PACKED WITHIN ANNULUS BETWEEN PIPE AND WALL OF CP 680-110/4"N DEVICE. ++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2" DEVICE ETC.) L
RATING DOES NOT APPLY TO CP 680N DEVICES.
4. FIRESTOP DEVICE — TOP SEAL PLUG FOR USE WITH CP 680-P 2" DEVICE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38 MM). W RATING APPLIES ONLY TO THE IPS TOP SEAL PLUG AND NOM 2 IN. DIAM PENETRANTS AND CPS TOP SEAL PLUG FOR NOM ½ TO 2 IN. (13 TO 51 MM) DIAM
PENETRANTS.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - ALTERNATE TO TOP SEAL PLUG (ITEM 4). APPLIES TO NOM 2", 3", 4" AND 6" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3", CP 680-P 4" AND CP 680-P 6" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN WATER BARRIER MODULE IS USED AND NOM DIAM OF PENETRANT EQUALS SIZE OF DEVICE.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
NOM PIPE DIAMETER FIRESTOP DEVICE T RATING - HR
1/2 IN. TO 2 IN.
(19 MM TO 51 MM)
3 IN. (76 MM)
4 IN. (102 MM)
6 IN. (152 MM)
CP 680-75/2.5"N
CP 680-P 2"
CP 680-110-P 4"
CP 680-110/4"N
CP 680-P 3", CP 680-P 4"
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
0 AND 3+
SINGLE NON-METALLIC PIPE OR CONDUIT
A A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US C
R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
CIRCULAR BLANK OPENINGS SINGLE NON-METALLIC PIPE OR CONDUITSINGLE INSULATED PIPES
SINGLE INSULATED PIPES
SYSTEM NO. C-BJ-2016
F RATING - 4 HR
T RATING - 2 HR
SYSTEM NO. C-BJ-5006
F RATING - 4 HR
T RATING - 1/2 HR
SYSTEM NO. C-BJ-1034
F RATING - 4 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 10-1/2 IN.SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES
OF MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND
SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT — NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
3. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS
OF FILL MATERIAL.
4. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE, CONDUIT OR TUBING AND METAL COVER PLATE (ITEM
NO. 5) AND OVER BUTTED SEAMS OF METAL COVER PLATE.
5. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE OR CONDUIT AND SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN.
FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A SECTION A-A
SYSTEM NO. C-AJ-0055
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATING - 3 HR
FT RATING - 0 HR
FH RATINGS - 3 HR
FTH RATING - 0HR
F RATING - 3 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY- MIN 4-112 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL
CLASSIFIED CONCRETE BLOCKS'. MAX DIAM OF OPENING IS 4 IN. (102 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES
OF MANUFACTURERS.
2. METALLIC SLEEVE- NOM 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL
PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH
FLOOR OR WALL SURFACES. SLEEVE MAY EXTEND MAX 3 IN. (76 MM) ABOVE TOP SURFACE OF
FLOOR.
3. FILL, VOID OR CAVITY MATENAL'- FIRE BLOCK MIN 2 IN. (51 MM) THICK CUT TO A DIAM 1/2 IN. (13
MM) LARGER THAN THE OPENING, FLUSH WITH BOTTOM SURFACE
OF FLOOR OR WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
1. FLOOR OR WALL ASSEMBLY -- MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX
DIAMETER OF OPENING IS 3 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS
2. STEEL SLEEVE -- NOM 3 IN. DIAM SCHEDULE 40 (OR SMALLER) STEEL PIPE CAST OR GROUTED INTO
FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.
3. POLYVINYLIDENE FLUORIDE PVDF PIPE -- NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 40 PVDF FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. ANNULAR SPACE BETWEEN PIPE AND SLEEVE TO BE MIN 0 IN. (POINT CONTACT) AND MAX 5/8 IN. PIPE TO BE RIGIDLY
SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
4. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FILL, VOID OR CAVITY MATERIALS*-SEALANT -- MIN 1/2 IN. THICKNESS OF FILL MATERIAL APPLIED
WITHIN THE ANNULUS, FLUSH WITH BOTTOM SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
B. FILL, VOID OR CAVITY MATERIAL* -- WRAP STRIP -- NOM 1/4 IN. THICK BY 2 IN. WIDE INTUMESCENT WRAP STRIP. TWO LAYERS OF WRAP STRIP ARE CONTINUOUSLY WRAPPED AROUND THE PIPE AND HELD IN PLACE WITH TAPE. WRAP STRIP BUTTED TIGHTLY AGAINST BOTTOM SURFACE OF FLOOR OR BOTH
SURFACES OF WALL.
C. STEEL COLLAR -- COLLAR FABRICATED FROM COILS OF PRECUT MIN 0.017 IN. THICK (NO. 28 MSG) GALV STEEL AVAILABLE FROM THE SEALANT MANUFACTURER. COLLAR SHALL BE NOM 1-3/4 IN. DEEP WITH 1 IN. WIDE BY 2 IN. LONG ANCHORS TABS ON 2 IN. CENTERS FOR SECUREMENT TO FLOOR OR WALL ASSEMBLY. THE ANCHOR TABS SHALL BE BENT 90 DEGREE OUTWARD FOR SECUREMENT TO THE FLOOR OR WALL ASSEMBLY. THE OPPOSITE SIDE INCORPORATES RETAINER TABS, 1/2 IN. WIDE BY 3/16 IN. LONG, PREBENT TOWARD THE PIPE SURFACE. COLLAR SHALL BE TIGHTLY WRAPPED OVER THE WRAP STRIP, OVERLAPPING MIN. 1 IN AT SEAM. A NOM 1/2 IN. WIDE STAINLESS STEEL HOSE CLAMP SHALL BE SECURED TO THE COLLAR AT ITS MID-HEIGHT. EVERY OTHER ANCHOR TAB OF COLLAR SECURED TO CONCRETE SLAB WITH 1/4 IN. DIAM BY 1-3/4 IN. LONG STEEL EXPANSION TYPE MASONRY FASTENERS, 1-1/2 IN LONG CONCRETE SCREW ANCHORS OR 0.145 IN. DIAM BY 1-1/4 IN. LONG POWDER ACTUATED FASTENERS UTILIZING A 1-7/16 DIAM BY 1/16 IN. THICK STEEL WASHER. IN FLOOR ASSEMBLIES, ONE COLLAR TO BE USED AT THE BOTTOM OF THE CONCRETE FLOOR ONLY. IN WALL ASSEMBLIES, A COLLAR IS
USED ON BOTH SURFACES.
*BEARING THE UL CLASSIFICATION MARK
4A
4B 4C
1 2
1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL.
WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 29 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR
WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES MAY BE USED:
A. STEEL PIPE — NOM 20 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
3. PIPE COVERING — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE.TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. PIPE COVERING TO TERMINATE MIN 6 IN. FROM EACH SIDE OF FLOOR OR WALL ASSEMBLY. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
4. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PIPE COVERING* — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 5.2 PCF) UNFACED MINERAL WOOL UNITS EXTENDING MIN 6 IN. BEYOND EACH SURFACE OF THE FLOOR OR WALL. PIPE COVERING SECURED WITH NO. 18 GAUGE TIE WIRE 3 IN. BEYOND EACH SURFACE OF THE CONCRETE SLAB. THE ANNULAR SPACE SHALL BE MIN 1 IN. TO MAX 2-1/4 IN. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
B. SHEATHING MATERIAL* — ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE COVERING MATERIAL (ITEM 4A) WITH KRAFT FACING EXPOSED. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS. SEE SHEATHING MATERIAL (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS
AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
C. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF
FILL MATERIAL.
D. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE COVERING AND METAL COVER PLATE (ITEM NO.
4E) AND OVER BUTTED SEAMS OF METAL COVER PLATE.
E. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE, PENETRATING THE SHEATHING MATERIAL AND PIPE COVERING (ITEM NOS. 4B AND 4A) TO FULLY CONTACT THE PIPE. SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF
EACH SEAM AND A MAX OF 4 IN. OC THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
4E 4D
4C
4D
4A
4B
SINGLE NON-METALLIC PIPE OR CONDUIT
1. WALL ASSEMBLY — MIN 7-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANYUL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 4 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY
FOR NAMES OF MANUFACTURERS.
2. STEEL SLEEVE — NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE FRICTION FIT IN NOM 4 IN. DIAM CIRCULAR OPENING CORE DRILLED THROUGH WALL. LENGTH OF STEEL
SLEEVE TO BE EQUAL TO THICKNESS OF WALL.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE AND THE STEEL SLEEVE SHALL BE MIN 1/2 IN. TO A MAX 1 IN. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES
MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 2 IN. DIAM (OR SMALLER) CELLULAR OR SOLID CORE SCHEDULE 40 (OR HEAVIER) PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — NOM 2 IN. DIAM (OR SMALLER) SDR 17 CPVC
PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
4. FILL, VOID OR CAVITY MATERIAL*—SEALANT — MIN 2 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN
ANNULUS, FLUSH WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
SINGLE NON-METALLIC PIPE OR CONDUIT
SYSTEM NO. W-J-2057
F RATING - 4 HR
T RATING - 2 HR
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
A
A
SECTION A-A
SINGLE INSULATED PIPES
NOM PIPE DIAM, IN.
(MM)
NOM THICK. OF PIPE
INSUL., IN. (MM)
FIRESTOP DEVICE T-
RATING,
HR
1/2 (13)
1 (25)
2 (51)
2 (51)
4 (102)
1 (25)
1 (25) (SEE ITEM 5)
1 (25)
3/4 (19)
1 (25)
1 (25)
1 (25)
3/4(19)
3/4(19)
CP 680-75/2.5"N, CP 682-72/2.5"CP
680-M 2", CP 680-P 2"
CP 680-75/2.5"N CP 680-P 3"
CP 680-M 3", CP 680-P 3"
CP 682-110/4"CP 680-M 4"
CP 680 110/4"N, CP682 110/4"CP
680-M 4", CP 680-P 4"
CP 680-100/4"NCP 680-P 4"
CP 680-160/6"NCP 680-P 6
3/4
1/2
1/2
1/2
1/2
1/2
1/2
TUBE INSULATION - PLASTICS+ - NOM 3/4 OR 1 IN. (19 OR 25 MM) THICK ACRYONITRILE
BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF
TUBING. SEE PLASTICS+ (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED COMPONENT
DIRECTORY FOR NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE
INSULATION MATERIAL MEETING THE ABOVE SPECIFICATIONS AND HAVING A UL94
FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.
PACKING MATERIAL - (NOT SHOWN) - WHEN USING A 1 IN. (25 MM) DIAM PIPE WITH 1 IN. (25 MM) AB/PVC PIPE INSULATION IN A 4 IN. (102 MM) DEVICE, AND A MIN 2 IN. (51 MM) THICKNESS OF MIN
4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION SHALL BE FIRMLY PACKED INTO TOP OF
DEVICES, FLUSH WITH THE TOP OF THE DEVICE.
*BEARING THE UL CLASSIFICATION MARK
4.
5.
THE FIRESTOP DEVICE AND METALLIC PENETRANT SHALL BE SIZED AS FOLLOWS:
FLOOR OR WALL ASSEMBLY - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE.
FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) - THE FIRE RATED UNPROTECTED CONCRETE
AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN TEH
MANNER SPECIFIED IN TEH INDIVIDUAL D900 SERIES DESIGNS IN THE FIRE RESISTANCE
DIRECTORY AND AS SUMMARIZED BELOW:
1.
1A.
2.
3.
A. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON-COMPOSITE MAX
2 IN. (76 MM) DEEP GALV STEEL FLUTED UNITS AS SPECIFIED IN THE
INDIVIDUAL FLOOR-CEILING DESIGN.
B. CONCRETE - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE.
FIRESTOP DEVICE* - CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING
CONCRETE PLACEMENT OR GROUTED IN CONCRETE FLOOR ASSEMBLY IN ACCORDANCE WITH
ACCOMPANYING INSTALLATION INSTRUCTIONS WITH A MAX 2 IN. (51 MM) PROJECTION ABOVE
THE TOP SURFACE OF THE CONCRETE.
THROUGH PENERANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN
THE FIRESTOP DEVICE. PIPE, CONDUIT, OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES
OF FLOOR ASSEMBLY. THE FOLLOWING TYPES OF PIPE, CONDUIT OR TUBING MAY BE USED:
A. STEEL PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR
HEAVIER) STEEL PIPE.
B. COPPER TUBING - NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR
HEAVIER) COPPER TUBING.
C. COPPER PIPE. - NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR
HEAVIER) COPPER PIPE.
SYSTEM NO. F-A-5015
F RATING - 2 HR
T RATING - 1/2 HR AND 3/4 HR (SEE ITEM 3)
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
SECTION A-A
A A
P R
ELI
M
IN
AR
Y
N O
T F O
R
C O
N S
TR
U C
TIO
N
C B
LH
D E
SIG
N
IN
C
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
BID AND CONSTRUCTION
Project Number
Building Number
Drawing Number
VA Building 330
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
/6 /2
:1
:4
P
M C
R e v it L o c a l\
M e n ta l H e a lt h F lo o r
C e n tr a l_
R
C e n tr a l_ rb o u k z a m
.r v t
GI-103
552-20-101
MS CE
VA DAYTON RENOVATE MENTAL
HEALTH 6TH FLOOR
09/20/2021
4100 WEST THIRD STREET, DAYTON, OHIO 45428
PENETRATION FIRE STOPPING DETAILS
SYSTEM NO. C-AJ-1226
F RATING - 3 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - 4 CFM/SQFT
SYSTEM NO. C-AJ-3180
F RATING - 3 HR
T RATING - 0 HR
SYSTEM NO. C-AJ-7051
F RATING - 3 HR
T RATING - 1 HR
SINGLE METAL PIPES OR CONDUIT SINGLE OR BUNDLED CABLES
NON-INSULATED MECHANICAL DUCTWORK
WITHOUT DAMPERS
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US C
R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
A
A
SECTION A-A
4B
4B 1
4A
SECTION A-A
A
A
A
A SECTION A-A
3B
3A
*BEARING THE UL CLASSIFICATION MARK
FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL
WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED
CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 32 IN.
METALLIC SLEEVE - (OPTIONAL) NOM 32 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER)
STEEL SLEEVE CST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR
WALL SURFACES OR EXTENDING A MAX OF 3 IN. ABOVE FLOOR OR BEYONE BOTH SURFACES
OF WALL.
SHEET METAL SLEEVE - (OPTIONAL) MAX 6 IN. DIAM, MIN 26 GA GALV STEEL PROVIDED WITH A 26
GA GALV STEEL SQURE FLANGE SPOT WELDED TO THE SLEEVE AT A APPROX MID-HEIGHT, OR
FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A MIN OF 2 IN. LARGER THAN
THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN PLACE AND MAY EXTEND A MAX OF 4 IN.
BELOW THE BOTTOM OF THE DECK AND A MAX OF 1 IN. ABOVE THE TOP SURFACE OF THE
CONCRETE FLOOR.
THROUGH-PENETRANT - ONE METALLIC PIPE, TUBE OR CONDUIT TO BE INSTALLED EITHER
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE
BETWEEN PENETRANT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO
MAX 1-7/8 IN. SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING
TYPES AND SIZES OF METALLIC PENETRANTS MAY BE USED:
1.
2.
3.
4.
5.
A. STEEL PIPE - NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER)
STEEL PIPE.
B. IRON PIPE - NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER)
COPPER PIPE.
D. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER)
COPPER TUBING.
E. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.
F. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
TUBING (EMT).
FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL
BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT
FORM. PACKING METERIAL TO BE RECESSED FROM TOP SURFACE OF
FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL OR SLEEVE AS
REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
MATERIAL.
B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. THICKNESS OF
FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP
SURFACE OF FLOOR OR SLEEVE OR WITH BOTH SURFACES OF WALL OR
SLEEVE. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BEWEEN
PENETRANT AND CONCRETE OR SLEEVE, A MIN 1/4 IN. DIAM BEAD OF FILL
MATERIAL SHALL BE APPLIED AT THE CONCRETE OR SLEEVE/PIPE
PENETRANT INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH
SURFACES OF WALL.
FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE FLOOR OR MIN 4-3/4 IN. (152
MM). SEE CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 6 IN. (152 MM). SEE CONCRETE
BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
STEEL SLEEVE - (OPTIONAL) - NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR
HEAVIER) STEEL PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH
FLOOR OR WALLL SURFACES.
CABLES - AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN OPENING TO BE MAX 45% OF
THE AGGREGATE CROSS-SECTIONAL AREA OF THE OPENING. CABLES TO BE RIGIDLY
SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. ANY COMBINATION OF THE
FOLLOWING TYPES AND SIZES OF METALLIC CONDUCTOR OR FIBER OPTIC CABLE MAY BE
USED:
1.
2.
3.
4.
5.
A. MAX 500 KCMIL SINGLE COPPER CONNECTOR POWER CABLE WITH
THERMOPLASTIC INSULATION AND POLYVINYL CHLORIDE ( PVC) JACKET.
B. MAX 300 KCMIL SINGLE COPPER CONDUCTOR TELECOMMUNICATION
CABLES WITH POLYVINYL CHLORIDE (PVC) INSULATION AND JACKET
MATERIAL.
C. MAX 7/C COPPER CONDUTOR NO. 12 AWG MULTICONDUTOR POWER AND
CONTROL CABLES WITH POLYVNYL CHOLORIDE (PVC) OR CROSS-LINKED
POLYETHYLENE (XLPE) INSULATION AND PVC JACKET.
D. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC
AND HAVING A MAX OUTSIDE DIAM OF 1/2 IN. (13 MM).
E. MAX 3/C COPPER CONDUCTOR NO. 12 AWG WITH BARE ALUMINUM
GROUND, POLYVINYL CHOLRIDE (PVC) INSULATED STEEL, METAL-CLAD
CABLE.
F. MAX 3/C WITH GROUND 2/0 AWG COPPER CONDUCTOR SER CABLE WITH
CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND POLYVINYL
CHLORIDE (PVC) JACKET.
G. RG/U COAXIAL CABLE WITH POLYETHYLENE (PE) INSULATION AND
POLYVINYL CHLORIDE (PVC) JACKET HAVING A MAX OUTSIDE DIAMTER
OF 1/2 IN. (13 MM).
H. FIRE RESISTIVE CABLES* - MAX 1-1/4 IN. (32 MM) DIAM SINGLE
CONDUCTOR OR MULTI CONDUCTOR TYPE MI CABLE. A MIN1/8 IN. (3 MM)
SEPARATION SHALL BE MAINTAINED BETWEEN MI CABLES AND ANY
OTHER TYPES OF CABLE.
PACKING MATERIAL - MIN 4-1/4 IN. (108 MM) THICKNESS OF MIN 4 PCF (64 KG/M³) MINERAL WOOL
BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL
TO BE RECESSED FROM TOP SURFACE OF FLOOR TO ACCOMMODATE THE REQUIRED
THICKNESS OF FILL METERIAL.
FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. (6.4 MM) THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH
SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE. WALL MAY ALSO BE
CONSTRUCTED OF ANY UNDERWRITERS LABORATORIES INC.
CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 1024 IN. SQ. WITH A MAX
DIMENSION OF 32 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
STEEL DUCT - NOM 30 BY 30 IN. (OR SMALLER) NO. 24 GAUGE (OR HEAVIER) GALV STEEL DUCT.
ONE STEEL DUCT TO BE POSITIONED WITHIN THE FIRESTIP SYSTEM. THE ANNULAR SPACE
SHALL BE MIN 1/4 IN. TO A MAX 1-3/4 IN. DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES FO
FLOOR OR WALL ASSEMBLY.
FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
1.
2.
3.
4.
A. PACKING MATERIALS - MIN 3-1/2 IN. THICKNESS OF MIN 4 PCF MINERAL
WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
PERMANENT FORM BETWEEN TEH BARE STEEL DUCT AND THE
PERIPHERY OF THE OPENING. PACKING MATERIAL TO BE RECESSED
FROM TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL AS
REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
MATERIAL
B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1 IN. THICKNESS OF
FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF
FLOOR OR BOTH SURFACES OF WALL.
STEEL RETAINING ANGLE - NOM 2 IN. BY 2 IN. BY NO. 16 GUAGE (OR HEAVIER) STEEL ANGLES
ATTACHED TO ALL FOUR SIDES OF THE STEEL DUCT ON THE TOP SURFACE OR BOTH
SURFACES OF THE WALL. THE ANGLES SHALL BE ATTACHED WITH NO. 8 (OR LARGER) STEEL
SHEET METAL SCREWS SPACED MAX OF 1 IN. FROM EACH END AND A MAX OF 3 IN. O.C.
*BEARING THE UL CLASSIFICATION MARK
SYSTEM NO. W-J-8007
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
1. WALL ASSEMBLY — MIN 7-5/8 IN. (194 MM) THICK WALL ASSEMBLY CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 2496 IN. SQ. (161 M2) WITH MAX DIMENSION OF 52 IN. (1321 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
2. CABLE TRAY* — MAX 36 IN. (914 MM) WIDE BY 6 IN. (152 MM) DEEP OPEN-LADDER CABLE TRAY WITH CHANNEL-SHAPED SIDE RAILS FORMED OF 0.067 IN. (1.7MM) THICK ALUMINUM AND WITH 1-1/2 IN. (38 MM) WIDE BY 3/4 IN. (19 MM) DEEP CHANNEL- SHAPED RUNGS SPACED 10 IN. (254 MM) OC.
ONE CABLE TRAY TO BE INSTALLED IN THE OPENING. THE ANNULAR SPACE BETWEEN ADJACENT PENETRATING ITEMS SHALL BE MIN 2 IN. (51 MM) TO MAX 4-1/2 IN. (114 MM). THE MAX ANNULAR SPACE BETWEEN THE PERIPHERY OF THE OPENING SHALL BE MIN 1 IN. (25 MM) TO MAX 3 IN. (76
MM). CABLE TRAY TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
3. CABLES — AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN CABLE TRAY TO BE MAX 40
PERCENT OF THE CROSS-SECTIONAL AREA OF THE CABLE TRAY BASED ON A MAX 6 IN. (152 MM) CABLE LOADING DEPTH WITHIN THE CABLE TRAY. ANY COMBINATION OF THE FOLLOWING TYPES
AND SIZES OF CABLES MAY BE USED:
A. 300 PAIR — NO. 24 AWG TELEPHONE CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION
AND PVC JACKET.
B. 1/C - 500 KCMIL WITH THERMOPLASTIC INSULATION AND NYLON JACKET.
C. 24 FIBER OPTIC CABLE WITH POLYVINYL CHLORIDE (PVC) OUTER AND SUBUNIT JACKET.
D. 7/C NO. 12 AWG CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC JACKET.
4. THROUGH PENETRANTS — ONE OR MORE PIPES OR TUBES TO BE INSTALLED WITHIN THE
OPENING. THE TOTAL NUMBER OF THROUGH-PENETRANTS IS DEPENDENT ON THE SIZE OF THE
OPENING AND TYPES AND SIZES OF THE PENETRANTS. ANY COMBINATION OF THE PENETRANTS
DESCRIBED BELOW MAY BE USED PROVIDED THAT THE FOLLOWING PARAMETERS RELATIVE TO THE
ANNULAR SPACES AND THE SPACINGS BETWEEN THE PIPES ARE MAINTAINED. THE SPACE
BETWEEN PIPES, CONDUITS OR TUBING SHALL BE MIN 1-1/2 IN.(38 MM) TO MAX 4-3/4 IN. (121 MM). THE SPACE BETWEEN THE PERIPHERY OF THE OPENING AND THE PIPES OR CONDUITS SHALL BE MIN 3 IN. (76 MM) TO MAX 4-1/4 IN. (108 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL
PIPE.
B. IRON PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRIC METALLIC TUBING OR
6 IN. (152 MM) DIAM STEEL CONDUIT.
D. COPPER TUBING — NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER
TUBING.
E. COPPER PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR…