03 60 00 - Grouting.pdf

PDF 226 KB Posted

Attached to
Blue Ball Water Storage Tank Painting Project
Solicitation number
Not on record
Issued by
Lancaster County, Blawnox Borough, Pennsylvania

About this file

This is a specification document for grouting work prepared by Herbert, Rowland & Grubic, Inc., the engineer of record for projects issued by the Weaverland Valley Authority in Pennsylvania. The document establishes requirements for two types of grout materials: Portland cement grout and nonshrink cementitious grout. Portland cement grout must comply with ASTM C150/C150M Type II and I/II standards and be mixed at a ratio of two parts sand to one part cement by volume, achieving minimum compressive strength of 2,400 psi in 48 hours and 7,000 psi in 28 days. Nonshrink cementitious grout must be pre-mixed, ready-for-use formulations that maintain initial placement volume or expand after set, with minimum compressive strength of 4,000 psi in 48 hours and 10,000 psi in 28 days, and maximum expansion of 0.10 to 0.40 percent. The specification includes comprehensive requirements for surface preparation, mixing procedures, placement methods, and curing practices, with all grout materials requiring protection from moisture, dust, and temperature extremes between 40 degrees F and 90 degrees F. Grouting work must not utilize pneumatic-pressure or dry-packing methods, and leveling shims cannot be removed for at least 48 hours after placement. All grout must be cured for a minimum of three days while kept damp following initial set.

The specification requires that grout manufacturers have minimum three years of experience and that all products submit manufacturer certifications and detailed instructions for mixing, handling, and installation. Field quality control testing must comply with ACI 301 and ACI 318 standards, with proposed mix designs submitted to the engineer of record for review prior to work commencement. Water used in grout preparation must be potable and free from impurities, suspended particles, algae, or dissolved salts capable of causing corrosion, volume change, efflorescence, or excess air entrainment. Fine aggregate must be washed natural sand complying with ASTM C33/C33M gradation requirements and free from organic impurities per ASTM C40/C40M. No ferrous aggregate or staining ingredients are permitted in any grout mixes. All materials must be stored in clean, dry locations protected from construction operations and handled according to manufacturer instructions upon delivery in original packaging.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

03 60 00 - GROUTING

Herbert, Rowland & Grubic, Inc. 03 60 00 - 1 011361.0461

SECTION 03 60 00 - GROUTING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Portland cement grout.

2. Nonshrink cementitious grout.

1.2 REFERENCE STANDARDS

A. American Concrete Institute:

1. ACI 301 - Specifications for Structural Concrete for Buildings.

2. ACI 301M - Specifications for Structural Concrete (Metric).

3. ACI 318 - Building Code Requirements for Structural Concrete.

4. ACI 318M - Metric Building Code Requirements for Structural Concrete.

B. ASTM International:

1. ASTM C33/C33M - Standard Specification for Concrete Aggregates.

2. ASTM C40/C40M - Standard Test Method for Organic Impurities in Fine

Aggregates for Concrete.

3. ASTM C150/C150M - Standard Specification for Portland Cement.

4. ASTM C191 - Standard Test Methods for Time of Setting of Hydraulic Cement by

Vicat Needle.

5. ASTM C307 - Standard Test Method for Tensile Strength of Chemical-Resistant

Mortar, Grouts, and Monolithic Surfacings.

6. ASTM C531 - Standard Test Method for Linear Shrinkage and Coefficient of

Thermal Expansion of Chemical-Resistant Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes.

7. ASTM C579 - Standard Test Methods for Compressive Strength of Chemical- Resistant Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes.

8. ASTM C827/C827M - Standard Test Method for Change in Height at Early Ages of Cylindrical Specimens of Cementitious Mixtures.

C. U. S. Army Corps of Engineers Concrete Research Division (CRD):

1. CRD-C621 - Non-Shrink Grout.

1.3 SUBMITTALS

A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.

B. Product Data: Submit manufacturer information regarding grout.

C. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.

D. Manufacturer Instructions: Submit instructions for mixing, handling, surface preparation, and placing epoxy-type and non-shrink grouts.

Herbert, Rowland & Grubic, Inc. 03 60 00 - 2 011361.0461

E. Field Quality-Control Submittals: Indicate results of Contractor-furnished tests and inspections.

1.4 QUALIFICATIONS

A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' experience.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Section 01 61 00 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.

B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.

C. Store materials according to manufacturer instructions.

D. Protection:

1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.

2. Provide additional protection according to manufacturer instructions.

1.6 AMBIENT CONDITIONS

A. Section 01 50 00 - Temporary Facilities and Controls: Requirements for ambient condition control facilities for product storage and installation.

B. Maximum Conditions: Do not perform grouting if temperatures exceed 90 degrees F.

C. Minimum Conditions: Maintain minimum temperature of 40 degrees F before, during, and after grouting, until grout has set.

PART 2 - PRODUCTS

2.1 PORTLAND CEMENT GROUT

A. Portland Cement: Comply with ASTM C150/C150M, Type II and I/II.

B. Water:

1. Potable.

2. No impurities, suspended particles, algae, or dissolved natural salts in quantities capable of causing:

a. Corrosion of steel.

b. Volume change increasing shrinkage cracking.

c. Efflorescence.

d. Excess air entraining.

C. Fine Aggregate:

Herbert, Rowland & Grubic, Inc. 03 60 00 - 3 011361.0461

1. Washed natural sand.

2. Gradation:

a. Comply with ASTM C33/C33M.

b. Represented by smooth granulometric curve within required limits.

3. Free from injurious amounts of organic impurities according to ASTM C40/C40M.

D. Mix:

1. Portland cement, sand, and water.

2. Do not use ferrous aggregate or staining ingredients in grout mixes.

2.2 NONSHRINK CEMENTITIOUS GROUT

A. Description:

1. Pre-mixed and ready-for-use formulation requiring only addition of water.

2. Nonshrink, non-corrosive, nonmetallic, non-gas forming, and no chlorides.

B. Performance and Design Criteria:

1. Certified to maintain initial placement volume or expand after set, and to meet following minimum properties when tested according to CRD-C621 for Type D nonshrink grout:

a. Setting Time:

1) Initial: Approximately two hours.

2) Final: Approximately three hours.

3) Comply with ASTM C191.

b. Maximum Expansion: 0.10 to 0.40 percent.

c. Compressive Strength:

1) One-Day: 4,000 psi.

2) Seven-Day: 7,000 psi.

3) 28-Day: 10,000 to 10,800 psi.

4) Comply with CRD-C621.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.

B. Verify areas to receive grout.

3.2 PREPARATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation preparation.

B. Remove defective concrete, laitance, dirt, oil, grease, and other foreign material from concrete surfaces by brushing, hammering, chipping, or other similar means until sound and clean concrete surface is achieved.

C. Roughen concrete lightly, but not to interfere with placement of grout.

Herbert, Rowland & Grubic, Inc. 03 60 00 - 4 011361.0461

D. Remove foreign materials from metal surfaces in contact with grout.

E. Align, level, and maintain final positioning of components to be grouted.

F. Saturate concrete surfaces with clean water, and then remove excess water.

3.3 INSTALLATION

A. Mixing:

1. Portland Cement Grout:

a. Use proportions of two parts sand and one part cement, measured by volume.

b. Prepare grout with water to obtain consistency to permit placing and packing.

c. Mix water and grout in two steps:

1) Premix using approximately 2/3 of water.

2) After partial mixing, add remaining water to bring mix to desired placement consistency and continue mixing two to three minutes.

d. Mix only quantities of grout capable of being placed within 30 minutes after mixing.

e. Do not add additional water after grout has been mixed.

f. Minimum Compressive Strength: 2,400 psi in 48 hours and 7,000 psi in 28 days.

2. Nonshrink Cementitious Grout:

a. Mix and prepare according to manufacturer instructions.

b. Minimum Compressive Strength: 4,000 psi in 48 hours and 10,000 psi in

28 days.

3. Mix grout components in proximity to Work area and transport mixture quickly and in manner not permitting segregation of materials.

B. Placing of Grout:

1. Place grout material quickly and continuously.

2. Do not use pneumatic-pressure or dry-packing methods.

3. Apply grout from one side only to avoid entrapping air.

4. Do not vibrate placed grout mixture or permit placement if area is being vibrated by nearby equipment.

5. Thoroughly compact final installation and eliminate air pockets.

6. Do not remove leveling shims for at least 48 hours after grout has been placed.

C. Curing:

1. Prevent rapid loss of water from grout during first 48 hours by use of approved membrane curing compound or by using wet burlap method.

2. Immediately after placement, protect grout from premature drying, excessively hot or cold temperatures, and mechanical injury.

3. After grout has attained its initial set, keep damp for minimum three days.

Herbert, Rowland & Grubic, Inc. 03 60 00 - 5 011361.0461

3.4 FIELD QUALITY CONTROL

A. Section 01 40 00 - Quality Requirements: Requirements for inspecting and testing.

B. Inspection and Testing:

1. Comply with ACI 301, ACI 318 and as specified in Section 01 40 00 - Quality

Requirements.

2. Submit proposed mix design of each class of grout to Engineer of Record for review prior to commencement of Work.

3. Tests of grout components may be performed to ensure compliance with specified requirements.

END OF SECTION