0083-0270_Bridge06770_04_Structures.pdf
PDF 10 MB Posted
- Solicitation number
- 0083-0270
- Issued by
- New Haven County, Connecticut
About this file
This is a structural design and construction plan document issued by the Connecticut Department of Transportation for the rehabilitation of Bridge No. 06770, an existing 72-inch diameter corrugated metal pipe (ACCMP) culvert located on State Route 796 in Milford, Connecticut. The project involves the installation of a 65-inch outside diameter glass-fiber reinforced polymer (GRP) pipe liner within the existing culvert that passes under the Milford Parkway Extension over Unnamed Brook. The work includes cleaning and repair of the existing culvert structure, construction of cutoff walls and wingwalls at both the inlet and outlet, installation of preformed scour holes, surface repair concrete for headwalls and wingwalls, and comprehensive water management systems during construction. The project encompasses hydraulic design for a 50-year frequency discharge of 220 cubic feet per second (CFS) with upstream and downstream water surface elevations of 75.14 feet and 42.81 feet, respectively. Construction sequencing includes temporary earth retaining systems, a temporary access tunnel (12 feet by 12 feet) to access the north side of the site, temporary water handling cofferdams, and permanent restoration with slope stabilization and riprap installation. The design was completed as of July 9, 2026, with sheets prepared by Clough, Harbour & Associates, LLP, and the work is constrained by the presence of a 24-inch diameter high-pressure gas main located approximately 16 feet below the existing grade.
The construction specifications require concrete classes of PCC03340 (3,000 PSI compressive strength) for cutoff walls and wingwall footings, and PCC04460 (4,400 PSI) for surface repair concrete. All reinforcement must conform to ASTM A615 Grade 60 and be hot-dip galvanized per ASTM A767, Class 1, with specified cover requirements and drill-and-bond anchor details provided throughout. Slip-lining grout is required between the existing pipe and the GRP liner, with grout ports to be removed prior to final completion. The document specifies design standards including AASHTO LRFD Bridge Design Specifications (Ninth Edition, 2020) supplemented by the Connecticut Department of Transportation Bridge Design Manual (2003) and Form 819 Supplemental Specifications (2024). Environmental constraints include restrictions on in-stream work to periods between June 1 and September 30, prohibition on trimming or removal of trees three inches in diameter or greater from April 15 to October 31 due to tri-colored bat protection, and comprehensive best management practices for sediment control and wetland impact minimization. The contractor is responsible for verifying all field conditions, taking necessary measurements to ensure proper fit and alignment of the GRP liner, managing excavated material without separate payment, and coordinating with the Iroquois Pipeline utility representative to protect the high-pressure gas main during all construction activities.
View the file
Other files
Show 40 more
Latest 50 of 58 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CULVERT DETAILS 5S-08
CULVERT DETAILS 4S-07
CULVERT DETAILS 3S-06
CULVERT DETAILS 2S-05
CULVERT DETAILSS-04
SUGGESTED SEQUENCE OF CONSTRUCTION AND WATER HANDLING PLANS-03
GENERAL PLANS-02
STRUCTURE INDEX OF DRAWINGSS-01
DRAWING TITLEDRAWING NUMBERDRAWING TITLEDRAWING NUMBER
INDEX OF DRAWINGS
04 - STRUCTURE
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/28/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-01
TOWN(S):
MILFORD
PARKWAY EXTENSION) OVER UNNAMED BROOK
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
\\cha-llp.com\proj\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_01_StructuresCoverSheet.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
0083-0270
DESIGNER/DRAFTER: CLR CHECKED BY: CEP
DRAWINGS
STRUCTURE INDEX OF
TRANSPORTATION
DEPARTMENT OF
CONNECTICUT
04.01
ROCKY HILL, CT 06067
SUITE 301
400 CAPITAL BOULEVARD
& ASSOCIATES, LLP
CLOUGH, HARBOUR
DESIGNED BY:
GENERAL NOTES
CONCRETE NOTES
: N/AMASH TEST LEVEL
: 24" DIA. HIGH PRESSURE GAS MAIN, 8" DIA. PVC SANITARY SEWERUTILITIES
SHALL ALSO BE SUBMITTED FOR REFERENCE BY THE REVIEWER.
SHOP DRAWINGS BASED ON FIELD MEASUREMENTS ARE SUBMITTED FOR REVIEW, THE FIELD MEASUREMENTS
PROPER FIT OF THE FINISHED WORK AND SHALL ASSUME FULL RESPONSIBILITY FOR THEIR ACCURACY. WHEN
NOT GUARANTEED. THE CONTRACTOR SHALL TAKE ALL FIELD MEASUREMENTS NECESSARY TO ASSURE
GENERAL REFERENCE ONLY. THEY HAVE BEEN TAKEN FROM THE ORIGINAL DESIGN DRAWINGS AND ARE
: DIMENSIONS OF THE EXISTING STRUCTURE SHOWN ON THESE PLANS ARE FOR EXISTING DIMENSIONS
OMITTED DIGITS SHALL BE ASSUMED TO BE ZEROS.
: WHEN DECIMAL DIMENSIONS ARE GIVEN TO LESS THAN THREE DECIMAL PLACES, THE DIMENSIONS
: NONEFUTURE PAVING ALLOWANCE
: N/ALIVE LOAD
: (ASTM A615 GRADE 60)..........fy = 60,000 PSIREINFORCEMENT
THE REQUIREMENTS OF 6.01 - CONCRETE FOR STRUCTURES, AND M.03 - PORTLAND CEMENT CONCRETE.
COMPRESSIVE STRENGTH OF THE CONCRETE IN THE CONSTRUCTED COMPONENTS SHALL CONFORM TO
THE CONCRETE STRENGTH, f’c, USED IN DESIGN OF THE CONCRETE COMPONENTS IS NOTED ABOVE. THE
CLASS PCC04460..................................................f'c = 4,400 PSI CLASS PCC03340 .................................................f'c = 3,000 PSI
CONCRETE:
: MATERIAL STRENGTHS
WITH REVISIONS TO 2022.
SUPPLEMENTED BY THE CONNECTICUT DEPARTMENT OF TRANSPORTATION BRIDGE DESIGN MANUAL (2003), : AASHTO LRFD BRIDGE DESIGN SPECIFICATIONS (NINTH EDITION - 2020), AS DESIGN SPECIFICATIONS
SPECIFICATIONS DATED JANUARY 2026, AND SPECIAL PROVISIONS.
: CONNECTICUT DEPARTMENT OF TRANSPORTATION FORM 819 (2024), SUPPLEMENTAL SPECIFICATIONS
EXPANSION JOINT FILLER IS PAID FOR AS "1/2" PREFORMED EXPANSION JOINT FILLER FOR BRIDGES."
: THE COST OF FURNISHING AND INSTALLING PREFORMED PREFORMED EXPANSION JOINT FILLER
SUPPLEMENTAL REQUIREMENTS.
ALL REINFORCEMENT SHALL CONFORM TO THE REQUIREMENTS OF ASTM A767, CLASS 1, INCLUDING SURFACE REPAIR CONCRETE SHALL BE GALVANIZED AFTER FABRICATION UNLESS NOTED OTHERWISE.
: ALL REINFORCEMENT FOR PROPOSED STRUCTURES AND WELDED WIRE FABRIC FOR REINFORCEMENT
OTHERWISE.
: ALL REINFORCEMENT SHALL HAVE TWO INCHES COVER UNLESS DIMENSIONED CONCRETE COVER
OTHERWISE.
: EXPOSED EDGES OF CONCRETE SHALL BE BEVELED 1"X1" UNLESS DIMENSIONED EXPOSED EDGES
NOT BE PERMITTED WITHOUT THE PRIOR APPROVAL OF THE ENGINEER.
: CONSTRUCTION JOINTS, OTHER THAN THOSE SHOWN ON THE PLANS, WILL CONSTRUCTION JOINTS
COMPONENTS:
THE FOLLOWING PAY ITEMS AND CONCRETE CLASS ARE REQUIRED FOR CAST-IN-PLACE BRIDGE
BRIDGE COMPONENT PCC CLASS
TRANSPORTATION DATA
(APPROXIMATE MAXIMUM ESTIMATED VALUES)
LENGTH
SHIPPING
MEMBER
GRP PIPE LINER
WIDTH
SHIPPING
HEIGHT
SHIPPING
WEIGHT
SHIPPING
8 FT 5.417 FT 5.417 FT 1,600 LB.
DRAINAGE AREA (SQ. MI.)
DESIGN FREQUENCY (YR)
DESIGN DISCHARGE (CFS)
AVG. DAILY FLOW ELEV. (ESTIMATED) (FT)
UPSTREAM DESIGN WATER SURFACE ELEV. (FT)
DOWNSTREAM DESIGN WATER SURFACE ELEV. (FT)
0.2 SQ. MI.
50-YEAR
220 CFS
HYDRAULIC DATA - UNNAMED BROOK
42.81 FT
0.4 CFS
LEGEND
75.14 FT
ITEM BRIDGE COMPONENT PCC CLASS
0601062 CUTOFF WALL, WINGWALL FOOTING PCC03340
CONNECTICUT
COORDINATE G
RID
0601064 WINGWALL STEM PCC03340
PCC044600601072 SURFACE REPAIR CONCRETE
CONTRACTOR SHALL VERIFY THE WEIGHT PRIOR TO SHIPPING AND INSTALLATION.
NOTE: SHIPPING WEIGHT IS APPROXIMATE AND MAY VARY PER MANUFACTURER.
NOTES:
FROM WHICH IT WAS GENERATED OR INCLUDED IN THE ACCESS ROAD ITEMS.
COVERED UNDER AND IN ACCORDANCE WITH THE RESPECTIVE EXCAVATION ITEM
HANDLING, PLACEMENT OR COMPACTING EXCAVATED MATERIAL, AS THIS IS
MATERIAL AT THE END OF THE PROJECT. NO SEPARATE PAYMENT WILL BE MADE FOR
PROVIDES FOR PLACEMENT OF EXCAVATED MATERIAL SUCH THAT THERE IS NO SURPLUS
STOCKPILING EXCAVATED MATERIAL. THE FINAL GRADING SHOWN ON THIS PLAN
THE CONTRACTOR IS RESPONSIBLE FOR MANAGING THE EARTHWORK AND 2.
HIGHWAY SHEET HWY-06 FOR ADDITIONAL DETAILS.
AREAS WHERE THE SLOPE IS STEEPER THAN 2:1 REQUIRE SLOPE STABILIZATION. SEE 1.
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
7/9/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-02
MILFORDPARKWAY EXTENSION) OVER UNNAMED BROOK
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_02_GeneralPlan_ATW1.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
GENERAL PLAN
TRANSPORTATION
800.888.3982.
FOR ADDITIONAL INFORMATION, PLEASE CALL 800.253.5152. FOR EMERGENCIES, PLEASE CALL
ANY DELAYS TO THE CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE IROQUOIS IN ADVANCE TO PREVENT
BEGIN WITHOUT COORDINATING WITH THE UTILITY REPRESENTATIVE (IROQUOIS PIPELINE). THE
GAS MAIN IMMEDIATELY DOWNSTREAM OF BRIDGE NO. 06670. WORK IN THIS AREA CAN NOT
CONTRACTOR IS HEREBY NOTIFIED OF THE SENSITIVE IN-SERVICE 24" DIAMETER HIGH PRESSURE
UTILITY NOTES:
STATE/FEDERAL WETLANDS
SURVEYED EDGE OF WATER
ORDINARY HIGH WATER (OHW)
SCALE: 1" = 30'-0"
GENERAL PLAN
STATE ONLY WETLANDS
17+
18+0
19+00
20+00 21+00
22+00
23+00
10+
+0
+0
C P -5
INTERS
TATE 95
TO
E. B
IT
E. BIT
E. BIT
D R
IV
E G
R A
V E L
D -3
R A
N
(N /F
C H
D (N /F
C H
D
(N /F
C H
D
(N /F
C H
D
DRIVE
GRAVEL
APPROXIMATE PROPERTY LINE
/3
M E R
R
ITT C
O R P
O R A
TE
W
O O
D S
N /F
R A
ILR
O A
D C
O M
P A
N Y
C O
M M
U
TE
R M
E
TR
O -N
O R
TH
N /F
STA
TE
O
F C O
N N
E C
TIC
U T
N /F
24" GAS
APPROX. LOC.
17+
18+0
19+00
20+00 21+00
22+00
23+00
10+
+0
+0
0+
1+0
2+0
3+
4+
5+00
6+00
ROUTE 796 EB
ROUTE 796 WB
CONSTRUCTION)
TUNNEL/CULVERT (FOR
12 FT X 12 FT ACCESS
ROADWAY (TYP.)
EDGE OF
(TO REMAIN)
(SANITARY SEWER)
8" DIA. PVC
WINGWALL (TO REMAIN)
WETLANDS (TYP.)
STATE INLAND
STA. 10+50.00
BEGIN CULVERT
ROUTE 796�
(TO REMAIN)
72" DIA. ACCMP CULVERT
BRIDGE NO. 06770
(L = 196FT)
65" O.D. 63.11" I.D.
GRP PIPE LINER
(TO BE REMOVED)
24" DIA. CCMP PIPE & OUTLET
STA. 12+45.77
END CULVERT
HEADWALL (TO REMAIN)
CUTOFF WALL
HIGHWAY PLANS)
(0-10FT DEEP) (SEE
MANHOLE (6' DIA.)
(SEE HIGHWAY PLANS)
AND OUTLET (L = 84FT)
24" DIA. CMP PIPE
BEYOND PROPOSED MANHOLE
EXISTING 12" CCMP OUTLET TO BE REMOVED
(SEE SPECIAL PROVISIONS)
MAIN (TO BE PROTECTED)
24" DIA. HIGH PRESSURE GAS
HIGHWAY LINE
HIGHWAY LINE
HIGHWAY LINE
WINGWALL
CONSTRUCT PROPOSED
EXISTING WINGWALL AND
REMOVE AND DISPOSE OF
(TO REMAIN)
WINGWALL
HEADWALL (TO REMAIN)
CUTOFF WALL
WINGWALL (TO REMAIN)
REMOVE AND REPLACE STANDARD RIPRAP
(L = 7FT)
30" DIA. CMP
WETLANDS (TYP.)
STATE/FEDERAL
STATE INLAND WETLANDS (TYP.)
(SEE NOTE 1)
SLOPE STABILIZATION
GRADE TO DRAIN TO OUTLET
RESTORE SWALE OUTLET
MORE INFORMATION)
(SEE SHEET S-04 FOR
INTERMEDIATE RIPRAP
PREFORMED SCOUR HOLE
PERMANENT EASEMENT
PERMANENT ACCESS ROAD
MILFORD PARKWAY EXTENSION
UNNAMED BROOK
CONSTRUCTION MATERIALS)
TEMPORARY EASEMENT (FOR
O.:
04.02
+0
18+
19+00
20+00 21+00
22+00
23+00
+0
C P -5
INTERS
TATE 9
5TO
E. B
IT
E. BIT
E. BIT
D R
IV
E G
R A
V E L
D -3
R A
N
(N F
C H
D
(N F
C H
D
(N F
C H
D
(N F
C H
D
DRIVE
GRAVEL
APPROXIM
ATE PROPERTY LINE
S T A
T E O
F C
O N
N E C
T
IC
U T
N F
R A
IL
R O
A D C
O M
P A
N Y
C O
M M
U T E R
M E T R
O -N
O R
T H
N F
S T A
T E O
F C
O N
N E C
T
IC
U T
N F
24" GAS
APPROX. LOC.
+0
18+
19+00
20+00 21+00
22+00
23+00
81+00
+0
0+
1+
2+0
3+
4+
5+00
6+00
LEGEND
TEMPORARY WATER-HANDLING-COFFERDAM
3.2 CFS
TEMPORARY HYDRAULIC DATA
0.4 CFSAVERAGE DAILY FLOW
AVERAGE SPRING FLOW 0.8 CFS
70 CFS
= 10X AVERAGE SPRING
TEMPORARY DESIGN DISCHARGE
GRAVITY FLOW BYPASS PIPE
2-YEAR FREQUENCY DISCHARGE
ELEVATION UPSTREAM
TEMPORARY WATER SURFACE
ELEVATION DOWNSTREAM
TEMPORARY WATER SURFACE
8 CFS
72.84 FT
40.07 FT
= 4 x AVERAGE SPRING FLOW
TEMPORARY DESIGN DISCHARGE
LOW FLOW PUMPING
SUGGESTED SEQUENCE OF CONSTRUCTION
(SANDBAGS)
WATER-HANDLING-COFFERDAM CONCEPT
NOT TO SCALE
SECTION VIEW
MIN. TOP ELEV. DOWNSTREAM = 42.00 FT
MIN. TOP ELEV. UPSTREAM = 74.00 FT
HANDLING-COFFERDAM
TEMPORARY WATER-
PLASTIC SEAL LINER
(SEE TEMP. HYDRAULIC TABLE)
TEMP. WATER SURFACE ELEV.
FLOW
CONNECTIC
UT
COORDIN
ATE G
RID
FLOW.
UNCONFINED INSTREAM WORK SHALL BE DONE DURING PERIODS OF LOW -
THE EXTENT POSSIBLE.
DISTURBED AREAS AND THE DURATION OF DISTURBANCE SHALL BE MINIMIZED TO -
MINIMIZE TURBIDITY/SEDIMENT TRANSPORT DOWNSTREAM.
BEST MANAGEMENT PRACTICE SHALL BE UTILIZED WHEREVER POSSIBLE TO -
TEMPORARY AND PERMANENT WETLAND/WATERCOURSE IMPACT.
DISTURBANCE SHALL BE LIMITED TO AREAS THAT HAVE BEEN APPROVED FOR -
ALL UNCONFINED IN-WATER WORK SHALL BE MINOR IN NATURE. -
PROPOSED SCHEDULE FOR WORK OPERATIONS. -
WATER WORK WITH CONSIDERATION OF THE FOLLOWING:
THE DEPARTMENT WILL REVIEW AND MAY APPROVE THE METHODS OF UNCONFINED IN-2.
TO THE PERIOD FROM JUNE 1 TO SEPTEMBER 30, INCLUSIVE.
ANY UNCONFINED IN-STREAM WORK WITHIN THE WATERCOURSE SHALL BE RESTRICTED 1.
:UNCONFINED IN-STREAM WORK BMP NOTES
:PLANS NOTES
THROUGH THE WORK AREA.
PLAN, WHICH MINIMIZES NEGATIVE IMPACTS AND SAFELY CONVEYS LARGER FLOWS
PLAN WITH LOWER PUMPING FLOWS, PROVIDED THAT THIS INCLUDES A CONTINGENCY
CONDITIONS, THE ENGINEER MAY APPROVE A CONSTRUCTION WATER HANDLING
BASED UPON FIELD CONDITIONS, WORK DURATION, AND EXPECTED WEATHER
SYSTEM PLAN SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL.
CONDITIONS, THE PUMP SYSTEM SHALL BE DESIGNED BY THE CONTRACTOR. PUMP
IF A PUMP SYSTEM IS PROPOSED FOR RELINING THE STRUCTURE DURING LOW FLOW 7.
ENGINEER FOR APPROVAL AND IS INCLUDED AS PART OF WATER-HANDLING.
SHALL SUBMIT THE MEANS AND METHODS OF HANDLING STORM DRAINAGE TO THE
EXPECTED FLOWS AND BE DISCHARGED TO A STABLE LOCATION. THE CONTRACTOR
CONFINED AREAS. PUMPS/PIPES SHALL BE SIZED BY THE CONTRACTOR TO HANDLE THE
OR PROPOSED STORM DRAINAGE PIPES SHALL BE DIVERTED OR PUMPED OUTSIDE THE
ANY STORM DRAINAGE DISCHARGING INTO A CONFINED WORK AREA FROM EXISTING 6.
WETLAND IMPACT SHEET OF THE PERMIT PLANS.
WATER HANDLING MEASURES SHALL NOT EXCEED IMPACT AREAS SHOWN ON THE 5.
CONTRACTOR TO THE ENGINEER FOR APPROVAL.
MEANS AND METHOD FOR WATER HANDLING SYSTEM SHALL BE SUBMITTED BY THE
WATER TYPICAL SCHEMATICS" MAY BE UTILIZED UNLESS SPECIFICALLY PROHIBITED. A
ANY WATER HANDLING SCHEME DEPICTED WITHIN THE DEPARTMENT'S "HANDLING
CONSTRUCTION ACTIVITY AND SHALL CONFORM TO THE ENVIRONMENTAL PERMIT(S).
FLOWS THROUGH THE CONSTRUCTION AREA, SHALL BE ABLE TO SUPPORT
SYSTEM THAT THE CONTRACTOR ELECTS TO USE WHICH WILL SAFELY CONVEY WATER
TEMPORARY WATER-HANDLING-COFFERDAM SHALL CONSIST OF AN APPROVED 4.
3. A DEWATERING BASIN SHALL BE ESTABLISHED OUTSIDE OF THE WETLAND LIMITS.
STRUCTURE WHERE NECESSARY.
BYPASS FLOWS DURING CONSTRUCTION FOR CLEANING AND PATCHING THE
A TEMPORARY WATER HANDLING PIPE WITH A DIAMETER OF 18" SHALL BE UTILIZED TO 2.
HANDLING SYSTEM AS REQUIRED DURING CONSTRUCTION.
THE CONTRACTOR SHALL MAINTAIN WATER THROUGH THE TEMPORARY WATER 1.
:WATER HANDLING NOTES
TREES 3" DBH OR GREATER FROM APRIL 15 TO OCTOBER 31.
TRI-COLORED BAT - NO TRIMMING, CUTTING, OR REMOVAL OF
PROTECTED SPECIES TIME-OF-YEAR:
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/30/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-03
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_03_ConstructionSequence_ATW1.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
DESIGNER/DRAFTER: CLR CHECKED BY: CEP WATER HANDLING PLAN
OF CONSTRUCTION AND
SUGGESTED SEQUENCE
TRANSPORTATION
REMOVE E&S CONTROLS UPON FINAL STABILIZATION.19.
PERFORM SITE RESTORATION, FINAL GRADING INSTALL PLANTINGS AND SEEDING.18.
REMOVE TEMPORARY ACCESS ROAD AND TEMPORARY EARTH RETAINING SYSTEMS.17.
REMOVE WATER HANDLING.16.
CONSTRUCT PREFORMED SCOUR HOLE AT OUTLET.15.
COMPLETE DRAINAGE WORK, BACKFILL AND RESTORE GRADES.14.
CONSTRUCT EAST WINGWALL AND CUTOFF WALL AT OUTLET.13.
REMOVE EAST WINGWALL AT OUTLET.12.
BACKFILL AND RESTORE INLET.11.
EXCAVATE & CONSTRUCT CUTOFF WALL AT INLET.10.
INSTALL GRP STRUCTURAL LINER.9.
CLEAN AND REPAIR EXISTING CULVERT.8.
INSTALL WATER HANDLING.7.
PERFORM TEST PITS TO CONFIRM GAS MAIN DEPTHS. 6.
INSTALL MANHOLE AND TEMPORARY STORMWATER BYPASS PIPES.5.
CONSTRUCT TEMPORARY ACCESS ROAD (SITE NO. 2) AND INSTALL TERS AT OUTLET.4.
INSTALL TERS AT INLET.3.
PERFORM CLEARING AND GRUBBING & INVASIVE SPECIES REMOVAL.2.
TRACKING PAD.
INSTALL SEDIMENTATION CONTROL, CONSTRUCT PERMANENT ACCESS ROAD & ANTI-1.
THE INLET CUTOFF WALL.
PROVIDING ADDITIONAL AREA FOR INSTALLING THE PIPE LINING MATERIALS AND CONSTRUCTING
WORK AREA SHOWN ON THIS SHEETS IS TEMPORARY AND INTENDED FOR THE PURPOSES OF 4.
SHOWN ON THE PLANS.
DIMENSIONS OF ALL EXISTING FEATURES, AS ACTUAL CONDITIONS MAY DIFFER FROM INFORMATION
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY LOCATIONS, CONDITIONS, AND FIELD 3.
RETAINING SYSTEM WILL BE PAID FOR UNDER THE ITEM - "TEMPORARY EARTH RETAINING SYSTEM".
& METHOD FOR SUPPORTING THE LIMITS OF EXCAVATION. NON-DRIVEN TEMPORARY EARTH
VICINITY OF THE EXISTING GAS MAIN. THE CONTRACTOR IS RESPONSIBLE FOR DEVELOPING A MEANS
RETAINING SYSTEM". NON-DRIVEN TEMPORARY EARTH RETAINING SYSTEM SHALL BE INSTALLED IN THE
TEMPORARY EARTH RETAINING SYSTEMS SHALL BE PAID FOR UNDER ITEM "TEMPORARY EARTH 2.
ACTIVITIES. THE CONTRACTOR NEEDS TO ACCOUNT FOR THIS IN THEIR BID.
THE TYPE/SIZE OF THE EQUIPMENT USED IN THIS AREA TO COMPLETE THE REQUIRED CONSTRUCTION
IS 12FT X 12FT. THE CONTRACTOR MAY NEED TO ADJUST THEIR MEANS AND METHODS AS WELL AS
ACCESS TUNNEL IS REQUIRED TO GAIN ACCESS TO THE NORTH SIDE OF THE SITE. THE ACCESS TUNNEL 1.
ROAD (SITE NO. 2)
TEMPORARY ACCESS
RELOCATED)
(TO BE REMOVED AND
CCMP PIPE & OUTLET
EXISTING 24" DIA.
TEMPORARY WATER-HANDLING - COFFERDAM
PIPE (SEE WATER HANDLING NOTE 2)
18" DIAMETER TEMPORARY BYPASS
PIPE (TO REMAIN)
EXISTING 12" CCMP
(TO REMAIN) (TYP.)
EXISTING HEADWALL
(TO REMAIN) (TYP.)
EXISTING WINGWALL
HANDLING - COFFERDAM
TEMPORARY WATER-
CUTOFF WALL
WETLANDS (TYP.)
STATE INLAND
ROUTE 796�
CULVERT NO. 06770
EXISTING 72" ACCMP
65" O.D. (63.11" I.D.)
GRP PIPE LINER
ROADWAY (TYP.)
EDGE OF
(L = 68'-0" ±)
RETAINING SYSTEM
TEMPORARY EARTH
(SITE NO. 1)
ACCESS ROAD
PERMANENT
SYSTEM (SEE NOTE 4)
24" TEMPORARY DRAINAGE
CUTOFF WALL
HIGHWAY PLANS)
(0-10 FT DEEP) (SEE
MANHOLE (6' DIA.)
IN PROPOSED WINGWALL
BE REMOVED AND RELOCATED
EXISTING 12" CCMP OUTLET TO
(SEE HIGHWAY PLANS)
24" CMP PIPE AND OUTLET
(SEE SPECIAL PROVISIONS)
MAIN (TO BE PROTECTED)
24" DIA. HIGH PRESSURE GAS
ACCESS TUNNEL
WINGWALL
PROPOSED
TEMPORARY DEWATERING BASIN
APPROXIMATE LOCATION OF
TEMPORARY DEWATERING BASIN
APPROXIMATE LOCATION OF
HANDLING - COFFERDAM
TEMPORARY WATER-
(TYP.)
HIGHWAY LINE
BASIN
CONTROL AT CATCH
SEDIMENTATION
(TYP.)
HIGHWAY LINE
RESTORE SLOPE
SLOPE
RESTORE RIP-RAP
( L = 50FT ±)
CONSTRUCTION IS COMPLETE.
CONSTRUCTION. REMOVE WHEN
INSTALL HIGH VISIBILTY FENCE DURING
AREA (SEE PLAN NOTES 4)
APPROXIMATE LIMITS OF WORK
PERMANENT EASEMENT
BAR (TYP.)
TEMPORARY WATER
PIPE (TO REMAIN)
EXISTING 18" RCP
PIPE (TO REMAIN)
EXISTING 24" CMP
PIPE (TO REMAIN)
EXISTING 24" CMP
PIPE (TO REMAIN)
EXISTING 12" CCMP
CONSTRUCTION MATERIALS)
TEMPORARY EASEMENT (FOR
(SEE HIGHWAY PLANS)
ANTI-TRACKING PAD
TEST PIT NO. 1
TEST PIT NO. 2
(L = 75'-0" ±)
RETAINING SYSTEM
TEMPORARY EARTH
(L = 23'-0" ±)
RETAINING SYSTEM
TEMPORARY EARTH
UNNAMED BROOK
ROUTE 796 EB
ROUTE 796 WBMILFO
RD PARKWAY EXTENSION
(L=45'-0" ±)
RETAINING SYSTEM
TEMPORARY EARTH
STATE/FEDERAL WETLANDS
ORDINARY HIGH WATER
(SEE WATER HANDLING NOTES 2)
TEMPORARY BYPASS PIPE
SCALE: 1" = 30'-0"
CONSTRUCTION SEQUENCE PLAN
SURVEYED EDGE OF WATER
STATE-ONLY WETLANDS
SEDIMENTATION CONTROL SYSTEM (APPROX. LOCATION)
TEST PIT
04.03
STRUCTURAL LINER.
CONDITIONS OF THE PIPE AND CONFIRM THE ACCURACY OF FIT FOR THE GRP
WATER, THE CONTRACTOR SHALL SCAN THE PIPE TO VERIFY THE EXISTING
BYPASS PIPE IS IN PLACE AND THE HOST PIPE IS CLEAR OF ANY DEBRIS AND
PRIOR TO ORDERING THE GRP STRUCTURAL LINER, AFTER THE TEMPORARY 8.
STANDARD RIPRAP SHALL BE PAID FOR UNDER ITEM "STANDARD RIPRAP".7.
GRANULAR FILL SHALL BE PAID FOR UNDER ITEM "GRANULAR FILL".6.
CRUSHED STONE SHALL BE PAID FOR UNDER ITEM "NO. 6 CRUSHED STONE".5.
INTERMEDIATE RIPRAP SHALL BE PAID FOR UNDER ITEM "INTERMEDIATE RIPRAP".4.
FOR UNDER ITEM "SURFACE REPAIR CONCRETE".
SHALL BE SURFACE REPAIR CONCRETE CLASS PCC04460 AND SHALL BE PAID
PATCHING MATERIAL FOR SURFACE REPAIRS TO HEADWALLS AND WINGWALLS 3.
REINFORCED POLYMER (GRP) PIPE".
65" DIA. GRP PIPE LINER SHALL BE PAID FOR UNDER ITEM "65IN DIA GLASSFIBER 2.
UNDER ITEM "SLIP-LINING GROUT".
PIPE AND THE PROPOSED PIPE LINER. SLIP-LINING GROUT SHALL BE PAID FOR
SLIP-LINING GROUT SHALL BE USED TO GROUT THE VOID BETWEEN THE EXISTING 1.
NOTES:
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/28/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-04
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_04_CulvertDetails.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
CULVERT DETAILS
TRANSPORTATION
EL. 42.94
OUTLET (PROPOSED CONDITION)
50-YEAR DEPTH OF WATER AT
EL. 41.80
DOWNSTREAM OHW
DOWNSTREAM ELEVATION
" = 1'4
SCALE
(TO REMAIN)
EXISTING HEADWALL
CUTOFF WALL
PROPOSED
12" NO. 6 CRUSHED STONE
12" GRANULAR FILL
TYPE 1 DETAIL)
RIPRAP (SEE PREFORMED SCOUR HOLE
REMOVE AND REPLACE 36" STANDARD
PROPOSED GRADE
CULVERT (TO REMAIN)
EXISTING 72" ACCMP
I.D. = 63.11"
O.D. = 65"
GRP LINER
(TO REMAIN) (TYP.)
EXISTING WINGWALL
HEADWALLS AND WINGWALLS (TYP.)
SURFACE REPAIR CONCRETE FOR
INVERT EL. 42.07
EL. 46.63
EL. 44.42
WINGWALL
PROPOSED
(TOP OF EXISTING PIPE EL. 46.06 ±)
16 FT BELOW EXISTING GRADE
GAS MAIN APPROXIMATELY
EXISTING 24" HIGH-PRESSURE
(SEPARATION - CLASS 2)
GEOTEXTILE
(SEPARATION - CLASS 2)
GEOTEXTILE
EL. 36.72 ±
BOTTOM OF FOOTING
INVERT EL. 40.72
(EXISTING)
INNER TOP EL. OF GRP PIPE EL. 45.98 ±
INVERT EL. 40.56
(PROPOSED)
CUTOFF WALL
EL. 70.60
UPSTREAM OHW
18" INTERMEDIATE RIPRAP
EXISTING GRADE
REMAIN
AND HEADWALL TO
EXISTING WINGWALLS
PROPOSED GRADE
(TYP.)
MBR (R-B MASH)
SHLDR
12'-0"
LANE
12'-0"
ROUTE 796�
LANE
14'-0"
SHLDR
8'-0"
SHLDR
5'-0"
SHLDR
5'-0"
GRADE (TYP.)
EXISTING
ACCMP, WHERE NECESSARY
CLEAN AND REPAIR EXISTING
(SEE DETAIL THIS SHEET)
PREFORMED SCOUR HOLE
EXISTING GRADE
HEADWALL (TO REMAIN)
EXISTING WEST WINGWALL AND
EL. 41.80
DOWNSTREAM OHW
CUTOFF WALL
EXISTING 24" GAS MAIN
TYPICAL LONGITUDINAL SECTION
SCALE 1" = 20'
ACCMP CULVERT
RELINED EXISTING 72"
22 ± %
FLOW
14 ± %
7 ± %
(SEE NOTE 8)
LINE OF CULVERT NEAR MID-SPAN
APPROXIMATE 1FT DROP IN GRADE
12" GRANULAR FILL
43'-6" ±
METAL BEAM RAIL
UPSTREAM ELEVATION
" = 1'4
1SCALE
(TO REMAIN) (TYP.)
EXISTING WINGWALL
PROPOSED CUTOFF WALL
12" NO. 6 CRUSHED STONE
HEADWALLS AND WINGWALLS (TYP.)
SURFACE REPAIR CONCRETE FOR
CULVERT (TO REMAIN)
EXISTING 72" ACCMP
(TO REMAIN)
EXISTING HEADWALL
EXISTING GRADE
70.60
UPSTREAM OHW EL.
EL. 75.14
INLET (PROPOSED CONDITION)
50-YEAR DEPTH OF WATER AT
(TOP OF EXISTING PIPE EL. 74.42 ±)
INNER TOP EL. OF GRP PIPE EL. 73.60 ±
I.D. = 63.11"
O.D. = 65"
GRP LINER
18" INTERMEDIATE RIPRAP
PROPOSED GRADE
(SEPARATION - CLASS 2)
GEOTEXTILE
EL. 64.34 ±
BOTTOM OF FOOTING
INVERT EL. 68.34
(EXISTING)INVERT EL. 68.18
(PROPOSED)
EXISTING EDGE OF ROAD AT GUTTERLINE
GEOTEXTILE (SEPARATION - CLASS 2)
12" GRANULAR FILL
MANUFACTURER DETAIL
BEVELED INLET PER
METAL BEAM RAIL
EXISTING EDGE OF ROAD AT GUTTERLINE
56'-0"
04.04
COMPLETION OF THE GROUTING OF ANNULAR SPACE.
ADJUSTING RODS SHALL BE TRIMMED FLUSH WITH THE LINER AFTER 7.
PIPE". SEE SPECIAL PROVISIONS.
PAID FOR UNDER ITEM "65IN DIA GLASSFIBER REINFORCED POLYMER (GRP)
IS THE PURPOSE OF THE BLOCKING OR SKID RAILS. ADJUSTING RODS SHALL BE
INTENDED TO PREVENT MOVEMENT DURING THE GROUTING PROCESS, WHICH
LINING PIPE INSIDE THE EXISTING PIPE. THE ADJUSTING RODS ARE NOT
OPTIONAL ADJUSTING RODS SHALL BE USED TO POSITION THE PROPOSED SLIP-6.
"REPAIR EXISTING CULVERT (ESTIMATED COST)". SEE SPECIAL PROVISIONS.
APPROVED BY THE ENGINEER. THIS WORK SHALL BE PAID FOR UNDER ITEM
HYDRAULIC CEMENT OR APPROPRIATE MATERIAL AS DIRECTED AND
VOIDS OR SERIOUS DETERIORATION IN THE EXISTING PIPE SHALL BE FILLED WITH 5.
(ESTIMATED COST)". SEE SPECIAL PROVISIONS.
THIS WORK SHALL BE PAID FOR UNDER ITEM "REPAIR EXISTING CULVERT
CONSTRUCTION WILL FACILITATE INSTALLATION OF THE PIPE CONSTRUCTION.
CLEARANCES AND VERIFY THAT THE PROPOSED MEANS AND METHODS OF
EXISTING PIPE. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING
THE CONTRACTOR SHALL NOTE THAT THERE MAY BE DEFORMATIONS IN THE 4.
SPECIAL PROVISIONS.
UNDER ITEM "CLEAN EXISTING CULVERT - GREATER THAN 42" DIAMETER". SEE
INSTALLATION OF THE GRP CULVERT LINER. THIS WORK SHALL BE PAID FOR
THE EXISTING ACCMP CULVERT SHALL BE CLEANED IN PREPARATION FOR THE 3.
REINFORCED POLYMER (GRP) PIPE". SEE SPECIAL PROVISIONS.
PERMITTED. BLOCKING SHALL BE PAID FOR UNDER ITEM "65IN DIA GLASSFIBER
HARDWARE PENETRATING THE PIPE WALL TO ATTACH THE BLOCKING IS NOT
PROPOSED LINER PIPE SUCH AS SKID RAILS (SEE SPECIAL PROVISIONS).
ALTERNATIVES TO BLOCKING MAY BE USED BETWEEN EXISTING PIPE AND 2.
SUPPLIER.
DETERMINED BY THE CONTRACTOR IN COORDINATION WITH THE GRP
GROUT". THE LOCATION, SIZE AND NUMBER OF GROUT PORTS WILL BE
REMOVAL. GROUT PORTS SHALL BE PAID FOR UNDER ITEM "SLIP-LINING
CONTRACTOR SHALL REMOVE GROUT PORTS PRIOR TO BYPASS PIPE 1.
NOTES:
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
7/9/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-05
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_05_SlipLiningDetails.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
CULVERT DETAILS 2
TRANSPORTATION
1.5
FLOW DIRECTION
(T
Y P
(SEE NOTE 1)
2" DIAMETER GROUT PORT (TYP.)
(SEE NOTE 2)
BLOCKING AS REQUIRED (TYP.)
65" DIA. GRP LINER
SLIP-LINING GROUT
EXISTING 72" ACCMP CULVERT
(SEE NOTES 6 & 7)
RODS (TYP.)
OPTIONAL ADJUSTING
SCALE: 1" - 1'-0"
CULVERT SECTION
SCALE: N.T.S.
EXISTING BOTTOM OF PIPE REPAIR DETAILS
EXISTING HEADWALL
EXISTING 72" ACCMP CULVERT
65" DIA. GRP LINER
INJECTED WITH HYDRAULIC CEMENT
VOIDS BEHIND EXISTING PIPE SHALL BE
BE CUT BACK TO SOUND MATERIAL
DETERIORATED PIPE SECTIONS SHALL
INJECTED WITH HYDRAULIC CEMENT
VOIDS BEHIND EXISTING PIPE SHALL BE
BE CUT BACK TO SOUND MATERIAL
DETERIORATED PIPE SECTIONS SHALL
SCALE: N.T.S.
PIPE BEVEL DETAILS
SLIP-LINING GROUT
O.:
04.05
3" COVER (TYP.)
SEE DWG. NO. S-04 FOR PREFORMED SCOUR HOLE PAY NOTES. 6.
SEE DWG. NO. S-02 FOR EXPANSION JOINT PAY NOTES.5.
SIMILAR.
PLAN AND ELEVATION DETAILS SHOWN FOR CULVERT OUTLET. CUTOFF WALL AT INLET 4.
PAID FOR UNDER ITEM "STRUCTURE EXCAVATION - EARTH (COMPLETE)".
EXCAVATION REQUIRED FOR CONSTRUCTING PROPOSED CUTOFF WALLS SHALL BE 3.
"DEFORMED STEEL BARS - GALVANIZED".
REINFORCEMENT FOR THE PROPOSED CUTOFF WALL SHALL BE PAID FOR UNDER ITEM 2.
FOR UNDER ITEM "FOOTING CONCRETE".
PROPOSED CUTOFF WALL CONCRETE WILL BE CLASS PCC03340 AND SHALL BE PAID 1.
NOTES:
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/28/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-06
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_06-08_WallDetails.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
CULVERT DETAILS 3
TRANSPORTATION
36'-3"
15'-9"
(SEE DETAIL)
PROPOSED CUTOFF WALL
EXISTING HEADWALL
PROPOSED CUTOFF WALL
3:1 SLOPE
36" STANDARD RIP RAP
GEOTEXTILE (SEPARATION - CLASS 2)
12" GRANULAR FILL
PIPE�
A
EXISTING HEADWALL
CULVERT
PROPOSED WINGWALL
(TO REMAIN)
EXISTING DOWNSTREAM CULVERT
M
IN
SECTION
" = 1'-0"4
1SCALE:
PLAN VIEW
" = 1'-0"4
1SCALE:
PREFORMED SCOUR HOLE TYPE 1
A
CUTOFF WALL DETAIL
12" NO. 6 CRUSHED STONE
1'-0"
" = 1'-0"1SCALE:
4' -0
#4 @ 12"
#4 @ 12"
IF
N
E C
E S
S A
R Y
U S
E
S P
L
IC
E
(1
F
U L L L
E N
(T Y
P
S P
L
IC
E
6"
30°
SPACE AT 12" O.C. MIN. 6" EMBEDMENT DEPTH
BOND ANCHORS INTO EXISTING HEADWALL.
#4 HOOKED ANCHORS. DRILL HOLES AND
04.06
9"
8"
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/28/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-07
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_06-08_WallDetails.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
CULVERT DETAILS 4
TRANSPORTATION
ITEM "DRILL HOLES AND BONDING ANCHORS".
DRILLING AND BONDING OF ANCHOR REINFORCEMENT TO BE PAID FOR UNDER 10.
WING.
SHALL EXTEND FROM THE TOP OF THE PROPOSED FOOTING TO THE TOP OF THE
JOINTS BETWEEN THE FLARED WINGS AND EXISTING HEADWALL, THE JOINT SEAL
JOINT SEAL TO EXTEND FROM TOP OF FOOTING TO TOP OF WINGWALL. FOR THE 9.
GROUT SHALL BE PAID FOR UNDER ITEM "ABUTMENT AND WALL CONCRETE".
WILL BE INCULDED IN THE QUANTITY FOR WINGWALL CONCRETE. NON-SHRINK
NON-SHRINK GROUT WILL NOT BE MEASURED SEPARATELY FOR PAYMENT RATHER 8.
SEE DWG. NO. S-06 FOR ADDITIONAL DETAILS. .7
EARTH (COMPLETE)".
WINGWALL AT OUTLET SHALL BE PAID FOR UNDER ITEM "STRUCTURE EXCAVATION -
EXCAVATION REQUIRED FOR CONSTRUCTING PROPOSED RECONSTRUCTED EAST 6.
DAMPPROOFING SHALL BE PAID FOR UNDER ITEM "DAMPPROOFING".5.
"PERVIOUS STRUCTURE BACKFILL".
PERVIOUS STRUCTURE BACKFILL BEHIND WINGWALL SHALL BE PAID FOR UNDER ITEM 4.
GALVANIZED".
CUTOFF WALL SHALL BE PAID FOR UNDER ITEM "DEFORMED STEEL BARS -
REINFORCEMENT FOR THE PROPOSED WINGWALL, WINGWALL FOOTING, AND 3.
FOR UNDER ITEM "ABUTMENT AND WALL CONCRETE".
PROPOSED WINGWALL CONCRETE WILL BE CLASS PCC03340 AND SHALL BE PAID 2.
PCC03340 AND SHALL BE PAID FOR UNDER ITEM "FOOTING CONCRETE".
PROPOSED WINGWALL FOOTING AND CUTOFF WALL CONCRETE WILL BE CLASS 1.
NOTES:
3" COVER (TYP.)
BLOCKOUT FOR PIPE PENETRATION
WINGWALL ANCHOR DETAIL
SCALE:
4" = 1'-0"
NOTE: WINGWALL STEM SHOWN, FOOTING SIMILAR.
CUTOFF WALL ANCHOR DETAIL
SCALE:
4" = 1'-0"
(TYP.)
1'-0"
(T Y
P
ADHESIVE BONDED ANCHOR NOTES:
5.183#4 ANCHORS 12"CUTOFF WALL
6.953#5 ANCHORS @ 18"WINGWALL
(KIPS)
TEST LOAD
PROOF
TO BE TESTED
OF ANCHORS
MIN. NUMBER
DESCRIPTION
ANCHOR
LOCATION
“DRILLING HOLES AND BONDING ANCHORS.”
ANCHORS, AND INSPECT AND TEST THE ANCHORS SHALL BE PAID FOR UNDER THE ITEM #0610001 - THE WORK TO FURNISH THE ANCHORS AND ADHESIVE BONDING MATERIAL, DRILL HOLES, INSTALL 5.
UNLESS OTHERWISE SPECIFIED, THE ENGINEER SHALL RANDOMLY SELECT THE ANCHORS TO BE TESTED.
PROOF LOAD:
THE MINIMUM NUMBER OF ANCHORSS AT EACH LOCATION TO BE FIELD TESTED TO THE TABULATED PROCEDURES AND INSTALLED ADHESIVE BONDED ANCHOR STRENGTH. THE FOLLOWING TABLE DETAILS THE ANCHOR SHALL BE FIELD TESTED UNDER A PROOF TEST LOAD TO VERIFY THE INSTALLATION 5.
NOT PERMITTED.
REQUIRED CONCRETE COVER. THE USE OF CORE DRILLING THROUGH THE EXISTING REINFORCEMENT IS WHEN DRILLING HOLES, IF EXISTING REINFORCEMENT IS ENCOUNTERED, RELOCATE HOLE MAINTAINING 4.
THE ADHESIVE BONDING METERIAL SHALL BE AT LEAST CATEGORY 2.
OR GREATER IN DRY, CRACKED CONCRETE AT TEMPERATURE RANGE A. THE ANCHOR CATEGORYOF THE ADHESIVE BONDING MATERIAL SHALL HAVE A MINIMUM CHARACTERISTIC BOND STRESS OF 1.00 KSI 3.
ACCORDANCE WITH ASTM A767, CLASS 1, INCLUDING SUPPLEMENTAL REQUIREMENTS.
THE ANCHOR SHALL CONFORM TO ASTM A615, GRADE 60 AND BE HOT DIP GALVANIZED IN 2.
ANCHORS WAS 3 KSI.
THE COMPRESSIVE STRENGTH OF THE EXISTING CONCRETE IN THE DESIGN OF ADHESIVE BONDED 1.
CUTOFF WALL DETAIL
12" NO. 6 CRUSHED STONE
1'-0"
" = 1'-0"1SCALE:
4' -0
#4 @ 12"
#4 @ 12"
IF
N
E C
E S
S A
R Y
U S
E
S P
L
IC
E
(1
F
U L
L L
E N
(T Y
P
S P
L
IC
E
6"
30°
SPACE AT 12" O.C. MIN. 6" EMBEDMENT DEPTH
BOND ANCHORS INTO EXISTING HEADWALL.
#4 HOOKED ANCHORS. DRILL HOLES AND
CUTOFF WALL AND WINGWALL PLAN
" = 1'-0"2
1SCALE
WINGWALL
PROPOSED
(SEE DETAIL)
#4 HOOKED DOWELS (TYP.)
(TO REMAIN) (TYP.)
EXISTING WINGWALL
(TO REMAIN)
EXISTING HEADWALL
CULVERT (TO REMAIN)
EXISTING 72" ACCMP
GRP LINER
FOOTING
WINGWALL
PROPOSED
NON-SHRINK GROUT
6"
FLOW
JOINT FILLER FOR BRIDGES
" EXPANSION JOINT WITH PREFORMED2
(SEE DETAIL)
PROPOSED CUTOFF WALL
4" DIA. PVC WEEP
" JOINT2
120°
(SEE DETAIL)
#5 DRILL AND BOND ANCHOR
FOOTING
PROPOSED WINGWALL
STEM
PROPOSED WINGWALL
HEADWALL
EXISTING
JOINT
" EXPANSION 2
1BOND ANCHOR
#5 @18" DRILL AND
CUTOFF WALL
PROPOSED
HEADWALL
EXISTING
WALL
PROPOSED CUTOFF
BOND ANCHOR
#4 @ 12" DRILL AND
FOOTING
PROPOSED WINGWALL
04.07
PROJECT TITLE: PROJECT NO.: DRAWING NO.:
SHEET NO.:
5/28/2026
SIGNATURE BLOCK: DRAWING TITLE:
S-08
REHABILITATION OF BRIDGE NO. 06770 SR 796 (MILFORD
PLOTTED DATE:
V:\Projects\ANY\K6\075442.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0083_0270_S_06-08_WallDetails.dgn FILE NAME: 7379 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
CULVERT DETAILS 5
TRANSPORTATION
SEE DWG. NO. S-07 FOR ADDITIONAL DETAILS. 9.
" PROFILE TO BE PROVIDED BETWEEN POURS. 2
MINIMUM OF
IF CONSTRUCTION JOINT IS ADDED, A ROUGHENED SURFACE CONSISTING OF A 8.
BE PAID FOR UNDER ITEM "PERVIOUS STRUCTURE BACKFILL".
BAGGED STONE WILL NOT BE MEASURED SEPARATELY FOR PAYMENT RATHER SHALL .7
"STRUCTURE EXCAVATION - EARTH (COMPLETE)".
RECONSTRUCTED EAST WINGWALL AT OUTLET SHALL BE PAID FOR UNDER ITEM
LIMITS OF STRUCTURE EXCAVATION REQUIRED FOR CONSTRUCTING PROPOSED 6.
DAMPPROOFING SHALL BE PAID FOR UNDER ITEM "DAMPPROOFING".5.
"PERVIOUS STRUCTURE BACKFILL".
PERVIOUS STRUCTURE BACKFILL BEHIND WINGWALL SHALL BE PAID FOR UNDER ITEM 4.
BE PAID FOR UNDER ITEM "DEFORMED STEEL BARS - GALVANIZED".
REINFORCEMENT FOR THE PROPOSED WINGWALL AND WINGWALL FOOTING SHALL 3.
FOR UNDER ITEM "ABUTMENT AND WALL CONCRETE".
PROPOSED WINGWALL CONCRETE WILL BE CLASS PCC03340 AND SHALL BE PAID 2.
BE PAID FOR UNDER ITEM "FOOTING CONCRETE".
PROPOSED WINGWALL FOOTING CONCRETE WILL BE CLASS PCC03340 AND SHALL 1.
NOTES:
(TYP.)
2"
2" (TYP.)
1'-0" (TYP.)
1" BEVEL (TYP.)
TYPICAL WINGWALL SECTION
NOT TO SCALE
1'-3"
5'-3"
BACKFILL
PERVIOUS STRUCTURE
EL. 36.64 ±
FOOTING
BOTTOM OF
1.5
1'-3" MIN.
M
IN
IM
U
M
1.5
L
IM
IT
S
O F
D A
M P
P R
O O
F
IN
G
FINISHED GRADE
APPROXIMATE
FINISHED GRADE
APPROXIMATE
STONE
CRUSHED
12" NO. 6
INVERT EL. 42.62
6" X 2" KEY
(SEPARATION - CLASS 2)
GEOTEXTILE
M I N
4" PVC WEEP HOLE 8H:1V
1 CF BAGGED STONE
2'-0"
LIMITS OF STRUCTURE EXCAVATION (SEE NOTES)
L
IM
IT
S
O F
S T
R U
C T
U R
E E
X C
A V
A T
IO
N
S
E E
N O
T E
S
WINGWALL REINFORCING
NOT TO SCALE
1'-3"
EL. 36.64 ±
BOTTOM OF FOOTING
#5 @ 12" (E.F.)
#5 @ 18" (E.F.)
ADD'L #5 IN HOOK (TYP.)
2" COVER (TYP.)
3" COVER
(T&B)
#5 @ 15"
#5 @ 18" (T&B)
(T Y
P
S
P L
IC
E
6" X 2" KEY
3" COVER
3" COVER
#5 @ 12" HOOKED BAR (E.F.)
(TO REMAIN)
EXISTING HEADWALL
FOOTING
WINGWALL
PROPOSED
(TYP.)
#5 @ 15" T&B
(TYP.)
#5 @ 18" T&B
3" CL. (TYP.)
(2) ADD'L #6 BOT. MAT
12" SPLICE TO #5
ADD'L #6 TOP MAT
WINGWALL FOOTING REINFORCEMENT PLAN
" = 1'-0"2
SCALE
2'-9" SPLICE
BAR (TYP.)
#5 HOOKED
(SEE DETAIL ON S-07)
#5 DRILL AND BOND ANCHOR
FOR PIPE PENETRATION E.F.
ADDITIONAL #5 REINFORCING
ADDITIONAL REINFORCEMENT AT PIPE
" = 1'-0"2
SCALE
WINGWALL FOOTING
2" CL.
30" DIA. CMP
4" PVC WEEPHOLE
MIN. SPLICE LENGTH
REQUIRED TO PROVIDE
FIELD BEND BARS AS
PENETRATION
BLOCK OUT FOR PIPE
(SEE NOTE 8)
OPTIONAL CONSTRUCTION JOINT
NON-SHRINK GROUT
4'-1" ±
- SERVICE LIMIT STATE = 2,000 PSF
- STRENGTH LIMIT STATE = 3,000 PSF
THE MAXIMUM FACTORED BEARING RESISTANCE:
04.08
| BR_CP_0083_0270_S_01_StructuresCoverSheet |
| BR_CP_0083_0270_S_02_GeneralPlan_ATW1 |
| BR_CP_0083_0270_S_03_ConstructionSequence_ATW1 |
| BR_CP_0083_0270_S_04_CulvertDetails |
| BR_CP_0083_0270_S_05_SlipLiningDetails |
| BR_CP_0083_0270_S_06-08_WallDetails |
| BR_CP_0083_0270_S_06-08_WallDetails |
| BR_CP_0083_0270_S_06-08_WallDetails |
| 2026-07-09T16:42:29-0400 | |
| Bryan L Busch -- CHA Consulting Inc. |
File details come from the government source that posted it. Updated .