Z2DA--(CON) *635 - OKLAHOMA CITY VAMC Replace Lawton Outpatient Clinic Air Cool Chiller (VA-21-00046407)

Closed Pre-Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
36C25921R0064
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Place of performance
Lawton Outpatient Clinic located on Ft Sill OK Fort Sill, Oklahoma 73503, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19 is seeking to replace an existing 100-ton Trane air-cooled chiller at the Lawton Outpatient Clinic in Lawton, Oklahoma. Offerors must propose a replacement chiller unit, including specifications, delivery lead time, and ability to meet the requirements outlined in the solicitation documents. Proposals will be evaluated based on meeting the technical requirements for model CGAM chillers by Trane or approved equivalents. The full solicitation is expected to be posted on or after March 31, 2021, with proposals due by May 4, 2021.

This requirement has been designated as a Service-Disabled Veteran Owned Small Business set-aside, with a NAICS code of 238220. The estimated value is between $250,000 to $500,000 to replace one 100-ton air-cooled chiller unit. The incumbent chiller is a 100-ton unit manufactured by Trane. The selected contractor will be responsible for removal of the existing chiller, installation of the new unit, and all associated chilled water piping, electrical, and controls integration work at the specified location in Lawton, Oklahoma.

Notice text

2 versions

Update #2 · Latest ·

Veteran Affairs Healthcare Systems (VA HCS) Project # 635-21-114, Replace Lawton Outpatient Clinic Air Cool Chiller at Lawton, OK I. GENERAL: THIS IS A PRESOLICITATION NOTICE THE FULL SOLICITATION WILL BE POSTED ON or AFTER 3/31/2021 Construction Replace Chiller NAICS CODE 238220 This solicitation will be a Service-Disabled Veteran Owned Small Business Set-Aside. Magnitude; $250,000.00 - $500,000.00 This will be a Brand Name or Equal solicitation Proposal must include make, model and data characteristics of Chiller proposed. Also the lead time for delivery of the chiller unit being proposed must be included in proposal. Any proposal received without that information will be determined to be nonresponsive and will not be considered. This project is to replace existing 100 tons Trane air cool chiller with new 100 tons air cool chiller located at Lawton Outpatient Clinic, Lawton, Oklahoma. The contractor is fully responsible for verifying and validating all information contained within this statement of work. Contractor must fully evaluate the condition of the existing structures and verify the current condition of the project site. All measurements/quantities provided in this document are approximate and are to be used for reference only. The contractor will be responsible for taking on-site measurements and verifying all quantities and distances. All materials/fasteners/etc. must be new and provided by the contractor unless otherwise specified. The contractor shall abide by all Safety, Security and Infection Control Policies and Procedures of the Oklahoma City VA Medical Center. VA facilities are tobacco free. No smoking is permitted on VA property. The contractor is responsible for their subcontractor s compliance with this policy. All work must conform to, and comply with, the latest edition/version of ALL applicable VA, federal, state, and local laws, rules, regulations, codes, and standards. The contractor shall provide supervision, manpower, and materials turnkey to replace existing Trane air cool chiller with new 100 tons air cool chiller. Contractor shall provide including but not limit to the following: Disconnect power and tagout logout electrical to existing Trane air cool chiller. Drain water from existing Trane air cool chiller and disconnect existing chilled water piping from existing Trane air cool chiller. Lift existing Trane air cool chiller up to trailer and remove from site. Set new 100 tons air cool chiller packet with circulation pump on the existing chiller pad. Contractor shall replace existing butterfly valves at existing chilled water supply and return piping. Necessary retrofit existing chilled water piping to accommodate new air cool chiller chilled water piping connection and connect existing chilled water piping to new air cool chiller chilled water piping connection. Retrofit Chilled water piping at the existing chilled water pump with bypass butterfly valve around the existing chilled water pump. Valve and piping configuration to isolate the existing chilled water pump for future use. On-board pump package in new air cool chiller will be used to pump chilled water through existing chilled water piping loop. Insulate new chilled water piping with fiberglass insulation and aluminum jacket. Install junction box for new air cool chiller at the existing chiller pad and connect power to new air cool chiller. Install heat trace cable on new piping section to prevent freezing. The existing air cool chiller controls by Johnson controls Building HVAC control in the facility, connect Johnson Controls to new air cool chiller. After the installation of new air cool chiller completed, factory start up shall perform and put new air cool chiller in operation. 13. The new replacement 100 tons air cool chiller is based on Trane air cool chiller Model CGAM. The other air cool chiller manufacture can be used if their air cool chiller meets specification section 23 64 00 and Trane air cool chiller Model CGAM specifications or exceeds. 14. The existing air cool chiller concrete pad can be reused, if the dimension of existing concrete pad is sufficiency to support new air cool chiller. There is some repair may require. 15. Should the new air cool chiller dimension is bigger than existing concrete pad, the contractor shall enlarge the existing concrete pad for supporting new air cool chiller. 16. Contractor may provide temporary air cool chiller and electric generator during the replacement of the air cool chiller. The temporary air cool chiller should provide chilled water 120 gpm at 45 deg-F. The temporary air cool chiller and electric generator shall be bid as an option.

Update #1 ·

Veteran Affairs Healthcare Systems (VA HCS)

Project # 635-21-114, Replace Lawton Outpatient Clinic Air Cool Chiller at Lawton, OK

I. GENERAL: THIS IS A PRESOLICITATION NOTICE THE FULL SOLICITATION WILL BE POSTED ON or AFTER 3/31/2021

Construction Replace Chiller

NAICS CODE 238220

This solicitation will be a Service-Disabled Veteran Owned Small Business Set-Aside.

Magnitude; $250,000.00 - $500,000.00

This will be a Brand Name or Equal solicitation

Proposal must include make, model and data characteristics of Chiller proposed. Also the lead time for delivery of the chiller unit being proposed must be included in proposal. Any proposal received without that information will be determined to be nonresponsive and will not be considered.

This project is to replace existing 100 tons Trane air cool chiller with new 100 tons air

cool chiller located at Lawton Outpatient Clinic, Lawton, Oklahoma.

The contractor is fully responsible for verifying and validating all information contained within this statement of work. Contractor must fully evaluate the condition of the existing structures and verify the current condition of the project site.

All measurements/quantities provided in this document are approximate and are to be used for reference only. The contractor will be responsible for taking on-site measurements and verifying all quantities and distances.

All materials/fasteners/etc. must be new and provided by the contractor unless otherwise specified.

The contractor shall abide by all Safety, Security and Infection Control Policies and Procedures of the Oklahoma City VA Medical Center.

VA facilities are tobacco free. No smoking is permitted on VA property. The contractor is responsible for their subcontractor s compliance with this policy.

All work must conform to, and comply with, the latest edition/version of ALL applicable VA, federal, state, and local laws, rules, regulations, codes, and standards.

The contractor shall provide supervision, manpower, and materials turnkey to replace

existing Trane air cool chiller with new 100 tons air cool chiller. Contractor shall provide

including but not limit to the following:

Disconnect power and tagout logout electrical to existing Trane air cool chiller.

Drain water from existing Trane air cool chiller and disconnect existing chilled water piping from existing Trane air cool chiller.

Lift existing Trane air cool chiller up to trailer and remove from site.

Set new 100 tons air cool chiller packet with circulation pump on the existing chiller pad.

Contractor shall replace existing butterfly valves at existing chilled water supply and return piping.

Necessary retrofit existing chilled water piping to accommodate new air cool chiller chilled water piping connection and connect existing chilled water piping to new air cool chiller chilled water piping connection.

Retrofit Chilled water piping at the existing chilled water pump with bypass butterfly valve around the existing chilled water pump. Valve and piping configuration to isolate the existing chilled water pump for future use. On-board pump package in new air cool chiller will be used to pump chilled water through existing chilled water piping loop.

Insulate new chilled water piping with fiberglass insulation and aluminum jacket.

Install junction box for new air cool chiller at the existing chiller pad and connect power to new air cool chiller.

Install heat trace cable on new piping section to prevent freezing.

The existing air cool chiller controls by Johnson controls Building HVAC control in the facility, connect Johnson Controls to new air cool chiller.

After the installation of new air cool chiller completed, factory start up shall perform and

put new air cool chiller in operation.

13. The new replacement 100 tons air cool chiller is based on Trane air cool chiller Model

CGAM. The other air cool chiller manufacture can be used if their air cool chiller meets

specification section 23 64 00 and Trane air cool chiller Model CGAM specifications or

exceeds.

14. The existing air cool chiller concrete pad can be reused, if the dimension of existing

concrete pad is sufficiency to support new air cool chiller. There is some repair may

require.

15. Should the new air cool chiller dimension is bigger than existing concrete pad, the

contractor shall enlarge the existing concrete pad for supporting new air cool chiller.

16. Contractor may provide temporary air cool chiller and electric generator during the

replacement of the air cool chiller. The temporary air cool chiller should provide chilled

water 120 gpm at 45 deg-F. The temporary air cool chiller and electric generator shall

be bid as an option.

Files

File Type Posted
36C25921R0064 0007.docx DOCX document
Amended SOW.pdf PDF
36C25921R0064 0006.pdf PDF
36C25921R0064 0005.pdf PDF
RFI 2 Answers.pdf PDF
260526 Ground and Boning.pdf PDF
260519 Low Voltage Electrical Power Conductors and Cables.pdf PDF
36C25921R0064 0003.pdf PDF
RFI1 Chiller Lawton.pdf PDF
Clinic Chiller Pre-Bid Sign in.pdf PDF
260511 Requirement for Electrical Installation.pdf PDF
A004 WD Comanche Couty OK 4_9_2021.docx DOCX document
36C25921R0064 0004.pdf PDF
WD OK20210049 April 9 2021.pdf PDF
36C25921R0064 0002.pdf PDF
36C25921R0064 0001.pdf PDF
013323 Shopdrawings.pdf PDF
36C25921R0064 full solicitation.docx DOCX document
H12-Large Scale Mechanicl Floor Plans LAWTON.pdf PDF
230800 COMMISSIONING HVAC.pdf PDF
010000 General Requirement.pdf PDF
H10-Floor Plan Piping LAWTON.pdf PDF
013526 Safety.pdf PDF
236400 Packged Chiller.pdf PDF
36C25921R0064_1.docx DOCX document
Show all 25

Notice history

Notice Type Posted
Z2DA--(CON) *635 - OKLAHOMA CITY VAMC Replace Lawton Outpatient Clinic Air Cool Chiller (VA-21-00046407) Award Award Notice
This notice Latest pre-solicitation Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
Z2NZ--Turn Key Chiller Equipment (Purchase and Install) NAICS 238220 Veterans Integrated Service Network 16 No set-aside
Rental of two chillers for one year Asheville, North Carolina 28805, United States · NAICS 238220 Veterans Integrated Service Network 6 Service-Disabled Veteran-Owned Small Business
CON | Z2DA | replace chiller 1 B104 | 580-24-111 | solicitation Houston, Texas 77030, United States · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
C221--402-27-001 Repair Chiller 3 (AE) Veterans Affairs Medical Center Augusta ME 04330, United States · NAICS 541330 Veterans Integrated Service Network 1 Service-Disabled Veteran-Owned Small Business
CON | Z1DA | replace or chillers | 580-23-105 | solicitation Houston, Texas 77030, United States · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors